Air Outlets

Zamzam for Engineer Industries, established in 2002 in Egypt, specializes in manufacturing a wide range of HVAC air distribution products and has gained significant market share in the MENA region and Africa. The company employs 200 skilled workers and is certified in various ISO standards to ensure product quality. The document includes details on the company's organizational structure, legal papers, product catalogs, and technical specifications for their offerings.

Uploaded by

hosam slama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
10 views158 pages

Air Outlets

Zamzam for Engineer Industries, established in 2002 in Egypt, specializes in manufacturing a wide range of HVAC air distribution products and has gained significant market share in the MENA region and Africa. The company employs 200 skilled workers and is certified in various ISO standards to ensure product quality. The document includes details on the company's organizational structure, legal papers, product catalogs, and technical specifications for their offerings.

Uploaded by

hosam slama
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 158

Index

Company profile
Organizational chart
License & legal company papers
I. VAT
II. Commercial paper
III. Tax card
Material list
Compliance Sheet
Technical Catalogs
Certificates
I. Intertek Certificate
II. UL Certificate
III. ISO Certificate
IV. Tests from NATIONAL RESEARCH CENTER
Project list
Previous approval
 Company profile
** Company Profile **
Zamzam for Engineer Industries was established in 2002 in Egypt .we started
with a complete German line of manufacturing round spiral ducts and fittings.
Over the time our range of products has grown to include all air distribution
products such as HVAC ducts (round and rectangular), air outlets, dampers,
silencers, terminal boxes, VAVS and duct heaters .we also produce cable trays
and garbage shuts .

Our 200 skilled engineers and employees at our 8000 m2 premises located in
6th of October city succeeded to gain the market’s confidence in very short
period of time leading to a remarkable increase in our market share as we
became the only manufacture in Egypt producing this wide range of quality
products serving HVAC air distribution systems.

Over the years the support of our loyal clients, help for our dedicated and
hard working employees led us to grow serving other markets as well. we are
proud to manufacture and distribute across the MENA region and Africa. we
always endeavor to continue adapting innovative approach to add value to our
products and transfer the value to our customers.

To ensure the best quality, our products are manufactured using latest
technology; the manufacturing process is closely monitored so that they
conform to the latest technology quality tests and hence our company is ISO:
9001: 2008 , ISO: 14001, and ISO: 18001 certified
 Organizational chart
Zamzam for engineering industries
Chairman quality department
REV : 1/2

Deputy Chairman

General manager

I.T Secretary

maintenance Human Resources Warehouse sales Production Purchases financial quality


Planning
manager Manager manager manager Manager Manager manager manager
and Follow-

Ores Tech. Office


Repair Local Treasury documents
marketing
Maintenance
Half manu. Ores Control
Sales services General
extrernal Q.Assur
Combinations

Final product COST


operation Costs saftey

Internal audit
Q.control
Workers affairs Managing Director
Air outlets Paint Airways Kit workshop

training Attend , leave Insurances Transport Security services


Final Phased Importation
Preparation assempling Sheet metal Accessories foam Square round
 License & legal company papers

IV. VAT
V. Commercial paper
VI. Tax card
• ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••
 Material list
 Compliance Sheet
 Technical Catalogs
SQUARE & RECTANGULAR CEILING DIFFUSERS
Supply diffusers are recommended for heating, ventilating and cooling, and
for irregularly space conditions Requiring directional air diffusion patterns.
Removable snap-in directional cores provide 4,3,2 or 1- way horizontal air
diffusion patterns on ceiling applications. High diffusion induction rates result
in rapid temperature and velocity equalization of the mixed air mass well above
the zone of occupancy. The reliable performance of the multi-directional pattern
°
air diffusers assures confident use of cooling temperature differentials of 25 F
and greater, at predicted low air motion (35 fpm) in the zone of occupancy. Supply
diffuser perform efficiently with air loadings from 6 to 20 air changes per hour
(based on 1 0 ft. ceiling height), and sound level range of NC 25 to 35.

FEATURES:
• Removal Snap-in directional cores for 4,3,2 or 1 - way diffusion pattern
provide accesses to accessories and connecting duct and are interchangeable
in the field in the same size in any margin style.
• Supply Diffusers are equipped with flat overlap margins designed to cover
ceiling opening and minimize smudging.
• Diffusers screw-fasten to connecting duct collar for tight adjustment of margins
to ceiling.
• Diffusers are available with optional countersunk screw holes for fastening
through the face.
• Di ffusers and accessories are manufactured of extruded aluminum.
• Baked white enamel or satin anodized finish for diffusers other colors· are
available as option.

Installation dimension
---LISTED SIZE____..:

!l/\/\/\1\I!
:r
I
i:
I
T
i�i-----i l
I I

------ LISTED SIZE+ 6" ------1

CEILING OPENING = LISTED SIZE+ 3"

All dimension in inches

Engineering Performance Data on pages 4 Thru 10


-2-
ALUMINUM LOUVER
Model ZAL

Introduction

A louver is a ventilation product that allows air to pass through it while


keeping out unwanted elements such as water, dirt, and debris. A number of
fixed blades mounted in a frame can provide this functionality. The basic
considerations for selecting louvers are Free Area, and Resistance to
Airflow (Pressure Loss)..

Free Area

Free area is derived by taking the total open area of a louver (after
subtracting all obstructions - blades and frame) and dividing by the overall
wall opening.

..........................
Models

Models ZAL are available in two designs : ZAL-S for perforations


up to 1000X1000 mm. and ZAL-L in larger sizes up to 2000X2000
mm. as single units.

Construction

· Frames and blades : from high quality extruded aluminum


profiles or galvanized steel both available upon request

· Galvanized steel wire mesh in the back side ( option )


· Trim mitered corners, rivet fasten through the frame into
louver core

Finishes: Electrostatic powder coated in standard RAL colors

Sizes

Model Min. Size inches Max. Size inches


ZAL-S 4X4 40X40
ZAL-L 14X14 80X80

Free area
Shown in table 1&2 for the most common combinations of width W and height H

in square feet . for both models S & L


Construction
ZAL-L
– Frames and blades of extruded aluminum sections or galvanized steel both available
upon request

– Wire mesh screen from galvanized steel, mesh size20 x 20mm

– Flange drilled as standard

ZAL-S
Frames and blades of extruded aluminium sections or galvanized steel both available
upon request

– Wire mesh screen of galvanized steel,mesh size 6 x 6 mm

– Flange drilled as standard


Free area for ZAL- S

Free area for ZAL- L


Performance

Knowing the flow rate and the recommended velocity the free area
can be determined as

A = Q/v , entering the table at the nearest smaller area the W & H
of the louver may be chosen

Or ,

Knowing the louver size WxH , the free area A is known from the
table , the velocity will be calculated as

V = Q/A

For the face velocity A the pressure drop across the louver is
plotted in chart 1
Chart 1
700
Static Pressure Drop (inches w.g.)

600

500

400
x 10-3

300

200

100

0
0 500 1000 1500 2000 2500

Free Area Velocity (ft/min)

Example 1
Given air flow rate of 1500 cfm select a louver size

Dividing flow rate by free area velocity (let say 600 fpm )

Free area = 2.5 ft2 , from the table above , 34”X 22” will be the least louver satisfy the
desired free velocity

Note : other selections are also available

Determine free velocity 1500 /2.51 = 597 fpm

Check for pressure drop across the louver at 597 fpm from chart 1 = 0.06 Wg “

Example 2
Knowing louver size as 24”X28” determine the maximum flow rate

From table 1 free area = 2.28 feet2

For velocity 800 fpm the flow rate = 2.28X 800 = 1824 cfm

Check for pressure drop across the louver at 800 fpm from chart 1 = 0.14 Wg “
DISC VALVE

Construction:
• Disc: Steel sheet construction.
• Mounting rings: spun Aluminum

Description:
• Disc is made of high quality galvanized steel sheet
construction with powder coating to RAL colors.
• Disc is attached to the frame by galvanized threaded
rod.
• Air flow can be adjusted by regulating the disc up
or down.
• These valves can be used for supply, exhaust and
ventilation applications.
• Can be mounted in wall, ceiling or exposed air
ducts with mounting rings
• Recommended for exhaust of greasy and damp
air in damp areas such as toilets, bathrooms and
kitchens
Standard finishes:
Steel sheet powder coated to RAL 9010
Color flexibility of finishing is available as option.

Standard Sizes

4,5,6, and 8 inches neck diameter .

Technical Data
Air capacities , pressure drop , and noise level through
the valves in three different openings are shown in the
following tables for both supply and return.
Supply air

Neck position Air flow rate


Size in of disc CFM 10 20 40 60 80 100 120 140
Inches M 0.0047 0.0094 0.0189 0.0283 0.0378 0.0472 0.0567 0.0661
P 0.51 1.12 3.46 6.6
Max NC <20 <20 30 38 ……. ……. ……. …….
P 0.71 2.04 6.11 11.21
4
MED. NC <20 20 36 44 ……. ……. ……. …….
P 1.43 4.08 12.23 >20
MIN.
NC <20 31 45 >45 ……. ……. ……. …….
P 0.41 1.12 3.06 5.61 9.2
Max NC <20 <20 26 33 42 ……. ……. …….
P 0.82 1.83 5.61 9.4 14.78
5
MED. NC <20 <20 33 40 >45 ……. ……. …….
P 1.22 3.06 8.87 16.3 >20
MIN.
NC <20 26 42 >45 >45 ……. ……. …….
P <0.4 0.61 1.83 4.3 5.7
Max NC <20 <20 20 25 31 ……. ……. …….
P <0.4 1.22 3.78 8.2 11.2 9.2 12.7
6
MED. NC <20 <20 25 35 41 37 40 …….
P 1.2 2.75 8.2 16.3 >20 18.3 20
MIN.
NC <20 30 41 >45 >45 45 >45 …….
P <0.4 <0.4 0.82 1.63 3.1 20 20 7.9
Max NC <20 <20 <20 <20 22 >45 >45 37
P <0.4 0.71 1.83 4.1 5.61 9.1 5.1 18.3
8
MED. NC <20 <20 20 24 30 36 33 45
P <0.4 1.22 4.3 7.6 10.7 18.3 20 20
MIN.
NC <20 <20 26 35 39 45 >45 >45
Return air

Neck position Air flow rate


Size in of disc CFM 10 20 40 60 80 100 150 200
Inches M 0.005 0.0094 0.0189 0.0283 0.0378 0.0472 0.071 0.094
P 0.4 <0.4 1.63 3.8 5.8 9.7
Max NC 20 <20 <20 23 31 37 ……. …….
P 0.4 0.76 2.5 5.6 9.7 14.7
4
MED. NC 20 <20 <20 30 35 45 ……. …….
P 0.61 2.24 7.6 15.2 >20 >20
MIN.
NC 20 <20 35 40 >45 >45 ……. …….
P 0.4 <0.4 0.71 1.42 4.1 4.1 9.7
Max NC 20 <20 <20 <20 25 25 37 …….
P 0.4 <0.4 1.83 4.1 11.2 11.2 20
5
MED. NC 20 <20 <20 21 35 35 >45 …….
P 0.4 2.1 7.1 16.8 >20 >20 20
MIN.
NC 20 <20 23 35 >45 >45 >45 …….
P 0.4 <0.4 0.4 0.81 1.43 2.1 5.2 9.7
Max NC 20 <20 <20 <20 <20 <20 28 37
P 0.4 <0.4 0.81 1.74 3.4 5.3 12.2 20
6
MED. NC 20 <20 <20 <20 <20 25 37 45
P 0.4 0.5 1.47 3.8 7.6 14.7 20 20
MIN.
NC 20 <20 <20 <20 27 35 >45 45
P 0.4 <0.4 <0.4 <0.4 0.76 1.12 2.6 4.38
Max NC 20 <20 <20 <20 <20 <20 27 34
P 0.4 <0.4 0.7 1.4 2.3 3.4 8.4 12.2
8
MED. NC 20 <20 <20 <20 <20 20 35 42
P 0.4 0.5 1.62 3.4 7.1 11.2 20 20
MIN.
NC 20 <20 <20 <20 <20 34 >45 45

Where :
P the pressure drop in mm of water
NC based on room attenuation of 10dB
Floor Grille

Description
For supply or extract air, having single set of fixed blades.
Designed to replace 600 x 600 floor tiles and meet Heavy Duty
and Extra Heavy Duty requirements.
Construction
From extruded aluminum sections, frame 3.0mm thick, blades
are 6mm thick tapering to 2.5mm thick. The frame is of fully
welded.
the Extra Heavy Duty rating.
Size and Weight
600 x 600 tile module size as standard though smaller and
larger units can be produced on request.

Technical data
Based on the standers module of 600X600 mm nominal size the
technical performance of both supply and extract grilles is
tabulated below where
• Q is the flow rate through the grille in liter per seconds
• Vf face velocity in meter per second
• Lt throw distance in meters
• PS pressure drop in mm of water
• NC noise level in dB

Technical Data (supply)


Vf Lt (without damper) (with damper)
q(l/s)
(M/s) (metres) ps(pa) NC ps(pa) NC
100 0.29 1.6 1 - 1 -
150 0.44 1.9 2 - 3 -
200 0.58 2.4 3 - 4 15
250 0.73 2.6 5 14 7 17
300 0.88 2.9 6 16 9 20
350 1.02 3.2 9 19 13 24
400 1.17 3.7 11 21 16 26
450 1.32 3.9 13 24 16 29
500 1.46 4.3 15 25 22 31
550 1.61 4.5 18 27 26 33
600 1.75 - 20 28 30 36

Technical Data (Extract)


Vf without damper) (with damper))
q(l/s)
(M/s) ps(pa) NC ps(pa) NC
100 0.29 2 - 3 -
200 0.58 4 18 7 22
300 0.88 8 21 11 25
400 1.17 13 24 19 29
500 1.46 18 26 23 31
600 1.75 23 28 27 33
700 2.04 26 34 39 39
800 2.33 32 37 46 43
Gravity Shutter
ZGS

General:

Gravity shutters are used in ventilation systems to allow airflow in one direction and prevent
it in the opposite direction. So that a constant level of air pressure is maintained inside the
concerned area.

Construction:

- Extruded aluminum section frame


- Blades form formed aluminum sheet
- Front flange drilled

Features:

Corrosion-resistant extruded aluminum construction highlights the model’s features which


include a reinforced mitered corner frame that resists racking, and aerodynamic blades that
overlap the jambs for maximum weather protection.

Dampers can be used in applications for:

• Gravity hood intake and exhaust

• Stairwell pressurization

• Room pressurization

• Ductwork outlets

ENGINEERING PERFORMANCE DATA:-


Penthouse Louver (ZPL)

ZPL Penthouses are typically four louvers joined together with a roof, are
mounted on a curb, mitered corners, removable hoods.

Standard Construction

 Frame & Blades


o Are made from 1.5mm thickness extruded aluminum alloy.
 Cover
o The top of the unit is covered with hinged access door for easy
access.
 Box
o Made of steel sheet metal of thickness 1.25 mm.

 Connection
o Louvers are connected with the box by self-drill screws from the
front
 Finish
o Electrostatic polyester powder coated.
 Painting Color
o Upon request.

 Bird Screen
o is an option to prevent the entry of birds.

 Pre-filter
o 1” aluminum washable filters are available upon request, which
could be removed for cleaning, replaced from the top of unit
Perforated Ceiling Diffuser
Model ZPD

Construction:

· Frame: High quality extruded aluminum profile with 30 mm flange width


Perforated panel: 0.8 mm thick galvanized perforated steel sheet as
standard , 1.5 mm thick aluminum and 0.8 St. steel are also available

Description:

· Frame is fabricated from high quality extruded aluminum profiles with the
advantages of corrosion resistance and rigidity.
· Galvanized steel box of 0.8 mm thickness , internal lining and powder coating
in black matt are options.
· Foam gasket is sealed on the back of the frame as option to avoid air
leakage.

Standard finishes:

· Powder coated color finish RAL 9010 for galvanized steel and aluminum faces
· Flexibility of finishing other available color codes as an option.

Standard sizes:

• Available in sizes 300,450 and 600 face size


• Size 600 adapted for installation in modular 600x600 mm
suspended ceiling
Size W W1 H1 H ØD

100-300 300 245 280 50 99

125-300 300 245 280 50 124

160-450 450 395 370 60 159

200-450 450 395 370 60 199

200-600 595 540 450 80 199

250-600 595 540 450 80 249

315-600 595 540 450 80 314

Performance and selection

the combinations of the face sizes and the inlet spigot diameter
cover wide rage of air rats and noise levels to satisfy different
applications requirements

Technical Data
The pressure, drop noise level and minimum distance between two adjacent diffusers are
shown in the following table

air flow rate


1/s 20 30 40 50 60 80 100 120 140 160 200 250 300 400
model
CFM 42 63 84 106 127 169 211 253 295 338 422 528 633 844
NC dB 20 26 37 46
ZPD 100-300 Δ ptot 7 15 27 43
Lmin
NC dB 21 22 28 35 46
ZPD125-300 Δ ptot 6 11 18 25 45
Lmin 1.8
NC dB 20 22 32 39
ZPD160-450 Δ ptot 6 8 15 23
Lmin 1.8 1.8 3.2
NC dB 20 26 31 36 43
ZPD200-450 Δ ptot 6 10 14 19 25
Lmin 1.8 2.2 3.6 4.6 5.2
NC dB 20 24 28 34 39
ZPD200-600 Δ ptot 6 10 14 19 25
Lmin 2.0 2.4 3.6 4.6 5.2
NC dB 18 20 25 28 36
ZPD250-600 Δ ptot 5 7 9 12 19
Lmin 2.0 2.0 3.2 4.0 5.2
LpA 20 23 30 36 42
ZPD315-600 Δ ptot 6 9 14 20 27
Lmin 3.0 3.2 3.6 4.0

Where
ZPD xxx-yyy
ZPD zamzam ceiling diffuser with with perforated face
Neck diameter in mm
YYY diffuser face size in mm

NC noise level in dB Δ ptot pressure drop in pascals


L min. min. distance between center lines of two diffusers
Stainless Steel EXHAUST GRILL Model St.EG (Without damper)
St.ER (With damper)
Item Description
Frame Material Stainless Steel profile- flanged type (30mm)
Frame Thickness 1.25 mm
Blade Material Sheet metal Stainless Steel profile 45°- 1.5 mm
Blade Spacing 19mm
Aluminum Opposed Blade Damper operated by plastic gears
Accessories
(optional)

* Engineering Performance data of aluminium model can be applied for this model
STAINLESS STEEL GRILLES
Linear Bar Grilles

Introduction:

The linear stainless steel bar grilles are designed to provide a clean,
strong, horizontal look while offering optimum performance. The
availability of a variety of frames allow the grilles to blend,
compliment, or contrast with the ceiling, sidewall, or sill installations.
These grilles can be used on supply or return portions of heating,
cooling or ventilation systems. Linear stainless steel bar grille is an
excellent choice for installation in soffit/sill applications where
airflow is required to wash over a window in a high humidity location.

MODELS
ACCESSORIES
• Aluminum l OBD fixed to unit, adjustable Li-st-15 - Supply or Return Linear Bar Grille with 0° or 15° Blade
STAINLESS STEEL GRILLES

from face of grille Deflection, 15mm Bar Spacing, and 1.5mm bar
• Blank-off strip. thickness
• Linear straightening grid.
li-st-0- Supply or Return Linear Bar Grille with 0° Blade Deflec on,
15mm Bar Spacing, and 1.5mm Bar Thickness
FINISH

• Standard finish is not painted. FEATURES

• Section lengths from 4” - 72”; section widths from 4” - 24”.


• 304 Stainless steel construction (316 optional

(35m) (35 cm)
MAXIMU MAXIMUM


 Certificates

V. Intertek Certificate
VI. UL Certificate
VII. ISO Certificate
VIII. Tests from NATIONAL RESEARCH CENTER
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Double Deflection Grille

A Double Deflection Grille 40 X 6 inch was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The double deflection grille was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004i dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Return Linear Grille

A Return Linear Grille 100 X 15 cm was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The return linear grille was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004e dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Return Slot Ceiling Diffuser

A Return Slot Ceiling Diffuser 3 – ¾ inch wide slots was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The return slot diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004g dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Return Square Ceiling Diffuser

A Return Square Ceiling Diffuser 12 X 12 inch was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The ceiling diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004a dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
REPORT
3933 US ROUTE 11 CORTLAND, NEW YORK 13045

Order No. 104566351 Date: January 20, 2021

REPORT NO. 104566351CRT-001a

AIR EROSION TEST ON A


SOUND ATTENUATOR

RENDERED TO

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

INTRODUCTION

This report gives the results of an Air Erosion Test, which was performed on sound
attenuator with an elbow configuration. The test specimen was selected and supplied by
the client and was received at the laboratories on January 4 and 11, 2021. The sample
appeared to be in new unused condition upon arrival.

AUTHORIZATION

Signed Intertek SWA

GENERAL

The test was conducted in accordance with UL 181 Issued: 2013/07/25 Ed: 11 “UL
Standard for Safety Factory-Made Air Ducts and Connectors” Section 18, Air Erosion
Testing.

DESCRIPTION OF TEST SPECIMEN

The test specimen consisted of one 78 inch length of duct silencer upstream, a 90°
elbow and a 78 inch length of duct silencer downstream. The interior of the 12 inch by
12 inch lined metal duct system measured 8 inches square. The interior of the lined
sections consisted of metal screening over a woven cloth face covering the nominal 2
inch thick insulated walls.

This report is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's responsibility and
liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in accordance with the
agreement, for any loss, expense or damage occasioned by the use of this report. Only the Client is authorized to copy or distribute this report and then only in its
entirety. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service must first be approved in writing
by Intertek. The observations and test results in this report are relevant only to the sample tested. This report by itself does not imply that the material, product, or
service is or has ever been under an Intertek certification program. Measurement uncertainty budgets have been determined for applicable test methods and are
available upon request.
PICTURES OF SAMPLE

Report No. 104566351CRT-001a Page 2 of 3 January 20, 2021


TEST METHOD

The air was supplied by a 12,000 cfm Buffalo Forge Blower which was driven by a 40
HP variable speed drive for the purpose of varying the velocity. The fan outlet was
covered with a double layer of cheesecloth (14 to 15 square yards per pound and
known to the trade as “count of 32 by 28”).

For the collecting screen a double layer of cheesecloth (the same type as mentioned
above) was stretched taut on a frame sized to provide an area greater than five times
the inside cross-sectional area of the test specimen. Prior to the installation of the
collection screen, air was passed through the test section at a velocity of 10,500 fpm for
a one-hour period. The collecting screen was then installed one foot from the outlet of
the test section.

After the collecting screen was set in place and the velocity set at 11,250 fpm, the test
continued for four hours. The collecting screen was examined for macroscopic particles
at the end of each hour by taping the screen with the adhesive side of transparent tape
to remove any eroded particles. At the end of the four hour period, the test was
stopped, and the final examination was made.

TEST REQUIREMENT

At the end of the test period, there should be no evidence of continued erosion, and the
interior surfaces of the sample are not to show evidence of cracking, flaking, peeling or
delamination.

TEST RESULTS - Test Velocity 11,250 fpm (2.5 times the 4,500 fpm rating). At the end
of each test period, there was no evidence of continued erosion, and the interior
surfaces of the sample did not show any evidence of cracking, flaking, peeling or
delamination.

REMARKS

Date of Test: January 12, 2021

Dry Bulb: 69F


Relative Humidity: 33

Report Approved by: Report Reviewed By:

Brian Cyr James R. Kline


Engineer Engineer/Quality Supervisor
Acoustical Testing Acoustical Testing

Report No. 104566351CRT-001a Page 3 of 3 January 20, 2021


Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
50 X 50 cm Volume Control Damper

A 50 X 50 cm Volume Control Damper was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

AMCA Standard 500-D-2012 entitled, “Laboratory Methods of Testing Dampers for Rating”

SCOPE OF TESTING

The volume control damper was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-003c dated December 20, 2019”

A) Leakage
B) Air Performance-Pressure Drop

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
50 X 100 cm Acoustical Louver

A 50 X 100 cm Acoustical Louver was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARDS

ASTM E90-09 (2016), "Standard Test Method for Laboratory Measurement


of Airborne Sound Transmission Loss of Building Partitions"

SCOPE OF TESTING

The acoustical louver was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-002 dated December 19, 2019”

A) Sound Transmission Class (STC)


B) Outdoor-Indoor Transmission (OITC)

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
14 X 14 inch Volume Control Damper

A 14 X 14 inch Volume Control Damper was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

AMCA Standard 500-D-2012 entitled, “Laboratory Methods of Testing Dampers for Rating”

SCOPE OF TESTING

The volume control damper was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-003b dated December 20, 2019”

A) Leakage
B) Air Performance-Pressure Drop

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
VAV Type Bypass Terminal

A VAV Type Bypass Terminal with 12 inch inlet was tested


in accordance with the standards listed below and was found
to perform in a manner appropriate to the dictates of the standards.

STANDARDS

ASHRAE 130-2016, “Methods of Testing Air Terminal Units”


AHRI 880-2017, “Performance Rating of Air Terminals”

SCOPE OF TESTING

The bypass terminal was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-001c November 27, 2019”

A) Primary Airflow Rate, cfm / Minimum Operating Pressure


B) Radiated Sound Power Level, dB
C) Discharge Sound Power Level, dB

Date: December 3, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
50 X 50 cm Sand Trap Louver

A 50 X 50 cm Sand Trap Louver was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

AMCA Standard 500-L-2015 entitled, “Laboratory Methods of Testing Louvers for Rating”

SCOPE OF TESTING

The sand trap louver was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-003a dated December 20, 2019”

A) Air Performance – Pressure Drop test

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Model RSA4 Silencer

A Model RSA4: W = 24”, H = 24”, L = 36” Silencer was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASTM Standard E477-13, entitled “Standard Test Method for Laboratory


Measurements of Acoustical and Airflow Performance of Duct Liner Materials
and Prefabricated Silencers”

SCOPE OF TESTING

The silencer was tested for the following performance characteristics:


"Reference Intertek Report Number 104129960CRT-001a November 27, 2019”

A) Insertion Loss With and Without Airflow


B) Airflow Generated Sound
C) Air Velocity Versus Static Pressure

Date: December 3, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Single Deflection Grille

A Single Deflection Grille 40 X 6 inch was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The single deflection grille was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004h dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
VAV Type Single Duct Shut Off Terminal

A VAV Type Single Duct Shut Off Terminal with 12 inch inlet was tested
in accordance with the standards listed below and was found
to perform in a manner appropriate to the dictates of the standards.

STANDARDS

ASHRAE 130-2016, “Methods of Testing Air Terminal Units”


AHRI 880-2017, “Performance Rating of Air Terminals”

SCOPE OF TESTING

The single duct terminal was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-001b November 27, 2019”

A) Primary Airflow Rate, cfm / Minimum Operating Pressure


B) Radiated Sound Power Level, dB
C) Discharge Sound Power Level, dB

Date: December 3, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Supply Jet Diffuser

A Supply Jet Diffuser 14 inch diameter was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The jet diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004f dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Supply Round Ceiling Diffuser

A Supply Round Ceiling Diffuser 14 inch diameter was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The ceiling diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004c dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Supply Slot Ceiling Diffuser

A Supply Slot Ceiling Diffuser 3 – ¾ inch wide slots was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The slot ceiling diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004d dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
Supply Square Ceiling Diffuser

A Supply Square Ceiling Diffuser 12 X 12 inch was tested


in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE 70-2006 Standard


“Method of Testing for Rating the Performance of Air Outlets and Inlets”

SCOPE OF TESTING

The ceiling diffuser was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-004b dated December 20, 2019”

A) Sound Power Level ((NC)


B) Air Volume versus Static Pressure
C) Area Factor
D) Throw Pattern

Date: December 27, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
HEPA Filter Box

A Size: 55.5 X 55.5 CM, L= 42 CM, D=Ø8” HEPA filter box was tested
in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE Standard 193 “Method of Test for Determining the Airtightness of HVAC Equipment”

SCOPE OF TESTING

The HEPA Filter Box was tested for the following performance characteristic:
"Reference Intertek Report Number 104350774CRT-001 dated June 26, 2020”

A) Air Leakage

Date: July 1, 2020

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
VAV Type Single Duct Shut Off Terminal

A VAV Type Single Duct Shut Off Terminal with 12 inch inlet was tested
in accordance with the standards listed below and was found
to perform in a manner appropriate to the dictates of the standards.

STANDARDS

ASHRAE 130-2016, “Methods of Testing Air Terminal Units”


AHRI 880-2017, “Performance Rating of Air Terminals”

SCOPE OF TESTING

The single duct terminal was tested for the following performance characteristics:
"Reference Intertek Report Number 104129960CRT-001b November 27, 2019”

A) Primary Airflow Rate, cfm / Minimum Operating Pressure


B) Radiated Sound Power Level, dB
C) Discharge Sound Power Level, dB

Date: December 3, 2019

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
Performance Test Certificate
Issued To

ZAMZAM ENGINEERING INDUSTRIES


6TH OCTOBER CITY
INDUSTRIAL ZONE 3
BLOCK 232, EGYPT

Intertek has tested a representative sample of


Zamzam Engineering Industries
HEPA Filter Box

A Size: 55.5 X 55.5 CM, L= 42 CM, D=Ø8” HEPA filter box was tested
in accordance with the standard listed below and was found
to perform in a manner appropriate to the dictates of the standard.

STANDARD

ASHRAE Standard 193 “Method of Test for Determining the Airtightness of HVAC Equipment”

SCOPE OF TESTING

The HEPA Filter Box was tested for the following performance characteristic:
"Reference Intertek Report Number 104350774CRT-001 dated June 26, 2020”

A) Air Leakage

Date: July 1, 2020

James R. Kline
Intertek
Engineer / Quality Supervisor

This Verification is for the exclusive use of Intertek's Client and is provided pursuant to the agreement between Intertek and its Client. Intertek's
responsibility and liability are limited to the terms and conditions of the agreement. Intertek assumes no liability to any party, other than to the Client in
accordance with the agreement, for any loss, expense or damage occasioned by the use of this Verification. Only the Client is authorized to copy or
distribute this Verification. Any use of the Intertek name or one of its marks for the sale or advertisement of the tested material, product or service
must first be approved in writing by Intertek. The observations and test results referenced from this Verification are relevant only to the sample tested.
This Verification by itself does not imply that the material, product, or service is or has ever been under an Intertek certification program.
UNDERWRITERS LABORATORIES
INSPECTION REPORT
R271371200921133559

Date 09/21/2020 File Number R27137


Responsible Office Bangalore Volume 1
Inspection Center 398 CCN EMME
Product Type Fire and Smoke Damper UL Rep Name Naji Geha
Deliverable Type Listed UL Representative ID 00424
Party Site Number 603121 Subscriber Number 100409-306
Manufacturer Name ZAMZAM ENGINEERING INDUSTRIES Factory Representative Mr. Atef Rashad
and Address Industrial Zone 3 Factory Rep Phone 20-122-5440658
St 36 Blk 232 Factory Rep Email [email protected]
6Th Of October City

Were non-denominational, in-plant use, in-house printed, or two-level service charge labels used since the
last inspection?
The customer will be invoiced for the number entered in this field.
No Yes

Nature of Visit Regular Inspection Sample Status eTag Sample Selected


Listing/Classification/Recognized Yes Listing/Classification/Recognized No
(Unlisted) Component Marks (Unlisted) Component Marks
Used Since Last Visit Removed
Variation Notice Issued No
Inspection Conducted Yes No
Remotely
Comments After Submission

PRODUCT DOCUMENTS / PRODUCTION READY VISIT

Section/ Multiple
Model Product Class RNN Listed
CFD Fire Damper 1 No

SAMPLE DOCUMENTS
If samples are required to be sent to ULI Laboratory, indicate below. If required samples are not sent, explain in the Comments area.
Type/Style/
Cat/Model Name Sample Tag Number Shipped to Office
eTag Sample

Additional Comments:

In addition to the requirements specified in the applicable UL Services agreement and Follow-Up Service Procedure, UL further defines
responsibilities, duties and requirements for both manufacturers and UL representatives in the document titled "UL Mark Surveillance
Requirements" that can be located at www.ul.com/fus, and in accordance with the applicable terms and conditions of the document at
www.ul.com/responsibilities. Manufacturers without Internet access may obtain the current versions of these documents from their local UL
customer service representative or UL field representative.
iRTIFICATE OF COM r-Arycr
certificateNumber 20130123-R27137
ReportReference R27137-20130123
ReportReference R27137 2013!123-
lssueDate 2013-JANUARY-23
.
to:
lssued ENGINEERING
ZAN'4ZAIV
lOuO-r*rgq . , r, :,
INDUSTRIAL ZONE3
ST 36 BLK232
'r
6THOF OCTOBER CITY cler'..t
.-tl.--
that ?IYTT:.I:I
rhisi5tocertify FlR. toR ,,..
samples
sentative of APPLICATIONS
11.*u*os*1fti.
FiredamPer'ModelCFD20 , curtaintype,for vertical
andfor usein staticsystemsfor 1.5hr rating
installation

Havebeeninvestigated bYUL in accordance withthe


indicatedon tl'
Standard(s) is Certificate.

aty: tJL
i) for satutv: 555, Fire
IJL555, FireDamF
Dampers
on: iions Directoryat
:::.:i:"'^:i1l: dditionalirformation

rdnglhe UL Classificati idered as boing cov€ted bY


Follow-UpService.

qlkf e9i islEtED'6 (asshown); a controt


".9u!9.".1u1i1 r the extenioi UL s evaiuationof
den"v) as ndk t€d ln the appropriateIJL

::::"::",:ducl
t, '....
,, i:.
:'. '.
...1 , :l
.,.,-., ,,'. ,

1.";-..1.*" . I

':,, t
'. :,1
JGiX.Guidelnfo - FusibleLinks PageI of2

JGIX.GuideInfo
Fusible Links
Mew Listings PaoeBottom

Fusible Links

GuideInformationfor BuildingMaterials

Guide Information for Fire ResistanceRatings

Guidelnformationfor Heatino.coolino.ventilatingand cookino Equioment

USE AND INSTALLATION

This categorycoversfusiblelinks intendedfor use in connectionwith automatic


closingdevicesfor doorsand windows,and other automaticdevices
requiringfusible links' The responsecharacteristicsof these links may oe
eitner standird Responseoi euick Response.Links are stanctardResponse
unlessotherwisespecifiedin the individualListinas.

Thesedevicesare intendedfor installationunder load conditionswithinthe ranges


specifiedin the individualListinos.

TEMPERATURERATINGS

Linksare markedwith the temperatureratings.The cimmon temperatureratings


of fusiblelinks are as follows:

Max
Temp Ambient Temp
Qlass Temp, oF Rating, oF
LOW on
12 5 - 1 3 0
Ordinary 100 1 3 5 - 17 0
Intermediate 150 t75-225
High lzJ 250-300
Extra High 300 5ZJ-5 /5

Very Extra High


400-475
Ultra High 475

ADDTTIONAL TNFORMATION

For additionalinformation,see BuildingMaterials(AABM),Fire Resistance


Ratings(BXRH)and Heating,cooling,ventilatingand cooking Equipment
(AAHC).

REQUIREMENTS

The basicstandard used to investigateproducts in this category is uL 33, " Heat


ResponsiveLinks for Fire protectionservice.,,

UL MARK

I uL symbol on the product and the ListingMark of underwriters Laboratories


'Listing Mark on the product is the only method provided Inc. on the smallestunit containerin which the product is packagedor
* by uL to identify productsmanufacturedunder its Listingand Follow-upservice. The
rsting Mark for these products includesthe uL symbol (as i,lustratedin the introduction
of this Directory)together with the word ',LisrED,,,a control

htrp://database.ul'comlcgt-binlxYvltemplate/LISEXTIlFRAME/showpage.html?&name:JGlX.Guidelnfo...
g/gl100s
- FusibleLinks
JGFX.R6789 Page I of I

JGIX.R5789
FusibleLinks
PaoeBottom

Fusible Links

See Generalinformation for FusibleLilks

DURO DYNE CORP R6789


81 SPENCE
ST
BAYSHORE,NY 11706USA

IssueA, in the 135 , 160 , and 212 F temperatureratings.For loadsfrom 1 to 30 lbs incl. Bearinglength2 in.

IssueB, in the 135 , 160 , and 212 F temperatureratings.For loadsfrom 1 to 10 lbs incl. Bearinglength 1-3116in.

For use in connectionwith automatic closingdevicesfor doors, windows,and other automatic devicesrequiringfusible links where loads do not exceed
aboveratings,

Last Updatedon 1992-09-25

\..
Questions? Noticeof Disclairner PageTop

CopyrightG) 2008 UnderwritersLaboratoriesInc.@

The appearanceof a company'sname or product in this databasedoes not In itself assurethat productsso identifiedhave been manufacturedunder
ul's Follow-UpService.Only those productsbearingthe UL Mark should be consideredto be Listedand covered under UL's Follow-UpService.Always
look for the Mark on the oroduct. r

UL permits the reproductionof the material containedin the Online CertificationDirectorysubject to the following conditions: 1. The Guide
Information,Designsand/or Listings(files)must be presentedin their entiretyand in a non-misleading manner,withoutany manipulationof the data
(or drawings). 2. The statement "Reprintedfrom the OnlinecertificationsDirectorywith permissionfrom Underwriterstaboratoriei Inc." must appear
adjacentto the extracted materlal. In addition,the reprinted material must includea copyright notice in the followingformat: "Copyright€) 2008
UnderwritersLaboratoriesInc.@"

An independent 0rganizatl0n working lor a safer world with integrity, precision and knowledge

http://database.ul.com/cgi-bin/XYvltemplatelllSEXT/lFRAME/showpage.hfinl?name:JGlX.R6789&ccn...glglZAAg
t NATIONAL RESEARCH CENTRE
TAHRIR St. DOKKl, CAIRO, EGYPT
Central Unit For Analysis And
Scientifical Services (CUASS)
~".dl ~
~.>11
~J~

~1.:aL.e~IJ
• jj~l.ill . ~~I
~ta:al ;~J
~1.JllJ~1 J-..
Material Test Lab.

I",I.), ••!. '-tI


_, 1..._~.'_'~~.' ",>:.)-_..IM~'-:••
r-!

"-S~
MOl 3827 09 2020 joI,.ji:U1 J
I

4~I~u' .lit' ~,~J--A.J


. ... :.
I
~I -Ji J.sy!JI ~!

r • r •/0., /'i I
~1~..J\.:j

4..i~.lA c~ ~fi' ~ ~ o)yJl ~~ JI..,U:..I


"I~J ylb I
oJ.LAII..I~I
~. ~I

'r""r •xr •
.J~I I~ ~ ~ J~I 4.i...:.lyJl
\.i,tb
:
La ,; ;. ,,,1-1\ ~~'.J4l'
..>-:1fil w6.i....:. ~ ~w
_. ~ _. ..,..,~.lA d J t...w..
. ':II ~ '\:ij ~ I ~
'LliJI

. ( w6.i....:. £ J:lfil w6.i....:. ol~) ~.;-JI

<:: 1··,,1\ ~ ~,,~ Y.#/ ~WI J:.;ill


I

cJ.!cL.u..1
~)I ¥- oJL-.,.., /Y~ u.lT ~b-J j:J~ ~us
~.J~~/Y.#
ol.., •.•.•~f'~I/ Y.#
c.5.;---S.9 "I.>----Ajll L..J::.\j / ~L......~.ili. ~I J LA~I
• ~L'
-J.. 'WI
• u.JA-I
&1'y'1 ~ .l.4.:o.1
/ ~L......~.ili.
~L.....;JI·~ .
)1.lJc ..,~ /'~r.r--

~~j~/ol.l ul~1
~I ~ ~I ~ C~I J-!l/ol.l

4..;.f..,ol1~1.:.i1o~1~

~~~loil,...oJI~~J4lI~~I~I~~H
~~j~1
~b.:ill
J~.tJIll:i.w1l1
d~~ dJloilJIL40 ~J (,
I

'I .""r
( ~~
U;.-; J~.l-~

~I
,
.~~
...•»oLII~~
J~IJ:.w1

:1 \
rJ :11 ~
d~~lt doi~1 H.~~ ~I dJloill1
~:~~(O

\ );;1A.
I
,I.... .
t<I"
lJll~~
r • r •/o.,/V
"""4' •••••• ;-' •• 'll .•~"I,.J • .'~ '"

I
,"~~:~:~;;;.~" JI~~I ~J\.:j

%'\. - c , 0:!-!L... ~".b.J 4.Jol..,/ n .l.ic WAi .l9 d).,u=..':/IJS


I
~IJ4lio~1-J ~I u-J~
o~J ;i",..jlol
~ U"4i11o~'l4....YUI d.J:!1..a...J1
~ "Ifi'j t'"

-'-LA
«««AVA.« ..jJJJ. V,,·. L:.·I~
~liJ ,nt ~
E-mail: [email protected]
t NATIONAL RESEARCH CENTRE
TAHRIR St. DOKKI, CAIRO, EGYPT
Central Unit For Analysis And
Scientifical Services (CUASS)
~".dl ~ ~J~

a.us.;-11~1.::.tL...».lIJ
• jj~1.iJ1. uUi~1
J:IJ~I
.31.Jl1
J~I
;~ J
J..-
Material Test Lab.

'"
~ ~ o)yJI ~b .J~I yl..»J u~ r . r , /~/r 6!.JG.: ~)..,JI~1...b:.. ~J o)~,/~

. ~'( • x r • ~y\l~ <:~ ~..»


: ~tJI ~I uJy:. ~ wI).:u.~,:~1\l.J..o yl+U'il ~ .illJ

w~1 ~~i <Y'Y! ~ ~ ',' ., .u§~<Y'4i-o ~~J (,


Muffle Furnace type VECSTAR jI.;b ~~~ u..;3 ~~J ('(
• o.J;lt......
4....~1 oJP.'i1~ u~ Wc. (r
~Ull\ o~ 64 ~ ~ 6A OJ)..,J\ ~\ ~ U4:j ~\ ~\.)~~\ o~ ~Lli ~ lA.:!.J

J\~\ .)~\ ~ ~\ J\~\.J ~\.J ~\~\ ~ ~\ OJ)..,l\ ~\ .liii ~


~.Hcrjil\ ]SA

4L.,.
TTTAVA.T ~. \A\ •. ''':''t~
~lSJ un ~
E-mail: [email protected]
t NATIONAL RESEARCH CENTRE
TAHRIR St. DOKKI, CAIRO, EGYPT
Central Unit For Analysis And
Scientifical Services (CUASS)
~.,.dl JI=IJ'

4t)S..,l1 ~I
ii.:!J~
~L..~IJ
. ;i.•••liiJl . ~.:all
~b.:iJ1 Oo.b-J
~1,.t.1
J~I J..-
Material Test Lab.

o )\ aJ\ t4b )~i ~~


~'\'. X'\'. 4J~..l.4 ~l.....o~..?.)c

~4....J+l\~L.&.I i,,,,ll,. H 3 L.s d (}A OJ)\ tl\;

~UllI (.IAjll ;;)~I 4.).1


(~.I) (CO)
t:" 01A.ll1~ JI.Jh1 W~ ,.'\' t ••
yl...a..w ~ lli~1 ~ \.....dl
t:" ,.,
~~'il ~ fo WJ~ r-~

~~I
.). ~I
.Ia..l....)~ ;; *

.•. ~
YYYAVA·Y ~. ""'., I~t~
~LSJ un ~
E-mail: [email protected]
t NATIONAL RESEARCH CENTRE
TAHRIR St. DOKKI, CAIRO, EGYPT
Central Unit For Analysis And
Scientifical Services (CUASS)
~J.cJl ~
~jll ~I
~J~

~t..~lj
• jj~1.iJ1 . ~.:all
J:/J~I

~1,t1.J~1
~j

J..-
Material Test Lab.

. ~~ cJc J'W'lI.J w~ r.r~1 jSyJl

;10 ~ ml909 Mot=&;io Jll hil:i..i ;10 ~ lo..! ):!,.i:iJllla):!~9 •W cO±! JI)~1!0 $

Al,w
YYYAVA.Y ...)-lM. ''''' •. I~t~
~lSJ ,tyt ~
E-mail: [email protected]
 Project list
‫اﻟﻤـﻮﺿـﻮع ‪ :‬ﺑﻴــﺎن ﺳـﺎﺑـﻘـﺔ اﻷﻋﻤـﺎل ﻟﺸﺮﻛﺔ زﻣﺰم ﻟﻠﺼﻨﺎﻋﺎت اﻟﻬﻨﺪﺳﻴﺔ‬

‫ﲢﻴﺔ ﻃﻴﺒﺔ ‪ ...‬و ﺑﻌﺪ ‪،،،‬‬


‫ﺑﺎﻹﺷﺎرة إﱃ اﳌﻮﺿﻮع ﻋﺎﻟﻴﻪ ‪ ،‬ﻳﺸﺮﻓﻨﺎ أن ﻧﻘﺪم ﻟﻜﻢ ﻓﻴﻤﺎ ﻳﻠﻲ ﺳﺎﺑﻘﺔ أﻋﻤﺎﻟﻨﺎ ﻋﻦ ﺗﺼﻨﻴﻊ و ﺗﻮرﻳﺪ ﳐﺎرج اﳍﻮاء و دﻧﺎﺑﺮ‬
‫اﻟﺘﺤﻜﻢ و ﻛﻮاﰎ اﻟﺼﻮت و ﺧﻼﻓﺔ ﺑﺄﻧﻮاﻋﻬﺎ و ﻛﺬﻟﻚ ﳎﺎري اﳍﻮاء اﳊﻠﺰوﻧﻴﺔ و اﳌﺴﺘﻄﻴﻠﺔ و اﳌﺮﻧﺔ ‪.‬‬
‫أوﻻ‪:‬ﻣﺴﺘﺸﻔﻴﺎت ﺧﺎﺻﺔ و ﻋﺎﻣﺔ‬

‫اﺳﻢ اﻻﺳﺘﺸﺎرى‬ ‫اﳌﺸﺮوع‬


‫م ‪ ٠‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫ﻣﺴﺘﺸﻔﻲ دﻣﯿﺎط‬
‫د ‪ .‬م ﻣﺤﺴﻦ رﺿﻮان‬ ‫ﻣﺴﺘﺸﻒ اﻟﻘﻠﺐ و اﻟﺼﺪر ﺑﺴﻮھﺎج‬
‫د ‪ .‬م ﻣﺤﺴﻦ رﺿﻮان‬ ‫ﻣﺴﺘﺸﻒ اﻟﻘﻠﺐ و اﻟﺼﺪر ﺑﻘﻨﺎ‬
‫د ‪ .‬م ﻣﺤﺴﻦ رﺿﻮان‬ ‫ﻣﺴﺘﺸﻒ اﻟﻘﻠﺐ و اﻟﺼﺪر ﺑﺄﺳﯿﻮط‬
‫د ‪ .‬ﺛﺮوت أﺑﻮ ﻋﺰب‬ ‫ﻣﻌﮭﺪ اﻟﻘﻠﺐ ﻗﺴﻢ اﻟﺘﻌﻘﯿﻢ اﻟﻤﺮﻛﺰي ﺑﺎﻣﺒﺎﺑﺔ‬
‫د ‪ .‬م ‪ .‬ﻋﺼﺎم ﺧﻠﯿﻞ‬ ‫ﻣﺴﺘﺸﻔﻲ اﻟﺴﻼم اﻟﺪوﻟﻲ‬
‫د ‪ .‬م ‪ .‬ﺷﺎﻛﺮ‬ ‫ﻣﻌﮭﺪ اﻷورام‬
‫اﻟﻨﯿﻞ ﻟﻠﮭﻨﺪﺳﺔ اﻟﻌﻤﻮﻣﯿﺔ‬ ‫ﻣﺴﺘﺸﻔﻲ اﻟﺠﻤﮭﻮرﯾﺔ ﺑﻜﺮﻣﻮز‬
‫اﺳﺒﻜﺘﺮا ﺟﺮوب‬ ‫ﻣﺴﺘﺸﻔﻲ أﺑﻮ اﻟﺮﯾﺶ ﻟﻸطﻔﺎل‬
‫د ‪ .‬ﻣﺨﺘﺎر ﻋﻔﯿﻔﻲ‬ ‫ﻣﺴﺘﺸﻔﻲ اﻟﻤﻄﺮﯾﺔ‬
‫م ‪ .‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫ﻣﺴﺘﺸﻔﻲ اﻟﻤﻌﻠﻤﯿﻦ ﺑﻨﻲ ﺳﻮﯾﻒ‬
‫د ‪ .‬م ‪ .‬ﻣﺤﺴﻦ رﺿﻮان‬ ‫ﻣﺴﺘﺸﻔﻲ اﻟﻘﻠﺐ و اﻟﺼﺪر ﺑﺪﻣﯿﺎط‬
‫اﻟﺤﻤﺪ ﻟﻠﻤﻘﺎوﻻت‬ ‫اﻟﻤﺮﻛﺰ اﻟﻘﻮﻣﻲ ﻟﻠﺴﻤﻮم‬
‫إدارة اﻟﻤﺸﺮوﻋﺎت‬ ‫ﻣﺴﺘﺸﻔﻰ ﻣﺼﺮ ﻟﻠﻄﯿﺮان ) وﺣﺪة اﻟﻐﺴﯿﻞ اﻟﻜﻠﻮي (‬
‫اﻟﯿﻜﻮن‬ ‫ﻣﺸﺮوع اﻟﻘﺎھﺮة ﻟﻸدوﯾﺔ‬
‫ﻧﯿﻞ ﻣﺼﺮ‬ ‫ﻣﺴﺘﺸﻔﻰ ﻓﻠﻤﯿﻨﺞ‬
‫اﻟﯿﻜﻮن‬ ‫ﻣﺴﺘﺸﻔﻰ ﺑﻮرﺳﻌﯿﺪ اﻟﻌﺴﻜﺮى‬
‫اﻟﻤﺸﺮوع‬ ‫اﺳﻢ اﻟﺸﺮﻛﺔ‪/‬اﻟﻤﻘﺎول‬
‫طﺐ اﻻزھﺮ‬ ‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﺮﺣﻤﺔ اﻟﺪوﻟﯿﺔ‬ ‫طﯿﺒﺔ ﺟﺮوب‬
‫ﻣﺴﺘﺸﻔﻲ ھﺮﻣﻞ‬ ‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫ﻣﺴﺘﺸﻔﻲ طﻨﻄﺎ اﻟﻌﺴﻜﺮي‬ ‫اﻻﺳﺘﺸﺎرﯾﻮن ﻟﻠﺼﻨﺎﻋﺔ‬
‫اﻟﻤﺤﺎﻟﯿﻞ اﻟﻄﺒﯿﺔ‬ ‫ﻓﺎرﻣﺎ راد‬
‫ﻣﺴﺘﺸﻔﻲ ﺳﺮطﺎن اﻻطﻔﺎل‬
‫ﯾﻮﻧﻲ ﺗﻚ‬
‫طﻨﻄﺎ‬
‫ﻣﺴﺘﺸﻔﻲ ﻣﺼﺮ ﻟﻠﻄﯿﺮان‬ ‫ﻣﺤﻔﻮظ‬
‫ﻣﻌﮭﺪ اﻻورام‬ ‫اﻟﯿﻜﻮن‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﺠﻨﺰوري‬ ‫ﻣﺼﺮ ﻛﻮل‬
‫ﻣﺮﻛﺰ اﻻورام ﺑﺴﻮھﺎج‬ ‫اﻻﺳﺘﺸﺎرﯾﻮن ﻟﻠﺼﻨﺎﻋﺔ‬
‫ﻣﺴﺘﺸﻔﻲ ﻏﺰل اﻟﻤﺤﻠﺔ‬ ‫اﻟﺴﻮاﻋﺪ‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﺴﻼﻣﺔ‬ ‫ﺗﺮاﺳﺖ ﺟﺮوب‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﺰھﺮاء‬ ‫اﻟﯿﻜﻮن‬
‫ﻣﺴﺘﺸﻔﻲ ﻏﺮب اﻟﻨﻮﺑﺎرﯾﺔ‬ ‫اﻟﯿﻜﻮن‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﻌﺒﻮر‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ذوي اﻻﺣﺘﯿﺎﺟﺎت اﻟﺨﺎﺻﺔ‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ﻣﺴﺘﺸﻔﻲ اﻟﮭﻼل‬ ‫ﺷﻤﺲ‬
‫اﻟﺤﻤﻲ اﻟﻘﻼﻋﯿﺔ‬ ‫ﻓﺎرﻣﺎ راد‬
‫ﻣﺴﺘﺸﻔﻲ ﻋﯿﻦ ﺷﻤﺲ اﻟﺠﺎﻣﻌﻲ‬ ‫اﯾﺘﻚ‬

‫ﺛﺎﻧﻴﺎً ‪ :‬أﻋﻤﺎل اﻟﻤﺼﺎﻧﻊ‬

‫اﻻﺳﺘﺸﺎري ‪ /‬اﳌﻘﺎول‬ ‫أﺳﻢ اﻟﻤﺸﺮوع‬


‫وزارة اﻟﻜﮭﺮﺑﺎء‬ ‫ﺷﺮﻛﺔ ﺑﺮوﺗﻜﺸﻦ ) ﻣﺤﻄﺔ اﻟﻜﮭﺮﺑﺎء ﺷﺒﺮا اﻟﺨﯿﻤﺔ (‬
‫ﺗﺮوﺗﺸﺰﻟﺮ اﻷﻟﻤﺎﻧﯿﺔ‬ ‫اﻟﻌﻼ ﺗﻜﺲ‬
‫ﺗﺮوﺗﺸﺰﻟﺮ اﻷﻟﻤﺎﻧﯿﺔ‬ ‫ﺷﺮﻛﺔ ﻛﻔﺮ اﻟﺸﯿﺦ ﻟﻠﻐﺰل واﻟﻨﺴﯿﺞ‬
‫م ‪.‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫اﻟﺴﻮﯾﺴﺮﯾﺔ ﻟﻠﻤﻼﺑﺲ اﻟﺠﺎھﺰة اﻟﻌﺎﺷﺮ ﻣﻦ رﻣﻀﺎن‬
‫م ‪.‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫اﯾﺠﯿﺒﺖ ﺗﺎﯾﻠﻮرﻧﺞ اﻟﻌﺎﺷﺮ ﻣﻦ رﻣﻀﺎن‬

‫اﻟﻤﺎﻟﻚ‬ ‫ﻣﺼﻨﻊ ﺟﻮﻟﺪن ﻓﻮدز‬


‫اﻧﻜﻮ‬ ‫ﻣﺼﻨﻊ اﻟﺠﻮﻧﺔ‬
‫ﻣﻜﺘﺐ اﻟﺘﺼﻤﯿﻤﺎت د‪ .‬ﻣﺪﺣﺖ‬
‫ﻣﺼﻨﻊ ‪ ) BMW‬ﻣﺮﻛﺰ اﻟﺨﺪﻣﺔ( ﺑﺎﻟﻘﻄﺎﻣﯿﺔ‬
‫اﻟﺸﺎزﻟﻲ‬
‫م‪ .‬ﻣﺮوان ﻛﺮاوﯾﮫ‬ ‫ﻣﺼﻨﻊ ‪ BMW‬ﺑﺎﻛﺘﻮﺑﺮ‬
‫د‪.‬م‪ .‬ﺣﻜﯿﻢ اﻟﻌﻔﯿﻔﻰ‬ ‫ﻣﺼﻨﻊ ﺑﻄﺎﻗﺎت ‪ ATM‬ﺑﺎﻟﻌﺒﻮر‬
‫ﻧﯿﻮﻛﻮﻟﺮ‬ ‫اﻟﺸﺮﻛﺔ اﻟﺸﺮﻗﯿﺔ ﻟﻠﺪﺧﺎن‬
‫م ‪ .‬ﻣﺤﻤﺪ ﺑﺴﯿﻮﻧﻲ‬ ‫دﻟﺘﺎ ﻟﻺﻧﺸﺎء و اﻟﺘﺼﻨﯿﻊ‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﺳﯿﺮاﻣﯿﻜﺎ ﻛﻠﯿﻮﺑﺎﺗﺮا‬
‫د ‪ ٠‬ﺣﺰﯾﻦ‬ ‫ﺷﺮﻛﺔ اﻟﻨﯿﻞ ﻟﻸدوﯾﺔ ﻣﺒﻨﻲ اﻟﻤﺨﺎزن و ﻣﻨﻄﻘﺔ اﻟﻮزن‬
‫د ‪.‬م ‪ .‬ﻣﺤﻤﺪ اﻟﺪﺳﻮﻗﻲ‬ ‫ﻣﺼﻨﻊ طﺎﺑﺎ ﻟﻠﺒﻼﺳﺘﻚ‬
‫اﻟﮭﯿﺌﺔ اﻟﻌﺮﺑﯿﺔ ﻟﻠﺘﺼﻨﯿﻊ‬ ‫ﻣﺼﻨﻊ ﻗﺎدر اﻟﺤﺮﺑﻲ ) ﻣﺸﺮوع ﻣﺼﻨﻊ أﻣﯿﻜﻮ (‬
‫ﻣﺼﻨﻊ ﯾﻮﻧﯿﻔﺮﺳﺎل‬
‫ﻣﺼﻨﻊ ﺟﻨﺮال ﻣﻮﺗﻮرز‬
‫م ‪ .‬ﺧﺎﻟﺪ ﻓﻄﯿﻢ‬ ‫اﻟﻨﯿﻞ ﻟﻸدوﯾﺔ‬
‫ﯾﻮﻧﯿﻮن اﯾﺮ‬ ‫ﻣﺼﻨﻊ ﯾﻮﻧﯿﻮن اﯾﺮ )ﻗﺴﻢ اﻟﺪھﺎﻧﺎت (‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﺷﺮﻛﺔ إﯾﻤﺎ ﺑﺎﺳﺘﺎ ﺑﺎﻟﻌﺎﺷﺮ‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﺷﺮﻛﺔ أﻣﻮن ﻟﻸدوﯾﺔ‬
‫ﻣﯿﺘﻮ اﻟﻌﺎﻟﻤﯿﻦ‬ ‫ﻣﺼﻨﻊ اﻟﺴﻨﺪﯾﺎن ﻟﻠﻮرق )ﻓﺎﯾﻦ(‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﻣﺼﻨﻊ ﻋﺸﺮاﺗﻜﺲ ﻟﻠﻐﺰل واﻟﻨﺴﯿﺞ‬
‫اﻟﻤﺎﻟﻠﻚ‬ ‫ﻣﺼﻨﻊ اﺑﻮ اﻟﺴﺒﺎع ﻟﻠﻐﺰل واﻟﻨﺴﯿﺞ‬
‫ﺑﺮوﺳﺮﻓﯿﺲ‬ ‫ﻣﺼﻨﻊ ﺑﺎﻛﯿﻦ ﻟﻠﺒﻮﯾﺎت‬
‫ﻣﺤﺮم ﺑﺎﺧﻮم‬ ‫اﻟﺸﺮﻗﯿﺔ ﻟﻠﺪﺧﺎن‬
‫ﺻﺒﻮر‬ ‫ﻣﺼﻨﻊ ﺑﯿﻮﻓﺎرم ﻟﻼدوﯾﮫ‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﻣﺼﻨﻊ ھﺎﯾﺪﻟﯿﻨﺎ ﻟﻼدوﯾﺔ‬
‫ﻣﺮﻛﺰ ﺧﺪﻣﮫ وﺻﯿﺎﻧﮫ اﻟﺸﺮﻛﺔ اﻟﺘﺠﺎرﯾﺔ اﺗﻮﻣﻮﺗﯿﻒ ﻓﻮﻟﻜﺲ‬
‫واﺟﻦ‬
‫اﻟﻤﺸﺮوع‬ ‫اﺳﻢ اﻟﺸﺮﻛﺔ‪/‬اﻟﻤﻘﺎول‬
‫‪NPC‬‬ ‫اﯾﺒﻚ‬
‫ﻣﺨﺎزن دھﺸﻮر‬ ‫ﺟﺎس ﻛﻮل‬
‫ﻣﺼﻨﻊ ﻟﯿﻮﻧﻲ‬ ‫اﯾﺒﻚ‬
‫‪Store‬‬ ‫اﻻﻣﺎم‬
‫‪Invensys Process‬‬
‫ﺷﻤﺲ‬
‫‪system‬‬
‫ﻣﺤﻄﺔ ﻛﮭﺮﺑﺎء ﺟﺒﻞ ﻋﺘﺎﻗﺔ‬ ‫ﺷﻤﺲ‬
‫اﺳﺘﻜﻤﺎل اﻟﺸﺮﻗﯿﺔ ﻟﻠﺪﺧﺎن‬ ‫ﻛﻮﻧﺴﻘﻮرة‬
‫ﺳﻜﻮدا‬ ‫ﺷﺎھﯿﻦ‬
‫ﻣﺨﺎزن اﻟﺸﺎﻣﯿﺔ‬ ‫ﺷﻤﺲ‬
‫ﻧﺴﻠﺔ‬ ‫ﺗﻮ واﯾﺮز‬
‫ﻓﯿﺰا‬ ‫طﻨﻄﺎ ﻣﻮﺗﻮرز‬
‫ﻣﺨﺎزن ﺑﺪر‬ ‫اﻟﺤﻤﺪ ﻟﻠﻤﻘﺎوﻻت‬
‫داﺑﺮ اﻣﻼ ﻣﺼﺮ‬ ‫ﻧﯿﻮ ﻛﻮﻟﺮ‬
‫ادﯾﺘﺎ‬ ‫ﺑﺮوﺗﻜﺸﻦ‬
‫ﻣﯿﺘﺴﻮﺑﯿﺸﻲ‬ ‫طﻨﻄﺎ ﻣﻮﺗﻮرز‬
‫ﻣﺨﺎزن ﻣﺘﺮو ﻣﺎرﻛﺖ‬ ‫اﻟﻤﺘﺤﺪة ﻟﻠﻤﻘﺎوﻻت‬
‫ﻛﻼﺑﺸﺔ اﻟﺼﺤﺮاء اﻟﻐﺮﺑﯿﺔ‬ ‫ﺗﻜﻨﯿﻜﺎ‬
‫ﻣﺼﻨﻊ ﺳﺴﻮﯾﺰ ﺑﻮر ﺳﻌﯿﺪ‬ ‫اﻟﯿﻜﻮن‬
‫ﻣﺼﻨﻊ ‪ ٨١‬اﻟﺤﺮﺑﻲ‬ ‫ﻣﺎﯾﻚ‬
‫ﻣﺼﻨﻊ اﻛﺪﯾﻤﺎ اﻟﻌﺒﻮر‬ ‫ﺟﺎﻛﻮ‬
‫ﻛﻮﻧﻜﺮﯾﺖ ﻟﻠﻤﻼﺑﺲ اﻛﺘﻮﺑﺮ‬ ‫اﻟﻨﺪي‬
‫ﻏﺒﻮر ھﯿﻮﻧﺪاي‬ ‫اﻟﯿﻜﻮن‬
‫ﻣﺼﻨﻊ اﯾﺪﯾﺘﺎ ﺑﻨﻲ ﺳﻮﯾﻒ‬ ‫ﺗﻮ واﯾﺮز‬
‫ﻣﺼﻨﻊ اﻟﺴﻜﺮ‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ﻣﺼﻨﻊ ﻛﯿﻤﺎﻓﺎرم ‪ ٦‬اﻛﺘﻮﺑﺮ‬ ‫ﻣﯿﺪﻛﻮم‬
‫وﺣﺪة ﻋﺠﻦ اﻟﺒﺎرود اﻻﺣﺎدي‬ ‫ﺗﺮاﺳﺖ ﺟﺮوب‬
‫ﻣﺼﻨﻊ اﺳﻤﻨﺖ اﻟﻨﮭﻀﺔ ﺑﻘﻨﺎ‬ ‫ﺗﺮاﺳﺖ ﺟﺮوب‬
‫‪P&G‬‬ ‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫ﺑﺪر ﻓﺎرﻣﺎ‬ ‫اﻟﻌﺮﺑﯿﺔ ﺑﻼس‬
‫ﻣﺼﻨﻊ اﻟﺒﻄﺎطﺲ اﻛﺘﻮﺑﺮ‬ ‫ﻛﻮﻧﺘﺮاﻣﻜﺲ‬
‫‪act‬‬ ‫اﺳﯿﻚ‬
‫ﺷﺮﻛﺔ اﻟﺒﺤﺮ اﻟﻤﺘﻮﺳﻂ‬
‫ﻛﻮﻧﺘﺮاﻣﻜﺲ‬
‫اﻟﺴﺎدات‬
‫ﻣﺼﻨﻊ ﯾﻮﻧﯿﻔﺮﺳﺎل‬ ‫اﻻھﻠﯿﺔ ﻟﻠﺘﻜﯿﯿﻒ‬
‫ﺳﯿﺪﻛﻮ ﻟﻼدوﯾﺔ اﻛﺘﻮﺑﺮ‬ ‫ﺗﺎرﺟﯿﺖ اﯾﺠﯿﺒﺖ‬
‫ﺗﺠﺪﯾﺪات ﻣﺼﻨﻊ ﻛﺎدﺑﻮري‬ ‫ﺟﻮدﻛﻮ ﻟﻼﻧﺸﺎءات‬
‫ﻣﺼﻨﻊ ﻛﯿﻤﺎوﯾﺎت اﺑﻮ زﻋﺒﻞ‬ ‫اﻟﺪﻟﺘﺎ ﻟﻠﻤﻘﺎوﻻت و اﻟﺘﻮرﯾﺪات‬
‫ﻣﺨﺎزن ﺑﺪر ﺑﺘﺮوﺟﯿﺖ‬ ‫اﻟﺤﻤﺪ ﻟﻠﻤﻘﺎوﻻت‬
‫ﺣﺎوﯾﺎت ﺷﺮق اﻟﺘﻔﺮﯾﻌﺔ‬ ‫اﻟﺤﻤﺪ‬
‫ﻣﺼﻨﻊ اﻻﯾﺜﻠﯿﻦ )‪(ethydco‬‬ ‫ارﺟﻨﻮت‬
‫ﻣﺒﻨﻰ ‪(ethydco)utilities‬‬ ‫اﻟﯿﻜﻮن‬

‫ﺛﺎﻟﺜﺎ ‪:‬ﺟﺎﻣﻌﺎت ‪,‬ﺻﺎﻻت أﻟﻌﺎب وﻣﻌﺎرض‬

‫ﻛﻠﯿﺔ اﻟﮭﻨﺪﺳﺔ أﺳﯿﻮط‬ ‫ﺟﺎﻣﻌﺔ ﺟﻨﻮب اﻟﻮادي ﺑﺴﻮھﺎج‬


‫م‪.‬ﻋﺒﺪ اﻟﺤﻤﯿﺪ ﻋﻔﯿﻔﻰ‬ ‫ﺟﺎﻣﻌﺔ ﺣﻠﻮان‬
‫ﻛﻠﯿﺔ اﻟﮭﻨﺪﺳﺔ ﺑﺄﺳﯿﻮط‬ ‫ﻛﻠﯿﺔ اﻟﺘﺠﺎرة ﺑﺴﻮھﺎج‬
‫اﻟﻨﯿﻞ ﻟﻠﮭﻨﺪﺳﺔ اﻟﻌﻤﻮﻣﯿﺔ‬ ‫ﺟﺎﻣﻌﺔ ﻗﻨﺎة اﻟﺴﻮﯾﺲ ﺑﻮر ﺳﻌﯿﺪ ) ﺻﺎﻟﺔ اﻷﻟﻌﺎب(‬
‫م ‪ .‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫ﻣﻄﺎر اﻟﻘﺎھﺮة ) ﺻﺎﻟﺔ ‪( ٢‬‬
‫ﻧﯿﻞ ﻣﺼﺮ‬ ‫ارض اﻟﻤﻌﺎرض ) ﺻﺎﻟﺔ ‪(٢٠‬‬
‫ﻧﯿﻞ ﻣﺼﺮ‬ ‫أرض اﻟﻤﻌﺎرض ) ﻣﺸﺮوع ﺻﺎﻟﺔ ‪( ٣،٥‬‬
‫ﺑﺘﺮوﺟﯿﺖ‬ ‫ﺷﺮﻛﺔ اﻟﻨﺼﺮ ﻟﻠﺒﺘﺮول ) ﺻﺎﻟﺔ اﻷﻟﻌﺎب (‬
‫اﻟﻤﺤﺎور )ﻟﯿﺒﯿﺎ(‬ ‫اﻟﻤﺪﯾﻨﺔ اﻻﻟﻌﺎب اﻟﺮﯾﺎﺿﯿﺔ ﺑﺒﻨﻐﺎزى‬
‫راﺑﻌﺎ ‪ -:‬اﻟﻔﻨﺎدق‬
‫د‪.‬م ﻣﺤﻤﺪ اﻟﺪﺳﻮﻗﻰ‬ ‫ﺣﯿﺎة رﯾﺠﯿﻨﺴﻰ ﺷﺮم اﻟﺸﯿﺦ‬
‫د‪.‬م ﻋﻼء ﻋﻠﻤﮫ‬ ‫ﻏﺰاﻟﺔ اﻟﻌﻠﻤﯿﻦ‬
‫اﻟﻤﺎﻟﻚ‬ ‫ﻛﺮاون ﺑﻼزا ﺷﺮم اﻟﺸﯿﺦ‬
‫د‪ .‬ﺷﺎﻛﺮ‬ ‫ﻗﺮﯾﺔ ﻣﺮﺳﻰ ﻋﻠﻢ‬
‫‪C.C.C‬‬ ‫ﺳﻮﻓﺘﯿﻞ اﻟﺠﺰﯾﺮة‬
‫‪ABB‬‬ ‫ﻓﻮرﺳﯿﺰون ﻧﺎﯾﻞ ﺑﻼزا‬
‫ﻧﯿﻞ ﻣﺼﺮ‬ ‫ﻣﻮﻓﯿﻨﺒﯿﻚ اﺳﻮان‬
‫ﺷﻤﺲ‬ ‫ﻛﺎرﯾﺒﯿﺎن وورﻟﺪ رﯾﺰورت‬
‫ﻛﺮاون ھﻮم‬ ‫ﺑﺴﺘﺎن اﻟﺴﺨﻨﮫ‬
‫د‪ /‬اﺣﻤﺪ ﺧﻄﺎب‬ ‫ﺷﺎرﻣﯿﻨﺞ ھﻠﯿﺰ‬
‫اﻟﻤﺸﺮوع‬ ‫اﺳﻢ اﻟﺸﺮﻛﺔ‪/‬اﻟﻤﻘﺎول‬
‫ﻛﻮرال ﺳﻲ ﺳﺒﻼش‬ ‫ﺷﻤﺲ‬
‫ﺳﯿﺘﻲ ﻓﯿﻮ‬ ‫اﯾﻤﻜﻮ‬
‫‪lake view‬‬ ‫اﻻﻣﺎم‬
‫ﻓﻨﺪق ﻓﻠﺴﻄﯿﻦ‬ ‫طﯿﺒﺔ ﺟﺮوب‬
‫ﻓﻨﺪق اﻟﻘﻄﺎﻣﯿﺔ‬ ‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫‪Invensys‬‬ ‫ﺷﻤﺲ‬
‫ﻓﻨﺪق ﻣﻮﻓﻨﺒﯿﻚ اﺳﻮان‬ ‫ﻧﯿﻞ ﻣﺼﺮ‬
‫ﺑﺴﺘﺎن اﻟﺴﺨﻨﺔ‬ ‫ﺷﻤﺲ‬
‫‪cfc‬‬ ‫‪ABB‬‬
‫ﻏﻨﺎظﺔ‬ ‫ﺷﻤﺲ‬
‫ﺷﺎرﻣﻨﺞ ھﯿﻠﺰ‬ ‫ﺷﻤﺲ‬
‫ﺑﺘﺮ ھﻮم ‪ ٦‬اﻛﺘﻮﺑﺮ‬ ‫ﻣﺎﯾﻚ‬
‫‪Urban plaza‬‬ ‫ﺑﯿﺮوﺳﯿﺮﻓﯿﺲ‬
‫ﻓﻨﺪق ﻟﻮﺑﺎﺳﺎج اﻟﻤﻄﺎر‬ ‫اﻟﯿﻜﻮن‬
‫ﻓﻨﺪق ﻧﻮﻓﺘﯿﻞ ﺷﺮم اﻟﺸﯿﺦ‬ ‫ﺳﻤﺎ‬
‫ﻓﻨﺪق ﻓﻠﺴﻄﯿﻦ اﻻﺳﻜﻨﺪرﯾﺔ‬ ‫طﯿﺒﺔ ﺟﺮوب‬
‫‪swam lake‬‬ ‫اﻻﻣﺎم‬
‫اﻧﺘﺮﻛﻮﻧﺘﻨﻨﺘﺎل ﺳﯿﺘﻲ‬
‫طﯿﺒﺔ ﺟﺮوب‬
‫ﺳﺘﺎرز‬
‫ﺟﻮﻟﺪن ﻛﻮﺳﺖ ﺷﺎرم‬
‫اﻟﺠﺎﺑﺮي‬
‫اﻟﺸﯿﺦ‬
‫‪New Giza‬‬ ‫اﻟﺘﻮﺣﯿﺪ‬
‫ﻓﻨﺪق ﻣﯿﺮدﯾﺎن دھﺐ‬ ‫ﻧﯿﻞ ﻣﺼﺮ‬
‫اﻟﻤﻄﻌﻢ اﻟﺮﺋﯿﺴﻲ ﺑﻔﻨﺪق‬
‫اﻟﺤﻤﺪ ﻟﻠﻤﻘﺎوﻻت‬
‫ﺗﺮﯾﻤﻒ‬
‫ﺧﺎﻣﺴﺎ‪:‬ﻣﺸﺮوﻋﺎت ﻣﺘﻨﻮﻋﺔ‬

‫م‪ .‬ﻋﺒﺪ اﻟﺤﻤﯿﺪ اﻟﺒﻜﺮى‬ ‫ﻛﺎرﻓﻮر ﺑﺎﺑﻮرواش‬


‫م‪ .‬ﻋﺒﺪ اﻟﺤﻤﯿﺪ اﻟﺒﻜﺮى‬ ‫ﻛﺎرﻓﻮر ﺳﯿﺘﻰ ﺳﻨﺘﺮ‬
‫م‪ .‬ﻋﺒﺪ اﻟﺤﻤﯿﺪ اﻟﺒﻜﺮى‬ ‫ﻛﺎرﻓﻮر اﻻﺳﻜﻨﺪرﯾﺔ‬
‫اﯾﮭﺎف‬ ‫ﺑﺮج اﻟﻤﺼﺮﯾﻦ ﺑﺎﻟﻤﺒﺘﺪﯾﺎن‬
‫ﻣﺮﻛﺰ ھﻨﺪﺳﺔ اﻟﺘﺒﺮﯾﺪ‬ ‫ﺳﻔﻦ ﺳﯿﺎﺣﯿﺔ‬
‫إﯾﺠﯿﻜﺎت‬ ‫ﻣﺸﺮوع ﺑﻨﻚ اﻟﺘﻌﻤﯿﺮ و اﻹﺳﻜﺎن ﻣﺪﯾﻨﺔ ﻧﺼﺮ‬
‫ﻛﻮﺑﯿﺮا‬ ‫ﻛﻮﺑﯿﺮا‬
‫ﺷﺎھﯿﻦ ﺟﺮوب‬ ‫ﻧﻘﺎﺑﺔ اﻟﻤﻌﻠﻤﯿﻦ ﺑﺎﻟﺰﻗﺎزﯾﻖ‬
‫ﻣﺎﺳﯿﺒﯿﺮو‬ ‫اﺳﺘﻮدﯾﻮ اﻟﻤﻨﺎظﺮ‪ -‬اﺗﺤﺎد اﻻذاﻋﺔ و اﻟﺘﻠﯿﻔﺰﯾﻮن‬
‫د‪.‬م‪ .‬ﻋﻼء ﻋﻠﻤﮫ‬ ‫وﯾﺒﻜﻮ ﻟﻠﺒﺘﺮول‬
‫م ‪ .‬ﻧﺒﯿﻞ إﻣﺎم‬ ‫ﻓﯿﻼ ھﺸﺎم اﻟﻔﺘﻲ‬
‫إﻟﯿﻜﻮن‬ ‫ﻣﺒﻨﻲ ﺗﺠﺎري ﺑﺨﺎن اﻟﻌﺮب‬
‫أﯾﺘﻚ‬ ‫اﻟﺴﻔﺎرة اﻟﻨﻤﺴﺎوﯾﺔ‬
‫اﻟﯿﻜﻮن‬ ‫ﻣﺎﺳﺒﯿﺮو‬
‫أﻣﯿﻜﻮ‬ ‫أﻣﯿﻜﻮ‬
‫اﻟﯿﻜﻮن‬ ‫ﺳﯿﺪى ﻛﺮﯾﺮ ﻟﻠﺒﺘﺮول‬
‫اﻟﮭﻨﺪﺳﺔ اﻹذاﻋﯿﺔ‬ ‫ﻣﺎﺳﺒﯿﺮو أﺳﺘﻮدﯾﻮ اﻟﻤﺮاﻗﺒﺔ‬
‫اﻟﻤﺎﻟﻚ‬ ‫وزارة اﻟﺘﻌﺎون اﻟﺪوﻟﻲ‬
‫ﻧﯿﻞ ﻣﺼﺮ‬ ‫ﻣﺒﻨﻰ اﻟﺼﻨﺪوق اﻻﺟﺘﻤﺎﻋﻰ )ﺻﺎﻟﺔ ‪( ٢٠‬‬
‫ﺑﺮوﺳﺮﻓﯿﺲ‬ ‫ﻣﻮﺑﯿﻨﯿﻞ ) اﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ(‬
‫اﻛﻤﻰ‬ ‫ﻣﺒﻨﻰ وﻓﯿﻼت اﻋﻤﺎر اﻟﻤﻘﻄﻢ‬
‫اﻟﺪار ﻻﻧﻈﻤﺔ اﻟﮭﻮاء‬ ‫ﺳﻮﺑﺮ ﻣﺎرﻛﺖ ﻣﺘﺮو ) اﻻﺳﻜﻨﺪرﯾﺔ (‬
‫ﺣﺮب‬ ‫ﻗﻨﺎطﺮ ﻧﺠﻊ ﺣﻤﺎدى‬
‫ﻣﻜﺘﺐ ﺻﺒﻮر‬ ‫ﻗﺼﺮ ﺿﯿﺎﻓﺔ ﺑﯿﺖ اﻟﻘﺎھﺮة )رﺋﺎﺳﺔ اﻟﺠﻤﮭﻮرﯾﺔ (‬
‫ﻣﺘﺮو اﻻﻧﻔﺎق اﻋﻤﺎل‬
‫اﻟﺼﺎج ﻛﺎﻣﻠﺔ‬ ‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫وﻣﺨﺎرج اﻟﮭﻮاء‬
‫اﻟﻤﺸﺮوع‬ ‫اﺳﻢ اﻟﺸﺮﻛﺔ‪/‬اﻟﻤﻘﺎول‬
‫ﻣﺠﻤﻊ ﺗﺮﻓﯿﮭﻲ‬
‫ﻧﯿﻮ ﻛﻮﻟﺮ‬
‫ﺑﺒﻮرﺳﻌﯿﺪ‬
‫راﯾﺔ اﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ‬ ‫اﻻﻣﺎم‬
‫ﺑﺎرﺑﻜﯿﻮ داون ﺗﺎون‬ ‫ﺗﺮاﺳﺖ ﺟﺮوب‬
‫ﻣﺘﺤﻒ ﺳﻜﻚ ﺣﺪﯾﺪ‬
‫ﻓﻼش‬
‫ﻣﺼﺮ‬
‫ﻧﻤﺎء ‪٤٤‬‬ ‫اﻻﻓﻖ‬
‫اﻟﻤﺒﻨﻰ اﻻدارى ﺣﺴﻦ ﻋﻼم‬ ‫‪Brand of quality‬‬
‫‪TB3‬‬ ‫اﻻﻣﺎم‬
‫ﻣﺪارس اﻟﻨﯿﻞ اﻟﻤﺘﻤﯿﺰة‬
‫ﻧﯿﻮ ﻛﻮﻟﺮ‬
‫ﺑﺒﻮرﺳﻌﯿﺪ‬
‫ﻣﺘﺮو اﻻﻧﻔﺎق اﻋﻤﺎل‬
‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫اﻟﻤﺨﺎرج اﻟﮭﻮاء ﻛﺎﻣﻠﺔ‬
‫ﻣﺒﻨﻲ اﻟﺒﺮﯾﺪ ﺷﺒﯿﻦ‬
‫ﺗﺮاﺳﺖ ﺟﺮوب‬
‫اﻟﻜﻮم‬
‫ﻓﯿﻼ ﻣﺤﻤﺪ ﺑﻚ‬
‫راﻣﻮ‬
‫اﻟﺸﺮﻗﺎوي‬
‫ﻣﻄﺎر اﺳﯿﻮط اﻟﺪوﻟﻲ‬ ‫اﻻﻣﺎم‬
‫ﻣﻄﺎر ﺳﻮھﺎج‬ ‫ﻣﺎﻓﻜﻮ‬
‫ﻣﻌﺮض ﻏﺒﻮر‬ ‫اﻟﯿﻜﻮن‬
‫ﻓﻮداﻓﻮن اﻟﻤﻨﺸﯿﺔ‬ ‫اﻟﻤﺆﺳﺴﺔ اﻟﻌﺎﻟﻤﯿﺔ‬
‫ﻣﺪرﺳﺔ اﻟﻤﻨﯿﺎ‬ ‫اﻻﻣﺎم‬
‫ﺟﻮھﺮة اﻟﺤﺮس‬
‫اﻟﯿﻜﻮن‬
‫اﻟﺠﻤﮭﻮري‬
‫ﻓﻮداﻓﻮن اﻟﻤﺤﻠﺔ‬ ‫اﻟﻤﺆﺳﺴﺔ اﻟﻌﺎﻟﻤﯿﺔ‬
‫طﯿﺒﺔ ﻣﻮل‬ ‫ﻣﺼﺮ ﻟﻠﻤﻘﺎوﻻت اﻟﻤﯿﻜﺎﻧﯿﻜﯿﺔ‬
‫‪Carrefour sun‬‬
‫ﺗﻮ واﯾﺮز‬
‫‪city‬‬
‫ﺻﺎﻟﺔ اﻟﺤﺠﺎج اﻟﻤﻄﺎر‬ ‫ﯾﻮﻧﻲ ﺗﻚ‬
‫ﻓﯿﻼ ﻏﺒﻮر ھﻀﺒﺔ‬
‫ﺟﯿﻚ ﻟﻠﻤﻘﺎوﻻت‬
‫اﻟﮭﺮم‬
‫ﻣﺘﺤﻒ ﺳﻮزان ﻣﺒﺎرك‬ ‫ﻣﻜﺘﺐ اﻻھﺮاﻣﺎت‬
‫ﻣﺎﻛﺮو اﻟﺴﻼم‬ ‫اﻟﺨﺒﺮاء‬
‫ﻣﺮﻛﺰ اﻟﻘﺎھﺮة اﻟﻤﺎﻟﻲ‬ ‫اﻻﻣﺎم‬
‫ﻣﺒﻨﻲ اﻟﺒﺮﯾﺪ اﻟﻤﺼﺮي‬ ‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫ﻣﺒﻨﻲ اﻟﻤﻨﻈﻤﺔ اﻟﻌﺮﺑﯿﺔ‬ ‫اﻟﯿﻜﻮن‬
‫ﺗﺠﺪﯾﺪات ﻣﺠﻠﺲ‬
‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫اﻟﺸﻌﺐ‬
‫ﺑﯿﺖ اﻟﺨﺒﺮة‬ ‫اﻻﻓﻖ‬
‫اﻟﺴﻔﺎرة اﻻﻟﻤﺎﻧﯿﺔ‬ ‫اﻟﯿﻜﻮن‬
‫‪Egyptian‬‬
‫ﻛﻮﻧﺴﻘﻮرة‬
‫‪Bahrinicas‬‬
‫‪Al awali‬‬ ‫ﻛﻮﻧﺴﻘﻮرة‬
‫اﯾﺴﻜﻮر اﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ‬ ‫ﻛﻮﻟﻤﺎن ﻣﺼﺮ‬
‫ﺳﻌﻮدي ﻣﺎرﻛﺖ اﻟﺸﯿﺦ‬
‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫زاﯾﺪ‬
‫ﻣﻄﻌﻢ اﻟﻌﺸﺎئ‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ﻛﺎﯾﺮو ﺑﻼزا‬ ‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫اﻟﻤﺒﻨﻲ اﻟﺨﺪﻣﻲ اﻟﻤﻄﺎر‬ ‫اﻻﻣﺎم‬
‫ﻣﻌﺮض اﻟﻄﺎرق‬ ‫ﯾﻮﻧﯿﺘﺪ ار‬
‫ﻣﺤﻄﺔ ﻛﮭﺮﺑﺎء اﻟﻌﯿﻦ‬
‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫اﻟﺴﺨﻨﺔ‬
‫ﻗﺎﻋﺔ ﻣﺆﺗﻤﺮات ﻛﻔﺮ‬
‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫اﻟﺸﯿﺦ‬
‫ﻣﺤﻄﺔ ﻛﮭﺮﺑﺎء ﺷﻤﺎل‬
‫ﻣﺆﺳﺴﺔ اﻟﺮﺿﺎ‬
‫ﺳﯿﻨﺎء‬
‫راﯾﺔ اﻛﺘﻮﺑﺮ‬ ‫اﻻﻣﺎم‬
‫ﻣﻄﺎر ﻣﺎﻻﺑﻮ ﻏﯿﻨﯿﺎ‬ ‫اﻻﻣﺎم‬
‫اﻟﯿﺎﻧﺰ ﻟﻠﺘﺎﻣﯿﻦ اﻟﺪور‬
‫ﻛﻮﻣﯿﺘﻤﻨﺖ‬
‫اﻟﻌﺎﺷﺮ‬
‫دھﺸﻮر‬ ‫ﺟﺎس ﻛﻮل‬
‫اﻛﺪﯾﻤﺎ‬ ‫ﺟﺎﻛﻮ‬
‫اﻟﺠﮭﺎز اﻟﻘﻮﻣﻲ ﻟﺘﻨﻈﯿﻢ‬
‫اﻟﯿﻜﻮن‬
‫اﻻﺗﺼﺎﻻت‬
‫ﺣﻤﺎم ﺳﺒﺎﺣﺔ ﻧﺎدي‬
‫ﻛﻮﻟﻤﺎن ﻣﺼﺮ‬
‫اﻟﺼﯿﺪ‬
‫ﻣﺸﺮوع اﻟﻘﻄﺎر اﻟﻄﺎﺋﺮ‬
‫اﻟﻤﺮاﺳﻢ‬
‫ﻣﻄﺎر اﻟﻘﺎھﺮة‬
‫اﻟﺸﺮﻛﺔ اﻟﻤﺼﺮﯾﺔ‬
‫ﺟﺎس ﻛﻮل‬
‫ﻟﻠﺘﺒﺮﯾﺪ ﺑﺎﻟﻐﺎز اﻟﻄﺒﯿﻌﻲ‬
‫ھﺎرد روك ﻛﺎﻓﯿﮫ ﺷﺮم‬ ‫ﯾﻮﻧﯿﺘﺪ ار‬
‫‪ hns mall‬اﻟﻤﻄﺎر‬ ‫‪HNs‬‬
‫‪Cairo Festeval‬‬ ‫ﻧﺎﯾﻞ ﺗﻜﻨﻮﻟﻮﺟﻲ‬
‫‪Cib arbia mall‬‬ ‫ﻣﺤﻔﻮظ‬
‫ﻣﺤﻄﺔ ﻛﮭﺮﺑﺎء ﻣﺮﺳﻲ‬
‫ﻧﯿﻞ ﻣﺼﺮ‬
‫ﻣﻄﺮوح‬
‫ﻣﻮل ﻣﺪﺳﺘﺎر‬ ‫ﻣﺪﺳﺘﺎر‬
‫ﻣﺘﺮو ﻣﺎرﻛﺖ‬ ‫ﺑﺮوﺗﻜﺸﻦ‬
‫ﻣﺤﻄﺔ دﻣﯿﺎط‬ ‫ھﻠﯿﻮﻛﻮل‬
‫ﻣﻌﮭﺪ ﺗﺪرﯾﺐ وھﺪان‬ ‫اﻟﺒﺎﺷﺎ‬
‫اﻟﻤﻼﺣﺔ اﻟﺠﻮﯾﺔ‬ ‫دﻟﺘﺎ ﻟﻠﻤﻘﺎوﻻت‬
‫‪Upper cairo‬‬ ‫اﻟﻌﺮﺑﯿﺔ ﻟﻼﻧﺸﺎءات‬
‫ﻛﺎرﻓﻮر اﻛﺴﺒﺮﯾﺲ‬
‫اﻟﻤﺆﺳﺴﺔ اﻟﻌﺎﻟﻤﯿﺔ‬
‫طﯿﺒﺔ ﻣﻮل‬
‫‪sodic‬‬ ‫ﺷﺎھﯿﻦ‬
‫ﺟﺎﻣﻊ اﺑﻮ ﺑﻜﺮ اﻟﺼﺪﯾﻖ‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ﺷﯿﺒﺴﻲ‬ ‫ﻛﺎﺑﯿﺘﺎل‬
‫ﻣﻄﻌﻢ دار اﻟﻘﻤﺮ‬ ‫ھﺎﯾﺒﺮ اﯾﺮ‬
‫ﻣﻌﺮض ﺑﺮاﻧﺪر‬
‫اﻟﻨﺪي‬
‫ﻟﻠﻤﻼﺑﺲ طﯿﺒﺔ ﻣﻮل‬
‫ﻛﺎرﻓﻮر طﯿﺒﺔ ﻣﻮل‬ ‫ﯾﻮﻧﯿﻔﺮﺳﺎل‬
‫ﺑﯿﺖ اﻟﻌﺰ ‪٢‬‬ ‫ﻧﺎﯾﻞ ﻛﻮل‬
‫اﻟﺼﺎﻟﺔ اﻟﻤﻐﺎة ﻟﮭﯿﺌﺔ‬
‫ﻣﺮﻛﺰ اﻟﻌﻤﺎرة و اﻻﻧﺸﺎء‬
‫ﻗﻨﺎة اﻟﺴﻮﯾﺲ‬
‫‪utilities building‬‬ ‫اﻻﻣﺎم‬
‫اﻟﻤﺮﻛﺰ اﻻﻗﻠﯿﻤﻲ‬
‫ﻧﯿﻮ ﻛﻮﻟﺮ‬
‫ﻟﻼﺳﻌﺎف ﺷﺮم اﻟﺸﯿﺦ‬
‫‪El shabab powex‬‬
‫‪Eco Associates‬‬
‫‪Station‬‬
‫‪Cairo American‬‬
‫ﺑﺮوﺳﯿﺮﻓﯿﺲ‬
‫‪college‬‬
‫اﻟﺠﺎﻣﻌﺔ اﻟﻌﺮﺑﯿﺔ‬
‫اﻟﻤﺘﺤﺪة ﻟﻠﻤﻘﺎوﻻت‬
‫اﻟﻤﻔﺘﻮﺣﺔ‬
‫‪ Ncp‬اﻟﺪﯾﺎر اﻟﻘﻄﺮﯾﺔ‬ ‫درﯾﻚ اﻧﺪ ﺳﻜﺎل‬
‫اﻟﺼﺎﻟﺔ اﻟﻤﻐﻄﺎة ﻣﺮﻛﺰ‬
‫اﻟﺸﺮﻛﺔ اﻟﻤﺘﺤﺪة ﻟﻠﻤﻘﺎوﻻت‬
‫ﺷﺒﺎب ﻣﯿﺖ ﻋﻘﺒﺔ‬
‫ﺑﻮرﺟﺮ ﻛﯿﻨﺞ اﻟﺘﺠﻤﻊ‬ ‫اﻟﻌﺮﺑﯿﺔ ﻟﻠﺘﻜﯿﯿﻒ و اﻟﺘﺒﺮﯾﺪ‬
‫‪sun city cenima‬‬ ‫اﯾﻤﻜﻮ‬
‫اوﻻد رﺟﺐ اﻟﻮاﯾﻠﻲ‬ ‫اﻟﺪار‬
‫ﻣﺎﻛﺮو اﻧﺪ ﻛﺎش اﻟﺴﻼم‬ ‫اﻟﺨﺒﺮاء‬
‫اﻟﻤﺮﻛﺰ اﻟﺜﻘﺎﻓﻲ اﻟﻘﺒﻄﻲ‬ ‫ﻣﯿﻜﺎﺗﺮوﻧﯿﻜﺲ‬
‫ﺗﺸﯿﻠﯿﯿﺰ ‪ -‬ﻣﻮل اﻟﻌﺮب‬
‫ﯾﻮﻧﯿﺘﺪ ار‬
‫اﻛﺘﻮﺑﺮ‬
‫ﻣﺠﻤﻊ ﺳﻨﯿﻤﺎت‬
‫طﯿﺒﺔ ﻟﻠﻤﻘﺎوﻻت‬
‫اﻣﺮﯾﻜﺎﻧﺎ‬
‫ﻛﻨﯿﺴﺔ ﻣﺎرﺟﺮﺟﺲ‬
‫ﺗﻮ واﯾﺮز‬
‫ﺣﻠﻮان‬
‫ﻣﺨﺎرج ھﻮاء ‪MP3‬‬ ‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫ﻣﻮل اﻟﻌﺮﺑﻲ‬ ‫ﻧﯿﻮ ﻣﺎﺗﻜﻮ‬
‫ﻛﺎرﻓﻮر ﺑﻼزا‬ ‫ﻣﯿﻜﺎﻧﻮ‬
‫ﻧﻔﻖ اﻟﻤﻌﺮاج‬ ‫اﻟﻤﻘﺎوﻟﻮن‬
‫‪new giza‬‬ ‫اﻟﺘﻮﺣﯿﺪ‬
‫ﻣﺠﻠﺲ ﻗﯿﺎدة اﻟﺜﻮرة‬ ‫اﻟﻤﻘﺎوﻟﻮن‬
‫ﺗﺠﺪﯾﺪات ﻣﺤﻄﺔ ﻣﺼﺮ‬ ‫اﻻﻣﺎم‬
‫‪BBC‬‬ ‫اﻟﺘﻮﺣﯿﺪ‬
‫اﻋﻤﺎر اﻟﻤﻘﻄﻢ‬ ‫‪acc‬‬
‫ﺟﺮاج ﻣﺮﻛﺰ اﻟﺘﺠﺎرة‬ ‫اﯾﺒﻚ‬
‫‪future mall‬‬ ‫ﻛﻮﻧﺴﻘﻮرة‬
‫ﻛﺎرﻓﻮر اﻟﻌﺮوﺑﺔ‬ ‫ﺗﻮ واﯾﺮز‬
‫اﻟﻤﮭﻨﺪﺳﯿﻦ ‪chartis‬‬ ‫اﻟﻨﺪى‬
‫‪hanimix‬‬ ‫ﺟﺎس ﺷﻞ‬
‫اﻟﻤﮭﻨﺪﺳﯿﻦ ‪chartis‬‬ ‫اﻟﻨﺪى‬
‫ﻛﺎرﻓﻮر اﻟﻌﺮوﺑﺔ‬ ‫ﺗﻮ واﯾﺮز‬
‫اﻟﺠﺎﻣﻌﺔ اﻻﻟﻤﺎﻧﯿﺔ‬ ‫ﻋﯿﻦ ﺷﻤﺲ‬
‫ﻣﺴﺠﺪ اﻟﺤﻤﺪ‬ ‫ﻛﻮﻟﻤﺎن ﻣﺼﺮ‬
‫اﺳﺘﻘﺒﺎل ﻣﻮل اﻟﻌﺮب‬ ‫ﺗﺎرﺟﺖ اﯾﺠﯿﺒﺖ‬
‫اﻟﻤﺠﻤﻊ اﻟﺘﻜﻨﻮﻟﻮﺟﻰ‬ ‫اﻟﻤﻘﺎوﻟﻮن‬
‫‪cfc‬‬ ‫ﻧﺎﯾﻞ اﺳﺘﺮ‬
‫‪ -٦‬اﻋﻤﺎل اﻟﺒﻨﻮك‬

‫ﺑﻨﻚ اﻟﺘﻨﻤﯿﺔ اﻟﻮطﻨﻲ اﻟﻤﻨﺼﻮرة‬ ‫ﻓﺎن ﺗﻚ‬

‫ﺑﻨﻚ ﻛﺮﯾﺪي اﺟﺮﯾﻜﻮل ﻓﺮع ﻧﺎدي اﻟﺼﯿﺪ اﻟﺪﻗﻲ‬ ‫اﻟﻤﺆﺳﺴﺔ اﻟﻌﺎﻟﻤﯿﺔ‬

‫اﻣﻮال اﻟﻌﺮﺑﯿﺔ ﺑﺎﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ‬ ‫اﺑﯿﻚ‬


‫اﻟﺒﻨﻚ اﻻھﻠﻲ ﻓﺮع ﻓﯿﺼﻞ‬ ‫اﻟﻤﻘﺎوﻟﻮن اﻟﻌﺮب‬
‫ﺑﻨﻚ ﻋﻮدة‬ ‫ﺗﻮ واﯾﺮز‬
‫اﻟﺒﻨﻚ اﻟﻮطﻨﻲ‬ ‫ﻛﻮﻧﺴﻘﻮرة‬
‫‪alex bank‬‬ ‫ﻣﯿﻜﺎﻧﻮ اﯾﺠﯿﺒﺖ‬
‫‪cib bank‬‬ ‫اﯾﻤﻜﻮ‬
‫ﺑﻨﻚ ﻛﺮﯾﺪي اﺟﺮﯾﻜﻮل اﻟﻤﮭﻨﺪﺳﯿﻦ ﺳﻮرﯾﺎ‬ ‫اﻟﺪار ﺟﺮوب‬
‫ﺑﻨﻚ ﺳﺎن ﺑﺎوﻟﻮ اﻻﺳﻜﻨﺪرﯾﺔ‬ ‫اوراﺳﻜﻮم‬
‫ﺑﻨﻚ ‪HSBC‬‬ ‫اﻟﺪار‬
‫ﺑﻨﻚ ﻣﺼﺮ اﯾﺮان اﻟﻘﺎھﺮة‬ ‫ﻣﺼﺮ ﻛﻮﻧﺘﺮاﻛﻮ‬
‫ﺑﻨﻚ ‪ NSGB‬طﻠﻌﺖ ﺣﺮب‬ ‫ﻣﺼﺮ ﻛﻮﻧﺘﺮاﻛﻮ‬
‫ﻟﻮران ‪HSBC‬‬ ‫اﻟﺸﺮق اﻻوﺳﻂ‬
‫اﻻﺗﺤﺎد اﻟﻮطﻨﻲ‬ ‫ﻣﺼﺮ ﻛﻮﻧﺘﺮاﻛﻮ‬
‫‪Priaues bank‬‬ ‫ﺗﻮ واﯾﺮز‬
‫اﻟﺒﻨﻚ اﻻھﻠﻲ اﻟﻤﺼﺮي ﻓﺮع ﺷﺮم اﻟﺸﯿﺦ‬ ‫اﻟﻨﺪي‬
‫ﺑﻨﻚ اﻻﺳﺘﺜﻤﺎر اﻟﻘﻮﻣﻲ‬ ‫اﻟﺤﻤﺪ‬
‫‪NSGB‬ﺑﺪر‬ ‫ﯾﻮﻧﯿﻔﺮﺳﺎل‬
‫اﻟﺒﻨﻚ اﻟﺘﺠﺎري اﻟﺪوﻟﻲ ‪ -‬اﻟﻤﺤﻠﺔ‬ ‫ﻣﯿﻜﺎﻧﻮ اﯾﺠﯿﺒﺖ‬
‫ﺑﻨﻚ ﻣﺼﺮ ﻓﺮع اﻟﺴﻨﺒﻼوﯾﻦ‬ ‫اﯾﺘﻚ‬
‫ﺑﻨﻚ ﻋﻮدة ﻓﺮع اﻟﻼﺳﻠﻜﻲ‬ ‫ﻣﺤﻔﻮظ‬

‫‪alex bank‬‬ ‫ﻣﯿﻜﺎﻧﻮ اﯾﺠﯿﺒﺖ‬


‫اﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ ‪cib‬‬ ‫اﯾﻤﻜﻮ‬
‫اﻟﺒﻨﻚ اﻻھﻠﻲ ﺑﺮج اﻟﺠﺎﻣﻌﺔ‬ ‫اﻻﻓﻖ‬

‫‪CIB‬اﻟﺠﯿﺰة‬ ‫طﯿﺒﺔ ﻟﻠﻤﻘﺎوﻻت و ﻧﻈﻢ اﻟﺘﻜﯿﯿﻒ‬

‫‪Elwatany bark‬‬ ‫ﻛﻮﻧﺴﻘﻮرة‬


‫‪HSBC‬‬ ‫ﻛﺎﺑﯿﺘﺎل ﻟﻠﻤﻘﺎوﻻت‬
‫اﺑﻮ رواش ‪NSGB‬‬ ‫اﻟﺪار‬
‫اﻣﻮال اﻟﻌﺮﺑﯿﺔ اﻟﻘﺮﯾﺔ اﻟﺬﻛﯿﺔ‬ ‫اﯾﺒﻚ‬
‫ﺑﻨﻚ ﻣﺼﺮ اﯾﺮان اﻟﻘﺎھﺮة اﻟﺠﺪﯾﺪة‬ ‫ﻣﺼﺮ ﻛﻮﻧﺘﺮاﻛﻮ‬
‫اﻟﺒﻨﻚ اﻟﻤﺮﻛﺰى‬ ‫ھﻮﻟﺰ ﺗﻚ‬
‫ﻛﺮﯾﺪى اﺟﺮﯾﻜﻮل اﻟﻜﺮﺑﺔ‬ ‫اﻟﺪار‬
‫اﻟﺒﻨﻚ اﻻھﻠﻰ‪-‬اﻟﺠﺎﻣﻌﺔ‬ ‫اﻻﻓﻖ‬
‫ﺑﻨﻚ ﻛﺮﯾﺪى اﺟﺮﯾﻜﻮل اﻟﺪﻗﻰ‬ ‫طﯿﺒﺔ ﻟﻠﻤﻘﺎوﻻت‬
‫ﻛﺮﯾﺪى اﺟﺮﯾﻜﻮل ھﻠﯿﻮﺑﻠﯿﺲ‬ ‫اﻟﻨﺪى‬
‫اﻟﻮﺣﺪة اﻟﻤﺼﺮﻓﯿﺔ اﺑﻮ ﻗﺮﻗﺎص اﻟﻤﻨﯿﺎ‬ ‫اﻟﺴﺒﻌﺎوى‬

‫ﺑﻨﻚ ﻗﻨﺎة اﻟﺴﻮﯾﺲ طﻨﻄﺎ‬ ‫ﻣﺤﻔﻮظ‬


‫اﻛﺘﻮﺑﺮ ‪cib‬‬ ‫ﻣﺤﻔﻮظ‬
‫ﺑﻨﻚ ﻋﻮدة ﻣﺼﺪق‬ ‫ﺗﻮ واﯾﺮز‬
‫اﻟﺒﻨﻚ اﻻھﻠﻰ اﻟﺸﮭﺪاء‬ ‫اﻟﯿﻜﺲ اﻧﺘﺮﻧﺎﺷﯿﻮﻧﺎل‬

‫ﻓﻲ ﺣﺎﻟﺔ اﻻﺳﺘﻔﺴﺎر ﻋﻦ أي ﻣﻌﻠﻮﻣﺎت ﻧﺮﺟﻮا ﺳﺮﻋﺔ اﻻﺗﺼﺎل ﺑﻨﺎ ‪ ،‬وﻧﺄﻣﻞ اﻟﺘﻌﺎون ﻣﻌﻜﻢ ﻓﻲ ﻣﺸﺎرﻳﻌﻜﻢ‬
‫اﻟﻘـﺎدﻣﺔ‬

‫ادارة اﻟﻤﺒﻴﻌﺎت واﻟﺘﺴﻮﻳﻖ‬

‫ﻣﺤﻤﺪ زﻛﺮﻳﺎ ﻣﺤﻤﺪ‬


 Previous approval

You might also like