Cable Fault Locator
Cable Fault Locator
GENERAL SPECIFICATIONS
Typical Example :
An illustration of the method of fault location in case of two phase to earth fault and open circuit faults using Model-2000A is given below. Similar method with
minor alterations in cable connection has to be adopted for locating other types of faults.
Example / Two phase to earth fault
END 1 Connection diagram END 2
RED GOOD
&
V1 I1
POTENTIAL CURRENT PHASE
OUTPUT CLIP LOOP
INPUT CLIP YELLOW
V2/CX FAULTY
I2
POTENTIAL
INPUT CLIP & CURRENT
OUTPUT CLIP BLUE FAULTY
PHASE
V12/CX FAULTY
POTENTIAL ARMOUR
INPUT CLIP
COMMON
*Technical Specifications & Appearance are subject to change without prior notice
Procedure in Brief :
l Connect phases of the faulty cable to the equipment as per the connection diagram. Loop at the far end as shown.
l Switch ON the equipment. Null the digital meter reading to indicate zero. Set V1/V2 selector switch to V1 position.
l Press push button marked Push to read and note down the reading on the digital meter. Denote it as V1.
l Set V1/V2 switch to V2 position. Press the Push Button. Note down the reading on the digital meter. Denote it as V2.
l Substitute V1 & V2 readings in the formula given below to compute the distance to fault.
2V1
Distance to fault from testing end = (V1+V2) x length of the cable from end 1 to end 2 in mts/feet.
l Repeat the test from End 2 to cross check the results computed
Connection diagram
END 1 END 2
RED
V2/CX
POTENTIAL GOOD PHASE
INPUT CLIP YELLOW
OPEN FAULT
BLUE
V12/CX
POTENTIAL
INPUT CLIP
COMMON ARMOUR
Procedure in Brief :
l Connect the faulty phase and sheath/armouring of the faulty cable to the equipment as shown in the connection diagram
l Set the earth / open switch to Open position
l Switch ON the equipment
l Press the push button marked Push to Read, Note down the reading on the digital meter. Denote it as Cx
l Now connect the output lead clip V2 to a good phase of the same cable
l Press the push button and note down the digital meter reading, Denote is as C
l Substitute the readings Cx and C in the formula given below to compute the distance to fault
Cx
Distance to fault from testing End1 = C X length of the cable from End1 and End2 in mts/feet
l Repeat the experiment from End2 to cross check the results obtained.
TECHNICAL SPECIFICATIONS
Test Range : 50 mts to 1000mts
Display : 3½ Digit large LCD Display
Potential Distribution : By LCD DPM in three ranges (0.2V,
Measurement (V1 & V2 mode) 2V, 20V)
Current Measurement : By moving coil analog meter
(0-5A, FSD)
Input Impedance : In three ranges (1M Ohm, 10M Ohm
& 50M Ohm)
Capacitance Measurement : Direct in four ranges (1nF, 10nF,
100nF & 1000nF)
Nulling Controls : By Coarse & Fine Controls
Standard Accessories : i) Batteries: 6V/10AH
Rechargeable battery - 1 No.
12V/3.8 AH Rechargeable
battery - 2 Nos.
ii) Fault simulating board & leads
iii) Leatherite carrying case
*Technical Specifications & Appearance are subject to change without prior notice