Russelectric - Model #RMTD Wiring Diagram

This specification sheet outlines the details for RUSSELECTRIC Model RMT2603CE automatic transfer switches, rated at 260 amperes for use on a 480 volt AC service. The document includes customer information, item quantities, and a comprehensive accessory list detailing various functionalities and programmable features. Additional references for installation and wiring diagrams are provided throughout the document.

Uploaded by

sfb5nwz52h
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views9 pages

Russelectric - Model #RMTD Wiring Diagram

This specification sheet outlines the details for RUSSELECTRIC Model RMT2603CE automatic transfer switches, rated at 260 amperes for use on a 480 volt AC service. The document includes customer information, item quantities, and a comprehensive accessory list detailing various functionalities and programmable features. Additional references for installation and wiring diagrams are provided throughout the document.

Uploaded by

sfb5nwz52h
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

SPECIFICATION SHEET

RUSSELECTRIC JOB NO. 27597

NAME OF JOB CARPENTERS TRUST


LOS ANGELES, CALIFORNIA

CUSTOMER WESCO
ANAHEIM, CALIFORNIA

CUSTOMER P.O. NUMBER DS6733329605

ITEM NUMBER QUANTITY MARKING


1 2

DESCRIPTION

RUSSELECTRIC MODEL RMT2603CE, MICROPROCESSOR BASED, AUTOMATIC TRANSFER SWITCHES,


RATED 260 AMPERES, TO BE USED ON A 480 VOLT AC 3-PHASE, 3-WIRE, 60HZ SERVICE, IN A
NEMA 1 WALL MOUNTED ENCLOSURE, WITH ACCESSORIES AS ITEMIZED ON ACCESSORY LIST.

FOR GENERAL NOTES AND LEGEND REFER TO EDS-190 REV 0

FOR SCHEMATIC DIAGRAM REFER TO SHEET 2

FOR RELAY PLATE WIRING DIAGRAM REFER TO SHEET 3

FOR SWITCH BASE WIRING DIAGRAM REFER TO SHEET 4

FOR DOOR WIRING DIAGRAM REFER TO SHEET 5

FOR ACCESSORY LIST REFER TO SHEETS 6 & 7

OTHER APPLICABLE DRAWINGS

ENCLOSURE: 27597-1 SHEET 8

INSTALLATION:

REV. NO. DESCRIPTION DATE BY

DWG. NO. 27597-1


APPROVED DATE REV
07/28/00 0 SHEET 1 OF 8
EDS-190

GENERAL NOTES - SCHEMATIC DIAGRAMS

BOX SELECTED INDICATES TYPE OF MICROPROCESSOR PROVIDED

x ATSA - AUTOMATIC MICROPROCESSOR.

¨ ATSM - MANUAL MICROPROCESSOR.

¨ ATSP - PREFERRED SOURCE MICROPROCESSOR.

¨ ATSC - CLOSED TRANSITION MICROPROCESSOR.

1. ALL CONTACTS SHOWN WITH NORMAL AND EMERGENCY


POWER DE-ENERGIZED.

2. DOTTED LINES INDICATE EXTERNAL CONNECTIONS


FROM THE ATSCS. (AUTOMATIC TRANSFER SWITCH CONTROL SYSTEM)

LEGEND

CONTACT ON NORMAL SHAFT CLOSED WHEN SWITCH


IS IN NORMAL POSITION -- OPEN WHEN SWITCH
IS IN EMERGENCY POSITION.

CONTACT ON NORMAL SHAFT OPEN WHEN SWITCH


IS IN NORMAL POSITION -- CLOSED WHEN SWITCH
IS IN EMERGENCY POSITION.

CONTACT ON EMERGENCY SHAFT CLOSED WHEN SWITCH


IS IN NORMAL POSITION -- OPEN WHEN SWITCH
IS IN EMERGENCY POSITION.

CONTACT ON EMERGENCY SHAFT OPEN WHEN SWITCH


IS IN NORMAL POSITION -- CLOSED WHEN SWITCH
IS IN EMERGENCY POSITION.

DATE REV ATS SCHEMATIC DIAGRAM


06/19/95 0 GENERAL NOTES AND LEGEND PAGE 1 OF 1

RUSSELECTRIC INC. HINGHAM, MA 02043


ACCESSORY LIST

ACC. NO. FUNCTION DEVICE

(INTERNAL): Internal feature of the microprocessor. ATSCS


(EXTERNAL): Separate feature from the microprocessor. ATSCS

STD UNDER VOLTAGE SENSING OF THE NORMAL SOURCE TO PICK UP AT 90%


AND DROP OUT AT 80%, UNDER FREQUENCY SENSING TO PICK UP AT 90%
AND DROP OUT AT 70%. (INTERNAL)

STD UNDER VOLTAGE SENSING OF THE EMERGENCY SOURCE TO PICK UP AT 90%


AND DROP OUT AT 80%, UNDER FREQUENCY SENSING TO PICK UP AT 90%
AND DROP OUT AT 70%. (INTERNAL)

1d TIME DELAY TO OVERRIDE MOMENTARY NORMAL SOURCE POWER OUTAGES TD1


TO DELAY ENGINE START SIGNAL AND TRANSFER SWITCH OPERATION.
PROGRAMMABLE 0-9999 SECONDS, FACTORY SET AT 3 SECONDS.
A TIME SETTING GREATER THAN 6 SECONDS REQUIRES AN EXTERNAL
24 VOLT DC, 1 AMP POWER SUPPLY. (INTERNAL)

2a TIME DELAY ON RETRANSFER TO NORMAL. PROGRAMMABLE 0-9999 TD2


SECONDS, FACTORY SET AT 300 SECONDS. (INTERNAL)

2e ENGINE OVERRUN TO PROVIDE UNLOADED ENGINE OPERATION AFTER AUT


RETRANSFER TO NORMAL. PROGRAMMABLE 0-9999 SECONDS, FACTORY
SET AT 300 SECONDS. (INTERNAL)

4b PROGRAMMABLE VOLTAGE AND FREQUENCY SENSING OF NORMAL SOURCE.


OVER VOLTAGE SENSING TO PICK UP AT 120% AND DROP OUT AT 110%
OVER FREQUENCY SENSING TO PICK UP AT 120% AND DROP OUT AT 110%
DIFFERENTIAL: 20%, PHASE SEQUENCE: ABC OR CBA (INTERNAL)

5a PROGRAMMABLE LOAD TEST FUNCTION TO SIMULATE NORMAL POWER ACC.5a


FAILURE. KEYPAD INITIATED. (INTERNAL)

6b PROGRAMMABLE FUNCTION TO BYPASS (TD2) TIME DELAY ON RETRANSFER ACC.6b


TO NORMAL, KEYPAD INITIATED. (INTERNAL)

7 CONTACT TO CLOSE ON FAILURE OF NORMAL SOURCE TO INITIATE ACC.7


ENGINE STARTING OR OTHER CUSTOMER FUNCTIONS. (INTERNAL)

8 CONTACT TO OPEN ON FAILURE OF NORMAL SOURCE FOR CUSTOMER ACC.8


FUNCTIONS. (INTERNAL)

9a GREEN LED TO INDICATE SWITCH IN NORMAL POSITION. (INTERNAL) ACC.9a

9b RED LED TO INDICATE SWITCH IN EMERGENCY POSITION. (INTERNAL) ACC.9b

DWG. NO. 27597-1


APPROVED DATE REV
07/28/00 0 SHEET 6 OF 8
ACC. NO. FUNCTION DEVICE

11c PLANT EXERCISER WITH (10) 7 DAY PROGRAMMABLE EVENTS FOR ANY ACC.11c
DAY OF THE WEEK (Mon. Tues. ...etc), AND (24) PROGRAMMABLE
CALENDAR EVENTS FOR ANY MONTH (03/01, 04/15 ...etc)
TO AUTOMATICALLY EXERCISE THE GENERATING PLANT. PROGRAMMABLE
IN 1 MINUTE MINIMUM INCREMENTS. (INTERNAL)
WITH
PROGRAMMABLE FUNCTION TO SELECT EITHER "NO LOAD" (SWITCH WILL
NOT TRANSFER) OR "LOAD" (SWITCH WILL TRANSFER) EXERCISE PERIOD.
KEYPAD INITIATED. (INTERNAL)

14a AUXILIARY CONTACT CLOSED IN NORMAL POSITION. QUANTITY OF 1. ACC.14a


WIRED TO TERMINAL STRIP TB3 ON RELAY PLATE. (EXTERNAL)

14b AUXILIARY CONTACT CLOSED IN EMERGENCY POSITION. QUANTITY OF 1. ACC.14b


WIRED TO TERMINAL STRIP TB3 ON RELAY PLATE. (EXTERNAL)

19bd DIGITAL VOLTMETER. KEYPAD INITIATED. THREE PHASE TYPE TO READ VM/FM
PHASE-TO-PHASE VOLTAGE & FREQUENCY ON THE NORMAL AND EMERGENCY
SOURCE. 1% ACCURACY. (INTERNAL)

23c TIME DELAY FUNCTION TO PROVIDE (2) FORM "C" CONTACTS THAT TDBT
CHANGE STATE SIMULTANEOUSLY BEFORE TRANSFER TO EITHER SOURCE, TDMI
PROGRAMMABLE 0-9999 SECONDS, FACTORY SET AT 5 SECONDS. THEN
RE-SET AFTER THE A.T.S. HAS COMPLETED TRANSFER, PROGRAMMABLE
0-9999 SECONDS FACTORY SET AT 5 SECONDS. (INTERNAL)

26 PROGRAMMABLE VOLTAGE AND FREQUENCY SENSING OF EMERGENCY SOURCE.


OVER VOLTAGE SENSING TO PICK UP AT 120% AND DROP OUT AT 110%
OVER FREQUENCY SENSING TO PICK UP AT 120% AND DROP OUT AT 110%
DIFFERENTIAL: 20%, PHASE SEQUENCE: ABC OR CBA (INTERNAL)

DWG. NO. 27597-1


APPROVED DATE REV
07/28/00 0 SHEET 7 OF 8