PIS301
PIS301
2022.6_Ver1.0
CONTENT
1 Brief introduction............................................................................................. 3
1.1 Function introduction ............................................................................................... 3
1.2 Brief uses introduction ............................................................................................. 4
2 Product appearance ........................................................................................ 5
2.1 Product appearance drawing .................................................................................... 5
2.2 Product port introduction ......................................................................................... 6
2.3 Introduction of product signal light ......................................................................... 6
3 UPSViewer setting ........................................................................................... 7
3.1 Hardware installation ............................................................................................... 7
3.1.1 UPSViewer card slot installation ...................................................................... 7
3.1.2 UPSViewer installation..................................................................................... 7
3.1.3 Temperature & humidity sensor installation .................................................... 8
3.1.4 Water leakage sensor installation ..................................................................... 9
3.1.5 SMS alarm installation...................................................................................... 9
3.2 Software installation .............................................................................................. 10
3.3 UPSViewer using step ........................................................................................... 10
3.4 IPsearch function introduction ............................................................................... 13
3.4.1 IPsearch instruction......................................................................................... 13
3.4.2 Use IPsearch software to assign dynamic IP address to UPSViewer ............. 13
3.4.3 Use IPsearch software to manually set a static IP address for UPSViewer ... 14
3.4.4 Use IPSearch to open UPSViewer webpage .................................................. 14
3.5 Check computer network information ................................................................... 15
4 UPSViewer webpage introduction ................................................................ 17
4.1 UPSViewer webpage functions ............................................................................. 17
4.2 Open UPSViewer webpage ................................................................................... 17
4.3 Introduction to user navigation with different permissions ................................... 17
4.4 System overview .................................................................................................... 18
4.5 UPS ........................................................................................................................ 23
4.5.1 Current Status.................................................................................................. 23
4.5.2 Device Information ......................................................................................... 25
4.6 Expansion Equipment (this navigation bar will only be displayed when the
expansion device is connected) ........................................................................... 26
4.6.1 Automatically search and add devices (search for devices) ........................... 26
4.6.2 Manually add device ....................................................................................... 29
4.6.3 Delete expansion device ................................................................................. 33
4.7 Alarm Management ............................................................................................... 33
4.7.1 Current Alarms ............................................................................................... 33
4.7.2 History Record ............................................................................................... 34
4.7.3 Operation Log ................................................................................................ 35
4.8 Data Management .................................................................................................. 35
4.8.1 History Data ................................................................................................... 35
4.8.2 Data Chart ...................................................................................................... 35
Page I
4.9 Settings (administrator user specific permissions) ................................................ 36
4.9.1 Monitoring Settings ........................................................................................ 36
4.9.2 COM Settings ................................................................................................. 36
4.9.3 Device management ....................................................................................... 37
4.9.4 SNMP Settings ................................................................................................ 40
4.9.5 TCP/IP............................................................................................................. 45
4.9.6 Alarm Settings ................................................................................................ 46
4.9.7 Email Settings ................................................................................................. 46
4.9.8 SMS Settings................................................................................................... 49
4.9.9 Time Settings .................................................................................................. 52
4.9.10 Language Settings ......................................................................................... 53
4.9.11 User Management ......................................................................................... 54
4.9.12 Config Settings ............................................................................................. 55
4.9.13 Factory Reset ................................................................................................ 56
5 Support (Help) ............................................................................................... 57
5.1 Hide & Change Logo ......................................................................................... 57
5.1.1 Hide Logo ....................................................................................................... 57
5.1.2 Change Logo ................................................................................................... 59
Page II
Brief introduction
1 Brief introduction
Page 3
Brief introduction
Page 4
Product appearance
2 Product appearance
Figure-1
Figure-2
Figure 1 is the front of UPSViewer, figure 2 is the side profile of
UPSViewer.
In figure 1:
① NETWORK: RJ45 network interface;
② COMM: Expanded COMM port;
③ Signal light.
Page 5
Product appearance
Port Function
Page 6
UPSViewer setting
3 UPSViewer setting
② Push the UPSViewer to the bottom along the track inside the slot;
Page 7
UPSViewer setting
Page 8
UPSViewer setting
Connect the RS485 port of the flood sensor to the COMM port of the
UPSViewer with a network cable (or the COMM port of other devices
that have been connected to the UPSViewer) to check whether the
liquid crystal interface of the flood sensor is lit up and whether there is
any information display. If so, the connection is successful.
Temperature & humidity sensor and Water leakage sensor
installation:
Page 9
UPSViewer setting
Omit.
Page 10
UPSViewer setting
Page 11
UPSViewer setting
If you do not know how to check the Modbus address, port protocol, and
Modbus mode of the UPS product, you can refer to the UPS manual or consult
the UPS vendor, or refer to 4.9.3 Device Management. After setting, click
Page 12
UPSViewer setting
"OK" button and then click "Apply" button. Refresh the interface and check
the alarm event. If there is no "communication failure" alarm event, the
communication is normal.
IPsearch: is a search tool that can quickly find information about the online
UPSViewer that is already online on the LAN.
3.4.1 IPsearch instruction
IPsearch Interface
IPsearch consists of two regions: UPSViewer device information
display area, operation area. (The list refreshes automatically
every 15s.) When the user opens the IPsearch tool, it will
automatically search the UPSViewer information that is currently
online on the LAN, and retrieves the device type, MAC address, IP
address, software version, hardware version, and IP address type
(DHCP, Static IP).
① Operating area;
② Online device list;
③ Equipment information.
When there are multiple devices in the list, the first one is selected as the
default device by default. When the user clicks on any device in the list, the
device information box will display the corresponding device type, software
version, hardware version, MAC address, IP type (manually set static IP and
DHCP dynamically assign IP).
3.4.2 Use IPsearch software to assign dynamic IP address to
UPSViewer
The steps are as follows:
Page 13
UPSViewer setting
Note: This DHCP service can only successfully allocate IP when there is a
DHCP server.
Page 14
UPSViewer setting
UPSViewer are in the same local area network, otherwise it will fail to open
the webpage.
④ Go to the webpage.
Before logging in, make sure that UPSViewer and the computer are on
the same network. When the UPSViewer IP and the computer IP are not in the
Page 15
UPSViewer setting
same network, you can use the following methods to set or view. For
Windows10 system, the process of viewing IP information and setting IP is as
follows: (same for other Windows operating systems)
Page 16
UPSViewer webpage introduction
Before opening the management webpage, make sure that your computer
and UPSViewer are connected normally and in the same network.
Page 17
UPSViewer webpage introduction
Running Status
There are 4 display meters, which display the current output voltage, load
rate, battery voltage and battery current respectively. It is convenient for users
to quickly obtain current UPS data.
The meaning of the color segment of "load rate running status meter":
Signal light Status and meaning
Color Meaning
Page 18
UPSViewer webpage introduction
Normal mode
Battery mode
Bypass mode
Page 19
UPSViewer webpage introduction
Alarm Overview
The alarm information is divided into levels: no alarm (blue), general
alarm (yellow), serious alarm (red). The alarm overview is displayed as a
percentage in a circular chart.
The user can click "General Alarm" "Serious Alarm" to determine the
chart display form.
The default mixed display of "General Alarm" and "Serious Alarm":
Page 20
UPSViewer webpage introduction
Page 21
UPSViewer webpage introduction
Battery information
Display the remaining battery time and battery capacity. (The battery
information will only be displayed when the UPS battery module is
connected).
Output Voltage
The abscissa is the time axis, and the time interval can be adjusted by
pulling the slider. When the output voltage is abnormal or sudden, it is
convenient for users to quickly lock the abnormal voltage time point.
Load Percentage
Page 22
UPSViewer webpage introduction
When the UPS product is three-phase type, there will be three-phase data
display of phase A、phase B and phase C, which can be set to display data
items in the chart through optional settings.
4.5 UPS
Main Input、Bypass、Output:
These three areas all show: voltage, current, frequency, power factor data
in different states.
Load:
Page 23
UPSViewer webpage introduction
The following picture shows the monitoring UPS module (other module
machines, the same model), display module data
Page 24
UPSViewer webpage introduction
Page 25
UPSViewer webpage introduction
Refresh the interface, you can see the alias and remark information.
Note: This setting function will not take effect after UPS communication
fails.
【Expansion Equipment】
Expansion equipment: equipment other than UPS.
Page 26
UPSViewer webpage introduction
Page 27
UPSViewer webpage introduction
At this time, the expansion device has been added successfully, and the
refresh interface will display the expansion device under the【Expansion
Equipment】navigation bar.
Page 28
UPSViewer webpage introduction
②【Setting】→【Device Management】→【Add】
Page 29
UPSViewer webpage introduction
Page 30
UPSViewer webpage introduction
&
Page 31
UPSViewer webpage introduction
②【Setting】→【Device Management】→【Add】
&
Page 32
UPSViewer webpage introduction
Page 33
UPSViewer webpage introduction
All alarm information will be displayed here in the form of a list, and the
data information includes device type, event, date and time. General alarms:
filter to display general alarm information, and severe alarms to filter to
display severe alarm information.
4.7.2 History Record
【Alarm Management】→【History Record】
History query:
① Device type:
In the drop-down list of device type, you can select (all
devices/UPS/system) for data filtering.
② Event level:
Set up (all levels, serious alarms, general alarms, common events)
options.
③ Query by time:
Quick query button (last day, last week, and last month) is set, and users
can also customize the start time and end time. After selecting the query
conditions, click the【query】button.
④ Query information display.
Note: When the storage space of UPSViewer is less than or equal to
10MB, a serious warning of "Insufficient memory space" will be issued. When
the storage space of UPSViewer is less than or equal to 5MB, historical data
will not be stored. Please clean up the data space and delete unnecessary
historical data.
Page 34
UPSViewer webpage introduction
Page 35
UPSViewer webpage introduction
Page 36
UPSViewer webpage introduction
【Settings】→【COM Settings】
This is the serial port communication setting page, which provides users
with settings for the baud rate, stop bit, and verification type of the extended
serial port and UPS communication.
Device management(UPS)
UPS device management, provide users with the modification operation
of UPS Modbus address UPS communication protocol Modbus mode. UPS
here is the default device. As long as the UPSViewer is powered on and works
normally, it will display by default without the need for users to add devices.
Modbus Address: The web page is set to ‘1’ by default, but here must
enter the Modbus address for the UPS product.
Now support: Invt, Megtec31, Megtec33 communication protocols. As
for ‘Invt’ protocol (small capacity UPS 1-3KVA and 6~ 20 KVA currently
does not apply)
Modbus mode is divided into: RTU, ASCII.
Page 37
UPSViewer webpage introduction
Page 38
UPSViewer webpage introduction
3
2
4
5
6
7
1
【Setting】→【COMM.】
① Read the "Device Address", fill in the Modbus address column of the
UPSViewer webpage, and select "Modbus" in the ‘R232 port protocol
selection’ ;
② ‘Baud rate’ selection: "9600". (Must be consistent with the
UPSViewer webpage);
③ ‘Modbus Mode’ selection: "ASCII". (Must be consistent with the
UPSViewer webpage);
④ ‘Modbus Parity’ selection: "None". (Must be consistent with the
management page);
⑤ Select to confirm the settings.
How to connect the Single-phase UPS?
Page 39
UPSViewer webpage introduction
Page 40
UPSViewer webpage introduction
Page 41
UPSViewer webpage introduction
【Access Control】
IP Address:
The user can designate ten hosts with specific IP addresses as the
administrator, and just enter a legal IP address. If the administrator IP address
is not set, any IP can be managed.
Version:
Set the SNMP version (All / SNMP V1&SNMP V2 / SNMP V3) used
for communication with the administrator host. When you choose to use all
and SNMP V3 versions, you need to set the user name / password /
authentication / encryption information.
Page 42
UPSViewer webpage introduction
Community:
The administrator host and the UPSViewer web page need to set the
same community string, otherwise communication will not be possible. The
UPSViewer web community string is defaulted to public. The administrator
host and the UPSViewer web page need to set the same community string,
otherwise communication will not be possible. The UPSViewer web
community string is defaulted to public.
Permission:
Set the administrator's authority (no authority / read only / read & write).
Note:
Provide description information for easy query and management.
【Trap Notification】
IP Address:
Ten people can be set to receive Trap notifications using IP addresses.
Accept:
Use the drop-down list to select which SNMP version Trap or Inform to
receive. When selecting SNMPv3 Trap or Inform, please set the account
password and authentication encryption information (SNMPv1 Trap /
SNMPv2 Trap / SNMPv2 Inform / SNMPv3 Trap / SNMPv3 Inform).
Page 43
UPSViewer webpage introduction
Community:
Trap recipients and UPSViewer web pages need to set the same string to
communicate. The default is public.
Note:
This field can provide management staff to mark the use of related
content.
SNMP notification request:
Open the "MIB Browser" software and load the .MIB file
Page 44
UPSViewer webpage introduction
Page 45
UPSViewer webpage introduction
The following figure shows the system alarm setting interface, which
provides events:
1. The remaining memory space is insufficient;
2. The data storage fails. The alarm levels are divided into: ordinary
events, general alarms, and severe alarms.
This is the UPS alarm setting. Users can set the alarm level according to
their needs.
4.9.7 Email Settings
Page 46
UPSViewer webpage introduction
【Setting】→【Email Settings】
UPSViewer can send online UPS data and events to the designated
mailbox through email notification.
Page 47
UPSViewer webpage introduction
&
④ Check the events that need to trigger the sending of emails. After
checking, you must click the in the upper right corner to close.
Page 48
UPSViewer webpage introduction
To sum up everything that has been stated so far is that users can select
all or customize to add alarm events.
4.9.8 SMS Settings
【Setting】→【SMS Settings】
UPSViewer can add an extended device SMS alarm. When an alarm
event occurs on the online UPS, the alarm information will be sent to the
designated mobile phone number by SMS in time.
Page 49
UPSViewer webpage introduction
Page 50
UPSViewer webpage introduction
&
Page 51
UPSViewer webpage introduction
The user needs to calibrate the time when entering the management
webpage for the first time, and the dialog box [Please check the system time]
will pop up, and click the [OK] button.
Page 52
UPSViewer webpage introduction
Click [Edit], enter the time server address or IP, click [Add], the list
below appears, and the value is now filled in, it means that the time server
address is successfully added.
Select the previously filled IP in the time server column, select the time
zone and automatic synchronization period, and click "Set".
When the middle area of the automatic synchronization time column
displays the green word "Synchronization successful", it means that the time
server can be connected.
Note: This function can be used only when the LAN can access the
external network and the server address will not be intercepted.
【Now】
In [Now], you can use [Set Value] to update the time immediately, and
you can also [Synch Local Date Time].
Use the [Update Now] button to change the date and time. Enter the
date and time in the corresponding time input box of the setting value,
and click [Update Now]
Use [Sync local date time]. Set the local time to the UPSViewer time.
If the update or synchronization is successful, there will be a "Update
Successful" Prompt information.
4.9.10 Language Settings
【Setting】→【Language Settings】
This is the webpage language setting page. The UPSViewer webpage
will automatically adjust according to the user's operating system language.
Currently, it supports "Simplified Chinese" and "English" languages, and
users can also set it manually according to their own habits.
Page 53
UPSViewer webpage introduction
Page 54
UPSViewer webpage introduction
Note: When adding a user, the user name and password are required.
Username: It can only consist of English letters, underscores, and Chinese
characters. When the "admin" administrator user modifies the passwords of
other users, there is no need to confirm the user's password and can be
modified directly.
Special note: When the browser is below IE9 or when the browser such
as 360 has no response when clicking to select the file, please download the
Adobe Flash Player plug-in from the Internet and refresh the page after
installation.
Page 55
UPSViewer webpage introduction
① Log Clear:
Clear the history information.
② Historical data Clear:
Clear historical data.
③ Factory Reset
Note: After restoring the factory settings, all data information and setting
information will be cleared, and the UPSViewer system will restart.
Page 56
Support (Help)
5 Support (Help)
【Support】→【System Upgrade】
[System upgrade] Provide UPSViewer system upgrade port.
Note: After the upgrade, the UPSViewer system will restart and you need
to log in to the web page again.
5.1 Hide & Change Logo
【Support】→【System Upgrade】
5.1.1 Hide Logo
① Use IPsearch to find the SNMP card
Page 57
Support (Help)
② Launch Web
Chose and Click “Launch Web”
Page 58
Support (Help)
Page 59
Support (Help)
Page 60
Support (Help)
Page 61
Support (Help)
Page 62