Kidat Short
Kidat Short
COLLEGE
BUILDING ELECTRICAL
INSTALLATION LEVEL III
Crossed Wires
Limit Switch
(Connected)
Push Button
Transformer Switch
(Normally Open)
Push Button
Fuse Switch
(Normally Closed)
Double Pole
Terminal Block Pushbutton
Switch
Mushroom
Pushbutton Overload Relay
Switch
Voltage Contactor
Transformer (Normally Open)
Contactor Three Phase
(Normally Closed) Winding (Star)
1. A Magnetic Starter connected across the line controls the electric motor
with START – STOP control circuit.
A control circuit is designed to prevent the unexpected starting ofmotors, which could
result in injury to machine operators or damage to the driven machinery. Figure 3–1 is
the schematic diagram of typical magnetic starter control circuit. The starter is energized
by pressing the Start button. An auxiliary holding circuit (HC) contact on the starter
forms a parallel circuit around the Start button contacts, holding the starter in after the
button is released. If a power failure occurs, the starter will drop out and will open the
holding circuit contact. When power is restored, the Start button must be operated
again before the motor will restart.
a. Control Circuit
L1 START L2
STOP COIL
1 2 3 4 96 95
A1 A2
OL
13 14
HC
b. Power Circuit
L1 L2 L3
L1 L1
c. Complete Circuit
L1 L2 L3
L1 L1
STOP
M M M
OL HC
COIL
START
Figure 3-3. Complete Circuit Diagram
Figure 3–3 shows the electrical relationship of the Control Circuitcontactor, power
circuit, and overload relay. The contactor and the overload relay have additional
contacts, referred to as auxiliary contacts, for use in the control circuit. In this circuit a
normally closed “OL” contact has been placed in series with the “M” contactor coil and
L2. A normally open “HC” has been placed in parallel with the “Start” pushbutton.
2. A Magnetic Starter connected across the line controls the electric motor in
two locations.
a. Control Circuit
L1 START L2
COIL
STOP STOP
2 1 2 3 4 96 95
1
A1 A2
START OL
3 4
Figure 3-4. Two location
Control circuit schematic
diagram
13 14
HC
b. Power Circuit
L1 L2 L3
L1 L1
L1 L2 L3
L1
STOP STOP
L1
START START HC
OL
COIL
Figure 3-6. Schematic Diagram of a magnetic starter connected across the line
controlling electric motor in Two Location.
The circuit in Figure 4, 5 and 6 is similar to start – stop motor control. The HC is
connected in parallel with the two START push button switch. The two start push button
switch connected in parallel so that the electric motor can be controlled either of the two
start push button switch. The two STOP push button witch is connected in series so that
either of this two open the electric motor will stop. This connection the electric motor can
be controlled in two location depending upon how the start stop push button switch
being installed.
3. A Magnetic Starter connected across the line controls the electric motor in
FORWARD – REVERSE connection.
a. Control Circuit
96
1 2 3 4 62
95
61 A1 A2
13 14
3 4
61 62 A1 A2
13 14
When the “Forward” pushbutton is actuated, M1 will energize, closing the normally-open
auxiliary contact in parallel with that switch. When the push button is released, the
closed M1 auxiliary contact will maintain current to the coil of M 1, thus latching the
“Forward” circuit in the “ON” state. The same sort of thing will happen when the
“Reverse” pushbutton is pressed. These parallel auxiliary contacts are sometimes
referred to as seal-in contacts, the word “seal” meaning essentially the same thing as
the word latch.
However, this creates a new problem: how to stop the motor.As the circuit exists right
now, the motor will run either forward or reverse once the corresponding pushbutton
switch is pressed, and will continue to run as long as there is power. To stop either
circuit (forward or reverse), we require some means for the operator to interrupt power
to the motor contactors. We’ll call this new switch, STOP:
Now, if either forward or reverse circuits are latched, they may be “unlatched” by
momentarily pressing the “Stop” pushbutton, which will open either forward or reverse
circuit, de-energizing the energized contactor, and returning the seal-in contact to its
normal (open) state. The “Stop” switch, having normally-closed contacts, will conduct
power to either forward or reverse circuits when released.
b. Power Circuit
L1 L2 L3
L1 L1
FORWARD REVERSE
a. Control Circuit
Figure 3-11. WYE-DELTA Control Circuit
a. Power Circuit
L1 L2 L3
L1 L1
WYE DELTA
L1 L1
3 5 3 5 1 3 5
1 1
2 4 6 2 4 6 2 4 6
OL
T1 T5
T4
T2
T3 T6
A normally close auxiliary contact from both star and delta contactors are also placed
opposite of both star and delta contactor coils, these interlock contacts serves as safety
switches to prevent simultaneous activation of both star and delta contactor coils, so
that one cannot be activated without the other deactivated first. Thus, the delta
contactor coil cannot be active when the star contactor coil is active, and similarly, the
star contactor coil cannot also be active while the delta contactor coil is active.
The control circuit above also provides two interrupting contacts to shutdown the motor.
The STOP push button switch is a manual operator access switch intended for shutting
OFF the circuit to stop the motor when necessary. The thermal overload contact is a
protective device which automatically opens the circuit in case when motor overload
current is detected by the thermal overload relay, this is to prevent burning of the motor
in case of excessive load beyond the rated capacity of the motor is detected by the
thermal overload relay.
I. Diagram
a. Control Circuit
b. Lamp Indicator
98 97
53 54
c. Power Circuit
L1 L2 L3
L1 L1