Design of Decentralized Fuzzy Logic Load Frequency
Design of Decentralized Fuzzy Logic Load Frequency
net/publication/266459484
CITATIONS READS
22 10,671
2 authors:
All content following this page was uploaded by Khaled El-Metwally on 27 April 2015.
K.A. El-Metwally
Department of Electrical Engineering, Cairo University, Cairo, Egypt
Email: [email protected]
Abstract— This paper presents a novel approach for designing a maintain the interchange power between control areas at
decentralized controller for load frequency control of scheduled values by adjusting the MW output power of
interconnected power areas. The proposed fuzzy logic load the selected generators so as to accommodate changing in
frequency controller (FLFC) has been designed to improve the
load demands [4].
dynamic performance of the frequency and tie line power under
a sudden load change in the power areas. The effect of
generation rate constraint (GRC) for both areas has been Many investigations in the area of LFC problem have
considered in the controller design. The proposed FLFC been reported and a number of control strategies have
consists of two internal fuzzy logic controllers namely, the PD- been employed in the design of load frequency (LF)
like fuzzy logic controller and the PI-like fuzzy logic controller. controller in order to achieve better dynamic performance
The FLFC has been co-coordinated with the conventional [6-8, 9-15]. In recent years, fuzzy system applications
integral controller. Time-domain simulations using have received increasing attention in power system
MATALB/SIMULINK program has been performed to operation and control [16, 17, 19, 24]. Fuzzy logic based
demonstrate the effectiveness of the proposed FLFC. The
controllers have been suggested as an appropriate choice
simulation results show that the proposed FLFC can provide
good damping and reduce the overshoot even in the presence of
to control non-linear system [17,18, 20] and are being
the GRC. investigated as an alternative to conventional control. The
basic feature of fuzzy logic controllers (FLCs) is that the
control strategy can be simply expressed by a set of rules
Index Terms—Load Frequency Control, Generation Rate which describe the behavior of the controller using
Constraints, Conventional Integral Control, Fuzzy Logic linguistic terms. Proper control action is then inferred
Control. from this rule base. In additional, FLCs are relatively
easy to develop and simple to implement. In the design of
load frequency controller, it should be recognized that
there is a limit to the rate at which generating unit outputs
I. INTRODUCTION can be changed. This is particularly true of steam
Large-scale power systems are normally composed of generating units where mechanical and thermal stress are
control areas or regions representing coherent groups of limiting factor. The controller designed for unconstrained
generators. The various areas are interconnected through situation may not be suitable. The analysis performed in
tie lines. The tie lines are utilized for energy exchange [11, 21] indicate that with constraints imposed by
between areas and provide inter-area support in case of generation rate constraints (GRC), the dynamic responses
abnormal condition [1-5]. Area load-changes and of the power area experience larger overshoots and longer
abnormal conditions, such as outages of generation, leads settling times, compared to the case without considering
to mismatch in scheduled power interchanges between the GRC.
areas. These mismatches have to be corrected via
supplementary control. In recent years, large tie-line This paper presents a design for LF controller to
power fluctuations have been observed as a result of improve the dynamic performance of power areas under
increased system capacity and very close interconnection disturbances such as a sudden load changes. The
among power systems [1]. This observation suggests a generation rate constraint (GRC) has considered in the
strong need of establishing a more advanced load controller design. The paper is organized as follows:
frequency control (LFC) scheme. LFC is one of the major Section 2 provides the model of the power two-area.
requirements in providing reliable and quality operation Section 3 shows the designed fuzzy controllers. The
in interconnected power systems. The primary objectives effectiveness of the proposed controller on the dynamic
of the LFC in an interconnected power system are to performance is also contained in Section 4. The
regulate the frequency to the nominal value and to conclusions are given in Section 5.
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
Design of Decentralized Fuzzy Logic Load Frequency Controller 67
ACEi = ∑ (ΔPij + γ i Δf )
n parameters of the controller are not chosen properly, the
(1) power area may have unacceptable dynamic response
j =1 (large overshoot and long settling time) or become
An overall satisfactory performance is achieved when γi is unstable. In the time-domain simulations presented in this
selected to be equal to the frequency bias factor of that paper, the linear model of turbine shown in Fig. 2 is
placed by a nonlinear model shown in Fig. 6. This
replacement is done to take into account the effect of
GRC that emulates the practical limit on the response of
1
B1
R1 ΔPL1
ACE1 _ Governor Turbine _ Generator & load
+ ΔPV1 ΔPm1 1 Δf1
K 1 1 Σ
Σ − 1 Σ
+ s 1 + sτ g 1 1 + sτ T 1 + _ 2 H 1 s + D1
+
+
Δ u1 ΔP12=ΔPtie T12 Σ
s _
Δ u2
_ +
+ ΔPV2 ΔPm2 Δf2
K 1 1 1
Σ − 2 Σ
1 + sτ T 2
Σ
2 H 2 s + D2
+ s _ 1 + sτ 2 + _
ACE2
1 ΔPL2
B2 R2
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
68 Design of Decentralized Fuzzy Logic Load Frequency Controller
that the system response is less damped and the overshot frequency and tie-line power of the power areas under
is large. To solve this problem, another control signals disturbances. This improvement can be achieved by
(Δu1, Δu2) are added to the system in presence of integral introducing an auxiliary stabilizing signal (Δu1 & Δu2)
controller. These signals are derived from the proposed drive from the controller as shown in Fig. 1. The
fuzzy logic controller. objective of the proposed fuzzy logic based frequency
controller (FLFC) is to increase transient response (i.e.
improve the damping and reduce the overshoots) of the
frequency deviations for the unequal areas and also to
maintain the interchanged power (tie-line power) about
ΔPv 1 1 ΔPt=ΔPm
the schedule, thus that loads in each area are self
Σ
+ - τt s contained.
NB NM NS Z PS PM PB
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
Design of Decentralized Fuzzy Logic Load Frequency Controller 69
The Xmax and Xmin represent maximum and the achieved by integrating the output of a PD-Like
minimum variation of the input and output signals. These controller [18]. Thus the final configuration of the
values are selected based on simulation information. The proposed FLFC is shown in Fig. 5. A symmetrical fuzzy
selected value of Xmax and Xmin was based on the rule set is used to describe both the PD and the PI like
performed dynamic simulations under different system fuzzy controller behaviors as shown in Table 1 and 2. The
operating conditions including different load changes to fuzzy rules have been selected based on experience
obtain a robust modulated signal (output signal of the gained form different simulations.
designed FLFC controller) which improve the dynamic
performance (reducing the overshoot and improving the Table 1: PD-Fuzzy Logic Rules
damping) of the system under diffent operating
conditions and system parameters change. The range of Δ2f
each fuzzy variable is normalized between –1 to 1 by Δf
introducing a scaling factor to represent the actual signal NB NM NS Z PS PM PB
so that: NB NB NB NB NB NM NS Z
NM NB NB NM NM NS Z PS
The PD-Like fuzzy controller initial gains are given by NS NB NM NM NS Z PS PM
[17, 18]:
1 1 Z NM NM NS Z PS PM PM
K Δf = ; K Δ2 f = 2 ; K upd = U pd max (3) PS NM NS Z PS PM PM PB
Δf max Δ f max
Similar definition applies in the case of the PI-like fuzzy PM NS Z PS PM PM PB PB
controller PB Z PS PM PB PB PB PB
1 1
K Δf = ; KPtie = ; K upi = U pi max (4)
Δf max ΔPtie max Table 2: PD-Fuzzy Logic Rules
1 KΔf
Δf Normalized Kupd
2 2
KΔ f FLC
2
Δ f
PD-Like fuzzy
+ 1
+
ΔUf
KΔf′
Normalized
Kupi +
FLC +
3 KPtie
ΔPtie 1
z
Delay
PI-Like fuzzy
FLFC
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
70 Design of Decentralized Fuzzy Logic Load Frequency Controller
Table 1 is
where μ(x) is the membership value of the fuzzy variable,
if Δf is NB and Δ2 f is PB then U pd is Z (5)
x.
Defuzzification is achieved using the center of The net control action (Uf) of the FLFC is the sum of the
gravity method [20]. In general, if the control output individual PD and PI-like fuzzy controller outputs (Upd,
membership functions centroids are represented by Upi) thus:
θ1,…,θM. Thus, for M rules, the crisp output of the
controller is: U f = U pd + U pi (8)
M
∑wθ i i
(6)
=θ ζ
T
u= i =1
M
IV. COMPUTER SIMULATION RESULTS
∑w
i =1
i
20.6
20
1/R1
dPL1
I1
0.3
1 1 1 1 ΔPm1 1
s 0.2s+1 0.5 s 10s+0.6
k1 T1 GRC1 Turbine1 Inertia, Load1
Governor1 Sum
df
Ptie
PI PD FLC 1
T12
400,800,5, PD
1 f1-f2
2
s
dP-tie I3
df
Mux
df
u d2f du/dt
Ptie dw2
PI PD FLC 2
I2
0.3
1 1 1 1 ΔPm2 1
s 0.3s+1 0.6 s 8s+0.9
k2 T2 GRC2 Turbine2 Inertia, Load2
Governor2
Sum1
1/R2
16
B2
dPL2
16.9
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
Design of Decentralized Fuzzy Logic Load Frequency Controller 71
( )
⎢ λ9 0 . 0480 0 . 0026 0 . 0010 0 . 6371 0 . 0000 0 . 0206 0 . 0007 0 . 0003 00 . 2987 ⎥
⎣ ⎦
σ i2 + ω i2
From the participation factors, it can be observed that
where ωi characterizes the frequency and σi the damping the largest participation factor 0.4198 is associated with
behavior of oscillations. the eigenvalue modes λ3,4 while the largest participation
factor 0.3918 is associated with the modes λ5,6. Figures
Participation factors technique [4, 26], can be used 7 and 8 show the system frequency response with
to associate state-variables (frequency deviation Δfi = 0, different values of integral controller gains K1 = K2 =
i=1,2) with the specific modes (dominant eigenvalues K1,,2 under 20% and 1% changes in the load demand at
modes λ3,4 & λ5,6). The participation factors Pki is defined area 2. From Fig. 7 and 8, it can be seen that the gains
as : K1 = K2 = K1,,2=0.3 gives the best damping response.
vik wki From Table 3 and the time response shown in Figs. 7 and
Pki = n
(10) 8, it can be seen that the higher gains of integral
∑vi =1
ik wki controller can lead the system to instability. The results
have shown that the system becomes unstable at K1,,2≥
0.74. Optimization technique presented in [12] can also
where vik and wik are the kth entries of the right and left be applied to determine the optimal integral controller
eigenvector associated with λi. The Pki provide a measure gains.
of the contribution of kth state variable to the ith
eigenvalue and so can be used to correlate the Case2: Simulations Result with the proposed fuzzy logic
contribution of each state variable to each eigenvalue frequency controller
mode The system eigenvalues are listed in Table 3. The
table clearly show that the system is stable at 0.3 gains From the system dynamic response shown in Figs.7
setting (all eigenvalues having negative real part) while and 8, it can be seen that the conventional integral
the system is unstable at 0.8 gains setting. controller provide zero frequency deviations (Δfi=0,
i=1,2) in the steady-state but it exhibits poor dynamic
Table 3: System Eigenvalues with integral controller performance; i.e. it exhibits large overshoot and less
Eigenvalues Stable Unstable damping [1, 9]. In order to improve frequency damping
λi (K1 =K2=0.3) (K1 =K2=0.8) (i.e. ensures zero frequency deviations in shortest time
possible) and to reduce the frequency overshoot
λ1 -5.8468 -5.788 whenever there is any disturbance. the fuzzy logic
λ2 -4.2717 -4.1894 frequency controller (FLFC) is proposed. To
demonstrate the effectiveness of the proposed FLFC
λ3,4 -0.3768 ± 1.7234i * -0.0912 ± 1.7122i compare to the conventional integral controller, time-
domain simulations of the two area power system have
λ5,6 -0.2231+ 1.5992i ** 0.0287 ± 1.5766i
been performed under disturbances (1% and 5% load
λ7,8 -0.2537 + 0.0484i -0.2216, -0.8494 changes). Similar responses were obtained for load
disturbance applied to area 2 as shown in Figs. 9-12.
λ9 -0.3468 -0.9992 Figures 9-12 show the system dynamic response for
*ξ3,4 of stable mode λ3,4=21.3592%
both 1% and 5% load change. From Figs. 9-12, it can be
**ξ5,6 of stable mode λ5,6= 13.8169% seen that the dynamic response of the frequency and tie-
line deviations is less damped (large settling time) and
The Participation factors have been calculated and the large overshoot with only the integral controller for both
eigenvalues modes associated with the frequency disturbances. On the other hand the dynamic response of
deviations have been identified. The calculated the frequency and tie-line deviations is well damped and
participation factors are given as : the overshoot (%OS) is reduced with the proposed
FLFC controller for all disturbances considered. The
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
72 Design of Decentralized Fuzzy Logic Load Frequency Controller
improvements in %OS are shown in Figs. 14 and 15. The disturbance matrix Γ equals to
This proves that the designed decentralized FLFC ⎡ 1 ⎤
T
[
Δx= Δf1 ΔPc1 ΔPm1 ΔPv1 ΔP12 Δf2 ΔPc2 ΔPm2 ΔPv2 ]
T
is the ⎡
⎢ 86.8631
⎢
2.5342 0.7289 − 20.0053 1.6851 − 41.3502 − 1.2733 − 0.2936 12.1153 ⎥
⎤
⎥
K =⎢
state variables vector. ⎢
⎥
⎥
⎢ − 32.1644 − 0.7891 − 0.1957 7.7316 − 0.6917 71.1184 3.0647 0.9946 − 17.8207 ⎥
⎣ ⎦
⎡ − D1 1 −1 ⎤ 0.01
⎢ 2H 0 0 0 0 0 0 ⎥
2H1 2H1
⎢ 1
⎥
−1 1
⎢ 0 0 0 0 0 0 0 ⎥
⎢ τ T1 τT1 ⎥
⎢ −1 −1 1 ⎥ 0.005
⎢ 0 0 0 0 0 0 ⎥
⎢ R1τ g 1 τ g1 τ g1 ⎥
⎢ − K 1 B1 0 0 0 − K1 0 0 0 0 ⎥
⎢ ⎥
A = ⎢ T12 0 0 0 0 − T12 0 0 0 ⎥ 0
⎢ 1 − D2 1 ⎥
⎢ 0 0 0 0
2H 2 2H 2 2H 2
0 0 ⎥
⎢ ⎥
−1 1
⎢ 0 0 0 0 0 0 0 ⎥
⎢ τT2 τT2 ⎥ -0.005
⎢ −1 −1 1 ⎥
⎢ 0 0 0 0 0 0 ⎥
⎢ R 2τ g 2 τ g2 τ g2 ⎥
⎢ 0
⎣ 0 0 0 K2 − K 2 B2 0 0 0 ⎥⎦
-0.01
0 5 10 15 20 25
Time [sec]
T
⎡ 1 ⎤
⎢0 0 0 0 0 0 0 0⎥ Fig. 7 Response of area 1 frequency deviation ∆f1due to 20%
τ load disturbance at area 2 at different integral controller
B = ⎢ G1
⎥
⎢0 1
0 0 0 0 0 0 0⎥ gains.
⎢⎣ τ G 2
⎥⎦
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
Design of Decentralized Fuzzy Logic Load Frequency Controller 73
0.02
0
0.01
-1
0
-2
-0.01
-3
-0.02
-4
-0.03
-0.04 -5
0 5 10 15 20 25 0 5 10 15 20 25
Time [sec] Time [sec]
Fig. 8 Response of area 2 frequency deviation ∆f2 due to Fig. 11 Response of area 2 frequency deviation ∆f2 due to 5%
20% load disturbance at area 2 at different integral load dsiturbance at area 2 with GRC
controller gains
-4 -3
x 10 Δf2 Response during 1% Load Change at Area 2 x 10 Δptie Response during 5% Load Change at Area 2
4 14
With FLFC With FLFC
Without FLFC 12 Without FLFC
2
10
0
8
-2
6
-4
4
-6
2
-8 0
-10 -2
0 5 10 15 20 25 0 5 10 15 20 25
Time [sec] Time [sec]
Fig. 9 Response of area 2 frequency deviation ∆f2 due to1% load Fig. 12 Response tie‐line power deviation ∆Ptie due to 5% load
dsiturbance at area 2 with GRC disturbance at area 2 with GRC
x 10
-3
Δptie Response during 1% Load Change at Area 2 Δf2 Response during 20% load change in Area 2
2.5 0.01
With FLFC
Without FLFC
2 0.005
1.5 0
1 -0.005
With FLFC
Without FLFC
0.5 -0.01 With Optimal
0 -0.015
-0.5 -0.02
0 5 10 15 20 25 0 5 10 15 20 25
Time [sec] Time (sec)
Fig. 10Response
Fig. 10 Responsetie‐line
tie-line power
power deviation
deviation ∆Ptie ∆P
duetietodue
1% to 1%
load Fig.Fig.
13 13
Response of area 2 frequency deviation ∆f2 ∆f
due to 20% load
Response of area 2 frequency deviation 2 due to 20%
loaddisturbance
disturbance at at area 2 with
GRCGRC
area 2 with loaddsiturbance
disturbanceatatarea
area22
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
74 Design of Decentralized Fuzzy Logic Load Frequency Controller
-3
x 10 ΔP-tie response during 20% load change in Area 2
20 to enhance the transients of the frequency deviation of
each area while the PI-fuzzy logic controller uses
WithWith
FLFCFLFC deviations of the frequency deviation and the tie line
15
WithoutFLFC
Without FLFC power to enhance the transient of the tie line power
WithOptimal
With Controller
OptimalController deviation and keep power in the tie line to the scheduled
value. The computer simulations results show that the
proposed FLFC is more effective means for improving
10
the dynamic performance of the two power area
compared to the conventional integral controller. The
proposed FLFC controller still achieves good dynamic
5
performance when the GRC is considered and ensures
the stability of power areas for all load demand changes.
Moreover, the proposed controller type is relatively
0 simple and suitable for practical on-line implementation.
-5
REFERENCES
0 5 10 15 20 25
Fig. 14 Response of area 2 frequency deviation ∆Ptie due to 20% load [1] Fosha, C.E. and Elgerd, O.I., The megawatt-frequency
dsiturbance at area 2 control problem: a New Approach via Optimal Control
Theory, IEEE Trans. Power Apparatus and Systems, 1970,
89(4): 563-577.
[2] Kothari, D.P. and Nagrath, I.J. Modern Power System
Analysis, 1st Edition, McGraw-Hill, New York, 2008.
[3] Kundur P. Power System Stability & Control, McGraw-
Hill, New York, 1994.
[4] Wood, A. Power Generation, Operation and Control, 2nd
Edition, Prentice-Hall. New York, 1996.
[5] Shayeghi H, Shayanfar HA, Jalili A. Load frequency
control strategies: a state of-the-art survey for the
researcher. Energy Conversion and Management, 2009,
50(2): 344–353
[6] Tan W. Decentralized load frequency controller analysis
Fig. 15 Percent overshoot of area 2 frequency deviation Δf1
and tuning for multi-area power systems, Energy
under load disturbance at area 2
Conversion and Management , 2011,52(5): 2015–2023.
[7] Al-Badi, M., Awlad Thani, A. Al-Omeiri, B. and Ellithy,
%Overshoot of Δf2 at differnt load change at area 2 K.A. Comparative Study of Load Frequency Controller
2
1.8 Design for Interconnected Power Systems, The Journal
1.6 for Scientific Research-Science and Technology, Sultan
1.4
1.2 Qaboos University,m 2002 , 7: 81-90.
%OS
1
0.8
[8] Chan, W.C. and Hsu, Y.Y., Automatic Generation
0.6 Control of Interconnected Power Systems Using Variable
0.4
0.2
Structure Controller. IEE Proc. on Generation,
0 Transmission and Distribution Pt. C, 1981: 269-279.
1% 2% 4% 6% 8% 10% 12% 14% 16% 18% 20%
[9] Feliach, A. , Optimal Decentralized Load Frequency
ΔPL
Control, IEEE Trans. on Power Systems, 1987, 2: 379-
Wthout FLFC With FLFC 386.
[10] Hiyama, T., Design of Decentralized Load Frequency
Fig. 16 Percent overshoot of area 1 frequency deviation Δf2 Regulators for Interconnected Power Systems, IEE Proc.,
under load disturbance at area 2 Pt C, 1982, 129 (1): 17-23.
[11] Hiyama, T. Optimization of Discrete-Type Load
Frequency Regulator Considering Generation Rate
V. CONCLUSIONS Constraints, Proc. IEE, Pt. C, Generation, Transmission
and Distribution, 1982, 129 (6): 285-289.
A decentralized fuzzy logic frequency controller [12] Kothari, M.L., Nanda, J., Kothari, D.P. and Das, D.,
(FLFC) coordinated with conventional integral Discrete-Mode Automatic Generation Control of Two-
controller has been proposed to damp out the deviations Area Reheat Thermal System with New Area Control
of the frequency and tie-line power for the Error, IEEE Transactions on Power Systems, 1989, 4(2):
interconnected power areas and also to keep the 730-738.
[13] Oysal, Y. A Comparative Study of Adaptive Load
interchanged power at the scheduled value. The
Frequency Controller Designs in a Power System with
proposed FLFC incorporate two fuzzy logic controllers Dynamic Neural Network Models, Energy Conversion
a PD-fuzzy logic controller and the PI-fuzzy logic and Management 2005, 46 (15-16): 2656-2668.
controller. The PD-fuzzy controller uses the frequency [14] Yang, T.C., Ding. and Yu, H. Decentralized power
deviation and the rate of the frequency deviation in order system load frequency control beyond the limit of
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75
Design of Decentralized Fuzzy Logic Load Frequency Controller 75
Copyright © 2012 MECS I.J. Intelligent Systems and Applications, 2012, 2, 66-75