Relays Setting 2

The document outlines the short circuit calculations and relay protection parameters for the 33/11.5 kV energy distribution system for the Ministry of Electricity in Iraq. It includes details on the system's characteristics, electrical data, and protection relay functions. The calculations provide insights into the expected short circuit currents and their implications for system protection.

Uploaded by

mo8157661
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views56 pages

Relays Setting 2

The document outlines the short circuit calculations and relay protection parameters for the 33/11.5 kV energy distribution system for the Ministry of Electricity in Iraq. It includes details on the system's characteristics, electrical data, and protection relay functions. The calculations provide insights into the expected short circuit currents and their implications for system protection.

Uploaded by

mo8157661
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 56

İSTANBUL

Purchaser TOYOTA TSUSHO CORPORATION


User THE REPUBLIC OF IRAQ
MINISTRY OF ELECTRICITY (MoE)
Plant
Plantsections 33/11,5 kV ENERGY DISTRIBUTION

Short Circuit Calculations


Relay Protection Parameters
Relay Tripping Diagrams

Document No: LOT4-COM-E-0113


Revision : 3

Project Reference

Date 10.03.2014
Rev : 3 / 20.02.2015
Editor : Selim Çokuğraş
Dep IC LMV MS
e-mail : [email protected]

Siemens Sanayi ve Ticaret A.Ş


Gebze OSB 1000 Cadde No:1004 41480 Gebze

Page 1/56
SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

INDEX

1. General Characteristics of the Distribution Network and Protection


System

a. Sources
b. Interlocks
c. Grounding
d. Notes Regarding the Methods of Operation
e. Protection Relays

2. Electrical Data
3. Short Circuit Calculation Study
4. Relay Protection Parameter
5. Protection Simulation & Tripping Diagrams

Document No: L OT4- COM- E- 0 113- 0 3 Page 2/56


DESCRIPTIONS

Document No: L OT4- COM- E- 0 113- 0 3 Page 3/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

General Characteristics of the Distribution Network and Protection System

a. Sources
System has basically two 33/11,5 kV and 31,5 MVA transformers in order to feed the bus
sections of the 11 kV energy distribution station.
The short circuit power of the 132 kV grid was taken into the calculation as 5000 MVA.

b. Interlocks
An unexpected parallel operation between two transformer incoming on 11,5 kV busbar is
prevented by electrical interlock which controls incomings and bus tie circuit breaker
positions.

c. Grounding
The star points of the 11,5 kV windings of the 33/11,5 kV MVA transformers are grounded
via 22,13 Ω , 300 A grounding resistors.

d. Operating methods
There are two operation alternatives to feed to 11 kV distribution system from the 33 kV
station:

· One of the transformer incomings and bus tie circuit breaker is in operation
· Each transformer incoming circuit breakers are in operation and bus tie circuit
breaker is in open position.

Document No: L OT4- COM- E- 0 113- 0 3 Page 4/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

e. Protection Relays
Relay types and their locations and protection functions which are used in the protection
system are listed below:

Table 1 Protection Relays: Location, Function and Type

Electrical Data

All of the electrical data which were used into calculations are given on the “Electrical Data”
diagram

Document No: L OT4- COM- E- 0 113- 0 3 Page 5/56


ELECTRICAL DATA

Document No: L OT4- COM- E- 0 113- 0 3 Page 6/56


SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

ELECTRİCAL DATA

GRID
Sk" = 5.000,0 MVA
R/X = 0,1 pu

Type = N2YSY Type = N2YSY 01AH 1AH02/DIFF 02AH 2AH02/DIFF


q = 400,0 mm² q = 400,0 mm² CT (P) = 600/1 A CT (P) = 600/1 A
N2 l = 25,00 km l = 25,00 km
p = 2,0 p = 2,0
Type = N2YSY
q = 400,0 mm² Type = N2YSY
E04 l = 0,10 km q = 400,0 mm²
CT (P) = 300/5 A p = 2,0 l = 0,10 km
1AHA02/C p = 2,0
2AHA02/C
CT (P) = 600/5 A CT (P) = 600/5 A
N81 R1 R2
3T15 CT (P) = 600/5 A CT (P) = 600/5 A
Sn12 = 120,0 MVA
Sn23 = 60,0 MVA
Sn31 = 60,0 MVA
vk12 = 7,4 %
vk23 = 3,8 %
vk31 = 8,6 % TR-1 TR-2
Sn = 31,50 MVA Sn = 31,50 MVA
vk = 10,2 % vk = 10,2 %

1AK07/DIFF 1AK21/DIFF
1800/1 A 1800/1 A

Type = N2XSY Type = N2XSY


q = 400,0 mm² q = 400,0 mm²
l = 0,05 km l = 0,05 km
1AK07 p = 3,0 1AK21 p = 3,0
CT (P) = 1800/5 A CT (P) = 1800/5 A

11 kV BB1 11 kV BB2

N22
Type = N2XSY

1AK12
CT (P) = 1800/5 A

1AK01
CT (P) = 50/5 A
q = 240,0 mm²

1AK03
CT (P) = 300/5 A

1AK02
CT (P) = 300/5 A
Type = N2XSY
l = 0,10 km

1AK10
CT (P) = 300/5 A
1AK13
CT (P) = 300/5 A
1AK14
CT (P) = 300/5 A
1AK15
CT (P) = 300/5 A
1AK16
CT (P) = 300/5 A
1AK18
CT (P) = 300/5 A
1AK19
CT (P) = 300/5 A
1AK20
CT (P) = 300/5 A
1AK21
CT (P) = 300/5 A

1AK05
CT (P) = 300/5 A
1AK06
CT (P) = 300/5 A
1AK08
CT (P) = 300/5 A
1AK09
CT (P) = 300/5 A

1AK04
CT (P) = 300/5 A
q = 400,0 mm²
p = 1,0
Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY l = 0,01 km Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY Type = N2XSY
AUX. TR q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² p = 4,0 Type = N2XSY Type = N2XSY Type = N2XSY q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² q = 150,0 mm²
Sn = 0,25 MVA l = 0,15 km l = 10,00 km l = 1,00 km l = 1,00 km l = 1,00 km l = 1,00 km l = 1,00 km l = 1,00 km q = 150,0 mm² q = 150,0 mm² q = 150,0 mm² l = 1,00 km l = 1,00 km l = 1,00 km l = 1,00 km l = 1,00 km
vk = 4,0 % p = 1,0 p = 1,0 p = 1,0 p = 1,0 p = 1,0 p = 1,0 p = 1,0 p = 1,0 l = 1,00 km l = 1,00 km l = 1,00 km p = 1,0 p = 1,0 p = 1,0 p = 1,0 p = 1,0
p = 1,0 p = 1,0 p = 1,0

LV_CB
N23
CT (P) = 400/5 A

Type = NYY
q = 240,0 mm²
l = 0,10 km
p = 1,0

N21

SHC84 SHC87
P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW P = 0,0 MW
Sn = 3,6 MVA Sn = 3,6 MVA
Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar Q = 0,0 Mvar
Vdi = 0,0 kW Vdi = 0,0 kW

Document No: L OT4- COM- E- 0 113- 0 3 Page 7/56


SHORT CIRCUIT CALCULATIONS

Document No: L OT4- COM- E- 0 113- 0 3 Page 8/56


SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

3-Phase Max Short Circuit Results


Name
Ik" [kA]
ip [kA]
I sym 1c [kA]
I mom peak [kA]

Ik" [kA] : The initial short circuit alternating current is the effective value
of the expected short circuit current at the beginning of the short circuit
Ip [kA] : The surge current is the largest peak value for the short circuit
current.
Isym 1c [kA] : Symmetrical Current First Cycle the maximum of the effective
Ik" = 22,60 kA Ik" = 22,60 kA values of the short circuit current of the individual conductors during the first
cycle following the moment the short circuit occurs
N2 I mom peak [kA] : The momentary value of the asymmetrical short circuit
Ik" = 21,87 kA 01AH Ik" = 0,00 kA 02AH Ik" = 0,00 kA current a half cycle following the moment the short circuit occurs.
ip = 54,00 kA GRID Ik" = 22,60 kA Ik" = 22,60 kA IL1a [kA] : L1 - Absolute, 1phase to ground circuit current
Ik" = 21,87 kA ip = 60,95 kA ip = 60,95 kA IL2a [kA] : L2 - Absolute, 2 phase short circuit current
IL3a [kA] : L3 - Absolute, 2 phase short circuit current
Ik" = 0,00 kA

N81
Ik" = 22,95 kA
ip = 62,50 kA Ik" = 0,00 kA Ik" = 0,00 kA

Ik" = 22,95 kA
Ik" = 22,46 kA
Ik" = 22,46 kA
Ik" = 35,23 kA
Ik" = 0,00 kA Ik" = 0,00 kA

Ik" = 13,70 kA
Ik" = 13,70 kA

Ik" = 0,00 kA
Ik" = 0,00 kA

11 kV BB1 11 kV BB2
Ik" = 13,65 kA Ik" = 13,65 kA
ip = 38,08 kA ip = 38,08 kA
Ik" = 13,65 kA Ik" = 13,65 kA

Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 13,63 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA

Ik" = 13,20 kA
N22
Ik" = 13,20 kA
ip = 35,94 kA
Ik" = 0,00 kA

Ik" = 9,48 kA
N23
Ik" = 9,48 kA
ip = 25,86 kA
Ik" = 0,00 kA

Ik" = 7,11 kA Ik" = 12,94 kA Ik" = 2,55 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA Ik" = 9,83 kA
N21
Ik" = 7,11 kA
ip = 15,10 kA
SHC84 LO46 LO56 LO58 LO60 LO62 LO64 LO66 LO68 LO70 LO72 LO74 LO76 LO78 LO80 SHC87
Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA Ik" = 0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 9/56


SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

2-Phase Min Short Circuit Results


Name
IL2a [kA]
IL3a [kA]

Ik" [kA] : The initial short circuit alternating current is the effective value
of the expected short circuit current at the beginning of the short circuit
Ip [kA] : The surge current is the largest peak value for the short circuit
current.
IL2a = 6,73 kA IL2a = 6,73 kA Isym 1c [kA] : Symmetrical Current First Cycle the maximum of the effective
IL3a = 6,73 kA IL3a = 6,73 kA values of the short circuit current of the individual conductors during the first
cycle following the moment the short circuit occurs
N2 I mom peak [kA] : The momentary value of the asymmetrical short circuit
IL2a = 18,94 kA GRID 01AH IL2a = 0,00 kA 02AH current a half cycle following the moment the short circuit occurs.
IL3a = 18,94 kA IL2a = 18,94 kA IL2a = 6,73 kA IL3a = 0,00 kA IL2a = 6,73 kA IL1a [kA] : L1 - Absolute, 1phase to ground circuit current
IL3a = 18,94 kA IL3a = 6,73 kA IL3a = 6,73 kA IL2a [kA] : L2 - Absolute, 2 phase short circuit current
IL3a [kA] : L3 - Absolute, 2 phase short circuit current
IL2a = 0,00 kA
IL3a = 0,00 kA

N81
IL2a = 18,51 kA IL2a = 0,00 kA IL2a = 0,00 kA
IL3a = 18,51 kA IL3a = 0,00 kA IL3a = 0,00 kA

IL2a = 18,51 kA
IL3a = 18,51 kA IL2a = 0,00 kA
IL3a = 0,00 kA IL2a = 6,71 kA
IL2a = 28,08 kA IL3a = 6,71 kA
IL3a = 28,08 kA

IL2a = 8,14 kA
IL3a = 8,14 kA

IL2a = 0,00 kA
IL3a = 0,00 kA

11 kV BB1 11 kV BB2
IL2a = 8,11 kA IL2a = 8,10 kA
IL3a = 8,11 kA IL2a = 8,11 kA IL3a = 8,10 kA
IL3a = 8,11 kA

IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 8,10 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA
IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 8,10 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA

IL2a = 7,89 kA
IL3a = 7,89 kA
N22
IL2a = 7,89 kA
IL3a = 7,89 kA
IL2a = 0,00 kA
IL3a = 0,00 kA

IL2a = 7,04 kA
IL3a = 7,04 kA
N23
IL2a = 7,04 kA
IL3a = 7,04 kA
IL2a = 0,00 kA
IL3a = 0,00 kA

IL2a = 5,22 kA IL2a = 7,75 kA IL2a = 1,77 kA IL2a = 6,13 kA IL2a = 6,13 kA IL2a = 6,13 kA IL2a = 6,13 kA IL2a = 6,13 kA IL2a = 6,13 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA IL2a = 6,12 kA
IL3a = 5,22 kA IL3a = 7,75 kA IL3a = 1,77 kA IL3a = 6,13 kA IL3a = 6,13 kA IL3a = 6,13 kA IL3a = 6,13 kA IL3a = 6,13 kA IL3a = 6,13 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA IL3a = 6,12 kA
N21
IL2a = 5,22 kA
IL3a = 5,22 kA
SHC84 LO46 LO56 LO58 LO60 LO62 LO64 LO66 LO68 LO70 LO72 LO74 LO76 LO78 LO80 SHC87
IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA IL2a = 0,00 kA
IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA IL3a = 0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 10/56


SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

1-Phase to Ground Circuit Results


Name
IL1a [kA]

Ik" [kA] : The initial short circuit alternating current is the effective value
of the expected short circuit current at the beginning of the short circuit
Ip [kA] : The surge current is the largest peak value for the short circuit
current.
Isym 1c [kA] : Symmetrical Current First Cycle the maximum of the effective
IL1a = 1,05 kA IL1a = 1,05 kA values of the short circuit current of the individual conductors during the first
cycle following the moment the short circuit occurs
I mom peak [kA] : The momentary value of the asymmetrical short circuit
N2 01AH IL1a = 0,00 kA 02AH current a half cycle following the moment the short circuit occurs.
IL1a = 7,20 kA GRID IL1a = 1,05 kA IL1a = 1,05 kA IL1a [kA] : L1 - Absolute, 1phase to ground circuit current
IL1a = 4,80 kA IL2a [kA] : L2 - Absolute, 2 phase short circuit current
IL3a [kA] : L3 - Absolute, 2 phase short circuit current
IL1a = 2,40 kA

N81
IL1a = 1,24 kA IL1a = 0,08 kA IL1a = 0,08 kA

IL1a = 1,18 kA
IL1a = 0,00 kA
IL1a = 1,05 kA
IL1a = 0,00 kA

IL1a = 0,30 kA

IL1a = 0,02 kA

11 kV BB1 11 kV BB2
IL1a = 0,31 kA IL1a = 0,31 kA
IL1a = 0,30 kA

IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,01 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,01 kA IL1a = 0,30 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA

IL1a = 0,30 kA
N22
IL1a = 0,30 kA
IL1a = 0,00 kA

IL1a = 8,35 kA
N23
IL1a = 8,35 kA
IL1a = 0,00 kA

IL1a = 4,80 kA IL1a = 0,30 kA IL1a = 0,26 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA IL1a = 0,30 kA
N21
IL1a = 4,80 kA
SHC84 LO46 LO56 LO58 LO60 LO62 LO64 LO66 LO68 LO70 LO72 LO74 LO76 LO78 LO80 SHC87
IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA IL1a = 0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 11/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

Short Circuit Calculation Study

Short circuit currents are calculated on the model of distribution network by using relevant
module of the SİNCAL ®
In order to calculate minimum and maximum short circuit currents of the system, different
operating scenarios given in the table below, have been taken into consideration:

Table 2 Operating Scenarios for Calculation of min-max. Short Circuits Currents

Results of Short Circuits Calculations based on scenarios which given above are presented
in tabular form below:

Table 3 Results of Short Circuit Calculation

Document No: L OT4- COM- E- 0 113- 0 3 Page 12/56


PROTECTION PARAMETERS

Document No: L OT4- COM- E- 0 113- 0 3 Page 13/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

Relay Protection Parameters

Relay Protection Parameters and over are presented in tabular form below.

The selective time interval of consecutive protection relays has been taken as 200 msec in
this study.
Current and time settings for phase and earth failure protection has been determined with
considering
· The maximum short circuit durability of the distribution network equipments
· The minimum short circuit current which can be sensed by protection relay
· Current carrying capacities of power cables which are used in the distribution
network of the substation.

Due to lack of information, some protection parameters have been estimated according to
previously experiences.

· Tripping parameters of the 33 kV Transformer feeder protection relays were


coordinated according to a minimum ( 2 phase) short circuit at the 25 km far end of
the 33kV cable and 5000 MVA short circuit power at the 132 kV side.

Document No: L OT4- COM- E- 0 113- 0 3 Page 14/56


SIEMENS

31,5 MVA TRANSFORMER OUTGOING Instantaneous o/c protection 67


Gn 50-3 Element Disabled
Protection Relay: 7SR2203-2AA87-0CA0 Gn 50-3 Dir. Control
TR-1,2 Gn 50-3 Setting
7SR22 33/11,5 kV
7SR22 7RW80
31,5 MVA
33/√3/0,11/√3 kV 7UT61
11,5/√3/0,11/√3 kV
Gn 50-3 Delay
Gn 50-3 Inrush action
600/5A 600/1A 1800/1A 1800/5A
01AHA02 Inst. earth fault protection 67n
01,2AH01,02 VME42 01AK07,17
02AHA02 Gn 50N-2 Element Disabled
33 kV 11,5 kV
300/5A
7SR11 Gn 50N-2 Dir. Control
300 A, 30 sec Gn 50N-2 Setting
21 Ω
Gn 50N-2 Delay
Gn 50N-2 Inrush action
PARAMETER SETTING VALUE Inst. earth fault protection 51n
Gn 51N-1 Element Enabled
Instantaneous o/c protection 50 Gn 51N-1 Dir. Control Non-Dir
Gn 50-1 Element Enabled Gn 51N-1 Setting 0,08 x In
Gn 50-1 Dir. Control Non-Dir Gn 51N-1 Char. IEC-VI
Gn 50-1 Setting 10,4 x In Gn 51N-1 Time Mult. 1
Gn 50-1 Delay 0,4 sec Gn 51N-1 Inrush action Inhibit
Gn 50-1 Inrush action Inhibit Inrush dedection 81HBL2
Gn 50-2 Element Enabled Gn 81HBL2 Element Enabled
Gn 50-2 Dir. Control Non-Dir Gn 81HBL2 Bias Sum
Gn 50-2 Setting 3,8 x In Gn 81HBL2 Setting 0,12 x In
Gn 50-2 Delay 1 sec
Gn 50-2 Inrush action Inhibit Relay Configuration
Time delayed o/c protection 51
Gn 51-1 Element Enabled
Gn 51-1 Dir. Control Non-Dir
Gn 51-1 Setting 1,1 x In
Gn 51-1 Char. Very Inverse
Gn 51-1 Delay -
Gn 51-1 Time mult. 1,2
Gn 51-1 Inrush action Inhibit
Inst. earth fault protection 50n
Gn 50N-1 Element Enabled
Gn 50N-1 Dir. Control Non-Dir
Gn 50N-1 Setting 0,15 x In
Gn 50N-1 Delay 0,4 sec
Gn 50N-1 Inrush action Inhibit
Thermal Overload 49
Gn 49 Thermal overload Enabled
Gn 49 Overload setting 1,01 x In
Gn 49 Time Constant 110 min
Gn 49 Capacity alarm 97%
Supervisions
Gn VT Supervision Enabled
Gn CT Supervision Enabled SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
Gn Broken Conductor Enabled TOYOTA TSUSHO CO.
Gn Trip Cct Supervision Enabled Planner Selim Çokuğraş
Gn Inrush Dedector Enabled Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 1

Document No: L OT4- COM- E- 0 113- 0 3 Page 15/56


SIEMENS

31,5 MVA TRANSFORMER OUTGOING


Protection Relay: 7UT6121-4EB90-1BA0
TR-1,2
7SR22 33/11,5 kV
7SR22 7RW80
31,5 MVA
33/√3/0,11/√3 kV 7UT61
11,5/√3/0,11/√3 kV

01AHA02
600/5A 600/1A 1800/1A 1800/5A
01,2AH01,02
02AHA02
VME42 01AK07,17
33 kV 11,5 kV
7SR11
300/5A

300 A, 30 sec
21 Ω

PARAMETER SETTING VALUE

1201 Differantial Protection ON 87T


1205 Inc.of trip during start OFF
1206 Inrush rest 15%
1207 5.Harm. 5. HARM
1221 Idif > 0,2 I/In0 [ 0,2 x Inobj. ]
1226 Tdif> 0.0 sec
1231 Idif>> 10 I/In0 [ 1,1 x Intr / uk% ]
1236 Tdif>> 0,0 sec
1241A Slope 1 0,25
1242A Base point for slope 1 0
1243A Slope 2 0.5
1244A Base point for slope 2 2,5
1256A I-Add on stab 4
1257A T- Add. on Stab 15 cycle

SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 2

Document No: L OT4- COM- E- 0 113- 0 3 Page 16/56


SIEMENS

31,5 MVA TRANSFORMER STAR POINT EARTHING


Protection Relay: 7SR2101-1GA12-1CA0
TR-1,2
7SR22 33/11,5 kV
7SR22 7RW80
31,5 MVA
33/√3/0,11/√3 kV 7UT61
11,5/√3/0,11/√3 kV

600/5A 600/1A 1800/1A 1800/5A


01,2AH01,02 VME42 01AK07,17
33 kV 11,5 kV
300/5A 7SR21

300 A, 30 sec
21 Ω

PARAMETER SETTING VALUE

Inst. earth fault protection 50g


Gn 50G-1 Element Enabled
Gn 50G-1 Setting 0,25 x In
Gn 50G-1 Delay 5 sec

Relay Configuration

SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 3

Document No: L OT4- COM- E- 0 113- 0 3 Page 17/56


Page 12/56
SIEMENS

31,5 MVA TRANSFORMER STAR POINT EARTHING


Protection Relay: VME42
TR-1,2
7SR22 33/11,5 kV
7SR22 7RW80
31,5 MVA
33/√3/0,11/√3 kV 7UT61
11,5/√3/0,11/√3 kV

600/5A 600/1A 1800/1A 1800/5A


01,2AH01,02 VME42 01AK07,17
33 kV 11,5 kV
300/5A 7SR11

300 A
21 Ω

PARAMETER SETTING VALUE


earth fault protection 59G
U> 33 V
T U> 7 sec

SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 4

Document No: L OT4- COM- E- 0 113- 0 3 Page 18/56


SIEMENS

11,5 kV INCOMING Instantaneous o/c protection 67


Gn 50-3 Element Enabled
Protection Relay: 7SR2203-2AA87-0CA0 Gn 50-3 Dir. Control Forward (Cable direction)
TR-1,2 Gn 50-3 Setting
7SR22 33/11,5 kV 7SR22 7RW80
33/√3/0,11/√3 kV 7UT61
31,5 MVA Gn 50-3 Delay
11,5/√3/0,11/√3 kV
Gn 50-3 Inrush action Inhibit
01AK07 Inst. earth fault protection 67n
600/5A 600/1A 1800/1A 1800/5A
01AK17 Gn 50N-2 Element Enabled
01,2AH01,02 VME42 01AK07,17
33 kV
300/5A 7SR11 11,5 kV Gn 50N-2 Dir. Control Forward (Cable direction)
300 A
Gn 50N-2 Setting
21 Ω Gn 50N-2 Delay
Gn 50N-2 Inrush action Inhibit
PARAMETER SETTING VALUE Inst. earth fault protection 51n
Gn 51N-1 Element Enabled
Instantaneous o/c protection 50 Gn 51N-1 Dir. Control Non-Dir
Gn 50-1 Element Disabled Gn 51N-1 Setting 0,06 x In
Gn 50-1 Dir. Control Gn 51N-1 Char. IEC-VI
Gn 50-1 Setting Gn 51N-1 Time Mult. 0,7
Gn 50-1 Delay Gn 51N-1 Inrush action Inhibit
Gn 50-1 Inrush action Inrush dedection 81HBL2
Gn 50-2 Element Enabled Gn 81HBL2 Element Disabled
Gn 50-2 Dir. Control Non-Dir Gn 81HBL2 Bias
Gn 50-2 Setting 2,4 x In Gn 81HBL2 Setting
Gn 50-2 Delay 0,8 sec Relay Configuration
Gn 50-2 Inrush action
Time delayed o/c protection 51
Gn 51-1 Element Enabled
Gn 51-1 Dir. Control Non-Dir
Gn 51-1 Setting 1 x In
Gn 51-1 Char. Very Inverse
Gn 51-1 Delay -
Gn 51-1 Time mult. 0,7
Gn 51-1 Inrush action
Inst. earth fault protection 50n
Gn 50N-1 Element Enabled
Gn 50N-1 Dir. Control Non-Dir
Gn 50N-1 Setting 0,11 x In
Gn 50N-1 Delay 0,8 sec
Gn 50N-1 Inrush action
Thermal Overload 49
Gn 49 Thermal overload Disabled
Gn 49 Overload setting
Gn 49 Time Constant
Gn 49 Capacity alarm
Supervisions
Gn VT Supervision Enabled
Gn CT Supervision Enabled SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
Gn Broken Conductor Enabled TOYOTA TSUSHO CO.
Gn Trip Cct Supervision Enabled Planner Selim Çokuğraş
Gn Inrush Dedector Enabled Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 5

Document No: L OT4- COM- E- 0 113- 0 3 Page 19/56


11,5 kV INCOMING
Protection Relay: 7RW8010-5EB90-1DA0
TR-1,2
7SR22 33/11,5 kV
7SR22 7RW80
31,5 MVA
33/ 3/0,11/ 3 kV 7UT61
11,5/ 3/0,11/ 3 kV

01AK07
600/5A 600/1A 1800/1A 1800/5A
01,2AH01,02
01AK17
VME42 01AK07,17
33 kV 11,5 kV
7SR11

300 A
21

PARAMETER SETTING VALUE

0150 U< / U> Enabled 27 59 trip command to capacitor cubicle


5001 59 U> ON
5102 U> Pickup 1,1 x Un
5104 U> Time Delay 1,5 sec
5009 Phases for U> protection Largest phase
5101 27 U< ON
5102 U< Pickup 0.8 x Un
5113A U< DOUT ratio 1,05
5106 U< Time delay 1,5 sec
0154 f>/f< Protection Enabled 81
5401 f>/f< Protection ON
5421 f>/f< Protection F1 ON-f< stage
5422 f>/f< Protection F2 ON-f< stage
5423 f>/f< Protection F3 ON-f< stage
5424 f>/f< Protection F4 ON-f< stage
5402 Min req. Volt. for operation 65 V
5403 F1 pickup 49,7 Hz
5405 T F1 Time delay 0 sec
5406 F2 pickup 49,5 Hz
5408 T F2 Time delay 0 sec load shedding commands to outgoings
5409 F1 pickup 49 Hz
5411 T F1 Time delay 0 sec
5412 F2 pickup 48,8 Hz
5414 T F2 Time delay 0 sec

IC LMV MS
THE REPUBLIC OF IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çoku ra
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision B / 19.02.2015 Relay Settings
(4) G77550-C0xxx-L900-B 6
PROTECTION PARAMETERS_V0 .xlsx
S.COKU RAS

Document No: L OT4-COM-E-0 113-0 3


SIEMENS

11,5 kV BUS SECTION


Koruma Rölesi: 7SJ6245-4EB90-3FE4
11,5/√3/0,11/√3 kV

7SJ62
INC .
1AK12
1800/5A
01AK11 01AK12
11,5 kV 11,5 kV

PARAMETER SETTING VALUE


1102 (Ir) 50 51
1107 (Imstart) -
1201 Phase time o/c ON
0112 50/51 Time overcurrent curve IEC
1202 I>> 50-2 Pickup OFF
1203 t>> 50-2 Time delay OFF
1204 I> 50-1 Pickup 6A
1205 t> 50-1 Time delay 0,6 sec
1207 Ip 50 Pickup 4,4 A
1208 51 Time delay 0,7 sec
1210 Drop-out characteristic Instantaneous
1211 IEC Curve Very Inverse
2201 Inrush Restraint ON
2202 2nd Harmonic 12%
2203 Cross Block NO
2204 Cross Block Timer 0
2205 IMAX 5,85 A
4201 Thermal Overload OFF 49
4202 K-Factor
4203 Time Constant
4204 θ Alarm
4205 IAlarm
7001 Breaker Failure on / off OFF 52BF
7004 Chk BRK Contact
7005 Trip Timer
1301 Ground time o/c ON 50/51n
0113 50N/51N Definite Time
1302 Ie>> 50N-2 Pickup OFF
1303 te>> 50N-2 Time delay OFF
1304 Ie> 50N-1 Pickup 0,3 A
1305 te> 50N-1 Time delay 0,6 sec

SIEMENS
IC LMV MS
THE REPUBLIC OF IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision 0 Relay Settings
(4) G77550-C0xxx-L900 7

Document No: L OT4- COM- E- 0 113- 0 3 Page 21/56


LINE OUTGOING PARAMETER SETTING VALUE

Protection Relay: 7SR2103-1AA87-0DA0 Autoreclose 79


11,5/ 3/0,11/ 3 kV Gn 79 Autoreclose Disabled
7SR21

INC . 01AK03-06 Gn 79 Num Shots 2


01AK08-10 Gn 79 Retry Enable Disabled
N2XY 3x150 mm2
01AK13-16 Gn 79 Reclose Blocked Delay
40 s
300/5A 01AK18-21
1AKxx Gn 79 Sequence Fail Timer
40 s
11,5 kV Gn 79 Sequence Co-ord Disabled

PARAMETER SETTING VALUE

Instantaneous o/c protection 50 Inrush detection 81HBL2


Gn 50-1 Element Enabled Gn 81HBL2 Element Enabled
Gn 50-1 Setting 3 x In Gn 81HBL2 Bias Sum
Gn 50-1 Delay 0,4 sec Gn 81HBL2 Setting 0,12 x In
Gn 50-1 Inrush action Inhibit
Relay Configuration
Time delayed o/c protection 51
Gn 51-1 Element Enabled
Gn 51-1 Setting 1 x In
Gn 51-1 Char. Very inverse
Gn 51-1 Delay -
Gn 51-1 Time mult. 0,6
Gn 51-1 Inrush action Inhibit
Gn 51-1 Reset 30 sec
Inst. earth fault protection 50n
Gn 50N-1 Element Enabled
Gn 50N-1 Setting 0,17 x In
Gn 50N-1 Delay 0,4 sec
Gn 50N-1 Inrush action Inhibit
Inst. earth fault protection 51n
Gn 51N-1 Element Enabled
Gn 51N-1 Dir. Control Non-Dir
Gn 51N-1 Setting 0,08 x In
Gn 51N-1 Char. IEC-VI
Gn 51N-1 Time Mult. 0,6
Gn 51N-1 Inrush action Inhibit
Thermal Overload 49
Gn 49 Thermal overload Disabled
Gn 49 Overload setting -
Gn 49 Time Constant -
Gn 49 Capacity alarm -
Supervisions
Gn VT Supervision Enabled
Gn CT Supervision Enabled
Gn Broken Conductor Enabled
IC LMV MS
THE REPUBLIC OF IRAQ
Gn Trip Cct Supervision Enabled
TOYOTA TSUSHO CO.
Gn Inrush Dedector Enabled Planner Selim Çoku ra
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision B / 19.02.2015 Relay Settings
(4) G77550-C0xxx-L900-B 8

PROTECTION PARAMETERS_V0 .xlsx


S.COKU RAS

Document No: L OT4-COM-E-0 113-0 3


SIEMENS

CAPACITOR OUTGOING
Protection Relay: 7SR2103-1AA87-0CA0
11,5/√3/0,11/√3 kV

7RW80 7SR21

INC .
01AK02
300/5A 3,6 MVA
1AKxx
11,5 kV

PARAMETER SETTING VALUE

Instantaneous o/c protection 50 Inrush dedection 81HBL2


Gn 50-1 Element Enabled Gn 81HBL2 Element Enabled
Gn 50-1 Setting 3 x In Gn 81HBL2 Bias Sum
Gn 50-1 Delay 0,2 sec Gn 81HBL2 Setting 0,12 x In
Gn 50-1 Inrush action Inhibit
Time delayed o/c protection 51 Relay Configuration
Gn 51-1 Element Enabled
Gn 51-1 Setting Very Inverse
Gn 51-1 Char. 0,84 x In
Gn 51-1 Delay -
Gn 51-1 Time mult. 0,6
Gn 51-1 Inrush action Inhibit
Inst. earth fault protection 50n
Gn 50N-1 Element Enabled
Gn 50N-1 Setting 0,17 x In
Gn 50N-1 Delay 0,2 sec
Gn 50N-1 Inrush action Inhibit
Inst. earth fault protection 51n

Gn 51N-1 Element Enabled


Gn 51N-1 Dir. Control Non-Dir
Gn 51N-1 Setting 0,08 x In
Gn 51N-1 Char. IEC-VI
Gn 51N-1 Time Mult. 0,6
Gn 51N-1 Inrush action Inhibit
Thermal Overload
Gn 49 Thermal overload Disabled
Gn 49 Overload setting
Gn 49 Time Constant
Gn 49 Capacity alarm
Supervisions
Gn VT Supervision Enabled
Gn CT Supervision Enabled
Gn Broken Conductor Enabled
Gn Trip Cct Supervision Enabled
Gn Inrush Dedector Enabled

SIEMENS THE REPUBLIC OF


IC LMV MS IRAQ
Planner Selim Çokuğraş TOYOTA TSUSHO CO.

Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION


Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 9

Document No: L OT4- COM- E- 0 113- 0 3 Page 23/56


SIEMENS

CAPACITOR OUTGOING
Protection Relay: 7RW8010-5EB90
11,5/√3/0,11/√3 kV

7RW80 7SR21

INC .
01AK02
300/5A 3,6 MVA
1AKxx
11,5 kV

PARAMETER SETTING VALUE

0150 U< / U> Enabled 27 59


5001 59 U> ON

5102 U> Pickup 1,1 x Un


5104 U> Time Delay 1,5 sec
5009 Phases for U> protection Largest phase
5101 27 U< ON
5102 U< Pickup 0.8 x Un
5113A U< DOUT ratio 1,05
5106 U< Time delay 1,5 sec

SIEMENS THE REPUBLIC OF


IC LMV MS IRAQ
Planner Selim Çokuğraş TOYOTA TSUSHO CO.

Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION


Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 9a

Document No: L OT4- COM- E- 0 113- 0 3 Page 24/56


SIEMENS

AUX. TRANSFORMER OUTGOING


Protection Relay: 7SR2103-1AA87-0CA0
11,5/√3/0,11/√3 kV
7SR21
TR. AUX.
INC . 250 kVA / 11/0,4 kV

01AK01
50/5A 7SR11
1AKxx
11,5 kV

PARAMETER SETTING VALUE Inrush dedection 81HBL2


Gn 81HBL2 Element Enabled
Instantaneous o/c protection 50 Gn 81HBL2 Bias Sum
Gn 50-1 Element Enabled Gn 81HBL2 Setting 0,12 x In
Gn 50-1 Dir. Control Non-Dir
Gn 50-1 Setting 7 x In Supervisions
Gn 50-1 Delay 0,2 Gn VT Supervision Enabled
Gn 50-1 Inrush action Inhibit Gn CT Supervision Enabled
Gn 50-2 Element Enabled Gn Broken Conductor Enabled
Gn 50-2 Dir. Control Non-Dir Gn Trip Cct Supervision Enabled
Gn 50-2 Setting 2,6 x In Gn Inrush Dedector Enabled
Gn 50-2 Delay 0,6 sec
Gn 50-2 Inrush action Inhibit
Time delayed o/c protection 51 Relay Configuration
Gn 51-1 Element Enabled
Gn 51-1 Dir. Control Non-Dir
Gn 51-1 Setting 0,3 x In
Gn 51-1 Char. Very Inverse
Gn 51-1 Delay -
Gn 51-1 Time mult. 1 sec
Gn 51-1 Inrush action Inhibit
Inst. earth fault protection 50n

Gn 50N-1 Element Enabled


Gn 50N-1 Dir. Control Non-Dir
Gn 50N-1 Setting 0,4 x In
Gn 50N-1 Delay 0,2
Gn 50N-1 Inrush action Inhibit
Inst. earth fault protection 51n

Gn 51N-1 Element Enabled


Gn 51N-1 Dir. Control Non-Dir
Gn 51N-1 Setting 0,2 x In
Gn 51N-1 Char. IEC-VI
Gn 51N-1 Time Mult. 0,5 sec
Gn 51N-1 Inrush action Inhibit
Thermal Overload 49
Gn 49 Thermal overload Enabled
Gn 49 Overload setting 0,1 x In
Gn 49 Time Constant 144 min SIEMENS THE REPUBLIC OF
Gn 49 Capacity alarm Disabled IC LMV MS
IRAQ
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 10

Document No: L OT4- COM- E- 0 113- 0 3 Page 25/56


SIEMENS

AUX. TR. STAR POINT EARTHING


Protection Relay: 7SR1101-1GA12-1CA0
11,5/√3/0,11/√3 kV
7SR21
TR. AUX.
INC . 250 kVA / 11/0,4 kV

01AK01
50/5A 7SR11
1AKxx 1000/5A

11,5 kV

PARAMETER SETTING VALUE

Inst. earth fault protection 50g

Gn 50G-1 Element Enabled


Gn 50G-1 Setting 0,25 x In
Gn 50G-1 Delay 0,4 sec

Relay Configuration

SIEMENS THE REPUBLIC OF


IC LMV MS IRAQ
TOYOTA TSUSHO CO.
Planner Selim Çokuğraş
Date 01.04.2014 33/11,5 kV ENERGY DISTRIBUTION
Revision A / 01.10.2014 Relay Settings
(4) G77550-C0xxx-L900-A 11

Document No: L OT4- COM- E- 0 113- 0 3 Page 26/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

Short Circuit Calculation Study

Short circuit currents are calculated on the model of distribution network by using relevant
module of the SİNCAL ®
In order to calculate minimum and maximum short circuit currents of the system, different
operating scenarios given in the table below, have been taken into consideration:

Table 2 Operating Scenarios for Calculation of min-max. Short Circuits Currents

Results of Short Circuits Calculations based on scenarios which given above are presented
in tabular form below:

Table 3 Results of Short Circuit Calculation

Document No: L OT4- COM- E- 0 113- 0 3 Page 27/56


PROTECTION SIMULATIONS
&
TRIPPING DIAGRAMS

Document No: L OT4- COM- E- 0 113- 0 3 Page 28/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

Protection Simulation and Tripping Diagrams

In order to test the response of protection relays in case of electrical failures, electrical
faults has been simulated at various locations of the distribution network by the protection
simulation function of SINCAL® which are specified and described by the following table.

Table 4 Fault locations and types for protection simulation study

In this study,
· Maximum failure currents have been considered as 3 phase sc at the beginning of
the cable in case of feeding from grid.
· Minimum failure currents have been considered as 2 phase sc at the end of cable in
case of feeding by from grid.

Document No: L OT4- COM- E- 0 113- 0 3 Page 29/56


SIEMENS
IC LMV /MS

CALCULATION OF SHORT-CIRCUIT CURRENTS,


RELAY SETTINGS&PROTECTION COORDINATION

The meanings of symbols and their colors which are seen on the simulation diagrams are
described below:

Figure 1 Descriptions of symbols and their colors on the protection simulation diagram

Results of protection simulation study and related tripping diagrams are given below.

The protection simulation study proves, that the response of protection relays which
parameterized according to given values in chapter “relay protection parameter table” are
selective and correct.

Document No: L OT4- COM- E- 0 113- 0 3 Page 30/56


SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S100A

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 4,58 kA
Not started 0,00 kA
None
0,00 s
1,15 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Pickup outside selective tripping time
Phase None None Phase
Ip 0,00 s 0,00 s I>
2,73 s 0,00 kA 0,00 kA 1,00 s
4,58 kA 4,58 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Phase
0,00 s I>>
0,00 kA 0,80 s
13,14 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Tripping Not started Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
Phase None None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
I>> 0,00 s 0,00 s None None None None None None None None None None None None None None
0,20 s 0,00 kA 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
13,14 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

100A
SC3
0,23 s 1AK12
13.144,83 A 7SJ62_5
13.144,83 A Pickup outside selective tripping time
13.144,83 A Phase
I>
0,60 s
13,14 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 31/56


t [s] Protection Coordination - Tripping Characteristics C100A
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


10 100 1000 10000 100000
I [A] (33 kV)
10 100 1000 10000

1AK01 - Tripping Curve (Phase) 2AHA02/C - Tripping Curve (Phase) R1 - Tripping Curve (Phase)
1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase)

Page 32/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S100B

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 0,07 kA
Not started 0,00 kA
None
0,00 s
0,02 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Not started Not started Not started Not started
None None None None
0,00 s 0,00 s 0,00 s 0,00 s
0,07 kA 0,00 kA 0,00 kA 0,07 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Ground
0,00 s I>>
0,00 kA 0,80 s
0,33 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Tripping Not started Pickup outside selective
7SR21tripping time 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
Ground None Ground Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
I> 0,00 s Ip None None None None None None None None None None None None None None
0,20 s 0,00 kA 135,65 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,34 kA 0,01 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

100A
SC3
0,23 s 1AK12
336,00 A 7SJ62_5
0,00 A Pickup outside selective tripping time
0,00 A Ground
I>
0,60 s
0,33 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 33/56


t [s] Protection Coordination - Tripping Characteristics C100B
1000

100

10

0,1 I [A] (11,5 kV)


1 10 100 1000 10000

1AK01 - Tripping Curve (Ground) 1AK12 - Tripping Curve (Ground) 1AK21 - Tripping Curve (Ground)

Page 34/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S101A

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 4,49 kA
Not started 0,00 kA
None
0,00 s
1,12 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Pickup outside selective tripping time
Phase None None Phase
Ip 0,00 s 0,00 s I>
2,79 s 0,00 kA 0,00 kA 1,00 s
4,49 kA 4,49 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Phase
0,00 s I>>
0,00 kA 0,80 s
12,88 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Tripping Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None Phase None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s I>> 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,20 s 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
12,88 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
Phase
I>
0,60 s
12,88 kA

LV_CB
3VF6 101A
Not started SC3
None 0,23 s
0,00 s 12.883,61 A
0,00 kA 12.883,61 A
12.883,61 A

Document No: L OT4- COM- E- 0 113- 0 3 Page 35/56


t [s] Protection Coordination - Tripping Characteristics C101A
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


100 1000 10000 100000
I [A] (33 kV)
100 1000 10000

1AK02 - Tripping Curve (Phase) 1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase)
2AHA02/C - Tripping Curve (Phase) R1 - Tripping Curve (Phase)

Page 36/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S101B

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 2,24 kA
Not started 0,00 kA
None
0,00 s
0,56 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Pickup outside selective tripping time
Phase None None Phase
Ip 0,00 s 0,00 s I>
2,79 s 0,00 kA 0,00 kA 1,00 s
2,24 kA 2,24 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Phase
0,00 s I>>
0,00 kA 0,80 s
0,00 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Tripping Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None Phase None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s I>> 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,20 s 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
Phase
I>
0,60 s
0,00 kA

LV_CB
3VF6 101A
Not started SC3
None 0,23 s
0,00 s 0,00 A
0,00 kA 11.157,54 A
11.157,54 A

Document No: L OT4- COM- E- 0 113- 0 3 Page 37/56


t [s] Protection Coordination - Tripping Characteristics C101B
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


100 1000 10000 100000
I [A] (33 kV)
100 1000 10000

1AK02 - Tripping Curve (Phase) 1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase)
2AHA02/C - Tripping Curve (Phase) R1 - Tripping Curve (Phase)

Page 38/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S101C

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 0,07 kA
Not started 0,00 kA
None
0,00 s
0,02 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Not started Not started Not started Not started
None None None None
0,00 s 0,00 s 0,00 s 0,00 s
0,07 kA 0,00 kA 0,00 kA 0,07 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Ground
0,00 s I>>
0,00 kA 0,80 s
0,33 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Tripping Pickup outside selective
7SR21tripping time 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None Ground Ground Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s I>> Ip None None None None None None None None None None None None None None
0,00 kA 0,20 s 137,13 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,34 kA 0,01 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
Ground
I>
0,60 s
0,33 kA

LV_CB
3VF6 101A
Not started SC3
None 0,23 s
0,00 s 335,69 A
0,00 kA 0,00 A
0,00 A

Document No: L OT4- COM- E- 0 113- 0 3 Page 39/56


t [s] Protection Coordination - Tripping Characteristics C101C
1000

100

10

0,1 I [A] (11,5 kV)


10 100 1000 10000

1AK02 - Tripping Curve (Ground) 1AK12 - Tripping Curve (Ground) 1AK21 - Tripping Curve (Ground)

Page 40/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S102A

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 4,73 kA
Not started 0,00 kA
None
0,00 s
1,18 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Pickup outside selective tripping time
Phase None None Phase
Ip 0,00 s 0,00 s I>
2,63 s 0,00 kA 0,00 kA 1,00 s
4,73 kA 4,73 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Phase
0,00 s I>>
0,00 kA 0,80 s
13,59 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Tripping 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None Phase Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s Ip None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,36 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
13,59 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
A102 Phase
SC3 I>
0,39 s 0,60 s
13.585,08 A 13,59 kA
13.585,08 A
13.585,08 A

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 41/56


t [s] Protection Coordination - Tripping Characteristics C102A
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


100 1000 10000 100000
I [A] (33 kV)
100 1000 10000

1AK03 - Tripping Curve (Phase) 1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase)
2AHA02/C - Tripping Curve (Phase) R1 - Tripping Curve (Phase)

Page 42/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S102B

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 0,44 kA
Not started 0,00 kA
None
0,00 s
0,11 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Pickup outside selective tripping time
Phase None None Phase
Ip 0,00 s 0,00 s Ip
47,91 s 0,00 kA 0,00 kA 39,92 s
0,44 kA 0,44 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Phase
0,00 s Ip
0,00 kA 42,10 s
0,00 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Tripping 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None Phase Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s I>> None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,40 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
Phase
I>
0,60 s
0,00 kA

LV_CB
3VF6 102B
Not started SC3
None 0,43 s
0,00 s 0,00 A
0,00 kA 2.206,42 A
2.206,42 A

Document No: L OT4- COM- E- 0 113- 0 3 Page 43/56


t [s] Protection Coordination - Tripping Characteristics C102B
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


100 1000 10000 100000
I [A] (33 kV)
100 1000 10000

1AK03 - Tripping Curve (Phase) 1AK12 - Tripping Curve (Phase) 2AHA02/C - Tripping Curve (Phase)
1AK21 - Tripping Curve (Phase) R1 - Tripping Curve (Phase)

Page 44/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S102C

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 0,06 kA
Not started 0,00 kA
None
0,00 s
0,01 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Not started Not started Not started Not started
None None None None
0,00 s 0,00 s 0,00 s 0,00 s
0,06 kA 0,00 kA 0,00 kA 0,06 kA

1AK07 1AK21
7SR22 7SR22
Not started Pickup outside selective tripping time
None Ground
0,00 s I>>
0,00 kA 0,80 s
0,29 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Tripping 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None Ground Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s I>> None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,40 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,29 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Pickup outside selective tripping time
Ground
I>
0,60 s
0,29 kA

LV_CB
3VF6 102B
Not started SC3
None 0,43 s
0,00 s 292,30 A
0,00 kA 0,00 A
0,00 A

Document No: L OT4- COM- E- 0 113- 0 3 Page 45/56


t [s] Protection Coordination - Tripping Characteristics C102C
1000

100

10

0,1 I [A] (11,5 kV)


10 100 1000 10000

1AK03 - Tripping Curve (Ground) 1AK12 - Tripping Curve (Ground) 1AK21 - Tripping Curve (Ground)

Page 46/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S103A

2AH02/DIFF
1AH02/DIFF 7UT6_1
7UT6_1 Not started
Not started None
E04 None 0,00 s
7SJ62_5 0,00 s 22,12 kA
Not started 0,00 kA
None
0,00 s
5,53 kA R1 R2 1AHA02/C 2AHA02/C
7SJ62_5 7SJ62_5 7SR22 7SR22
Pickup outside selective tripping time Not started Not started Tripping
Phase None None Phase
I> 0,00 s 0,00 s 103A I>>
0,60 s 0,00 kA 0,00 kA SC3 0,40 s
22,12 kA 0,43 s 22,12 kA
22.121,51 A
22.121,51 A
22.121,51 A

1AK07 1AK21
7SR22 7SR22
Not started Not started
None None
0,00 s 0,00 s
0,00 kA 0,00 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Not started
None
0,00 s
0,00 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 47/56


t [s] Protection Coordination - Tripping Characteristics C103A
1000

100

10

0,1

0,01

0,001 I [A] (33 kV)


100 1000 10000 100000

2AHA02/C - Tripping Curve (Phase) R1 - Tripping Curve (Phase)

Page 48/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S103B

2AH02/DIFF
7UT6_1
Not started
None
E04 0,00 s
7SJ62_5 1,22 kA
Not started
None
0,00 s
0,20 kA R1 2AHA02/C
7SJ62_5 7SR22
Pickup outside selective tripping time Tripping
Ground Ground
I> 103A I>
0,80 s SC3 0,40 s
1,22 kA 0,43 s 1,22 kA
1.223,77 A
0,00 A
0,00 A

1AK21
7SR22
Not started
None
0,00 s
0,00 kA

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Not started
None
0,00 s
0,00 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 49/56


t [s] Protection Coordination - Tripping Characteristics C103B
1000

100

10

0,1 I [A] (33 kV)


10 100 1000 10000

2AHA02/C - Tripping Curve (Ground) R1 - Tripping Curve (Ground)

Page 50/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S103C

2AH02/DIFF
7UT6_1
Not started
None
E04 0,00 s
7SJ62_5 4,74 kA
Not started
None
0,00 s
1,18 kA R1 2AHA02/C
7SJ62_5 7SR22
Pickup outside selective tripping time Pickup outside selective tripping time
Phase Phase
Ip I>
2,63 s 1,00 s
4,74 kA 4,74 kA

1AK21
7SR22
Pickup outside selective tripping time
103C Phase
SC3 I>>
0,63 s 0,80 s
13.589,97 A 13,59 kA
13.589,97 A
13.589,97 A

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Tripping
Phase
I>
0,60 s
13,59 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 51/56


t [s] Protection Coordination - Tripping Characteristics C103C
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


1000 10000 100000 1e+006
I [A] (33 kV)
1000 10000 100000

1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase) 2AHA02/C - Tripping Curve (Phase)
R1 - Tripping Curve (Phase)

Page 52/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S103D

2AH02/DIFF
7UT6_1
Not started
None
E04 0,00 s
7SJ62_5 2,37 kA
Not started
None
0,00 s
0,59 kA R1 2AHA02/C
7SJ62_5 7SR22
Pickup outside selective tripping time Pickup outside selective tripping time
Phase Phase
Ip I>
2,63 s 1,00 s
2,37 kA 2,37 kA

1AK21
7SR22
Pickup outside selective tripping time
103C Phase
SC3 I>>
0,63 s 0,80 s
0,00 A 0,00 kA
11.769,26 A
11.769,26 A

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Not started 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None None Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s 0,00 s None None None None None None None None None None None None None None
0,00 kA 0,00 kA 0,00 kA 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Tripping
Phase
I>
0,60 s
0,00 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 53/56


t [s] Protection Coordination - Tripping Characteristics C103D
1000

100

10

0,1

0,01

0,001 I [A] (11,5 kV)


1000 10000 100000 1e+006
I [A] (33 kV)
1000 10000 100000

1AK12 - Tripping Curve (Phase) 1AK21 - Tripping Curve (Phase) 2AHA02/C - Tripping Curve (Phase)
R1 - Tripping Curve (Phase)

Page 54/56
Document No: L OT4- COM- E- 0 113- 0 3
SIEMENS THE REPUBLIC OF IRAQ 01.04.2014

Protection Simulation Fault


Number: S103E

2AH02/DIFF
7UT6_1
Not started
None
E04 0,00 s
7SJ62_5 0,07 kA
Not started
None
0,00 s
0,02 kA R1 2AHA02/C
7SJ62_5 7SR22
Not started Not started
None None
0,00 s 0,00 s
0,07 kA 0,07 kA

1AK21
7SR22
Pickup outside selective tripping time
103C Ground
SC3 I>>
0,63 s 0,80 s
336,40 A 0,33 kA
0,00 A
0,00 A

1AK01 1AK02 1AK03


7SR21 7SR21 7SR21 1AK04 1AK05 1AK06 1AK08 1AK09 1AK10 1AK13 1AK14 1AK15 1AK16 1AK18 1AK19 1AK20 1AK21
Not started Not started Pickup outside selective
7SR21tripping time 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21 7SR21
None None Ground Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started Not started
0,00 s 0,00 s Ip None None None None None None None None None None None None None None
0,00 kA 0,00 kA 133,77 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s 0,00 s
0,01 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA 0,00 kA

1AK12
7SJ62_5
Tripping
Ground
I>
0,60 s
0,33 kA

LV_CB
3VF6
Not started
None
0,00 s
0,00 kA

Document No: L OT4- COM- E- 0 113- 0 3 Page 55/56


t [s] Protection Coordination - Tripping Characteristics C103E
1000

100

10

0,1 I [A] (11,5 kV)


10 100 1000 10000

1AK12 - Tripping Curve (Ground) 1AK21 - Tripping Curve (Ground)

Page 56/56
Document No: L OT4- COM- E- 0 113- 0 3