Lisa Operation Manual (Kleemann)
Lisa Operation Manual (Kleemann)
COMPLETE LIFTS PAGE – 2 –
LiSA CONTROLLER
HANGEKABEL
Fahrsimulator
+H 42 T1auf
1 1 1 1 1 1 1 1
-H X57 X49 X41 X33 X25 X17 X9 X1 T2auf
T1zu
F26 T2zu
X4
57 49 41 33 25 17 9 1
MATRIX-ANZ
F25
58 50 42 34 26 18 10 2
X3
F24
X2
IO-16
IO-16
IO-16
IO-16
59 51 43 35 27 19 11 3
F23
60 52 44 36 28 20 12 4
1
F22
61 53 45 37 29 21 5
1
F21 35 13
X10
62 54 46 38 30 22 6 20 +H2
HANGEK.
VO 34
63 55 47 39 31 23 7
SN75176
SN75179
VU +H2
SGO 64 56 48 40 32 24 8 18 -H
SGM
Strom
SGU 30 SK1 VO +H
SK2 SGO
+Bu 29 SK3 SGM
15 -H
SK3 SGM
SK2 SGU
SK4 SGO
SK1 Vu
Vo
s v Z * 1 2 3 4 5 SK4 SGU
L LS1 VU
M 27 0 1 : 1 2
LS2
SKB1
ZIMP
Turstop
+H 26 SKB2 Rufsim.
Lebenslicht Turblock
IMP+ Testmodus Aussen-Aus
IMP-
-H 23 JP12 JP11
2630
/1
Impulsteiler
A1 /2
/4
1 2 3
X21
Z1 JP1
/8
/16
HCPL
3700
/64
Z2 JP14 L4
19 /128
L4
AL Notruf JP2 4 5 6
Bundig-Anzeige
HCPL
NI
3700
NL Puffer- SK1
Relaisplatine Segment-Anz
JP10
+NV 16 Batterie SK1
7 8 9
X5
HCPL
3700
ACCU RAM SK2 5 SK2
14 Datum High-EPROM loschen
-
EIN SK3
* 0 #
HCPL
3700
AUF SK3
AB 11 SK4
X23
AA/SAK 10 NA
HCPL
3700
ULN 2804 ULN 2804 SK4
U2 ULN 2804 ULN 2804 ULN 2804
MAX/ 1 SK4*
REGST JP3 JP4
U1 XK1
MIN 6
-H K42 K41 K31 K17 K24 K23 K22 K21
K7 K6 K5 K15 K14 K13 K12 K11
3
JP5 freipr. freipr.
Notruf Vo/Ab
Ture2- Ture2- Ture1- Ture1-
Kontrolle
Stern./
Auf
Langs./
Ab Schnel
GR/6 Relais2 Relais1 Auf Zu Auf Zu Dreieck Fahren
+H 1
XK2
21 18 15 13 11 9 5 1 9 2 1
XK5 XK4
-H Ein Ab O C S O C S +HU Vo OT ST LGS SCH V2
Auf -H DR AUF AB
Ruckholen REL2 REL1 SS1 Hupe AB TURE 2 TURE 1
X1, X9, X17, X25, X33, X41, X49, X57: 10-pole flat cable plug connector on the I/O-cards. To any plug connector
8 I/O´s can be connected. The designations of the plug connectors depend on the position of the card slot. At slot
1 are I/O1 – I/O16, at slot 2 I/O17 – I/O32, at slot 3 I/O33 – I/O48 and at slot 4 I/O48 – I/O64.
X2: 26-pole travelling cable plug: plug connector for the internal part of the LiSA – travelling cable.
Pin assignment
1: door-open limit switch-door1 14: signal switch – centre
2: door-closed-limit switch-door1 15: signal switch – bottom
3: door-open –limit switch-door2 16: signal switch – top
4: door-closed-limit switch-door2 17: correction switch-top
5-10: data lines RS485 18: correction switch –bottom
10: alarm key 19: loudspeaker
12: emergency light 20: microphone
13: emergency power source 21-26: free wires in the travelling cable
X3: 10-pole plug connector for the LiSA – matrix-display. With an additional power source up to 16 matrix-
displays (16 * 8 / 8 * 8) can be connected to this connector. Alternatively also the LiSA – hand terminal can
be connected.
COMPLETE LIFTS PAGE – 3 –
LiSA CONTROLLER
X4: 14-pole plug connector for the connection of the LiSA travel simulator. The LiSA travel simulator enables in a
simple and reasonable way a simulation of the shaft signals. The simulator will be made available upon
request.
X5: 10-pole plug connector for the connection of the LiSA – segment indicator or of the expansion card IOW16
X10: 9-pole D-Sub-plug for the connection of a modem resp. of a PC.
X21: 10-pole plug connector for the connection of the LiSA-emergency call system
X23: 10-pole plug connector for the connection of the LiSA – relay card
HANGEKABEL
Fahrsimulator
+H 42 T1auf
1 1 1 1 1 1 1 1
-H X57 X49 X41 X33 X25 X17 X9 X1 T2auf
T1zu
F26 T2zu
X4
57 49 41 33 25 17 9 1
MATRIX-ANZ
F25
58 50 42 34 26 18 10 2
X3
F24
X2
IO-16
IO-16
IO-16
IO-16
24 59 51 43 35 27 19 11 3
F23
60 52 44 36 28 20 12 4
1
F22
61 53 45 37 29 21 5
1
F21 35 13
X10
62 54 46 38 30 22 6 20 +H2
HANGEK.
VO 34
63 55 47 39 31 23 7
SN75176
SN75179
VU +H2 1
23 SGO 64 56 48 40 32 24 8 18 -H
SGM
Strom
SGU 30 SK1 VO +H
+Bu 29
SK2 SGO 2
SK3 SGM
15 -H
SK3 SGM
SK2 SGU
SK4 SGO
SK1 Vu
Vo
s v Z * 1 2 3 4 5 SK4 SGU
L LS1 VU
22 27 LS2 ZIMP
M 0 1 : 1 2 SKB1 Turstop
+H 26 SKB2 Rufsim.
Lebenslicht Turblock
IMP+ Testmodus Aussen-Aus
21 IMP-
-H JP11
23 JP12
2630
/1
Impulsteiler
A1 /2
/4
1 2 3
X21
Z1 JP1
/8
20 /16
9 N2
A2 JP13/ Notrugbetrieb /32
HCPL
3700
/64
Z2 JP14 L4 3
19 /128
L4
Notruf JP2 4 5 6
AL Bundig-Anzeige
HCPL
NI
3700
19 NL Datum Low-EPROM Puffer- SK1
Relaisplatine Segment-Anz
JP10
+NV 16 Batterie SK1
7 8 9
X5
HCPL
3700
18 ACCU RAM SK2 5 SK2
14 Datum High-EPROM loschen
-
EIN SK3 4
* 0 #
HCPL
3700
17 AUF SK3
AB 11 SK4
X23
16 AA/SAK 10 NA
HCPL
3700
ULN 2804 ULN 2804 SK4
U2 ULN 2804 ULN 2804 ULN 2804
MAX/ 1 SK4*
15 REGST JP3 JP4
U1 XK1
MIN 6
-H K42 K41 K31 K17 K24 K23 K22 K21
14 K7 K6 K5 K15 K14 K13 K12 K11
3 freipr. freipr. Ture2- Ture2- Ture1- Ture1- Stern./ Langs./
JP5 Notruf Vo/Ab Kontrolle Auf Ab Schnel
GR/6 Relais2 Relais1 Auf Zu Auf Zu Dreieck Fahren
+H 1
XK2
21 18 15 13 11 9 5 1 9 2 1
XK5 XK4
-H Ein Ab O C S O C S +HU Vo OT ST LGS SCH V2
Auf -H DR AUF AB
Ruckholen REL2 REL1 SS1 Hupe AB TURE 2 TURE 1
13 12 11 10 9 8 7 6 5
COMPLETE LIFTS PAGE – 4 –
LiSA CONTROLLER
ST = connection for star contactor
DR = connection for delta contactor
( 6) OT = connection for door bypass
XK5: ( 8) = activation signals for the door operator
1 – 4: door 1 (relay K21)
5 – 8: door 2 (relay K22)
( 9) = potential-free contact for the travel signal V0 (= levelling speed with closed-loop controlled
lifts) or DOWN – signal in case of Hydro-Elevators (relay K17)
( 10 ) + Hu = connection for alarm hooter, if installed in the shaft (basically in the inspection box)
( 11 ) = potential-free contact for emergency call – forwarding (contact of relay K31)
( 12 ) = connections for one change-over contact each of the free programmable relays R1 and R2
(K41 and K42)
( 13 ) = connection for recall operation
XK2: ( 14 ) = connection of data lines for group communication
SendA = output transmission
EmpfA = input reception
-H = reference potential
( 15 ) = connections of motor protection
MIN = connection for minimum-pressure contact
U1 = connection for PTC-thermistor (excess temperature 1)
MAX/ = connection for maximum pressure contact with hydro-elevators resp. for controller-fault with
REGST closed-loop controlled traction elevators
U2 = connection for PTC-thermistor (excess temperature 2)
( 16 ) = connection for contact of external control – off, in case of installations acc. to TRA resp.
connection for contactor-drop monitoring with EN81. Switching signal is –H.
( 17 ) = connection for inspection mode.
If the connection card APO 8 is available the inspection mode is connected in the car. Only if APO 8 is not used
or in case that installer’s travel is carried out with a separatehand terminal these connections will not be needed.
( 18 ) = connection of storage battery
( 19 ) = connection of emergency call
AL = connection of emergency call button in the shaft
NL = connection of emergency light (only relevant if no APO 8 is used)
+NV = connection of emergency light
( 20 ) = door limit switch-signals (only relevant without APO 8)
A1 = door-open limit switch door 1 (switching voltage = +H)
Z1 = door-closed limit switch door 1 (switching voltage = +H)
A2 = door-open limit switch door 2 (switching voltage = +H)
Z2 = door-closed limit switch door 2 (switching voltage = +H)
( 21 ) = connection of pulse sequence for the digital shaft information
+H = supply voltage for pulse generator
IMP+ = positive pulse signal from pulse generator
IMP- = negative pulse signal from pulse generator
-H = supply voltage for pulse generator
( 22 ) = connection for wall mounted telephone (voice connection to the car)
L = loudspeaker connection
M = microphone connection
( 23 ) = tapping of shaft signals
V0 = signal from prelimit switch – top
SGO = signal from signal switch – top
SGM = signal from signal switch – centre
SGU = signal from signal switch – bottom
VU = signal prelimit switch – bottom
( 24 ) = F1 – F6 taps for free available cores of the travelling cable
Usage for emergency call system resp for special voice stations (screened wires), for pulse sequence from the
LiSA-pulse generator etc.
COMPLETE LIFTS PAGE – 5 –
LiSA CONTROLLER
1.1.3. Coding jumpers and functional elements
JP6,7,8,9
HANGEKABEL
Fahrsimulator
+H 42 T1auf
1 1 1 1 1 1 1 1
-H X57 X49 X41 X33 X25 X17 X9 X1 T2auf
T1zu
F26 T2zu
X4
57 49 41 33 25 17 9 1
MATRIX-ANZ
F25
58 50 42 34 26 18 10 2
X3
F24
X2
IO-16
IO-16
IO-16
IO-16
59 51 43 35 27 19 11 3
F23
60 52 44 36 28 20 12 4
1
F22
61 53 45 37 29 21 5
1
F21 35 13
X10
62 54 46 38 30 22 6 20 +H2
HANGEK.
VO 34
63 55 47 39 31 23 7
SN75176
SN75179
VU +H2
SGO 64 56 48 40 32 24 8 18 -H
SGM
Strom
SGU 30 SK1 VO +H
SK2 SGO
+Bu 29 SK3 SGM
15 -H
SK3 SGM
SK2 SGU
SK4 SGO
SK1 Vu
Vo
s v Z * 1 2 3 4 5 SK4 SGU
L LS1 VU
LS2 ZIMP
M 27 0 1 : 1 2 SKB1 Turstop
+H 26 SKB2 Rufsim.
Lebenslicht Turblock
IMP+ Testmodus Aussen-Aus
IMP- 8
-H 23 JP12 JP11
17 4 3 16 2 1
2630
7 /1
Impulsteiler
A1 /2
/4
1 2 3
X21
Z1 JP1
/8
/16
6 5 9 N2
A2 JP13/ Notrugbetrieb /32
HCPL
3700
/64
Z2 JP14 L4
19 /128
Notruf JP2 4 5 6 L4
AL Bundig-Anzeige
HCPL
NI
3700
NL Datum Low-EPROM Puffer- SK1
Relaisplatine Segment-Anz
JP10
+NV 16 Batterie SK1
7 8 9
X5
HCPL
15
3700
ACCU RAM SK2 5 SK2
14 Datum High-EPROM loschen
-
EIN 9 SK3
* 0 #
HCPL
3700
AUF 13 14 SK3
AB 11 10 11 12 SK4
X23
AA/SAK 10 NA
HCPL
3700
ULN 2804 ULN 2804 SK4
U2 ULN 2804 ULN 2804 ULN 2804
MAX/ 1 SK4*
REGST JP3 JP4
U1 XK1
MIN 6
-H K42 K41 K31 K17 K24 K23 K22 K21
K7 K6 K5 K15 K14 K13 K12 K11
3 Ture2- Ture1-
JP5 freipr. freipr.
Notruf Vo/Ab
Ture2- Ture1-
Kontrolle
Stern./
Auf
Langs./
Ab Schnel
GR/6 Relais2 Relais1 Auf Zu Auf Zu Dreieck Fahren
+H 1
XK2
21 18 15 13 11 9 5 1 9 2 1
XK5 XK4
-H Ein Ab O C S O C S +HU Vo OT ST LGS SCH V2
Auf -H DR AUF AB
Ruckholen REL2 REL1 SS1 Hupe AB TURE 2 TURE 1
Coding jumpers:
Jumper Function Plugged Not plugged
active (with LiSA as an emergency call
JP1 if no voltage at XK1.15 / .16 V, system / emergency lowering in case of inactive *)
Lisa10 is fed by storage battery hydro-elevators)
JP2 levelled-indication indicator = lamp indicator = LED *)
JP5 group operation for duplex no group relay required for groups always group
relay required
JP6 door limit switch door limit switch „door 1-open“ bridged
JP7 door limit switch door limit switch „door 1-closed“ bridged door limit switch on APO
bridged or connected
JP8 door limit switch door limit switch „door 2-open“ bridged
COMPLETE LIFTS PAGE – 6 –
LiSA CONTROLLER
Functional elements:
[1] = indication of the car position. Positions > 9 and < 20 are indicated with an additional dot.
[2] = indication of the operational status
[3] = indication of signal switch, pulse from pulse generator, door stop, call simulation, door blocking and
external control off
[4] = indication of safety circuit tapping, light barrier and closing force limiter for 2 doors, stand-by and test mode
[5] = reset key
[6] = programme-EPROM’s (2 * 256 kByte)
[7] = opto-coupler for pulse from pulse generator
[8] = potentiometer for contrast-setting on LCD-display
[9] = group relay ( Attention to mounting position: Dot to be below)
[ 10 ] = driver –IC ULN2804: activation of the free programmable relay
[ 11 ] = driver –IC ULN2804: switching of the emergency light
[ 12 ] = driver –IC ULN2804: activation of door relay and segment indicator
[ 13 ] = driver –IC ULN2804: activation of the emergency call relay on the LiSA-TAE-card and activation of
the high speed relay
[ 14 ] = driver –IC ULN2804: activation of relays up, down, slow, delta, Vo/down
[ 15 ] = 1 opto-coupler for tapping of car light and 4 opto-couplers for tapping of safety circuits
[ 16 ] = driver-ICs for serial data transmission to the car and to the LiSA-matrix displays
(left-hand IC: SN75176, right-hand IC: SN75179)
[ 17 ] = parameter-EEPROM (24C09 / 24C08)
COMPLETE LIFTS PAGE – 7 –
LiSA CONTROLLER
All functions that are not laid on the LiSA10-7 (over temperature, governor malfunction, etc.) are executed via
LBM-09.
The LBM-09 can be installed either in the control cabinet, in the elevator well or in the cabin.
It is connected to the control unit by the 3-pole LiSA-bus. This bus consists of two lines for the power supply to the
modules and one line for signals.
Physically in the elevator well, it consists of the special 3-pole LiSA-bus-cable (3 * 1,5 mm²) LBC-03.
3 lines of the travelling cable are required for connection to the cabin.
A novelty in the elevator industry is the special connection technique, connecting the bus modules via LBC-03 to
the control unit.
The LBC-03 follows the conception of ASI-bus cables (used in industrial applications), i.e. connection is done by
penetration.
Remark: It will also in future be possible to apply the IO16-pcboard in the control cabinet, either instead of
LBM-09 or even simultaneously with LBM-09.
COMPLETE LIFTS PAGE – 8 –
LiSA CONTROLLER
Schaltschrank
(control cabinet)
LBC-03
3 3
XK4 XK1 XK2
2 2 - 1 1 - 1 L
1 1 S S Im
Etagenbus Fahrkorbbus + + So
HANGEKABEL Im N+
(travelling cable)
Sm
VO 34 5 M Su
VU LiSA-Bus-Driver
XK5 1 Vo
SGO 1 14XK3
SGM Vu
SGU 30 15
Led-ready Ec
+BU 29 PE
L data-transfer LiSA-10 - LBD
M 27 X1 Busad-2
+H 26
IMP+
IMP- 24
-H 23
A1 (alternativ connection of travelling cable, if Busad-1 is not used)
Z1 Ec Vu Vo Su Sm So Im L M N+ + S -
A2 alternativer H ngkabelanschlu , wenn Platine Busad-1 nicht
Z2 19 verwendet
AL
NL
+NV 16 PE 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
XK2
16
Inspektionskasten:
inspectionbox:
Schacht 1 13 10 7 4 1
XK2 XK1
(shaft) Cal Vu Su So L M + -
LiSABUS L4 fan 16 15 14 Ec Vo Sm Im N+ S
Kabinenlicht
Cab.-Light
1
Ture2-Auf
Ture1-Auf
Ventilator
D2-Close
D1-Close
Ture2-Zu
Ture1-Zu
D2-Open
D1-Open
fan
X1
Fahrkorbtableau
XK9
(cabin-panel)
J1 NR/Ec APO-12
LiSABUS
1
LiSABUS
1
LiSABUS LiSABUS X1 X1
LiSABUS
LiSABUS LiSABUS
1 1
X2 XK2 X1 X1
X1
X3 X2
COMPLETE LIFTS PAGE – 9 –
LiSA CONTROLLER
2.1. LiSA10-7
Modifications of the LiSA10-pcboard (see the following picture):
- As an alternative to the 15V supply, now 24V can be supplied (plug XK5, pin3), i.e. control voltage of the entire
elevator plant can now be executed in 24V (this is forcing, if the bus functions are used).
- Instead of the fourth IO-board (IO49 – IO64) now a bus connector board (= LiSA bus driver LBD-02) can be
plugged. Principally, IO-boards need not be used anymore.
- Plug XK1 has been extended by a 220V-connection for the contactor-opening monitor (pin10 – SAK).
Evaluation of this function is thus significantly safer than the 24V contactor monitoring used up to now.
- For DCP-connection (= serial selection of inverters), an additional RS485-interface will be made available at
plug XK6. This interface is being prepared at present.
Remark:
Consequently to the future control voltage of 24V, a new power unit will have to be applied.
It is a unit to be installed on a top hat rail (good aeration). For normal cases, it can always be regarded at as
over dimensioned (24V, 5A) and will therefore, in comparison with the presently used unit, have a great chance
for the long life indicated in the data sheet (MTBF; 8,5 years).
3 4
JP6,7,8,9
HANGEKABEL
Fahrsimulator
+H 42 T1auf
3 +24 +24 3 1 1 1 1 1 1
-H X41 X33 X25 X17 X9 X1 T2auf
T1zu
F26 2 S S 2 T2zu
X4
1 -H -H 1 41 33 25 17 9 1
MATRIX-ANZ
F25
42 34 26 18 10 2
X3
F24
X2
IO-16
IO-16
IO-16
Etagenbus Fahrkorbbus 43 35 27 19 11 3
F23
44 36 28 20 12 4
1
F22
45 37 29 21 5
1
F21 35 13
X10
46 38 30 22 6 6
HANGEK.
VO 34 +H2
LiSA-Bus-Driver 47 39 31 23 7
SN75176
SN75179
VU +H2
SGO 48 40 32 24 8 -H
SGM 3 +24 1
Strom
SGU 30 SK1 VO
SK2 SGO +H
+Bu 29 SK3 SGM
SK3 SGM
SK2 SGU
SK4 SGO
SK1 Vu
Vo
s v Z * 1 2 3 4 5 SK4 SGU 1 -H
L LS1 VU
ZIMP
M 27 0 1 : 1 2
LS2
SKB1 Turstop
+H 26 SKB2 Rufsim.
Lebenslicht Turblock
IMP+ Testmodus Aussen-Aus
IMP-
-H JP11
23 JP12
2630
/1
Impulsteiler
A1 /2
/4
1 2 3 10 SAK 2
X21
Z1 JP1
/8
/16
/64
Z2 JP14 L4
19 /128
Notruf JP2 4 5 6 L4
AL Bundig-Anzeige
HCPL
NI
3700
JP10
+NV 16 Batterie SK1
7 8 9
X5
+ 2
HCPL
3700
AUF SK3
AB 11 SK4
X23
AA/SAK 10 NA
HCPL
3700
(1)= Connection of the 24V feed (15V feed also still possible at XK5, pin2)
(2)= Connection 230 V for contactor-opening monitor (SAK)
Conditions:
- Jumper JP13 in position 1 and –H connected with PE.
- New parameter (in parameter block 000*)
„LiSA-Typ (LiSA10-5 / LiSA10-7ohne220VSAK/ LiSA10-7mit220VSAK)“ is parameterized
with 2. (ohne = without; mit = with)
Remark:
COMPLETE LIFTS PAGE – 10 –
LiSA CONTROLLER
JP13 in position 0: Signal at pin 10 of XK2 (AA/SAK) is being evaluated with different meanings, depending of
whether the elevator plant has been executed according to German elevator standard TRA or European elevator
standard EN81.
TRA: landing controls off
EN81: contactor-opening monitor (parameter LiSA-type with 1 programme.)
(3)= Connector for LiSA-Bus-Driver (LBD-02)
(4)= Serial interface XK6 (RS485) for DCP (software still being prepared)
(5)= Reset-button (distinction mark on the surface of LiSA10-7)
The jumpers JP3 (rapid forced cut-out) and JP4 (muting of safety relay) have been removed.
For compatibility reasons with LiSA10-5, there are still connectors available for:
- IO16-boards
- 15V feed
- connection of matrix- und segment indicators as well as
- regular travelling cable.
LiSA-Bus-Driver (LBD-02):
The LiSA-Bus-Driver is the interface between LBC-03
LiSA10-7 and LiSA-Bus
- Reading out data from the LiSAbus-
3 3
modules of landings and cabin
2 2
and transferring them to Lisa10-7 as 1 1
well as vice versa: Etagenbus Fahrkorbbus
- Reading out data from LiSA10-7
and transferring them to the LiSA
bus modules. LiSA-Bus-Driver
Led-ready
data-transfer
COMPLETE LIFTS PAGE – 11 –
LiSA CONTROLLER
2.2. LiSA-Bus-Modul (LBM-09)
Layout and functions:
- 8 short-circuit proof (except continued short circuit) in-
Address-Jumper
/outputs (IO´s) at XK1 and XK2 resp. X1. If LBM-09 is used
as a landing bus module, the first 4 IO´s (XK1) have got defined
functions. Otherwise, the IOs are freely programmable.
Landing Module: Pin1: up-button, LiSABUS
1
Pin2: down-button, X1
Pin3: direction up,
Pin4: direction down XK4
- 8 IO-Status-LEDs XK3
- 1 LED (L1) for operation mode indicator R1
LED is shining: LBM-09 is OK
LED is flashing: LBM-09 is defective and cut from the bus by R1
- X1: connector for LiSA-components. XK5
- XK3 and XK4: connectors for LBM-09 to the mother boards APO 12 XK1 XK2
resp. LF 10 in the cabin.
/F1 F5
- XK5: connector for LiSA-Bus-Displays
- R1: mini-relay cutting a defective bus module from the bus. /F2 F6
- By the jumpers JP1 – JP32 the addresses are to be set (0 – max. /F3 F7
63) /F4 F8
Addresses on the landing bus: LBM9
0 – 47: address range for landing modules. -H +24
48-56: address range for modules in the control cabinet.
Addresses on the cabin bus:
0 – 47: address range for landing modules, door side 2 (selective door control as from the landing)
48-60: address range for modules in the cabin.
For easy configuration of the controls, furthermore the following boards are used.
They are adapter-boards resp. motherboards without electronic components:
16
COMPLETE LIFTS PAGE – 12 –
LiSA CONTROLLER
COMPLETE LIFTS PAGE – 13 –
LiSA CONTROLLER
Hangekabel - travelling-cable
Emer.-Call
Notruf
Kopiersignale Sprechv.
selector-signals Intercom LiSA-Bus
Stecker / connector X3 :
16 15 14
1: Notruf / emerg.-call
2-8: IO s 1 13 10 7 4 1
9: -H XK2 XK1
10: +24
11: Notlicht / emerg. light Cal Vu Su So L M + -
L4 fan 16 15 14 Ec Vo Sm Im N+ S
12: Notvers. / emerg.pow.
13: Lautsp. / loudspeaker
14: Micro Vo
Stecker / connector X2 : KF6 KF5 KF4 KF3 KF2 KF1
1: Notruf / emerg.-call So
Kabinenlicht
Cab.-Light
1
Ture2-Auf
Ture1-Auf
Ventilator
D2-Close
D1-Close
Ture2-Zu
Ture1-Zu
D2-Open
D1-Open
2-8: IO s
Sm
9: -H fan Kopierblock
X1
10: +24 Selectorblock
Su
11: Notlicht / emerg. light
12: Notvers. / emerg.pow. Vu
13: Lautsp. / loudspeaker Im
APO-12
XK9
14: Micro
Impulsgeber
|
15-16: -H----LiSA-Bus (Anschlu?-Platine)
17-18: S ----LiSA-Bus puls-generator
+
19-20: +24--LiSA-Bus XK10
XK12
Vollast full Uberlast
Overload
|
full-load 1
I
Lichtschranke
Inspection Ie
|
10 Light-Screen
Ie SL (Shaft-Light) Ls(Lightscreen) fan
Inspection-Up (Auf) Iu
Iu if FI(Forcelimiter) Loff
Inspection-Down (Ab) Id Force-Limiter
|
Id Os(Open-Switch)
|
| 8
|
|
10 Light-Screen
Signalgeber-Oben So
signal-generator Force-Limiter
|
|
6 Switch
Os(Open-Switch) 1o
|
Close
Do(Door-Open) S f1 S
middle + Switch
|
4
Dc(Door-Close) f2
Signalgeber-Unten Su Com Door 2 Ture 2
signal-generator at
|
Do open auf
bottom + 1
XK4 1 Dc close zu
XK7
X3 14 X2 20
1 R2 1
XK12
XK5 NC
R1 1
Com
Ec _ El N+ L M N+ + S _ OI f1 f2 f3 f4 _ + NO
COMPLETE LIFTS PAGE – 14 –
LiSA CONTROLLER
2.2.3 Connection Board in the Cabin Operation Panel (LF12):
LF12 is the connection board for emergency light in the cabin operation panel.
With respect to the LiSA-bus-system, three additional slots have been foreseen for LiSA bus modules (LBM-08).
If the LiSA pushbutton system is applied, to connector X1 normally the following pushbuttons are connected:
emergency alarm button, door open and door close buttons, fan button, door-stop button, key-operated functions
and eventually the first cabin operation buttons.
All other buttons can be plugged directly to the LBM-09 via flat cables.
X2 is the connector to APO12. In addition to the functions on connector X1, it has been extended by the LiSA-bus,
i.e, APO12 in the inspection control box and LF12 in the cabin operation panel are always connected to each other
by a 20-pole cable only.
J1 NR/Ec
K1
LiSABUS LiSABUS
XK1
Ec
E-light
-
El
Leuchtfeld-Platine:
E-light
+
S
L-Bus
-
L
X2 XK2
14 20
B1+ B2+
X1 1 1
COMPLETE LIFTS PAGE – 15 –
LiSA CONTROLLER
3. LiSA-cabin bus:
(3): cBus: LiSA-bus of cabin – in the inspection control box resp. cabin operation panel there are LiSA bus
modules (use of APO12)
(4): sLBus+cBus: like sLBus, however,with an additional LiSA-bus for the cabin
(5): Lbus+cBus: like Lbus and cBus together
Depending on the number of bus modules, there are 96 IOs available in the cabin (IO65 – IO160). In total 12 bus
modules can be connected in the cabin. 4 bus modules with addresses 48-51 can be plugged to the motherboard
APO12 in the inspection control box and 2 modules (addresses 52 & 53) to the emergency light board LF12. The
IOs of the emergency light board are freely programmable, whereas those of the APO12 are assessed to functions,
except f1-f4.
IO74: input-force limiter door 1
IO75: input-door-open-contact door 1
IO76: input-door-close-contact door 1
IO77: output-door-open-command door 1
IO78: output-door-close-command door 2
IO79: output-activate relay cabin fan
IO80: output-activate relay cabin light
LBM-09 with Addr. 50:
IO81: input-light screen door 2
IO82: input-force limiter door 2
IO83: input-door-open-contact door 2
IO84: input-door-close-contact door 2
IO85: output-door-open-command door 2
IO86: output-door-close-command door 2
IO87: not used
X3 14 X2 20
1 1 IO88: not used
LBM-09 with Addr. 51:
20
IO89: input - overload
IO90: output - overload
IO91: input-door-open-button door1 / 2
IO92: input-door-close-button
IO93: freely programmable IO
IO94: freely programmable IO
IO95: freely programmable IO
IO96: freely programmable IO
COMPLETE LIFTS PAGE – 16 –
LiSA CONTROLLER
4. Functions:
All functions are contained in one single programme version. Basically, the previous functions remain still available when
the scope of functions is going to be extended, i.e. old programme versions can always be replaced by new ones.
The activation of all functions is possible by means of the control-integrated keypad, by a hand terminal or, even more
conveniently, by a PC (Laptop/Notebook).
LiSA - keypad:
Input of commands and switching-on from parameter to parameter upon parameter processing is always
closed with the * - key
All inputs can be aborted by means of the # - key. Upon parameter-setting a short push on the # -key causes
#
paging down and a longer pressing causes a jump to the end of the parameter block.
SO
ones, a special LiSA encoder is counted on top of the SM
car. SU
magnet bottom
pre-limit
rail switch
CAR
magnet LEVEL 0
20cm
bottom
limit
switch
Weight
fixing bottom
of shaft
COMPLETE LIFTS PAGE – 17 –
LiSA CONTROLLER
4.1.2. Learning-run
During the learning-run the following values are established:
- all landing distances
- pulse constant in pulses / m
- rated speed
- deceleration paths up and down resp. distance of prelimit switch magnets from limit switches.
- braking retardation up and down.
Note: While with pulse method – after carrying out the learning-run – only slight corrections at the paths of
deceleration and braking retardation are required.
Proceed as follows:
Put the elevator to the bottom landing
- the centre signal switch must be within the zone
- the car should be unloaded and the counterweight already be provided with the correct weights.
Start of learning-run: Set 100*
- Prior to the start of the learning-run the LiSA shows "L" in the lefthand element of the 7-segment indicator
(operational condition). .
- Now the elevator runs with high speed to the top correction position. On this occassion the landing distances and
the rated speed are established.
- As a control, the travelling speed is permanently indicated righthand-below on the display
- At top correction switch the elevator decelerates and stops in the top landing
- After that, the elevator runs again with high speed to the bottom prelimit switch, decelerates and stops at the
bottom landing.
After termination of the learning-run the following message appears on the display:
Parameter to be overwritten ? (0/1)
If the question is answered with "1", the learnt values are immediately memorized in the EEPROM and the LiSA-
control shows the message:
Wait until parameters are memorized
In parameter group learning-run values (009*), the values established upon learning-run are registered.
COMPLETE LIFTS PAGE – 18 –
LiSA CONTROLLER
4.1.3. Parameter processing
All parameters and commands can be set either on the LiSA-keypad and on the PC/Laptop as well.
The parameters are subdivided into 11 groups. Selection is made by setting a 3 or 4 digit number and is closed by
the *-key. During parameter processing, switching from one parameter to the other is also done by this key.
Paging down is effected by a short push on the # - key. A long pressure on the #-key causes a jump to the end of
the parameter set.
Note: If the question "Parameter to be overwritten" is answered with "1", all parameters will be memorized,
not only those of the group that just has been processed.
Parameter groups :
0 0 0 General parameters of the installation
0 0 3 Input addresses
0 0 4 Output addresses
0 0 6 Relay addresses
0 0 7 Indicator functions
0 0 9 Learning-run values
0 0 1 0 Special parameters
COMPLETE LIFTS PAGE – 19 –
LiSA CONTROLLER
4.2. Description of Parameters
4.2.0. General Elevator Parameters: (Call in on LiSA-key board by typing 000*)
Elevator Type (Ropetraction/Hydro/VV/VF-control) :
(0) : Traction elevator, uncontrolled, 1-speed, 2-speed
(1) : Hydraulic elevator
(2) : VV/VF-controlled traction elevator
Interrogation in case of hydro-elevators:
Beringer Elevator Control Valve (0/1)
(0) : no Beringer LRV
(1) : Beringer LRV
- to minimize the cost, the delta-contactor is used jointly for the downward travel.
- inspection travel can be carried out with half the rated speed.
Interrogation in case of VV/VF-controlled traction elevators:
VV/VF- control (All / Dyn / Si / LiFU / LM/Die / Yask) :
Selection of driver for various controllers and inverters
(0) : Selection of all types of controllers except those following below
(1) : Dynatron-S, Dynatron-F, Dynatron-2000, VF30 (Schindler-Controller)
(2) : Binary control of Siemens-inverter (only applicable for elder inverters make KEB/Siemens with binary speed
selection).
(3) : Loher-frequency inverter
(4) : Elevator Material (Struckmeier) – inverter
(4) : Binary selection of FUJI-inverter
(5) : Dietz-inverter (only for Vektordrive) – to be set to "0" with Maxidrive!
(5) : Dietz-inverter (only for Vektordrive) – to be set to "0" with Maxidrive!
(6) : binary selection of Yaskawa (KONE) inverter
Binary selection:
st
travel speeds are selected by means of the binary code at the first three outputs defined by
parameter “1 output inverter signals”
Interrogation in case of hydro-elevators:
Overtravelling (no /valve /Motor / ALGI - ELRV):
Selection of type of engagement for different hydraulic systems
(0) no overtravelling
(1) Valve overtravelling:
In upward travel the up-valve is for a preset period longer engaged than the pump motor.
This leads to a softer stopping with e.g. the Oildynamic hydraulic block (GMV).
In parameter-set general elevator times (001*) "overtravel vale / pump".
(2) Motor coasting:
The function is similar to the valve overtravel. The difference is, that in upward travel first the control for the
UP-valve is switched off and the pump runs longer for the overtravel time. With many hydro-systems (Algi,
Beringer ..) stopping will also be softer with this function.
Additionally required parameters:
- In parameter-set General elevator times (001*): "Overtravel valve / pump".
- In parameter-set Relays addresses (006*) : "Rel.- Overtravel – pump"
(3) ALGI - ELRV:
For the new electronic elevator-regulating valve of ALGI a special control method is required.
Upward travel:
After disengagement of the UP direction signal the pump motor is switched off only after elapse of the
overtravel time.
Downward travel:
After disengagement of the DOWN direction signal the activation of the DOWN valve is switched off only when
the overtravel time has expired.
Additionally required parameters:
- In parameter-set "General elevator times" (001*): "Overtravel valve / pump“.
- In parameter-set "Relay addresses" (006*) : "Rel.- Overtravel – pump“
Stopping with the middle signal generator (0/1):
Selection of the signal switch for starting the deceleration
(0) : Starting of deceleration by that outer signal switch which has entered the zone at last (SGO / SGU), i.e. in
upward travel SGU and in downward travel SGO.
(1) : Start of deceleration by the middle signal generator (SGM)
Braking(stopping) by the pulse-method:
This method should be used wherever possible, despite the somewhat higher cost for an additionally required
pulse source. Besides of the convenience in adjustment, the steps occurring upon stopping when the time-
method is applied will be prevented.
For hydro-elevators, the choice of stopping with the middle signal generator allows, beyond that, an adjustment of
the relevelling independently from the stoppage. Then, positioning of SGO and SGU can be related to SGM so,
that even in case of a very low step (appr. 10 mm) the relevelling process will be started. For uncontrolled
traction elevators, the less sophisticated selector block (without SGO and SGU) can be used.
COMPLETE LIFTS PAGE – 20 –
LiSA CONTROLLER
Braking (stoppage) by time-method:
(Described only for reason of completeness). With hydro-elevators, when the time-method is applied, stopping
should basically be carried out with SGO resp. SGU, as otherwise the unavoidable load-dependence will result in
stopping inaccuracies. The same goes for uncontrolled traction elevators. Although here the use of selector
blocks with 3 detectors is not mandatory required, for reasons of stopping accuracy this solution should be
favourized.
Parameter "stop with middle singnal generator“ allows 2 solutions:
If the stop is made with SGM, an "utopic“ long deceleration can be set, as with the entering of SGO resp. SGU
(i.e. prior to the end of the deceleration process) the traveling signals are switched off anyway and the car will slip
into its leveled position. Naturally, this will work only, when SGO / SGU are "shifted together“ so, that the
respective slip is available.
2. The case of not stopping with SGM is a bit more favorable with regard to the adjusting of the levelling
accuracy, as here the adjustment of SGO and SGU is less critical. In this case, they are to be positioned still
closer to the SGM so that the stoppage is made after elapse of a relatively short deceleration. While in case 1
SGO and SGU are to be placed in accordance with the required slipping path, inaccuracies can be corrected in
case 2 by the deceleration.
Deceleration (time / fix / pulse):
Selects the signalizing method for initiating of deceleration (switch-over from high speed to low speed)
(0) : Signalizing method = time method. Switch-over comes after elapse of a set time (= time for the deceleration
path UP resp. DOWN, with long-distance travels and with high-speed travel in case of landing-to-landing
travels)
(1) : Signalizing method = fixed point. Switch-over is effected on invariably defined points (= magnets) in the well.
Attention: not applicable in case of overlapping deceleration paths!
(2) : Signalizing method = pulse method. Switch-over is effected following a preset number
of pulses, generated by a path-measuring system or a digital tacho.
In the landing next to the destination landing, provided that there is a sufficient interlanding distance, if SGM goes
off the inductor plate, the value preset by parameter "deceleration paths UP resp. DOWN", will be mapped by the
loading of a timer (with time method) or by the loading of a counter (with pulse method). After timer resp. counter
have run down, switch-over from high speed to low speed is effected.
Braking (Time / fix / pulse) :
Selection of signalizing method for stopping (switching off the travelling signals)
(0) : Signalizing method = time method. Stopping comes after elapse of a set time (= time for the deceleration
path UP resp. DOWN)
(1) : Signalizing method = fixed point. Stopping is effected on invariably defined points in the well (= magnet will
switch the middle signal generator SGM).
(2) : Signalizing method = pulse method. Stopping is initiated following a preset number of pulses, generated by
a path-measuring system or a digital tacho.
(3): hidden function – stopping is monitored in addition by the pulse method.
In connection with parameter “emergency stop after entering the landing zone after ? ms” (parameter set 002*),
stopping is monitored in addition by the pulse method.
No. of landings:
In case of group elevators, here always the maximum number of landings served by one group is to be
entered, irrespective of the real number of landings of that elevator for which the parameterizing is made.
No. of cars:
In case of groups, i.e. no. of cars > 1, the following parameters will be interrogated after that:
Car in group:
All cars in a group must get their own number, in the sequential order in which they are interconnected via the data
lines. Among one group it might happen that an elevator, owing to insufficient well length, can not run into the top or
bottom landing. The following parameters are considering such circumstances.
Bottom landing:
In the normal case, the bottom landing is also the 1st one. If the well starts one or more landings higher, this landing
has to be defined by the parameter "bottom landing“.
Top landing:
In the normal case, the top landing is also the last one. If the well ends one or more landings lower, this landing has
to be defined by the parameter "top landing“.
Interrogation in case of group elevators:
Door opening in group not simultaneously (0/1):
Presetting, whether upon pressing the landing call button only one elevator shall open or all elevators standing on the
respective landing.
(0) : opening of doors of all elevators
(1) : opening of door not simultaneously, i.e. only with that elevator on the landing that has the lowest number in
the group
COMPLETE LIFTS PAGE – 21 –
LiSA CONTROLLER
No of accesses (1/2): rd
Even with elevators having three accesses only 2 accesses can be set. For the switchover to the 3 access
side, position-relays are used.
(1) : one access side
(2) : two access sides
No of push buttons on landing (1/2):
(1) : one-button control
(2) : two-button control
The following parameter is available after introduction of LiSA 10-7
(approx. Jan. 2003) Starting with this version, it is possible to select the LiSA-bus.
LiSA-Bus (No / sLbus / Lbus / cbus / sLbus+cbus / Lbus+cbus (0..5)):
(0): without LiSA-Bus
(1): sLbus: small LiSA-landing-bus – max. 64 Ios in line like on the IO-boards. Consequently a maximum of 8
bus-modules is connected.
(2): Lbus: LiSA-landing-bus – like sLBus and additionally one LiSA-bus-module at each landing.
(3): cBus: LiSA-bus for the cabin – in the inspection control terminal resp. cabin control panel there are LiSA
bus-modules (APO10 is used).
(4): sLBus+cbus: like sLBus and additionally a LiSA-bus for the cabin.
(5): Lbus+cbus: a combination of Lbus together with cBus
LiSA-bus has been newly developed. Connection of the bus-modules to the elevator control and among each other is
done by means of 3 parallel running lines. Two lines are for voltage supply and one for data transmission.
Main landing
- In case of parking mode VarEt and Hhalt (see parameter "parking mode“) the main landing will be assigned with
priority.
- In case of one-button control with direction-dependent call cancellation (see parameter “Direction depending car call
canceling“) the collecting direction is defined by the main landing. All landing calls from the main landing and the
landings below are executed in upward direction. Consequently, landing calls from above main landing are executed
in downward direction.
- In two-button groups with varying no. of landings in the lower part, the definition of the main landing makes, that all
landing calls from below main landing, incl. the down call in main landing itself, are assigned to that car which will run
to the lower part.
Forced stop
The forced stop is for that landing, in which
- at any travel when this landing is passed-by a stop is made, or
- only when passing-by in downward direction, or
- only when passing-by in upward direction.
The respective function can be set by default of the respective value for the forced-stoppage landing:
forced stoppage = 0 : no forced stoppage
forced stoppage > 0 and <= no. of landings: car command for the forced-stoppage landing
forced stoppage > no. of landings and <= no. of landings * 2: landing call DOWN in forced-stoppage landing -
no. of landings
forced stoppage > no. of landings * 2 : landing call UP in forced-stoppage landing – no.of landings * 2
Parking mode (none / FixEt / Zone / VarEt / Hstop):
Selection of parking mode.
After expiring of parking-time, a parking landing is approached according to parking mode. The door(s) will not open
on parking level, if
– parking is made with doors closed, and
– no further call is registered for that landing.
Additionally required parameters for all parking modes:
In parameter-set General elevator times (001*): "parking time“:
(0) : Parking not set
(1) : Selection of a fix parking landing for normal and clock-controlled travel.
The following parameters have to be set:
Parking landing with normal travel:
Parking landing with clock-controlled travel:
Parking landing with clock-controlled travel 2:
(2) : Distribution of the elevators in parking zones (with elevator groups), with no elevator being assigned to a
specific parking zone. Always that elevator will run to the parking zone after elapse of the stay-time, which stands
closest to it, provided it is in a zone that is already occupied. Always the landing in the middle of the zone will be
occupied. The no.of zones correspond to the number of cars in the group, e.g. 2 zones for duplex groups, 3 zones
for triplex groups, etc.
COMPLETE LIFTS PAGE – 22 –
LiSA CONTROLLER
The
st
following parameters have to be set:
1nd Parking zone up to landing =
2rd Parking zone up to landing =
3 Parking zone up to landing =
(3) : Distribution of the elevators in varying parking landings (in case of elevator groups), with no elevator being
assigned to a specific parking landing. Always the elevator standing closest to it will run to the parking landing after
elapse of the stay-time, unless it is already parking on a parking landing.
The following parameters have to be set:
1st Parking zone =
2nd Parking zone =
3rd Parking zone =
Important: the main landing (see parameter "Main landing") is identical with the lowest parking landing:
The lowest parking landing ("Main landing") has the priority to being occupied, i.e. when the main landing is
unoccupied, an elevator that has already taken its parking position can leave this and run to the main landing.
(4) : Occupation of the main landing.
If the main landing is not occupied, that elevator that is situated nearest runs to the main landing.
In case of the main landing being occupied the other elevators don't perform parking runs.
in case of a parking-run the display shows for the destination landing a "P“ instead of "Z“
the elapse of the parking-time can be shown on the display (right-hand on top) by setting 4*
For synchronizing (position monitoring) two magnets are mounted in the well and two bi-stable magnet switches on
the car (more exactly: on the selector block) (top pre-limit switch VO and bottom pre-limit switch VU). The position
of the magnets is communicated to LiSA by the two parameters below:
Corrective position bottom:
Indication of the position where the magnet for the corrective position below is. Thendvalue to be set is identical with
the last landing that has been passed-by in downward travel. This is normally the 2 .
With short distance landings or high-speed elevators it might be necessary to place the magnet one or two landings
higher (corrective position below = 3 or higher).
Corrective position top:
Indication of the position where the magnet for the corrective position on top is. It is absolutely necessary to take care
that the magnet is mounted with sufficient distance from the terminal landing, so that the elevator - in case of a
search-run with high speed or of a learning run - comes to stop reliably in the terminal landing.
A search-run with high speed will be carried out always when the parameter "correction next stop“ is set to 0 (no
correction in next-above or next-below landing) and the elevator has to come to stop off-zone, for example
- after termination of the inspection resp. recall travel,
- after a reset,
- after termination of a travel without having reached the destination (SGM not in zone),
- after termination of a travel, having over-travelled the destination (SGM not in zone)
- after the reason for a probable out-of-service situation has been eliminated, or
- after an interruption of the safety circuit immediately before arrival at the destination.
The search-run is not performed automatically, only after a call has been set.
Hinged doors (0/1):
(0) : no hinged landing doors
(1) : hinged landing doors
The contacts of the hinged landing doors must be looped-in into the safety circuit between terminals 94 and 95. Upon
start of the closing motion of the car door, the hinged door will be interlocked.
Direction-dependent call cancellation (0/1):
(0) : no direction-dependent call cancellation
One-button service: for each landing call an upward and downward call will be generated, i.e., this call will be
answered in both travelling directions.
Two-button service: each landing call is answered in the set direction, however always both calls will be cancelled.
Consequently,
– the negative effects of the wrong operation by pressing both buttons (landing being approached 2 times although
actually only one call is set) will be reduced, but
– if the calls actually had been set correctly, the landing call for the opposite direction must be given once more.
(1) : direction-dependent call cancellation
One-button service: for each landing call, depending on the position of the main landing, either an upward or
downward call will be generated and processed accordingly, i.e. downward call from landings
above main landing, upward calls from landings below main landing and from main landing.
See also parameter "inp. Additional upward call in main landing“ in parameter-set 003*.
COMPLETE LIFTS PAGE – 23 –
LiSA CONTROLLER
Two-button service: each landing call is answered in correspondence with the set direction. Upon approach on the
landing (at its deceleration point) the call in the actual travelling direction always will be cancelled
(if the elevator approaches upward to the landing, the upward call is cancelled).
The landing call in opposite direction will be cancelled only, when
– the next travel goes to the opposite (reversing of direction), or
– after elapse of the stay-time no further call was set.
Therefore, faulty operation ("double-call“) will have a negative effect if the travelling direction is going to be reversed.
Example: th
In the 5 landing the up and down buttons were operated. A car coming from below will cancel the upward call. In
case of a faulty operation (somebody has set calls for both directions)
th
the elevator
- after answering to the calls from landings higher than the 5 - will unnecessarily stop again in downward direction.
If there was no faulty operation, however the person that has set the downward call had also entered the car
before (which happens frequently), the elevator will also stop again without necessity.
Note: "Double-call":
In the LiSA-software a double-call suppressing device is include. While one button is getting pressed, acceptance of
a call for the opposite direction is suppressed for a period of one second.
Additionally, double-call can be "punished" by activating the free-programmable input "canceling double-call". This
can be made by putting a permanent wire-bridge (to –H) or by a switch. In this case, the first call will be cancelled.
Opposite direction call canceling with car command (0/1):
Avoiding unnecessary stops in case of double setting
(0) : no opposite direction call cancellation
(1) : opposite direction call cancellation
In case of double-call in a landing, very often that user will enter, who actually wanted to go to the opposite
direction. So, after entering the elevator, he will normally set a car command in the direction desired by him.
The opposite direction call cancellation will cause, that the landing call for the opposite direction is cancelled upon
start of travel, with the result that afterwards the elevator will not stop unnecessarily on this landing.
Universal control (0/1):
(0) : no universal control – normal collective control
(1) : universal control
Nowadays universal controls are found only in older elevator installations. Here, only one command is
accepted at a time – preferably a car command.
A landing call (only one) will be accepted, if
- the hinged door is closed,
- No car command is registered.
- 3 seconds have gone since elapse of stay-time – before that an car command will have priority
Relevelling (0/1):
(0) : no relevelling
(1) : relevelling activated
As the relevelling process normally runs with door open, a safety circuit (K5, K6, K7 plugged on the LiSA-main
card) must be available and a selector block with 3 signal generators (SGO, SGM, SGU) must be installed.
Relevelling is active upon
- Approach to destination landing, if the elevator does not come to stop on level (SGU / SGO off - inductor
plate). Here it might happen that it comes to a stop too soon (fault message "too high“ resp. "too low“ in the
fault memory) or too late (fault message "SoZone“ / "Su- Zone“ in fault memory)
- Creeping-down of the car when at rest or owing to rope stretch.
Interrogation in case that relevelling is set:
COMPLETE LIFTS PAGE – 24 –
LiSA CONTROLLER
(0): Correction travel to the terminal landing.
Destination of the correction travel always is the terminal landing whether it is the top or bottom landing depends on
the car position. If it is for example less than 3 landings to the top landig, it will travel to the bottom landing.
(1): Correction travel to the next landing.
The correction travel will be done at low speed to the next landing up (resp. down, if the car is within the reach of
the next pre-limit switch in up-direction).
(2): Correction travel to the landing above resp. below the next landing up resp. down.
The correction travel will be done at nominal speed to the landing above the next landing up provided that the car is
not within the reach of the next pre-limit switch in up direction. In this case it would be a correction travel to the
landing below the next landing down.
(3): Correction travel to the next landing at v1.
The correction travel is done at medium speed to the next landing up or down. This function is sometimes used
for fire-brigade elevators with big landing distances in order that the elevator will reach the next landing without
exceeding the travel time resp. within a reasonable time, if it has to start from a position between the landings.
Approach with open door (NO / YES / EswithTest)
(0) : Approach or relevelling with open door switched off
(1) : Approach or relevelling with open door switched on
Prerequisite for approach or relevelling with open door are
- The existence of a safety circuit (safety relay K5, K6, K7) on the LiSA-main card,
- Usage of a selector block with 3 signal generators (SGO, SGM and SGU) and
- Bridging of the door zone area (between terminal 12 and 14)
(2) : Approach or relevelling with open door switched on, with additional test of the approaching speed by
LiSA. (Possible only if LiSA is running with digital well information). By means of the following parameters
"max. speed on opening of door in mm/sec“, the threshold for the speed can be fixed. If the approaching speed
is not lower than the threshold when the switch in the centre is reached, opening of door during approach will be
suppressed. This can be recognized by a considerably, longer door opening delay (appr. 4 sec.).
Interrogation if approach with open door and test of approaching speed is parameterized:
COMPLETE LIFTS PAGE – 25 –
LiSA CONTROLLER
Selective door control – landing / car to be selected only if there are in at least one landing two
opposite access sides in at least one landing! Or in elevators with bus installation, if this facilitates
the installation of the landing bus.
Special elevator (norm / Aut / US / inclined):
Selection of special functions found in special types of elevators only.
(0) : Normal elevator
(1) : Car elevator – causes the evaluation of a presence-checking sensor, in case that parameter "input –
presence – checking sensor in elevator car (003*) has been programmed ( > 0). In case of an elevator with
2 landings, for that landing where the car is not an car command will be generated automatically.
Meanwhile, a special program for car elevators is available (see fig. 1)
(2) : Special functions for the "U- and S-Bahn" of Berlin
(3) : Special functions for the "Hochbahn" of Hamburg
Interrogation in case of car elevators:
COMPLETE LIFTS PAGE – 26 –
LiSA CONTROLLER
Figure 1
Protective Area to small (no / top / bottom / top+bottom):
Adaptation to insufficient over-travelling clearance.
(0) : normal protective clearance (overtravelling) above car
(1) : insufficient protective clearance (overtravel) above car.
(2) : insufficient protective clearance (undertravel) below car
(3) : insufficient protective clearance on top and below
In case of inspection mode it is achieved
- that in the landing next to the last resp. in the 2nd landing speed will switch-over
automatically from high to slow and
- that the correction switch (VO resp. VU) can not be overshot.
Protective light screen (0/1):
Functions of a protective light screen for cars without car doors.
(0) : not provided
(1) : protective light screen installed.
The difference between a protective light screen and a conventional light screen consists - apart from the special
functions required in case of an interruption of the light screen – mainly in the fact that its functioning must be tested
prior to each travel. For that, a safety circuit is required.
Most light screens available in the market are offered in 2 versions:
1. One relatively cheap "light" – version (e.g. Cedes-Light), without an inherent safety circuit.
This safety circuit (4 additional auxiliary contactors) can be order with M/s Schneider / M/s Klinkhammer / M/S
Haider together with the order for the control. This solution is considerably cheaper than the 2nd version
2. The protective light screen has an inherent safety circuit.
In the electronic system of the protective light screen there is a relay, contact of which is looped into the safety circuit
in place of the absent door contacts (between terminal 95 and 11).
COMPLETE LIFTS PAGE – 27 –
LiSA CONTROLLER
- if the protective light screen gets interrupted during travel (SK3 and SK4 are disconnected), provided that the
elevator is not already within the zone of the destination landing, the elevator stops immediately as the contact
of this relay will open. All calls are cancelled and landing calls will no longer be accepted.
- on the LiSA-display the text light screen interruption so long, until the contact will be closed again.
- after setting of any car command a test signal will be applied at the light screen in 10 seconds repetition rate.
This is done via a free-programmable relay (parameter "Relays Reset light screen" in parameter-set 006*).
- after the obstacle has been eliminated the light screen will close again and the travel continued.
- at first, the originally set destination landing will be approached.
- if the interruption was distant from the destination more than one landing, ongoing travel will be with the high
speed.
- in case of interruption next to the destination, the further process depends on the value of parameter
"correction next stop":
- Correction next stop = 0 (correction in terminal landing):
This value is to be selected if the destination cannot be approached with slow speed, i.e for one-speed
elevators and elevators with Dynatron-S or –F. With these elevator types, the destination is reached by a
"reversing travel", e.g. if in downward travel an interruption of the light screen occurs prior to reaching the
destination landing 5, the elevator will run to landing 7, the doors remain closed and only then the original
destination landing 5 will be approached. If the elevator has only 6 landings, landing 4 will be approached
first, and then landing 5.
- Correction next stop > 0 (correction in next landing):
This setting can be selected with all other elevator types that can continue to run with slow speed.
Door position in parking mode (open / closed / open + blocked / close +blocked) (0..3):
Selection whether the car is in the landing with doors open or closed
(0) : parking with open doors
(1) : parking with closed doors
(2) : parking with open doors and hinged doors blocked
(3) : parking with closed doors and hinged doors blocked
via the free-programmable input – (parameter "input – door position in parking mode" in "003*")
the door position in parking mode can be inverted.
Door motor - off ( no / close / open / close+open):
Selection, if and in which position the door motor shall be shut down.
This function is important particularly if there are no door limit switches installed.
(0) : door motor will not be shut down
(1) : shut-down of door motor in end position with door closed.
By setting a travel order the door motor will be engaged again.
(2) : shut-down of door motor in end position with door open
(3) : shut-down of door motor in end position with both, door open and closed
Inspection speed (V0 / Vi / V2):
Selection of the speed for elevator running in inspection mode.
(0) : inspection travel with creeping speed (Vo / Ve)
(1) : inspection travel with inspection speed – Vi (medium speed) . Naturally, this setting makes sense only, if
the elevator can be run with medium speed, i.e. in case of VV/VF controlled traction elevators (except:
Dynatron), Beringer-LRV etc..
If a key is installed for inspection speed-high, and applied to an input programmed with the function
"inp.-inspection-high", Vi (medium speed) will be activated by the depressed button and not the high one
(V2). When the button is released, the elevator will run again with creeping speed.
Additionally required parameter:
in parameter-set "relay addresses" (006*): "Rel.-running with V1 (VZ1) "
(2) : Inspection travel with high speed (V2)
This setting is admissible only when the speed 1,2 m/sec is not exceeded.
the recall travel is always performed with creeping speed.
in case of inspection and recall travel being engaged simultaneously, all travelling motions are
prevented. There is no priority of inspection travel.
Length of inductor plate:
Default length of inductor plate (zone).
On the default length of the inductor plates a couple of measurements are basing, which die LiSA
carries out for the well information, as e.g.
- Measurement of speed (indicated on the display right-hand below)
- Definition of the landing distances and the pulse-constant
In case of the presently exclusively used electronic signal generators of Pepperl & Fuchs or Secatec
(3 connection wires) a length of inductor plate is indicated, that falls short by 7 mm compared with
the actual length of inductor plate. That is 193 mm in case of 200 mm long inductor plates.
On the length of the inductor plate depends also the minimum landing distance:
Selector blocks without SGO or SGU: min. landing distance = inductor plate length + 50 mm.
Selector blocks with SGO or SGU: min. landing distance = 2*inductor plate length + 50 mm.
COMPLETE LIFTS PAGE – 28 –
LiSA CONTROLLER
The minimum achievable landing distance depends also on the speed.
So, for example, in case of an elevator with 0,3 m/sec and arrangement of the signal switches SGO, SGM and
SGU beside each other, a landing distance of 50 mm can be realized. Another elevator with 1,2 m/sec is run with a
landing distance of 90 mm.
Landing-to-landing travel with VE / V1:
Default, between which landings the elevator shall be run in slow resp. in approaching speed.
The length of the sequence of numbers to be set, consisting of zeros "0" and units "1" is lower by
one digit than the number of landings.
Example: In case of an elevator with 8 landings, between landings 3 and 4 only with VE / V1 shall be run:
Out of this results the following input "0010000".
if the elevator is run with the time-method, the same effect is achieved with parameter
"high inter-landing travelling speed 3 <-> 4" is set to 0.
Max. car commands without light barrier interruption:
Default of max. no. of travels initiated by car command without interruption of light barrier.
Upon reaching the set parameter value, all car commands will be cancelled.
(0) : function switched off. Please set always to 0, if there is no light barrier installed.
(1) : canceling of all car commands if after completion of a travel initiated by an car command
after elapse of the stay-time, no interruption of the light barrier was following
(2) : canceling of all car commands if after completion of two travels initiated by car commands
after elapse of the stay-time, no interruption of the light barrier was following
(3) : canceling of all car commands if after completion of two travels initiated by car commands
after elapse of the stay-time, no interruption of the light barrier was following
(n) : canceling of all car commands if after completion of three travels initiated by car commands
after elapse of the stay-time, no interruption of the light barrier was following
Ignoring of landing calls in case of x car commands:
With elevators having no full-load device a pseudo full-load function can be realized herewith.
(0) : function switched off. (Please set always to "0" if the function should be switched off).
(n) : no. of car commands at which the control changes into full-load condition, with the result,
that landing calls actually will be stored but will not be considered upon call assignment.
Single-side access entitlement (0/1):
Selection whether the car must be left at that access side from which it has been entered.
(0) : no restriction of access entitlement
(1) : single-sided access entitlement
With elevators having 2 access sides it is sometimes necessary to ensure that a user entering from e.g. access side
1 will leave the car on access side 1, too. This requirement is found mainly, when the elevator is used by 2 different
user-groups, (e.g.: on access side 1 is a bank and on access side 2 are funeral directors).
For a safe functioning the installation of a zero-load contact (presence-checking sensor in the car) and the
programming of the respective input in parameter-set input addresses (003*): "Inp. -zero -load" is required.
If the risk can be accepted that occasionally a visitor might enter from one access side and leave to the other one,
this feature can be dropped.
In order to distinguish from which access side a call has been set, another additional parameter "selective door
control - landing" out of the parameter-set 000* is required.
When the elevator is in parking position the door-status must be "closed".
Functional process (Status: no calls registered and doors closed):
- Landing call from access side 1: the car gets reserved at once for access side 1 until all car and landing
calls for this side are processed and the doors have closed again. Landing calls from access side 2,
however, will be stored.
- Landing call from access side 2: analogous to the process for access side 1
Light barrier output active (closed / open) (0/1) :
Selection of when the light barrier signal is active ( -H applied on the light barrier input).
(0) : normal case: light barrier contact is closed (active) in dead condition and with light barrier interrupted.
(1) : light barrier contact is closed with light barrier not active.
Contact of closing for delimiter active (closed / open) (0/1):
Selection of when the closing force limiter signal is active.
(0) : normal case: closing force limiter contact is closed (active) with closing force limiter operated.
(1) : closing force limiter contact is closed with closing force limiter not active.
Standard (EN81 / TRA / otherEn81):
Selection of the standard the control has to comply with
(0) : EN81: European Standard
(1) : TRA : German technical directives for elevators
COMPLETE LIFTS PAGE – 29 –
LiSA CONTROLLER
(2) : Others: Same as with EN81, but monitoring the contactors additionally if they open.
Differences in control functions between EN81 and TRA:
- Travel to top limit switch with hydro-elevators (entry "ESTop?" in the fault memory)
- TRA: after re-closing of the limit switch (elevator having lowered) the elevator will be operative again.
- EN81: after re-closing of the limit switch (elevator having lowered) the elevator will lower to the bottom
landing and remains inoperative (indication O = out of operation on the 7-segmentdisplay for the
operational status). The elevator goes back into operation only after a change of the operational
status or after a reset.
- Exceeding of the running time monitoring period (entry "TTElap / ATElap / STElap / RTElap" in the fault memory)
TRA: 10 seconds after exceeding the running time another attempt to travelling will be made.
If this attempt again leads to an exceeding of the running time, the elevator will remain inoperative).
Indication Z on the operational status indicator.
EN81: already after the 1st exceeding of the running time the elevator becomes inoperative and
can be put in operation again only after a change in the operational status
(e.g. activation of recall function) or after a reset.
- Significance of input AA at the left-hand rim of the LiSA10-card:
TRA: landing control-off
EN81: monitoring of contactor drop-out.
Interrogation in case of group elevators:
COMPLETE LIFTS PAGE – 30 –
LiSA CONTROLLER
The actually expiring time and the counter content will be displayed:
- Stay-time: STZ = ..
- Door-opening monitoring time: OKZ = ..
- Door-closure monitoring time: SKZ = ..
Stay-time following a car command (sec):
Door keep-open time after approach to the landing with car command, without a landing call having been set
Start: - Door-opening monitoring time expired
- Door-open limit switch interrupted (door completely open)
- Light barrier released after stay-time has expired already once
- With values >= 25 sec. after setting an car command, the stay-time is set to 2 sec.
End: - Counter expired.
- Door-closure button operated.
Stay-time following a landing call (sec):
Door keep-open time after approach to landing with landing call.
Start: (see stay-time following an car command)
End : (see stay-time following an car command)
The value of stay-time following an car command cannot be lower than that for the stay-time following a landing call.
In case of values > 25 sec., following an car command the stay-time will be set to 2 sec. If at the moment of
stay-time starting another car command is registered already, the stay-time will be set to 10 sec.
Door-opening monitoring time (sec):
Time to monitor the opening of the door.
Start : Start of door opening motion (door-opening command applied)
End : - Counter expired.
- Signal of door-open limit switch received.
If after elapse of the door-opening monitoring time the safety circuit (at SK4 or SK3 with door-open limit switch installed)
is not cut, another attempt will be made to open the door. After 5 fruitless attempts the door-failure will be recognized.
If the door operator has got a door-open limit switch, the default-value for the door-opening monitoring time is not
critical (10 sec will be a good value), as upon receipt of the door limit switch signal the stay-time is started at once.
If no door-open limit switch is installed, the value for the door-opening monitoring time should be set about as high
as the door would really need to open.
Door-closure monitoring time (sec):
Time to monitor the closing of the door.
Start : Start of door closing motion (door-closing order applied)
End :- Counter expired.
- Signal of door-closed limit switch received.
- Safety circuit closed (at SK3)
If after elapse of the door-closure monitoring time the safety circuit (at SK3) is not closed, another attempt will be
made to close the door.
After 5 fruitless attempts the door-failure will be recognized.
- All car commands are cancelled.
- In case of a single elevator all landing calls are cancelled. To groups it refers only then, if no group elevator is in
a position to accept landing calls.
- Adoption of the operational status "door failure" . on the display for the operational status (7- segment-LED on
the main card) "T" is indicated.
- Following an car command – in case of a single elevator also in case of an landing one – the door failure is
cancelled and an attempt is made to close the door.
Now, already after 2 unsuccessful attempts only, the door failure will be recognized,
- After totally 10 door failures in sequence the operation of the elevator will be suspended.
- In the fault memory only the first failure is entered.
The default-value for the door-closure monitoring time is not critical (20 sec will be a good value).
Only if there are two access sides with large doors, a higher value should possibly be set in order to
avoid that in case of a basically correct door-closure on one access side the 2nd access side is opened again
(if SK3 has not been recognized after elapse of the door-closure monitoring time).
Travel monitoring time (sec):
Time for monitoring of the elevator motion.
Start :
- The elevator starts running while being within the reach of the inductor plate
- The car runs off the inductor plate (travel monitoring time = parameter value), i.e. the travel monitoring
time is started again in every landing.
- The car runs into the reach of the inductor plate on the destination landing.
- After switching-over to slow speed (travel monitoring time = parameter value)
- Upon relevelling (travel monitoring time = 95, if relevelling is made from outside the zone)
COMPLETE LIFTS PAGE – 31 –
LiSA CONTROLLER
End :
- Counter-expired travel monitoring time exceeded:
- All car commands will be cancelled.
- In case of a single elevator all landing calls are cancelled. To groups it refers only then, if no group elevator
is in a position to accept landing calls.
- Adoption of the operational status "exceeding of running time" on the display for the operational status
(7-segment-LED on the main card) "Z" is indicated.
10 sec. after exceeding the running time – upon setting of parameter "Norm" to TRA (= 1) – another attempt will be
made. If again the running time is exceeded, the elevator operation will be suspended definitely.
If "Norm" is set to EN81 (= 0) the elevator operation will be suspended. With hydro-elevators the lowering to the bottom
landing will be still carried out. The elevator goes back into operation only after a change of the operational status or
after a reset.
Entries in the fault memory:
- Exceeding of travelling time upon starting: "StElap" (starting time elapsed)
- Exceeding of travelling time between landings: "TTElap" (travel time elapsed)
- Exceeding of travelling time on approach to destination: "ATElap" (approach time elapsed)
- Exceeding of travelling time on relevelling: "RTElap" (relevel time elapsed)
Door - stop time (sec):
Function to keep the car door open during a defined time interval (time for loading of the car)
Start : Operation of the door - stop button.
The activated door – stopping function is indicated by the flashing of the door – stop button registered light.
If the registered light shall not flash, i.e. if it shall be permanently lit (maybe because the impression of a
hazardous situation should be avoided) this can be achieved by presetting the door - stop time at > 600
sec. The actual door - stop time will then be door stop time – 600.
End :
- Counter expired.
- The door – stop button has been operated while flashing within a dark phase prior to the elapse of the
door – stop time.
- When 0 has been set for the door – stop time, the function remains active until it gets deactivated by
pressing the door – stop button.
Additionally required parameters:
"Input-door stop button" in parameter-set "input addresses (003*)" Being member of a group, the elevator will
no longer participate in the distribution of the landing calls, i.e., it will behave as if the landing control was
switched off.
Car fan running time (sec):
Duration of car fan running time after pressing the fan button in the car.
Start :
- Operation of fan button activation of fan relay. The activated function can be identified by the flashing
of the fan button registered light.
- Upon completion of a travel, if there is no input for the fan button programmed.
End :
- Counter expired fan relay switched off
- The flashing fan button was operated during a dark phase; before elapse of the car fan running time.
Additionally required parameters:
"input fan button" in parameter-set "input addresses" (003*) "rel.- car fan" in parameter-set "relay addresses" (006*)
If the elevator comes to stop between the landings, the car fan will be activated automatically
Parking time (sec):
Time interval after which the parking travel will be carried out.
Start : Start of door opening.
End : Counter expired.
Additionally expired parameters:
"Parking mode (....)" in parameter-set "general elevator parameters" (000*)
In case of a hydro-elevator that is positioned in the lowering landing, no parking time will be started unless
parameter "delay of starting /multifunctional parameter 2" has been set to "206" .
Expiring of the parking time can be made available by pressing 4* on the display. If the elevator is already in the
parking landing, the counter will be loaded with 2 seconds only.
Car light switch-off time (sec):
Fixing of time for switching-off the car light
Start :
- End of door-closing motion (SK3 indicated).
- End of stay-time with door-open position in parking mode.
End :(car light – off)
- Counter expired.
- Door will be opened again
Additionally required parameters:"Rel. car light off" in parameter-set "Relayadresses" (006*)
COMPLETE LIFTS PAGE – 32 –
LiSA CONTROLLER
COMPLETE LIFTS PAGE – 33 –
LiSA CONTROLLER
- set the switch-off retardation to a very low value (e.g. 5 ms) direction signal will be switched off immediately after
v0-signal. After that the travel contactors are switched off as soon as the time has elapsed that is set by this
parameter "interval between direction off and travel contactor off" (approx. 1500 ms).
Start: End of braking retardation
As soon as retarded switching off has elapsed.
Speed control starts slowing down to speed 0 (electric stop).
End: time elapsed.
LiSA switches travel contactors K3 and K3Z off.
Interrogation in case of traction elevators:
COMPLETE LIFTS PAGE – 34 –
LiSA CONTROLLER
- If the landing is full of smoke (fire detector in the fire-affected landing was engaged) the elevator will go to the
alternate landing
- If this is also full of smoke, attempts will be made to approach to a not smoke-filled landing, starting from the top.
- If all landings are smoke-filled the fire emergency landing will be approached.
The actual fire emergency or firemen travel (released by key switch) has the priority, i.e.
in this case the elevator approaches even to a smoke-filled fire-service landing.
Warning signal prior to door-closing command (sec)
Time between door-closed command and actual door closing.)
Prior to the actual door closing motion a signal can be released as an indicating text that the door is going to be closed
very soon, or e.g. with car elevators, traffic light being switched to red.
Start : Door-closure command.
End : Time expired –door will close
Additionally required parameters:
"output-text door closing" in parameter-set output addresses (004*) with text output, or
"output-traffic light in car" in parameter-set 004* in case of car elevators.
Interrogation, in case of hinged doors
COMPLETE LIFTS PAGE – 35 –
LiSA CONTROLLER
= 103ms: Function "doors remain closed" only on access side 2 active.
120ms and 150ms: The activation of an input defined by parameter "1ST input car selection
generates an car command with an extended stay-time (=keeping door open time). The stay-time
is variable and is calculated: stay-time = door reversal delay – 120 seconds.
> 150ms and 200ms: If parameter "output-nudging" has been programmed, the output
"nudging" is activated after door reversal delay – 150 sec.
In case of an interrupted light barrier (= nudging signal for electronic door control).
Early opening of door interlock (ms)
Time interval between unlocking of the car door and the actual door-open signal, or delay of door opening motion in
case of approach with early opening doors.
Start : Middle signal generator enters the domain of inductor plate of destination landing
End : Time expired – car door will open
In case of automatic car doors being additionally interlocked, opening "against the interlocking" can be prevented hereby.
The parameter intended for this function, however, can be also used advantageously for early opening doors if the doors
shall not open already with the engagement of the SGM.
Door-lock contact delay
Time interval between closing of hinged door and engagement of interlock (energizing of retiring cam)
Start : Hinged door closes (Sk2 closed)
End : Time expired – retiring cam energized
In case of hinged doors with dampening devices hereby can be achieved, that the doors will be bolted only if it is
ensured that they are in closed position.
Max. waiting time for landing call (sec)
Period by which is prevented that landing calls are not executed when operational conditions are undefined, or that a
landing call remains unanswered for an excessively long time.
Start : Landing call is acknowledged
End : Time expired – generation of an car command for the respective landing.
Each landing call gets a separate counter.
The length of the maximum waiting time / landing can be identified by call-up of error amounts (010*).
Reservation after landing priority travel (sec)
Fixing of reservation- period (change to car priority travel).
Start : Arrival at the landing where the key-switch is installed, with key already removed while elevator was
travelling, or elevator being already in key-switch landing when key will be removed.
End : Expiring of time.
Offers the opportunity for the user to carry out an car priority travel without key.
Door-lock contact delay
Time interval between closing of hinged door and engagement of interlock (energizing of retiring cam)
Start : Hinged door closes (Sk2 closed)
End : Time expired – retiring cam energized
In case of hinged doors with dampening devices hereby can be achieved, that the doors will be bolted only if it is
ensured that they are in closed position.
Max. waiting time for landing call (sec)
Period by which is prevented that landing calls are not executed when operational conditions are undefined, or that a
landing call remains unanswered for an excessively long time.
Start : Landing call is acknowledged
End : Time expired – generation of an car command for the respective landing.
Each landing call gets a separate counter.
The length of the maximum waiting time / landing can be identified by call-up of error amounts (010*).
Reservation after landing priority travel (sec)
Fixing of reservation- period (change to car priority travel).
Start : Arrival at the landing where the key-switch is installed, with key already removed while elevator was
travelling, or elevator being already in key-switch landing when key will be removed.
End : Expiring of time.
Offers the opportunity for the user to carry out an car priority travel without key.
Retardation of collective fault message:
Presets the interval after that the signal (relay or IO) reporting a collective fault message will be sent to the porter’s
lodge, if a fault has occurred.
By this retardation collective fault messages can be filtered out, that have occurred for a few moments only.
COMPLETE LIFTS PAGE – 36 –
LiSA CONTROLLER
COMPLETE LIFTS PAGE – 37 –
LiSA CONTROLLER
Deceleration-path up with Vnenn (mm):
Path for default of deceleration point on travelling UP with rated speed.
The deceleration-path UP defines that point at which prior to reaching the destination the leveling speed will be
activated, in order to bring the elevator to a safe stop in upward travel.
Deceleration-path down Vnenn (mm):
Path for default of deceleration point on travelling DOWN with rated speed.
Similar to travelling UP, however for direction DOWN.
Interrogation only with VV/VF-controlled elevators.
Emergency stop within ? ms after car has entered the landing zone:
If in case of pulse-controlled braking the pulse-service fails, the car passes by the landing. By this parameter
"emergency stop within ? ms after car has entered the landing zone", braking is additionally monitored. As soon as
the middle pulse-generator enters the landing zone, the time function is initialized in addition to the deceleration
function. There will be an emergency stop, if it elapses, unless there has already been a regular stop.
Interrogation if parameter "relay limit velocity" was set:
COMPLETE LIFTS PAGE – 38 –
LiSA CONTROLLER
Correction short normal travel up (%/mm):
Extension of short-normal-travel time in upward direction in case of time-method in %.
With Dynatron-S / -F reduction of brake application (KBR-signal) in mm.
Correction short normal travel down (%/mm):
Extension of short-normal-travel time in downward direction in case of time-method in %.
With Dynatron-S / -F reduction of brake application (KBR-signal) in mm.
Short normal travel means a travel where up to the landing next to the destination the rated speed cannot be
reached.
For elevators with short distance landings resp. high speed it might be required to initiate the deceleration already
after leaving the landing of start. That means, prior to arrival at the destination no landing is passed-by with normal
speed (same as with landing-to-landing travel). As for calculation of deceleration point a relatively simple procedure is
used (addition of the landing-to-landing times between start and destination), a too long creeping distance will occur
in reality. Therefore, by means of the correction value, the period of travelling with higher speed can be prolonged.
With Dynatron a problem similar to that with landing-to-landing travel can be resolved.
Limit for relative limit speed:
If the limit speed adjusted by this parameter is reached the "relay limit speed" is switched on.
Correction with reduced overtravel – up ( mm) :
In case of a reduced overtravelling distance it is required that on travels toward the terminal landing the high speed is
deactivated by a positive acting well switch, with switched-over to a slower intermediate speed. This already happens,
depending on the speed, 0.5 – 1.5 m before the pre-limit switch is reached. As a result, the elevator would run an
extremely long distance with creeping speed unless the disconnection of the medium speed is retarded.
By correction of the reduced overtravel this switching point is shifted toward the terminal landing by the respective value.
Correction with reduced overtravel – down ( mm) :
Same function as above describt, but for overtravel down.
Fast landing-to-landing (1 <-> 2) ms/mm:
Fast landing-to-landing (2 <-> 3) ms/mm:
Fast landing-to-landing (last landing - 1 <-> last landing) ms/mm:
Duration of high speed between individual landings in ms or in mm.
Start :middle signal generator runs off the inductor plate.
End : Time expired / way covered.
If the time-method is applied this entry is a must, value "0" however causes, that the elevator absolves the landing-to-
landing travel with slow speed. The correct value must be established by trial.
With regulated elevators that run by pulse method and do not achieve the rated speed, the value <0> shall be set only,
when the controller / inverter is prepared for running along speed-adapter curve (e.g. Ziehl Abegg) . In case of controllers
that do not have this ability (e.g. Dietz) a slower speed must be used. If Vrated or the activated intermediate speed is
reached, the parameter must be set to 0. In this case LiSA is able to calculate the length of the normal speed landing-to-
landing travelling distance autonomously, out of the landing distance and the deceleration path for that speed by which the
landing-to-landing travel is carried out.
Interrogation in case of <dynatron without KRB-points in the well:
Step correction has an effect on KBR- / KS-signal (0/1):
(0): step correction has an effect on KBR-signal
(1): step correction has an effect on KS-Signal
Normally Dynatron with step correction shifts the switching point of the KBR-signal.
If the KS-signal is used, however, the step correction should shift the switching point of the KS-signal. Function: The
KS-signal is recognized by the inverter at a fix point ahead of the landing level after cutoff of the KBR-signal. This fixed
point is situated aprox. 100 mm ahead of the flush landing level (middle signal-generator enters the landing zone).
Consequently, the inverter is enabled to change the speed curve, if the speed at this point deviates from the present
value. This function, however, cannot correct inaccurately aligned inductor plates. By means of the parameter described
it is possible.
Interrogation excluding the fixed-point method and the Dynatron with KBR-points in the well.:
Correction of inaccurately aligned inductor plates in upward direction.
Step-correction up in 2nd landing ms / mm:
Step-correction up in last landing ms / mm:
Correction of inaccurately aligned inductor plates in downward direction.
Step-correction down in 1st landing ms / mm:
Step-correction down in 2nd landing ms / mm
Step–correction down in landing next last one:
The deceleration will be corrected in all elevators, except those with Dynatron and KBR-relay.
In case of Dynatron a correction of the deceleration path is carried out (SKA-distance)
Standard settings that will not cause a correction:
With time-method: 500 ms
With pulse-method: 30 mm
COMPLETE LIFTS PAGE – 39 –
LiSA CONTROLLER
Values deviating from the above mentioned "zero-points" will cause a correction. th
Example: Elevator in upward travel has overtravelled the flush position in the 5 landing by 8 mm (elevator by 8 mm
too high). Therefore, in this landing the inductor plate must be shifted 8 mmth lower or the deceleration-UP must be
reduced by 8 mm by means of step-correction (step-correction UP in the 5 landing = 30 – 8 = 22 mm).
So, for example, with the time-method a value of 300 causes a reduction of the deceleration-UP for the step-correction-
UP in the 5th landing by 200 ms (=500 – 300), i.e., the elevator stops earlier.
While for the time-method the accurate value for the correction must be established by trial, it can be set directly in case
of the pulse-method. A value of 10 mm above "zero" (=30mm) leads to a prolongation of the deceleration by 10 mm and
a value of 20 mm results in a reduction of the deceleration by 10 mm.
4.2.3. Input addresses:
(Call in on LiSA-key board by typing 003*)
In parameter-set "input addresses" a function out of the stock of functions "input addresses" is assigned to the
available hardware-based in/outputs (I/O´s). The available I/O´s on the LiSA10-main card (max. 64 ) and on the car
card APO8 (max. 32) are freely programmable, i.e. none of these I/O´s has a function when being switched-on for
the first time (parameter-EEprom is empty). These functions will come to a life only by means of assignment via input
addresses.
All I/O´s are accessible by screw-type terminals or flat ribbon cable.
They are short-circuit-proof only for a short period.
Some functions are not freely programmable or have already got additionally a defined connector on the card, like
recall and inspection mode.
Following "rules" are to be observed upon assignment of the addresses:
st
- All functions occupying several I/O´s in sequence,st
i.e. all those that start with 1 stinput..., must be connected to the
I/O´s in an
st
unbroken sequence. These are e.g. 1 input car command buttons, 1 input landing call buttons access
side 1, 1 input waiting area a.s.o.
- The buttons for access side 2 (selective door control) can be connected immediately to the last button on access
side 1, but this is not a must. In case of a possibly existing vacancy, no function shall be programmed there.
1. car command button access side 1:
I/O-area seized:
st
Depending on the no. of landings, starting with the 1 car command button, access side 1
Interrogation without car selective door control.
2. car command button:
I/O-area seized:
st
Depending on the no. of landings, starting with the 1 carstcommand button, access side 2
Normally, this value always exceeds the address of the 1 car command button by 1.
Only with LiSA-buttons arranged in the car operating panel in two rows lies the address above the last button in row 1.
Interrogation with car selective door control.
1. car command button access side 2:
I/O-area seized:
st
Depending on the no. of landings, starting with the 1 car command button, access side 2.
The address must be higher than that of the last button on access side 1.
1. landing call button access side 1:
I/O-area seized on One-button control:
st
Depending on the no. of landings, starting with 1 landing call button, access side 1
I/O-area seized on two-buttons control:
st
Depending on the no.of landings *2 - 2, starting with 1 landing call button, access side 1
Interrogation with landing selective door control.
1. landing call button side 2:
I/O-area seized by One-button control: (ref. to fig 1)
st
Depending on the no. of landings, starting with the 1 landing call button, access side 2
I/O-area seized by Two-button control:(ref. To fig 2)
st
Depending on the no. of landings *2 - 2, starting with the 1 landing call button, access side 2.
The address must be higher than that of the last button on access side 1.
access side 1 access side 2 access side 1 access side 2
Fig. 2 Fig. 1
COMPLETE LIFTS PAGE – 40 –
LiSA CONTROLLER
For control manufacturers that do not want to use the electronic system of the car (APO-card in the inspection box)
there is the possibility to connect light barriers and closing-force limiter to any I/O´s: Signals of light barrier and
closing-force limiter can be adapted in parameter "light barrier / closing-force limiter active open/closed" (usage of
breaking or making contacts).
If the light barrier / closing-force limiter is activated for more than 10 minutes, the entry LS1/SB1 for access side 1
resp. LS2/SB2 for access side 2 is registered in the fault memory. If a modem is connected the control-station will
be dialed.
If it is a group, the elevator will stop participation in the distribution of landing calls already after a 10 seconds-
interruption of the light barrier / closing-force limiter– landing calls will again be acknowledged in the landing where
the car is.
With matrix-displays (parameter "type of indicator in car/landing" set to 16*8withX), a tiny L will be indicated after 10
seconds. In case of firemen service and fire emergency control the light barrier will be ignored.
Access side 1 – door opening button:
Function to keep the car door open / reversing of car door on access side 1 while closing.
Acts also on access side 2 if no separate door opening button has been provided for it. With selective door control
only that access side will open for which a door-opening release is available (call for this access side was set).
Starts the door-opening monitoring time anew
Does not work with firemen service and fire emergency control.
Access side 1 – door closure button:
Function for the immediate initiation of door closing motion on access side 1.
Acts also on access side 2 if no separate door closure button has been provided for it.
If door-opening monitoring time is expired the door will close immediately.
If the doors are in door opening motion, no stay-time will be started after that, i.e. if a call has been set the door will close
immediately.
If the door is in opening motion and if parameter "door reversal delay" has been programmed with value 98, the door will
close at once.
The light barrier will no longer be regarded.
Input – Light barrier TS1:
Normally, the light barrier on access side 1 (TS1) (light screen) is connected to terminals L1 of the APO.
Input – closing force limiter TS1:
Normally, the closing-force limiter will be connected to terminals R1 of the APO.
Input-door-open limit switch door 1
Input for the detection of the door-open signal of door 1.
This function has been introduced especially for electronic door operators (particularly Siemens AT25).
The door-open limit switches are not, as usual, connected to the terminals A1 or A2 on the APO, i.e. the door-open
signal is continuously applied if the door is not going to close. That way, a long door-opening control period can be
set, without its negative consequences coming into effect (start of stay-time only after expiring of the door-opening
monitoring time, unless the signal door-open limit switch arrives before).
Consequence: possibly performed learn-travels of the door operator will not be disturbed by the (LiSA-) control (long
door-opening monitoring time).
Input door-close limit switch door 1
Input for the detection of the door-open signal of door 1.
Input – door stop button (see parameter "door stopping time" in 001*)
Function by which is achieved that the car door cannot be closed during an adjustable period (loading function).
Additionally required parameter: "door stop period" in parameter-set 001*.
Interrogation in case of 2 access sides.
Access side 2 – door opening button:
Function to keep the car open / reversing of car door on access side 2 during the closing process
Access side 2 – door closing button:
Function for the immediate initiation of door closing motion on access side 2.
Input – light barrier TS2:
Normally, the light barrier on access side 1 (TS1) (light screen) is connected to terminals L2 of the APO
Input – closing force limiter TS2:
Normally, the closing-force limiter is connected to terminals R2 of the APO.
Input-door-open limit switch door 2
Input for the detection of the door-open signal of door 2.
Input door-close limit switch door
Input for the detection of the door-open signal of door 2.
Input – inspection fast
Input for the switch-over to a higher inspection speed.
- With controlled elevators and Beringer hydraulic system the inspection speed will be activated.
- Otherwise, the high speed will be selected.
COMPLETE LIFTS PAGE – 41 –
LiSA CONTROLLER
Directional arrow in car-indicator (none / dir only / dir contin only / dir+dir con):
Definition if resp. how the directional arrows shall appear in the position indicator.
(0) : No arrow will be displayed.
(1) : Only travelling direction shall be displayed. During a travel - with matrix-displays – the respective travelling
direction shall be indicated left from the car position.
(2) : Only the direction of the ongoing travel shall be displayed. At standstill a blinking arrow for the respective
direction of ongoing travel is displayed at the left from the car position.
(3) : The travelling direction and the direction of ongoing travel is displayed.
This function includes both afore described functions.
COMPLETE LIFTS PAGE – 42 –
LiSA CONTROLLER
By here below following parameters the analogue scope of functions for LiSA-displays is programmed,
however for indicators installed on the landing:
Landing position-indicator (No / 8*8 / 16*8old / 16*8new / S35 / S15 / S7 / LCD / LCD/ Mseg
/ FPMat / hBu / vBu / hvBu):
Definition which kind of indicators is installed on landings.
(0) : No indicators on landings.
(1) : The display configured as a landing indicator (Jumper not plugged on indicator) has 8*8 dots.
(2) : The display configured as a landing indicator (Jumper not plugged on indicator) has 16*8 dots
(3) : The display configured as a landing indicator (Jumper not plugged on indicator) has 16*8 dots.
Additionally – in that area of the indicator where normally the travelling direction appears – useful
information will be displayed, like:
- x, if the elevator does not accept landing calls,
- _ , when the hinged door is open,
- L , when the light barrier is interrupted for more than 10 seconds
(4) : As landing position indicator either the LiSA-LED-segment display (1-digit / 1-digit with arrow / 2-digit / 2-
digit with arrow, 35 mm high) or the LiSA-foil-segment display (2-digit with arrow, 50 mm high) will be
used. For activation are no additional I/O´s required.
(5) : As landing position indicator the older type of the 15 mm LiSA-segment display is used. The parameter
value is of interest only for older elevators, as this indicator is no longer installed.
(6) : 7-segment indicator.
(7) : LCD-display (192*192 dots) with programming on a PC.
(8) : LCD-display as under (7), with additional functions as under (3).
(9) : Multi-segment display. Illuminated 2-digit LCD-position indicator with arrow (50 mm high).
38 segments perform each digit. Activation similar to the normal segment-display.
(10) : PC-programmable matrix-display plugged in the matrix-display connector (I2C).
(11) : Bus-Matrix-Display in horizontal position
(12) : Bus-Matrix-Display in vertical position
(13) : Bus-Matrix-Display in horizontal and vertical position
Interrogation in case of matrix-indicators on landings:
Type of landing position- (fix / chancing / scrolling):
Definition which kind of indicators is installed on landings.)
(0) : Car position permanently fully visible.
(1) : Car position alternating with the directional arrow.
During travelling within the zone the car position is displayed and off-zone only the travelling direction.
(2) : The change to the next display image comes scrolling.
Interrogation in case of matrix-indicators on landings:
Directional arrow in landing indicator (none / dir only / dir contin only / dir+dir con):
Definition if resp. how the directional arrows shall appear in the position indicator.
(0) : No arrow will be displayed.
(1) : Only travelling direction shall be displayed.
During a travel the respective travelling direction shall be indicated left from the car position.
(2) : Only the direction of the ongoing travel shall be displayed.
At standstill a blinking arrow for the respective direction of ongoing travel is displayed at the left from the car
position.
(3) : The travelling direction and the direction of ongoing travel is displayed.
This function includes both above described functions.
Interrogation when the type of car or landing indicator is parameterized as scrolling display:
Display – scrolling (rev. dir / in dir / rev. dir with arrow/ in dir with arrow):
Definition to which direction and what shall be scrolled.
(0) : The car position scrolls against the travelling direction. The directional arrow does not scroll.
This is the normally applied function.
(1) : The car position scrolls in travelling direction.
(2) : The complete image scrolls, i.e. car position and directional arrow. The scrolling direction is against
travelling direction.
(3) : The complete image scrolls, i.e. car position and directional arrow. The scrolling direction is in travelling
direction.
Out–of-operation (without / X / A-B):
Definition of what shall be displayed on the matrix-indicator in case of malfunction, of inspection mode or of recall. If,
however, a EL-foil (electro-luminescent-foil) is installed on landings and/or in the car, this parameter is used for the
parameterizing of the respective foil. In this case no out-of-operates status is indicated on a possibly additionally installed
matrix-indicator.
(0) : Indication of car position
(1) : Indication of sign "X"
(2) : Indication of signs A-B.
COMPLETE LIFTS PAGE – 43 –
LiSA CONTROLLER
Position indicator in car command button (0 / 1):
Definition, if the car position should shown by flashing a signal of the car command button.
(0) : no indication
(1) : car command button of that landing where the car is blinks in a seconds-cycle.
Ongoing-travel direction indicator (0 / 1):
Definition whether the indication of travelling direction, set by way of the free-programmable outputs
resp. relays, shall additionally indicate the ongoing travel during standstill.
(0) : Signalization of travelling direction only. No indication at standstill.
(1) : Additional signalization of direction of ongoing travel at standstill.
Interrogation, if car and landing indicators were preset by PI2C:
By the free programmable 16*8 matrix display, 4 different horizontally scrolling texts can be chosen, in order to
indicate different operational modes.
Horizontally scrolling text 1
(No / VoL / UeL / Vorz / Sofa / Not+Brand / Eva / Feu / Aus / Ins / AusB) :
(0) : No scrolling text
(1) : text in case of full load
(2) : text in case of overload
(3) : text in case of priority travel
(4) : text in case if special travel
(5) : text in case of emergency resp. fire emergency travel
(6) : text in case of evacuation travel
(7) : text in case of fire brigade operation
(8) : text if landing control is switched off
(9) : text in case of maintenance / inspection
(10) : text, if input for „out-of-operation"-indication is activated
Horizontally scrolling text 2
(No / VoL / UeL / Vorz / Sofa / Not+Brand / Eva / Feu / Aus / Ins / AusB) :
Analogue with scrolling text 1.
Horizontally scrolling text 3
(No / VoL / UeL / Vorz / Sofa / Not+Brand / Eva / Feu /Aus / Ins / AusB) :
Analogue with scrolling text 1.
Horizontallly scrolling text 4
(No / VoL / UeL / Vorz / Sofa / Not+Brand / Eva / Feu / Aus / Ins / AusB) :
Analogue to scrolling text 1.
The following interrogation is for the assignment of indicator images to the individual landings:
Indicator image on landing 1:
Input of the number- code (1 – 300) for landing 1.
Deactivation position indicator after ... X Sec:
Definitions of when the position indicator shall be switched off if no calls are registered.
(0) : The position indicator will not be switched off.
(X) : The position indicator will be switched off after X seconds.
Since 20.05.2003, indicator images (max. 2 figures) and horizontally scrolling texts can be allocated directly by means
of LiSA-keyboard Tastatur.
The allocation has to be done on the basis of the following code table.
Image Code Image Code Image Code Image Code Image Code
0 00 A 10 K 20 U 30 / 40
1 01 B 11 L 21 V 31 -1 *) 41
2 02 C 12 M 22 W 32
3 03 D 13 N 23 X 33
4 04 E 14 O 24 Y 34
5 05 F 15 P 25 Z 35
6 06 G 16 Q 26 36
7 07 H 17 R 27 + 37
8 08 I 18 S 28 - 38
9 09 J 19 T 29 . 39
*) Code 41 only for segment displays, if –1 has to be shown by one figure.
COMPLETE LIFTS PAGE – 44 –
LiSA CONTROLLER
The following interrogation is for the assignment of indicator images to the individual landings:
Indicator image on landing 1:
Input of the code corresponding to the table above for landing1.
For example: In landing 1 there should be shown U1. Input: 3001
Indicator image on landing 2:
Input of the code corresponding to the table above for landing2.
For example: In landing 2 should be shown 1OG. Input: 012416
Indicator image on top landing:
Input of the code corresponding to the table above for landing2.
For example: In top landing should be shown DG. Input: 1316
By here below following description of horizontally scrolling texts are only available with the new parameter- EEPROM
24C256. This EEPROM is installed on all LiSA10-7 boards delivered after 15.05.20003.
Interrogation, if car or landing indicators are matrix indicators (but not preset to PI2C):
Rolling text 1 = FULLOAD
Rolling text 2 = OVERLOAD
Rolling text 3 = PRIORITY TRAVEL
Rolling text 4 = SPECIAL SERVICE
Rolling text 5 = FIRE-EMERGENCY TRAVEL
Rolling text 6 = EVACUATION TRAVEL
Rolling text 7 = FIREMEN MODE
Rolling text 8 = MAINTENANCE - INSPECTION
Rolling text 9 = OUT OF SERVICE
Rolling text 10 = EMERGENCY TRAVEL
Above texts are standard texts for 10 different operational states and can be modified just as you like (only if 24C256
EEPROM is installed).
The input procedure is likewise to that one above descript for allocating indicator images; this means it is based on the
image-code table.
Texts with less than 3 figures are not shown. In this way texts for distinct operational states can be suppressed, if
one does not want to show a text for this state.
For example: Scrolling text 2 (OVERLOAD) should be changed to „CAR OVERLOADED".
Input: 1210273624311427212410131313
Entering „000000“ the standard text can be restored.
COMPLETE LIFTS PAGE – 46 –
LiSA CONTROLLER
The duration of the operational status "clock-controlled travel" will be set by the following parameters;
Begin – clock-controlled travel:
Upon change into operational status "clock-controlled travel" following parameters are activated:
- Clock-controlled travel: Opening – door 1 car command.
- Clock-controlled travel: Opening – door 2 car command.
- Clock-controlled travel: Opening – door 1 landing cal
- Clock-controlled travel: Opening – door 2 landing call
- Parking landing for clock-controlled travel
The operational status "clock-controlled travel" is shown on the LiSA- op. stat. display by „u“.
End – clock controlled travel:
With the integrated clock a treatment of Saturdays, Sundays and holidays deviating from the that of the weekdays is
not possible. If this should be required, an external time-clock must be used to operate the clock-controlled travel
through an "input – clock-controlled travel".
COMPLETE LIFTS PAGE – 47 –
LiSA CONTROLLER
5. Service and Maintenance
Within the range of the regular service and maintenance work with regard to the entire elevator, also the
LiSA-control unit is the be checked.
This check comprises a visual and a functional examination.
Visual examination:
1. Examine all relays with regard to burned contacts.
2. Examine the power contactors.
3. Examine the plug-connections.
Functional examination:
The functional examination mainly consists of the checks prescribed by the elevator attendant tasks and
the check of the fault memory.
1. Does the elevator stop at flush landing level?
2. Does the emergency call system work?
3. Does the door-open button work?
4. Is the car illuminated?
Check of the fault memory:
1. Fault memory, time sequence
2. Fault memory, parity check faults
3. Fault memory, interruptions of safety circuit, door malfunctions, inaccurate stops.
5.1 Push-button commands
The following commands can be initiated by means of the LiSA-keyboard.
It is inevitable to know these commands, in order to be able to execute the functional check of the elevator.
COMPLETE LIFTS PAGE – 48 –
LiSA CONTROLLER
010 * = cumulative fault display
011 * = Display of disturbed door operations, interruptions of the safety circuit and inaccurate landing stops
012 * = Display of faults in time sequence
013 * = Display of travel statistics (number of approaches to each landing)
015 * = Cancel display of faults in time sequence
016 * = Cancel cumulative fault display
017 * = Cancel display of disturbed door operations, interruptions of the safety circuit and inaccurate landing
stops
018 * = Cancel travel counter and travel statistics
019 * = Cancel counter of service intervals
100 * = Start teaching operation
200 * = Switch modem-operation on / off
201 * = Set alarm during modem-operation
202 * = Cancel alarm during modem-operation
204 * = Continuous LiSA-Display on / off
208 * = teaching operation by car control buttons on/off
400 * = overall hardware test
401 * = relay test
402 * = Continuous IO-Test on LiSA central pc-board
403 * = IO-Test by car control buttons
404 * = overall hardware test
405 * = Continuous IO-Test on LiSA central pc-board
600 * = Memorizes parameters of the elevator
Besides the serial interface between LiSA and PC (direct or via Modem), the LiSA display together with
the 12-key-board is the most important communication interface between control unit and user.
COMPLETE LIFTS PAGE – 49 –
LiSA CONTROLLER
5.2 LiSA displays the status of the elevator
= high speed travel down
= slow-speed travel up
car command /
SK3 SGM
SK4 SGO
SK2 SGU
SK1 Vu
Vo
s v Z * * mode of car commands /
car position
Ture 1 2 3 4 5
landing calls /
state of landing calls Ture - 2 0 1 : 1 2
Display description in sequence from top left (= 1st position) to bottom right (= 80th position):
1st Position: s = landing where elevator starts, i.e., elevator started from 1st landing
2nd Position: = Car calls for landing 2 are blocked, i.e., not accepted
3rd Position: = Elevators travels up at high speed, for the moment being it is at landing 3 resp. between 3
and 4.
4th Position: = Car calls for landing 5 are blocked, i.e. not accepted
5th Position: v = deceleration-landing. In landing 5 the point of deceleration is computed
6th Position: Z = destination landing
7th Position: * = Car call for landing 7
8th Position: * = Car call for landing 8
20th position: = photocell of door 1: light barrier not interrupted ( = interrupted)
21st position: = closing force limiter of door 1 not activated ( = activated)
22nd position: = Door-open-button of door 1 not pressed ( = pressed)
23rd position:0 = permission to open door 1 (blank = no permission)
24th position: = limit switch for door open position of door 1 not interrupted (= interrupted)
25th position: = limit switch for door closed position of door 1 is interrupted ( = not interrupted)
26th position: = car commands are blocked ( = not blocked)
27th position: = doors are not blocked ( = blocked)
29th position: = pre-limit switch bottom inactive ( = active)
30th position: = Signal generator-bottom inactive ( = active)
31st position: = middle signal generator inactive ( = active)
32nd position: = top signal generator inactive ( = active)
33rd position: = pre-limit switch - top inactive ( = active)
35th position - 40th position: travel counter or parking time (if parking landing function is active)
41st position: = landing call - up at landing 1 ( - = no landing call)
42nd position: = landing calls at landing 2 are blocked, i.e., not accepted
43rd position: - = no landing call - up at landing 3
44th position: - = no landing call - up at landing 4
45th position: - = no landing call - up at landing 5
46th position: = landing calls up and down at landing 6
47th position: = landing call - down at landing 7
48th position: = landing call - down at landing 8
60th position: = photocell of door 2: light barrier is not interrupted ( = interrupted)
COMPLETE LIFTS PAGE – 50 –
LiSA CONTROLLER
61st position: = closing force limiter of door 2 is not activated ( = activated)
62nd position: = door-open-button of door 2 is not activated ( = activated)
63rd position:0 = permission to open door 2 (blank = no permission)
64th position: = limit switch of open position of door 2 not interrupted ( = interrupted)
65th position: = limit switch of closed position of door 2 interrupted ( = not interrupted)
66th position: = landing calls are blocked ( = not blocked)
67th position: = door stop button not activated ( = activated)
69th position: = safety circuit closed up to safety gear contact inclusive (SK1) ( = open)
70th position: = safety circuit closed up to landing door inclusive (SK2) ( = open)
71st position: = safety circuit closed up to car door (SK3) inclusive ( = open)
72nd position: = safety circuit closed up to lock switch (SK4) inclusive ( = open)
75th position - 80th position:
display of speed during travel, after passing through an inductor plate
display of running time during normal operation and at standstill
display of operating state: all operating states <> normal operation
s v * OKZ = 2 1 2 3 4 5
V e r z w e g = 1 0 9 8 OKZ = 2 1 : 0 1 : 1 2
deceleration distance displayed for the duration of the door opening checkback time real time (at standstill)
travelling checkback time (during travels
COMPLETE LIFTS PAGE – 51 –
LiSA CONTROLLER
From the standard output (state of the elevator) get to the reference list of the IOs on the LiSA10-
Press the *-button again to see the IOs of the car (FBE).
On the APO 8-pcboard (connection pc-board in the car), IO65-IO80 are situated as well as
the connections for inspection operation, photocells and closing force limiters, which are
not freely programmable. IO81-IO96 can be found on a pc-board (APE), which might
eventually be required in addition.
The most important functions can be localized immediately by abbreviated designations of the functions in question
(e.g. a = Außenruf = landing call).
All other functions are designated with b (b = occupied), as there not enough abbreviations. They can be
recognized by studying the parameters (parameter sets 003, 004, 005).
Return to the original situation (display of the elevator status) by pressing the *-button.
COMPLETE LIFTS PAGE – 52 –
LiSA CONTROLLER
COMPLETE LIFTS PAGE – 53 –
LiSA CONTROLLER
Input: clock controlled operation u * * 1
Input: dividing door t * 1
Input: evacuation operation e * 1
Input: fulload / overload y * * 1
Input: brake jaw monitoring r * 1
Input: contactor monitoring r * 1
Signals:
Special operation, overload, out of
operation, fulload, evacuation operation,
special travel/landing, car in landing zone, k * * 1
travel, up-direction, down-direction,
occupied, operation, collective fault
message
Output: car illumination bridged l * 1
Input: door-opening-button o * * 1
Input: door-closing-button z * * 1
Input: door-stop-button j * * 1
Input: fan-button j * * 1
COMPLETE LIFTS PAGE – 54 –
LiSA CONTROLLER
Subsequent to the display of accumulated faults, an additional information is displayed, that
is important for banks of elevators. It cannot be regarded as a malfunction, but to simplify the
procedures, this information has been added to the display of accumulated faults: waiting time after
entering a landing call, referred to each single landing.
As for the following displays only one digit per landing is available each, the units digits of the
fault counter are displayed only. This means that 5 could also be 15, 25 etc.
COMPLETE LIFTS PAGE – 55 –
LiSA CONTROLLER
The counter related to an individual landing is increased, if the elevator stops above or below
the landing level. This means that the top resp. below signal generator is not within the zone of the
inductor plate and the step at the landing exceeds 1,5 cm.
In case of modem-operation, the building supervisory lodge is informed
Scroll by *-button
COMPLETE LIFTS PAGE – 56 –
LiSA CONTROLLER
5.7 Description of faults in time sequence
012 * = Display of faults in time sequence
Scroll on by *-button. Scroll back by any numeral key.
A maximum of 30 faults is displayed. In case of more than 30 faults, LiSA overwrites the oldest fault each.
Displaying always starts with the latest fault. Each fault is displayed by two related images.
1. Display (time when the fault occurred) :
COMPLETE LIFTS PAGE – 57 –
LiSA CONTROLLER
Reset:
Meaning: Information (no fault in the proper meaning) about the fact that LiSA has reset the programme.
Reaction:
- All outputs are deactivated, and consequently all travelling signals are cut out, which might possibly result in
an emergency stop.
- After that all inputs and outputs are tested (to be seen at the LEDs on the IO-cards quickly lighting up one
after the other) and the car commands are restored (whereas landing calls are cancelled),
- if the car is not within the zone, a correction travel will be executed.
Reasons for this fault:
- External interferences (such as for example interference voltages, mains impurities etc.) make the software
being processed with errors. As a consequence the monitoring module on the CPU-card (watch-dog-IC)
initiates a reset.
- External interferences caused by insufficient suppression measures.
- Defective hardware or software.
Put things right:
Decrease external interferences:
- Connect travelling cable shielding in the control cabinet to PE; provide brakes and locking magnets with
varistors, RC-links resp. freewheeling diodes (has in general already been done by the manufacturer of the
control unit).
- Provide 380 V door operator motors and locking motors with the condenser block make Schneider.
- Check the wiring system (feed lines and motor lines should not be laid in parallel with the control lines, or at
least over shorter distances only)
- possibly the CPU resp. power supply unit is to be replaced
- possibly the software is to be exchanged.
SK1Int:
Meaning: Safety circuit interrupted on tap SK1 (terminal 9 / 10)
Reaction: Emergency Stop, if elevator is running. Elevator is put out of operation.
Reasons for this fault:
- mains switch is cut out or control fuses are triggered,
- speed governor is triggered or elevator car is blocked by the safety gear.
- other safety contact upstream from terminal 4 is open.
Put things right: According to the reasons for this fault.
ESTop?:
Meaning: Emergency switch on top activated?
Interruption of safety circuit on tap SK1 (terminal 9/10) while the signal of the emergency switch on top is
being at hand and the signal transmitter top is missing. As possibly any other safety contact upstream from
SK1 might as well have caused this interruption, this message is provided with a question mark.
Reaction:
- Emergency stop, if elevator is running. Elevator is put out of operation.
Hydraulically operated elevators use to sink after each stop, so that the emergency limit switch will be closed
again.
- If the parameter “Norm” (“standard”) of this elevator is set to “TRA”, the elevator will resume operation.
- If this parameter is set to “EN81”, the message “NotOb” (without question mark) will be entered in the fault
memory, the elevator car will sink and remain out of operation.
Reasons for this fault:
- Brake had been released manually so that the car trundled upwards.
- Value of the parameter for the distance between the topmost landing and the landing before it is too high,
while at the same time the distance between the magnet of the preliminary limit switch on top and the
topmost landing is too small.
- The hydraulic elevator valve does not decelerate correctly (as it depends on the temperature).
- Emergency limit switch has not correctly been positioned (is triggered too early).
- Central signal transmitter or preliminary limit switch on top is defective.
Put things right:
- Enlarge distance between topmost landing and magnet of preliminary limit switch top.
- Check, if the preliminary switch top as well as the central signal transmitter switch correctly.
COMPLETE LIFTS PAGE – 58 –
LiSA CONTROLLER
ESBot?:
Meaning: Emergency switch on bottom activated?
Interruption of safety circuit on tap SK1 (terminal 9/10) while the signal of the emergency switch at bottom is
being at hand and the signal transmitter bottom is missing. As possibly any other safety contact upstream
from SK1 might as well have caused this interruption, this message is provided with a question mark.
Reaction: Emergency stop, if elevator is running. Elevator is put out of operation.
Reasons for this fault:
- Value of the parameter for the landing distance between landing1 and landing2 before it is too high, while at
the same time the distance between the magnet of the preliminary limit switch bottom and landing1 is too
small.
- The hydraulic elevator valve does not decelerate correctly (as it depends on the temperature).
- Car is overloaded
- Emergency limit switch has not correctly been positioned.
- Central signal transmitter or preliminary limit switch on top is defective.
Put things right:
- Enlarge distance between landing1 and magnet of preliminary limit switch.
- Check, if the preliminary switch bottom as well as the central signal transmitter switch correctly.
CoCFault:
Meaning: Fault on monitoring the switching-off of the contactor.
The software, monitoring the travel contactors, which should switch off at standstill, has responded. That
means that there is no signal at the input for contactor monitoring.
If the parameter „Norm“ („standard“) is set to EN81, the signal is to be connected to the in/output for
the landing control on the LiSA-card.
Reaction: The elevator control unit is put out of operation and stays so until a change of the operation mode is
initiated.
Reasons for this fault: At least one contactor has stuck.
Put things right: Remove defective contactor.
Brake:
Meaning: Fault on monitoring the brake.
The software, monitoring the brake-contacts, which shall switch off
- if the mechanical brake is closed at standstill of the elevator, or
- if it is open while the elevator is running, has responded.
Reaction: The elevator control unit is put out of operation and stays so until a change of the operation mode is
initiated.
Reasons for this fault:
- Selection of the brake does not work,
- Brake-jaw contact is not adjusted properly.
Vo+Vu:
Meaning: Pre-limit-switches have simultaneously been activated
Reaction: The elevator control unit is put out of operation and stays so until a change of the operation mode is
initiated.
Reasons for this fault:
- Either pre-limit switch top or pre-limit switch bottom has not been reset as the car left the respective landing
zone.
- Magnet for the pre-limit switch is positioned in a way that it simultaneously activates the other pre-limit switch
as well.
Put things right:
- Replace defective pre-limit switch,
- Check lateral position of the magnet with respect to the pre-limit switch.
SoZone: (So out of zone)
Meaning: Car has overrun the flush level while travelling up; that means that the signal transmitter top is not
within the destination landing zone anymore, and the car has stopped with a step above flush landing level.
Reaction: The elevator control unit initiates an emergency stop (immediate stop).
Reasons for this fault:
- Value of parameter „Bremsverzögerung-Auf“ („braking retardation up“) is too high,
- value of parameter “Verzögerungsweg-Auf” (“braking distance up”) is too low,
- levelling speed is too high,
- lug has not properly been adjusted
- hydraulic valve system depends on the temperature,
- signal transmitter top is too distant from lugs (signal transmitter top as well as signal transmitter bottom
should reach in the lugs by at least 1 cm)
Put things right:
- Reduce parameter-value for braking retardation up,
- increase parameter-value for braking distance up,
- reduce levelling speed.
COMPLETE LIFTS PAGE – 59 –
LiSA CONTROLLER
SuZone: (Su out of zone)
Meaning: Car has overrun the flush level while travelling down; that means that the signal transmitter bottom is not
within the destination-landing zone anymore, and the car has stopped with a step below flush landing level.
Reaction: The elevator control unit initiates an emergency stop (immediate stop).
Reasons for this fault:
- Value of parameter „Bremsverzögerung-Ab“ („braking retardation down“) is too high,
- value of parameter “Verzögerungsweg-Ab” (“braking distance down”) is too low,
- levelling speed is too high,
- lug has not properly been adjusted
- hydraulic valve system depends on the temperature,
- signal transmitter bottom is too distant from lugs (signal transmitter top as well as signal transmitter bottom
should reach in the lugs by at least 1 cm)
Put things right:
- Reduce parameter-value for braking retardation down,
- increase parameter-value for braking distance down,
- reduce levelling speed.
SmZone: (Sm out of zone)
Meaning: Car has overrun the flush level when travelling up or down; that means that the central signal
transmitter is not within the destination-landing zone anymore, and the car has stopped with a step of at least
10 cm above or below the flush landing level. This fault is in general entered in the fault memory immediately
after SuZone or SoZone.
Reaction: The elevator control unit initiates an emergency stop (immediate stop).
Reasons for this fault:
- Value of parameter „Bremsverzögerung-Ab resp. Auf“ („braking retardation down resp. up“) is much too high,
- value of parameter “Verzögerungsweg-Ab resp Auf” (“braking distance down resp. up”) is too low,
- stopping conditions (with Dynatron-S, -F) have too late been signalised by the elevator control unit / the
hydraulic valve system resp. the speed controlling unit have not accepted the braking command.
- levelling speed is too high,
- hydraulic valve system depends on the temperature,
Put things right:
- Reduce parameter-value for braking retardation
- increase parameter-value for braking distance,
- reduce levelling speed.
Zuhoch (Too high): (So not in zone)
Meaning: Car stopped above flush level while travelling down; that means that the car has properly stopped at
the destination landing, but the signal transmitter top has not yet entered the landing zone.
Reaction: The elevator control unit initiates relevelling, provided that this function has been activated.
Reasons for this fault:
- Value of the parameter „Bremsverzögerung-Ab“ (“braking retardation down“) is too low,
- step correction too large,
- pulse transmitter sends too many pulses (above all due to interferences on the pulse line),
- in case of Dynatron-S and –F:
The KBR-signal will come too early, if braking is initiated by a KBR-relay, as the firmly installed magnet for
the brake sits too high,
or the car is flush with the landing level, but the lug sits too low,
or the parameter “Verzögerungsweg-Ab” (“deceleration distance down”) has got a too high value,
Put things right:
- Increase value of the parameter „Bremsverzögerung-Ab“ (“braking retardation down”),
- reduce Step correction,
- measure input of the pulse on the LiSA-card (by an oscillographe), as possibly the pulse line has to be laid in
another way.
- Correct brake release resp. position of the lug.
Zutief (To low):(Su not in zone)
Meaning: Car stopped below flush level while travelling up; that means that the car has properly stopped at
the destination landing, but the bottom signal transmitter has not yet entered
the landing zone.
Reaction: The elevator control unit initiates relevelling, provided that this function has been activated.
Reasons for this fault:
- Value of the parameter „Bremsverzögerung-Auf“ (“braking retardation up“) is too low,
- step correction too large,
- pulse transmitter sends too many pulses (above all due to interferences on the pulse line),
- in case of Dynatron-S and –F:
The KBR-signal will come too early, if braking is initiated by a KBR-relay, as the firmly installed magnet for
the brake sits too low,
or the car is flush with the landing level, but the lug sits too high,
or the parameter “Verzögerungsweg-Auf” (“deceleration distance up”) has got a too high value,
COMPLETE LIFTS PAGE – 60 –
LiSA CONTROLLER
Put things right:
- Increase value of the parameter „Bremsverzögerung-Auf“ (“braking retardation up Increase value of the
parameter „Bremsverzögerung-Ab“ (“braking retardation down”),
- reduce Step correction,
- measure input of the pulse on the LiSA-card (by an oscillographe), as possibly the pulse line has to be laid in
another way.
- Correct brake release resp. position of the lug.
SoZReg: (So not in zone)
Meaning: Car has stopped too late while it was relevelling up. That means that the signal transmitter top has
left the zone and the car has stopped with a step above the flush landing level.
Reaction: The elevator control unit initiates an emergency stop.
Reasons for this fault:
- value of the parameter for brake retardation during relevelling is too high.
- signal choosing the relevelling speed is missing at the hydraulic control valve/inverter,
- relevelling speed is too high.
Put things right:
- Decrease the value of the parameter for braking retardation during relevelling,
- check, whether relay for Vn has been set and whether it is correctly wired,
- reduce relevelling speed.
SuZReg:(Su not in zone)
Meaning: Car has stopped to late while it was relevelling down (slowly creeping down). That means that
- the signal transmitter bottom has left the zone and the car has stopped with a step below the flush landing
level.
Reaction: refer to SoZreg
Reasons for this fault: refer to SoZReg
Put things right: refer to SoZReg
Cfault:
Meaning: Counting fault.
When the up-travelling car reaches the correction magnet top, in the elevator control unit a car position is at
hand which deviates from the parameter “Korrektur-Position-Oben” (“correction position top”). The same
situation is given when the car reaches the correction magnet bottom.
Reaction: The elevator control unit corrects the car position according to the value given by the respective
parameter “Korrektur-Position-Oben” resp. „-Unten“.
Reasons for this fault:
- Central signal-transmitter does not work properly from time to time or is defective,
- parameter “Korrektur-Position (“correction position”) is set to a wrong value,
- central signal-transmitter has entered a landing zone resp. left it, while during the travel the safety circuit was
interrupted (door contact / lock contact / end of travel during inspection or rescue operation / reset).
Put things right:
- Provided that the safety circuit had not been interrupted, possibly the central signal-transmitter is to be
replaced (if none is at hand, exchange it with a signal-transmitter bottom).
TTElap:
Meaning: Travel time elapsed.
During a travel between two adjacent landings the travel limit time preset by the parameter “Fahrkontrollzeit”
(“travel limit time”) elapsed.
Note: If the safety circuit is interrupted, the travel limit time will always be started again and will
consequently not lead to an error “FZUeb”.
Reaction:
The elevator control unit initiates an emergency stop and adopts the status “out of operation”. If the
parameter “Norm” (“standard”) is set to “TRA”, the control unit will initiate another trial after 10 seconds. If at
this repeated travel the travel limit time is again exceeded, the elevator control unit will finally adopt the status
“out of operation”.
Reasons for this fault:
- Central signal-transmitter does not work properly from time to time or is defective,
- hydraulic elevator stops as the control valve does not properly,
- speed-regulated elevator stops, as the speed control does not select the motor,
- mechanical brake has been applied.
Put things right:
- as regards signal-transmitter transfer to „Zfehler“ („time fault“),
- check, if the speed regulation indicates a fault. Check the activation signals of the control at the inputs of the
speed control (input level),
- Find out, why the brake is not released.
COMPLETE LIFTS PAGE – 61 –
LiSA CONTROLLER
STElap:
Meaning: Start time elapsed
The central signal-transmitter has not left the zone within 30 seconds after the start of a travel.
Note: If the safety circuit is interrupted, the start limit time will always be started again and will
consequently not lead to an error “SZUeb”.
Reaction: Refer to TTElap.
As the car is still within the landing zone, the door is opened.
Reasons for this fault: refer to TTElap.
Put things right: refer to TTElap
ATElap:
Meaning: 30 sec check-time for levelling elapsed
The travel limit time for entering the zone has elapsed. This fault will occur, if the travel limit time of 30
seconds that starts on a normal travel as soon as the central signal transmitter enters the zone elapses
before the counter of the braking distances has completely counted down to “0”.
Reaction:
The elevator control unit initiates an emergency stop and adopts the status “out of operation”. If the
parameter “Norm” (“standard”) is set to “TRA”, the control unit will initiate another trial after 10 seconds. If at
this repeated travel the travel limit time is again exceeded, the elevator control unit will finally adopt the status
“out of operation”.
Reasons for this fault:
- The speed control unit stops too early, i.e. the mechanical brake is activated too early (by the speed control
unit),
- the hydraulically operated elevator stands still, as the valve does not work properly,
- the speed-controlled elevator stands still, as the motor is not selected properly,
- the mechanical brake has been applied.
Put things right:
- As regards the signal-transmitter refer to „Zfehler“ („time fault“)
- check, if the speed regulation indicates a fault. Check the activation signals of the control at the inputs of the
speed control (input level),
- Find out, why the brake is not released.
RTElap:
Meaning: Computed duration of relevelling elapsed.
This fault will occur, if on relevelling actions the signal-transmitter top resp. bottom does not enter the lug
within 30 seconds, or if on braking-regulation by pulses the braking deceleration counter is not counted down
to “0” within the aforesaid time.
Reaction: refer to ATElap
Reasons for this fault:
- refer to ATElap
- at the speed control unit/inverter the signal for selection of the relevelling speed is missing.
Put things right: refer to ATElap
VVVFau:
Meaning: Fault on VVVF-Controller occurred.
The speed control unit (VVVF-controller) has sent a fault signal to the control as regards input “Max/Reg” on
the CPU-card.
Reaction:
The elevator control unit initiates an emergency stop and adopts the status “out of operation”. After 10
seconds, it initiates a new trial, provided the speed control unit has switched off the fault signal. If at this new
travel a fault signal is received as well, the elevator control unit will finally
adopt the status “out of operation”. For inspection and rescue operation this situation can be relieved by
switching the inspection resp. rescue control off and on again.
Reasons for this fault:
- Refer to the fault description of the manufacturer of the speed control unit,
- selecting signal of the elevator control has been missing,
- pulse signal of the speed control unit has not been connected, has been erroneous or defective.
Put things right:
- Refer to the fault description of the manufacturer of the speed control unit,
- measure the selecting signals at the speed control unit,
- measure the pulse signals by an oscillographe as possibly you will have to lay the pulse line in another way.
Maxpre:
Meaning: Fault “maximal pressure” has occurred.
The hydraulic speed control valve has sent a fault message to the input Max/Reg on the CPU-card of the
elevator control unit, saying that the maximum admissible operation pressure has been exceeded – in case
of a valve make Beringer it might also be a fault message from the electronics (contact-SIUA).
Reaction: The elevator control unit initiates an emergency stop and adopts the status “out of operation”. After
10 seconds, it initiates a new trial, provided the fault signal has been switched off.
COMPLETE LIFTS PAGE – 62 –
LiSA CONTROLLER
Reasons for this fault: Car overloaded
Put things right: Refer to manual of hydraulic valve manufacturer.
Minpre:
Meaning: Fault “minimal pressure” has occurred.
The hydraulic speed control valve has sent a fault message to the input “Min” on the CPU-card of the
elevator control unit, saying that the operation pressure has fallen below the minimum admissible value, resp.
that the pipe-rupture valve has responded.
Reaction: The elevator control unit initiates an emergency stop and adopts the status “out of operation”.
After 10 seconds, it initiates a new trial, provided the fault signal has been switched off.
Reasons for this fault: Loss of pressure in hydraulic system.
Put things right: refer to the fault description of the hydraulic valve manufacturer.
Ovtem2:
Meaning: Max. temperature 2 exceeded.
The PTC-thermistor of the driving motor resp. of the pump-motor of the hydraulic valve has sent a fault
message to input U2 on the CPU-card of the elevator control unit, saying that the maximum admissible
temperature (approx. 140 degrees Celsius) has been exceeded in this operation unit.
Reaction:
If the car is travelling at that moment, it will be stopped at the next possible landing, provided that this is
possible within 10 seconds. Otherwise the elevator control unit will initiate an emergency stop. As soon as the
unit is cooled down, the elevator control unit will put the elevator in service again.
Reasons for this fault:
- too many starts, environmental temperature too high, defective motor, brake is not released or is
- chafing,
- motor fan does not work or is not selected.
Put things right: according to the reasons
Ovtem1:
Meaning: Max. temperature 1 exceeded.
The PTC-thermistor of the driving motor resp. of the hydraulic oil-tank has sent a fault message to input U1
on the CPU-card of the elevator control unit, saying that the maximum admissible temperature (approx. 60
degrees Celsius) has been exceeded in this operation unit.
Reaction:
If a hydraulically operated elevator is travelling at that moment, it will be stopped at the next possible landing,
provided that this is possible within 10 seconds. Otherwise the elevator control unit will initiate an emergency
stop. As soon as the unit is cooled down, the elevator control unit will put the elevator in service again. In
case of a rope-traction elevator the motor fan will be switched on, provided that the appropriate relay-function
has been preset.
Reasons for this fault:
- Too many starts, environmental temperature too high, defective motor, brake is not released properly,
- motor fan does not work or is not selected.
Put things right: according to the reasons.
Safety:
Meaning: Fault of safety switches (please refer to LiSA-Manual part C)
After levelling of the car at the destination landing, the elevator control unit will trace a fault in the safety
circuit, if relay K5 monitored by the software has not changed its status during the travel.
Reaction:
The elevator is put out of operation. A rope-traction elevator will stay at the landing that was destination of the
last travel. A hydraulically operated elevator will creep to the lowest landing; if it, however, turns out on this
travel that the safety circuit works properly again, the elevator will be put in service again.
Reasons for this fault:
- hardware-fault on the LiSA-card.
- safety-relays do not work in the prescribed sequence or are defective.
Put things right:
- Replace safety circuit
- examine the selector switches
DFault: (please refer to fault memory for door faults)
Meaning: Door fault, because 5 trials to shut the door were not successful.
Reaction:
- All car commands are cancelled,
- in case of single lifts the landing orders are cancelled as well.
- If a new car command or landing order is entered, the elevator will be put in operation again, but will set a
door fault again after another two trials without success. In case of elevator banks, there will be up to 5 of
these trial cycless before the plant is finally put out of operation. Consequently another elevator of the bank
will respond to future landing calls from the special landing where the defective elevator parks. A single
elevator will be finally shut down after 20 trial cycles and only one fault message will be memorized.
COMPLETE LIFTS PAGE – 63 –
LiSA CONTROLLER
Reasons for this fault:
- locking device or lock-contact
- door operator ignores door-closing signal
- protection-switch of door motor has responded
- although the door-closing relay has been selected, it does not respond due to the door closing limit-switch
being open.
Put things right:
- Check, if locking relay is properly selected resp. if the door operating mechanism is properly adjusted,
- check door control unit, if necessary have it make a read-in travel,
- door motor protection switch is probably set to a too low value or too small; if selected without door
contactors, the contacts of the door relay are possibly burnt (short-circuit due to missing condenser block),
- condenser block not switched against neutral of the door motor but against zero resp. PE conductor
- check the door-closed contact.
DDoor:
Meaning: Dividing door activated (no fault, just for information) Message saying that the dividing door contact
has opened. This message is entered only while the plant is idle. If this situated occurs during operation, the
message will be entered after the end of the travel, only.
Reaction:
- all calls will be cancelled,
- the plant is switched over to the operation “shut out car commands”.
Reasons for this fault:
- dividing door has intentionally been opened,
- poor dividing door contact resp. contact resistance is too high so that the control unit cannot recognize it as a
valid signal.
Put things right:
-Replace resp. readjust the contact
-If necessary, install and additional relay via the dividing door contact and have the relay-contact transmit the
dividing door signal to the control input.
SK3Auf (SK3 open): (please refer to door faults memory)
Meaning: Interruption of safety circuit on tap SK3. (no fault, just for information) The safety circuit was
interrupted while the car was travelling at high speed, but only after the landing door contacts (terminal 95).
Interruption thus has been caused by a car door contact.
Reaction:
All travel contactors release. Travel signals in speed-controlled elevators are cut off by he elevator control units
as otherwise the speed-control unit would break down.
Reasons for this fault:
- The door contact does not properly close.
- in case of electronically control door motors (AT20, Sematic, Fermator etc.): disturbances on the door-closing
signal line.
Put things right: According to the reasons.
SK4Auf (Sk4 open): (please refer to door faults memory)
Meaning: Interruption of safety circuit on tap SK3. (no fault, just for information)
The safety circuit was interrupted while the car was travelling at high speed, but only after the car door contact
(terminal 11). Interruption thus has been caused by a locking device contact.
Reaction:
All travel contactors release. Travel signals in speed-controlled elevators are cut off by he elevator control units
as otherwise the speed-control unit would break down.
Reasons for this fault:
- The locking device contact does not properly close,
- the door coupling touches the rollers of the locking device while it is passing the landing zone.
Put things right: According to the reasons.
LS1/SB1:
Meaning: Photocell or force limiter activated longer than 60 minutes on door 1.
Reaction:
- Door not closed
- Elevator out of order.
Reasons for this fault:
- Photocell not working, because of poor adjusting or poor setting of parameter „signal force limiter active-
open“
- Photocell has intentionally been covered.
Put things right:
- According to the reasons.
- By the parameters „signal force limiter active-open“ the active status of either of these contacts can be preset.
LS2/SB2:
Meaning: Photocell or force limiter activated longer than 60 minutes on door 2.
COMPLETE LIFTS PAGE – 64 –
LiSA CONTROLLER
6. Risk assessments
6.1 Risk assessment of the safety circuit:
Preamble:
For the LiSA safety circuit and its sampling circuits a type examination certificate has been issued by the "TÜV"
(German Technical Inspectorate) with the designation EB-97A229. The following risk assessment as per ISO178
(draft) and EN1050 distinguishes between two situations: either with or without concern to the checkback signal K5.
During each travel, the principle of the control makes the relay K5 to execute a switching cycle. This means that
upon leaving the landing zone the relay picks up and upon entering the landing zone it drops. This procedure is
monitored by the processor of the LiSA10 - pcboard, which permanently evaluates the checkback signal K5
(breaking contact 21-22)
COMPLETE LIFTS PAGE – 65 –
LiSA CONTROLLER
3 K6 does not drop -contact of K6 is Welded -refer to item 1 un- seldom - Check the
anymore -K6 is mechanically important safety circuit,
blocked eventually
replace K5, K6,
K7 and B1
4 K7 does not drop -contact of K7 is welded -refer to item 1 un- seldom - Check the
anymore -K6 is mechanically important safety circuit,
blocked eventually
replace K5, K6,
K7 and B1
5 Simultaneous -travelling cable defective-bridging branch ÜZ remains un- seldom - replace
. contact to earth at -connecting cable of open while the car is outside important travelling cable
the outputs of the selector block defective the landing zone, as K/ above - replace
signal generators Cv and Rv picks up slowly. connecting
B2 and B3 -K7 does not drop when cable of
elevator car leaves landing selector block
zone
- refer to item 1.
6 Output of signal -travelling cable defective -elevator car slowly travels in un- seldom refer to item 5
. generator B1 -connecting cable of the emergency limit switch important
connected to earth selector block defective
7 Short circuit at the -travelling cable Defective -bridging branch ÜZ remains un- seldom refer to item 5
. outputs of signal -connecting cable of open, as K/ above Cv and RV important
generators B2 and selector block defective picks up slowly.
B3.
8 After voltage failure -Power is switched on -bridging branch ÜZ remains un- often - none
. simultaneous again after the elevator open, as K/ above Cv and RV important
voltage supply to had been disconnected. picks up slowly.
K5, K6 and K7
COMPLETE LIFTS PAGE – 66 –
LiSA CONTROLLER
Computational proof of item 2:
Assumptions:
- Short circuit between input capacitor of SK3 and optocoupler-input of SK4.
- Contactor voltage = 240V; contactor current = 150mA -> R contactor = 1,5 kOhm
U 240V R Contactor
; with Z Z
1
; with C C11 C12 100nF
Contactor
R Contactor
R Z Z
2 11 12
11 12
j C W
240V R Contactor
U Contactor
;
R 2 j 1
R Contactor 2
C
W
U 240V R Contactor
~
1,5kOhm
7
;
Contactor
R 2 j 1 1,5kOhm 4,7kOhm j 2 2 p 50 10
R Contactor 2
2 pf
1,5kOhm 1,5kOhm
U 240V 7
~ 240V ~ 5,6V
Contactor
6,2kOhm j 2 2 p 50 10 64.000 V / A
Hence it follows:
Even in the improbable case that there occurs a short circuit between the above-mentioned
points, the contactors cannot pick up, as there is an operational voltage for the contactor coils of
approx. 5,6 V only.
COMPLETE LIFTS PAGE – 67 –
LiSA CONTROLLER
84
84 83
83
81
81
LIGHT BLUE
FAST CONNECTORS /
MANUFACTURE BRIDGES
TOP LIMIT SWITCH
wire's number SC8 number
1 82 82
2 82
RED
Top Limit Switch
FAST
82
CONN ECTORS
GREY CABLE
2 0,50mm²
1
82
2
N.C. CONTACT
82
Vo
85
Vo
up travel switch
GREY CABLE
2 0,50mm²
pizzato
FR 538
N.O. CONTACT
Vu
86 87
DOWN TRAVEL SWITCH
wire's number SC8 number
1 86
2 87
Vu
down travel switch
GREY CABLE
2 0,50mm²
pizzato
FR 538
N.O. CONTACT
SC8 WIRE NUMBER
2 81
3 81
4 82
5 82
6 83
7 83
8 84
SC8 WIRE NUMBER
9 84
Vo 85
Vu 86
-H 87
PE 12 1
SC8 SC8
COMPLETE LIFTS PAGE – 68 –
LiSA CONTROLLER
84
84
83
83
81
81
LIGHT BLUE
FAST CONNECTORS /
84
YE
MANUFACTURE BRIDGES
LL
OW
/ GR
EE
N DOUBLE INSULATED CABLE
ORANGE FAST
CONNECTOR 3 1,00 mm²
R ED
EEN YELLOW
/GR
L OW /GREEN
Y EL
N R ED
W/GREE
Y ELLO
KNIT GOES THROUGH THE SHAFT
LOCK'S
84 CONTACT
83
YE
LLO
W/G
RE
DOUBLE INSULATED CABLE
E N ORANGE FAST
CONNECTOR 3 1,00 mm ²
R ED
EEN YELLOW
/GR
L OW /GREEN
Y EL
R ED
N
EE
/GR
OW
ELL
Y
83
SC8 WIRE NUMBER
2 81
3 81
4 82
5 82
6 83
7 83
12 1
8 84
SC8 WIRE NUMBER
9 84
Vo 85
1
Vu 86
SC8 SC8 -H 87
PE
COMPLETE LIFTS PAGE – 69 –
LiSA CONTROLLER
84
83 84
84
YE
LL
OW
/G
R EE DOUBLE INSULATED CABLE
N
ORANGE FAST 3 1,00 mm ²
CONNECTOR
KNIT GOES THROUGH THE SHAFT
RED
EEN YELLOW
/GR
LOW /GREEN
YEL
EN RED
W/GRE
YELLO
84
SC8 WIRE NUMBER
2 81
3 81
4 82
5 82
6 83
7 83
8 84
SC8 WIRE NUMBER
9 84
12 1 Vo 85
Vu 86
-H 87
1 PE
SC8 SC8
COMPLETE LIFTS PAGE – 70 –
LiSA CONTROLLER
COMPLETE LIFTS PAGE – 71 –
LiSA CONTROLLER
84
84
83
83
SPEED GOVERNOR
81 TOP CONTACT
81 WIRE'S
NUMBER SC8 NUMBER
1 82
PE GREEN/YELLOW
82 LIGHT BLUE FAST CONNECTORS / 2 82
MANUFACTURE BRIDGES
YE
LLO SPEED
W/ GOVERNOR
GR
EE
N ORANGE FAST TOP CONTACT
GREY CABLE
CONECTOR
3 0,50mm² 1
KNIT GOES THROUGH THE SHAFT
2
1 N YELLOW/GREEN
EE
/GR
OW
LL
YE
N
R EE
/G
OW
LL
YE
82
SPEED GOVERNOR
WEIGHT CONTACT
WIRE'S
NUMBER SC8 NUMBER
1 81
PE GREEN/YELLOW
2 81
12 1
BROWN
1 YELLOW / GREEN
SPEED
GOVERNOR
WEIGHT CONTACT
COMPLETE LIFTS PAGE – 72 –
LiSA CONTROLLER
CONNECTED TO
THE "KC-10"
A48
1 CONNECTOR ON
2
B48
3
THE VALVE BLOCK
C48 GR
D48 4
E
5 16 Y C
D12 X0 AB
6 ,75 L
COM
7 mm E
-H 8
2
U2
9
U1
10
-H
11
OL
PE
12
FL
PE
FL
3. 2
+H
3.2
3 .1
3.1
+H
OL
+H
KC-10
13
OL
-H
-H
U1
3.1
C10
U1
U2
U2
C OM
CO M
D12
14
D 48
D12
3.2
C48
D4 8
C 48
B48
A48
B48
A48
FL 15
PE YELLOW/GREEN
CONNECTED TO
THE "KC-10"
CONNECTOR ON VALVE BLOCK
THE CONTROLLER KLEEMANN
NOTE: in case that low “pressure switch” does not exist bridge in KC10 the “3.1” with the “3.2”
COMPLETE LIFTS PAGE – 73 –
LiSA CONTROLLER
CONNECTED TO
THE "KC-10"
6a
1 CONNECTOR ON
2
7
3 THE VALVE BLOCK
6b GR
16 EY C
4
8
5
X0
D12
6 ,75 ABL
COM
7
mm E
- 8
2
U2
9
U1
10
-
11
OL
12
+H
KC-10
13
C10
3.1
14
3.2
15
FL
PE YELLOWGREEN
VALVE BLOCK
CONNECTED TO
KLEEMANN
THE "KC-10"
CONNECTOR ON VALVE COIL OF
VALVE COIL OF
ASCENT
NOTE: in case that low “pressure switch” does not exist bridge in KC10 the “1 ” with the “2”
S/N CODE VVVF DOOR
1 -H 10
2 D.O. 12
3 D.C. 8
4 +H PHOTO CURTAIN SUPPLY
5 -H PHOTO CURTAIN SUPPLY
6 Light Screen PHOTO CURTAIN CONTACTS
7 Light Screen 41-38
8 Close Switch 33
9 Open Switch 30
10 EDO1 66
11 EDO1 67
12 7 CONNECTOR
13 8 CONNECTOR
14 LDAC 1
15 NDAC 3
YEL/GREEN PE 2
SUPLPLY
AUTOMATIC LANDING MANUAL LANDING
DOOR DOOR N 5 26 23 7 6 5
3 2
GND 6 STANDBY
LEFT & CENTRAL RIGHT
+12V
ON BAT FLOOR COM L2' GND L1'
100.230F 7
DO NOT
OPER THE CLOSE ON CLOSE OFF CONTROL OUTPUT
COVER +12Volt +12Volt INPUTS 2 VVVF4 VVVF4
OPEN 12
Com Com 1
4 1 0V 11
0Volt 1 INPUT 0Volt 2 INPUT COM 10 3
MASTER SLAVE OPEN OPEN OUT+12V 9
CLOSE 8
Use only fuse
4 Amps/250Volt SP F PRIORITY INPUTS
FLOOR LEVER 26 EMERGENCY
RE-OPEN 21
SLOW CLOSE 25
9
+12V COM 23
SUPPLIER
COMPLETE LIFTS
4 3 2 1
LiSA CONTROLLER
8 PHOTOCELL
AUTOADJUSTMENT
WHITE
20
RECEIVER GREEN SUPPLY 230V.AC
FLOOR
BLACK 19
PUSH TO CALIBRATE
BLACK 18
THE DOOR
EMITTER YELLOW 17
WHITE
L3 GND L2
SERIAL PORT
V- 16
TEST ?
RX 15 67
7
TX 14
66
PUSH TO CHECK THE BATTERY 3 2 1
DOOR V+ 13
+28 +29
11 10 14 / 15
+ - OW
BATTERY L L EN
YE GRE
3m
230Volt
Technical specifications
Voltage 230V AC
Max lamp power 40W
Integration of protection IP 20
Class II
COMPLETE LIFTS PAGE – 76 –
LiSA CONTROLLER
-H 2 -
EIN 3 S
AUF 4 +
AB 5 N+
3 6 M
3A 7 L
3B 8 Im
+H 9 EC
Sm Vo So
PE Vu Sm
-H SU/T.C.
PE CAM+
A48 CAM-
B48 INTERCOM
C48 INTERCOM
D48 5
D12 5B
Vo
COM 6
Vu
-H 7
-H
U1 8
U2 L4
OL N2
FL LDAC
+H PE
3.1
3.2
1
1A
L
-H M
AL
FRV
-H
CastRL
230
N
PE
COMPLETE LIFTS PAGE – 77 –
LiSA CONTROLLER
+ S -
23 21 19 17 15 13 11
1
3 2
PE 22 20 18 16 14 12
8 7 6 5 4
10 9
COMPLETE LIFTS PAGE – 78 –
LiSA CONTROLLER
UP TEST LIMIT
SWITCH
N.O.
CONTACT
2-WIRE CABLE
2x0.75mm²
-H
FRV
COMPLETE LIFTS PAGE – 79 –
LiSA CONTROLLER
SU/T.C.
REVISION BOX
Selectorblock Door 2 Switch Switch Limiter Screen Door 1 Switch Switch Limiter Screen Overload Puls-Gen
CAM+
Ec-Con.
XK1
Kopierblock Dc Do Com | Close | Open | Force + Light- Dc Do Com | Close | Open | Force | Light- | + | Im
XK12
CAM-
XK7
Ec Vu Vo Su Sm So Im Intercom. Lisabus
S
NO
NC
C
INTERCOM
M N+ +
X1
INTERCOM
+
5
_
D2-Open D2-Close D1-Open D1-Close
5B
f1 f2 f3 f4
L
6
LiSABUS
LiSABUS
7
8
L4
N2
LDAC
_ 01
PE
Al
No
Nc
Ec _ El N+ L M N+ + S
E-Call E-Light Int. -Com LBus
REV
16 15 14
LiSABUS
LiSABUS
fan
Cab.-Light
fan
Cal
APO-12
Rel-Emerg.-Light
L4
X3
XK5
XK2
full I
Sm
Sm
Vo
So
Su
Vu
Vo
Vu
So
Su
+N
Es
Ec
| | | | | |
Sl
Iu
Id
Ie
if
+
+S -
23 21 19 17 15 13 11
2 1
PE 22 20 18 16 14 12 4 3
8 7 6 5
10 9
COMPLETE LIFTS PAGE – 80 –
LiSA CONTROLLER
EC / - Emergency Alarm
EL / N+ Safety Emergency Lights
L/M Telephone Line
OL / - Over Load
/- Door Open Button
/- Door Close Button
F1 / - Attendant Key Or Lights Key
F2 / - Multifunction Fan Key
F3 / - Inputs Fire Fighter Key (Fincar)
F4 / - Fire Fighter Start Input (Finstart)
COMPLETE LIFTS PAGE – 81 –
LiSA CONTROLLER
Bus cable – shaft connections (surfaces mounted L.O.P.’s & over door indicators)
COMPLETE LIFTS PAGE – 82 –
LiSA CONTROLLER
LiSABUS
LiSABUS
- +
LBM9
LBM9
bezel
surface
bezel
surface
bezel
surface
bezel
surface
speed governor
weight contact
shaft rope
control
2 * manufacture
orange fast
bridge
connectors
3 red fast
connectors
4
orange fast
connectors
5
6
7 manufacture
orange fast connectors bridges
8
speed governor
landing door contacts top contact
9
Vo
Vu
-H
PE
COMPLETE LIFTS
LiSA CONTROLLER
REV
HYDRAULIC- SAFETY LANE CONNECTIONS-AUTOMATIC DOORS
5
5
5B 5B
6
6
7
7
8
8
PAGE – 83 –
6 4C
speed governor
weight contact
shaft rope
control
2 * manufacture
orange fast
bridge
connectors
3 red fast
connectors
4
orange fast
connectors
5
orange fast connectors
6
landing door contacts
7 manufacture
orange fast connectors
bridges
8
speed governor
landing door locks top contact
9
Vo
Vu
-H
PE
COMPLETE LIFTS
LiSA CONTROLLER
REV
5
5
5B
HYDRAULIC- SAFETY LANE CONNECTIONS-SEMI-AUTOMATIC DOORS
5B
6 6
7
7
8
8
PAGE – 84 –
6 4C
COMPLETE LIFTS PAGE – 85 –
LiSA CONTROLLER
Deceleration from floor to floor is achieved due to encoder signals, except the bottom and top floor, where
deceleration is performed due to top & bottom travel switches (N.O. contacts).
rail
magnet
5cm
20cm
5cm
magnetic
switches
(N.O. contact)
Place on each level one 20cm magnet. Then place 5cm above “Sm” magnetic switch, “So” magnetic switch and 5cm
below “Su” magnetic switch.
When the car is leveled on a floor, the “Sm” magnetic switch should be pointing the according magnet on its middle
point.
LiSA performs the shaft copy with the aid of “Sm”, “So” and “Su” magnetic switches, as seen above, and the signals
from the LiSA encoder.
Deceleration from floor to floor is achieved due to encoder signals, except the bottom and top floor, where
deceleration is performed due to top & bottom travel switches (N.O. contacts).
COMPLETE LIFTS PAGE – I –
LiSA CONTROLLER
1.1. Central electronic unit – (LiSA10)........................................................................................................................ 2
1.1.1. Plug-connections (flat cable plugs) ................................................................................................................. 2
1.1.2. Plug-connections (screw-type terminals) ........................................................................................................ 3
1.1.3. Coding jumpers and functional elements ....................................................................................................... 5
1.2. I/O – card - (IO16) .................................................................................................................................................. 6
2. LiSA Bus System...................................................................................................................................................... 7
2.1. LiSA10-7.................................................................................................................................................................. 9
2.2. LiSA-Bus-Modul (LBM-09) .................................................................................................................................. 11
2.2.1. LiSA-Travelling Cable Adapter (Busad-2):..................................................................................................... 11
2.2.2. Connection Board in the Cabin (APO12):...................................................................................................... 12
2.2.3 Connection Board in the Cabin Operation Panel (LF12): ............................................................................. 14
3. LiSA-cabin bus: ...................................................................................................................................................... 15
4. Functions: ............................................................................................................................................................... 16
4.1.1. Shaft information.............................................................................................................................................. 16
4.1.2. Learning-run...................................................................................................................................................... 17
4.1.3. Parameter processing...................................................................................................................................... 18
4.2. Description of Parameters.................................................................................................................................. 19
4.2.0. General Elevator Parameters: (Call in on LiSA-key board by typing 000*) ............................................... 19
4.2.1. General Elevator Times: (Call in on LiSA-key board by typing 001*) ........................................................ 29
4.2.2. Travel Times / Pulses: ..................................................................................................................................... 36
4.2.3. Input addresses:............................................................................................................................................... 39
4.2.4. Indicator functions: (Call in on LiSA-keyboard by typing 007*) ................................................................. 41
4.2.5. Door opening functions: (Call in on LiSA-keyboard by typing 008*) ......................................................... 44
4.2.6. Teaching operation values: (Call in on LiSA-keyboard by typing 009*) .................................................... 45
4.2.7. Special-parameters: (Call in on LiSA-keyboard by typing 0010*)............................................................... 46
5. Service and Maintenance ...................................................................................................................................... 47
5.1 Push-button commands ...................................................................................................................................... 47
5.2 LiSA displays the status of the elevator............................................................................................................ 49
5.3 Abbreviated designations of freely programmable IOs ................................................................................... 51
5.4 Description of accumulated faults ..................................................................................................................... 54
5.6 Display of the travel statistics ............................................................................................................................ 55
5.7 Description of faults in time sequence.............................................................................................................. 56
6. Risk assessments .............................................................................................................................................. 64
6.1 Risk assessment of the safety circuit: .............................................................................................................. 64
6.1.2 Risk assessment without concern to the checkback signal K5:................................................................. 64
6.2 Risk assessment of sampling operations in the safety circuit: ..................................................................... 65
CONNECTION OF SAFETY SWITCHES (TOP LIMIT & TRAVELERS) ................................................................... 67
CONNECTION OF LOCK & DOOR CONTACTS ON SEMI-AUTOMATIC LANDING DOORS ............................................. 68
CONNECTION OF AUTOMATIC DOOR CONTACTS ............................................................................................... 69
PIT STOP CONNECTIONS ......................................................................................................................................... 70
SPEED GOVERNOR CONTACTS .............................................................................................................................. 71
VALVE BLOCKS CONNECTIONS.............................................................................................................................. 72
BUCHER VALVE BLOCK CONNECTIONS................................................................................................................ 73
CONNECTION DIAGRAM OF AUTOMATIC CAR’S DOOR (VVVF) ......................................................................... 74
CONNECTION OF SHAFT LIGHTS (KSL 40) ............................................................................................................ 75
HYDRAULIC – TERMINAL STRIPS............................................................................................................................ 76
TRAVELLING CABLE FC1.......................................................................................................................................... 77
UP TEST LIMIT SWITCH ............................................................................................................................................ 78
TRAVELING CABLE CONNECTIONS INSIDE THE REVISION BOX ....................................................................... 79
C.O.P. CONNECTION WITH REVISION BOX ON TOP OF THE CAR ..................................................................... 80
Bus cable – shaft connections (surfaces mounted L.O.P.’s & over door indicators)........................................ 81
Landing Operation Panels & Over Door Indicators................................................................................................ 82
HYDRAULIC- SAFETY LANE CONNECTIONS-AUTOMATIC DOORS .................................................................... 83
HYDRAULIC- SAFETY LANE CONNECTIONS-SEMI-AUTOMATIC DOORS .......................................................... 84
SHAFT COPY (HYDRAULIC) ...................................................................................................................................... 85