Govind Parashar-1
Govind Parashar-1
TRANSFORMER PROTECTION
A dissertation -1
Submitted for partial fulfillment of the requirements for the award of the Master
degree of Master of Technology in Electrical Engineering (With
Submitted by :
Guided by :
Govind Parashar
Mr. Prateek Tiwari
(Assistant Professor) Enrollment:- 23E2RCPSM40P603
Department of Electrical Engineering Roll N:- 23ERCPS603
Power System
May 2024
CERTIFICATE
This is to certify, Mr. GOVIND PARASHAR of IInd. Semester M.Tech. (Power System), have
worked for their project entitled as TRANSFORMER PROTECTION UNDER my
guidance being submitted in partial fulfillment of award of degree of M.Tech from
Rajasthan Technical University, Kota during the session 2023-2024.
The satisfaction and euphoria that accompany the successful completion of any work will
be incomplete unless we mention the names of these people who made it possible, whose
valuable guidance and encouragement served as a beacon light and crowned the efforts
with success.
We express our earnest gratitude to our internal guide, Mr. Prateek Tiwari, Assistant
Professor, Department of Electrical Engineering, RCERT, our project guide, for his
constant support encouragement and guidance. We are grateful for his cooperation and
his valuable suggestion.
Finally, we express our gratitude to all other members who are involved either directly or
indirectly for completion of this project.
Govind Parashar
Introduction 1
Section 2 2
Electrical Protection 2
Factors to be Considered 6
Section III 10
Gas Analysis 10
References: 11
Transformer Protection
Section I
Introduction
The primary objective of the Transformer Protection is to detect internal faults in the
transformer with a high degree of sensitivity and cause subsequent de-energisation and, at the same time
be immune to faults external to the transformer i.e. through faults. Sensitive detection and
deenergisation enables the fault damage and hence necessary repairs to be limited. However, it should
be able to provide back up protection in case of through faults on the system, as these could lead to
deterioration and accelerated aging, and/or failure of the transformer winding insulation due to over
heating and high impact forces caused in the windings due to high fault currents. In addition to the
internal faults, abnormal system conditions such as over excitation, over voltage and loss of cooling can
lead to deterioration and accelerated aging or internal failure of the transformer. Hence protection again
these failures should be considered in as part of the comprehensive transformer protection scheme.
Like in most things in Transformer Protection too, the extent of protective devices applied to a
particular Transformer is dictated by the economics of the protection scheme vis-à-vis the probability
of a particular type of failure and the cost of replacing and repairing the transformer as well the
possibility of the failure leading to damage of adjacent equipment or infrastructure. Failure costs
include all the direct and indirect costs associated with it. The protection scheme cost includes the cost
of the protective device but is mainly the cost of the disconnecting device i.e. the Circuit Breaker and
other auxiliaries like batteries and necessary infrastructure. Further the life cycle cost is taken into
account.
There are no strict guidelines as to what protection devices should be used for a particular
transformer. However, typically Transformers below 5000 KVA (Category I & II) are protected using
Fuses. Transformers above 10,000KVA (Category III & IV) have more sensitive internal fault detection
by using a combination of protective devices as shown in Figure 1. For ratings between the above a
protection scheme is designed considering the service criticality, availability of standby transformers,
potential of hazardous damage to adjacent equipment and people etc.
1 of 12
Transformer Protection
Section 2
Electrical Protection
The electrical protection of the Transformer comprises of the following and each is elaborated
further.
• Fused Protection
• Differential Current Protection
2 of 12
Transformer Protection
Typically, fuses are used as primary protection for transformers below 10MVA. Above 10MVA
over current relays are used as back up along with differential relays as primary protection for
transformers. Instantaneous over current relays are also used for back up where differential relays have
been used. Typically they are set to 150% to 200% of the maximum of
1. Magnetising current inrush (If harmonic restraint is not used)
2. Short time load – Cold Pickup
3. Maximum 3 phase short circuit current
25 – 501, where
==
I 5 – 500 15 – 500 a – 1250 f 1250 t 2 at
2
60 Hz
60I I
a 70% – 100% of max possible fault where I2t =
II 501 – 1,667 501- 5,000 or 10
a+b K , K is determined at max I; where t = 2
a 50% – 100% of max possible fault where I2t =
1668 – 5,001 –
III or 5
10,000 30,000 a+c K , K is determined at max I; where t = 2
IV > 10,000 > 30,000 a+c – As Above
Note:
3 of 12
Transformer Protection
a)
It’s classified as Frequent Faults if the number of faults over the transformer life time is more than the
number shown. Else it’s classified as infrequent faults.
For category II & III the frequent fault curve may be used for backup protection in case it’s exposed
to frequent faults, but is protected by high speed primary relays
See Figure 3 – Guide to determine fault frequency
b)
I, symmetrical short circuit current in per unit of normal base current based on minimum nameplate
KVA rating; t, time in seconds; f, frequency in HZ.
4 of 12
Transformer Protection
5 of 12
Transformer Protection
==
Max withstand time curve ends point t 2 2 = 4.13sec
I 17.93
We now need to determine the points on the curve. The points above the dashed line
can be directly determined from the standard curve. The points on the dashed part of
the curve up to the end point as determined above are determined using the 1250
=
equation t 2. Some of the points are tabulated below:
I
Current PU
Time –t from Current PU From
Curve From Curve Current @ 480V
(a) (a) 1250
I= t
1000 2.3 6,916 500 2.8 8,419
300 3.0 9,021
100 4.0 12,028 50 5.0 15,035
12.5 10.0 30,070
4.13 17.39 52,296
6 of 12
Transformer Protection
3. CT Saturation – External fault currents can lead to CT saturation. This can cause relay
operating current to flow due to distortion of the saturated CT current. Alternatively the
harmonic current present in the saturated CT can cause a delay in the operation of the
differential relay during internal faults.
Proper selection of CT ratios is essential to minimize problems due to the saturation. CT
selection is discussed later
4. Different primary and secondary voltage levels, that is the primary & secondary CT’s are
of different types and ratios
5. Phase displacement in Delta-Wye transformers.
6. Transformer voltage control taps
7. Phase shift or voltage taps in regulating transformers
7 of 12
Transformer Protection
Step 1 – Phasing
The first step is to connect the CT’s so that the currents in the restraint windings are in phase.
There are to ways that this can be tried –
a) Connecting the ∆ side (ABC) CT’s in ∆ and the Y side (abc) CT’s in Y. However, in
case of a through ground fault, the secondary Y CT’s would circulate the zero sequence
currents through the restraint winding and as the HV primary windings are ∆
connected the corresponding zero sequence current would flow through the ∆ and the
same would not be sensed by the primary CT’s and hence the primary restraint
winding. This would lead to a current difference and cause the relay to operate on a
through fault. Therefore this would not be a correct option.
b) Connect ∆ side (ABC) CT’s in Y and, the Y side (abc) CT’s in ∆. In this case the zero
sequence currents would be restricted within the CT ∆ on the abc side and within the
main winding ∆ on the ABC side. Thus no zero sequence would flow through the
restraint winding and the balance maintained.
Next the CT’s must be connected so that the currents are in phase. Do this we assume balanced
current to be flowing through the transformer. Though we can assume flow in any direction it’s easier to
start with the Wye side. Assume Ia, Ib and Ic to be flowing out of the marked polarity this will cause the
current in the respective ∆ side windings to be (Ia – Ib), (Ib – Ic) and (Ic – Ia) and into the polarity
8 of 12
Transformer Protection
marked. The corresponding (ABC) CT current in the respective phase A, B & C restraint winding would
be (Ia – Ib), (Ib – Ic) and (Ic – Ia) and flowing from left to right as shown in figure 3. To maintain the
same phase in the ‘abc’ restraint windings the current in these should be the same i.e. (Ia – Ib), (Ib – Ic)
and (Ic – Ia) and flowing from left to right. The same can be obtained by connecting the abc side CT’s in
∆ as shown in the figure 3.
Step 2 – CT Ratio and Tap selection
Differential relay restraint winding’s typically have taps whereby difference in the restraint
current ratio can be set in the range of 2:1 or 3:1. The mismatch in the restraint currents is defined by
⎛ IIHL − TTHL ⎞
M =100× Abs⎜ ⎟%
⎝ S ⎠
Where:
S = Smaller Ratio of I
IHL & TTHL
Continuing with the transformer in our example
75000
IH == 313.8A at 138KV
3 138× Choosing
CT ratio as 400:5
IH = 3.92 = 0.516
IL 7.59
Let’s assume that we select relay taps as
T
TH =1 & L=2
9 of 12
Transformer Protection
Therefore
1
TH = = 0.5
TL 2
Using the mismatch equation M =100×
Section III
Gas Analysis
In oil immersed transformers different types of gases are generated due to different faults or due
to degradation of different materials in the transformer. The major advantage of this gas evolution is that
substantial amount of gas is evolved even for very incipient faults or material degradations. Thus
analysis of this gas forms a very important means for monitoring the health of the transformer or for
determining the fault in case of a fault.
The gas evolved is present dissolved in the oil. The gas is analyzed either online in case of such
systems have been installed on the transformer. Alternatively, oil samples are periodically withdrawn
and the oil is analysed in a lab. The periodicity depends on the size and criticality of the transformer. In
10 of 12
Transformer Protection
case a Gas Accumulation Relay (Buchholz Relay) is installed. These gases do get accumulated in it. Gas
samples or gas relays can be used in this case.
The implication of a few of the gases that may be observed in the oil is mentioned below.
Actual cause analysis is done by observing the ratio in which these gases are observed and is beyond the
scope of this report.
Hydrogen is generated by Corona or partial discharges. In conjunction with other gases observed
with it the source of the discharge can be determined
Ethylene is associated with thermal degradation of oil. Trace quantities of methane and ethane
are generated at 150° C. Ethylene is generated in significant quantities at 300° C.
Carbon dioxide &Carbon monoxide are evolved on when cellulose (paper) insulation gets over
heated.
Acetylene is produced significant quantities by arcing in oil
References:
1. Protective Relaying Principles and Applications, 3rd Edition by J Lewis Blackburn &
Thomas J Domin
2. IEEE Std. C37.91-2000
IEEE Guide for Protective Relay Applications to Power Transformers
11 of 12
Transformer Protec on Principles
1. Introduc on • on-load tap changer failures (mechanical, electrical, short
circuit, overhea ng)
Transformers are a cri cal and expensive component of the
power system. Due to the long lead me for repair of and Condi ons Protec on Philosophy
replacement of transformers, a major goal of transformer Internal
protec on is limi ng the damage to a faulted transformer.
Some protec on func ons, such as overexcita on protec on
Winding Phase-Phase, Differen al (87T), overcurrent (51,
and temperature-based protec on may aid this goal by
Phase-Ground faults 51N)
iden fying opera ng condi ons that may cause transformer Restricted ground fault protec on
failure. The comprehensive transformer protec on (87RGF)
provided by mul ple func on protec ve relays is appropriate
Winding inter-turn Differen al (87T), Buchholz relay,
for cri cal transformers of all applica ons. faults
External
45
4.2 Inrush Inhibit during Transformer Energiza
on:
The transformer energiza on resembles the condi on of
an internal fault. If no inhibi ng mechanism is provided,
the differen al element will trip. The magne zing inrush
current nd nd has significant 2 harmonic
content. The level of 2 harmonic current can be
used to differen ate between inrush and a fault condi on.
The UR T60 and T35 GE Mul lin nd transformer relays use
two different 2 harmonic modes to inhibit the
differen al element for inrush.
nd nd
Tradi onal 2 harmonic blocking – The tradi onal 2
harmonic restraint responds to the ra o of the
magnitudes of nd the 2 harmonic and the
fundamental frequency currents. nd nd
Ground fault current
Adap ve 2 harmonic blocking– The adap ve 2 harmonic
for impedance grounded neutral transformer for faults at different % of the winding.
blocking responds to both magnitudes and phase angles
of the nd
2 harmonic and the fundamental frequency currents. 46
The differen al element correctly dis nguishes between An alterna ve method for inrush inhibit is also available, where either
faults and nd transformer energiza on, when the 2 current, voltage, or breaker status is used to indicate a deenergized
harmonic current is nd nd less than the entered 2
transformer. The threshold can be lowered during energiza on of the
harmonic se ng. While levels of 2 harmonic during
inrush o en do not go below 20%, many nd transformers transformer as indicated either by breaker contact, current or voltage
are suscep ble of genera ng lower 2 nd harmonic sensing, and will last for a se able me delay. This allows se ngs of less
current during energiza on. Se ng the 2 harmonic than 20% for inrush inhibit during transformer energiza on.
restraint below 20% may result in incorrect inhibit of the Available in the 745.
differen al element during some internal fault events.
The
nd 4.3 Sensi ve Ground Fault Protec on to limit Transformer
adap ve 2 harmonic blocking allows se ngs in the tradi onal Damage
20% range, while maintaining the security of the differen
al element against inrush. Available in the T60, T35. Differen al and overcurrent protec on do not provide adequate protec
on for wye-connected windings with grounded neutrals. Faults close
to the neutral produces lesser fault current as shown by the current
distribu on curve. The restricted ground fault func on can be used to
provide differen al protec on for such ground faults, down to faults at
5% of the transformer winding. Restricted ground fault protec on can
be a low impedance differen al func on or a high impedance differen
86
Lockout
Power Transformers, HV Windings, Dual-Breaker Source Typical Func ons Addi onal Func ons
Lockout
Standalone
Integrated HEA61-A-RU-220-X2
T35-N00-HPH-FL-H6P-MN-P4L-UXX-WXX
T60-N00-HPH-FL-H6P-MN-P4L-UXX-WXX
Power System