Week 2
Week 2
Week 2
Noor Ul Ain
Topics to be Covered
Reference:
• Per unit analysis: Chapter 3, Article (3.13, 3.14), Hadi Saadat
• Impedance and Reactance Diagram: Chapter 1, Article (1.13, 1.14),
Stevenson
• Bus Admittance Matrix: Chapter 6, Article (6.1, 6.2), Hadi Saadat
Example - 1
Draw the impedance diagram of the following network with all reactances
marked in per-unit.
• A-B: 10000 kVA, 13.8/138kV, leakage reactance = 10%
• B-C: 10000 kVA, 138/69kV, leakage reactance = 8%
Select parameters of circuit B (10000 kVA, 138 kV) as base parameters
of system, find the per-unit impedance of 300 Ω resistive load in circuit
C referred to circuits C, B and A.
Solution
• SB = 10000
• VB for circuit B is 138 kV
• VB for circuit A is 138 kV × 1
10 = 13.8 kV
• VB for circuit C is 138 kV × 1
2 = 69 kV
ZL = 300Ω
(kVB )2 × 1000 (69)2 × 1000
ZB = = = 476 Ω
kV AB 10, 000
ZL 300
Zpu = = = 0.63pu
ZB 476
Load impedance referred to circuit B
2
2
ZL ( referred to circuit B ) = × 300 = 1200 Ω
1
(138)2 × 1000
ZB ( referred to circuit B ) = = 1900 Ω
10, 000
ZL 1200
Zpu ( referred to circuit B ) = = = 0.63 pu
ZB 1900
0.1j pu 0.08j pu
0.63 pu
Example - 2
Draw the reactance diagram of the following network with all reactances
marked in per unit.
• Generator: 300 MVA, 20 kV, X = 0.2 pu
• Transformer T1 : 350 MVA, 20/230 kV, X = 0.1 pu
• Transmission Line: 64 km, X = 0.5 Ω/km
• Transformer T2 : 3, 1-phase transformers each
100 MVA, 127/13.2 kV, X = 0.1pu
• Motor M1 : 200 MVA, 13.2 kV, X = 0.2 pu
• Motor M2 : 100 MVA, 13.2 kV, X = 0.2 pu
Solution
SB = 300 MVA
VB of circuit 1: VB1 = 20 kV
VB of circuit 2: VB2 = 230 kV
VB of circuit 3: VB2 = 13.8 kV
300 20 2
Xg1 = j0.2 × × = j0.2 pu
300 20
2
300 20
XT1 = j0.1 × × = j0.0857 pu
350 20
300 230 2
XT1 = j0.1 × × = j0.0857 pu
350 230
MV AB
XT L = Xa ×
(RVB )2
300
= 0.5 × 64 × = j0.18 pu
(230)2
(EED, UET Lahore) Week 2 January 24, 2025 11 / 34
Impedance and Reactance Diagram
300 13.2 2
XT2 = j0.1 × × = j0.09 pu
300 13.8
√ !2
300 127 3
XT2 = j0.1 × × = j0.09 pu
300 230
300 13.2 2
Xm1 = j0.2 × × = j0.27 pu
200 13.8
300 13.2 2
Xm2 = j0.2 × × = j0.54 pu
100 13.8
Reactance Diagram
0.2j
0.27j 0.54j
Eg Em1 Em2
Example - 3
Assume a three-phase, unity power factor load of 100 MVA with VLL of
69 kV is connected to a source through the below network. Convert the
two impedances to per unit,and then determine the per unit generator
voltage (magnitude and angle). Use a per unit three-phase 100 MVA
base, a line-to-line 138 kV voltage base on the left side of the
transformer and a line-to-line 69 kV voltage base on the right side
5.06 + j23.7 4j Ω
138:69
• VG pu =1.047 ∠11.45◦ pu
(EED, UET Lahore) Week 2 January 24, 2025 14 / 34
Nodal Analysis
VS 1
IS = and YS =
ZS ZS
• Y11 , Y22 , Y33 , Y44 are the self admittance of node or bus and are sum
of all admittance connected to that bus
• Y12 , Y13 , Y23 and Y34 are mutual admittances and are negative of
admittance connected between selected buses i and j.
(EED, UET Lahore) Week 2 January 24, 2025 19 / 34
Nodal Analysis
are modified to
I1 = Y11 V1 + Y12 V2 + Y13 V3 + Y14 V4
I2 = Y21 V1 + Y22 V2 + Y23 V3 + Y24 V4
I3 = Y31 V1 + Y32 V2 + Y33 V3 + Y34 V4
I4 = Y41 V1 + Y42 V2 + Y43 V3 + Y44 V4
In matrices form
I1 Y11 Y12 Y13 Y14 V1
I2 Y21 Y22 Y23 Y24 V2
=
I3 Y31 Y32 Y33 Y34 V3
I4 Y41 Y42 Y43 Y44 V4
−j8.50 j2.50 j5.00 0
j2.50 −j8.75 j5.00 0
Ybus =
j5.00 j5.00 −j22.50 j12.50
0 0 j12.50 −j12.50
−1
Vbus = Ybus Ibus
• Ibus is the vector of the injected bus currents (i.e., external current
sources).
• The current is positive when flowing towards the bus, and it is
negative if flowing away from the bus.
• Vbus is the vector of bus voltages measured from the reference node
(i.e., node voltages).
• Ybus is known as the bus admittance matrix.
• The inverse of the bus admittance matrix is known as the bus
impedance matrix Zbus .
Example - 3
Find Ybus
Solution
−j14.5 j8.0 j4.0 j2.5 V1 0
j8.0 −j17.0 j4.0 j5.0 V2 0
=
j4.0 j4.0 −j8.8 0.0 V3 1.00∠ − 90◦
j2.5 j5.0 0.0 −j8.3 V4 0.68∠ − 135◦
(EED, UET Lahore) Week 2 January 24, 2025 29 / 34
Ybus
Example - 4
Find Ybus
Example - 5
Find Ybus
Thank You