Genrator Protection 1
Genrator Protection 1
Niwat Sriklam
Generator Protection
The extent and types of protection specification
will be depend on the following factors :
Type of prime mover and generator construction
MW and voltage rating
Mode of operation
Method of connection to the power system
Method of earthing
Via Transformer :
Y Generator Y Generator
Transformer Station Transformer
Transformer
Earthing
Transformer
Unit/Station Unit
~ Transformer ~ Transformer
Y Y
R
R
Rotor
Welding of lamination
R low R High R
VT
Distribution Effective
R
Transformer High
Medium R
Effective
1/28/2008 Power System Protection High 18
Method of Earthing
Resistance Earthing via Earthing Transformer
Medium R
Distribution Tuned
Transformer
~ Y
Fault
~ Y
Fault
~ Y
Fault
~ Y
Fault
51
51
51N
50 51N
51N
50 51N
250:1
33 Ω
xV
R
Is IF = xV/R
For operation
Is (Primary) < IF
Is (Primary) < xV/R
< x.6600/33 < x.200
Is (Secondary) < x200x1/250 < 0.8.x
For protection of 90% of winding ; x = 1-0.9 = 0.1
Relay setting = 0.8x0.1 = 0.08A = 8% of 1 A
~ Y
51N 50N
Effective
Distribution High Overvoltage relay with
R 59
Transformer 3rd Harmonic rejection
Turn Ratio = N
SET > 3rd Harmonic current
51N
Or use relay with 3rd Harmonic Rejection
Field forcing
RStab
64
RStab
5xCT’s Required
64
Rstab
51N
4xCT’s Required
Earthing at busbars
R
R Stabilizing
87 87 87 Relay
B B
B B
B B
87 87 87 Operate
~ Y
50N
Injection
Transformer
~
~
No load
NEUTRAL TERMINAL
No load +V 3rd
Full load
NEUTRAL
Full load Normal Operation No load
-V 3rd
TERMINAL
NEUTRAL
No load
Fault at Neutral
Earthing
Transformer
R 59 27 59P
59P 59
27
Trip
27 Overlap
0 50 100
Earth Fault Position
1/28/2008 Power System Protection 48
Neutral to Ground Fault Detection
R 59N
59D
59N 59D
51 51 51
R
R Stabilizing
87 87 87 Relay
VA VB VC
Fault
VA
VB
VC
R
VR
3rd Harmonic rejection required VR = VA + VB + VC
1/28/2008 Power System Protection 56
Stator Interturn Fault Protection
B B
Transverse Differential Protection
B B (Double Wound Machines)
B B
87 87 87 Operate Coils
instantly recognized
P1
86A
P2
LP-1
2
86B
86A
P1 = Protective devices tripping CB via power interlock Trip Steam
P2 = Protective devices tripping CB direct
86A,86B = Trip relays 86B
LP = Low forward power interlock relay Trip Circuit
Breaker
Field
Exciter
Winding
Ie _
+
DC Relay (Setting < Ie Min)
0.2-1 Sec
T1
T2
Requires access to field connections 2-10 Sec Trip
Or
Not suitable if generator operates in normally with Alarm
low excitation (Large machines)
Alternative scheme monitors impedance at generator terminals
1/28/2008 Power System Protection 63
Loss of Excitation
XG XT Xs
EG ES
Diameter
Relay Characteristic
Typical :
Offset 50-75% Xd’ Time Delay
Diameter 50-100% Xs
-R R
R
Offset
Diameter
Relay Characteristic
XM XT Zs
EG
∑Z = |XM+XT+ZS | /Ө
0’
Zs S
T
XT ∑Z = |XM+XT+ZS | /ө
-R New axis F’ R
Relaying Point R EG > 1.0
F’ ES
Xm
EG = 1.0
jX
ө ES
A
0’ EG < 1.0
ES
-jX
1/28/2008 Power System Protection 70
Impedance Locus of the pole
Slipping Generator System
Relay Location
Xd
I
~
E
IXd
E V
V
σ Ø I
δ = Rotor angle
Ø = Power Factor Angle
Ø V2/C R
V.I.Cos Ø = C
I. Cos Ø = C
V V2
Z = V2 Cos Ø
C
jX
Offset 0.75Xd’
Constant σ
Relay Characteristic
ZA R
PF 0.5
46
Ia IaVZA +VZC
VZA VZA
VZC
Ic VZC Ib Ib Ic
Field
Exciter
Winding
Field
Exciter
Winding
~ AC. auxiliary
supply
R
Brushless Machines
No access to rotor circuit
Require special slip ring for measurement
If slip rings not present, must use tele-metering technique
1/28/2008 Power System Protection 82
Overload protection
Insulation Failure
51
51
~ ∆ Y
51
1/28/2008 Power System Protection 87
Generator Back-up Protection
Overcurrent Protection
Typical use :-
Very or extremely inverse for LV machines
Normal Inverse for HV machines
Must consider generator voltage decrement characteristic for close-in
faults
With reliable AVR system, “Conventional” overcurrent relay may be
used
Otherwise, voltage controlled / restrained relay are required
10xFL
With AVR
Full
Load
No AVR
Cycle
1/28/2008 Power System Protection 89
Generator Back-up Protection
Overcurrent Protection
Voltage Restrained
Operating characteristic is continuously varied depending
on measured voltage
Preferred option when generator is connected via step up
transformer
Alternatively use impedance relay
Voltage controlled
Relay switches between fault characteristic and load
t
Overload characteristic
(Normal voltage)
10
Fault
Characteristic
(Low voltage)
10 I
overload
fault
Is Is+ΔIs i
V
Vs setting range
overload
fault
Is Is+kΔIs i
V
k= V/ Vn-0.55/.35
6.6 kV bus
5 MVA
115%Xs
~
200:5
500:5
Fault Characteristic
1.0 Longest Outgoing Feeder
0.1
Generator Decrement curve
0.01
Amp
100 200 600 1000 3000 10,000
1/28/2008 Power System Protection 95
Impedance Relay
iX
Relay
Under Voltage
No danger to generator, may cause stalling of motors
Prolonged under voltage indicates abnormal conditions
saturation limited)
Under Voltage
No danger to generator, may cause stalling of motors
Prolonged under voltage indicates abnormal conditions