Sizing Example #1
Sizing Example #1
2,160 𝑤𝑎𝑡𝑡𝑠
𝐼= = 9.39 𝑎𝑚𝑝𝑒𝑟𝑒𝑠
230 𝑤𝑎𝑡𝑡𝑠
Conclusion:
The fuse rating is 20 amperes. Granting
that only 80% of 15 amperes is considered the
derated value is still higher than the computed
load of 15.65 amperes.
𝐼 = 28.52 𝑎𝑚𝑝𝑒𝑟𝑒𝑠
2. Apply 80% demand factor as
permitted by the National
Electrical Code
4Spare - 230
Scheduling
Total Current= 28,62 amp. X 80% demand factor = 22.8 amp
Use 2 pieces 8𝑚𝑚2 TW cu. Wire @ 20 mm conduit pipe
RSC – Rigid Solid Conduit
IMT – Intermediate Metal Tube
PvcCP – PVC Conduit pipe
THW – Thermoplastic moisture and heat resistance @ 45 amperes up.
TW – Thermoplastic moisture resistance @ 40 amp. Below.
Note: The quantity of
materials is subject to change
depending upon the area and
the choice of the designing
engineers. For open wiring
installation, conduit pipe can
be change to split knobs or
PDX wires