XDLC

The Siemens Fire Safety Class X Device Loop Card (Model XDLC) connects up to 252 addressable devices and supports multiple circuit configurations. It features diagnostic LEDs, ground-fault detection, and communicates device data to fire alarm control panels. The XDLC is UL and ULC listed for indoor use and operates within specified temperature and humidity ranges.

Uploaded by

Md Mouse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views2 pages

XDLC

The Siemens Fire Safety Class X Device Loop Card (Model XDLC) connects up to 252 addressable devices and supports multiple circuit configurations. It features diagnostic LEDs, ground-fault detection, and communicates device data to fire alarm control panels. The XDLC is UL and ULC listed for indoor use and operates within specified temperature and humidity ranges.

Uploaded by

Md Mouse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Cerberus® PRO Modular

System
Device Loop Card
Model XDLC

Architect & Engineer Specifications Product Overview


 Supports up to 252 addressable points The Siemens – Fire Safety `Class X’ Device Loop Card (Model XDLC) is the interface
used for connecting Siemens addressable, intelligent `X’ as well as `H’-series devices.
 Operates and maintains all devices
residing on up to four (4) `Class A’, Each Model XDLC plugs into one (1) slot of the Model CC-2 or Model CC-5 card cage.
eight (8) `Class B’ addressable circuits XDLC is accomplished via the Cerberus® PRO Modular , FireFinder® XLS and XLSV
 Compatible with Siemens intelligent, custom-configuration tool, Zeus-C. Model XDLC takes one (1) address on the
addressable ‘X’ and ‘H’-series devices: network, communicating up to a total 252 detectors and devices. Model XDLC has
- Multi-criteria / Carbon Monoxide (CO) 16 LEDs for diagnostic purposes, and provides ground-fault detection and zone-
Detector with ASAtechnologyTM isolation circuitry.
- Multi-criteria Detector
with ASAtechnologyTM
- Multi-criteria Detector Specifications
- Thermal (Heat) Detector The `Class X’ Device Loop Card (Model XDLC) initializes, operates and maintains all
- Input / Output Interface Module devices residing on up to four (4) ` Class A’, eight (8) `Class B’ addressable circuits.
 Polarity insensitive (in non-isolation Model XDLC communicates all relevant device and event data ( `Alarm’, Trouble’ and
mode) via SureWire™ technology: `Supervisory’ commands) to a Cerberus PRO Modular, FireFinder® XLS and XLSV fire-alarm control
- Modern technology supports panel (FACP), and supervises the device loop circuit.
comprehensive system and
interface communication Model XDLC is polarity insensitive via SSureWire technology, which greatly reduces
commissioning time normally spent tracing down crossed-field wiring. Model XDLC
 Quantity 16 diagnostic light-emitting
communicates detector data, such as sensitivity of intelligent fire detectors and logic-
diodes (LEDs) for easy circuit diagnosis
function information, to the Cerberus PRO Modular Operating Unit (Model FCM2041-
 Microchip controls on-board isolators U3), which is located within a given Cerberus® PRO Modular System, FireFinder® XLSV.
 Device Programmer / Tester
(Model DPU) programs and
Each device loop card supports four (4) `Class A’, eight (8) `Class B’ circuits for up to a
verifies device’s address: total of 252 addressable devices – as well as relay and audible bases, remote lamps
- programming capabilities include and duct-detector housings in any combination.
testing a duct detector, as well as
other Siemens addressable devices The microprocessor in a Model XDLC controls the
on-board isolation, in case there is a fault (short) in
 Supports `Class B’ | `Class A’ any of the circuits, thus allowing the other circuit to
| `Class X’ wiring
continue operating. For continuous protection, the
 Supports T-Tapping on-board microprocessor continues to operate even
 Degrade mode in the event of a CPU failure.
 UL864 | CAN / ULC Listed
NOTE: Refer to installation manual: P/N –
A6V101040156 to ensure Model XDLC
compatibility with the Siemens FACPs
intended for use in the given
application.

Model XDLC d

Side View
Model d

XDLC d

Front View

Siemens Data Sheet 8312


Smart Infrastructure – Building Products usa.siemens.com/fire
Model XDLC-
Diagram of an `Class X’ Device Loop Card
mounted to a Siemens Card Cage

Temperature and Humidity Range


`Class X’ Device Loop Cards are UL Listed | ULC Listed for indoor dry locations within a temperature range of 120+/-3°F
(49+/-2°C) to 32+/-3°F (0+/-2°C) and a relative humidity of 93+/-2% at a temperature of 90+/-3°F (32+/-2°C).

Technical Data Details for Ordering


24V CURRENT DRAW: MODEL PART
0 PRODUCT
[Back Plane] OR TYPE NUMBER

24V CURRENT DRAW: 100mA `Class X’


XDLC S54430-B8-A1
[Standby Current] Device Loop Card

6.2V CURRENT DRAW:


1mA, max.
[Back Plane]

24V CURRENT DRAW: 100mA


[Alarm Current]

DEVICE LOOP:
500mA, max. (power limited)
[@ 30 VDC Max.]

NOTICE – The information contained in this data-sheet document is intended only


as a summary, and is subject to change without notice.
The product(s) described here has/have a specific instruction sheet(s)
that cover various technical, limitation and liability information.
Copies of install-type, instruction sheets – as well as the General Product
Warning and Limitations document, which also contains important data,
are provided with the product, and are available from the Manufacturer.
Data contained in the aforesaid type of documentation should be consulted
with a fire-safety professional before specifying or using the product.

Any further questions or assistance concerning


particular problems that might arise, relative to the
proper functioning of the equipment, please contact
Cerberus® PRO
Siemens Industry, Inc.
the Manufacturer.
Smart Infrastructure – Building Products
2 Gatehall Drive • Parsippany, NJ 07054
Tel: (973) 593-2600
February -2023
(Rev. 3)