AIIe DP
AIIe DP
Transmitter
The FCX–AIIe differential
pressure (flow) transmitter accurately
measures differential pressure, liquid
level, gauge pressure or flow rate
and transmits a proportional 4 to 20
mA signal. The transmitter combines
a unique silicon capacitance sensor
with state-of-the-art microprocessor
technology to provide exceptional
performance and reliability.
Features
High Performance Application Flexibility
Combine the proven variable capacitance Various features and options make the FCX–AIIe
measurement principle with a sensor machined from a suitable for a wide variety of process applications:
single silicon wafer and the result is a performance • All 316 and 316L SST wetted parts
specification traditionally reserved for the elite class • 30:1 turndown for all ranges
transmitter. The standard accuracy of the FCX-AIIe • Analog indicator orients in either the vertical or
±0.1% and long term stability is ± 0.2% for three years. horizontal plane.
Isolated Sensor • Full range of hazardous area approvals
The "Advanced Floating Cell" serves to increase the • RFI filter and lightning arrester
mechanical integrity of the measuring cell by isolating • 5-digit LCD meter with support for engineering units
the silicon sensor from adverse conditions present in
Output Linearization
normal process applications. This unique cell
In addition to selectable linear or square root outputs,
construction reduces total measurement error by
the AIIe can also be programmed to linearize a
minimizing the effects of varying process temperature, Barton Instrument Systems, LLC
differential pressure curve of up to 14 points. This
static pressure, and overpressure. 900 S. Turnbull Canyon Road
programmable functionality renders the transmitter
suitable to tank volume applications. City of Industry, CA 91745
Communication Protocols
The FCX–AIIe communicates in both Fuji proprietary
Burnout Flexibility T (626) 961-2547
and HART(r) protocol. Any HART®compatible device
The AIIe's burnout signal is adjustable via the hand
can communicate with the FCX–AIIe. F (626) 933-7241 (Sales)
held communicator to either under scale (3.2 to 3.8 mA)
e [email protected]
over scale (20.8 to 21.6 mA) or output hold (last value)
complying with NAMUR NE43.
Specifications S
FUNCTIONAL SPECIFICATIONS Zero/span adjustment:
Service Adjustable via the HHC or external adjustment screw.
Liquid, gas, or vapor Damping:
Span and range limit Adjustable between 0 to 32 seconds via the HHC
DIFFERENTIAL PRESSURE Zero elevation/suppression:
Calibrated Span –100% to +100% of URL. Zero plus span not to exceed URL.
Range Minimum Maximum
Code in w.c. (psi) kPa mBar in w.c. (psi) kPa mBar Normal/reverse action
33 4 1.06 10.6 125 32 320 Selectable from HHC.
34 17 4.33 43.3 520 130 1300
35 (2.5) 16.66 166.6 (72) 500 5000 Burnout direction
Selectable from HHC
Vacuum Limitation If self-diagnostic detects transmitter failure, the analog signal will
Silicone fill sensor: Silicone Oil (Code:Y & G)
be driven to either “Output Hold” (last value), “Output Overscale”
(see diagram) 101 (between 20.8mA to 21.6mA) or “Output Underscale”
OPERATING PRESSURE , kPa abs (psi abs)
(14.65)
Fluorinated fill sensor: (between 3.2mA to 3.8mA).
66kPa abs /
Loop-check output
500mm Hg abs /
20 Operating Area
Any constant signal between 3.8mA and 21.6mA via HHC.
9.6 PSI abs (2.90)
at 60°C max. Temperature limit
Ambient: –40 to +85°C ( –40 to +185°F)
Static pressure and 4 –20 to +80°C ( –4 to +176°F) for LCD indicator
over range limit (0.58)
–40 to +60°C ( –40 to +140°F) for arrester option
16 MPa (2300 psig) 2.7
(0.39)
–10 to +60°C ( –14 to +140°F) for fluorinated oil filled transmitters
Output signal Non-operating Area
For explosion-proof units (flameproof or intrinsic safety), ambient
4 to 20mA DC c/w – 40 60 120 temperature must be within the limits specified in each standard.
HART & Fuji Protocol (-40) (140) (248)
Process: –40 to +120°C ( –40 to +248°F) for silicone fill sensor
PROCESS TEMPERATURE , °C (°F)
Power supply –20 to +80°C ( –4 to +176°F) for fluorinated oil fill sensor
Transmitter operates Storage: – 40 to +90°C ( –40 to +194°F)
on 10.5V to 45V DC at transmitter terminals. Humidity limit
10.5V to 32V DC for the units with optional arrester. 0 to 100% RH
Load limitations: see figure below Communication
Hart or Fuji proprietary protocol.
2000
1533 Ω Programmable output linearization function:
LOAD RESISTANCE , Ω
Process connections:
1/4-18 NPT or Rc1/4 on 54mm (2-1/8’’) centers, as specified. Accessories
Meets DIN 19213. Flange adapters:
Process-wetted parts material: Converts process connection to 1/2-14 NPT in carbon steel or in
316 stainless steel.
Material
code Wetted Hand-held communicator:
(7th digit Process cover Diaphragm sensor body Vent/drain
in Code Installed with Fuji Proprietary Protocol.
symbols)
V 316 stainless 316L stainless 316 stainless 316 stainless
steel steel steel steel
Notes:
1 The static pressure of any transmitter with B7M, L7M or 304SS bolting must be limited to 1450 psi (+10MPa) max.
2 Specify SS bolts for all tropicalized service
3 Specify this field only when necessary
Outline Diagram
FCX-AIIe Differential Pressure Transmitter
Bracket may be
wall mounted.
Four 9 mm (3/8’’)
diameter holes,
Zero Adj. Screw
2’’ pipe Detail “A”
Pressure Connection
(1-11/16’’)
(3-1/16’’)
43.5
120 (4-11/16’’)
130 (5-1/4’’)
ø 80
(3-1/16’’)
ø 80
52.5
(2’’)
38
U-Bolt Vent / Drain Plug
(1-1/2’’)
58 37
(2-5/16’’) (1-7/16’’)
210 27
(8-1/4’’) Detail “B” 154 (6’’)
(1-1/16’’)
Conduit Connection
59 43
(2-5/16’’) (1-11/16’’)
With Field Indicator (option)
Earth Terminal
231 (8-3/8’’)
Side Vent
(option)
(5/16’’)
Sensor
8
(1-5/8’’)
Unit
41.3
E
Pressure Connection
Pressure Connection
ø7 (High Pressure Side)
(Low Pressure Side)
(1/4’’) D
See Table 1 See Table 1
54 (2’’)
70 (2-3/4’’)
Local
Indicator