RAHU & Mixed AHU Sequence

SUPPLY FAN CONTROL:

The supply fan (SF-C) will be started based on occupancy schedule. The supply fan speed (SF-
O) will modulate from the minimum speed to the maximum cooling speed as the cooling command
increases and from the minimum speed to the maximum heating speed as the heating command
increases. When the supply fan status (SF-S) indicates the fan started, the control sequence will
be enabled. Upon a loss of airflow (SF-S), the supply fan will attempt to automatically restart until
positive status is received.

TEMPERATURE CONTROL:

The unit will control to maintain the return air temperature setpoint (RAT-SP) as sensed by the
return air temperature (RA-T) sensor.

COOLING COIL:

The cooling coil (CLG-O) will modulate to maintain the temperature setpoint. When the unit is
shutdown, the cooling coil will be off. Upon a loss of airflow (SF-S), the cooling coil will be off.

ADDITIONAL POINTS MONITORED BY THE FMS:


• Supply Fan Status (SF-S)
• Prefilter Status (PFILT-S)
• Bag filter Status (BFILT-S)