Illumination Specification
Illumination Specification
SECTION – E1
SUB-SECTION-XI
TECHNICAL SPECIFICATION
FOR
ILLUMINATION SYSTEM
DCPL-K6A11
CONTENT
ATTACHMENTS
SECTION – E1
SUB-SECTION-XI
TECHNICAL SPECIFICATION
FOR
ILLUMINATION SYSTEM
1.01.00 This section is intended to cover the design, manufacture, assembly, testing at
manufacturer's works, supply & delivery, properly packed for transport F.O.R.
site of LIGHTING SYSTEM, complete with all materials and accessories for
efficient and trouble-free operation.
1.02.00 The scope of work shall also include complete installation, testing,
commissioning and putting into successful commercial operation of the
Lighting System, inclusive of the supply of all labour, tools, implements and
supplies.
1.03.00 The major areas to be illuminated under the scope of this package are listed in
Annexure-B. The areas listed are however indicative only for the purpose of
guidance to the bidder and is subject to change during detail engineering after
finalisation of layouts.
2.01.00 The equipment and materials within the scope of supply shall include but not
limited to:
S-E1/SS-XI : 1
DCPL-K6A11
Major standards which shall be followed are listed below. Other applicable
Indian standards even if not covered in the listed standard shall be followed.
S-E1/SS-XI : 2
DCPL-K6A11
16. IS-694 PVC insulated Cables for working voltage upto &
including 1.1KV.
17. IS-1554 PVC insulated (heavy duty) electric cable
18. IS-9537 Conduits for electrical installations
19. IS-14772 Boxes for the enclosure of electrical accessories
5.01.01 The system provides lighting and electric power supply for lighting to all pump
house areas under scope of this package. In addition, it also provides lighting
to selected areas during emergency conditions.
5.01.03 The design shall be such as to provide minimum lighting levels as specified for
different areas.
5.01.04 The systems shall be suitable for operation on available power supply having
characteristics as given in the annexure.
This will be provided by A.C. lighting fixtures distributed throughout the pump
house. These lights will be ON as long as the A.C. supply is available.
A.C. lighting fixtures will be fed from respective area lighting panels, which in
turn will be connected to main lighting distribution board. The main lighting
distribution boards will be fed through respective 1:1 ratio lighting transformer
which forms a part of the MLDB. Normal A.C. supply thus made available by
the MLDB is 415V-3ph-4W-50HZ effectively grounded.
S-E1/SS-XI : 3
DCPL-K6A11
c) These lights will be ON all the time - normally from A.C. supply, but on
its failure from D.C. supply through automatic switching.
This will be provided in isolated building/area where station D.C. supply is not
available by self-contained battery/automatic charger/inverter/flood light units.
These portable emergency light units will be energized automatically on loss
of normal A.C. supply.
Time switch and photo-cell will be used for controlling street lights with
provision for manual override.
Same arrangement will also be used for controlling switchyard extension area
illumination.
5.03.01 All equipment and accessories shall be designed for continuous operation
under site conditions without exceeding permissible temperature rise as
stipulated in relevant standards.
5.03.02 Switch, fuses, miniature circuit breakers (MCB), busbar shall be fully rated for
short circuit level at the point of application. MCB shall have back-up HRC
fuse if its rating is less than the available short circuit current.
5.03.03 All equipment and accessories shall have proper enclosure to suit the site
conditions. Hazardous areas shall have flame-proof enclosure.
5.03.04 All wiring from lighting panels to fixtures and receptacles shall be carried out
by PVC wires in G.I. Conduits.
5.03.05 Heavy duty AXWY FRLS cables will be used only for connections:
5.04.01 Standard Lumen method shall be adopted for interior & exterior lighting in
order to determine the number of lighting fixtures for obtaining the desired
average level of illumination.
5.04.02 The coefficient of utilization shall be considered to take care of Lumen loss
due to -
e) mounting height.
5.04.03 Moreover a maintenance factor shall also be considered to account for the fall
of illumination due to aging, pollution like dust deposit etc. Maintenance
factors to be considered for various areas shall be as follows:
5.04.04 Lux level to be considered for various areas are given in Annexure-D.
5.04.05 Voltage drop at the fixture from the MLDB bus shall not exceed 3%
5.04.06 Circuit loading of each lighting Panel shall be done in such a way that almost
balanced loading in all the phases i.e R, Y & B is achieved.
5.04.07 At least two sub circuits shall be used for illumination of a particular area.
5.04.08 Sub circuit loading of each lighting panel shall be restricted to 2000 Watts.
S-E1/SS-XI : 5
DCPL-K6A11
6.01.01 Equipment and material shall comply with description, rating, type and size as
detailed in this specification, drawings and annexures.
6.01.02 Equipment and materials furnished shall be complete and operative in all
details.
6.01.03 All accessories, control devices, internal wiring, fittings, supports, hangers,
anchor bolts etc. which form part of the equipment or which are necessary for
safe and satisfactory installation and operation of the equipment shall be
furnished.
6.02.01 Lighting fixtures shall be designed for minimum glare. The surface finish shall
be smooth, unobtrusive and scratch resistant.
6.02.03 Fixture shall be suitable for 20 mm conduit entry and 16 SWG G.I. earth wire
connection.
6.02.04 High bay fixtures shall have provision for vibration damper to ensure rated
lamp life. Cost of each damper shall be separately indicated.
6.02.05 Fixture shall be furnished complete with lamps and integrally/non integrally or
separately mounted control gear & accessories as applicable for different
types of fixtures. These shall include holders, ballast, capacitor, starter,
ignitors etc.
6.02.06 Fixtures shall be fully wired up to respective terminal blocks, suitable for loop
in and loop out connection of PVC wires of following sizes :
a) Lighting fixture : 2.5 mm2 Copper
b) Flood Light fixture : 2x2.5 mm2 Copper
6.03.00 Lamps
6.03.01 General lighting service (GLS) lamps shall be with clear glass and screwed
caps.
6.03.02 All fluorescent lamp shall be bi-pin rotary type and either cool daylight or white
as per annexure. Lamp holder shall be spring loaded, low contact resistance
type and shall have resistance to wear.
S-E1/SS-XI : 6
DCPL-K6A11
6.03.03 Mercury/Sodium vapour lamp shall be colour corrected type with screwed cap.
6.03.04 Lamps shall be suitable for use in position and capable of withstanding small
vibrations. Restrictions and special features, if any, shall be clearly indicated
in the bid.
6.04.01 Ballasts shall be heavy duty, low loss, polyster-filled type with copper winding.
6.04.02 Ballast for Mercury/Sodium vapour lamp shall be provided with suitable
tapping to set the voltage within range specified.
6.04.03 Ballasts shall be free from hum. Ballasts which produce humming sound shall
be replaced, free of cost, by the Contractor.
6.04.04 In multi-lamp fixture, each lamp shall be provided with individual ballast.
6.04.05 Ballast windings shall have maximum operating temperature of 120 oC without
rated temperature rise marking.
6.04.06 Electronic Ballast shall be suitable for 220 V DC and also 240 V AC.
6.04.07 Electronic Ballast shall be compact, light weight, high frequency electronic
standard ballast for fluorescent lamps.
6.04.08 It shall be Flicker-free warm start, ideal for areas with high switching
frequency.
6.04.09 Electronic Ballast shall be of such design that minimum 25% reduction in
energy consumption at constant luminous flux compared with conventional
gear.
6.04.11 Electronic Ballast shall provide constant light independent of mains voltage
fluctuation.
6.05.02 Indoor Lighting Distribution Boards & Lighting Panels shall be dust and
vermin-proof, IP-52 or better; outdoor panels shall be weather-proof with
canopy, IP-55 or better. The cubicle housing transformer shall be minimum
IP-42 Lighting Distribution Boards and Lighting.
S-E1/SS-XI : 7
DCPL-K6A11
6.05.04 Lighting Distribution Boards shall have provision of cable entry from bottom
and, panels shall have provision of cable entry from top and bottom, as
required, with removable gland plates. Necessary double compression type
brass cable glands, tinned copper/Aluminium cable lugs are to be furnished.
6.05.05 Two ground pads with M10 G.I. bolts and nuts shall be provided on each
Lighting Distribution Board and Lighting Panel for connection to ground
conductor.
6.05.06 Each Lighting Distribution Board shall be complete with designation and
caution notice plates fixed on front cover and a directory plate fixed on inside
of the front cover. This directory plate shall contain details of the Lighting
Panels being fed from the Distribution Board including their designation,
location, loading etc.
Each Lighting Panel shall be complete with designation and caution notice
plates fixed on front cover and a circuit directory plate fixed on inside of the
front cover. Circuit directory plate shall contain details of the points to be
controlled by each circuit including the location of the point controlled, rating of
the protective units and loading of each circuit.
6.05.07 Bus bar shall be electrolytic grade hard drawn aluminium, colour coded for
easy identification and designed for a maximum temperature of 85ºC.
Minimum size shall be 25 x 6 mm.
6.05.08 Incoming and outgoing circuits shall be terminated in suitable terminal blocks.
6.06.01 Each Distribution Board shall consist of one dry type transformer housed in
the cubicle voltmeter with selector switch, C.T. operated ammeter and
incoming triple pole switch. Outgoing feeder from the Lighting Distribution
Board shall have switch fuse units. Proper discrimination between outgoing
fuse of Lighting Distribution Board and downstream MCB of Lighting Panel
should be ensured.
6.06.02 Each panel shall have an incoming triple pole switch fuse with neutral link and
a number of outgoing miniature circuit breakers (MCB) as per annexure.
6.06.03 Board/Panel access door shall be interlocked with incoming switch such that
the door can be opened only when the switch is in OFF position. Means shall
be provided to defeat this interlock.
S-E1/SS-XI : 8
DCPL-K6A11
6.06.04 All switches shall be heavy duty, quick-make quick-break type. Fuses shall be
HRC link type. Contractors shall be air break electromagnetic type. Push
buttons shall be push to actuate type.
6.06.05 MCB shall be suitable for manual closing and opening and also automatic trip
on overload and short circuit.
6.06.06 Time switch in street lighting panels shall be clock switch type with ON-OFF
time setting facility which shall ensure respective ON-OFF operation in every
24 Hours cycle. Voltmeter/Ammeter shall be of accuracy class 2.0 or better as
per IS:1248. Voltmeter/Ammeter selector switch shall be of reputed make.
6.07.00 Receptacles
6.07.01 Receptacles shall be heavy duty, complete with individual plug and switch as
detailed in the annexure.
6.07.02 The conduit box of the receptacle shall be provided with earthing screws with
washer and nuts welded on the surface for grounding with 16 SWG G.I. wire.
Arrangement shall be provided inside the conduit box for grounding of third
pin.
6.08.01 The fans shall have three well balanced blades, and shall be reasonably free
from noise. Pedestal fans shall also be provided as per Owner’s requirement.
6.08.02 Fan motor shall be totally enclosed type with copper winding and class E
insulation.
6.08.03 Regulator shall have minimum five steps. Electronic regulator with smooth
control is preferred.
6.09.02 Switch boards/boxes located in control room and office areas shall be flush
mounted type on brick wall with only the switch knob projecting outside.
6.09.03 Switch boards/boxes shall have conduit knock outs on the sides. Adequate
provision shall be made for ventilation of these boxes.
6.09.04 Flush type receptacles where provided shall be so located that only the plug
projects outside.
S-E1/SS-XI : 9
DCPL-K6A11
a) Street light poles shall be swaged and welded steel pole, complete
with fixing brackets, weather-proof junction box and all other
accessories.
6.11.01 The Contractor shall supply one (1) no. of wheel mounted adjustable
aluminium ladder for the maintenance of street lights.
6.11.02 For the maintenance of lighting fixtures within the power house, the contractor
shall also supply four (4) nos. free standing adjustable aluminium ladder,
adjustable from 5m. to 10m.
6.12.01 All outdoor illumination fixtures, unless it is fed from photo cell/time switch
controlled lighting panel, has to be provided with outdoor type local switches.
6.12.02 In all the air filtration units and air handling units, one marine type lamp (of 100
Watt approx.) shall be supplied and the wiring & fixing of the same has to be
done by the contractor.
S-E1/SS-XI : 10
DCPL-K6A11
6.13.01 Lighting Cable shall be heavy duty, 650/1100 Volt grade, multicore stranded
aluminium conductor, HR PVC or XLPE insulated, extruded PVC inner sheath,
single round G.I. wire armoured and overall PVC sheathed to IS 1554.
6.13.02 Lighting wires shall be 1100 Volt grade, PVC insulated, stranded conductor,
single core cable conforming to IS 694, colour coded as below :
6.14.01 Conduits shall be rigid steel, hot-dip galvanised, furnished in standard length
of 3 metres, threaded at both ends.
6.14.02 Thickness of conduits upto and including 25 mm dia shall be of 16 SWG and
conduits above 25 mm shall be of 14 SWG. Minimum size of conduits shall be
20 mm.
6.14.03 Each piece of conduit shall be straight, free from blister and other defects and
covered with capped bushings at both ends.
6.14.04 Flexible conduits shall be made with bright, cold rolled annealed and
electro-galvanised mild steel strips and coated with PVC.
6.15.01 Junction boxes shall be of 16 SWG sheet steel hot-dip galvanised, dust and
damp proof, generally conforming to IP-55.
6.15.02 Junction boxes shall be complete with gasketed inspection cover, conduit
knock out/threaded hub and terminal blocks.
6.15.03 Junction boxes for outdoor use shall be weatherproof IPW-55 and those for
hazardous location shall be flame-proof type.
6.16.00 Terminals
6.16.01 Multi way terminal blocks of approved type, complete with screws, nuts,
washers and marking strips shall be furnished for connection of
incoming/outgoing wires.
6.16.02 Each terminal shall be suitable for connection up to 2 nos. 10 Sq.mm stranded
aluminium conductors without any damage to the conductor or looseness of
connectors.
6.17.00 Nameplate
All lighting fixtures, receptacles, fans, junction boxes etc. shall be properly
marked up indelibly with corresponding circuit numbers.
6.18.00 Samples
Owner reserves the right to call for samples if considered necessary and the
same shall be submitted by the Bidder free and without any obligation.
7.01.01 The Contractor shall furnish all erection materials, hardware and consumables
required for the complete installation.
7.01.02 The materials shall include but shall not be limited to the following :
S-E1/SS-XI : 12
DCPL-K6A11
7.01.03 Supply of cement, sand, stone etc. required for the execution of the contract
shall be the responsibility of the Contractor.
7.02.01 The Contractor will provide such checking and testing equipment as test lamp,
buzzer, 500 volt meggar, earth meggar, lux-meter etc. and also other testing
equipment as required.
7.03.01 Installation work shall be carried out in accordance with good engineering
practices and also manufacturer's instructions/ recommendations where the
same are available.
7.04.02 Flood lights shall be mounted on steel base facing the tentative direction
shown on drawings. Fixing holes shall be provided with slot to turn the fixture
about 5 Deg on both sides. Bolts shall be finally tightened with spring washer.
The Contractor shall supply and install the steel base for fixing the flood light
on the flood light towers.
7.04.04 The fixtures after erection shall be marked up indelibly with corresponding
circuit number for easy identification of lamp circuit.
7.05.00 Receptacles
S-E1/SS-XI : 13
DCPL-K6A11
7.06.01 MLDB, EMLDB DCELDB and Lighting panels shall be erected at the locations
indicated in approved drawings.
Erection of Street Lighting poles together with all its accessories including civil
foundation work, installing lighting fixture, wiring and cabling work are included
within scope of contractor.
7.08.01 Erection of Flood Lighting Towers including civil foundation work shall be done
by Contractor.
7.08.02 Contractor shall also mount assembled fixtures, outdoor & lockable type
isolating switch cubicle, install necessary cabling and wiring and make
connections.
7.09.01 In case of unarmoured cable, all conduits shall originate from the respective
lighting panel and terminate in lighting fixtures, receptacles etc.
7.09.02 Exposed conduits shall be run in straight lines parallel to building columns,
beams and walls as far as practicable. Unnecessary bends and crossings
shall be avoided to present a neat appearance.
7.09.03 Conduit supports shall be provided at an interval of 750 mm for horizontal runs
and 1000 mm for vertical runs.
Wooden plug inserted in the masonry or concrete for conduit support is not
acceptable.
7.09.07 Where conduits are run on cable trays they shall be clamped to supporting
steel at an interval of 600 mm.
S-E1/SS-XI : 14
DCPL-K6A11
7.09.08 For directly embedding in soil, the conduits shall be coated with an asphalt -
base compound. Concrete pier or anchor shall be provided where necessary
to support the conduit rigidly and to hold it in place.
7.09.09 Conduits shall be installed in such a way as to ensure against trouble from
trapped condensation.
7.09.11 Conduits shall be kept, wherever possible, at least 300 mm away from hot
pipes, heating device etc. when it is evident that such proximity may impair the
service life of cables.
7.09.12 Slip joints shall be provided when conduits cross structural expansion joints or
where long run of exposed conduits are installed, so that temperature change
will cause no distortion due to expansion or contraction of conduit run.
7.09.13 For long run, junction/pull boxes shall be provided at suitable intervals to
facilitate wiring.
7.09.14 Conduits shall be securely fastened to junction box or cabinets, each with a
locknut and insulated bushing inside the box and locknut outside.
7.09.15 Conduit lengths shall be joined by screwed couplers. Couplers shall be clearly
cut.
S-E1/SS-XI : 15
DCPL-K6A11
7.09.16 Conduit joints and connections shall be made thoroughly water-tight and
rust-proof by application of a thread compound which will not insulate the
joints.
White lead is suitable for application on embedded conduit and red lead for
exposed conduit.
7.09.17 The Battery Room installation shall be made with acid fume proof conduits.
7.09.18 Field bends shall have a minimum radius of four (4) times the conduit
diameter. All bends shall be free of kinks, indentations or flattened surfaces.
Heat shall not be applied in making any conduit bend.
7.09.19 The entire metallic conduit system, whether embedded or exposed, shall be
electrically continuous and thoroughly grounded.
7.09.20 Lighting fixture shall not be suspended directly from junction box in the main
conduit run.
7.09.21 Conduits and fittings shall be properly protected during construction period
against mechanical injury. Conduits ends shall be plugged or capped to
prevent entry of foreign material.
7.09.22 After installation the conduits shall be thoroughly cleaned by compressed air
before pulling in the wire.
7.09.23 In control rooms and office areas provided with false ceiling conduct run shall
be concealed type, embedded in the walls.
7.10.00 Wiring
7.10.01 Wiring shall be generally carried out by PVC wires in conduits. All wires in a
conduit shall be drawn simultaneously. No subsequent drawing is
permissible.
7.10.02 Wire shall not be pulled through more than two equivalent 90º bends in a
single conduit run.
7.10.03 Wiring shall be spliced only at junction boxes with approved type connections
or terminal strips. Maximum two wires can be connected to each way of the
terminal block. Splicing of only one phase shall be done in a junction box.
7.10.04 For lighting fixtures, connection shall be teed off through suitable round
conduit or junction box, so that the connection can be attended without taking
down the fixture.
7.10.05 For vertical run of wires in conduit, wires shall be suitably supported by means
of wooden/hard rubber plugs at each pull/ junction box.
S-E1/SS-XI : 16
DCPL-K6A11
7.10.06 A.C. and D.C. circuits shall not be run in the same conduit and junction boxes.
Circuits fed from different transformers shall be run through different conduits
and Junction boxes.
7.10.07 Receptacle circuits shall be kept separate and distinct from lighting and fan
circuits.
7.10.08 Separate neutral wire shall be provided for each circuit. Wiring throughout the
installation shall be such that there is no break in the neutral wire in form of
switch or fuse.
7.11.00 Cabling
7.11.01 In outdoor areas, main runs from lighting panels shall be by means of AXWY
cables, directly buried in ground or laid in trenches for the underground portion
and through conduit for the over ground portion.
7.11.02 Buried cables shall be laid and covered with sand/ riddled earth, and protected
from damage by bricks at sides and pre cast concrete stab at top. Buried
cables shall have cable markers at 50M interval and projecting 150 mm above
ground. At cable bends and joints markers shall be provided.
7.11.03 When burried cables cross road / railway track, additional protection to be
provided in form of hume / G.I. pipe.
7.12.00 Grounding
7.12.01 All lighting panels, junction boxes, receptacles, fixtures, conduit etc. shall be
grounded in compliance with the provision of I.E. Rules.
7.12.02 Ground connections shall be made from nearest available station ground grid.
All connections to ground grid shall be done by arc welding.
7.12.04 All junction boxes, receptacles, lighting fixtures etc. shall be grounded with 16
SWG G.I. wire.
7.12.05 Each street lighting Pole shall be grounded at two points by two nos. 50x6 mm
G.I flat risers from two (2) nos. earthing spike 40 mm dia & 3m long directly
driven into ground at a depth of 1m from ground level. The junction box at
each lighting pole is grounded at two (2) points from two (2) nos earthing
terminals by 16 SWG GI wire. One 16 SWG G.I wire shall be taken up to the
junction box from lighting fixtures and connected to grounding point.
7.12.06 Two (2) nos earthing spike 3m long & 40 mm dia directly driven into ground at
a depth of 1m from ground level shall be provided for each flood lighting
tower.
S-E1/SS-XI : 17
DCPL-K6A11
The sheet steel cubicle housing the power supply Isolator at base of flood
lighting tower shall be connected at two (2) points from these earthing risers
by 16 SWG G.I. wire - The flood lighting fixtures shall be grounded by one (1)
16 SWG G.I wire running through the lighting conduit up to the distribution
box.
Two (2) nos separate spike of 3m long & 40 mm dia directly driven into ground
at a depth of one (1) m from ground level shall be provided for connection of
the lightning mast on top of flood lighting tower through two (2) nos 50x6 mm
G. I. flat down conductor.
7.12.07 A continuous ground conductor of 16 SWG G.I. wire shall be run all along
each conduit run and bonded to it every 600 mm by not less than two turns of
the same size of wire. This conductor shall be connected to each panel
ground bus.
All junction boxes, receptacles, fixtures etc. shall be connected to this 16 SWG
ground conductor.
7.13.01 Equipment foundations, panel foundations and all other civil work will be
provided by the Contractor.
7.14.01 The Contractor shall perform all excavation and backfilling as required for
buried cable and ground connections.
7.14.02 Excavation shall be performed up to the required depth. Such sheeting and
shorting shall be done as may be necessary for protection of the work.
7.14.03 The Contractor shall make use of his own arrangements for pumping out any
water that may be accumulated in the excavation.
7.14.04 All excavation shall be backfilled to the original level with good consolidation.
7.15.01 All supports, hangers & brackets shall be fabricated by the Contractor.
Necessary steel shall be supplied by the Contractor.
7.15.02 Steel for fabrication shall be straightened and cleaned of rust and grease. All
fabrication shall be free of sharp edge.
7.15.03 Every effort shall be made to minimize the wastage of steel as far as
practicable during fabrication. The wastage in no case shall exceed 3% of the
total quantity of steel fabricated.
7.16.00 Painting
S-E1/SS-XI : 18
DCPL-K6A11
7.16.01 Street light poles shall be given two coats of aluminium paints after
installation.
7.16.02 All steel fabrication shall be given two coats of redoxide primer followed by two
coats of battleship gray shade 632 of IS-5.
7.16.03 All equipment shall be given touch-up paint as required after installation.
7.17.01 On completion of erection works, the Contractor shall request the Engineer for
inspection and tests with minimum fourteen (14) days advance notice.
7.17.02 The Engineer shall arrange for joint inspection of the installation for
completeness and correctness of the work. Any defect pointed out during
such inspection shall be promptly rectified by the Contractor.
7.17.03 The installation shall be then tested and commissioned in presence of the
Engineer and put on trial run for stipulated contract period.
7.17.04 All rectification, repair or adjustment work found necessary during inspection,
testing, commissioning and trial run shall be carried out by the Contractor
without any extra cost.
8.00.00 TESTS
8.01.01 All equipment shall be completely assembled, wired, adjusted and routine
tested as per relevant Indian Standards at manufacturer's works.
c) Operational tests.
8.02.01 Contractor shall thoroughly test and meggar all cables, wires and equipment
to prove that the same are free from ground and short circuit.
8.02.02 If any ground or short circuit is found, the fault shall be rectified or the cable
and/or equipment replaced.
S-E1/SS-XI : 19
DCPL-K6A11
8.02.04 Illumination in different areas are as per designed lux level should be
established to the satisfaction of the Owner.
a) Certified copies of all tests carried out at works and at site shall be
furnished in requisite no. of copies for approval of the Owner.
9.01.00 Drawings, data and manuals shall be submitted in triplicate with the bid and in
quantities and procedures as specified in the General Condition of Contract
and/or elsewhere in this specification for approval and subsequent distribution
after the issue of Letter of Intent.
9.02.01 Make, type and catalogue number of lighting fixtures, lamps and accessories
along with technical leaflets, data sheets, polar curves etc.
9.02.02 Typical outline drawings, showing constructional features, cable/ conduit entry,
fixing arrangements etc of :
9.02.03 Technical leaflets and data sheet on each piece of equipment / device such as
MCB, switch fuse, receptacle etc.
9.02.04 Type test certificates on lighting fixtures and lighting panels, transformer,
ballast, power cables.
S-E1/SS-XI : 20
DCPL-K6A11
9.03.02 Data sheets for lighting fixture, lamps, accessories with light distribution
curves, co-efficient of utilization charts etc. Type and routine test certificates of
transformer and cables.
9.03.03 Control schematic and wiring diagram of 415V AC/220V DC lighting panel with
automatic changeover from AC to DC and vice-versa, 415V normal AC
street/area lighting panel with automatic ON/OFF feature.
9.03.04 Technical leaflets and data sheet on each piece of equipment/ device such as
MCB, switch, fuse, receptacle etc. Type and routine test certificates of
transformer and cables.
9.03.06 Key Single Line Diagram for lighting distribution, board wise single line
diagram with feeder loading, cable schedule and interconnection chart, design
calculation for lighting.
9.03.07 AS-BUILT lighting layout and erection drawings, properly incorporating the
changes/alterations/field modifications, if any, as carried out at field along with
circuit distribution schemes of all lighting panels, conduit and cable routing and
as acceptable to the Owner.
9.03.08 Any other relevant drawings, data and manuals necessary for satisfactory
installation, operation and maintenance.
9.03.09 The Bidder may note that the drawings, data and manuals listed are minimum
requirement only. The Bidder shall ensure that all other necessary write-ups,
curves and information required to fully describe the equipment offered are
submitted with his bid.
S-E1/SS-XI : 21
DCPL-K6A11
ANNEXURE-A
Fault Level 15 * KA
Frequency + 5%
Combined
Voltage + Frequency 10% (absolute sum)
* Indicative only; actual value will be decided by the Bidder after substantiating the
same by calculation.
S-E1/SS-XI/Annx-A : 22
DCPL-K6A11
ANNEXURE-B
Purpose of this list is to give general guidance on major areas to be illuminated. The list is
however not exhaustive. Illumination engineering shall be done by the Contractor based on
the detail layout developed for rooms/areas during detail engineering and considering the
guidance provided in Lighting Notes & Details Drawing No.: K6A11-DWG-E0800.
2. Electrical Switchgear Building, Control Room, Cable Spreader Room, Battery Room.
5. All roads including approach roads, general area, falling within illumination zone
identified to be covered under main pump house turnkey package.
S-E1/SS-XI/Annx-B : 23
DCPL-K6A11
ANNEXURE-C
Lighting fixture shall be furnished complete with associated lamp and integral control
gear fully wired-up. Control gear shall include ballast, starter, capacitor, electronic
ignitor, connector block etc. For fixture mounting details refer Drg No. K6A11-DWG-E-
0800.
1.3 CB 1 x 100W. GLS 240 V A.C./ 220 V D.C Well glass fixture :
Dust-tight & rainproof, die cast aluminium body, stove
enamel finish, canopy made of sheet aluminium, screw
neck, heat resistant well glass fitted with neoprene
gasket, galvanized wire guard suitable for "J" bracket
mounting.
S-E1/SS-XI/Annx-C : 24
DCPL-K6A11
ANNEXURE-C
2.1 MLDB & 415 V A.C. Indoor type Lighting distribution board with
EMLDB transformer (details in Annexure-E), 415 V, 200A, 3 ph, 4
S-E1/SS-XI/Annx-C : 25
DCPL-K6A11
ANNEXURE-C
2.3 LP-1 415 V A.C. Indoor type Lighting Panel with 415 V, 100A, 3
ph, 4 wire bus, one (1) no. 100A TP & N switch as incomer,
18 nos. 20A, 240 V, 1 pole MCBs as outgoing feeders.
2.4 LP-2 415 V A.C. Indoor Lighting panel with 415 V, 3ph, 4W bus
& one 63A TP & N Switch as incomer and 12 nos 20A ,
240V 1 pole MCBs as outgoing feeder.
2.5 LP-3 415 V A.C. Indoor type Lighting Panel with 415 V, 63 A, 3
ph, 4 wire bus, one (1) no. 32 A TP & N switch as incomer,
6 nos. 20A, 240V, 1 pole MCBs as outgoing feeders.
2.6 SLP 415 V A.C. Outdoor type Panel with 415 V, 100A, 3 ph, 4
wire bus, one 100A TP & N switch as incomer, 18 nos.
20A, 240V, 1 pole MCBs as outgoing feeders.
2.7 DCELP Indoor type emergency lighting panel with 240V bus, one
no 20A switch fuse as incomer and 6 nos 16A two pole
MCB with back up fuse as outgoing feeders.
2.8 FLP Outdoor, lookable type Isolating switch of 415V, 32A, 3 ph,
4 wire TP & N. with 2 mm sheet steel/cast iron cubicle.
3.0 RECEPTACLE
3.1 RA 5A, 240 V, 2 pole, 3 pin with third pin earthed, suitable for
flush mounting in office areas and control room. the switch
shall be also flush mounted piano type.
S-E1/SS-XI/Annx-C : 26
DCPL-K6A11
ANNEXURE-C
3.3 RC 63A, 415 V, 3 phase, 4 pin interlocked plug and switch with
earthing contact, wall/column mounted, metal clad
gasketed construction, weatherproof, suitable for
loop-in/loop-out connection of 4/C-35 Sq.mm AYWY cable.
These shall be fed from AC Distribution Board/Station
MCC.
3.4 RD 125 A, 415 V, 3 phase 5 pin interlocked plug & switch with
fifth pin earthed, wall/column mounted metal clad gasketed
construction, weatherproof, suitable for loop in and loop out
connection of 3-1/2C -95 Sq.mm AYWY cable. These shall
be fed from A.C-Distribution Board/Station MCC.
4.1 FA 1200 mm sweep ceiling fan with regulator, down rod and
canopy.
4.2 FB 1400 mm sweep ceiling fan with regulator, down rod and
canopy.
5.1 TA/TB Single arm/double arm swaged and welded steel pole with
junction box and all accessories.
6.0 SWITCHBOARD
6.2 S-2 Switch board with 3-5A switch and 1-5A receptacle.
6.3 S-3 Switch board with 6-5A switch and 1-5A receptacle.
S-E1/SS-XI/Annx-C : 27
DCPL-K6A11
ANNEXURE-C
7.3 M3 Portable Emergency light set complete with one 20W tube
light, battery, battery charger and all other accessories.
S-E1/SS-XI/Annx-C : 28
DCPL-K6A11
ANNEXURE-D
ILLUMINATION LEVEL
1. Control Rooms
(with false ceiling) H and B 300
2. Switchgear/MCC/Electrical
equipment Rooms DA/DB and A 250
* Medium bay fixtures shall be used where the room height is 8 M. Otherwise high bay
fixtures are to be used.
Lux level for A.C. Emergency lighting in control room shall be 50 and for other areas 20
lux.
S-E1/SS-XI/Annx-D : 29
DCPL-K6A11
ANNEXURE-E
Cooling : AN
The secondary neutral of the transformer shall be brought out for getting a grounded 4wire
supply. Each transformer shall be routine tested and one transformer shall be type tested in
accordance with relevant standard.
The transformer shall be liable for rejection if the tolerance on the quoted values of losses,
impedance, temperature rise, etc. exceeds the specified values of relevant standard.
The transformer shall be mounted inside sheet steel enclosure which shall be an integral part
of Lighting Distribution Board.
S-E1/SS-XI/Annx-E : 30
DCPL-K6A11
ANNEXURE-F
Each transformer shall be equipped with fittings and accessories as listed below :
1. 150 mm dia. winding temperature indicator with maximum reading pointer and
electrically separate sets of contacts for trip and alarm.
2. Handling and lifting lugs both for enclosure and core-coil assembly.
5. Door handle operated safety limit switch with 1NO + 1NC contact.
6. Ground bus.
Note
All indication, alarm, trip contacts provided shall be rated for 0.5A at 220 V D.C. and 5A at
240 V A.C.
S-E1/SS-XI/Annx-F : 31
DCPL-K6A11
ANNEXURE-G
The following list of mandatory spare parts for the Lighting System covered under this
specification.
S-E1/SS-XI/Annx-G : 32
DCPL-K6A11
ANNEXURE-G
S-E1/SS-XI/Annx-G : 33
DCPL-K6A11
ANNEXURE-G
S-E1/SS-XI/Annx-G : 34