6. Characteristic Curve
FB063-6EK.4I.V4P
1~ 230V 50Hz measurement density 1,16 kg/m³
Air performance
10153
Please note: It’s not allowed to use this fan in the stall area!*
*In doubt please ask your responsible ZIEHL-ABEGG sales contact.
Article number
101680
7. Drawing
Dimensions in mm
The illustrations shown make no claim to completeness and are for orientation purposes only.
Article number
101680
8. Connection diagram
Article number
101680
Measurement method
The characteristic map display shows the pressure increase ∆psF in Pa
as a function of the volume flow rate qV in m3/h.
Technical conditions of supply
The specified performance data meet the respective requirements
for accuracy
- AN2 for centrifugal impellers without motor
- AN3 for centrifugal fans with standard motors
- AN2 for centrifugal impellers with ECblue motors (except EC055)
- AN3 for centrifugal impellers with ECblue motor EC055 (see type key)
- AN3 for axial fans with ECblue motors
- AN4 for axial fans with AC external rotor motors
in line with ISO 13348 and apply to the rated data and air performance
curves at the rated voltage. The continuous line in the characteristic
curve represents the optimum reliable operating range for fans.
Installation type A according to ISO
5801
Fan test bench
The fan characteristic curves are determined on a combined ventilation
and sound test bench.
The characteristic curves are measured in compliance with DIN EN ISO
5801 and AMCA 210-99. The sound power levels are measured in
compliance with DIN EN ISO 3745 and ISO 13347-3 using the
enveloping surface measuring method.
The figure below shows an example of the measuring setup. The fan is
installed in the measuring chamber at free inlet and free exhaust
Technology Centre (InVent)
(installation type A as per DIN EN ISO 5801 or AMCA 210-99).
Air density
The air density and humidity are conditioned during the measurement
using heat exchangers and kept largely constant. The characteristic
curves shown refer to the measuring density. The mean measuring
density is 1.16 kg/m³.
① Test fan
② pfs
③ Flow straightener
④ Nozzles
⑤ ∆p Differential pressure
⑥ Auxiliary fan