Coke Built Up in EDC Cracker. VCM Process
Coke Built Up in EDC Cracker. VCM Process
CHLORIDE PLANTS
0
𝐶𝑙𝐶𝐻2 − 𝐶𝑙𝐶𝐻2 → 𝐶𝐻2 = 𝐶𝐻𝐶𝑙 + 𝐻𝐶𝑙 ∆𝐻298 71 𝐾𝑗/𝑚𝑜𝑙
EDC crackers receive purified EDC (99,96 % minimal for the actual process
license) from a storage tank or directly from the EDC purification unit. The
technologies differ in the way the EDC is preheated before being fed to the
furnace cracker. Geon/Ineos preheats the EDC by means of the direct
chlorination reactor outlet stream and the quench column overhead
gases; vapor EDC is fed to the convection zone of the cracker. Vinnolit(1)
preheats with steam generated in the oxychlorination unit and feeds the
EDC in the form of vapor through an EDC evaporator heat exchanger,
which exchanges heat with stream leaving from the radiation zone of the
cracking furnace; subsequently the EDC is fed to the convection section
and passes to the radiation zone, where, by the burners, the temperature
is raised to 500°C for thermal cracking, to produce vinyl monomer (VCM)
and hydrogen chloride (HCl).
Coke formation into the crackers tubes is a process condition that must be
reduced or avoided, because it will plug the coil, increasing the pressure
drop (in liquid feed systems, the discharge pressure becomes to increase
and the flow control valve opens above the normal value) and eventually a
shutdown of the furnace to clean the tubes. In general, a decoking
shutdown time for the cracking unit takes around 4 – 6 days with an
economic loss. The designers calculated the decoking time every 18
months as a standard adopted; some licensors reached that their furnaces
could run 2 and a half years without loading reduction of the cracker.
Fig 2 VCM Cracking Furnace vapor Feed
- EDC Quality
1. Conversion Rate
The conversion rate should be limited to 52% as a maximum, because
higher conversions imply accelerated carbon formation into the coil.
Furnace conversion is inversely related to selectivity; at a temperature of
500 °C, the selectivity of EDC to MVC conversion is in the order of 99%. As
the conversion increases, the selectivity decreases, and more
unsaturated, saturated, and coke impurities are generated. See fig. 2,
where it is shown that at a furnace temp of around 505 °C, the mass
fraction of impurities is around 0.9% (2).
·10−2
460
1.2
Temperature [°C]
420 1.1
Mass fraction [-]
1
380
0.9
340 0.8
300 0.7
Tf = 1170 K 0.6
260
Tf =1160 K 0.5
0 0.2 0.4 0.6 0.8 1 1.2 1.4 0 0.2 0.4 0.6 0.8 1 1.2 1.4
z [-] z [-]
Fig 2 Conversion (left) and selectivity (right) as a function of cracker, z, for flue gas
temperature (2).
The secondary reactions in the formation of unsaturated compounds are
as follows (4):
- Burner flame flow goes directly to the coil and not to the furnace walls.
The hot spots generate localized high conversions rates in that zone/place
that induce the production of chloroprene or unsaturated that promote the
coke formation in the coils. Studies indicate that chloroprene and any
unsaturated organics form a pyrolytic carbon, which accumulates in very
compact layers, unlike the carbon formed by proper pyrolysis of EDC,
which is soft and does not accumulate in the 90° bends.
Field operators should inspect the coil during night shifts, searching
for hot spots, poor flame distributions and improper heat flow
distributions by observing the burner flame.
A hot spot will eventually promoted and accelerated coke deposit into the
coils and will cause a significant drop in pressure which will be reflected
as an increase in the feed pressure to the cracker to maintain the same
loading of EDC. In any scenario a hot spot is an indication that a furnace
shutdown for decoking should be planned.
EDC Quality
The EDC fed to the cracker must have:
1. Iron impurity
Fe++ was the first compound identified in the 1960's as a promoter of coke
formation in EDC cracker coils, observed at values of 1 - 2 PPM over
periods of days causing short running times and shutdowns due to coke
accumulation in the Cracker; this is identified by a general increase in tube
skin temperatures.
The dry EDC feed quality has a normal value of 0.1 ppm of Fe++, higher
values is a sign of process abnormality and shutdown values to feed EDC
is 0.5 ppm.
Unsaturated compounds can also come from the direct chlorination unit,
when excesses of free chlorine or HC produce unsaturated components;
however, these events do not last over time because the operating
procedures establish a shutdown of this unit when uncontrolled events of
excess Cl2 or HCL are detected.
A particular case is the acetylene impurities in the feed EDC, the actual
furnace design and coils configuration have reduced the skin temperature
in the coils. If a plant has events of acetylene, furnace operation must be
check and control.