MSIG 2025 - Part4
MSIG 2025 - Part4
4. Oil and Grease (O&G): Organic matter, primarily edible oils and fatty
substances of animal or vegetable origin present in a sewage sample.
5. Suspended Solids (SS): Solid particles that are not dissolved and remain
suspended in a sewage sample. These particles can consist of both organic
and inorganic matter.
2-25
2-25
MSIG V1 Planning Principle and Tools
Sewage Characteristics & Flow Generation
6. Total Nitrogen (TN): The sum of all nitrogen forms present in a sewage
sample, including ammonia, ammonium ions, nitrate, nitrite and organic
nitrogen compounds.
Table 2-1 demonstrates the design influent values for raw sewage to be adopted
in designing treatment processes. Meanwhile, the ealuent discharge standards
are subject to the Environmental Quality (Sewage) Regulations under the
Environmental Quality Act 1974 or as prescribed by the Department of
Environment in the Environmental Impact Assessment report.
The influent quality values in Table 2-1 were established by analysing a series of
sampling and testing of raw sewage in several STPs, accounting for these factors:
The raw sewage influent quality to be used as design values is segmented into
bands based on the STP catchment profiles. A catchment profile with significant
sewage volume is characteristic of non-residential premises with commercial
activities, such as food and beverages sectors. This catchment tends to have
higher pollutant concentrations. Larger capacity STPs have greater dilution
capability than smaller capacity counterparts and, thus, can better cope with
mixed catchment profiles.
2-26
2-26
MSIG V1 Planning Principle and Tools
Sewage Characteristics & Flow Generation
Band 1: Applies to Class 1 or 2 STPs where more than 70% of the total
development PE are from residential premises.
Band 2: Applies to Class 1 and 2 STPs other than those specified in Band 1
(total development PE from residential premises are less than 70%)
Band 3: Applies to Class 3 STPs where more than 35% of the total
development PE are from residential premises.
Band 4: Applies to Class 3 STPs other than those specified in Band 3 (total
development PE from residential premises are less than 35%).
Band 5: Applies to Class 4 STPs.
2-27
2-27
MSIG V1 Planning Principle and Tools
Sewage Characteristics & Flow Generation
Step 1: Determine the ultimate design PE for the STP (not based on the STP
modules) to determine the class, as shown in Table 2-2.
PE Range Class
>20,000 Class 4
Step 2: Calculate the PE percentage from residential units over the ultimate
development PE that will be connected to the STP. The selection of the band is
based on the percentage established in Table 2-3.
2-28
2-28
MSIG V1 Planning Principle and Tools
Sewage Characteristics & Flow Generation
The daily volume of sewage generated per person is set at 210 litres/person/day.
The sewage generation rate will be used to determine the required capacity of
the sewerage infrastructure.
Peak flow refers to the maximum flow rate that may occur during a given day,
accounting for daily flow fluctuations as well as additional contributions from
infiltration, inflow, and other factors. This value is typically calculated by applying
a peak factor (a multiplier) to the average flow, providing an estimate of the
maximum expected flow rate. The peak factor shall be estimated using the
following formula:
!0 32.11
!"#$ &#'()* = ,. . ×
1222
The peak flow factor was derived from the influent flow measurements
conducted over 90 days.
2-29
2-29
Chapter 3
Population
Equivalent
Contribution
MSIG V1 Planning Principle and Tools
PE Contribution
Residential
4 PE per residential units
Industrial
Institutions
Workers Quarters/Dormitory/
Construction Site (Specifically 1 PE per bed
Planned/Designated)
3-32
3-33
MSIG V1 Planning Principle and Tools
MSIG V1 Planning Principle and Tools
PE Contribution
PE Contribution
Commercial
With facilities:
25 PE per water closet
Camp Site
Without facilities:
15 PE per water closet
3-34
3-33
Chapter 4
Siting and Buffer
Zone Requirements
MSIG V1 Planning Principle and Tools
MSIG V1 Planning Principle and Tools
PE Contribution
PE Contribution
Note:
1. The water closet (WC) for people with disabilities (OKU) shall not be accounted for in
the PE calculation.
2. If the premises or establishments have additional use besides their primary purpose
(a religious establishment with workers’ quarters and classes), these secondary
components must be considered in the PE calculation.
3. If the premises or establishments to be developed are not listed in Table 3-1, select
the closest description to the premises or establishments in the table and use the
value to calculate the PE contribution.
4. Facilities provided only for the residents’ use in residential premises or
establishments shall not be counted in the PE calculation.
5. The project owner or consultant is responsible for ensuring the accuracy of the PE
calculation or provision if the development needs exceed the PE stated in Table 3-1.
3-35
3-34