Fx5-4DA Hardware Manual

The document is a hardware manual for the MELSEC iQ-F FX5-4DA analog output module, detailing its specifications, installation, wiring precautions, and safety information. It emphasizes the importance of following safety protocols to prevent electric shock and equipment damage during installation and operation. The manual also includes guidelines for proper wiring and grounding to ensure reliable performance in industrial applications.

Uploaded by

bachcongminh9214
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
184 views1 page

Fx5-4DA Hardware Manual

The document is a hardware manual for the MELSEC iQ-F FX5-4DA analog output module, detailing its specifications, installation, wiring precautions, and safety information. It emphasizes the importance of following safety protocols to prevent electric shock and equipment damage during installation and operation. The manual also includes guidelines for proper wiring and grounding to ensure reliable performance in industrial applications.

Uploaded by

bachcongminh9214
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

IB(NA)-0800577-E Side

B
Side
A JAPANESE
Side
B ENGLISH
1. Outline 1.4 Terminal Layout 3. Wiring
FX5-4DA analog output module (hereinafter called FX5-4DA) can convert 4 points of
digital values into analog output values (voltage output and current output). WIRING PRECAUTIONS
1.1 Incorporated Items
V+ V+  Make sure to cut off all phases of the power supply externally before
MELSEC iQ-F FX5-4DA Check that the following product and items are included in the package:
CH1 I+ I+ CH3
attempting installation or wiring work.
Product FX5-4DA analog output module Failure to do so may cause electric shock or damage to the product.
 Make sure to properly wire to the spring clamp terminal block in accordance
Hardware Manual Included Items
Dust proof protection sheet (1 sheet)
Hardware manual [Japanese /English] (This manual)
COM COM with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit,
V+ V+ wire breakage, malfunctions, or damage to the product.
Hardware manual [Chinese]
Manual Number IB(NA)-0800577 - The disposal size of the cable end should follow the dimensions described
CH2 I+ I+ CH4 in the manual.
Revision E 1.2 External Dimensions, Part Names
- Twist the ends of stranded wires and make sure that there are no loose wires.
[6] Unit: mm
COM COM
Date October 2023 2-φ4.5 Mounting holes - Do not solder-plate the electric wire ends.
24V 24G - Do not connect more than the specified number of wires or electric wires
[3]
of unspecified size.

80 (Mounting hole pitch)


[2] [4] - Affix the electric wires so that neither the terminal block nor the connected
This manual describes the part names, dimensions, installation, and parts are directly stressed.
specifications of the product. Before use, read this manual and manuals of
relevant products fully to acquire proficiency in handling and operating the [7]
[5]

90
product. Make sure to learn all the product information, safety information, and WIRING PRECAUTIONS
precautions.
And, store this manual in a safe place so that you can take it out and read it
For further information on terminal, refer to the following manual.  Make sure to observe the following precautions in order to prevent any
whenever necessary. Always forward it to the end user. [1]
Registration: damage to the machinery or accidents due to malfunction of the PLC caused
MELSEC iQ-F FX5 Analog Module User's Manual
The company names, system names and product names mentioned in this by abnormal data written to the PLC due to the effects of noise:
manual are either registered trademarks or trademarks of their respective [8] - Do not bundle the power line and communication cables together with or
companies. In some cases, trademark symbols such as '' or '' are not specified 20 8 2. Installation lay them close to the main circuit, high-voltage line, load line or power line.
in this manual. 40 19.2 83 As a guideline, lay the power line, control line and communication cables
INSTALLATION at least 100 mm away from the main circuit, high-voltage line, load line or
Effective October 2023 PRECAUTIONS power line.
Specifications are subject to change without notice. [9] MASS (Weight): Approx. 0.2 kg
- Ground the shield of the analog input/output cable in accordance with the
Outer painting color: Munsell 0.6B7.6/0.2  Make sure to cut off all phases of the power supply externally before attempting
manuals of each model. However, do not use common grounding with
 2017 MITSUBISHI ELECTRIC CORPORATION installation or wiring work. heavy electrical systems.
Failure to do so may cause electric shock or damage to the product.
 Check the interface type and correctly connect the cable. Incorrect wiring
 Use the product within the generic environment specifications described in the (connecting the cable to an incorrect interface) may cause failure of the
Safety Precautions (Read these precautions before use.) User's Manual (Hardware) for the CPU module to be used. module and external device.
This manual classifies the safety precautions into two categories: Never use the product in areas with excessive dust, oily smoke, conductive dusts,  To terminal blocks, connect circuits isolated from hazardous voltage by
corrosive gas (salt air, Cl 2 , H 2 S, SO 2 or NO 2 ), flammable gas, vibration or double/reinforced insulation.
and . impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions, 3.1 Applicable Cable
Indicates that incorrect handling may cause hazardous deterioration or damage may occur.
3.1.1 Spring clamp terminal block
conditions, resulting in death or severe injury.
1) Suitable wiring
INSTALLATION
Indicates that incorrect handling may cause hazardous PRECAUTIONS Wire size
No. of
conditions, resulting in minor or moderate injury or [1] Terminal block [6] Name plate Temperature
wire per Single wire, Strand wire Ferrules with
property damage. (Spring clamp terminal block) [7] DIN rail mounting groove  Do not touch the conductive parts of the product directly. rating
terminal (Material: Copper wire) insulation sleeve
[2] Extension cable (DIN rail: DIN 46277, 35 mm wide) Doing so may cause device failures or malfunctions.
Depending on the circumstances, procedures indicated by may also [3] Direct mounting hole: 2 holes of 4.5 [8] DIN rail mounting hook  When drilling screw holes or wiring, make sure that cutting and wiring debris do AWG24 to 16 AWG23 to 19
One wire 80 or more
cause severe injury. (mounting screw: M4 screw) [9] Pullout tab not enter the ventilation slits of the PLC. (0.2 to 1.5 mm2) (0.25 to 0.75 mm2)
It is important to follow all precautions for personal safety. [4] Operation status display LEDs Failure to do so may cause fire, equipment failures or malfunctions.
[5] Extension connector (for next module)  The dust proof sheet should be affixed to the ventilation slits before installation 2) Wire end treatment
Associated Manual and wiring work to block foreign objects such as cutting and wiring debris. Strip the cable about 10 mm from the tip to connect a wire ferrule at the
1.3 Indications of LEDs However, when the installation work is completed, make sure to remove the sheet
stripped area. Failure to do so may result in electric shock or short circuit
Manual name Manual No. Description between adjacent terminals because the conductive part. If the wire strip
LED display LED color Status Indication to provide adequate ventilation. length is too short, it may result in an unstable connection to the spring clamp
MELSEC iQ-F FX5 Explains analog input module, Failure to do so may cause fire, equipment failures or malfunctions. terminal part.
Analog Module SH-081802ENG analog output module, multiple On Power on  Install the product on a flat surface. When using a wire ferrule with an insulating sleeve, choose a wire with
User's Manual input module. POWER Green If the mounting surface is rough, undue force will be applied to the PC board, proper cable sheath referring to the above outside dimensions, otherwise the
Off Power off or module failure thereby causing nonconformities. wire cannot be inserted easily.
Describes the details of hardware
MELSEC iQ-F FX5S/
of the CPU module, including On Normal operation  Install the product securely using a DIN rail or mounting screws. - Strand wire/single wire - Ferrule with insulation sleeve
FX5UJ/FX5U/FX5UC  Connect the extension cables securely to their designated connectors.
SH-082452ENG performance specifications, RUN Green Flashing Offset/gain setting mode Insulation sleeve Contact area
User's Manual Loose connections may cause malfunctions.
wiring, installation, and (Crimp area)
(Hardware)
maintenance. Off Error
For further information on mounting, refer to the following manual.
How to obtain manuals On Minor error MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware)
10 mm
For the necessary product manuals or documents, consult with your local 10 mm
Mitsubishi Electric representative. ERROR Red Flashing Moderate error or major error
2 to 2.8 mm
Applicable standards Off Normal operation 16 to 18 mm
FX5-4DA complies with the EU Directive (EMC Directive), UL standards (UL, cUL)
On Alarm issued
and UKCA marking. Further information can be found in the following manual. ALM Red
MELSEC iQ-F FX5 Analog Module User's Manual Off Normal operation
Regarding the standards that relate to the CPU module, please refer to either the
product catalog or consult with your local Mitsubishi Electric representative.
Attention
This product is designed for use in industrial applications.

Check the shape of the wire insertion opening with the following chart, and 3.3 Grounding 4.2 General Specifications
use the smaller wire ferrule than the described size. Also, insert the wire with Ground the PLC as stated below. The items other than the following are equivalent to those of the CPU module.
care so that the wire ferrule is in proper orientation. Failure to do so may
 Perform class D grounding. (Grounding resistance: 100  or less) For the general specification, refer to the following manual.
cause the bite of the terminal and the damage of the terminal block.
 Ground the PLC independently if possible. MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware)
Shape of the wire Sectional shape of a wire ferrule If the PLC cannot be grounded independently, perform the "Shared grounding"
insertion opening Items Specifications
shown below.
For details, refer to the following manual. Dielectric withstand
2.4 mm MELSEC iQ-F FX5S/FX5UJ/FX5U/FX5UC User's Manual (Hardware) 500 V AC for 1 minute
voltage Between all terminals and
PLC
Other
PLC
Other
PLC
Other Insulation 10 M or higher by 500 V DC ground terminal
1.5 mm When using a tool of the reference equipment equipment equipment
resistance insulation resistance tester
product, the sectional shape becomes
a trapezoid close to a rectangle.
4.3 Power Supply Specifications
Independent grounding Shared grounding Common grounding
Terminal block (Best condition) (Good condition) (Not allowed) Items Specifications
The following table shows wire ferrules and its associated tools compatible  Bring the grounding point close to the PLC as much as possible so that the ground
with the terminal block. The shape of the wire ferrule differs depending on the Power supply voltage 24 V DC +20%, -15%
cable can be shortened.
crimp tool to be used, use the reference product. If the product other than External Operation continues when the
referenced products is used, the wire ferrule cannot be removed. Sufficiently Allowable instantaneous
confirm that the wire ferrule can be removed before use.
4. Specification power
power failure time
instantaneous power failure is shorter than
supply 5 ms.
<Reference product>
DESIGN PRECAUTIONS Current consumption 150 mA
Manufacturer Model Wire size Crimp tool
 Make sure to set up the following safety circuits outside the PLC to ensure safe Internal Power supply voltage 5 V DC
AI 0.5-10 WH 0.5 mm2
system operation even during external power supply problems or PLC failure. power
AI 0.75-10 GY 0.75 mm2 supply Current consumption 100 mA
PHOENIX CONTACT Otherwise, malfunctions may cause serious accidents.
CRIMPFOX 6
GmbH & Co. KG A 1.0-10 1.0 mm2 - Most importantly, set up the following: an emergency stop circuit, a protection
4.4 Performance Specifications
circuit, an interlock circuit for opposite movements (such as normal vs. reverse
A 1.5-10 1.5 mm2 rotation), and an interlock circuit (to prevent damage to the equipment at the Items Specifications
upper and lower positioning limits).
3) Connecting a cable Number of analog output points 4 points (4 channels)
- Note that when the CPU module detects an error, such as a watchdog timer
 When ferrules with insulation sleeve are used error, during self-diagnosis, all outputs are turned off. Also, when an error that Conversion speed 80 s/CH
Insert a wire with the ferrule with insulation sleeve into the wire insertion cannot be detected by the CPU module occurs in an input/output control block,
opening and push the wire. output control may be disabled. Between output terminal and PLC: Photocoupler
 When stranded wires and solid wires are used External circuits and mechanisms should be designed to ensure safe Isolation method Between output terminal and channels: Non-
Push the open/close button of the terminal block with a flathead machinery operation in such a case. isolation
screwdriver. While pushing the open/close button, insert the wire into the
Number of occupied I/O points 8 points
insertion opening until the wire reaches the back, and then release the
open/close button. DESIGN PRECAUTIONS
4.5 Output specifications
Then, pull the wire lightly and check that it is clamped securely.
<Reference>  Simultaneously turn on and off the power supplies of the CPU module and Items Specifications
extension modules.
Model name of a flathead Digital input 16-bit signed binary (-32768 to +32767)
Manufacturer
screwdriver
STARTUP AND Analog output
-10 to +10 V DC (external load resistance value 1 k to 1 M)
PHOENIX CONTACT GmbH & Co. KG SZS 0.4×2.5 VDE MAINTENANCE voltage
PRECAUTIONS
Analog output
4) Disconnecting a cable 0 to 20 mA DC (external load resistance value 0 to 500 )
 Do not disassemble or modify the PLC. current
Push the open/close button of the wire to be disconnected with a flathead
screwdriver. Pull out the wire with the open/close button pushed. Doing so may cause fire, equipment failures, or malfunctions.
Analog output range Digital value Resolution
For repair, contact your local Mitsubishi Electric representative.
3.2 Example of Output Wiring  Do not drop the product or exert strong impact to it. 0 to 10 V 0 to 32000 312.5 V
Doing so may cause damage.
0 to 5 V 0 to 32000 156.3 V
FX5-4DA  Before handling the module, touch a conducting object such as a grounded metal
*1 CH
Shielded wire to discharge the static electricity from the human body. Failure to do so may cause 1 to 5 V 0 to 32000 125 V
V+
Voltage
the module to fail or malfunction. Output
I+ Voltage output -10 to +10 V -32000 to +32000 312.5 V
*2 COM ch ara cte ristics,
User range
DISPOSAL PRECAUTIONS resolution*1 -32000 to +32000 312.5 V
setting
*1
Shielded wire CH 0 to 20 mA 0 to 32000 625 nA
 Please contact a certified electronic waste disposal company for the
V+
Current output environmentally safe recycling and disposal of your device. 4 to 20 mA 0 to 32000 500 nA This manual confers no industrial property rights or any rights of any other kind,
I+ Current
*2 COM nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
TRANSPORTATION User range held responsible for any problems involving industrial property rights which may
-32000 to +32000 500 nA
PRECAUTIONS setting occur as a result of using the contents noted in this manual.
Ambient temperature 25±5: ±0.1 % (Voltage ±20 mV, Current
24V  The product is a precision instrument. During transportation, avoid impacts larger Warranty
24 V DC Accuracy ±20 A) Exclusion of loss in opportunity and secondary loss from warranty liability
24G External power supply than those specified in the general specifications by using dedicated packaging
(accuracy for the full Ambient temperature 0 to 55: ±0.2 % (Voltage ±40 mV,
boxes and shock-absorbing palettes. Regardless of the gratis warranty term, Mitsubishi shall not be liable for compensation to:
Grounding *3 scale of the analog Current ±40 A)
(Ground resistance: Failure to do so may cause failures in the product. After transportation, verify (1) Damages caused by any cause found not to be the responsibility of Mitsubishi.
output value) Ambient temperature -20 to 0: ±0.3 % (Voltage ±60 mV,
100 Ω or less) operation of the product and check for damage of the mounting part, etc. (2) Loss in opportunity, lost profits incurred to the user by Failures of Mitsubishi products.
Current ±60 A)
CH : represents the channel number. (3) Special damages and secondary damages whether foreseeable or not, compensation for
4.1 Applicable CPU module *1 For the output characteristic, refer to the following. accidents, and compensation for damages to products other than Mitsubishi products.
*1 Use 2-core shielded twisted pair cable for the analog output lines, and MELSEC iQ-F FX5 Analog Module User's Manual (4) Replacement by the user, maintenance of on-site equipment, start-up test run
separate the analog output lines from other power lines or inductive lines. Model name Applicability and other tasks.
*2 Ground the shielded wire at one point on the signal receiving side. FX5UJ CPU module From first production
*3 " " terminals are internally connected. Perform class D grounding by either FX5U CPU module Ver. 1.050 or later
For safe use
terminal.
• This product has been manufactured as a general-purpose part for general
FX5UC CPU module*1 Ver. 1.050 or later
industries, and has not been designed or manufactured to be incorporated in
*1 FX5-CNV-IFC or FX5-C1PS-5V is necessary to connect FX5-4DA to the FX5UC a device or system used in purposes related to human life.
CPU module. • Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
• This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.