Micrologix1100Mixer Unloader Flyashsilo
Micrologix1100Mixer Unloader Flyashsilo
1307_143e.RSS Revision E
November 10th, 2010
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Table Of Contents
Report Section P
Processor Info 3
I/O Config 4
Channel Config 5
Program File List 6
Data File List 7
Ladder Table of Contents 8
Program Files 9
Data Files 9
Custom Data Monitor 1
Cross Reference 1
Memory Usage 1
Address/Symbols 1
2
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Processor Information
Total Memory Used: 2298 Instruction Words Used - 361 Data Table Word
Program Files: 9
Data Files: 9
3
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
I/O Configuration
4
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Channel Configuration
5
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
[SYSTEM] 0 SYS 0 No 0
1 SYS 0 No 0
MAIN 2 LADDER 8 No 80
IO MAP 3 LADDER 35 No 593
NORMAL OP 4 LADDER 49 No 3558
ANALOGS 5 LADDER 24 No 1181
HMI 6 LADDER 54 No 2603
TIMER_SAVE 7 LADDER 30 No 3952
ALARMS 8 LADDER 26 No 1113
6
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
7
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
8
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
JSR
0001 Jump To Subroutine
SBR File Number U:3
JSR
0002 Jump To Subroutine
SBR File Number U:4
JSR
0003 Jump To Subroutine
SBR File Number U:5
JSR
0004 Jump To Subroutine
SBR File Number U:6
JSR
0005 Jump To Subroutine
SBR File Number U:7
JSR
0006 Jump To Subroutine
SBR File Number U:8
0007 END
9
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Open Conditioning
Water Zone 1 Conditioning Water
Valve(s) Zone 1 Solenoid(s)
SAV05 ZONE1_OPEN
B3:8 O:3
0006
5 1
1762-OW8
Open Conditioning
Water Zone 3 Conditioning Water
Valve(s) Zone 3 Solenoid(s)
SAV07 ZONE3_OPEN
B3:8 O:3
0008
9 3
1762-OW8
10
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Momentary push
button that will
increase signal to
water valve as long Increase water to
as pushed. PB6 or 6A the Unloader.
MORE_WATER INCREASE_WATER
I:0 B3:1
0016
4 4
Bul.1763
Momentary push
button that will
decrease signal to
water valve as long Decrease water to
as pushed. PB7 or7A the Unloader.
LESS_WATER DECREASE_WATER
I:0 B3:1
0017
5 5
Bul.1763
Momentary push
button that will
increase signal to
Ash Feed as long as Increase Ash to
pushed. PB8 or PB8A Unloader.
MORE_ASH INCREASE_ASH
I:0 B3:1
0018
6 6
Bul.1763
Momentary push
button that will
decrease signal to
Ash Feed as long as Decrease Ash to
pushed. PB9 or PB9A Unloader
LESS_ASH DECREASE_ASH
I:0 B3:1
0019
7 7
Bul.1763
11
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
N.O. PSL01
(air pressure
switch). Switch is
held closed by Instrument air
adequate pressure pressure is OK
AIR_PRESSURE_SWITCH AIR_OK
I:2 B3:1
0022
0 8
1762-IQ16
15
14
Alarm acknowledged.
Alarm Acknowledge Reset all alarms
PushButton ALARM_RESET
I:2 B3:1
0028
6 13
1762-IQ16
12
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
15
0034 END
13
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
0 4 1
The Unloader is
running normally to
condition product
RUNNING_NORMALLY
B3:2
0001
4
Unloader time
Conditioning Water Conditioning Water Conditioning Water Conditioning Water delay of Bin
Zone 1 Normal Start Zone 2 Normal Start Zone 3 Normal Start Zone 4 Normal Start Isolation Valve
Delay Delay Delay Delay opening
ZONE1_NORM_START/DN ZONE2_NORM_START/DN ZONE3_NORM_START/DN ZONE4_NORM_START/DN DELAY_BIV_OPENING/DN
T4:35 T4:36 T4:37 T4:38 T4:4
DN DN DN DN DN
DN
DN DN DN DN DN
DN
14
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
15
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Delay in stopping
Unloader Motor Timer to Close the
during Normal Fluidized Conveyor
Stop Air Valve after
NORMAL_MTR_STOP Normal Stop
T4:12 CLOSE_FLUID_CONV_NS
TON
DN Timer On Delay EN
Timer T4:39
Time Base 1.0 DN
Timer to Close the Preset 0<
Fluidized Conveyor Accum 0<
Air Valve after
Normal Stop
CLOSE_FLUID_CONV_NS/DN
T4:39
DN
16
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
Timer to Close the
Conditioning Water
Timer to Close the Zone 3 Solenoid(s)
Conditioning Water after Normal Stop
Zone 4 Solenoid CLOSE_ZONE3_NS_DELAY
after Normal Stop TON
CLOSE_ZONE4_NS_DELAY/DN Timer On Delay EN
T4:58 Timer T4:57
Time Base 1.0 DN
DN Preset 0<
Accum 0<
Delay in closing Bin Delay in stopping Timer to Close the Timer to Close the
Isolation Valve Unloader delay in Delay in closing Unloader Motor Fluidized Conveyor Conditioning Water
during Normal stopping Ash Feed Water Valve during during Normal Air Valve after Zone 1 Solenoid(s)
Stop during Normal Stop Normal Stop Stop Normal Stop after Normal Stop
NORMAL_BIV_CLOSE AF_STOP_ON_NORM/DN NORMAL_WATER_OFF NORMAL_MTR_STOP CLOSE_FLUID_CONV_NS/DN CLOSE_ZONE1_NS_DELAY/DN
T4:9 T4:10 T4:11 T4:12 T4:39 T4:55
0004
DN DN DN DN DN DN
DN DN DN 3
17
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Delay in stopping
Unloader Motor Unloader delay in
during Final Load Stopping Ash Feed
Stop during Final Load
FINAL_MTR_OFF stop
T4:16 AF_STOP_ON_FINAL
TON
DN Timer On Delay EN
Timer T4:14
Time Base 1.0 DN
Timer to Close the Preset 2<
Fluidized Conveyor Accum 0<
Air Valve after
Final Stop
CLOSE_FLUID_CONV_FS/DN
T4:63 Unloader delay in
closing Water Valve
DN during Final Load
Stop
WATER_OFF_0N_FINAL
Timer to Close the TON
Conditioning Water Timer On Delay EN
Zone 1 Solenoid(s) Timer T4:15
after Final Stop Time Base 1.0 DN
CLOSE_ZONE1_FS_DELAY/DN Preset 15<
T4:59 Accum 0<
DN
Unloader delay in
Timer to Close the stopping Unloader
Conditioning Water Motor during Final
Zone 2 Solenoid(s) Load Stop
after Final Stop MTR_STOP_ON_FINAL
CLOSE_ZONE2_FS_DELAY/DN TON
T4:60 Timer On Delay EN
Timer T4:16
DN Time Base 1.0 DN
Preset 90<
Accum 0<
Timer to Close the
Conditioning Water
Zone 3 Solenoid(s)
after Final Stop Timer to Close the
CLOSE_ZONE3_FS_DELAY/DN Fluidized Conveyor
T4:61 Air Valve after
Final Stop
DN CLOSE_FLUID_CONV_FS
TON
Timer On Delay EN
Timer to Close the Timer T4:63
Conditioning Water Time Base 1.0 DN
Zone 4 Solenoid(s) Preset 0<
after Final Stop Accum 0<
CLOSE_ZONE4_FS_DELAY/DN
T4:62
DN
18
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
19
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
The Unloader is
running normally to Initial Start on
condition product Next Load Timer
RUNNING_NORMALLY I_START_OFF_TIMER
B3:2 TON
0007 Timer On Delay EN
4 Timer T4:27
Time Base 1.0 DN
Preset 7200<
Accum 95<
Delay in closing
The Unloader is in a Water Valve during
Final Load Stop Final Load Stop
IN_FINAL_LOAD_STOP FINAL_WATER_OFF
B3:2 T4:15
3 DN
8 2
Ready to run or to
cycle Ash Feed with
any Normal or Final
Load stop push
button
OK_TO_START
B3:5
Initial Start
Enabled
ENABLE_I_START
B3:2
20
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
The Unloader is
running normally to
condition product
RUNNING_NORMALLY
B3:2
The Unloader is in
the process of a
Normal Stop
NORMAL_STOP
B3:2
The Unloader is in a
Final Load Stop
IN_FINAL_LOAD_STOP
B3:2
5 9
By setting the DELAY_MOTOR_START timer longer than the DELAY_WATER_OPEN the water will come on first and then the motor start. In some cases, where the Ash left in the Unloader dries out between loads, this
feature can be used to reduce dust during start up. The normal preset for the DELAY_MOTOR_START timer is zero. In all cases, the motor must be running before the Ash valves or Conditioning valves can open.
Ready to run or to
I/O Power has failed cycle Ash Feed with
or there is a major any Normal or Final The Unloader is
alarm on the mixer Load stop push Start the Unloader running normally to
motor. button Start Up Sequence condition product
IMMEDIATE_STOP OK_TO_START UNLOADING_START RUNNING_NORMALLY
B3:4 B3:5 B3:1 B3:2
0011
4 1 3 4
4 2 3
21
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader automatic
shut down timer
which will initiate
a Normal Stop
AUTO_SHUT_DOWN
TON
Timer On Delay EN
Timer T4:8
Time Base 1.0 DN
Preset 900<
Accum 0<
22
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 2 Normal Start
Delay
ZONE2_NORM_START
TON
Timer On Delay EN
Timer T4:36
Time Base 1.0 DN
Preset 2<
Accum 0<
Conditioning Water
Zone 3 Normal Start
Delay
ZONE3_NORM_START
TON
Timer On Delay EN
Timer T4:37
Time Base 1.0 DN
Preset 4<
Accum 0<
Conditioning Water
Zone 4 Normal Start
Delay
ZONE4_NORM_START
TON
Timer On Delay EN
Timer T4:38
Time Base 1.0 DN
Preset 6<
Accum 0<
23
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader Automatic
Shut Down Timer
Which will initiate
a Normal Stop
AUTO_STOP_I_START
TON
Timer On Delay EN
Timer T4:48
Time Base 1.0 DN
Preset 900<
Accum 0<
24
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 2 Initial Start
Delay
ZONE2_INIT_START
TON
Timer On Delay EN
Timer T4:52
Time Base 1.0 DN
Preset 0<
Accum 0<
Conditioning Water
Zone 3 Initial Start
Delay
ZONE3_INIT_START
TON
Timer On Delay EN
Timer T4:53
Time Base 1.0 DN
Preset 3<
Accum 0<
Conditioning Water
Zone 4 Initial Start
Delay
ZONE4_INIT_START
TON
Timer On Delay EN
Timer T4:54
Time Base 1.0 DN
Preset 4<
Accum 0<
2 DN
Delay in stopping
Unloader Motor
The Unloader is in a during Final Load
Final Load Stop Stop
IN_FINAL_LOAD_STOP FINAL_MTR_OFF
B3:2 T4:16
3 DN
25
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
TT 4
TT 4
Output O:0/1 is on
when none of the
The Unloader is e-stops is pushed
running normally to in. It normally
condition product starts fluidizing.
RUNNING_NORMALLY RUN_FLUIDIZER
B3:2 B3:0
0019
4 1
TT
TT
26
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
2 DN 7
3 DN 7
9 5 13
4 14
27
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
2 DN 13
Unloader delay in
Stopping Ash Feed
The Unloader is in a during Final Load Ash Feed Device
Final Load Stop stop set for "AUTO"
IN_FINAL_LOAD_STOP AF_STOP_ON_FINAL/DN AF_IN_AUTO
B3:2 T4:14 B3:5
3 DN 13
3 11
ASH_FEED_ON
B3:0
28
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
8 11 3
DN 0
29
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
13
10 DN 7
DN 6
30
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
2 DN 3
Delay in closing
The Unloader is in a Water Valve during Water Supply Valve
Final Load Stop Final Load Stop set for "AUTO"
IN_FINAL_LOAD_STOP FINAL_WATER_OFF WATER_IN_AUTO
B3:2 T4:15 B3:6
3 DN 3
8 5
15 7
31
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
2 DN
3 DN
Next 4 Rungs are for the new Conditioning Water Header Solenoids.
I/O Power has failed
or there is a major The Unloader is Conditioning Water Open Conditioning
alarm on the mixer running normally to Zone 1 Normal Start Water Supply Valve Water Zone 1
motor. condition product Delay set for "OFF" Valve(s)
IMMEDIATE_STOP Low Air Alarm RUNNING_NORMALLY ZONE1_NORM_START/DN WATER_IN_OFF SAV05
B3:4 B3:10 B3:2 T4:35 B3:5 B3:8
0030
4 2 4 DN 15 5
Conditioning Water
Zone 1 Initial Start
Delay
ZONE1_INIT_START/DN
T4:51
DN
2 DN
3 DN
8 5
32
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 2 Initial Start
Delay
ZONE2_INIT_START/DN
T4:52
DN
2 DN
3 DN
8 5
Conditioning Water
Zone 3 Initial Start
Delay
ZONE3_INIT_START/DN
T4:53
DN
2 DN
3 DN
8 5
33
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 4 Initial Start
Delay
ZONE4_INIT_START/DN
T4:54
DN
2 DN
3 DN
8 5
DN
Unloader delay in
stopping Ash Feed
during Normal Stop
AF_STOP_ON_NORM/TT
T4:10
TT
Unloader delay in
Stopping Ash Feed
during Final Load
stop
AF_STOP_ON_FINAL/TT
T4:14
TT
3 11
7 3
34
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
Unloader delay in
stopping Ash Feed
during Normal Stop
AF_STOP_ON_NORM/TT
T4:10
TT
Unloader delay in
Stopping Ash Feed
during Final Load
stop
AF_STOP_ON_FINAL/TT
T4:14
TT
3 11
3 2
35
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
5 DN
DN DN
Alarm acknowledged.
Reset all alarms
ALARM_RESET
B3:1
13
Run Rotary Vane Feeder in reverse to try and clear the jam.
Stop for Direction Run Reverse to clear
Change Jam
RVF_REV_DELAY/DN REVERSE_RUN
T4:20 TON
0041 Timer On Delay EN
DN Timer T4:21
Time Base 1.0 DN
Preset 5<
Accum 0<
Stop before running Rotary Vane Feeder forward after running in reverse.
Run Reverse to clear Stop for Direction
Jam Change
REVERSE_RUN/DN RVF_FWD_DELAY
T4:21 TON
0042 Timer On Delay EN
DN Timer T4:30
Time Base 1.0 DN
Preset 2<
Accum 0<
36
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN 5
0048 END
37
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader Motor
Current
MTR_AMPS_0_100 High Amps Delay
GEQ TON
Grtr Than or Eql (A>=B) Timer On Delay EN
Source A N7:0 Timer T4:64
24< Time Base 1.0 DN
Source B N7:30 Preset 1<
40< Accum 0<
Timer used to
generate a 2% change
in signal to Water
Increase water to Position Valve per
Water 0 - 100 % the Unloader. Second Water 0 - 100 %
Setpoint INCREASE_WATER WAT_2PER_SEC/TT Change One Percent Setpoint
NEQ B3:1 T4:19 B3:8 ADD
0005 Not Equal ONS Add
Source A N7:34 4 TT 2 Source A N7:34
77< 77<
Source B 100 Timer used to Source B 1
100< generate a 2% change 1<
in signal to Water Dest N7:34
More Water PB on the Position Valve per 77<
touch panel Second
TP_MORE_WATER WAT_2PER_SEC/TT
B3:7 T4:19
0 TT
38
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
1 TT
Timer used to
generate 5% change
in signal to Ash
Increase water to Feed Device per
the Unloader. second
INCREASE_WATER WATER_RAMP_DEL
B3:1 TON
0007 Timer On Delay EN
4 Timer T4:24
Time Base 1.0 DN
More Water PB on the Preset 3<
touch panel Accum 0<
TP_MORE_WATER
B3:7
Decrease water to
the Unloader.
DECREASE_WATER
B3:1
39
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
This rung converts the 0-100% signal to the water valve to 4-20, the value in mA for display on the touch panel
SCP
0012 Scale w/Parameters
Input O:1.1
6216<
Input Min. 6242
6242<
Input Max. 31208
31208<
Scaled Min. 4
4<
Scaled Max. 20
20<
Output N7:42
4<
Timer used to
1st step in generate a 2% change 1st step in
generating signal to in signal to Ash generating signal to
Ash Feed. Increase Ash to Feed Device per Ash Feed.
0-50 range Unloader. Second 0-50 range
AF_STEP_1 INCREASE_ASH 2_PERCENT_SEC/TT Change One Percent AF_STEP_1
NEQ B3:1 T4:23 B3:8 ADD
0014 Not Equal ONS Add
Source A N7:36 6 TT 11 Source A N7:36
73< 73<
Source B 100 Timer used to Source B 1
100< generate a 2% change 1<
in signal to Ash Dest N7:36
More Ash push button Feed Device per 73<
on the touch panel Second
INC_ASH 2_PERCENT_SEC/TT
B3:7 T4:23
4 TT
Timer used to
1st step in generate a 2% change 1st step in
generating signal to in signal to Ash generating signal to
Ash Feed. Decrease Ash to Feed Device per Ash Feed.
0-50 range Unloader Second 0-50 range
AF_STEP_1 DECREASE_ASH 2_PERCENT_SEC/TT Change One Percent AF_STEP_1
NEQ B3:1 T4:23 B3:8 SUB
0015 Not Equal ONS Subtract
Source A N7:36 7 TT 14 Source A N7:36
73< 73<
Source B 0 Timer used to Source B 1
0< generate a 2% change 1<
in signal to Ash Dest N7:36
Less Ash push button Feed Device per 73<
on the touch panel Second
DEC_ASH 2_PERCENT_SEC/TT
B3:7 T4:23
5 TT
40
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Decrease Ash to
Unloader
DECREASE_ASH
B3:1
41
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
42
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Convert signal to
the Ash Feed to
4-20(mA) for display
on the touch panel
SIGNAL_TO_ASH_FEED
SCP
0020 Scale w/Parameters
Input O:1.0
6216<
Input Min. 6216
6216<
Input Max. 31110
31110<
Scaled Min. 4
4<
Scaled Max. 20
20<
Output N7:43
4<
43
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
0023 END
44
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
If Full Load amps is 0 on first pass demand good data. If 0 is loaded into FLA for whatever reason, put into SHOP TEST mode.
Full Load Amps
current set point
from the HMI Values have been Values have been
FLA_I_SET_POINT confirmed confirmed
EQU EQU MOV
0001 Equal Equal Move
Source A N7:32 Source A N7:54 Source 0
50< 0< 0<
Source B 0 Source B 100 Dest N7:54
0< 100< 0<
If values were not confirmed load 0's into motor data on first pass.
Full Load Amps
current set point
Values have been from the HMI
First Pass confirmed FLA_I_SET_POINT
S:1 NEQ MOV
0002 Not Equal Move
15 Source A N7:54 Source 0
0< 0<
Source B 100 Dest N7:32
100< 50<
45
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Service Factor
0=1.00
1=1.15
2=1.25 Hi-Hi Amps
SERVICE_FACTOR_IND Calculated
EQU MOV
0007 Equal Move
Source A N7:65 Source N7:32
0< 50<
Source B 0 Dest N7:66
0< 50<
Service Factor
0=1.00
1=1.15
2=1.25 Hi-Hi Amps
SERVICE_FACTOR_IND Calculated
EQU MUL
0008 Equal Multiply
Source A N7:65 Source A N7:32
0< 50<
Source B 1 Source B 115
1< 115<
Dest N7:66
50<
Hi-Hi Amps
Calculated
DIV
Divide
Source A N7:66
50<
Source B 100
100<
Dest N7:66
50<
Service Factor
0=1.00
1=1.15
2=1.25 Hi-Hi Amps
SERVICE_FACTOR_IND Calculated
EQU MUL
0009 Equal Multiply
Source A N7:65 Source A N7:32
0< 50<
Source B 2 Source B 125
2< 125<
Dest N7:66
50<
Hi-Hi Amps
Calculated
DIV
Divide
Source A N7:66
50<
Source B 100
100<
Dest N7:66
50<
46
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN
4 11 12
Screen Number
Finalize Selected Written to HMI
FINALIZE_SCREEN Move Screen Once HMI_SCREEN_WRITE
B3:0 B3:3 MOV
0015 ONS Move
11 6 Source 15
15<
Dest N7:45
0<
Screen Number
Bypass selected Written to HMI
BYPASS_SCREEN Move Screen Once HMI_SCREEN_WRITE
B3:0 B3:3 MOV
0016 ONS Move
12 8 Source 16
16<
Dest N7:45
0<
47
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
48
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
For Percentage of
Full Load Amps
Calculation
MUL
Multiply
Source A N7:28
10<
Source B 100
100<
Dest N7:27
1000<
High Amps is
currently ##% of
Full Load Amps
DIV
Divide
Source A N7:26
4000<
Source B N7:66
50<
Dest N7:39
80<
Low Amps is
currently ##% of
Full Load Amps
DIV
Divide
Source A N7:27
1000<
Source B N7:66
50<
Dest N7:40
20<
Low Amps is
currently ##% of
Full Load Amps
MOV
Move
Source 0
0<
Dest N7:40
20<
49
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Screen Number
Bypass Confirmed Force Scren to Main Written to HMI
BYPASS_SELECTED Screen HMI_SCREEN_WRITE
B3:0 B3:3 MOV
0024 ONS Move
14 1 Source 1
1<
Yes Selected Dest N7:45
YES_SELECTED 0<
B3:0
15
Screen Number
HMI Screen Number Written to HMI
Read HMI_SCREEN_WRITE
EQU MOV
0025 Equal Move
Source A N7:48 Source 0
6< 0<
Source B N7:45 Dest N7:45
0< 0<
50
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
51
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
The next two rungs recalculate the current preset in minutes so it can be displayed accurately on the HMI.
Normal Stop Current
Preset for
Fluidizing On Timer
DIV
0031 Divide
Source A T4:49.PRE
3600<
Source B 60
60<
Dest N7:21
10<
52
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
7 3 5
13 9 11
53
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
10 15 15
3 15 1
54
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
5 15 7
Conditioning Water
on during the Store Conditioning Retentive Memory for
Washout has been Water On Selection Condition Water On
selected into Retentive During Washout
First Pass COND_ON_ENABLED Memory Selection
S:1 B3:6 B3:4 MOV
0044 ONS Move
15 5 9 Source 1
1<
Dest N7:29
1<
Conditioning Water
on during the Store Conditioning Retentive Memory for
Washout has been Water On Selection Condition Water On
selected into Retentive During Washout
First Pass COND_ON_ENABLED Memory Selection
S:1 B3:6 B3:7 MOV
0045 ONS Move
15 5 2 Source 0
0<
Dest N7:29
1<
55
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
0053 END
56
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
15
Restore System
Defaults
RESTORE_DEFAULTS
B3:3
Restore System
Save or Restore Defaults Indicate current
Timer Presets RESTORE_DEFAULTS Timer presets
T4:33 B3:3 MOV
0004 Move
DN 4 Source 3
3<
Dest N7:53
0<
57
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
58
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
12
59
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
60
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Go to the Set Up
Screen
SAVING_I_STARTS
B3:2
10
61
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader automatic
shut down timer
which will initiate
a Normal Stop
AUTO_SHUT_DOWN.PRE
MOV
Move
Source N7:5
900<
Dest T4:8.PRE
900<
Conditioning Water
Zone 1 Normal Start
Delay
ZONE1_NORM_START.PRE
MOV
Move
Source N7:61
0<
Dest T4:35.PRE
0<
Conditioning Water
Zone 2 Normal Start
Delay
ZONE2_NORM_START.PRE
MOV
Move
Source N7:62
2<
Dest T4:36.PRE
2<
62
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 3 Normal Start
Delay
ZONE3_NORM_START.PRE
MOV
Move
Source N7:63
4<
Dest T4:37.PRE
4<
Conditioning Water
Zone 4 Normal Start
Delay
ZONE4_NORM_START.PRE
MOV
Move
Source N7:64
6<
Dest T4:38.PRE
6<
63
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader Automatic
Shut Down Timer
Which will initiate
a Normal Stop
AUTO_STOP_I_START.PRE
MOV
Move
Source N7:18
900<
Dest T4:48.PRE
900<
Conditioning Water
Zone 1 Initial Start
Delay
ZONE1_INIT_START.PRE
MOV
Move
Source N7:57
0<
Dest T4:51.PRE
0<
Conditioning Water
Zone 2 Initial Start
Delay
ZONE2_INIT_START.PRE
MOV
Move
Source N7:58
0<
Dest T4:52.PRE
0<
64
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 3 Initial Start
Delay
ZONE3_INIT_START.PRE
MOV
Move
Source N7:59
3<
Dest T4:53.PRE
3<
Conditioning Water
Zone 4 Initial Start
Delay
ZONE4_INIT_START.PRE
MOV
Move
Source N7:60
4<
Dest T4:54.PRE
4<
Conditioning Water Conditioning Water Conditioning Water Conditioning Water Normal Start Values
Zone 1 Normal Start Zone 2 Normal Start Zone 3 Normal Start Zone 4 Normal Start of presets are the
Delay Delay Delay Delay same as memory
ZONE1_NORM_START.PRE ZONE2_NORM_START.PRE ZONE3_NORM_START.PRE ZONE4_NORM_START.PRE MEM_START_SAME
EQU EQU EQU EQU B3:2
Equal Equal Equal Equal
Source A T4:35.PRE Source A T4:36.PRE Source A T4:37.PRE Source A T4:38.PRE 14
0< 2< 4< 6<
Source B N7:61 Source B N7:62 Source B N7:63 Source B N7:64
0< 2< 4< 6<
Unloader time delay Unloader Time Delay Unloader time delay Unloader Automatic
of Bin Isolation of Ash Feed Start of Water Valve Unloader time delay Shut Down Timer
Valve Opening on Opening on Initial Opening on Initical of Unloader Motor Which will initiate
Initial Start Start Start Initial Starting a Normal Stop
DELAY_BIV_I_START.PRE DELAY_ASH_I_START.PRE DELAY_WATER_I_START.PRE DELAY_MOTOR_I_START.PRE AUTO_STOP_I_START.PRE
EQU EQU EQU EQU EQU
0010 Equal Equal Equal Equal Equal
Source A T4:46.PRE Source A T4:47.PRE Source A T4:45.PRE Source A T4:44.PRE Source A T4:48.PRE
5< 0< 0< 0< 900<
Source B N7:14 Source B N7:15 Source B N7:16 Source B N7:17 Source B N7:18
5< 0< 0< 0< 900<
Conditioning Water Conditioning Water Conditioning Water Conditioning Water Initial Start Values
Zone 1 Initial Start Zone 2 Initial Start Zone 3 Initial Start Zone 4 Initial Start of presets are the
Delay Delay Delay Delay same as memory
ZONE1_INIT_START.PRE ZONE2_INIT_START.PRE ZONE3_INIT_START.PRE ZONE4_INIT_START.PRE MEM_ISTART_SAME
EQU EQU EQU EQU B3:2
Equal Equal Equal Equal
Source A T4:51.PRE Source A T4:52.PRE Source A T4:53.PRE Source A T4:54.PRE 15
0< 0< 3< 4<
Source B N7:57 Source B N7:58 Source B N7:59 Source B N7:60
0< 0< 3< 4<
65
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
66
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Saving current
Normal Stop time
delay presets
SAVE_NS_PRESETS
B3:3
10
67
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader delay in
closing Water Valve
during Normal Stop
WATER_OFF_ON_NORM.PRE
MOV
Move
Source N7:8
3<
Dest T4:11.PRE
3<
Unloader delay is
stopping Unloader
Motor during Normal
Stop
MTR_STOP_ON_NORM.PRE
MOV
Move
Source N7:9
25<
Dest T4:12.PRE
25<
68
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Timer to Close the Timer to Close the Timer to Close the Timer to Close the Timer to Close the
Fluidized Conveyor Conditioning Water Conditioning Water Conditioning Water Conditioning Water
Air Valve after Zone 1 Solenoid(s) Zone 2 Solenoid Zone 3 Solenoid(s) Zone 4 Solenoid
Normal Stop after Normal Stop after Normal Stop after Normal Stop after Normal Stop
CLOSE_FLUID_CONV_NS.PRE CLOSE_ZONE1_NS_DELAY.PRE CLOSE_ZONE2_NS_DELAY.PRE CLOSE_ZONE3_NS_DELAY.PRE CLOSE_ZONE4_NS_DELAY.PRE
EQU EQU EQU EQU EQU
Equal Equal Equal Equal Equal
Source A T4:39.PRE Source A T4:55.PRE Source A T4:56.PRE Source A T4:57.PRE Source A T4:58.PRE
0< 0< 0< 0< 0<
Source B N7:75 Source B N7:67 Source B N7:68 Source B N7:69 Source B N7:70
0< 0< 0< 0< 0<
11
69
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
70
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
13
71
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader delay in
closing Water Valve
during Final Load
Stop
WATER_OFF_0N_FINAL.PRE
MOV
Move
Source N7:12
15<
Dest T4:15.PRE
15<
Unloader delay in
stopping Unloader
Motor during Final
Load Stop
MTR_STOP_ON_FINAL.PRE
MOV
Move
Source N7:13
90<
Dest T4:16.PRE
90<
72
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader delay in
closing Bin Unloader delay in Unloader delay in Unloader delay in
Isolation Valve stopping Ash Feed closing Water Valve stopping Unloader
during Final Load during Final Load during Final Load Motor during Final Final Stop Current
Stop Stop Stop Load Stop Preset for
BIV_CLOSE_ON_FINAL.PRE AFV_CLOSE_ON_FL WATER_OFF_0N_FINAL.PRE MTR_STOP_ON_FINAL.PRE Fluidizing On Timer
EQU EQU EQU EQU EQU
0016 Equal Equal Equal Equal Equal
Source A T4:13.PRE Source A T4:14.PRE Source A T4:15.PRE Source A T4:16.PRE Source A N7:22
0< 2< 15< 90< 30<
Source B N7:10 Source B N7:11 Source B N7:12 Source B N7:13 Source B N7:25
0< 2< 15< 90< 30<
Timer to Close the Timer to Close the Timer to Close the Timer to Close the Timer to Close the
Fluidized Conveyor Conditioning Water Conditioning Water Conditioning Water Conditioning Water
Air Valve after Zone 1 Solenoid(s) Zone 2 Solenoid(s) Zone 3 Solenoid(s) Zone 4 Solenoid(s)
Final Stop after Final Stop after Final Stop after Final Stop after Final Stop
CLOSE_FLUID_CONV_FS.PRE CLOSE_ZONE1_FS_DELAY.PRE CLOSE_ZONE2_FS_DELAY.PRE CLOSE_ZONE3_FS_DELAY.PRE CLOSE_ZONE4_FS_DELAY.PRE
EQU EQU EQU EQU EQU
Equal Equal Equal Equal Equal
Source A T4:63.PRE Source A T4:59.PRE Source A T4:60.PRE Source A T4:61.PRE Source A T4:62.PRE
0< 0< 0< 0< 0<
Source B N7:76 Source B N7:71 Source B N7:72 Source B N7:73 Source B N7:74
0< 0< 0< 0< 0<
14
73
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
15
Full Load Amps Saved High Amps Saved Low Amps Saved Motor Data is the
Setting Setting Setting same as memory
MEM_I_FLA MEM_I_HIAMP MEM_I_LOAMP MEM_I_SAME
EQU EQU EQU B3:8
0019 Equal Equal Equal
Source A N7:33 Source A N7:55 Source A N7:56 1
50< 46< 12<
Source B N7:32 Source B N7:30 Source B N7:28
50< 40< 10<
74
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
75
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
9 5
Unloader automatic
shut down timer
which will initiate
a Normal Stop
AUTO_SHUT_DOWN.PRE
MOV
Move
Source 900
900<
Dest T4:8.PRE
900<
Conditioning Water
Zone 1 Normal Start
Delay
ZONE1_NORM_START.PRE
MOV
Move
Source 0
0<
Dest T4:35.PRE
0<
76
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 2 Normal Start
Delay
ZONE2_NORM_START.PRE
MOV
Move
Source 2
2<
Dest T4:36.PRE
2<
Conditioning Water
Zone 3 Normal Start
Delay
ZONE3_NORM_START.PRE
MOV
Move
Source 4
4<
Dest T4:37.PRE
4<
Conditioning Water
Zone 4 Normal Start
Delay
ZONE4_NORM_START.PRE
MOV
Move
Source 6
6<
Dest T4:38.PRE
6<
77
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
6 5
Unloader Automatic
Shut Down Timer
Which will initiate
a Normal Stop
AUTO_STOP_I_START.PRE
MOV
Move
Source 900
900<
Dest T4:48.PRE
900<
Conditioning Water
Zone 1 Initial Start
Delay
ZONE1_INIT_START.PRE
MOV
Move
Source 0
0<
Dest T4:51.PRE
0<
78
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Conditioning Water
Zone 2 Initial Start
Delay
ZONE2_INIT_START.PRE
MOV
Move
Source 0
0<
Dest T4:52.PRE
0<
Conditioning Water
Zone 3 Initial Start
Delay
ZONE3_INIT_START.PRE
MOV
Move
Source 3
3<
Dest T4:53.PRE
3<
Conditioning Water
Zone 4 Initial Start
Delay
ZONE4_INIT_START.PRE
MOV
Move
Source 4
4<
Dest T4:54.PRE
4<
Unloader time delay Unloader Time Delay Unloader time delay Unloader Automatic
of Bin Isolation of Ash Feed Start of Water Valve Unloader time delay Shut Down Timer
Valve Opening on Opening on Initial Opening on Initical of Unloader Motor Which will initiate
Initial Start Start Start Initial Starting a Normal Stop
DELAY_BIV_I_START.PRE DELAY_ASH_I_START.PRE DELAY_WATER_I_START.PRE DELAY_MOTOR_I_START.PRE AUTO_STOP_I_START.PRE
EQU EQU EQU EQU EQU
0024 Equal Equal Equal Equal Equal
Source A T4:46.PRE Source A T4:47.PRE Source A T4:45.PRE Source A T4:44.PRE Source A T4:48.PRE
5< 0< 0< 0< 900<
Source B 5 Source B 0 Source B 0 Source B 0 Source B 900
5< 0< 0< 0< 900<
79
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Restore System
Defaults Save or Restore
RESTORE_DEFAULTS Timer Presets Unloader delay in
B3:3 T4:33 stopping Ash Feed
during Normal Stop
4 DN AF_STOP_ON_NORM.PRE
MOV
Move
Source 5
5<
Dest T4:10.PRE
5<
Unloader delay in
closing Water Valve
during Normal Stop
WATER_OFF_ON_NORM.PRE
MOV
Move
Source 3
3<
Dest T4:11.PRE
3<
Unloader delay is
stopping Unloader
Motor during Normal
Stop
MTR_STOP_ON_NORM.PRE
MOV
Move
Source 25
25<
Dest T4:12.PRE
25<
80
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Timer to Close the Timer to Close the Timer to Close the Timer to Close the Timer to Close the
Conditioning Water Conditioning Water Conditioning Water Conditioning Water Fluidized Conveyor
Zone 1 Solenoid(s) Zone 2 Solenoid Zone 3 Solenoid(s) Zone 4 Solenoid Air Valve after
after Normal Stop after Normal Stop after Normal Stop after Normal Stop Normal Stop
CLOSE_ZONE1_NS_DELAY.PRE CLOSE_ZONE2_NS_DELAY.PRE CLOSE_ZONE3_NS_DELAY.PRE CLOSE_ZONE4_NS_DELAY.PRE CLOSE_FLUID_CONV_NS.PRE
EQU EQU EQU EQU EQU
Equal Equal Equal Equal Equal
Source A T4:55.PRE Source A T4:56.PRE Source A T4:57.PRE Source A T4:58.PRE Source A T4:39.PRE
0< 0< 0< 0< 0<
Source B 0 Source B 0 Source B 0 Source B 0 Source B 0
0< 0< 0< 0< 0<
81
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader delay in
closing Water Valve
during Final Load
Stop
WATER_OFF_0N_FINAL.PRE
MOV
Move
Source 15
15<
Dest T4:15.PRE
15<
Unloader delay in
stopping Unloader
Motor during Final
Load Stop
MTR_STOP_ON_FINAL.PRE
MOV
Move
Source 90
90<
Dest T4:16.PRE
90<
82
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Unloader delay in
closing Bin Unloader delay in Unloader delay in Unloader delay in
Isolation Valve stopping Ash Feed closing Water Valve stopping Unloader
during Final Load during Final Load during Final Load Motor during Final Run Fluidizer for
Stop Stop Stop Load Stop preset Amount of
BIV_CLOSE_ON_FINAL.PRE AFV_CLOSE_ON_FL WATER_OFF_0N_FINAL.PRE MTR_STOP_ON_FINAL.PRE Time on Final Stop
EQU EQU EQU EQU EQU
0028 Equal Equal Equal Equal Equal
Source A T4:13.PRE Source A T4:14.PRE Source A T4:15.PRE Source A T4:16.PRE Source A T4:50.PRE
0< 2< 15< 90< 1800<
Source B 0 Source B 2 Source B 15 Source B 90 Source B 1800
0< 2< 15< 90< 1800<
Timer to Close the Timer to Close the Timer to Close the Timer to Close the Timer to Close the
Conditioning Water Conditioning Water Conditioning Water Conditioning Water Fluidized Conveyor
Zone 1 Solenoid(s) Zone 2 Solenoid(s) Zone 3 Solenoid(s) Zone 4 Solenoid(s) Air Valve after
after Final Stop after Final Stop after Final Stop after Final Stop Final Stop
CLOSE_ZONE1_FS_DELAY.PRE CLOSE_ZONE2_FS_DELAY.PRE CLOSE_ZONE3_FS_DELAY.PRE CLOSE_ZONE4_FS_DELAY.PRE CLOSE_FLUID_CONV_FS.PRE
EQU EQU EQU EQU EQU
Equal Equal Equal Equal Equal
Source A T4:59.PRE Source A T4:60.PRE Source A T4:61.PRE Source A T4:62.PRE Source A T4:63.PRE
0< 0< 0< 0< 0<
Source B 0 Source B 0 Source B 0 Source B 0 Source B 0
0< 0< 0< 0< 0<
11
0029 END
83
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
10 8
DN
14
84
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Test Bit
NOOP
B3:0
Rungs 2 & 3 have been modified per EWR 801104, regardless of whether the input has been true since power up an XIO test bit is forcing the program to recognize that the switch exists.
PSL02 (Water
Pressure Switch)
Water pressure is OK found by logic
WATER_OK PSL02_FOUND
B3:1 B3:2
0003
9 13
PSL02 (Water
Pressure Switch)
found by logic
PSL02_FOUND
B3:2
13
Test Bit
NOOP
B3:0
85
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN 13
DN 13
86
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
4 10
1 0 4 1
4 1
DN 13
DN 13
DN 13
87
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
DN 13
88
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Alarm acknowledged.
Reset all alarms
No I/O Power Alarm ALARM_RESET
B3:10 B3:1
0 13
Unloader motor
starter failed to
pull in Aux contacts
on start signal
MOTOR_FAILED Motor Failed Alarm
T4:3 B3:10
0017
DN 4
Alarm acknowledged.
Reset all alarms
RVF Jammed Alarm ALARM_RESET
B3:10 B3:1
7 13
Rung 21 has been modified per ECN 801696. Now looks for whether the VFD has been commanded to run rather than if a Fault has occurred.
Rotary Vane Feeder
Rotary Vane Feeder I/O power is on, all Command to Run The VFD Running Without
has been selected E-Stops are out. VFD in Forward Fault RVF VFD Fault Alarm
RVF_SELECTED IO_POWER_IS_ON VFD_RUN_FORWARD VFD_NO_FAULT Delay
B3:6 B3:1 B3:0 B3:4 TON
0021 Timer On Delay EN
10 14 3 10 Timer T4:65
Time Base 0.01 DN
Command to Run The Preset 200<
VFD in Reverse Accum 0<
VFD_RUN_REVERSE
B3:0
RVF VFD Fault Alarm
2 Delay RVF VFD Fault Alarm
T4:65 B3:10
Alarm acknowledged.
RVF VFD Fault Alarm Reset all alarms DN 8
Delay ALARM_RESET
T4:65 B3:1
DN 13
89
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Remote Panel
Temperature High Remote Panel
TS4 Overtemp Alarm
B3:4 B3:10
0023
13 10
0025 END
90
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
91
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
92
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Main
Proc
Scan Times
Math
Chan 0
Debug
Errors
Protection
93
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Mem Module
Forces
94
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
B3:0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
B3:1 0 1 0 0 1 1 1 1 0 0 0 0 0 0 0 0
B3:2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
B3:3 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
B3:4 1 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 Go Back To the Home Screen
B3:5 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0
B3:6 0 0 0 0 0 0 0 0 0 0 1 0 1 0 0 0
B3:7 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0
B3:8 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0
B3:9 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0
B3:10 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0
95
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
T4:0 0 0 0 1.0 sec 3 0 (LOAIR) Time delay in low air pressure alarm logic
T4:1 0 0 0 1.0 sec 3 0 (LOH2O) Time delay in low water pressure alarm
T4:2 0 0 0 1.0 sec 5 0 (BIV__FAILED) Bin Isolation Valve failed logic
T4:3 0 0 0 1.0 sec 3 0 (MOTOR__FAILED) Unloader motor failed to start. (Aux cont
T4:4 0 0 0 1.0 sec 5 0 (DELAY_BIV_OPENING) Unloader time delay of Bin Isolation
T4:5 0 0 0 1.0 sec 0 0 (DELAY_ASH_FEED_START) Unloader time delay of Ash Feed St
T4:6 0 0 0 1.0 sec 7 0 (DELAY_WATER_OPEN) Unloader time delay of Water Valve ope
T4:7 0 0 0 1.0 sec 0 0 (DELAY_MOTOR_START) Unloader time delay of Unloader Motor
T4:8 0 0 0 1.0 sec 900 0 (AUTO_SHUT_DOWN) Unloader automatic shut down timer which
T4:9 0 0 0 1.0 sec 0 0 (BIV_CLOSE_ON_NORM) Unloader delay in closing Bin Isolati
T4:10 0 0 0 1.0 sec 5 0 (AF_STOP_ON_NORM) Unloader delay in stopping Ash Feed dur
T4:11 0 0 0 1.0 sec 3 0 (WATER_OFF_ON_NORM) Unloader delay in closing Water Valve
T4:12 0 0 0 1.0 sec 25 0 (MTR_STOP_ON_NORM) Unloader delay is stopping Unloader Mo
T4:13 0 0 0 1.0 sec 0 0 (BIV_CLOSE_ON_FINAL) Unloader delay in closing Bin Isolat
T4:14 0 0 0 1.0 sec 2 0 (AF_STOP_ON_FINAL) Unloader delay in Stopping Ash Feed du
T4:15 0 0 0 1.0 sec 15 0 (WATER_OFF_0N_FINAL) Unloader delay in closing Water Valv
T4:16 0 0 0 1.0 sec 90 0 (MTR_STOP_ON_FINAL) Unloader delay in stopping Unloader M
T4:17 0 0 0 1.0 sec 3 0 (INRUSH_DELAY_TIMER) Timer to prevent motor inrush curren
T4:18 0 0 0 1.0 sec 3 0 (HI_HI_MTR_AMPS_TD) Time delay to prevent spikes from tri
T4:19 0 0 0 .01 sec 50 0 (WAT_2PER_SEC) Timer used to generate a 2% change in sign
T4:20 0 0 0 1.0 sec 2 0 (RVF_REV_DELAY) Stop for Direction Change
T4:21 0 0 0 1.0 sec 5 0 (REVERSE_RUN) Run Reverse to clear Jam
T4:22 0 0 0 1.0 sec 3 0 (ASH_RAMP_SLO) Timer used to determine ramping rate of ou
T4:23 0 0 0 .01 sec 50 0 (2_PERCENT_SEC) Timer used to generate a 2% change in sig
T4:24 0 0 0 1.0 sec 3 0 (WATER_RAMP_DEL) Timer used to generate 5% change in sign
T4:25 0 0 0 1.0 sec 5 0 (LOHIAMPS_ENABLED) Water off because of low or high amps
T4:26 0 0 0 1.0 sec 5 0 (LOHIAMPS_DISABLED) Water off because of low or high amps
T4:27 1 1 0 1.0 sec 7200 95 (I_START_OFF_TIMER) Initial Start on Next Load Timer
T4:28 0 0 0 1.0 sec 3600 1380 (RUN_1_HR_FOR_DONE) Times out when the Unloader has 1 Hou
T4:29 0 0 0 1.0 sec 4 0 (AFV_CLOSED_LS) Ash Feed Valve Closed Limit Switch time d
T4:30 0 0 0 1.0 sec 2 0 (RVF_FWD_DELAY) Stop for Direction Change
T4:31 0 0 0 1.0 sec 5 0 (FOWARD_RUN) Run Foward to check if Jam is Cleared
T4:32 0 0 0 .01 sec 100 0 (OVERTORQUE_DELAY) Wait for current overtorque check
T4:33 0 0 0 .01 sec 200 0 Save or Restore Timer Presets
T4:34 0 0 0 .01 sec 200 0 (T4_34) Rewrite Screen Until a Selection has been Made
T4:35 0 0 0 1.0 sec 0 0 (ZONE1_NORM_START) Conditioning Water Zone 1 Normal Start
T4:36 0 0 0 1.0 sec 2 0 (ZONE2_NORM_START) Conditioning Water Zone 2 Normal Start
T4:37 0 0 0 1.0 sec 4 0 (ZONE3_NORM_START) Conditioning Water Zone 3 Normal Start
T4:38 0 0 0 1.0 sec 6 0 (ZONE4_NORM_START) Conditioning Water Zone 4 Normal Start
T4:39 0 0 0 1.0 sec 0 0 (CLOSE_FLUID_CONV_NS) Timer to Close the Fluidized Convey
T4:40 0 0 0 1.0 sec 5 5 Indicate Alarm preventing opening of BIV for 5 sec
T4:41 0 0 0 1.0 sec 5 0 (LOAMPS_ENABLED) Ash Flip off because of low amps
T4:42 0 0 0 1.0 sec 5 0 (LOAMPS_DISABLED) Ash Flip off because of low amps
T4:43 0 0 0 1.0 sec 2 0 (T4_43) VFD Overtorque Timer
T4:44 0 0 0 1.0 sec 0 0 (DELAY_MOTOR_I_START) Unloader time delay of Unloader Mot
T4:45 0 0 0 1.0 sec 0 0 (DELAY_WATER_I_START) Unloader time delay of Water Valve
T4:46 0 0 0 1.0 sec 5 0 (DELAY_BIV_I_START) Unloader time delay of Bin Isolation
T4:47 0 0 0 1.0 sec 0 0 (DELAY_ASH_I_START) Unloader Time Delay of Ash Feed Start
T4:48 0 0 0 1.0 sec 900 0 (AUTO_STOP_I_START) Unloader Automatic Shut Down Timer Wh
T4:49 1 1 0 1.0 sec 3600 95 Run Fluidizer for preset Amount of Time on Normal Stop
T4:50 0 0 0 1.0 sec 1800 0 Run Fluidizer for preset Amount of Time on Final Stop
T4:51 0 0 0 1.0 sec 0 0 (ZONE1_INIT_START) Conditioning Water Zone 1 Initial Star
T4:52 0 0 0 1.0 sec 0 0 (ZONE2_INIT_START) Conditioning Water Zone 2 Initial Star
T4:53 0 0 0 1.0 sec 3 0 (ZONE3_INIT_START) Conditioning Water Zone 3 Initial Star
T4:54 0 0 0 1.0 sec 4 0 (ZONE4_INIT_START) Conditioning Water Zone 4 Initial Star
T4:55 0 0 0 1.0 sec 0 0 (CLOSE_ZONE1_NS_DELAY) Timer to Close the Conditioning Wa
T4:56 0 0 0 1.0 sec 0 0 (CLOSE_ZONE2_NS_DELAY) Timer to Close the Conditioning Wa
T4:57 0 0 0 1.0 sec 0 0 (CLOSE_ZONE3_NS_DELAY) Timer to Close the Conditioning Wa
T4:58 0 0 0 1.0 sec 0 0 (CLOSE_ZONE4_NS_DELAY) Timer to Close the Conditioning Wa
T4:59 0 0 0 1.0 sec 0 0 (CLOSE_ZONE1_FS_DELAY) Timer to Close the Conditioning Wa
T4:60 0 0 0 1.0 sec 0 0 (CLOSE_ZONE2_FS_DELAY) Timer to Close the Conditioning Wa
T4:61 0 0 0 1.0 sec 0 0 (CLOSE_ZONE3_FS_DELAY) Timer to Close the Conditioning Wa
96
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
97
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
98
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset 0 1 2 3 4 5 6 7 8 9
N7:0 24 5 0 7 0 900 0 5 3 25
N7:10 0 2 15 90 5 0 0 0 900 10
N7:20 5 10 30 38 60 30 4000 1000 10 1
N7:30 40 0 50 50 77 25466 73 15309 127 80
N7:40 20 0 4 4 0 0 2 0 6 2
N7:50 2 2 0 0 0 46 12 0 0 3
N7:60 4 0 2 4 6 0 50 0 0 0
N7:70 0 0 0 0 0 0 0 0
99
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
CDM 0 - Untitled
100
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
O:0/0 - Pull in relay CR. Close contacts wired into Mixer Motor
Starter
OTE - File #3 IO MAP - 0
O:0/1 - {FLUIDIZE_ON} Dry Contacts of PLC relay (output 0/1).
Contacts closed when not E-Stopped Dry Contacts in PLC.
OTE - File #3 IO MAP - 1
O:0/2 - {NO_DRAIN_VALVE} N.O. Drain valve. Close when water goes on
and open 1 hr after water off. SAV03
OTE - File #3 IO MAP - 2
O:0/3 - {VFD_FORWARD} Rotary Vane Feeder Run Forward Command
OTE - File #3 IO MAP - 3
O:0/4 - {VFD_REVERSE} Rotary Vane Feeder Run Reverse Command
OTE - File #3 IO MAP - 4
O:1.0 - Analog Output to Ash Feed Device
MOV - File #4 NORMAL OP - 23, 24
SCP - File #5 ANALOGS - 20, 21
LIM - File #8 ALARMS - 12
O:1.1 - MOV - File #4 NORMAL OP - 27, 28
SCP - File #5 ANALOGS - 12, 13
O:3/0 - {BIV_OPEN} Bin Isolation Valve SAV04 & Adaptor Fluidizing
Solenoid SAV09
OTE - File #3 IO MAP - 5
O:3/1 - {ZONE1_OPEN} Conditioning Water Zone 1 Solenoid(s)
OTE - File #3 IO MAP - 6
O:3/2 - {ZONE2_OPEN} Conditioning Water Zone 2 Solenoid
OTE - File #3 IO MAP - 7
O:3/3 - {ZONE3_OPEN} Conditioning Water Zone 3 Solenoid(s)
OTE - File #3 IO MAP - 8
O:3/4 - {ZONE4_OPEN} Conditioning Water Zone 4 Solenoid
OTE - File #3 IO MAP - 9
O:3/5 - {WASHOUT_SAV10} Used if optional wash out header is
provided. SAV05
OTE - File #3 IO MAP - 10
O:3/6 - {FLUID_CONV_OPEN} Fluidized Conveyor Valve Solenoid
OTE - File #3 IO MAP - 11
I:0/0 - {START_UNLOADING} N.O. Start Unloading Push Button. PB2 or
PB2A
XIC - File #3 IO MAP - 12
I:0/1 - {NORMAL_STOP_PB} N.O. Normal stop Push Button. PB3 or PB3A
XIC - File #3 IO MAP - 13
I:0/2 - {FINAL_LOAD_STOP_PB} N.O. Final Load Stop Push Button. PB4
or PB4A
XIC - File #3 IO MAP - 14
I:0/3 - Wash out on. N.O. momentary contacts of Wash Out on push
button. PB5 or PB5A
XIC - File #3 IO MAP - 15
I:0/4 - {MORE_WATER} Momentary push button that will increase signal
to water valve as long as pushed. PB6 or 6A
XIC - File #3 IO MAP - 16
I:0/5 - {LESS_WATER} Momentary push button that will decrease signal
to water valve as long as pushed. PB7 or7A
XIC - File #3 IO MAP - 17
I:0/6 - {MORE_ASH} Momentary push button that will increase signal
to Ash Feed as long as pushed. PB8 or PB8A
XIC - File #3 IO MAP - 18
I:0/7 - {LESS_ASH} Momentary push button that will decrease signal
to Ash Feed as long as pushed. PB9 or PB9A
XIC - File #3 IO MAP - 19
I:0/8 - All E-Stop buttons are out indicating a safe condition
XIC - File #3 IO MAP - 20
I:0/9 - Remote Panel Active
XIC - File #3 IO MAP - 21
I:1.0 - SCP - File #5 ANALOGS - 22
I:2/0 - {AIR_PRESSURE_SWITCH} N.O. PSL01 (air pressure switch).
Switch is held closed by adequate pressure
101
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
102
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
103
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
104
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
for 5 sec.
OTE - File #4 NORMAL OP - 25
XIC - File #4 NORMAL OP - 25
XIO - File #4 NORMAL OP - 26
B3:2/7 - {PSL01_FOUND} PSL01 found by logic
OTE - File #8 ALARMS - 2
XIC - File #8 ALARMS - 2, 7
B3:2/8 - {SET_MEM_SAME} Memory and values currently set are the same
OTE - File #7 TIMER_SAVE - 20
B3:2/9 - {ENABLE_I_START} Initial Start Enabled
OTE - File #4 NORMAL OP - 8
XIC - File #4 NORMAL OP - 2, 8, 14
XIO - File #4 NORMAL OP - 2, 9, 10, 12
B3:2/10 - {SAVING_I_STARTS} Go to the Set Up Screen
OTE - File #7 TIMER_SAVE - 6
XIC - File #7 TIMER_SAVE - 6
B3:2/11 - {SAVE_VALUES} Store current & timer settings in memory. This
bit is set from touch panel
XIC - File #7 TIMER_SAVE - 0, 2, 5, 6, 11, 14, 17
B3:2/12 - {SAVING_STARTS} Saving current start time delay presets
OTE - File #7 TIMER_SAVE - 5
XIC - File #7 TIMER_SAVE - 5
B3:2/13 - {PSL02_FOUND} PSL02 (Water Pressure Switch) found by logic
OTE - File #8 ALARMS - 3
XIC - File #8 ALARMS - 3, 8
B3:2/14 - {MEM_START_SAME} Normal Start Values of presets are the same
as memory
OTE - File #7 TIMER_SAVE - 9
XIC - File #7 TIMER_SAVE - 20
XIO - File #7 TIMER_SAVE - 5, 6, 7
B3:2/15 - {MEM_ISTART_SAME} Initial Start Values of presets are the
same as memory
OTE - File #7 TIMER_SAVE - 10
XIC - File #7 TIMER_SAVE - 20
XIO - File #7 TIMER_SAVE - 8
B3:3/0 - Force Screen to Operation Screen
ONS - File #6 HMI - 23
B3:3/1 - Force Scren to Main Screen
ONS - File #6 HMI - 24
B3:3/2 - Enter Normal Stop Minutes in Fluidizing Preset
XIC - File #6 HMI - 29
B3:3/3 - Enter Final Stop Minutes in Fluidizing Preset
XIC - File #6 HMI - 30
B3:3/4 - {RESTORE_DEFAULTS} Restore System Defaults
XIC - File #7 TIMER_SAVE - 0, 4, 21, 23, 25, 27
B3:3/5 - {2LOADING_DEFAULTS} If the Water, AFV and BIV delay timer
presets are 0 (like a new PLC would be) load Istart
defaults
OTE - File #7 TIMER_SAVE - 23
XIC - File #7 TIMER_SAVE - 23
B3:3/6 - Move Screen Once
ONS - File #6 HMI - 15
B3:3/7 - Move Screen Once
ONS - File #6 HMI - 17
B3:3/8 - Move Screen Once
ONS - File #6 HMI - 16
B3:3/9 - {RESET_RUN_TIME} Reset hours counter for Unloader from the
touch panel
XIC - File #6 HMI - 28
B3:3/10 - {SAVE_NS_PRESETS} Saving current Normal Stop time delay
presets
OTE - File #7 TIMER_SAVE - 11
XIC - File #7 TIMER_SAVE - 11
B3:3/11 - {MEM_NS_SAME} Normal Stop values in presets are the same as
memory
105
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
106
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
107
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
108
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
109
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
110
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
111
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
112
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
113
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
114
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
115
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
116
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
117
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
118
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
119
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
120
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
121
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
122
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset FW 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
123
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset FW 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
124
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset 0 1 2 3 4 5 6 7 8 9
S:0 . X . . . . . . . .
S:10 . . . . . . . . . .
S:20 . . . . . . . . . .
S:30 . . . . . . . . . .
S:40 . . . . . . . . . .
S:50 . . . . . . . . . .
S:60 . . . . . .
125
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
B3:0 X X X X X X X X X X X X X X X X
B3:1 X X X X X X X X X X X X X X X X
B3:2 X X X X X X X X X X X X X X X X
B3:3 X X X X X X X X X X X X X X X X
B3:4 X X X X X X X X X X X X X X X X Go Back To the Home Screen
B3:5 X X X X X X X X X X X X X X X X
B3:6 X X X X X X X X X X X X X X X X
B3:7 X X X . X X X X X X X X X X X X
B3:8 X X X X X X X X X X X X X X X X
B3:9 X X . . . . . . . . X X X X X X
B3:10 . . . . X X X X X X X X X X X X
126
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
127
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
128
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
129
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Offset 0 1 2 3 4 5 6 7 8 9
N7:0 X X X X X X X X X X
N7:10 X X X X X X X X X X
N7:20 X X X . X X X X X X
N7:30 X X X X X X X X X X
N7:40 X X X X X X X X X X
N7:50 X X X X X X X X X X
N7:60 X X X X X X X X X X
N7:70 X X X X X X X X
130
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
B3:0/0 START_MOTOR Global Output O:0/0 is on Mixer Motor start relay (CR) is pulled in.
B3:0/1 RUN_FLUIDIZER Global Output O:0/1 is on when none of the e-stops is pushed in. It normally starts fl
B3:0/2 VFD_RUN_REVERSE Global Command to Run The VFD in Reverse
B3:0/3 VFD_RUN_FORWARD Global Command to Run The VFD in Forward
B3:0/4 OPEN_BIV Global Output 0/4 is pulled in. This output is on when the Bin Isolation Valve is to o
B3:0/5 CLOSE_DRAIN Global Output 0/2 is pulled in. This output is on when the water drain valve (N.O.) is
B3:0/6 ASH_FEED_ON Global Output O:0/6 and O:1.0 (4-20mA) are on
B3:0/7 WATER_ON Global Output O:0/7 and O:1.1 (4-20mA) are on
B3:0/8 WASH_OUT_ON Global Optional wash out header solenoid valve output and normal wash out on
B3:0/9 NOOP Global Test Bit
B3:0/10 CONFIRM_SETPOINT Global Motor Setpoints have been confirmed
B3:0/11 FINALIZE_SCREEN Global Finalize Selected
B3:0/12 BYPASS_SCREEN Global Bypass selected
B3:0/13 NO_SELECTED Global No Selected
B3:0/14 BYPASS_SELECTED Global Bypass Confirmed
B3:0/15 YES_SELECTED Global Yes Selected
B3:1/0 Momentary Wash Out start push button depressed. PB5 or PB5A
B3:1/1 PB3 or PB3A Normal Stop Stops wash out or starts normal stop.
B3:1/2 FINAL_LOAD_STOP Global PB4 or PB4A Final Load Stop Stops wash out or starts Final Load Stop
B3:1/3 UNLOADING_START Global Start the Unloader Start Up Sequence
B3:1/4 INCREASE_WATER Global Increase water to the Unloader.
B3:1/5 DECREASE_WATER Global Decrease water to the Unloader.
B3:1/6 INCREASE_ASH Global Increase Ash to Unloader.
B3:1/7 DECREASE_ASH Global Decrease Ash to Unloader
B3:1/8 AIR_OK Global Instrument air pressure is OK
B3:1/9 WATER_OK Global Water pressure is OK
B3:1/10 BIV_CLOSED Global Bin Isolation Valve closed limit switch is made
B3:1/11 AFV_CLOSED Global Ash Feed Valve closed limit switch is made
B3:1/12 MOTOR_ON Global Unloader motor start auxiliary contacts are closed indicating starter is pulled
B3:1/13 ALARM_RESET Global Alarm acknowledged. Reset all alarms
B3:1/14 IO_POWER_IS_ON Global I/O power is on, all E-Stops are out.
B3:1/15 HMI Increase Service Factor
B3:2/0 ALARM_SHUT_DOWN Global Any of the alarm conditions in rung 0 of program file 8 will initiate a Normal S
B3:2/1 BIV_IS_OPEN Global Bin Isolation Valve Open limit Switch is made
B3:2/2 NORMAL_STOP Global The Unloader is in the process of a Normal Stop
B3:2/3 IN_FINAL_LOAD_STOP Global The Unloader is in a Final Load Stop
B3:2/4 RUNNING_NORMALLY Global The Unloader is running normally to condition product
B3:2/5 1LOADING_DEFAULTS Global If the Water, AFV and BIV delay timer presets are 0 (like a new PLC would be) lo
B3:2/6 LOHIAMPS Global water will shut off for 5 sec. and then stay on for 5 sec.
B3:2/7 PSL01_FOUND Global PSL01 found by logic
B3:2/8 SET_MEM_SAME Global Memory and values currently set are the same
B3:2/9 ENABLE_I_START Global Initial Start Enabled
B3:2/10 SAVING_I_STARTS Global Go to the Set Up Screen
B3:2/11 SAVE_VALUES Global Store current & timer settings in memory. This bit is set from touch panel
B3:2/12 SAVING_STARTS Global Saving current start time delay presets
B3:2/13 PSL02_FOUND Global PSL02 (Water Pressure Switch) found by logic
B3:2/14 MEM_START_SAME Global Normal Start Values of presets are the same as memory
B3:2/15 MEM_ISTART_SAME Global Initial Start Values of presets are the same as memory
B3:3/0 Force Screen to Operation Screen
B3:3/1 Force Scren to Main Screen
B3:3/2 Enter Normal Stop Minutes in Fluidizing Preset
B3:3/3 Enter Final Stop Minutes in Fluidizing Preset
B3:3/4 RESTORE_DEFAULTS Global Restore System Defaults
B3:3/5 2LOADING_DEFAULTS Global If the Water, AFV and BIV delay timer presets are 0 (like a new PLC would be) lo
B3:3/6 Move Screen Once
B3:3/7 Move Screen Once
B3:3/8 Move Screen Once
B3:3/9 RESET_RUN_TIME Global Reset hours counter for Unloader from the touch panel
B3:3/10 SAVE_NS_PRESETS Global Saving current Normal Stop time delay presets
B3:3/11 MEM_NS_SAME Global Normal Stop values in presets are the same as memory
B3:3/12 Populate Low and High Amps
B3:3/13 SAVE_FS_PRESETS Global Saving current Final Load Stop time delay presets
B3:3/14 MEM_FS_SAME Global Final Load Stop timer presets are the same as memory
B3:3/15 RESTORE_MEMORY Global Restore the Current set points and Timer Presets from memory.
B3:4 Go Back To the Home Screen
B3:4/0 BIV_CLOSED_LS_FOUND Global ZSC04 the Bin Isolation Valve Closed Limit Switch has been found by the logic
B3:4/1 BIV_OPEN_LS_FOUND Global ZSO04 the Bin Isolation Valve Open Limit Switch has been found by the logic
B3:4/2 RESTORE_I_STARTS Global Restore the Initial Start timer presets from memory
B3:4/3 AFV_CLOSED_LS_FOUND Global N.O. ZSC01 Ash Feed Valve Closed Limit Switch found by logic
B3:4/4 IMMEDIATE_STOP Global I/O Power has failed or there is a major alarm on the mixer motor.
B3:4/5 RVF_TEST Global Lock in RVF VFD Reversing Simulation Until One Cycle Complete
B3:4/6 RESTORE_STARTS Global Restore the Normal Start timer presets from memory
B3:4/7 RESTORE_NS_PRESETS Global Restore the Normal Stop timer presets from memory
B3:4/8 RESTORE_FS_MEM Global Restore the Final Load Stop timer presets from memory
B3:4/9 Store Conditioning Water On Selection into Retentive Memory
B3:4/10 VFD_NO_FAULT Global Rotary Vane Feeder VFD Running Without Fault
B3:4/11 VFD_OVERTORQUE Global Rotary Vane Feeder VFD Overcurrent Condition
B3:4/12 TS2 Global Main Control Panel Temperature High
B3:4/13 TS4 Global Remote Panel Temperature High
B3:4/14 SW1 Global Remote Panel Active
131
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
132
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
133
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
N7:28 LOW_I_SET_POINT Global Low Current set point from the HMI
N7:29 Retentive Memory for Condition Water On During Washout Selection
N7:30 HI_I_SET_POINT Global High Current set point from the HMI
N7:31 Retentive Memory for Ash Feed Device Selection
N7:32 FLA_I_SET_POINT Global Full Load Amps current set point from the HMI
N7:33 MEM_I_FLA Global Full Load Amps Saved Setting
N7:33/0 Retain Choice of Ash Feed Device.
N7:33/1 Retain Choice of Water Supply Valve Control
N7:34 Water 0 - 100 % Setpoint
N7:35 WATER_CONTROL Global Digital signal used by the Analog output module to generate 4-20mA output
N7:36 AF_STEP_1 Global 1st step in generating signal to Ash Feed. 0-50 range
N7:37 ASH_CONTROL Global Digital signal used by the Analog module to generate 4-20mA
N7:38 OPEN_MINUS_SIGNAL Global Read difference between full open & signal.
N7:39 High Amps is currently ##% of Full Load Amps
N7:40 Low Amps is currently ##% of Full Load Amps
N7:41 ASH_FEED_SIGNAL Global 0-100% for Ash Feed signal to Touch Panel
N7:43 SIGNAL_TO_ASH_FEED Global Convert signal to the Ash Feed to 4-20(mA) for display on the touch panel
N7:44 0-100% for Water Positioner to Touch Panel
N7:45 HMI_SCREEN_WRITE Global Screen Number Written to HMI
N7:46 RUN_TIME_IN_HOURS Global Unloader run time in hours to the Touch Panel
N7:47 CURRENT_MODE Global 0=off, 1=norm unl, 2=i-start, 3=norm-start, 4=norm-stop, 5=FLS, 6=Washout
N7:48 HMI Screen Number Read
N7:49 BIV_CONTROL_SELECTED Global Bin Isolation Valve 0=BIV Off 1=BIV Test 2=BIV Auto
N7:50 ASH_CONTROL_SELECTED Global Ash Feed Device 0=AF Off 1=AF Test 2=AF Auto
N7:51 WATER_CONTROL_SELECT Global Water Supply Valve 0=WSV Off 1=WSV Test 2=WSV Auto
N7:52 HILO_AMPS Global Null, Low or Hi Amps 0=No Indication 1=Low Amps 2=Hi Amps
N7:53 Indicate current Timer presets
N7:54 Values have been confirmed
N7:55 MEM_I_HIAMP Global High Amps Saved Setting
N7:56 MEM_I_LOAMP Global Low Amps Saved Setting
N7:57 MEM_ZONE1_I_START Global Stored Value of Time delay in opening Zone 1 on Initial Start
N7:58 MEM_ZONE2_I_START Global Stored Value of Time delay in opening Zone 2 on Initial Start
N7:59 MEM_ZONE3_I_START Global Stored Value of Time delay in opening Zone 3 on Initial Start
N7:60 MEM_ZONE4_I_START Global Stored Value of Time delay in opening Zone 4 on Initial Start
N7:61 MEM_ZONE1_N_START Global Stored Value of Time delay in opening Zone 1 on Normal Start
N7:62 MEM_ZONE2_N_START Global Stored Value of Time delay in opening Zone 2 on Normal Start
N7:63 MEM_ZONE3_N_START Global Stored Value of Time delay in opening Zone 3 on Normal Start
N7:64 MEM_ZONE4_N_START Global Stored Value of Time delay in opening Zone 4 on Normal Start
N7:65 SERVICE_FACTOR_IND Global Service Factor 0=1.00 1=1.15 2=1.25
N7:66 Hi-Hi Amps Calculated
N7:67 MEM_ZONE1_NS Global Stored value of time delay in closing the Conditioning Water Zone 1 Valve after
N7:68 MEM_ZONE2_NS Global Stored value of time delay in closing the Conditioning Water Zone 2 Valve after
N7:69 MEM_ZONE3_NS Global Stored value of time delay in closing the Conditioning Water Zone 3 Valve after
N7:70 MEM_ZONE4_NS Global Stored value of time delay in closing the Conditioning Water Zone 4 Valve after
N7:71 MEM_ZONE1_FS Global Stored value of time delay in closing the Conditioning Water Zone 1 Valve after
N7:72 MEM_ZONE2_FS Global Stored value of time delay in closing the Conditioning Water Zone 2 Valve after
N7:73 MEM_ZONE3_FS Global Stored value of time delay in closing the Conditioning Water Zone 3 Valve after
N7:74 MEM_ZONE4_FS Global Stored value of time delay in closing the Conditioning Water Zone 4 Valve after
N7:75 MEM_FLUID_CONV_NS Global Stored value of time delay in closing the Fluidized Conveyor Air Valve.
N7:76 MEM_FLUID_CONV_FS Global Stored value of time delay in closing the Fluidized Conveyor Air Valve on a Fina
N7:77 For the Mode Select screen multistate indicator. 0=Closed, 1=Open, 2=Low Air, 3=
O:0/0 Pull in relay CR. Close contacts wired into Mixer Motor Starter
O:0/1 FLUIDIZE_ON Global Dry Contacts of PLC relay (output 0/1). Contacts closed when not E-Stopped Dry C
O:0/2 NO_DRAIN_VALVE Global N.O. Drain valve. Close when water goes on and open 1 hr after water off. SAV03
O:0/3 VFD_FORWARD Global Rotary Vane Feeder Run Forward Command
O:0/4 VFD_REVERSE Global Rotary Vane Feeder Run Reverse Command
O:0/5
O:0/6 ASH_ON_OFF_OUTPUT Global Ash Feed On/Off output. SAV01
O:0/7 COND_WATER Global Conditioning water on. On/off output to solenoid if used. SAV02
O:0/8
O:0/9 COND_1 Global This is a timed output used if conditioning used or water sequenced. SAV06
O:0/10 COND_2 Global This is a timed output used if conditioning used or water sequenced. SAV07
O:0/11 COND_3 Global This is a timed output used if conditioning used or water sequenced. SAV08
O:0/12 SPARE_OUT_12 Global This is a spare. It is grouped with Output 13,14 & 15
O:0/13 SPARE_OUT_13 Global This is a spare. It is grouped with Output 12,14 & 15
O:0/14 SPARE_OUT_14 Global This is a spare. It is grouped with Output 12,13, & 15
O:0/15 SPARE_OUT_15 Global This is a spare. It is grouped with Output 12,13, & 14
O:1.0 Analog Output to Ash Feed Device
O:2.0 Analog output to Ash Feed Devise
O:2.1 Analog output to water valve
O:3/0 BIV_OPEN Global Bin Isolation Valve SAV04 & Adaptor Fluidizing Solenoid SAV09
O:3/1 ZONE1_OPEN Global Conditioning Water Zone 1 Solenoid(s)
O:3/2 ZONE2_OPEN Global Conditioning Water Zone 2 Solenoid
O:3/3 ZONE3_OPEN Global Conditioning Water Zone 3 Solenoid(s)
O:3/4 ZONE4_OPEN Global Conditioning Water Zone 4 Solenoid
O:3/5 WASHOUT_SAV10 Global Used if optional wash out header is provided. SAV05
O:3/6 FLUID_CONV_OPEN Global Fluidized Conveyor Valve Solenoid
O:3/7 spare
O:5.0 ANALOG_ASH_FEED Global Analog output to Ash Feed Devise
O:5.1 ANALOG_TO_WATER Global Analog output to water valve
134
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
Q4:1 End
S:0 Arithmetic Flags
S:0/0 Processor Arithmetic Carry Flag
S:0/1 Processor Arithmetic Underflow/ Overflow Flag
S:0/2 Processor Arithmetic Zero Flag
S:0/3 Processor Arithmetic Sign Flag
S:1 Processor Mode Status/ Control
S:1/0 Processor Mode Bit 0
S:1/1 Processor Mode Bit 1
S:1/2 Processor Mode Bit 2
S:1/3 Processor Mode Bit 3
S:1/4 Processor Mode Bit 4
S:1/5 Forces Enabled
S:1/6 Forces Present
S:1/7 Comms Active
S:1/8 Fault Override at Powerup
S:1/9 Startup Protection Fault
S:1/10 Load Memory Module on Memory Error
S:1/11 Load Memory Module Always
S:1/12 Load Memory Module and RUN
S:1/13 Major Error Halted
S:1/14 Access Denied
S:1/15 First Pass
S:2/0 STI Pending
S:2/1 STI Enabled
S:2/2 STI Executing
S:2/3 Index Addressing File Range
S:2/4 Saved with Debug Single Step
S:2/5 DH-485 Incoming Command Pending
S:2/6 DH-485 Message Reply Pending
S:2/7 DH-485 Outgoing Message Command Pending
S:2/15 Comms Servicing Selection
S:3 Current Scan Time/ Watchdog Scan Time
S:4 Time Base
S:5/0 Overflow Trap
S:5/2 Control Register Error
S:5/3 Major Err Detected Executing UserFault Routine
S:5/4 M0-M1 Referenced on Disabled Slot
S:5/8 Memory Module Boot
S:5/9 Memory Module Password Mismatch
S:5/10 STI Overflow
S:5/11 Battery Low
S:6 Major Error Fault Code
S:7 Suspend Code
S:8 Suspend File
S:9 Active Nodes
S:10 Active Nodes
S:11 I/O Slot Enables
S:12 I/O Slot Enables
S:13 Math Register
S:14 Math Register
S:15 Node Address/ Baud Rate
S:16 Debug Single Step Rung
S:17 Debug Single Step File
S:18 Debug Single Step Breakpoint Rung
S:19 Debug Single Step Breakpoint File
S:20 Debug Fault/ Powerdown Rung
S:21 Debug Fault/ Powerdown File
S:22 Maximum Observed Scan Time
S:23 Average Scan Time
S:24 Index Register
S:25 I/O Interrupt Pending
S:26 I/O Interrupt Pending
S:27 I/O Interrupt Enabled
S:28 I/O Interrupt Enabled
S:29 User Fault Routine File Number
S:30 STI Setpoint
S:31 STI File Number
S:32 I/O Interrupt Executing
S:33 Extended Proc Status Control Word
S:33/0 Incoming Command Pending
S:33/1 Message Reply Pending
S:33/2 Outgoing Message Command Pending
S:33/3 Selection Status User/DF1
S:33/4 Communicat Active
S:33/5 Communicat Servicing Selection
S:33/6 Message Servicing Selection Channel 0
S:33/7 Message Servicing Selection Channel 1
S:33/8 Interrupt Latency Control Flag
S:33/9 Scan Toggle Flag
135
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
136
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
T4:9 BIV_CLOSE_ON_NORM Global Unloader delay in closing Bin Isolation Valve during Normal Stop
T4:9/DN NORMAL_BIV_CLOSE Global Delay in closing Bin Isolation Valve during Normal Stop
T4:10 AF_STOP_ON_NORM Global Unloader delay in stopping Ash Feed during Normal Stop
T4:10/DN
T4:11 WATER_OFF_ON_NORM Global Unloader delay in closing Water Valve during Normal Stop
T4:11/DN NORMAL_WATER_OFF Global Delay in closing Water Valve during Normal Stop
T4:12 MTR_STOP_ON_NORM Global Unloader delay is stopping Unloader Motor during Normal Stop
T4:12/DN NORMAL_MTR_STOP Global Delay in stopping Unloader Motor during Normal Stop
T4:13 BIV_CLOSE_ON_FINAL Global Unloader delay in closing Bin Isolation Valve during Final Load Stop
T4:13/DN FINAL_BIV_CLOSE Global Delay in closing Bin Isolation Valve during Final Load Stop
T4:14 AF_STOP_ON_FINAL Global Unloader delay in Stopping Ash Feed during Final Load stop
T4:14.PRE AFV_CLOSE_ON_FL Global Unloader delay in stopping Ash Feed during Final Load Stop
T4:14/DN
T4:15 WATER_OFF_0N_FINAL Global Unloader delay in closing Water Valve during Final Load Stop
T4:15/DN FINAL_WATER_OFF Global Delay in closing Water Valve during Final Load Stop
T4:16 MTR_STOP_ON_FINAL Global Unloader delay in stopping Unloader Motor during Final Load Stop
T4:16/DN FINAL_MTR_OFF Global Delay in stopping Unloader Motor during Final Load Stop
T4:17 INRUSH_DELAY_TIMER Global Timer to prevent motor inrush current from tripping high and high-high alarms
T4:18 HI_HI_MTR_AMPS_TD Global Time delay to prevent spikes from tripping a High High amps shut down
T4:18/DN High High Motor Amps above Set Point from HMI
T4:19 WAT_2PER_SEC Global Timer used to generate a 2% change in signal to Water Position Valve per Second
T4:19/DN
T4:20 RVF_REV_DELAY Global Stop for Direction Change
T4:20.ACC B_LOAIR Global Unloader B time delay in low air pressure alarm logic
T4:20/DN
T4:21 REVERSE_RUN Global Run Reverse to clear Jam
T4:21.ACC B_LOH2O Global Unloader B time delay in low water pressure alarm
T4:21/TT
T4:22 ASH_RAMP_SLO Global Timer used to determine ramping rate of output to Ash Feed Device
T4:22/DN
T4:23 2_PERCENT_SEC Global Timer used to generate a 2% change in signal to Ash Feed Device per Second
T4:23/DN
T4:23/TT
T4:24 WATER_RAMP_DEL Global Timer used to generate 5% change in signal to Ash Feed Device per second
T4:25 LOHIAMPS_ENABLED Global Water off because of low or high amps
T4:26 LOHIAMPS_DISABLED Global Water off because of low or high amps
T4:27 I_START_OFF_TIMER Global Initial Start on Next Load Timer
T4:28 RUN_1_HR_FOR_DONE Global Times out when the Unloader has 1 Hour of run time
T4:28/DN Times out when the Unloader has 1 hour of run time
T4:29 AFV_CLOSED_LS Global Ash Feed Valve Closed Limit Switch time delay to stroke
T4:30 RVF_FWD_DELAY Global Stop for Direction Change
T4:30.PRE DELAY_START_1_COND Global T4:30.PRE Conditioner output 1 delay in opening on a normal start
T4:30/DN
T4:31 FOWARD_RUN Global Run Foward to check if Jam is Cleared
T4:31.PRE DELAY_START_2_COND Global T4:31.PRE Conditioner output 2 delay in opening on a normal start
T4:31/TT
T4:32 OVERTORQUE_DELAY Global Wait for current overtorque check
T4:32.PRE DELAY_START_3_COND Global T4:32.PRE Conditioner output 3 delay in opening on a normal start
T4:33 Save or Restore Timer Presets
T4:33.PRE NS_COND_1_DELAY Global T4:33.PRE Delay in closing Conditioner valve 1 on a normal stop
T4:34 T4_34 Global Rewrite Screen Until a Selection has been Made
T4:34.PRE NS_COND_2_DELAY Global T4:34.PRE Delay in closing Conditioner valve 2 on a normal stop
T4:34/DN
T4:35 ZONE1_NORM_START Global Conditioning Water Zone 1 Normal Start Delay
T4:35.PRE
T4:36 ZONE2_NORM_START Global Conditioning Water Zone 2 Normal Start Delay
T4:36.PRE
T4:37 ZONE3_NORM_START Global Conditioning Water Zone 3 Normal Start Delay
T4:37.PRE
T4:38 ZONE4_NORM_START Global Conditioning Water Zone 4 Normal Start Delay
T4:38.PRE
T4:39 CLOSE_FLUID_CONV_NS Global Timer to Close the Fluidized Conveyor Air Valve after Normal Stop
T4:40 Indicate Alarm preventing opening of BIV for 5 sec
T4:40/DN
T4:40/EN
T4:41 LOAMPS_ENABLED Global Ash Flip off because of low amps
T4:42 LOAMPS_DISABLED Global Ash Flip off because of low amps
T4:43 T4_43 Global VFD Overtorque Timer
T4:44 DELAY_MOTOR_I_START Global Unloader time delay of Unloader Motor Initial Starting
T4:45 DELAY_WATER_I_START Global Unloader time delay of Water Valve Opening on Initical Start
T4:46 DELAY_BIV_I_START Global Unloader time delay of Bin Isolation Valve Opening on Initial Start
T4:47 DELAY_ASH_I_START Global Unloader Time Delay of Ash Feed Start Opening on Initial Start
T4:48 AUTO_STOP_I_START Global Unloader Automatic Shut Down Timer Which will initiate a Normal Stop
T4:49 Run Fluidizer for preset Amount of Time on Normal Stop
T4:50 Run Fluidizer for preset Amount of Time on Final Stop
T4:51 ZONE1_INIT_START Global Conditioning Water Zone 1 Initial Start Delay
T4:52 ZONE2_INIT_START Global Conditioning Water Zone 2 Initial Start Delay
T4:53 ZONE3_INIT_START Global Conditioning Water Zone 3 Initial Start Delay
T4:54 ZONE4_INIT_START Global Conditioning Water Zone 4 Initial Start Delay
T4:55 CLOSE_ZONE1_NS_DELAY Global Timer to Close the Conditioning Water Zone 1 Solenoid(s) after Normal Stop
137
Mixer/Unloader 1307_143e.RSS Revision E November 10th, 2010
Address/Symbol Database
T4:56 CLOSE_ZONE2_NS_DELAY Global Timer to Close the Conditioning Water Zone 2 Solenoid after Normal Stop
T4:57 CLOSE_ZONE3_NS_DELAY Global Timer to Close the Conditioning Water Zone 3 Solenoid(s) after Normal Stop
T4:58 CLOSE_ZONE4_NS_DELAY Global Timer to Close the Conditioning Water Zone 4 Solenoid after Normal Stop
T4:59 CLOSE_ZONE1_FS_DELAY Global Timer to Close the Conditioning Water Zone 1 Solenoid(s) after Final Stop
T4:60 CLOSE_ZONE2_FS_DELAY Global Timer to Close the Conditioning Water Zone 2 Solenoid(s) after Final Stop
T4:61 CLOSE_ZONE3_FS_DELAY Global Timer to Close the Conditioning Water Zone 3 Solenoid(s) after Final Stop
T4:62 CLOSE_ZONE4_FS_DELAY Global Timer to Close the Conditioning Water Zone 4 Solenoid(s) after Final Stop
T4:63 CLOSE_FLUID_CONV_FS Global Timer to Close the Fluidized Conveyor Air Valve after Final Stop
T4:64 High Amps Delay
T4:65 RVF VFD Fault Alarm Delay
138