The SmokeShield PTC™ is a range of automatic smoke and fire dampers designed for air conditioning and ventilation systems, offering up to 4 hours of protection. These dampers feature stainless steel construction, various control modes, and fail-safe operations, ensuring reliable performance in fire safety applications. The product includes advanced features such as a unique snaplock™ drive interface for easy installation and maintenance, as well as multiple thermal release options for effective operation during fire conditions.

Uploaded by

Thomas Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views24 pages

Damper SmokeShield

The SmokeShield PTC™ is a range of automatic smoke and fire dampers designed for air conditioning and ventilation systems, offering up to 4 hours of protection. These dampers feature stainless steel construction, various control modes, and fail-safe operations, ensuring reliable performance in fire safety applications. The product includes advanced features such as a unique snaplock™ drive interface for easy installation and maintenance, as well as multiple thermal release options for effective operation during fire conditions.

Uploaded by

Thomas Garcia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 24

SmokeShield PTC™

Proportional Torque Control


Automatic Smoke and Fire Dampers

actionair
Dampers Controls Fancoils

Ruskin Air Management Limited


www.ruskinuk.co.uk

INQ00015166/1
INQ00015166_0001
actionair SmokeShield PTC™

Introduction Specification
SmokeShield PTC™ out of airstream for protection against
Proportional Torque Control Automatic damage, be hard wearing and free
Smoke and Fire Dampers with 75mm x running.
0.5mm thick stainless steel aerodynamic The Control Mode/Damper connection
interlocking blades incorporating synthetic shall be by means of the sncplock™
seal, with steel blade end bearings and drive interface mechanism, which is
peripheral gasketting. Housed in a totally independent of the ductwork.
galvanised steel fully welded I .2mm SmokeShield PTC™ Automatic Smoke
spigotted casing suitable for square, and Fire Dampers with their
rectangular, circular or flat oval appropriate control modes shall have
connections. spring Fail-Safe Closed operation.
All PTC™ Dampers are supplied with SmokeShield PTC™ Damper and
blades in the closed position. selected Control Mode (Ml, M5, M6
The totally enclosed precise movement and M9 with ATEX options) as
opposed blade drive shall be positioned supplied by Actionair.
I
SmokeShield PTC™ VentShield PTC™
Actionair has always been at the forefront
A Fire Rated Damper in accordance Proportional Torque Control Automatic
in the innovative development, design and
with British Standard BS 9999: 2008 Smoke Release Dampers with
manufacture of life safety dampers and
(Ref 33.4.5.3). should be held in the 75mm x 0.5mm thick stainless steel
associated controls. Now with the unique
Open Position by means of a aerodynamic blades incorporating
SmokeShield PTC™ range of Automatic
Thermally Actuated Device set to synthetic seal, with steel blade end
Smoke and Fire Dampers Actionair
operate at approximately 7 4 °C. bearings and peripheral gasketting.
continues this tradition.
Housed in a galvanised steel fully
SmokeShield PTC™ Automatic welded spigotted casing suitable for
Smoke and Fire Control Dampers are square, rectangular, circular or flat
Fire Rated Dampers as they are held
The Range in the Reset (Open) Position by a
oval duct connections.
The totally enclosed precise
The SmokeShield PTC TM range of Thermally Actuated Device (Control
Mode I - Mechanical Fusible Link, movement opposed blade drive shall
Quality Engineered Dampers are suitable be positioned out of airstream for
for air conditioning and ventilation Control Modes 5 and 6 - Electrical
Thermal Release, Control Mode 9 - protection against damage, be hard
systems requiring up to 4 hours wearing and free running.
protection. Refer to the Action air Pneumatic Thermal Release) operating
Approved Fire and Smoke Dampers at a temperature of approximately The Control Mode/Damper
Installation Manual for precise details. 72 °C ± 4 °C. connection shall be by means of the
sncplock™ drive interface
These aerodynamic stainless steel mechanism, which is totally
interlocking opposed blade dampers are independent of the ductwork.
fail-safe spring close with manual or
electrical reset control modes. VentShield PTC™ Automatic Smoke
Note: Thermally activated devices are
Release Dampers with their
not supplied with VentShield Control
appropriate control modes shall have
Modes as standard.
spring Fail-Safe Open operation.
The VentShield PTC™ Damper range
are reverse acting for smoke release VentShield PTC™ Damper and
or exhaust. (Manual system not selected Control Modes as supplied
available). by Actionair.

Proportional Application position for smoke release or exhaust.


Dampers may be installed both vertically
Torque Control Parameters and horizontally. In addition, for vertical
installations, the damper may be installed
The control mode and sm:plock™ drive SmokeShield PTC™ and VentShield with the blades running vertically. Airflow
interface provides the optimum PTC™ Dampers to maximum width and can be from either direction.
mechanical advantage to the damper by height dimensions (see pages 16 and 17) Actionair SmokeShield PTC™ and
delivering: can be used where the operating total VentShield PTC™ Dampers are designed
the right torque, in the right place, at system pressure is up to 1500 Pascals for applications in normal dry filtered air
the right time. and duct velocities to 15m/second. systems. If exposed to fresh air intakes
The SmokeShield PTC™ Damper blades and/or inclement conditions, the dampers
are normally open and fail-safe to the should be subject to a planned inspection
closed position.This product is fire rated. programme.
The VentShield PTC™ Damper blades are For specialist and/or aggressive applications,
normally closed and fail-safe to the open please refer to Actionair Sales Office.

2 www.actionair.co.uk
INQ00015166/2
INQ00015166_0002
SmokeShield PTC™ actionair
Casing Features
With double skin spigotted galvanised Damper casings are manufactured with
steel (to BS EN 10346:2009) 1 .2mm thick fully welded spigotted connections

~I
casing the SmokeShield PTC™ dampers suitable for Square, Rectangular, Circular
comply to Class A and B of Eurovent and Flat Oval duct connections.
Document 2/2 and Test Procedures for
As an extra cost option, casings can be
Classes A, B and C of HVCA Ductwork
manufactured in 430 grade (Type 1.4016)
Specification OWi 44.
Ferritic or 316 grade (Type 1.4401)
Austenitic stainless steel, 1 .2mm thick. Type SPG Square I Rectangular

0
0 0
Q
o~

:~%.:
a

Type SPG Circular

IC-~IType SPG Flat Oval

Blade Features Multiple Assemblies


SmokeShield damper blades are Stainless steel blade end bearing and Square and rectangular casings are
aerodynamic double skin, Type 1 .4016 peripheral gasketting maintain the low available in multiple module arrangements
(430) Ferritic stainless steel, which are closed blade smoke leakage whilst supplied complete with joining channels
75mm x 0.5mm thick and interlock to allowing for expansion under full fire for site fixing by others.
form a positive smoke and fire resisting conditions.
shield.
Optional Blade construction Type 1 .4401

II
Incorporated within the blade profile is a (316) Austenitic stainless steel. STD
RHD
synthetic seal to ensure low closed blade
smoke leakage.
PLAN VIEW ~] LHD

+ +
75 41.5 STD 1•1---------------1•,~j LHD
SmokeShield PTC™ blade dimensions RHD

I
I
I
I

\_ \
I

~ I STD 1•1---------------1•,~j LHD


I RHD
I
I
I

()
I
I

~
I
I
I
I
I
I

\_ \
I

SmokeShield PTC™ fail-safe closed VentShield PTC™ fail-safe open

www.actionair.co.uk 3
INQ00015166/3
INQ00015166_0003
actionair SmokeShield PTC™

Damper - Control Mode Interface (Right Hand Damper shown)

snaplock™ Drive Interface 3 Position Electrical (ATEX)


Designed to develop Location Plates Actuator
Proportional Torque Control

SmokeShield PTC™ Damper Drive Shroud and Control Mode Mode 9, Pneumatic
501 Damper Transit Plate 5/6 shown (ATEX) Actuator

SmokeShield PTC™ Damper with


unique snaplock™ Damper/Control
Control Modes 5 and 6 Electrical
Mode Interface Control Options Optimised motor/spring return control
Automatic Smoke and Fire Damper and modes with remote reset-release facilities,
A choice of Control Modes are located
Control Mode assembly with a unique with volt free contacts for provision of
outside of the ductwork for easy access
and dedicated Proportional Torque external indication, monitoring and control
and installation.
Control for optimised Damper/Control by means of an Actionpac damper
All SmokeShield Control Modes must be in
Mode torque performance. control system, or by a suitable
the released position prior to connection.
alternative proprietary control format.
The unique snaplock™ drive interface
Control Mode 1 Mechanical The motorised Control Modes 5 and 6
ensures user friendly, easy and secure
Manual reset - with volt free contact for can be fitted in 3 positions through 180°
connection of the Control Mode to the
provision of external indication of damper (see page 15) allowing maximum on-site
Damper.
status. installation flexibility. (Position 2 is
The drive interface which is totally (Not available on Vent Shield). supplied as standard).
independent of the ductwork, eliminates
Control Mode 9
the need for costly dedicated duct
Pneumatic
sections, and provides ease of
connection to square, rectangular, circular
Note: VentShield PTC™ Dampers and
and flat oval ductwork.
associated control modes are reverse
This drive interface guarantees that only action with spring opening (Mode I not
the correct and certified Actionair available).
products can be used.

4 www.actionair.co.uk
INQ00015166/4
INQ00015166_0004
SmokeShield PTC™ actionair
Thermal Links and Release Types (SmokeShield Only)

Mechanical Fusible Link Pneumatic Thermal Release (PTR)


Control Mode 1 Control Mode 9
Fail-safe by means of a unique and patented Mechanical Fusible Fail-safe is by means of a Pneumatic Thermal Release (PTR) which
Link which operates at approx. 72 °C, complying with BS 9999 : operates at 74 °C, or if air supply is interrupted.
2008 (Ref 33.4.5.3).

The link assembly incorporates a safety feature that ensures the


fail safe status of the damper if the link is not fitted on to the
ductwork.

A manual test may be performed by simple unscrewing the wing


nut situated on the fusible link.

FUSIBLE LINK

Electrical Thermal Release (ETR) Fail-safe by means of a unique and patented electrical thermal
release which operates at approx 72 °C or if power supply is
Control Modes 5 and 6 interrupted, complying with BS 9999 : 2008 (Ref 33.4.5.3).

The ETR incorporates triple safety features, including an ingenious


device that ensures the fail-safe status of the damper if the ETR is
not fitted on to the ductwork.
A manual test switch allows periodic operation of the damper for
testing purposes simulating actual fail-safe release under
smoke/fire conditions.
For safety reasons the ETR/PTR is designed to operate once only
when the activation temperature is reached.

, I/ POWER -./'
--- ETR FITTED -./'
/ I ' THERMAL FUSE -./'

ETR Indication light


As standard, a green LED lamp is built into the ETR
housing. This gives the user a simple and clear visual
check that the Actuator is receiving power, the ETR is
correctly fitted, and the thermal fuse is intact.

www.actionair.co.uk 5
INQ00015166/5
INQ00015166_0005
actionair SmokeShield PTC™

Control Mode Details

Control Mode 5 PTC and Control Mode 6 PTC Control Mode 9PTC

Control Mode 5 PTC and Control Mode The Electro Thermal Release (ETR) Control Mode 9 PTC
6 PTC 60 seconds MAX Reset/ 22 supplied for fire damper use has an This mode has been developed to provide
seconds Release Operation. integral fail-safe device to ensure that it is pneumatic operation of the damper and is
This series of control modes achieve 60 installed into the ductwork correctly. ETR available in spring return versions for fail-
seconds to drive to the end position, with units are not supplied with VentShield, safe operation. A Pneumatic Thermal
a 22 second spring return time. because these are designed to fail-safe Release assembly (PTR) is available
open. (SmokeShield only) to react to fire
As with all PTC modes, this series uses
the snaplock™ interface. Fire rated End switches are provided with each conditions. As with all PTC actuators, this
dampers are primarily designed to be mode, so that damper Reset and Release series uses the snaplock™ interface. Switch
fitted into a wall or floor, and the interface positions may be monitored. The mode is box and solenoid accessories available.
displaces the mode from the line of the permanently attached to the mechanism ATEX optional available when fitted with
wall. Dampers may be installed and finally driving the damper blades. correct Solenoid Valve and Switch Box.
the mode removed from storage for easy
fitting, thus preventing damage to the M9 PTC Pneumatic Thermal Release I
mode before it is required. End switches Air Off - Fail-safe Close
and LSF cable are provided as standard
M9 PTC Vent Pneumatic
on these modes. Air Off - Fail-safe Open
Versions are available to allow fail-safe
close for fire safety (SmokeShield) or fail-
safe open for smoke extract (VentShield).

SmokeShield and VentShield


M5 PTC 10/2W (12.5VAMAX) 24V end switches SPOT 250V 6(3)A SmokeShield Thermal Release I Power Off - Fail-safe Close*
M6 PTC 12/4W (14VAMAX) 230V end switches SPOT 250V 6(3)A SmokeShield Thermal Release I Power Off - Fail-safe Close*
M5 PTC Vent 10/2W (12.5VAMAX) 24V end switches SPOT 250V 6(3)A VentShield Thermal Release I Power Off - Fail-safe Open*
M6 PTC Vent 12/4W (14VAMAX) 230V end switches SPOT 250V 6(3)A VentShield Thermal Release I Power Off - Fail-safe Open*
M5 PTC NON ETR 10/2W (12.5VAMAX) 24V end switches SPOT 250V 6(3)A SmokeShield Power Off - Fail-safe Close
M6 PTC NON ETR 12/4W (14VAMAX) 230V end switches SPOT 250V 6(3)A SmokeShield Power Off - Fail-safe Close
M5 PTC Vent NON ETR 10/2W (12.5VAMAX) 24V end switches SPOT 250V 6(3)A VentShield Power Off - Fail-safe Open
M6 PTC Vent NON ETR 12/4W (14VAMAX) 230V end switches SPOT 250V 6(3)A VentShield Power Off - Fail-safe Open

*SmokeShield Control Modes M5 PTC and M6 PTC are supplied as standard with the Electrical Thermal Release (ETR) (Not fitted
to VentShield). The units Fail-safe by means of the unique and patented ETR device which operates at 72 °C, or if the power
supply is off/interrupted. Complying with BS 9999 : 2008 (Ref 33.4.5.3). Non ETR versions Fail-safe when the power is
off/interrupted.

6 www.actionair.co.uk
INQ00015166/6
INQ00015166_0006
SmokeShield PTC™ actionair
Control Mode Details Continued

Control Mode 5 - 3P PTC Control Monitoring Station


M5-3P 24V and M5-3P 230V
CMS Control Stations

.!.- ', 4 ..f',...


~~II!:·•.

M5-3P-CMS M5 - 3P - CMS (230V)

The M5-3P CMS (Control Monitoring


Station) this control unit gives the user the
Control Mode 5 - 3P PTC with additional As with all PTC modes, this series uses opportunity to set a control position using
facility for third (Control) Position. the snaplock™ interface. Fire rated an integral potentiometer, or use an
150 seconds Reset, 20 seconds dampers are primarily designed to be externally supplied control voltage. It
Release. fitted into a wall or floor, and the interface provides visual (lamp) and volt free (relay)
This 3 position control mode allows a displaces the mode from the line of the indication of damper position (Released, at
damper to be moved to both the reset wall. Dampers may be installed and then Control Position, Reset). A terminal is
and release position, with the additional the mode removed from storage for easy provided to allow feedback of the
facility to move the damper to a third fitting, thus preventing damage to the 2-1 OV DC monitoring voltage. In addition, a
control position. The mode is given a mode before it is required. End switches, fire alarm input may be made (NC) which
2 - 1OV DC signal, defining the control LSF cable, and Electro Thermal Release will cause the damper to Release if the
position of the blades. (ETR) are provided as standard (not fitted contact is broken. A second input is
A return signal of 2-1 OV DC is provided to on VentShield). available to cause the damper to fully Reset
allow monitoring of position. Versions are available to allow fail-safe to allow full air flow for smoke venting as an
To support this actuator and allow close for fire safety or fail-safe open for example. The fire alarm Release input takes
positioning to be set local to the damper, smoke venting. precedence. Switches are provided that
Actionair have the M5-3P 24V and M5- allow the unit to be driven to Release or
3P 230V control units. Reset positions for testing purposes.
SmokeShield and VentShield
M5-3P PTC 24V 7/2W (1 OVA) end switches SPOT 250V 6(3)A SmokeShield Thermal Release I Power Off - Fail-safe Close 2-10V Set Position
M5-3P PTC NON ETR 24V 7/2W (1 OVA) end switches SPOT 250V 6(3)A SmokeShield Power Off - Fail-safe Close 2-10V Set Position
M5-3P PTC Vent 24V 7/2W (1 OVA) end switches SPOT 250V 6(3)A VentShield Thermal Release I Power Off - Fail-safe Open 2-10V Set Position
M5-3P PTC Vent NON ETR 24V 7/2W (1 OVA) end switches SPOT 250V 6(3)A VentShield Power Off - Fail-safe Open 2-10V Set Position

SmokeShield Control Modes M5 -3P PTC are supplied with the Electrical Thermal Release (ETR) (Not fitted to VentShield).
The units Fail-safe by means of the unique and patented ETR device which operates at 72 °C, or if the power supply is
off/interrupted. Complying with BS 9999: 2008 (Ref 33.4.5.3) Non ETR versions Fail-safe when the power is off/interrupted.

Control Mode 5 - 2P PTC and Control Mode 6 - 2P PTC Drive Open I Drive Closed. 60 seconds
operation
This 2 position control mode has been
developed to provide drive open I drive
closed damper operation. These modes do
not have ETRs.
As with all PTC actuators, this series uses
the snaplock™ interface. All modes have
LSF cables.

SmokeShield and VentShield


M5-2P PTC 24V 12W (18VA), end switches SPOT 250V 6(3)A
M6-2P PTC 230V SW (15VA), end switches SPOT 250V 6(3)A

www.actionair.co.uk 7
INQ00015166/7
INQ00015166_0007
actionair SmokeShield PTC™

Application and Wiring - Smoke (with ETR)

0---GREEN/
SmokeShield YELLOW ___L_
--
Mode 1 PTC (Manual System) VOLT FREE CONTACT
r---BROWN COMMON
Manual opening.
Spring instant closure via mechanical
v--- BLUE NORMALLY CLOS ED
]
CLOSED WHEN
DAMPER RESET
(at85 4
RATED 250V 5A
fusible link. 0 - - - BLACK NORMALLY OPEN

(SmokeShield version only, VentShield


not available.) DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

SmokeShield tfi\ BLACK ---A--- 1 SUPPLY


Mode 5 PTC (24V System) AC/DC24V 24V AC or DC
50/ 60 Hz ~W~TE~ 2 + TYPICALLY 1OW (MOTORING)
The following applies for ETR version. 2W (RESET)
(ETR not supplied on VentShield.)

Supply On - Damper motors reset.


1 VOLT FREE
Supply Off - Spring release. 2 CONTACT MADE BETWEEN
1 AND 2 WHEN DAMPER
Electrical Thermal Release.
3 FULLY RELEASED
External mechanical position indicator with
pointer. AC 4 VOLT FREE
Release Time "' 22 sees. 12.5 VA 250V
CONTACT MADE BETWEEN
Reset Time "' 60 sees. 10/2W 6(3)A 5 4 AND 6 WHEN DAMPER
FULLY RESET
(Connect 24V via a safety isolating lmax 6
transformer.) 8.3A@5ms

IP54 Rated.
ELECTRICAL THERMAL RELEASE

Trnc~ (MUST BE FITTED TO DUCTING

J------l~)l---1-. .
FOR DAMPER OPERATION). NON
-30... +50C ETR VERSION AVAILABLE ON
CONTINUOUS REQUEST
I-·
(SPRING BIASED TEST SWITCH)

DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

SmokeShield
AC230V
di\ BLUE ---A--- N SUPPLY
230V AC 50/60 Hz
Mode 6 PTC (230V System)
50/ 60 Hz ~BROWN~ L1 TYPICALLY12W (MOTORING)
4W (RESET
The following applies for ETR version.
(ETR not supplied on VentShield.)

Supply On - Damper motors reset. 1 VOLT FREE


Supply Off - Spring release. 2 CONTACT MADE BETWEEN
1 AND 2 WHEN DAMPER
Electrical Thermal Release.
3 FULLY RELEASED
External mechanical position indicator
with pointer. 4 VOLT FREE
Release Time "' 22 sees. 14VA
AC CONTACT MADE BETWEEN
Reset Time "' 60 sees. 12/4W 5
250V 4 AND 6 WHEN DAMPER
6(3)A FULLY RESET
(To isolate from main power supply, the system 6
must incorporate a device which disconnects
the phase conductors, with a least 3mm
contact gap.) ELECTRICAL THERMAL RELEASE
-30 ... +50C (MUST BE FITTED FITTED TO
Trnc!

J,_ _ ,------<~,.__-1-
Note: 120V A.C. version also available. CONTINUOUS DUCTING FOR DAMPER
OPERATION). NON ETR VERSION
IP54 Rated. AVAILABLE ON REQUEST
(SPRING BIASED TEST SWITCH)

DIAGRAM SHOWS ACTUATOR IN FULLY RELEASED STATE

8 www.actionair.co.uk
INQ00015166/8
INQ00015166_0008
SmokeShield PTC™ actionair
Application and Wiring - VentShield PTC™ Dampers and
associated Control Modes M5 and M6
Vent (or Smoke Non-ETR) are reverse action with spring opening.

VentShield Mode 5 (24V System)


~BLACK ~ 1 - SUPPLY
Supply On - Damper motors reset. AC/DC24V 24V AC or DC
Supply Off - Spring release. 50/60 Hz
~WHITE ----<~>-!------ 2 +
(Connect via a safety
isolating transformer)
Cable specification:
12.5VA
Si HF Low Smoke and Fume, Halogen
Free, to IEC 754-1. Conforming to
10/2W 1 VOLT FREE CONTACT
CLOSED WHEN
73/23/EEC directive.
2 DAMPER RELEASED
lmax
Release Time "' 22 sees.
8.3A@5ms
Reset Time "' 60 sees. 3 VOLT FREE CONTACT
AC
(Connect 24V via a safety isolating CLOSED WHEN
-30 ... +50C 250V
6(3)A 4 DAMPER RESET
transformer.) CONTINUOUS

IP54 Rated

VentShield Mode 6 (230V System)


AC 230V [Q]

~
Supply On - Damper motors reset. LBLUE N
50/60 Hz SUPPLY
Supply Off - Spring release. 230V AC 50/60 Hz
Cable specification:
BROWN L1
Si HF Low Smoke and Fume, Halogen 14VA
12/4W
Free, to IEC 754-1. Conforming to
73/23/EEC directive.
1 VOLT FR EE CONT ACT

Release Time "' 22 sees.


Reset Time "' 60 sees.
1~-
~
2
CLOSED WHEN
DAMPER RELEASED

[Q]
(To isolate from main power supply, the system must 3 VOLT FREE CONTACT
incorporate a device which disconnects the phase AC
-30 ... +50C CLOSED WHEN
conductors, with a least 3mm contact gap.) 250V
CONTINUOUS
6(3)A 4 DAMPER RESET
Note: 120V A.C. version also available.

IP54 Rated

General (Electrical) Smoke Shield or Vent Shield Mode 9


PTC (Pneumatic Operation)
One metre of halogen free low smoke and Control Modes 5 and 6 are available
fume electric cable is also included with without the ETR where thermal operation
Control Modes 1, 5 and 6 for is not required. (This would not comply
convenience of on site wiring. This also with BS 9999: 2008).
provides the distinct safety advantage of
all electrics terminating outside the duct,
eliminating potential in-duct fire hazards
from wiring faults.

(Prewired Connection boxes available as


factory fitted option.)
Air On - Damper resets.
The Electrical Thermal Release is pre- Air Off - Spring release.
wired with 0.5m halogen free low smoke Release time "' 2 - 4 sees.
and fume cable on Control Modes 5 and Reset time "' 2 - 4 sees.
6. (Not supplied on VentShield). Air inlet - 6mm dia. quick fit coupling.
74 °C Pneumatic Thermal Link (PTR).
A Manual test switch fitted on the ETR (PTR not supplied on VentShield.)
allows periodic operation of damper Air pressure "'5.5 - 8.0 bar.
simulating actual fail-safe release under Air consumption to reset @ 5.5 bar -
smoke/fire conditions. 535CC.
External mechanical position indicator.
Test operation by removing fusible link
element.

www.actionair.co.uk 9
INQ00015166/9
INQ00015166_0009
actionair SmokeShield PTC™

Damper Installation and Control Mode Fitting

Step 1

Install the SmokeShield PTC™ Automatic Smoke and Fire


Dampers (complete with transit plate) into the structure. Refer
to the Actionair Approved Fire and Smoke Dampers Installation
Manual.

(Care must be taken when back filling to ensure that the


sncplock™ retaining pin location hole and the entry slot of the
damper drive shroud is clear of builders work debris).

Right Hand
Damper
Shown

Step 2

Slide the sncplock™ Drive Interface into the damper drive


shroud, 'sncplock™' into position.

The 'sncplock™' feature provides a user friendly, easy and secure


direct connection. It comes pre-set to enable direct fit to
SmokeNentShield damper.

Control
Mode 5/6
shown

Step 3 For Control Modes with Electrical Thermal


Releases.

Identify location for the Thermal Release. Ideally, this


should be fitted to the top half of the duct, adjacent to
the control mode. Fit the self adhesive drilling template
(supplied) in this position. Drill holes as detailed on the
template. Using the 2 fixing screws provided, secure
the Electrical Thermal Release to the duct. Connect
electrically, and test operation.

As a safety feature the actuator will only operate if


the ETR is correctly fitted to the duct.

1o www.actionair.co.uk
INQ00015166/10
INQ00015166_0010
SmokeShield PTC™ actionair

Damper Installation and Control Mode Fitting Continued

Step 3 (Control Mode 1) SmokeShield only Step 3 (Control Mode 9)

SMOKE/SHIELD MECHANICAL SMOKE/SHI ELD FLOW AIR SUPPLY


DAMPER FUSIBLE LINK DAMPER RESTRICTOR INLET

315 ± 20mm

BOWDEN CABLE

l--5mm
E
E _...__.._,--=-'
OJ
0 o-----~

C0
0

40 ± *75mm

135mm
4mm NYLON PNEUMATIC
*This dimension will vary on Circular TUBING THERMAL
Damper. Select dimension to give 500mm RELEASE
smoothest radius on bowden cable. LENGTH

Mark the Fusible Link position on the duct as dimensioned in the 1. Select position for PTR. (SmokeShield only). Ideally this
diagram above. should be in the top half of the duct and sufficiently close to
the actuator to allow easy connection of the 4mm diameter
Fit the self adhesive drilling template (supplied) in this position. nylon tube supplied.
Drill holes as detailed on template. Using the 2 fixing screws
provided, secure the Fusible Link to the duct. Reset Damper 2. Drill hole in selected position using a 30mm diameter hole
using a 14mm A/F spanner, clockwise 1/4 turn. Test unit by cutter, removing any sharp edges.
simply unscrewing wing nut - Damper releases. For ductless
installations a suitable sized plate or bracket must be fitted to the 3. Position PTR and drill the 4 off 3mm diameter fixing holes.
installation to allow the fitting of the Fusible Link.
4. Remove PTR and apply approved fire retardant sealant on
As a safety feature the Control Mode will only operate if the the duct around the hole.
Fusible Link is correctly fitted to the duct.
5. Refit PTR and secure with the 4 off Pozi head screws
provided.

6. Connect 4mm diameter tube to actuator and PTR.

7. Connect 6mm diameter tube to input side of PTR.

8. Connect air supply. Damper opens fully.

9. Test operation.

www.actionair.co.uk 11
INQ00015166/11
INQ00015166_0011
actionair SmokeShield PTC™

Installation Methods, Classification and Test Report Summary

DWFX™ (DRY WALL FIX) DWFX-F Flange+ Cleats DWFX-F Flange + Cleats DWFX-C Dry Wall - Cleats
Installation System Dry Wall Masonry Wall
Typically for installation into
Dry Wall, Stud Partitions.
HEVAC I HVCA Galvanised
Steel Installation Frames
Typically for installation into
Blockwork, Concrete walls
and floors.

S&A Sleeve and Angle


Installation System.
Typically used to fill voids
around dampers to complete
a penetration seal.

Classification Classification Classification


El20, ESl20 El20, ESl20 El20, ESl20

BSEN 1366-2 Test I BSEN 1366-2 Test I BSEN 1366-2 Test I


Assessment Assessment Assessment
BRE 256493 BRECC 270714A BRE 231741

S&A Sleeve and Angle + S&A Sleeve and Angle + S&A Sleeve and Angle Dry S&A Sleeve and Angle
BATT + Dry Wall BATT + Masonry Wall Wall Masonry Wall

Classification Classification Classification Classification


El20, ESl20 El20, ESl20 El20, ESl20 El20, ESl20

BSEN 1366-2 Test I BSEN 1366-2 Test I BSEN 1366-2 Test I BSEN 1366-2 Test I
Assessment Assessment Assessment Assessment
BRE 267924 BRECC 270714A BRECC 270714A BRECC 270714C

12 www.actionair.co.uk
INQ00015166/12
INQ00015166_0012
SmokeShield PTC™ actionair

HEVAC I HVCA Installation HEVAC I HVCA Installation S & A Sleeve and Angle
Frame Vertical Frame Horizontal + BATT Horizontal

Classification Classification Classification


E240, ESl20 E240, ES240 El20, ES90

BSEN 1366-2 Test I BSEN 1366-2 Test I BRE 275926 Test I


Assessment Assessment Assessment
BRE 259933 BRE 231740 BRE 275926

Approved Installations
The Actionair Approved Fire and Smoke
Dampers Installation manual is available
for free download, along with OW 145
check sheets, on our web site.
Building and Local Authority control,
cannot refuse these tested methods.

www.actionair.co.uk 13
INQ00015166/13
INQ00015166_0013
actionair SmokeShield PTC™

A range of indicator panels, push button switches and


Accessories damper test units are also available. The housing for
these units are manufactured in rigid ABS plastic.
Electrical The Damper Connection Box is in galvanised steel.

DTU24 24V AC/DC


Damper Test Unit
Reset and release indication.
DTU120 120V AC
Spring bias (power OFF) test switch.
Power normally ON.
DTU230 230V AC

DSl24 24V AC/DC

Damper Status Indicator


DSll20 120V AC
Reset and release indication.
DSl230 230V AC

DCU24 24V AC/DC

Damper Control Unit


Switch ON/OFF function. 120V AC
Reset and release indication.
DCU230 230V AC

Damper Release and Indication prior to installation and connection LED position and operation
Module (DRIM) of actuator and supply. indication is provided.
This is designed for control and The DRIM may be used singly to Operation is by push button to
monitoring of the electrically operated provide local damper control, or close and twist to re-open
Smoke Shield PTC™ Fire and Smoke in pairs to provide control from damper.
dampers. either side of a damper. It can Tested to BS EN 6IOIO - I: 2001
It will operate from 24V, I 20V or 230V also operate 2 actuators when and is CE compliant.
supplies, 50 or 60 Hz. dampers are provided in 2 IP44 rated.
Selection of the operating voltage is multiple sections. Operating range 5 - 40 °c.
by use of internal links on the PCB,

DRIM 24V - 230V AC/DC

M5 and M6 - 2P Damper Control Unit M52PDCU 24V AC/DC


Switch power open/power close. Open
and closed indication. M62PDCU 230V AC

Damper Connection Box DCB 24V - 230V AC/DC


(All Voltages).

M53PCMS 24V AC/DC


M5 - 3P - CMS Control Unit

230V M53PCMS 230V AC


230V M5 - 3P - CMS Control Unit

Pneumatic

Solenoid, (24\1, 120\1, or 230V). EEXD Solenoid, (24\1, 24 - 230V AC/DC


120\1, or 230V). Damper Status Beacon. Switch box and
Status Beacon. Zone 2 Switchbox and Status Beacon.

14 www.actionair.co.uk
INQ00015166/14
INQ00015166_0014
SmokeShield PTC™ actionair
Control Mode Dimensions and Orientation
Mode 1 (SmokeShield only)
SmokeShield PTC™ Control Modes are located
outside of the ductwork for ease of access and
installation.
INPUT
SHAFT Mn
~=r"\IL-1_;_0 I§
IT_J4

Snaplock
RETAINING PIN
LOCATION HOLE

Modes 5 and 6 Three position 180° (Pivotable


84
Control Mode) - 260
SmokeShield PTC™ Control Modes are located 54-
outside of the ductwork for ease of access and
I
installation.
I -· 1 I Position 3
Control Modes 5 and 6 can be fitted in any one of
three orientations i.e. - 28 II
I
II

Vertically down (Position 1)


Horizontally (Position 2), or
Vertically up (Position 3).
This can be simply and easily carried out on site,
- ! 0
Po~iti~n :.J
- -
1

--

by repositioning the Location Plate (see page 2) Position 1


and Control Mode on to the snaplock™ Drive -
25r~::
Interface. 12 100
This flexibility ensures that the damper and control 56
mode require the minimal amount of room. 109 112
(Supplied in position 2 as standard.)

143
Mode 9 Pneumatic Control
SmokeShield PTC™ Control Modes are located
outside of the ductwork for ease of access and
installation.

Hytock - 71 (ATEX) Hytock - 71 (ATEX)


Aluminium Switch Box Polycarbonate Switch Box

L{)
L{) 0
GJ
C'l
GJ

a a

n
[!]
[!] I
I 0
0 f-
f- :;;:
:;;:
(f)
(f)

+
O<'.
a:
0
I;::
I

www.actionair.co.uk 15
INQ00015166/15
INQ00015166_0015
actionair SmokeShield PTC™

Dimensional Data
For Rectangular Dampers spigots are 5mm under duct size. Please refer to the Actionair Approved Fire and Smoke Dampers
* Widths and heights available in I mm increments. Installation Manual.

Base Dampers Dampers with Installation Systems


Dampers with DWFX-F HEVAC I HVCA IF Dampers with S&A

Rectangular Dampers Series 501 and 1501 OVERALL FLANGE OVERALL WIDTH OF OVERALL FLANGE WIDTH
WIDTH IS 398mm INSTALLATION IS 398mm
For Ducts with widths of 100-150mm* For Ducts with heights OVERALL FLANGE FRAME IS 314mm OVERALL FLANGE HEIGHT
of 100 -150mm* HEIGHT IS 395mm OVERALL HEIGHT OF IS 395mm
INSTALLATION
FRAME IS 340mm

I~ 100-150 ~
---150r-
:'_'_l__ I DUCT WIDTH I ~g---- r
550 .....-~~~~~~~--.

J
0
co

200

For Ducts with widths of 151 -199mm* For Ducts with heights OVERALL FLANGE OVERALL WIDTH OF OVERALL FLANGE WIDTH
of 151 -199mm* WIDTH IS 448mm INSTALLATION IS 448mm
OVERALL FLANGE FRAME IS 364mm OVERALL FLANGE HEIGHT
HEIGHT IS 445mm OVERALL HEIGHT OF IS 445mm
INSTALLATION
FRAME IS 390mm

~25

l
151 -199

DUCT WIDTH

~~~
J
l+----2-5-0------+l~j "' l,J"'I"' l,J,,1

For Ducts with widths and heights of 200-1000mm* OVERALL FLANGE WIDTH OVERALL WIDTH OF OVERALL FLANGE WIDTH
DUCT WIDTH+ 198mm INSTALLATION FRAME DUCT WIDTH+ 198mm
OVERALL FLANGE HEIGHT DUCT WIDTH+ 114mm OVERALL FLANGE HEIGHT
DUCT HEIGHT+ 195mm OVERALL HEIGHT OF +DUCT HEIGHT+ 195mm
INSTALLATION FRAME
DUCT HEIGHT+ 140mm

200 -1000

r
~
"1 DUCT WIDTH '5

]
f-
I
0
~ 0
w ;'
I
f- 0
0 0
N
::i
0

~
0
co

U"' I,
16 www.actionair.co.uk
INQ00015166/16
INQ00015166_0016
SmokeShield PTC™ actionair
For Circular and Flat Oval Dampers spigots are 3mm under For Installation Details Please refer to the Actionair Approved
duct size. *Diameters and flat oval diameters in I mm Fire and Smoke Damper Installation Manual.
increments.

Base Dampers Dampers with Installation Systems


Dampers with DWFX-F HEVAC I HVCA IF Dampers with S&A
OVERALL FLANGE WIDTH IS 398 OVERALL WIDTH OF INSTALLATION OVERALL FLANGE WIDTH =
Circular Dampers Series 601 and 1601 OVERALL FLANGE HEIGHT IS 395mm FRAME IS 314mm 448mm
1 mm Increments* OVERALL HEIGHT OF INSTALLATION OVERALL FLANGE HEIGHT=
FRAME IS 340mm 445mm

1 mm Increments* OVERALL FLANGE WIDTH IS 448mm OVERALL WIDTH OF INSTALLATION OVERALL FLANGE WIDTH=
OVERALL FLANGE HEIGHT IS 445mm FRAME IS 364mm 448mm
OVERALL HEIGHT OF INSTALLATION OVERALL FLANGE HEIGHT=
FRAME IS 390mm 445mm
DUCT DIA.
151 - 199*
---1=
__'L_

0,
°'
~

~
~
§
1 mm Increments* OVERALL FLANGE WIDTH= OVERALL WIDTH OF INSTALLATION FRAME OVERALL FLANGE WIDTH=
DUCT DIA+ 248mm =DUCT DIA+ 114mm DUCT DIA T 248mm
OVERALL FLANGE HEIGHT= OVERALL HEIGHT OF INSTALLATION FRAME OVERALL FLANGE HEIGHT=
DUCT DIA+ 245mm =DUCT DIA+ 190mm DUCT DIA+ 245mm

~I ~I DUCTDIA.+50 I~
(FOR DUCT DIA 951 - 1000mm
DUCT DIA+ 30mm)

Flat Oval Dampers Series 701 and 1701 OVERALL FLANGE WIDTH
DUCT WIDTH+ 248mm
OVERALL WIDTH OF INSTALLATION FRAME
DUCT WIDTH +114mm
OVERALL FLANGE WIDTH=
DUCT DIA T 248mm
1 mm Increments* OVERAL FLANGE HEIGHT OVERALL HEIGHT OF INSTALLATION FRAME OVERALL FLANGE HEIGHT=
DUCT HEIGHT+ 245mm DUCT HEIGHT+ 190mm DUCT DIA+ 245mm

50 _l~~D-U_C_T_W_l_D-TH~*~~~
,...1
300 - 950*

L!)
I'-

DUCT WIDTH.+ 50mm*


(FOR DUCT WIDTH 951 - 1000mm
DUCT WIDTH + 30mm)

www.actionair.co.uk 17
INQ00015166/17
INQ00015166_0017
actionair SmokeShield PTC™

DWFX-C Dimensional Data

--150 r--

Acoustic Data Pressure Drop Vs Velocity


The data presented is from the Graph 1 100
90
Laboratory Determination of Acoustic and
80
Aerodynamic Performance of 70
SmokeShield PTC Automatic Smoke and 60
Fire Control Dampers. 50 /J
A programme of extensive tests was 40
II
carried out in the Reverberation Chamber
and North Transmission Chamber of 30 ~
Sound research Laboratories Limited,
Holbrook Hall, Sudbury, Suffolk, generally I 'l
20
ro
~~
in accordance with BRITISH STANDARDS
Nos. 4196, 4773, 4856, 4857 and 4954. e:.
a. :;; .?
This independent test facility is approved
under the NAMAS Scheme.
From the selection of a duct velocity
0
a:
Cl
w
10
,,...If

I ' 'l !
a: II
within the operational parameters of the ::J l
en l
damper a resultant pressure drop from en
w II
Graph I can be determined and the sum a:
a.
of these two components applied to the 1/
Velocity x Pressure Drop Vs Sound Power
Level Graph. (Graph 2) /J
II
The graph is the result of a full
range of acoustic tests on SmokeShield

//
PTC™ Automatic Smoke and Fire Control
Dampers with the blades set in their fully
open position.
The Spectrum Correction Data is applied
5 6 7 8 9 10 15
to the number obtained from the graph
and a complete Sound Spectrum of Flow VELOCITY (m/s)
Generated Noise for both Outlet (in duct)
and Breakout (casing radiated) can be Example: From Sound Power Graph (Graph 2) plot
obtained from Table I. 168 on horizontal Velocity/Pressure axis
Duct with a design velocity of 8 m/sec.
SmokeShield PTC Damper Series 501 against 501 outlet (induct) graph to obtain
fully open. 47 dBW on Vertical Sound Power Level
Axis. Add or subtract corrections to the
Pressure Drop= 21 Pa (Graph I).
47 dBW to provide full spectrum analysis
Multiply Velocity x Pressure Drop
using appropriate Correction Table.
8 x 21 = 168.

18 www.actionair.co.uk
INQ00015166/18
INQ00015166_0018
SmokeShield PTC™ actionair

Velocity (m/s) X Pressure Drop (Pa) Vs Damper Leakage


Sound Power Level (dBW)
Graph 3
Graph 2
SmokeShield PTC™ and VentShield
PTC™ closed blade leakage as tested on
90
a damper 1000mm wide x 1000mm high.

Leakage data at Ambient temperature (Cold Smoke).


,/~
80 , 1500

A /
/
,;
/
/,I
,I
;;
;~

1200
I
70

~ ~'
~
~ ;~ 1000

§' 60
'~~;
c)
;~
0 /
:;,~"'·
p~
~,I
;;

;'
~
ea-
e::. I
~~
~() a:
v
[£l
::l w
~
~ ~
~~ /,I a.
j
~
...J
~
w
/ / <(
>
/v
~ / I

---v
w 50 Cl
...J
EXAMI LE L NE II"" ;
- - - - - - - - - - - - --
;~ Cl 500
a: w
w
s: v
;/
,;~
;
en
0 I
.,v v / '
...J
0 40
a. v ()
/~~ : en
~v v I
Cl en
I
/. ~
z 'fl)~ 0
::J a: 300 I
0 30 ()
en ;~w p:S·

~
I~
/ <(
250
II~ ...J

20
/'
~
~/ Iii;
;~ <ll~ '
·~" :
<(
i=
z
w
200
I
I
/ /
' a:
w

~/
' u.. 150
'
u..
10
/ :
'
Ci
w
a: 120
I
0
'
:
80 88888888
::J
en
en
w
a:
100 I
I
C\I
00000000
C')-tj-L()CDr'--aJGO
a.

VELOCITY X PRESSURE DROP (m/s Pa) 70 I


Correction Tables I
Table 1 50
5
I 10 20 30 40 50 100
SmokeShield PTC™ Outlet (Induct) Spectrum Corrections
Octave Band Hz 63 125 250 500 1k 2k 4k Bk LEAKAGE (l/s)
Series 501 dB 5 4 5 5 3 1 -3 -5
Series 601 dB 9 4 4 5 3 1 -3 -6 The SmokeShield PTC™ Damper has
been tested in accordance with BS ISO
Table 2 10294-1 and BS EN 1366-2. It achieved
SmokeShield PTC™ Breakout Spectrum Corrections ES classification in accordance with BS
ISO 10294-2:1999. ES classification allows
Octave Band Hz 63 125 250 500 1k 2k 4k Bk
a maximum of 200m 3/ Hr/m2 (corrected to
Series 501 dB 8 11 9 6 -3 -6 -14 -17 20 °C) hot gas leakage throughout the test
at 300 Pa pressure differential across the
Series 601 dB 6 10 8 4 -3 -3 -11 -14
damper.

www.actionair.co.uk 19
INQ00015166/19
INQ00015166_0019
actionair SmokeShield PTC™

Actionpac Damper Control Systems

Electro Mechanical Systems Actionpac LNS3 Intelligent Damper accommodates any last minute
Control and Monitoring System changes to strategy, zones, damper
Actionpac EMS - Standard Control and quantities, references and descriptions
Monitoring System The Actionpac LNS3 system represents a etc and enables standardisation of
new generation of smoke/fire damper software (no bespoke site specific
Control and monitoring of Mode 5 or
control. The system has been designed versions required)
Mode 6 damper actuators in groups of
with the user in mind, providing an
12, 24 or 36.
advanced tool that simplifies installation • Off site system witnessing can be
and commissioning of smoke/fire arranged
Actionpac EMB - Bespoke Control and dampers and peripheral devices. The
Monitoring System Control Panel Panel PC operates on a Windows TM • Open and interoperable protocol
(LonWorks®) allows possible support
The EMB Control Panels typically consists platform making it universally accepted
and utilises solid state technology for by others and future proof lifecycle
of the appropriate number of switches to preventative maintenance costs
optimum reliability.
provide individual or group control, LED
indication for status monitoring and all It's server architecture delivers new • Optional networking of panels to a
necessary relays and timers to comply benefits such as reduced commissioning central control and monitoring panel -
with the customer needs for fully or semi time, simplified operation and scope for up to 32 networked panels to meet
automatic damper operation. The EMB future growth. practically any building's damper
panels are purposely manufactured for requirements
any particular project to suit specific client The Actionpac LNS3 system is designed
to protect life and property from damage • Optional automatic scheduled damper
requirements.
caused by smoke and fire, by providing testing, including omit option for critical
the means to:- dampers

• Compartmentalise fire zones. • Optional remote access via internet

• Reduce the spread of smoke and fire. • System designed to cater for
environmental occupancy (energy
• Keep escape routes and fire-fighting saving) as well as the building's
access open. smoke/fire strategy

• Allow pressurisation and smoke extract


by combined operation of dampers
and fans.

Addressable Systems Benefits



• Actionair experience and know-how in
Actionpac LNS Smart Cost Effective the damper market
Intelligent Damper Control and
Monitoring System • Actionair Smoke/Fire Dampers LPCB
Actionpac Smart for the approved
control I monitoring of up to 36 off • Allows for phased commissioning and
SmokeShield dampers. future expansion
Actionpac 60/120 (LNS 60/120)
Intelligent Damper Control and
• Backward compatible •
Monitoring System • CE marked, EMC and LVD compliant
Actionpac LNS 60 for the • Customer testimonials available
control I monitoring of up to 60 off
SmokeShield dampers. • Hundreds of prestigious reference sites
Actionpac LNS3 Intelligent Damper
Actionpac LNS 120 for the
• Powerful and very flexible functionality Control and Monitoring System
control I monitoring of up to 120 off
SmokeShield dampers.

Fully comprehensive
brochures are available on
all Actionpac products.
Visit the Actionair website
w.w.w.actionair.co.uk and
download the relevant pdf.

'!l~i! ir
-~~r'

20 www.actionair.co.uk
INQ00015166/20
INQ00015166_0020
SmokeShield PTC™ actionair
Typical Network Schematic

General Schematic of Actionpac LNS3 Damper Control System

To additional To additional
devices as required devices as required

~ Smoke Fire Damper Interface


L..:..:_J One per Control Mode

CSS Smoke ES Rated


Fire Damper

24/230 volt 3PSFDI SDI 24/230 volt


(local power ...___ _ _____. (local power
by others) Smoke Shaft Ventilation by others)
System Series SSV

~ Damper Control Mode*

SFDI
a Nll404
Network Digital Input I Output
Interface - provides up to four
inputs I outputs
SFDI 24/230 volt
(local power
24/230 volt ~ 3 Position Smoke/Fire
~ Damper Interface by others)
(local power ~---~
by others) one per Control Mode

ls;-1
Smoke damper Interface
~ one per Control Mode

One SFDI, SDI or 3PFSDI is required


per Damper/Section.
Supply to each Damper Interface from 24/230 volt
nearest local distribution board. (local power
by others)
24/230 volt SDI
(local power ~---~ Outp1 .;
by others)

SFDI 24/230 volt 24/230 volt


(local power (local power
by others) by others)

Inputs

1111

Panel Router(s)

Vent Panel

B.M.S.
.....• (fJ
~
D...
••••• • I-5
• ~
~
z
•.....
•····· Fire Alarm Inputs
BMS Inputs

• •••••• Fireman's Switch Inputs

---• • Panel PC to Panel PC


Cable (Cat 5e)
r=: - To additional
Panel PCs
as required

www.actionair.co.uk 21
INQ00015166/21
INQ00015166_0021
actionair SmokeShield PTC™

Customer Service Approvals

Actionair provides quality products Approved by LPCB for use in up to 4 Seismic Qualification
backed by a dedicated team committed hour constructions.
SS501 PTC, have been subjected to
to providing the very best in customer Refer to the Actionair Approved Fire and
triaxial seismic qualification tests in
service. Smoke Dampers Installation Manual.
accordance with BNFL Technical Services
Offering experienced technical backup, The SmokeShield PTC™ Damper tested Report ET 372 Schedule No. Twelve, to
comprehensive sales and administrative and assessed to the levels detailed in Costain Document
customer support, product BS ISO I 0294-1 , 6733-0250-064-10-0020, Rev C,
commissioning and maintenance service. BS EN 1366-2 and Specification for Diesel Generator and
BS 476 pt. 20. It achieved ES Load Bank. The testing was also in
classification in accordance with general accordance with IEEE 344-2004
BS ISO !0294-2:1999. IEEE Recommended Practice for Seismic
Qualification of Class I E Equipment for
Maintenance Low gas/smoke and fire integrity to
Classification ES in vertical and horizontal
Nuclear Power Generating Stations -
Time History Method.
The SmokeShield PTC™ Dampers test installations.
are designed for applications in
normal dry filtered air systems and An LPCB approved product, compliant to
should be subjected to a planned the new Loss Prevention Council Design
inspection programme, with cleaning Guide for Fire Protection of Buildings.
Quality Assurance
and light oil lubrication in Fire tested in vertical and horizontal
accordance with BS9999. When applications under dynamic conditions by
exposed to fresh air intakes and/or The Loss Prevention Council.
inclement conditions this may need
to be performed more regularly Corrosion tested to BS EN 60068-2-52:
based on experience gained from 1996 to satisfy the requirements within
LPS H G2 Cert No. 017a
previous inspections. LPS 1162.
Complies with the latest OW 144 casing
leakage specification.
The Electrical Control Modes satisfy
requirements of the following standard(s)
As ~seo to- 1so 5!001 : 2000
or other normative documents, EN 6100- LPCB Cert No. 11

6-2 I EN 6100-6-3 I EN60730- I I EN


60730-2-14 following the provision of
Directive 2004/108/EG, 2006/95/EG.

Approximate Weights (Kg)


Square or Circular 100 150 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000
Duct Size (mm)
Series 501 Square 3.4 3.4 3.4 4.2 4.8 5.6 6.5 7.4 8.6 9.6 I0.8 12.4 13.6 14.9 16.2 17.7 19.2 20.8 23.5
Series 501 Square + l/F 6.2 6.2 6.2 7.4 8.7 I0.3 11.9 13.2 14.6 16.3 18.5 20.5 22.1 24.0 25.9 28.1 30.3 32.4 34.5
Series 601 Circular 5.3 5.3 5.3 6.1 7.2 8.4 9.6 11.2 12.6 14.0 15.9 17.5 19.1 20.7 22.5 24.3 26.2 29.3 32.1
Series 601 Circular+ l/F 8.5 8.5 8.5 IO.O 11.9 13.7 15.4 17.1 19.2 21.8 24.0 26.0 28.2 30.4 32.8 35.3 37.8 40.3 43.1

Control Mode 1 (SmokeShield only) (including drive interface) 4.1 Kg


Control Modes 5, 5 - 3P, 5 - 2P, 6, 6 - 2P and 9 (including drive interface) 4.4Kg

The information contained herein is subject to change


without notice due to continuing research and
development.

22 www.actionair.co.uk
INQ00015166/22
INQ00015166_0022
SmokeShield PTC™ actionair

Ordering Information
Example

Quantity Series Fixing Options Duct Size Control Mode Accessories


3 SS501/PTC IF 6000/V) x 450(H) M5

Number of SS 501 /PTC 1. DWFX-F M1 PTC Electrical


units required SmokeShield PTC™ Dry Wall Fixing System Manual System
1. DTU
Square or Rectangular Flange plus Cleats Damper Test Unit
(Fail-safe closed) M5 PTC
Damper Test Unit For Control
2. DWFX-C 24V IOW (12.5VA)
Modes. Spring bias test
Dry Wall Fixing System switch providing illuminated
SS601/PTC Cleats M6 PTC
SmokeShield PTC™ reset and release status
230V 12W (14VA)
Circular 3. IF HEVAC I HVCA 2. DSI
(Fail-safe closed) Installation Frame M5 PTC Vent NON ETR Damper Status Indicator
24V IOW (12.5VA) Reset and Release Indication
4. Sleeve plus Angle 3. DCU
SS701/PTC
M6 PTC Vent NON ETR Damper Control Unit
SmokeShield PTC™
5. Other Special 230V 12W (14VA) Damper Control Unit for
Flat Oval
(Fail-safe closed) Fixings Control Modes. Switch
M5 PTC NON ETR ON/OFF function, reset and
24V IOW (12.5VA) release indication
VS1501/PTC
M6 PTC NON ETR 4. DRIM
VentShield PTC™
230V 12W (14VA) Damper Release and
Square or Rectangular
Indication Module
(Fail-safe open)
M5 PTC Vent 5. M52PDCU I M62PDCU
24V IOW (12.5VA) Switch Power Open/Power
VS1601/PTC Close. Open and Closed
VentShield PTC™ M6 PTC Vent Indication
Circular 230V 12W (14VA)
(Fail-safe open) 6. DCB
M5-2P ON/OFF Connection Box
24V 7W (I OVA) For Control Modes I , 5 and 6
VS1701/PTC (see page I O for above)
VentShield PTC™ M6-2P ON/OFF
Flat Oval 230V SW (12.5VA) 7. M5 - 3P - CMS
(Fail-safe open) Control Unit
M5-3P PTC
24V 7W (I OVA) 8. 230V M5 - 3P - CMS
Control Unit
M5-3P PTC Vent NON ETR
24V 7W (I OVA) Pneumatic
24 Volt Solenoid, (24, 120, or
M5-3P PTC NON ETR 230 Volt).
24V 7W (I OVA) Status Beacon, Switchbox
and Status Beacon.
M5-3P PTC Vent PTR XNNN05017
24V 7W (I OVA)
Mechanical
M9 PTC
Pneumatic Operation snaplock™ Interface Locking
Plate (See page I 0)
M9 PTC Vent NON PTR
Pneumatic Operation Actionpac Damper
Control Systems
SCHISCHEK Electrical (See page 20 and 21)
ATEX

www.actionair.co.uk 23
INQ00015166/23
INQ00015166_0023
Ruskin Air Management Limited
is a ISO 9001 and 14001 registered
company.
The statements made in this brochure or by our
representatives in consequence of any enquiries
arising out of this document are given for information
purposes only. They are not intended to have any
legal effect and the company is not to be regarded
as bound thereby. The company will only accept
obligations which are expressly negotiated for and
agreed and incorporated into a written agreement
made with its customers.

Due to a policy of continuous product development


the specification and details contained herein are
subject to alteration without prior notice.

Comprehensive and detailed information


is available for all Actionair products.
Visit our website at www.actionair.co.uk