TCL & MD Table - 1 Phase
TCL & MD Table - 1 Phase
1 CONNECTED LOAD 1 = LOAD ESTIMATION (W) X QUANTITY / (230V X 0.85PF) = _________ AMP
2 TOTAL CONNECTED LOAD = CONNECTED LOAD 1 + CONNECTED LOAD 2 + …...…. = _________ AMP
3 MAXIMUM DEMAND = TOTAL CONNECTED LOAD X DIVERSITY FACTOR = _________ AMP
QUANTITY
DIVERSITY FACTOR 0.80 0.80 0.80 0.80 1.00 1.00 1.00 0.50 0.50 0.50 0.50 0.50
CONNECTED LOAD (AMP) 0.68 0.65 0.53 1.88 3.82 7.67 2.56 1.28 2.56 2.56 7.67 2.56
CONNECTED LOAD (WATT) 133 128 104 367 746 1500 500 250 500 500 1500 500
1 1 X 18W FLUORESCENT 24 2 2 1 3 8
2 2 X 18W FLUORESCENT 48 0
3 3 X 18W FLUORESCENT 72 0
8 BELL 5 1 1
9 AIRCOND 746 1 1
CIRUCIT NO 1 2 3 4 5 6 7 8 9 10 11 12
MAIN SWITCH/MCB
63A
DP
POWER CURRENT 10kA