Automatic Star-Delta Starter Using Timer - Power, Control & Wiring Diagrams
Automatic Star-Delta Starter Using Timer - Power, Control & Wiring Diagrams
ELECTRICAL TECHNOLOGY
Why Do We Need to Install a Starter with a Motor?
Difference between Star and Delta Connections – Comparison Of Y/Δ
ELECTRICAL TECHNOLOGY
Control Diagram
Click image to enlarge
Click
image to enlarge
ELECTRICAL TECHNOLOGY
Automatic Star-Delta (Y-Δ) Starter with Timer for 3-Phase Induction Motor
Ladder Diagram of Y-Δ Starter using PLC
ELECTRICAL TECHNOLOGY
We have published an article that specifically covers the programming of a Star/Delta starter
using a Programmable Logic Controller (PLC). The article includes detailed explanations and
illustrations of the ladder, power, and control circuit diagrams for the setup.
Related Posts:
Starting & Stopping of 3-Phase Motor from More than One Place – Power & Control Diagrams
How to Start & Stop a 3-Phase Motor Using Direct-On-Line (DOL) Starter?
Controlling of 3-Phase Motor from More than Two Places – Power & Control Diagrams
Related Posts
Disadvantages
Starting Torque is also reduced to one-third because the starter reduces the starting current
to one-third of the rated current [as Line voltage is also reduced to 57% (1/√3)].
It requires six leads or terminals for a Delta-connected motor.
For Delta connection, the supply voltage must be the same as the rated motor voltage.
At switching time (from Star to Delta), if the motor does not reach at least 90% of its rated
speed, then the current peak may be equally high as in a Direct ON Line starter( D.O.L), thus
causing harmful effects on the contactor’s contacts, making it unreliable.
We should not use a star-delta starter if the required (application or load) torque is more
than 50% of the three-phase induction motor’s rated torque.
Related Posts:
The starting
current is 33%
of the fullload currentfor a star-delta
starter.
ELECTRICAL TECHNOLOGY