Lab 3 Data
Lab 3 Data
AUTOMATIC
WET BULB ˚C DRY BULB ˚C HUMIDITY
28.7 31.2 82.9%
28.3 31.2 80.5%
28.2 31.3 79.6%
28.4 31.2 81.3%
LASER
WALL 1 22.7 ˚C
WALL 2 23.2 ˚C
WALL 3 22.6 ˚C
WALL 4 24.5 ˚C
@ 0 - 3 minute intervals
Given:
Tdb = 31.1 ˚C
Twb = 27.3˚C
FORMULA:
17.27 x T
( )
T x237.3
Psaturation vapor =0.61078 x e
3.628 kPa
RH = x 100 %
4.518 kPa
RH =80.31 %
3.628 kPa
237.3 x ln ( )
0.61078
T dp=
3.628 kPa
17.27−ln ( )
0.61078
T dp=27.298 ˚ C
1 1
ρ= =
v 0.894 m 3 /kg
3
ρ=1.119kg /m
where:
@ 3 - 6 minute intervals
Given:
Tdb = 30.6 ˚C
Twb = 27.5 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
2.961 kPa
RH = x 100 %
3.476 kPa
RH =85.18 %
2.961 kPa
237.3 x ln ( )
0.61078
T dp=
2.961 kPa
17.27−ln ( )
0.61078
T dp=27.494 ˚ C
1 1
ρ= =
v 0.886 m3 /kg
3
ρ=1.129 kg/m
where:
@ 6 - 9 minute intervals
Given:
Tdb = 30 ˚C
Twb = 27.2 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
RH =86.50 %
2.916 kPa
237.3 x ln ( )
0.61078
T dp=
2.916 kPa
17.27−ln ( )
0.61078
T dp=23.618 ˚ C
1 1
ρ= =
v 0.884 m3 /kg
3
ρ=1.131 kg/m
where:
h=77.23 kJ /kg
@ 9 - 12 minute intervals
Given:
Tdb = 31.5 ˚C
Twb = 27.4 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
2.946 kPa
RH = x 100 %
3.639 kPa
RH =80.96 %
2.946 kPa
237.3 x ln ( )
0.61078
T dp=
2.946 kPa
17.27−ln ( )
0.61078
T dp=23.79 ˚ C
1 1
ρ= =
v 0.889 m3 /kg
3
ρ=1.125 kg/m
where:
h=79.30 kJ /kg
@ 12 - 15 minute intervals
Given:
Tdb = 31 ˚C
Twb = 26.8 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.523 Pa
RH = x 100 %
4.492 kPa
RH =78.42 %
3.523 kPa
237.3 x ln ( )
0.61078
T dp=
3.523 kPa
17.27−ln ( )
0.61078
T dp=26.80 ˚ C
1 1
ρ= =
v 0.893 m3 /kg
3
ρ=1.120 kg/m
where:
1.006 kJ/kg·K = specific heat of dry air
2501 kJ/kg = latent heat of vaporization
1.86 kJ/kg·K = specific heat of water vapor
h=88.50 kJ /kg
@ 15 - 18 minute intervals
Given:
Tdb = 32 ˚C
Twb = 26.5 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.350 Pa
RH = x 100 %
4.755 kPa
RH =70.45 %
3.350 kPa
237.3 x ln ( )
0.61078
T dp=
3.350 kPa
17.27−ln ( )
0.61078
T dp=25.94 ˚ C
1 1
ρ= =
v 0.894 m3 /kg
3
ρ=1.119kg /m
h=86.48 kJ /kg
@ 18 - 21 minute intervals
Given:
Tdb = 30.5 ˚C
Twb = 26 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.361 Pa
RH = x 100 %
4.366 kPa
RH =76.98 %
3.361 kPa
237.3 x ln ( )
0.61078
T dp=
3.361 kPa
17.27−ln ( )
0.61078
T dp=26 ˚ C
1 1
ρ= =
v 0.890 m3 /kg
3
ρ=1.124 kg /m
FOR ENTHALPY (h):
where:
h=85.16 kJ /kg
@ 21 - 24 minute intervals
Given:
Tdb = 31 ˚C
Twb = 27.2 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.307 Pa
RH = x 100 %
4.492 kPa
RH =73.61 %
3.307 kPa
237.3 x ln ( )
0.61078
T dp=
3.307 kPa
17.27−ln ( )
0.61078
T dp=25.72 ˚ C
1 1
ρ= =
v 0.893 m3 /kg
3
ρ=1.120 kg/m
where:
h=90.04 kJ /kg
@ 24 - 27 minute intervals
Given:
Tdb = 30.8 ˚C
Twb = 26.5 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.462 Pa
RH = x 100 %
4.442 kPa
RH =77.94 %
3.462 kPa
237.3 x ln ( )
0.61078
T dp=
3.462 kPa
17.27−ln ( )
0.61078
T dp=30.52 ˚ C
3
ρ=1.122 kg/m
where:
h=87.27 kJ /kg
@ 27 - 30 minute intervals
Given:
Tdb = 32 ˚C
Twb = 26 ˚C
FORMULA:
17.27 x T
( )
T +237.3
Psaturation vapor =0.61078 x e
3.361 Pa
RH = x 100 %
4.755 kPa
RH =70.68 %
3.361 kPa
237.3 x ln ( )
0.61078
T dp=
3.361 kPa
17.27−ln ( )
0.61078
T dp=29.94 ˚ C
1 1
ρ= =
v 0.894 m 3 /kg
3
ρ=1.119kg /m
where:
h=86.73 kJ /kg
According to the ASHRAE standard of Ventilation for Acceptable Indoor Air Quality,
page 3, table 6.1: Minimum Ventilation Rates in Breathing Zone for office buildings, specifically
office space, is 0.3 L/s-m2.
( )( )( )
3
kg L 1m
ms = (22 m2) 1.2 3
0.3 2
m s−m 1000 L
ms = 0.00792 kg/sec
kJ
Where; Cp = 1.0
kg ° C
@ 0-3 min:
(
Qs = 0.00792
kg
sec)(
1.0
kJ
kg ° C )
( 31.1−27.3 ) ° C
Qs = 0.030 kW
@ 3-6 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 30.6−27.5 ) ° C
Qs = 0.025 kW
@ 6-9 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 30−27.2 ) °C
Qs = 0.022 kW
@ 9-12 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 31.5−27.4 ) ° C
Qs = 0.032 kW
@ 12-15 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 31−26.8 ) °C
Qs = 0.033 kW
@ 15-18 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 32−26.5 ) ° C
Qs = 0.044 kW
@ 18-21 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 30.5−26 ) ° C
Qs = 0.036 kW
@ 21-24 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 31−27.2 ) ° C
Qs = 0.030 kW
@ 24-27 min:
(
Qs = 0.00792
kg
sec)(
1.0
kJ
kg ° C )
( 30.8−26.5 ) ° C
Qs = 0.034 kW
@ 27-30 min:
(
Qs = 0.00792
kg
sec )(
1.0
kJ
kg ° C )
( 32−26 ) ° C
Qs = 0.048 kW
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0231−0.0170 )
kg moisture
kg dry air
QL = 0.118 kW
@ 3-6 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0187−0.0170 )
kg moisture
kg dry air
QL = 0.033 kW
@ 6-9 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0184−0.0170 )
kg moisture
kg dry air
QL = 0.027 kW
@ 9-12 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0186−0.0170 )
kg moisture
kg dry air
QL = 0.031 kW
@ 12-15 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0224−0.0170 )
kg moisture
kg dry air
QL = 0.104 kW
@ 15-18 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0212−0.0170 )
kg moisture
kg dry air
QL = 0.081 kW
@ 18-21 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0213−0.0170 )
kg moisture
kg dry air
QL = 0.083 kW
@ 21-24 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0230−0.0170 )
kg moisture
kg dry air
QL = 0.116 kW
@ 24-27 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0220−0.0170 )
kg moisture
kg dry air
QL = 0.097 kW
@ 27-30 min:
(
QL = 0.00792
kg
sec)(
2442
kJ
kg )
( 0.0213−0.0170 )
kg moisture
kg dry air
QL = 0.083 kW
Where; Qs = 0.334 kW
QL = 0.773 kW
0.334 kW
SHR =
0.334 kW +0.773 kW
SHR = 0.302
Based on your cooling load of 0.773 kW (or 2,639.002 BTU), you’ll want to choose an
air conditioner that can handle at least that amount of cooling capacity.
Air conditioners need an air conditioner rated around, 800 watts or ≈ 2,639.002–3,000
EER
COP =
3.412
11
COP =
3.412
COP = 3.224