Q 4
Q 4
4. A transformer is operating at 85% of its full load at 0.7 power factor leading.
The no-load losses are 500 W, and full-load copper losses are 1200 W. Determine the
actual efficiency.
5. A 150 kVA transformer has iron losses of 900 W and full-load copper losses of
2500 W. At what fraction of full load will the efficiency be maximum?
7. Find the equivalent resistance and reactance referred to both primary and
secondary sides.
10. Find the voltage regulation at full load, 0.8 power factor lagging.
11. A 100 kVA, 11 kV/415 V Δ-Y transformer supplies a balanced three-phase load of
75 kW at 0.9 power factor lagging. Calculate the primary and secondary line
currents.
12. A three-phase, 100 kVA, 6.6 kV/400 V Δ-Δ transformer has leakage impedance per
phase referred to primary as (0.5 + j2.0) Ω. Find the voltage regulation at 0.8
power factor lagging.
15. Two single-phase transformers rated 100 kVA and 150 kVA have per-unit
impedances of (0.02 + j0.06) pu and (0.03 + j0.07) pu, respectively. Determine the
load shared by each transformer when supplying a total load of 180 kVA at 0.9 power
factor lagging.
16. Two three-phase, 200 kVA transformers are operating in parallel. Their
impedance ratios are 1:1.5. If the total load is 300 kVA, determine the real and
reactive power handled by each transformer.
18. A 500 kVA, 50 Hz transformer has an iron loss of 3000 W at full voltage and
1600 W at half voltage. Determine the hysteresis and eddy current losses
separately.
19. A current transformer (CT) has a turns ratio of 500:5 and burdens of 5Ω. If the
secondary current is 4 A, determine the primary current and burden voltage.
A potential transformer (PT) with a ratio of 10:1 has a burden impedance of 20Ω.
If the secondary voltage is 100V, determine the primary voltage and total power
dissipation in the burden.