Source: HANDBOOK OF MECHANICAL ENGINEERING CALCULATIONS

POWER GENERATION

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

POWER GENERATION

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

Source: HANDBOOK OF MECHANICAL ENGINEERING CALCULATIONS

SECTION 1

MODERN POWER-PLANT CYCLES AND EQUIPMENT


CYCLE ANALYSES 1.4 Choosing Best Options for Boosting Combined-Cycle Plant Output 1.4 Selecting Gas-Turbine Heat-Recovery Boilers 1.10 Gas-Turbine Cycle Efciency Analysis and Output Determination 1.13 Determining Best-Relative-Value of Industrial Gas Turbines Using a LifeCycle Cost Model 1.18 Tube Bundle Vibration and Noise Determination in HRSGs 1.22 Determining Oxygen and Fuel Input in Gas-Turbine Plants 1.25 Heat-Recovery Steam Generator (HRSG) Simulation 1.28 Predicting Heat-Recovery Steam Generator (HRSG) Temperature Proles 1.33 Steam Turbogenerator Efciency and Steam Rate 1.36 Turbogenerator Reheat-Regenerative Cycle Alternatives Analysis 1.37 Turbine Exhaust Steam Enthalpy and Moisture Content 1.42 Steam Turbine No-Load and PartialLoad Steam Flow 1.43 Power Plant Performance Based on Test Data 1.45 Determining Turbogenerator Steam Rate at Various Loads 1.47 Analysis of Reheating-Regenerative Turbine Cycle 1.48 Steam Rate for Reheat-Regenerative Cycle 1.49 Binary Cycle Plant Efciency Analysis
1.51

Steam-Turbine Regenerative-Cycle Performance 1.71 Reheat-Regenerative Steam-Turbine Heat Rates 1.74 Steam Turbine-Gas Turbine Cycle Analysis 1.76 Gas Turbine Combustion Chamber Inlet Air Temperature 1.81 Regenerative-Cycle Gas-Turbine Analysis 1.83 Extraction Turbine kW Output 1.86 STEAM PROPERTIES AND PROCESSES
1.87

Steam Mollier Diagram and Steam Table Use 1.87 Interpolation of Steam Table Values
1.90

Constant-Pressure Steam Process


1.93

Constant-Volume Steam Process


1.95

Constant-Temperature Steam Process


1.97

Constant-Entropy Steam Process


1.99

Irreversible Adiabatic Expansion of Steam 1.101 Irreversible Adiabatic Steam Compression 1.103 Throttling Processes for Steam and Water 1.105 Reversible Heating Process for Steam
1.107

Determining Steam Enthalpy and Quality Using the Steam Tables


1.109

CONVENTIONAL STEAM CYCLES 1.53 Finding Cogeneration System Efciency vs a Conventional Steam Cycle 1.53 Bleed-Steam Regenerative Cycle Layout and T-S Plot 1.55 Bleed Regenerative Steam Cycle Analysis 1.59 Reheat-Steam Cycle Performance
1.62

Maximizing Cogeneration ElectricPower and Process-Steam Output


1.110

ECONOMIC ANALYSES OF ALTERNATIVE ENERGY SOURCES


1.112

Mechanical-Drive Steam-Turbine Power-Output Analysis 1.67 Condensing Steam-Turbine PowerOutput Analysis 1.69 1.3

Choice of Most Economic Energy Source Using the Total-Annual-Cost Method 1.112 Seven Comparison Methods for Energy Source Choice 1.115 Selection of Prime Mover Based on Annual Cost Analyses 1.120 Determining If a Prime Mover Should Be Overhauled 1.122

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.4


POWER GENERATION

Cycle Analyses
CHOOSING BEST OPTION FOR BOOSTING COMBINED-CYCLE PLANT OUTPUT
Select the best option to boost the output of a 230-MW facility based on a 155MW natural-gas-red gas turbine (GT) featuring a dry low NOx combustor (Fig. 1). The plant has a heat-recovery steam generator (HRSG) which is a triple-pressure design with an integral deaerator. A reheat condensing steam turbine (ST) is used and it is coupled to a cooling-tower / surface-condenser heat sink turbine inlet. Steam conditions are 1450-lb / in2 (gage) / 1000 F (9991-kPa / 538 C). Unit ratings are for operation at International Standard Organization (ISO) conditions. Evaluate the various technologies considered for summer peaking conditions with a dry bulb (DB) temperature of 95 F and 60 percent RH (relative humidity) (35 C and 60 percent RH). The plant heat sink is a four-cell, counterow, mechanical-draft cooling tower optimized to achieve a steam-turbine exhaust pressure of 3.75 inHg absolute (9.5 cmHg) for all alternatives considered in this evaluation. Base circulating-water system includes a surface condenser and two 50 percent-capacity pumps. Watertreatment, consumption, and disposal-related O&M (operating & maintenance)

H-p turbine

I-p turbine

L-p turbine Cooling tower Generator

H-p steam L-p steam Makeup water Feedwater pumps Condensate pumps Deaerator Reheater Fuel H-p evaporator I-p suprerheater H-p economizer I-p suprerheater I-p evaporator I-p economizer L-p evaporator L-p economizer Gas turbine H-p superheater Air Blowdown Blowdown I-p pump I-p pump

Cold reheat steam Hot reheat I-p steam

Generator

FIGURE 1 155-MW natural-gas-red gas turbine featuring a dry low NOx combustor (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.5

costs for the zero-discharge facility are assumed to be $3 / 1000 gal ($3 / 3.8 m3) of raw water, $6 / 1000 gal ($6 / 3.8 m3) of treated demineralized water, and $5 / 1000 gal ($5 / 3.8 m3) of water disposal. The plant is congured to burn liquid distillate as a backup fuel.
Calculation Procedure:

1. List the options available for boosting output Seven options can be developed for boosting the output of this theoretical reference plant. Although plant-specic issues will have a signicant effect on selecting an option, comparing performance based on a reference plant, Fig. 1, can be helpful. Table 1 shows the various options available in this study for boosting output. The comparisons shown in this procedure illustrate the characteristics, advantages, and disadvantages of the major power augmentation technologies now in use. Amidst the many advantages of gas turbine (GT) combined cycles (CC) popular today from various standpoints (lower investment than for new greeneld plants, reduced environmental impact, and faster installation and startup), one drawback is that the achievable output decreases signicantly as the ambient inlet air temperature increases. The lower density of warm air reduces mass ow through the GT. And, unfortunately, hot weather typically corresponds to peak power loads in many areas. So the need to meet peak-load and power-sales contract requirements causes many power engineers and developers to compensate for ambient-temperatureoutput loss. The three most common methods of increasing output include: (1) injecting water or steam into the GT, (2) precooling GT inlet air, and / or (3) supplementary ring of the heat-recovery steam generator (HRSG). All three options require signicant capital outlays and affect other performance parameters. Further, the options

TABLE 1 Performance Summary for Enhanced-Output Options

Measured change from base case GT output, MW ST output, MW Plant aux. load, MW Net plant output, MW Net heat rate, Btu / kWh3 Incremental costs Change in total water cost, $ / h Change in wastewater cost, $ / h Change in capital cost / net output, $ / kW
1 2 3

Case 61 Case 72 Case 1 Case 2 Case 3 Case 4 Case 5 Supp.- Supp.Water Evap. Mech. Absorp. Steam red red cooler chiller chiller injection injection HRSG HRSG 5.8 0.9 0.05 6.65 15 15 1 180 20.2 2.4 4.5 18.1 55 35 17 165 20.2 2.1 0.7 17.4 70 35 17 230 21.8 13 400 8.4 270 115 2 75 15.5 3.7 0.2 19 435 85 1 15 0 8 0.4 7.6 90 35 1 70 0 35 1 34 320 155 30 450

Partial supplementary ring. Full supplementary ring. Based on lower heating value of fuel.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.6


POWER GENERATION

may uniquely impact the operation and / or selection of other components, including boiler feedwater and condensate pumps, valves, steam turbine / generators, condensers, cooling towers, and emissions-control systems. 2. Evaluate and analyze inlet-air precooling Evaporative cooling, Case 1, Table 1, boosts GT output by increasing the density and mass ow of the air entering the unit. Water sprayed into the inlet-air stream cools the air to a point near the ambient wet-bulb temperature. At reference conditions of 95 F (35 C) DB and 60 percent RH, an 85 percent effective evaporative cooler can alter the inlet-air temperature and moisture content to 85 F (29 C) and 92 percent RH, respectively, using conventional humidity chart calculations, page 16.79. This boosts the output of both the GT andbecause of energy added to the GT exhaustthe steam turbine / generator. Overall, plant output for Case 1 is increased by 5.8 MW GT output 0.9 MW ST outputplant auxiliary load of 0.9 MW 6.65 MW, or 3.3 percent. The CC heat rate is improved 0.2 percent, or 15 Btu / kWh (14.2 kJ / kWh). The total installed cost for the evaporative cooling system, based on estimates provided by contractors and staff, is $1.2-million. The incremental cost is $1,200,000 / 6650 kW $180.45 / kW for this ambient condition. The effectiveness of the same system operating in less-humid conditionssay 95 F DB (35 C) and 40 percent RHis much greater. In this case, the same evaporative cooler can reduce inlet-air temperature to 75 F DB (23.9 C) by increasing RH to 88 percent. Here, CC output is increased by 7 percent, heat rate is improved (reduced) by 1.9 percent, and the incremental installed cost is $85 / kW, computed as above. As you can clearly see, the effectiveness of evaporative cooling is directly related to reduced RH. Water-treatment requirements must also be recognized for this Case, No. 1. Because demineralized water degrades the integrity of evaporative-cooler lm media, manufacturers may suggest that only raw or ltered water be used for cooling purposes. However, both GT and evaporative-cooler suppliers specify limits for turbidity, pH, hardness, and sodium (Na) and potassium (K) concentrations in the injected water. Thus, a nominal increase in water-treatment costs can be expected. In particular, the cooling water requires periodic blowdown to limit solids buildup and system scaling. Overall, the evaporation process can signicantly increase a plants makeup-water feed rate, treatment, and blowdown requirements. Compared to the base case, water supply costs increase by $15 / h of operation for the rst approach, and $20 / h for the second, lower RH mode. Disposal of evaporativecooler blowdown costs $1 / h in the rst mode, $2 / h in the second. Evaporative cooling has little or no effect on the design of the steam turbine. 3. Evaluate the economics of inlet-air chilling The effectiveness of evaporative cooling is limited by the RH of the ambient air. Further, the inlet air cannot be cooled below the wet-bulb (WB) temperature of the inlet air. Thus, chillers may be used for further cooling of the inlet air below the wet-bulb temperature. To achieve this goal, industrial-grade mechanical or absorption air-conditioning systems are used, Fig. 2. Both consist of a cooling medium (water or a refrigerant), an energy source to drive the chiller, a heat exchanger for extracting heat from the inlet air, and a heat-rejection system. A mechanical chilling system, Case 2, Table 1, is based on a compressor-driven unit. The compressor is the most expensive part of the system and consumes a signicant amount of energy. In general, chillers rated above 12-million Btu / h (3.5 MW) (1000 tons of refrigeration) (3500 kW) employ centrifugal compressors. Units smaller than this may use either screw-type or reciprocating compressors. Overall,

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT
Ambient air (95F, 60% RH) Chilledwater coils Chilled air (60F, 100% RH) HRSG Gas turbine/ generator Electricdriven centrifugal chiller Cooling water

1.7

Circulating water pump

Chilled water

Cooling tower

Chilled-water loop 25-psia steam from HRSG Cooling tower

2-stage lithium bromide Condensate adsorption return chiller

FIGURE 2 Inlet-air chilling using either centrifugal or absorption-type chillers, boosts the achieveable mass ow and power output during warm weather (Power).

compressor-based chillers are highly reliable and can handle rapid load changes without difculty. A centrifugal-compressor-based chiller can easily reduce the temperature of the GT inlet air from 95 F (35 C) to 60 F (15.6 C) DBa level that is generally accepted as a safe lower limit for preventing icing on compressor inlet bladesand 2.4 achieve 100 percent RH. This increases plant output by 20.2 MW for GT 4.5 MW plant auxiliary load 18.1 MW, or 8.9 percent. But it MW for ST degrades the net CC heat rate by 0.8 percent and results in a 1.5-in-(3.8-cm)-H2O inlet-air pressure drop because of heat-exchanger equipment located in the inlet-air stream. Cooling requirements of the chilling system increase the plants required circulating water ow by 12,500 gal / min (47.3 m3 / min). Combined with the need for increased steam condensing capacity, use of a chiller may necessitate a heat sink 25 percent larger than the base case. The total installed cost for the mechanical chilling system for Case 2 is $3-million, or about $3,000,000 / 18,100 kW $165.75 / kW of added output. Again, costs come from contractor and staff studies. Raw-water consumption increase the plants overall O&M costs by $35 / h when the chiller is operating. Disposal of additional cooling-tower blowdown costs $17 / h. The compressor used in Case 2 consumes about 4 MW of auxiliary power to handle the plants 68-million Btu / h (19.9 MW) cooling load. 4. Analyze an absorption chilling system Absorption chilling systems are somewhat more complex than mechanical chillers. They use steam or hot water as the cooling motive force. To achieve the same inletair conditions as the mechanical chiller (60 F DB, 100 percent RH) (15.6 C, 100

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.8


POWER GENERATION

percent RH), an absorption chiller requires about 111,400 lb / h (50,576 kg / h) of 10.3-lb / in2 (gage) (70.9-kPa) saturated steam, or 6830 gal / min (25.9 m3 / min) of 370 F (188 C) hot water. Cost-effective supply of this steam or hot water requires a redesign of the reference plant. Steam is extracted from the low-pressure (l-p) steam turbine at 20.3 lb / in2 (gage) (139.9 kPa) and attemperated until it is saturated. In this case, the absorption chiller increases plant output by 8.7 percent or 17.4 MW but degrades the plants heat rate by 1 percent. Although the capacity of the absorption cooling systems cooling-water loop must be twice that of the mechanical chillers, the size of the plants overall heat sink is identical25 percent larger than the base casebecause the steam extracted from the l-p turbine reduces the required cooling capacity. Note that this also reduces steam-turbine output by 2 MW compared to the mechanical chiller, but has less effect on overall plant output. Cost estimates summarized in Table 1 show that the absorption chilling system required here costs about $4-million, or about $230 / kW of added output. Compared to the base case, raw-water consumption increases O&M costs by $35 / h when the chiller is operating. Disposal of additional cooling-water blowdown adds $17 / h. Compared to mechanical chillers, absorption units may not handle load changes as well; therefore they may not be acceptable for cycling or load-following operation. When forced to operate below their rated capacity, absorption chillers suffer a loss in efciency and reportedly require more operator attention than mechanical systems. Refrigerant issues affect the comparison between mechanical and absorption chilling. Mechanical chillers use either halogenated or nonhalogenated uorocarbons at this time. Halogenated uorocarbons, preferred by industry because they reduce the compressor load compared to nonhalogenated materials, will be phased out by the end of the decade because of environmental considerations (destruction of the ozone layer). Use of nonhalogenated refrigerants is expected to increase both the cost and parasitic power consumption for mechanical systems, at least in the near term. However, absorption chillers using either ammonia or lithium bromide will be unaffected by the new environmental regulations. Off-peak thermal storage is one way to mitigate the impact of inlet-air chillings major drawback: high parasitic power consumption. A portion of the plants electrical or thermal output is used to make ice or cool water during off-peak hours. During peak hours, the chilling system is turned off and the stored ice and / or cold water is used to chill the turbine inlet air. A major advantage is that plants can maximize their output during periods of peak demand when capacity payments are at the highest level. Thermal storage and its equipment requirements are analyzed elsewhere in this handbooknamely at page 18.70. 5. Compare steam and water injection alternatives Injecting steam or water into a GTs combustor can signicantly increase power output, but either approach also degrades overall CC efciency. With steam injection, steam extracted from the bottoming cycle is typically injected directly into the GTs combustor, Fig. 3. For advanced GTs, the steam source may be extracted from either the high-pressure (h-p) turbine exhaust, an h-p extraction, or the heat recovery steam generators (HRSG) h-p section. Cycle economics and plant-specic considerations determine the steam extraction point. For example, advanced, large-frame GTs require steam pressures of 410 to 435 lb / in2 (gage) (2825 to 2997 kPa). This is typically higher than the economically optimal range of h-p steam turbine exhaust pressures of 285 to 395 lb / in2

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.9

Demin. storage

Water-injection power sugmentation Attemperating station

Steam-injection power sugmentation

Water injection skid

HRSG Gas turbine/ generator High-pressure superheater

FIGURE 3 Water or steam injection can be used for both power augmentation and NOx control (Power).

(gage) (1964 to 2722 kPa). Thus, steam must be supplied from either the HRSG or an h-p turbine extraction ahead of the reheat section. Based on installed-cost considerations alone, extracting steam from the HRSG is favored for peaking service and may be accomplished without altering the reheat steam turbine. But if a plant operates in the steam-injection mode for extended periods, extracting steam from the turbine or increasing the h-p turbine exhaust pressure becomes more cost-effective. Injecting steam from the HRSG superheat section into the GT increases unit output by 21.8 MS, Case 4 Table 1, but decreases the steam turbine / generators output by about 12.8 MW. Net gain to the CC is 8.4 MW. But CC plant heat rate also suffers by 4 percent, or 270 Btu / kWh (256.5 kJ / kWh). Because the steam-injection system requires makeup water as pure as boiler feedwater, some means to treat up to 350 gal / min (22.1 L / s) of additional water is necessary. A dual-train demineralizer this size could cost up to $1.5-million. However, treated water could also be bought from a third party and stored. Or portable treatment equipment could be rented during peak periods to reduce capital costs. For the latter case, the average expected cost for raw and treated water is about $130 / h of operation. This analysis assumes that steam- or water-injection equipment is already in place for NOx control during distillate-fuel ring. Thus, no additional capital cost is incurred. When water injection is used for power augmentation or NOx control, the recommended water quality may be no more than ltered raw water in some cases, provided the source meets pH, turbidity, and hardness requirements. Thus, watertreatment costs may be negligible. Water injection, Case 5 Table 1, can increase the GT output by 15.5 MW. In Case 5, the bottoming cycle benets from increased GT-exhaust mass ow, increasing steam turbine / generator output by about 3.7 MW. Overall, the CC output increases by 9.4 percent or 19 MW, but the net plant heat rate suffers by 6.4 percent, or 435 Btu / kWh (413.3 kJ / kWh). Given the higher increase in the net plant heat rate and lower operating expenses, water injection is preferred over steam injection in this case. 6. Evaluate supplementary-red HRSG for this plant The amount of excess O2 in a GT exhaust gas generally permits the efcient ring of gaseous and liquid fuels upstream of the HRSG, thereby increasing the output

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.10


POWER GENERATION

from the steam bottoming cycle. For this study, two types of supplementary ring are considered(1) partial supplementary ring, Case 6 Table 1, and (2) full supplementary ring, Case 7 Table 1. There are three main drawbacks to supplementary ring for peak power enhancement, including 910 lower cycle efciency, (2) higher NOx and CO emissions, (3) higher costs for the larger plant equipment required. For this plant, each 100-million Btu / h (29.3 MW) of added supplementary ring capacity increases the net plant output by 5.5 percent, but increases the heat rate by 2 percent. The installed cost for supplementary ring can be signicant because all the following equipment is affected: (1) boiler feed pumps, (2) condensate pumps, (3) steam turbine / generator, (4) steam and water piping and valves, and (5) selective-catalytic reduction (SCR) system. Thus, a plant designed for supplementary ring to meet peak-load requirements will operate in an inefcient, off-design condition for most of the year. 7. Compare the options studied and evaluate results Comparing the results in Table 1 shows that mechanical chilling, Case 2, gives the largest increase in plant output for the least penalty on plant heat ratei.e., 18.1 MW output for a net heat rate increase of 55 Btu / kWh (52.3 kJ / kWh). However, this option has the highest estimated installed cost ($3-million), and has a relatively high incremental installed cost. Water injection, Case 5 Table 1, has the dual advantage of high added net output and low installed cost for plants already equipped with water-injection skids for NOx control during distillate-fuel ring. Steam injection, Case 4 Table 1, has a signicantly higher installed cost because of water-treatment requirements. Supplementary ring, Cases 6 and 7 Table 1, proves to be more acceptable for plants requiring extended periods of increased output, not just seasonal peaking. This calculation procedure is the work of M. Boswell, R. Tawney, and R. Narula, all of Bechtel Corporation, as reported in Power magazine, where it was edited by Steven Collins. SI values were added by the editor of this handbook. Related Calculations. Use of gas turbines for expanding plant capacity or for repowering older stations is a popular option today. GT capacity can be installed quickly and economically, compared to conventional steam turbines and boilers. Further, the GT is environmentally acceptable in most areas. So long as there is a supply of combustible gas, the GT is a viable alternative that should be considered in all plant expansion and repowering today, and especially where environmental conditions are critical.

SELECTING GAS-TURBINE HEAT-RECOVERY BOILERS


Choose a suitable heat-recovery boiler equipped with an evaporator and economizer to serve a gas turbine in a manufacturing plant where the gas ow rate is 150,000 lb / h (68,040 kg / h) at 950 F (510 C) and which will generate steam at 205 lb / in2 (gage) (1413.5 kPa). Feedwater enters the boiler at 227 F (108.3 C). Determine if supplementary ring of the exhaust is required to generate the needed steam. Use an approach temperature of 20 F (36 C) between the feedwater and the water leaving the economizer.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.11

Calculation Procedure:

1. Determine the critical gas inlet-temperature Turbine exhaust gas (TEG) typically leaves a gas turbine at 9001000 F (482538 C) and has about 13 to 16 percent free oxygen. If steam is injected into the gas turbine for NOx control, the oxygen content will decrease by 2 to 5 percent by volume. To evaluate whether supplementary ring of the exhaust is required to generate needed steam, a knowledge of the temperature proles in the boiler is needed. Prepare a gas / steam prole for this heat-recovery boiler as shown in Fig. 4. TEG enters on the left at 950 F (510 C). Steam generated in the boiler at 205 lb / in2 (gage) (1413.5 kPa) has a temperature of 390 F (198.9 C), from steam tables. For steam to be generated in the boiler, two conditions must be met: (1) The pinch point temperature must be greater than the saturated steam temperature of 390 F (198.9 C), and (2) the temperature of the saturated steam leaving the boiler economizer must be greater than that of the feedwater. The pinch point occurs somewhere along the TEG temperature line, Fig. 4, which starts at the inlet temperature of 950 F (510 C) and ends at the boiler gas outlet temperature, which is to be determined by calculation. A pinch-point temperature will be assumed during the calculation and its suitability determined. To determine the critical gas inlet-temperature, T1, get from the steam tables the 390 F (198.9 C); hl, heat of properties of the steam generated by this boiler: ts 364 Btu / lb (846.7 kJ / kg); hs, total heat of saturated vapor saturated liquid 1199.6 Btu / lb (2790.3 kJ / kg; hw, heat of saturated liquid of feedwater leaving the economizer at 370 F (187.8 C) 342 Btu / lb (795.5 kJ / kg); and h, heat of saturated liquid of the feedwater at 227 F (108.3 C) 196.3 Btu / lb (456.6 kJ / kg).

T1 950 1,550

Top Numbers: Example 1 Bottom Numbers: Example 2 T2 415 440 Tl 390 390 Approach point Pinch point T3 317 296

Tw 370 325

Tt 227 227

950F (510C) 415F (213C) 317F (158C)

1550F (843C) 440F (227C) 296F (147C)

390F (199C) 370F (188C) 227F (108C)

390F (199C) 325F (163C) 227F (108C)

FIGURE 4 Gas / steam prole and data (Chemical Engineering).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.12


POWER GENERATION

Writing an energy balance across the evaporator neglecting heat and blowdown T2) / (T1 T3) (hs hw ) / (hs h) X, where T1 gas losses, we get: (T1 temperature in boiler, F ( C); T2 pinch-point gas temperature, F ( C); T3 outlet gas temperature for TEG, F ( C); enthalpy, h, values as listed above; X ratio of temperature or enthalpy differences. Substituting, X (1199.6 342) / (1199.9 196.3) 0.855, using enthalpy values as given above. (ts Xt) / (1 X ), where ts temThe critical gas inlet-temperature, T1c perature of saturated steam, F ( C); t temperature of feedwater, F ( C); other symbols as before. Using the values determined above, T1c [390 (0.855)(227)] / (1 0.855) 1351 F (732.8 C). 2. Determine the system pinch point and gas / steam prole Up to a gas inlet temperature of approximately 1351 F (732.8 C), the pinch point can be arbitrarily selected. Beyond this, the feedwater inlet temperature limits the temperature prole. Lets then select a pinch point of 25 F (13.9 C), Fig. 4. Then, T2, the gas-turbine gas temperature at the pinch point, F ( C) t pinch-point temperature difference, or 390 F 25 F 415 F (212.8 C). Setting up an energy balance across the evaporator, assuming a heat loss of 2 heat loss)(TEG percent and a blowdown of 3 percent, leads to: Qevap We (1 heat capacity, Btu / F) (T1 T2), where We TEG ow, lb / h; heat capacity of 0.27 Btu / F; T1 TEG inlet temperature, F ( C). Substituting, Qevap TEG 150,000(0.98)(0.27)(950 415) 21.23 106 Btu / h (6.22 MW). blowdown percent The rate of steam generation, Ws Qevap / [(hs hw ) (hl hw )], where the symbols are as given earlier. Substituting, Ws 21.23 106 / [(1199.6 342) 0.03 (364 342)] 24,736 lb / h (11,230 kg / h). (1 blowdown)(Ws ) Determine the boiler economizer duty from Qecon (hw h), where symbols are as before. Substituting, Qecon 1.03(24,736)(342 196.3) 3.71 106 Btu / h (1.09 MW). T2 Qecon / TEG gas ow, lb / h)(1 heat The gas exit-temperature, T3 loss)(heat capacity, Btu / lb F). Since all values are known, T3 415 3.71 106 / (150,000 0.98 0.27) 317 F (158 C). Figure 4 shows the temperature prole for this installation. Related Calculations. Use this procedure for heat-recovery boilers red by gas-turbine exhaust in any industry or utility application. Such boilers may be unred, supplementary red, or exhaust red, depending on steam requirements. Typically, the gas pressure drop across the boiler system ranges from 6 to 12 in (15.2 to 30.5 cm) of water. There is an important tradeoff: a lower pressure drop means the gas-turbine power output will be higher, while the boiler surface and the capital cost will be higher, and vice versa. Generally, a lower gas pressure drop offers a quick payback time. If Pe is the additional gas pressure in the system, the power, kW, consumed in overcoming this loss can be shown approximately from P 5 10 8 (We Pe T / E, where E efciency of compression). To show the application of this equation and the related payback period, assume 150,000 lb / g (68,100 kg / h), T 1000 R (average gas temperature in the We boiler, Pe 4 in water (10.2 cm), and E 0.7. Then P 5 10 8 (150,000 4 1000 / 0.7) 42 kW. If the gas turbine output is 4000 kW, nearly 1 percent of the power is lost due to the 4-in (10.2-cm) pressure drop. If electricity costs 7 cent / kWh, and the gas 0.07 42 $23,520. If turbine runs 8000 h / yr, the annual loss will be 8000 the incremental cost of a boiler having a 4-in (10.2-cm) lower pressure drop is, say $22,000, the payback period is about one year.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.13

Fuel F, Wf

We, T1 Burner TEG

(We

Wf),T1

(Weh1

LHV

Wt)

(We

Wf)h1

FIGURE 5 Gas / steam prole for red mode (Chemical Engineering).

If steam requirements are not stated for a particular gas inlet condition, and maximum steaming rate is desired, a boiler can be designed with a low pinch point, a large evaporator, and an economizer. Check the economizer for steaming. Such a choice results in a low gas exit temperature and a high steam ow. Then, the incremental boiler cost must be evaluated against the additional steam ow and gas-pressure drop. For example, Boiler A generates 24,000 lb / h (10,896 kg / h), while Boiler B provides 25,000 lb / h (11,350 kg / h) for the same gas pressure-drop but costs $30,000 more. Is Boiler B worth the extra expense? To answer this question, look at the annual differential gain in steam ow. Assuming steam costs $3.50 / 1000 lb (3.50 / 454 kg), the annual differential gain in 1000 3.5 8000 / 1000 $28,000. Thus, the simple payback is steam ow about a year ($30,000 vs $28,000), which is attractive. You must, however, be certain you assess payback time against the actual amount of time the boiler will operate. If the boiler is likely to be used for only half this period, then the payback time is actually two years. The general procedure presented here can be used for any type industry using gas-turbine heat-recovery boilerschemical, petroleum, power, textile, food, etc. This procedure is the work of V. Ganapathy, Heat-Transfer Specialist, ABCO Industries, Inc., and was presented in Chemical Engineering magazine. When supplementary fuel is added to the turbine exhaust gas before it enters the boiler, or between boiler surfaces, to increase steam production, one has to perform an energy balance around the burner, Fig. 5, to evaluate accurately the gas temperature increase that can be obtained. V. Ganapathy, cited above, has a computer program he developed to speed this calculation.

GAS-TURBINE CYCLE EFFICIENCY ANALYSIS AND OUTPUT DETERMINATION


A gas turbine consisting of a compressor, combustor, and an expander has air entering at 60 F (15.6 C) and 14.0 lb / in2 (abs) (96.5 kPa). Inlet air is compressed

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.14


POWER GENERATION

to 56 lb / in2 (abs) (385.8 kPa); the isentropic efciency of the compressor is 82 percent. Sufcient fuel is injected to give the mixture of fuel vapor and air a heating value of 200 Btu / lb (466 kJ / kg). Assume complete combustion of the fuel. The expander reduces the ow pressure to 14.9 lb / in2 (abs), with an engine efciency of 85 percent. Assuming that the combustion products have the same thermody0.24, and is constant. The isentropic exponent may namic properties as air, cp be taken as 1.4. (a) Find the temperature after compression, after combustion, and at the exhaust. (b) Determine the Btu / lb (kJ / kg) of air supplied, the work delivered by the expander, the net work produced by the gas turbine, and its thermal efciency.

Calculation Procedure:

1. Plot the ideal and actual cycles Draw the ideal cycle as 1-2-3-4-1, Figs. 6 and 7. Actual compression takes place along 1-2 . Actual heat added lies along 2 -3 . The ideal expansion process path is cp (ideal temperature difference). Actual work cp (actual 3 -4 . Ideal work temperature difference). 2. Find the temperature after compression Use the relation (T2 / T1) (P2 / P1)(k 1) / k, where T1 entering air temperature, R; T2 temperature after adiabatic compression, R; P1 entering air pressure, in pressure after compression, in units given above; k units given above; P2 isentropic exponent 1.4. With an entering air temperature, T1 of 60 F (15.6 C), 460 520 R, and using the data given, T2 520[(56 / 14)](1.4 1) / 1.4 or 60 772.7 R, or 772.7 520 252.7 F (122.6 C). (a) Here we have isentropic compression in the compressor with an ef(cp )(T2 T1) / ciency of 85 percent. Using the equation, Efciency, isentropic T1), and solve for T2 , the temperature after isentropic compression. Solv(cp )(T2 ing, T2 0.82 0.24(772.7 520) / 0.24(T2 520) 828.4 R, or 368 F. This is the temperature after compression. 3. Determine the temperature after combustion To nd the temperature after combustion, use the relation Heating value of fuel Q cp (T3 T2 ), where T3 temperature after combustion, R. Substituting, 200 0.24(T3 828). Solving, T3 1661.3 R; 1201.3 F (649.6 C).

FIGURE 6 Ideal gas-turbine cycle, 1-2-3-4-1. Actual compression takes place along 1-2 ; actual heat added 2 -3 ; ideal expansion 3 -4 .

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.15

FIGURE 7 Ideal gas-turbine cycle T-S diagram with the same processes as in Fig. 6; completecycle gas turbine shown below the T-S diagram.

4. Find the temperature at the exhaust of the gas turbine Using an approach similar to that above, determine T4 from (T4 / T3 ) [(P4 / P3 )]k 1 / k. Substituting and solving for T4 1661[(14.9 / 56)](1.4 1) / 1.4 1137.9 R, or 677.8 F (358.8 C). Now use the equation for gas-turbine efciency, namely, Turbine efciency cp (T3 T4 )/ cp (T3 T4 ) 0.85, and solve for T4 , the temperature after expansion, at the exhaust. Substituting as earlier, T4 1218.2 R, 758.2 F (403.4 C). This is the temperature after expansion, i.e., at the exhaust of the gas turbine. 5. Determine the work of compression, expander work, and thermal efciency (b) The work of compression cp(T2 T1) 0.24(828 520) 74.16 Btu (78.23 J). cp(T2 T1) 0.24 (1661 1218) The work delivered by the expander 106.32 Btu (112.16 J). 106.3 74.2 32.1 Btu (33.86 J). Then, the thermal The net work net work / heat supplied 32.1 / 200 0.1605, 16.6 percent thermal efciency efciency. Related Calculations. With the widespread use today of gas turbines in a variety of cycles in industrial and central-station plants, it is important that an engineer be able to analyze this important prime mover. Because gas turbines can be quickly installed and easily hooked to heat-recovery steam generators (HRSG), they are more popular than ever before in history.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.16


POWER GENERATION

Further, as aircraft engines become largersuch as those for the Boeing 777 and the Airbus 340the power output of aeroderivative machines increases at little cost to the power industry. The result is further application of gas turbines for topping, expansion, cogeneration and a variety of other key services throughout the world of power generation and energy conservation. With further renement in gas-turbine cycles, specic fuel consumption, Fig. 8, declines. Thus, the complete cycle gas turbine has the lowest specic fuel consumption, with the regenerative cycle a close second in the 6-to-1 compressionratio range. Two recent developments in gas-turbine plants promise much for the future. The rst of these developments is the single-shaft combined-cycle gas and steam turbine, Fig. 9. In this cycle, the gas turbine exhausts into a heat-recovery steam generator (HRSG) that supplies steam to the turbine. This cycle is the most signicant electric generating system available today. Further, its capital costs are signicantly lower than competing nuclear, fossil-red steam, and renewable-energy stations. Other advantages include low air emissions, low water consumption, smaller space requirements, and a reduced physical prole, Fig. 10. All these advantages are important in todays strict permitting and siting processes.

FIGURE 8 With further gas-turbine cycle renement, the specic fuel consumption declines. These curves are based on assumed efciencies with T3 1400 F (760 C).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.17
Stack

Inlet air Generator Gas turbine H-p I-p L-p

L-p

I-p H-p Steam turbine

Synchronous clutch

HRSG Fuel

FIGURE 9 Single-shaft combined-cycle technology can reduce costs and increase thermal efciency over multi-shaft arrangements. This concept is popular in Europe (Power).

68.5 ft (20.9 m)

(51.9 m) 170.6 ft

29.5 ft (8.99 m)

152 ft (46.33 m)

95 ft (28.95 m)

FIGURE 10 Steam turbine, electric generator, and gas turbine t into one compact building when all three machines are arranged on a single shaft. Net result: Reduced site footprint and civilengineering work (Power).

Having the gas turbine, steam turbine, and generator all on one shaft simplies plant design and operation, and may lower rst costs. When used for large reheat cycles, as shown here, separate high-pressure (h-p), intermediate-pressure (i-p), and low-pressure (l-p) turbine elements are all on the same shaft as the gas turbine and generator. Modern high-technology combined-cycle single-shaft units deliver a simple-cycle net efciency of 38.5 percent for a combine-cycle net efciency of 58 percent on a lower heating value (LHV) basis.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.18


POWER GENERATION

The second important gas-turbine development worth noting is the dual-fueled turbine located at the intersection of both gas and oil pipelines. Being able to use either fuel gives the gas turbine greater opportunity to increase its economy by switching to the lowest-cost fuel whenever necessary. Further developments along these lines is expected in the future. The data in the last three paragraphs and the two illustrations are from Power magazine.

DETERMINING BEST-RELATIVE-VALUE OF INDUSTRIAL GAS TURBINES USING A LIFE-CYCLE COST MODEL


An industrial application requires a 21-MW continuous electrical output year-round. Five different gas turbines are under consideration. Determine which of these ve turbines is the best choice, using a suitable life-cycle cost analysis.

Calculation Procedure:

1. Assemble the cost data for each gas turbine being considered Assemble the cost data as shown below for each of the ve gas turbines identied by the letters A through E. Contact the gas-turbine manufacturers for the initial cost, $ / kW, thermal efciency, availability, fuel consumption, generator efciency, and maintenance cost, $ / kWh. List these data as shown below. The loan period, years, will be the same for all the gas turbines being considered, and is based on an equipment life-expectancy of 20 years. Interest rate on the capital investment for each turbine will vary, depending on the amount invested and the way in which the loan must be repaid and will be provided by the accounting department of the rm considering gas-turbine purchase.
Equipment Attributes for Typical Candidates* Gas-turbine candidates Parameter Initial cost, $ / kW Thermal efciency, % Loan period, yr Availability Fuel cost, $ / million Btu Interes, % Generator efciency, % Maintenance cost, $ / kWh A 205 32.5 20 0.96 4 6.5 98.0 0.004 B 320 35.5 20 0.94 4 8.0 98.5 0.005 C 275 34.0 20 0.95 4 7.0 98.5 0.005 D 320 36.5 20 0.94 4 8.5 98.0 0.005 E 200 30.0 20 0.96 4 7.5 98.5 0.004

*Assuming an equipment life of 20 years, an output of 21 MW.

2. Select a life-cycle cost model for the gas turbines being considered A popular and widely used life-cycle cost model for gas turbines has three parts: (1) the annual investment cost, Cp ; (2) annual fuel cost, C; (3) annual maintenance cost, Cm. Summing these three annual costs, all of which are expressed in mils / kWh, gives CT , the life-cycle cost model. The equations for each of the three components are given below, along with the life-cycle working model, CT :

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.19

The life-cycle cost model (CT ) consists of annual investment cost (Cp ) annual fuel cost (C) annual maintenance cost (Cm ). Equations for these values are: Cp where l i n A kW 8760 G l {i / [1 (1 i ) n ]} (A )(kW)(8760)(G )

initial capital cost of equipment, dollars interest rate number of payment periods availability (expressed as decimal) kilowatts of electricity produced total hours in year efciency of electric generator C E(293)

where E 293

thermal efciency of gas turbine conversion of Btu to kWh Cm M / kW

where M

maintenance cost, dollars per operating (red) hour.

Thus, the life-cycle working model can be expressed as CT where F l {i / [1 (1 i ) n ]} (A )(kW)(8760)(G ) F / E(293) M / kW

fuel cost, dollars per million Btu (higher heating value)

To evaluate the comparative capital cost of a gas-turbine electrical generating package the above model uses the capital-recovery factor technique. This approach spreads the initial investment and interest costs for the repayment period into an equal annual expense using the time value of money. The approach also allows for the comparison of other periodic expenses, like fuel and maintenance costs. 3. Perform the computation for each of the gas turbines being considered Using the compiled data shown above, compute the values for Cp, C, and Cm, and sum the results. List for each of the units as shown below.
Results from Cost Model Unit A B C D E Mils / kWh produced 48.3 47.5 48.3 46.6 51.9

4. Analyze the ndings of the life-cycle model Note that the initial investment cost for the turbines being considered ranges between $200 and $320 / kW. On a $ / kW basis, only unit E at the $200 level, would be considered. However, the life-cycle cost model, above, shows the cost per kWh

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.20


POWER GENERATION

produced for each of the gas-turbine units being considered. This gives a much different perspective of the units. From a life-cycle standpoint, the choice of unit E over unit D would result in an added expenditure of about $975,000 annually during the life span of the equipment, found from [(51.9 46.6) / 1000](8760 hr / yr)(21,000 kW) $974,988; this was rounded to $975,000. Since the difference in the initial cost between units D $4,200,000 $2,520,000, this cost difference will be reand E is $6,720,000 2.58 years, or about one-eighth of the 20-year covered in $2,520,000 / 974,988 life span of the equipment. Also, note that the 20-year differential in cost / kWh produced between units D and E is equivalent to over 4.6 times the initial equipment cost of unit E. When considering the values output of a life-cycle model, remember that such values are only as valid as the data input. So take precautions to input both reasonable and accurate data to the life-cycle cost model. Be careful in attempting to distinguish model outputs that vary less than 0.5 mil from one another. Since the predictions of this life-cycle cost model cannot be compared to actual measurements at this time, a potential shortcoming of the model lies with the validity of the data and assumptions used for input. For this reason, the model is best applied to establish comparisons to differentiate between several pieces of competing equipment. Related Calculations. The rst gas turbines to enter industrial service in the early 1950s represented a blend of steam-turbine and aerothermodynamic design. In the late 1950s / early-1960s, lightweight industrial gas turbines derived directly from aircraft engines were introduced into electric power generation, pipeline compression, industrial power generation, and a variety of other applications. These machines had performance characteristics similar to their steam-turbine counterparts, namely pressure ratios of about 12 1, ring temperatures of 12001500 F (649816 C), and thermal efciencies in the 2327 percent range. In the 1970s, a new breed of aeroderivative gas turbines entered industrial service. These units, with simple-cycle thermal efciencies in the 3237 percent bracket, represented a new technological approach to aerothermodynamic design. Today, these second-generation units are joined by hybrid designs that incorporate some of the aeroderivative design advances but still maintain the basic structural concepts of the heavy-frame machines. These hybrid units are not approaching the simple-cycle thermal-efciency levels reached by some of the early secondgeneration aeroderivative units rst earmarked for industrial use. Traditionally, the major focus has been on rst cost of industrial gas-turbine units, not on operating cost. Experience with higher-technology equipment, however, reveals that a low rst cost does not mean a lower total cost during the expected life of the equipment. Conversely, reliable, high-quality equipment with demonstrated availability will be remembered long after the emotional distress associated with high initial cost is forgotten. The life-cycle cost model presented here uses 10 independent variables. A single-point solution can easily be obtained, but multiple solutions require repeated calculations. Although curves depicting simultaneous variations in all variables would be difcult to interpret, simplied diagrams can be constructed to illustrate the relative importance of different variables. Thus, the simplied diagrams shown in Fig. 11, all plot production cost, mils / kWh, versus investment cost. All the plots are based on continuous operation of 8760 h / yr at 21-MW capacity with an equipment life expectancy of 20 years. The curves shown depict the variation in production cost of electricity as a function of initial investment cost for various levels of thermal efciency, loan

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.21 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

FIGURE 11 Economic study plots for life-cycle costs (Power).

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.22


POWER GENERATION

repayment period, gas-turbine availability, and fuel cost. Each of these factors is an element in the life-cycle cost model presented here. This procedure is the work of R. B. Spector, General Electric Co., as reported in Power magazine.

TUBE BUNDLE VIBRATION AND NOISE DETERMINATION IN HRSGs


A tubular air heater 11.7 ft (3.57 m) wide, 12.5 ft (3.81 m) deep and 13.5 ft (4.11 m) high is used in a boiler plant. Carbon steel tubes 2 in (5.08 cm) in outer diameter and 0.08 in (0.20 cm) thick are used in inline fashion with a traverse pitch of 3.5 in (8.89 cm) and a longitudinal pitch of 3 in (7.62 m). There are 40 tubes wide and 60 tubes deep in the heater; 300,000 lb (136,200 kg) of air ows across the tubes at an average temperature of 219 F (103.9 C). The tubes are xed at both 1.67 lb / ft (2.49 kg / m). Check this air heater ends. Tube mass per unit length for possible tube vibration problems.

Calculation Procedure:

1. Determine the mode of vibration for the tube bundle Whenever a uid ows across a tube bundle such as boiler tubes in an evaporator, economizer, HRSG, superheater, or air heater, vortices are formed and shed in the wake beyond the tubes. This shedding on alternate sides of the tubes causes a harmonically varying force on the tubes perpendicular to the normal ow of the uid. It is a self-excited vibration. If the frequency of the Von Karman vortices, as they are termed, coincides with the natural frequency of vibration of the tubes, then resonance occurs and the tubes vibrate, leading to possible damage of the tubes. Vortex shedding is most prevalent in the range of Reynolds numbers from 300 to 200,000, the range in which most boilers operate. Another problem encountered with vortex shedding is acoustic vibration, which is normal to both the uid ow and tube length observed in only gases and vapors. This occurs when the vortex shedding frequency is close to the acoustic frequency. Excessive noise is generated, leading to large gas pressure drops and bundle and casing damage. The starting point in the evaluation for noise and vibration is the estimation of various frequencies. Use the listing of C values shown below to determine the mode of vibration. Note that C is a factor determined by the end conditions of the tube bundle.
Mode of vibration End conditions Both ends clamped One end clamped, one end hinged Both hinged 1 22.37 15.42 9.87 2 61.67 49.97 39.48 3 120.9 104.2 88.8

Since the tubes are xed at both ends, i.e., clamped, select the mode of vibration as 1, with C 22.37. For most situations, Mode 1 is the most important case.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.23

2. Find the natural frequency of the tube bundle 90C [d 4 d 4 ] / (L 2 M 0.5). Substituting, with C 22.37, Use the relation, n o i n (90)(22.37)[24 1.844]0.5 / (13.52 1.670.5) 18.2 cycles per second (cps). In Mode 2, n 50.2, as C 61.67. 3. Compute the vortex shedding frequency To compute the vortex shedding frequency we must know several factors, the rst of which is the Strouhl Number, S. Using Fig. 12 with a transverse pitch / diameter of 1.75 and a longitudinal pitch diameter of 1.5 we nd S 0.33. Then, the air density 40 / (460 219) 0.059 lb / ft3 (0.95 kg / m3); free gas area 40(3.5 2)(13.5 / 12) 67.5 ft2 (6.3 m2); gas velocity, V 300,000 / (67.5)(0.059)(3600) 21 ft / s (6.4 m / s). Use the relation, c 12(S )(V ) / do 12(0.33)(21) / 2 41.6 cps, where c vortex shedding frequency, cps. 4. Determine the acoustic frequency As with vortex frequency, we must rst determine several variables, namely: absolute temperature R 219 460 679 R; sonic velocity, Vs 49(679)0.5 1277 ft / s (389.2 m / s); wave length, 2(w ) / n, where w width of tube bank, ft (m); n mode of vibration 1 for this tube bank; then 2(11.7) / 1 23.4 ft (7.13 m). The acoustic frequency, a (Vs ) / , where Vs velocity of sound at the gas temperature in the duct or shell, ft / s (m / s); Vs [(g )( )(RT )]0.5, where R gas constant 1546 / molecular weight of the gas; T gas temperature, R; ratio of gas specic heats, typically 1.4 for common ue gases; the molecular weight 29. Simplifying, we get Vs 49(T )0.5, as shown above. Substituting, a 1277 / 23.4 54.5 cps. For n 2; a 54.4(2) 109 cps. The results for Modes 1 and 2 are summarized in the tabulation below.
Mode of vibration n n, cps c, cps a (without bafes) a (with bafes) 1 18.2 41.6 54.5 109 2 50.2 41.6 109 218

FIGURE 12 Strouhl number, S, for inline tube banks. Each curve represents a different longitudinal pitch / diameter ratio (Chen).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.24


POWER GENERATION

The tube natural frequency and the vortex shedding frequency are far apart. Hence, the tube bundle vibration problem is unlikely to occur. However, the vortex shedding and acoustic frequencies are close. If the air ow increases slightly, the two frequencies will be close. By inserting a bafe in the tube bundle (dividing the ductwork into two along the gas ow direction) we can double the acoustic frequency as the width of the gas path is now halved. This increases the difference between vortex shedding and acoustic frequencies and prevents noise problems. Noise problems arise when the acoustic and vortex shedding frequencies are closeusually within 20 percent. Tube bundle vibration problems arise when the vortex shedding frequency and natural frequency of the bundle are closewithin 20 percent. Potential noise problems must also be considered at various turndown conditions of the equipment. Related Calculations. For a thorough analysis of a plant or its components, evaluate the performance of heat-transfer equipment as a function of load. Analyze at various loads the possible vibration problems that might occur. At low loads in the above case, tube bundle vibration is likely, while at high loads acoustic vibration is likely without bafes. Hence, a wide range of performance must be reviewed before nalizing any tube bundle design, Fig. 13. This procedure is the work of V. Ganapathy, Heat Transfer Specialist, ABCO Industries, Inc.
Moment-connected corners Main wall beams Main roof beams Roof cross-tie beams
1/ -in. casing 4

Insulation Liner Roof pressure-part supports Pressure-part expansion guides Main frame Tube-bundle support beam Suspension bolt Vibration stopper Heattransfer tube bundle Casing Vibration stopper
1 Wall cross-tie /2-in. dia. liner stud beams

Upper header Tube restraint

Tube restraint supports

Ga

w s flo

Tubes Lower header Lower header cradle Floor pressure-part supports Main floor beams Floor cross-tie beams

Moment-connected corners

FIGURE 13 Tube bundles in HRSGs require appropriate support mechanisms; thermal cycling in combined-cycle units makes this consideration even more important (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.25

DETERMINING OXYGEN AND FUEL INPUT IN GAS-TURBINE PLANTS


In a gas-turbine HRSG (heat-recovery steam generator) it is desired to raise the temperature of 150,000 lb / h (68,100 kg / h) of exhaust gases from 950 F (510 C) to 1575 F (857.2 C) in order to nearly double the output of the HRSG. If the exhaust gases contain 15 percent oxygen by volume, determine the fuel input and oxygen consumed, using the gas specic-heat method.

Calculation Procedure:

1. Determine the air equivalent in the exhaust gases In gas-turbine based cogeneration / combined-cycle projects the HRSG may be red to generate more steam than that produced by the gas-turbine exhaust gases. Typically, the gas-turbine exhaust gas contains 14 to 15 percent oxygen by volume. So the question arises: How much fuel can be red to generate more steam? Would the oxygen in the exhaust gases run out if we red to a desired temperature? These questions are addressed in this procedure. If 0 percent oxygen is available in Wg lb / h (kg / h) of exhaust gases, the airequivalent Wa in lb / h (kg / h) is given by: Wa 100(Wg )(32Ox ) / [23(100)(29.5)] 0.0417 Wg (O). In this relation, we are converting the oxygen from a volume basis to a weight basis by multiplying by its molecular weight of 32 and dividing by the molecular weight of the exhaust gases, namely 29.5. Then multiplying by (100 / 23) gives the air equivalent as air contains 23 percent by weight of oxygen. 2. Relate the air required with the fuel red using the MM Btu (kJ ) method Each MM Btu (kJ) of fuel red (HHV basis) requires a certain amount of air, A. amount of fuel red in the turbine exhaust gases on a LHV basis (calcuIf Q lations for turbine exhaust gases fuel input are done on a low-heating-value basis) then the fuel red in lb / h (kJ / h) W Q / LHV. The heat input on an HHV basis W(HHV) / (106) (Q / LHV)(HHV) / 106 Btu / h (kJ / h). Air required lb / h (kg / h) (Q / LHV)(HHV)(A ), using the MM Btu, amount of air required, lb (kg) per MM Btu (kJ) red. The above where A quantity air available in the exhaust gases, Wa 0.0417 Wg (O). 3. Simplify the gas relations further From the data in step 2, (Q / LHV)(HHV)(A ) / 106 0.0417 Wg (O). For natural gas and fuel oils it can be shown that (LHV / Ax HHV) 0.00124. For example, LHV 21,520 Btu / lb (50,055.5 kJ / kg); HHV 23,879 Btu / lb (55,542.6 of methane 730 lb (331.4 kg). Hence, (LHV / Ax HHV) 21,520 / (730 kJ / kg), and A 23,879) 0.00124. By substituting in the equation in step 1, we have Q 58.4 (Wg )(O). This is an important equation because it relates the oxygen consumption from the exhaust gases to the burner fuel consumption. 4. Find the fuel input to the HRSG hg 1 Q (Wg W)(hg 2), where hg 1 and hg 2 The fuel input is given by Wg are the enthalpies of the exhaust gas before and after the fuel burner; W fuel input, lb / h (kg / h); Q fuel input in Btu / h (kJ / h).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.26


POWER GENERATION

The relation above requires enthalpies of the gases before and after the burner, which entails detailed combustion calculations. However, considering that the mass of fuel is a small fraction of the total gas ow through the HRSG, the fuel ow can be neglected. Using a specic heat for the gases of 0.31 Btu / lb F (1297.9 J / kg K), we have, Q 150,000(0.31)(1575 950) 29 106 Btu / h (8.49 kW). (29 106) / (58.4 150,000) 3.32 The percent of oxygen by volume, O percent. That is, only 3.32 percent oxygen by volume is consumed and we still have 15.00 3.32 11.68 percent left in the ue gases. Thus, more fuel can be red and the gases will not run out of oxygen for combustion. Typically, the nal oxygen content of the gases can go as low as 2 to 3 percent using 3 percent nal oxygen, the amount of fuel that can be red (150,000)(58.4)(15 3) 105 MM Btu / h (110.8 MMJ / h). It can be shown through an HRSG simulation program (contact the author for more information) that all of the fuel energy goes into steam. Thus, if the unred HRSG were generating 23,000 lb / h (10,442 kg / h) of steam with an energy absorption of 23 MM Btu / h (24.3 MM J / h), approximately, the amount of steam that can be generated 23 105 128 MM Btu / h (135 MM J / h), or by ring fuel in the HRSG 128,000 lb / h (58,112 kg / h) of steam. This is close to a ring temperature of 3000 to 3100 F (1648 to 1704 C). Related Calculations. Using the methods given elsewhere in this handbook, one may make detailed combustion calculations and obtain a ue-gas analysis after combustion. Then compute the enthalpies of the exhaust gas before and after the burner. Using this approach, you can check the burner duty more accurately than using the gas specic-heat method presented above. This procedure is the work of V. Ganapathy, Heat Transfer Specialist, ABCO Industries, Inc. Power magazine recently commented on the place of gas turbines in todays modern power cycles thus: Using an HRSG with a gas turbine enhances the overall efciency of the cycle by recovering heat in the gas-turbines hot exhaust gases. The recovered heat can be used to generate steam in the HRSG for either (1) injection back into the gas turbine, Fig. 14, (2) use in district heating or an industrial process, (3) driving a steam turbine-generator in a combined-cycle arrangement, or (4) any combination of the rst three.
H-p steam Exhaust To process

L-p steam Air Fuel HRSG

Combustor

H-p compressor L-p compressor

H-p turbine L-p turbine Power turbine

Load

FIGURE 14 Steam injection systems offer substantial improvement in both capacity and efciency (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.27

Steam injection into the gas turbine has many benets, including: (1) achievable output is increased by 25 percent or more, depending on the gas-turbine design, (2) part-load gas-turbine efciency can be signicantly improved, (3) gas-red NOx emissions can be markedly reducedup to the 1545 ppm range in many cases, (4) operating exibility is improved for cogeneration plants because electrical and thermal outputs can be balanced to optimize overall plant efciency and protability. Combined-cycle gas-turbine plants are inherently more efcient than simplecycle plants employing steam injection. Further, combined-cycle plants may also be considered more adaptable to cogeneration compared to steam-injected gas turbines. The reason for this is that the maximum achievable electrical output decreases signicantly for steam-injected units in the cogeneration mode because less steam is available for use in the gas turbine. In contrast, the impact of cogeneration on electrical output is much less for combined-cycle plants. Repowering in the utility industry can use any of several plant-revitalization schemes. One of the most common repowering options employed or considered today by utilities consists of replacing an aging steam generator with a gasturbine / generator and HRSG, Fig. 15. It is estimated that within the next few years, more than 3500 utility power plants will have reached their 30th birthdays. A signicant number of these facilitiesmore than 20 GW of capacity by some estimatesare candidates for repowering, an option that can cut emissions and boost plant efciency, reliability, output, and service life. And repowering often proves to be more economical, per cost of kilowatt generated, compared to other options for adding capacity. Further, compared to building a new power plant, the permitting process for repowering its typically much shorter and less complex. The HRSG will often have a separate ring capability such as that discussed in this calculation procedure.

To Existing Steam existing generator turbine 11.5 kV switchyard

L-p steam H-p steam

Existing circ-water system Existing fuel-oil storage tank Fuel gas To 115-kV switchyard

Condenser Deaerator Existing condensate pump Fuel oil Boiler feed pump L-p drum H-p drum

HRSG Stack Combustion turbine H-p superheater L-p superheater L-p economizer H-p economizer

FIGURE 15 HRSG and gas turbine used in repowering (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.28


POWER GENERATION

These comments from Power magazine were prepared by Steven Collins, Assistant Editor of the publication.

HEAT-RECOVERY STEAM GENERATOR (HRSG) SIMULATION


A gas turbine exhausts 140,000 lb / h (63,560 kg / h) of gas at 980 F (526.7 C) to an HRSG generating saturated steam at 200 lb / in2 (gage) (1378 kPa). Determine the steam-generation and design-temperature proles if the feedwater temperature is 230 F (110 C) and blowdown 5 percent. The average gas-turbine exhaust gas specic heat is 0.27 Btu / lb F (1.13 kJ / kg C) at the evaporator and 0.253 Btu / lb F (1.06 kJ / kg C) at the economizer. Use a 20 F (11.1 C) pinch point, 15 F (8.3 C) approach point and 1 percent heat loss. Evaluate the evaporator duty, steam ow, economizer duty, and exit-gas temperature for normal load conditions. Then determine how the HRSG off-design temperature prole changes when the gas-turbine exhaust-gas ow becomes 165,000 lb / h (74,910 kg / h) at 880 F (471 C) with the HRSG generating 150-lb / in2 (gage) (1033.5 kPa) steam with the feedwater temperature remaining the same.

Calculation Procedure:

1. Compute the evaporator duty and steam ow Engineers should be able to predict both the design and off-design performance of an HRSG, such as that in Fig. 16, under different conditions of exhaust ow, temperature, and auxiliary ring without delving into the mechanical design aspects of tube size, length, or n conguration. This procedure shows how to make such predictions for HRSGs of various sizes by using simulation techniques.

To steam turbine H-p drum L-p evaporator H-p economizer H-p feedwater pump SuperH-p heater evaporator

To steam turbine L-p drum

Gas flow

L-p economizer

Condensate pump

FIGURE 16 HRSG circuit shown is used by at least one manufacturer to prevent steaming in the economizer during startup and low-load operation (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.29

HRSGs operate at different exhaust-gas conditions. For example, variations in ambient temperature or gas-turbine load affect exhaust-gas ow and temperature. This, in turn, affects HRSG performance, temperature proles, efciency, and steam generation. The tool consultants use for evaluating HRSG performance under different operating conditions is simulation. With this tool you can: (1) Predict offdesign performance of an HRSG; (2) Predict auxiliary fuel consumption for periods when the gas-turbine exhaust-gas ow is insufcient to generate the required steam ow; (3) Evaluate options for improving an HRSG system; (4) Evaluate eld data for validating an HRSG design; (5) Evaluate different HRSG congurations for maximizing efciency. In this HRSG, using steam-table data, the saturation temperature of 200-lb / in2 (gage) (1378-kPa) steam 388 F (197.8 C). The gas temperature leaving the evap388 20 408 F (208.9 C). Water orator with the 20 F (11.1 C) pinch point temperature entering the evaporator saturated-steam temperature the approach point temperature difference, or 388 15 373 F (189.4 C). Then, the energy absorbed by the evaporator, Q1 (gas ow, lb / h)(1.0 heat loss)(gas specic heat, Btu / lb F)(gas-turbine exhaust gas HRSG entering tempergas temperature leaving evaporator, F). Or, Q1 ature, F (140,000)(0.99)(0.27)(980 408) 21.4 MM Btu / h (6.26 MW). The enthalpy absorbed by the steam in the evaporator, Btu / lb (kJ / kg) (enthalpy of the saturated enthalpy of the feedwater entering the evaporator at steam in the HRSG outlet (blowdown percentage)(enthalpy of the saturated liquid of the outlet 373 F) steam enthalpy of the water entering the evaporator, all in Btu / lb). Or, enthalpy (1199.3 345) (0.05)(362.2 345) 855.2 absorbed in the evaporator (Q1, energy absorbed Btu / lb (1992.6 kJ / kg). The quantity of steam generated by the evaporator, Btu / h) / (enthalpy absorbed by the steam in the evaporator, Btu / lb) (21.4 106) / 855.2 25,023 lb / h (11,360 kg / h). 2. Determine the economizer duty and exit gas temperature The economizer duty (steam generated, lb / h)(enthalpy of water entering the economizer, Btu / lb enthalpy enthalpy of the feedwater at 230 F, Btu / lb)(1 blowdown percentage) (25,023)(345 198.5)(1.05) 3.849 MM Btu / h (1.12 MW). (economizer duty) / (gas The gas temperature drop through the economizer heat loss percentage)(specic heat of gas, Btu / lb F) ow rate, lb / h)(1 (3.849 106) / (140,000)(0.99)(0.253) 109.8 F (60.9 C). Hence, the exit-gas temperature from the economizer (steam saturation temperature, F exit-gas temperature from the economizer, F) (408 109) 299 F (148.3 C). 3. Calculate the constant K for evaporator performance In simulating evaporator performance the constant K1 is used to compute revised performance under differing ow conditions. In equation form, K1 ln[(temperature of gas-turbine exhaust gas entering the HRSG, F HRSG saturated steam temperature, F) / (gas temperature leaving the evaporator, F HRSG ln[(980 saturate steam temperature, F)] / (gas ow, lb / h). Substituting, K1 388) / (408 388)] / 140,000 387.6, where the temperatures used reect design condition. 4. Compute the revised evaporator performance Under the revised performance conditions, using the given data and the above value 366) / of K1 and solving for Tg 2, the evaporator exit gas temperature, ln[(880 366)] 387.6(165,000) 0.4; Tg 2 388 F (197.8 C). Then, the evaporator (Tg 2

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.30


POWER GENERATION

duty, using the same equation as in step 1 above (165,000)(0.99)(0.27)(880 388) 21.7 MM Btu / h (6.36 MW). In this calculation, we assumed that the exhaust-gas analysis had not changed. If there are changes in the exhaust-gas analysis, then the gas properties must be evaluated and corrections made for variations in the exhaust-gas temperature. See Waste Heat Boiler Deskbook by V. Ganapathy for ways to do this. 5. Find the assumed duty, Qa, for the economizer Let the economizer leaving-water temperature 360 F (182.2 C). The enthalpy of the feedwater 332 Btu / lb (773.6 kJ / kg); saturated-steam enthalpy 1195.7 Btu/ lb (2785.9 kJ / kg); saturated liquid enthalpy 338.5 Btu / lb (788.7 kJ / kg). Then, (21.5 106) / [(1195.7 332) 0.05 (338.5 the steam ow, as before, 332)] 25,115.7 lb / h (11,043 kg / h). Then, the assumed duty for the economizer, Qa (25,115.7)(1.05)(332 198.5) 3.52 MM Btu / h (1.03 MW). 6. Determine the UA value for the economizer in both design and off-design conditions For the design conditions, UA Q / ( T ), where Q economizer duty from step design temperature conditions from the earlier data in this proce2, above; T (3.84 106) / {[(299 230) (408 373)] / ln(69 / 35)} dure. Solving, UA 76,800 Btu / h F (40.5 kW). For off-design conditions, UA (UA at design conditions)(gas ow at off-design / gas ow at design conditions)0.65 (76,800)(165,000 / 140,000)0.65 85,456 Btu / h F (45.1 kW). 7. Calculate the economizer duty The energy transferred Qt (UA)( T ). Based on 360 F (182.2 C) water leaving 3.52 MM Btu / h (1.03 MW). Solving for tg 2 as before the economizer, Qa 382 [(3.52 106) / (165,000)(0.9)(0.253)] 388 85 303 F (150.6 C). Then, T [(303 230) (388 360)] / ln(73 / 28) 47 F (26.1 C). The energy transferred Qt (UA)( T ) (85,456)(47) 4.01 MM Btu / h (1.18 MW). Since the assumed and transferred duty do not match, i.e., 3.52 MM Btu / h vs. 4.01 MM Btu / h, another iteration is required. Continued iteration will show that Qt 3.55 MM Btu / h (1.04 MW), and the temperature of the water when Qa leaving the economizer 366 F (185.6 C) (saturation) and exit-gas temperature 301 F (149.4 C), the amount of steam generated 25,310 lb / h (11,491 kg / h). Related Calculations. Studying the effect of gas inlet temperature and gas ows on HRSG performance will show that at lower steam generation rates or at lower pressures that the economizer water temperature approaches saturation temperature, a situation called steaming in the economizer. This steaming condition should be avoided by generating more steam by increasing the inlet gas temperature or through supplementary ring, or by reducing exhaust-gas ow. Supplementary ring in an HRSG also improves the efciency of the HRSG in two ways: (1) The economizer acts as a bigger heat sink as more steam and hence more feedwater ows through the economizer. This reduces the exit gas temperature. So with a higher gas inlet temperature to the HRSG we have a lower exit gas temperature, thanks to the economizer. (2) Additional fuel burned in the HRSG reduces the excess air as more air is not added; instead, the excess oxygen is used. In conventional boilers we know that the higher the excess air, the lower the boiler efciency. Similarly, in the HRSG, the efciency increases with more supplementary ring. HRSGs used in combined-cycle steam cycles, Fig. 17, may use multiple pressure levels, gas-turbine steam injection, reheat, selective-catalytic-reduction (SCR) elements for NOx control, and feedwater heating. Such HRSGs require ex-

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

Steam for GT injection To condenser Condensate makeup

To GT steam injection

To I-p turbine

For reheater

Reheat steam to i-p turbine H-p steam to h-p turbine I-p steam Deaerator To I-p superheater I-p steam for deaerator H-p drum I-p drum L-p drum

H-p steam

Reheat steam from h-p turbine SCR

Reheater 2

Reheater 1

I-p superheater

L-p superheater

I-p evaporator

I-p economizer 3

L-p evaporator

H-p superheater 1

H-p superheater 2

H-p evaporator

H-p economizer 1

H-p economizer 2

H-p economizer 3

Feedwater heater

MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.31
H-p economizer bypass Spray for reheater and superheater desuperheating

From deaerator

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

FIGURE 17 HRSGs in combined-cycle steam cycles are somewhat more involved when multiple pressure levels, gas-turbine steam injection, reheat, SCR, and feedwater heating are used (Power).

TABLE 2 HRSG Performance in Fired Mode

Item

Case 1

Case 2

Case 3

MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.32

Gas ow, lb / h (kg / h) Inlet gas temp, F ( C) Firing temperature, F ( C) Burner duty, MM Btu / h (LHV)* Steam ow, lb / h (kg / hr) Steam pressure, lb / in2 (gage) (kPa) Feed water temperature, F ( C) Exit gas temperature, F ( C) System efciency, % Steam duty, MM Btu / h (MW) (6.64) (11.69)

150,000 900 900 0 22,780 200 240 327 68.7 22.67

(68,100) (482.2) (482.2) (0) (10,342) (1378.0) (115.6) (163.9)

150,000 900 1290 17.3 40,000 200 240 315 79.2 39.90

(68,100) (482.2) (698.9) (5.06) (18,160) (1378.0) (115.6) (157.2)

150,000 900 1715 37.6 60,000 200 240 310 84.90 59.90

(68,100) (482.2) (935.0) (11.01) (27,240) (1378.0) (115.6) (154.4) (17.55)

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

*(MW)

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.33

tensive analysis to determine the best arrangement of the various heat-absorbing surfaces. For example, an HRSG generates 22,780 lb / h (10.342 kg / h) of steam in the unred mode. The various parameters are shown in Table 2. Studying this table shows that as the steam generation rate increases, more and more of the fuel energy goes into making steam. Fuel utilization is typically 100 percent in an HRSG. The ASME efciency is also shown in the table. This simulation was done using the HRSG simulation software developed by the author, V. Ganapathy, Heat Transfer Specialist, ABCO Industries, Inc.

PREDICTING HEAT-RECOVERY STEAM GENERATOR (HRSG) TEMPERATURE PROFILES


A gas turbine exhausts 150,000 lb / h (68,100 kg / h) of gas at 900 F (482.2 C) to an HRSG generating steam at 450 lb / in2 (gage) (3100.5 kPa) and 650 F (343.3 C). Feedwater temperature to the HRSG is 240 F (115.6 C) and blowdown is 2 percent. Exhaust gas analysis by percent volume is: CO2 3; H2O 7; O2 15. Determine the steam generation and temperature proles with a 7-lb / in2 (48.2-kPa) pressure 7 457 lb / in2 drop in the superheater, giving an evaporator pressure of 450 (gage) (3148.7 kPa) for a saturation temperature of the steam of 460 F (237.8 C). There is a heat loss of 1 percent in the HRSG. Find the ASME efciency for this HRSG unit.
Calculation Procedure:

1. Select the pinch and approach points for the HRSG Gas turbine heat recovery steam generators (HRSGs) are widely used in cogeneration and combined-cycle plants. Unlike conventionally red steam generators where the rate of steam generation is predetermined and can be achieved, steamow determination in an HRSG requires an analysis of the gas / steam temperature proles. This requirement is mainly because we are starting at a much lower gas temperature900 to 1100 F(482.2 to 593.3 C) at the HRSG inlet, compared to 3000 to 3400 F (1648.9 to 1871.1 C) in a conventionally red boiler. As a result, the exit gas temperature from an HRSG cannot be assumed. It is a function of the operating steam pressure, steam temperature, and pinch and approach points used, Fig. 18. Typically, the pinch and approach points range from 10 to 30 F (5.56 to 16.6 C). Higher values may be used if less steam generation is required. In this case, we ts ) and 10 F (5.56 C) approach ( will use 20 F (11.1 C) pinch point ( Tg 3 ts tw 2). Hence, the gas temperature leaving the evaporator 460 20 480 F (248.9 C), and the water temperature leaving the economizer 460 10 450 F (232.2 C). 2. Compute the steam generation rate The energy transferred to the superheater and evaporator Q1 Q2 (rate of gas ow, lb / h)(gas specic heat, Btu / lb F)(entering gas temperature, F temperature (150,000)(0.267)(900 of gas leaving evaporator, F)(1.0 percent heat loss) 480)(0.99) 16.65 MM Btu / h (4.879 MW). (enThe enthalpy absorbed by the steam in the evaporator and superheater thalpy of the superheated steam at 450 lb / in2 (gage) and 650 F enthalpy of the

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.34


POWER GENERATION

(a)

900F 843F 481F 372F 650F 461F 451F 240F

(482C) (450C) (249C) (189C) (343C) (238C) (233C) (115C)

(b) FIGURE 18 Gas / steam temperature proles.

water entering the evaporator at 450 F) (blowdown percentage)(enthalpy of the saturated liquid at the superheated condition enthalpy of the water entering the evaporator, all expressed in Btu / lb). Or, enthalpy absorbed in the evaporator and superheater (1330.8 431.2) (0.02)(442.3 431.2) 899.8 Btu / lb (2096.5 kJ / kg). To compute the steam generation rate, set up the energy balance, 899.8(Ws ) 16.65 MM Btu / h, where Ws steam generation rate. 3. Calculate the energy absorbed by the superheater and the exit gas temperature Q1, the energy absorbed by the superheater (steam generation rate, lb / h)(enthalpy enthalpy of saturated steam at the superheater of superheated steam, Btu / lb pressure, Btu / lb) (18,502)(1330.8 1204.4) 2.338 MM Btu / h (0.685 MW). (Q1) / (rate of gas-turbine exhaust-gas The superheater gas-temperature drop heat loss)(gas specic heat) (2,338,000) / ow, lb / h)(1.0 57.67 F, say 58 F (32.0 C). Hence, the superheater exit (150,000)(0.99)(0.273) gas temperature 900 58 842 F (450 C). In this calculation the exhaust-gas specic heat is taken as 0.273 because the gas temperature in the superheater is different from the inlet gas temperature. 4. Compute the energy absorbed by the evaporator The total energy absorbed by the superheater and evaporator, from the above, is 16.65 MM Btu / h (4.878 MW). Hence, the evaporator duty Q2 16.65 2.34 14.31 MM Btu / h (4.19 MW).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.35

5. Determine the economizer duty and exit-gas temperature (rate of steam generation, lb / h)(1 blowdown exThe economizer duty, Q3 enthalpy of pressed as a decimal)(enthalpy of water leaving the economizer (18,502)(1.02)(431.2 209.6) 4.182 MM Btu / h (1.225 feedwater at 240 F) MW). (480, the exit gas temperature at the evapThe HRSG exit gas temperature (economizer duty) / (gas-turbine exhaust-gas orator computed in step 1, above) ow, lb / h)(1.0 heat loss)(exhaust gas specic heat) 371.73 F (188.9 C); round to 372 F (188.9 C). Note that you must compute the gas specic heat at the average gas temperature of each of the heat-transmission surfaces. 6. Compute the ASME HRSG efciency The ASME Power Test Code PTC 4.4 denes the efciency of an HRSG as: E efciency (energy absorbed by the steam and uids) / [gas ow inlet enthalpy fuel input to HRSG on LHV basis]. In the above case, E (16.65 4.182)(106) / (150,000 220) 0.63, or 63 percent. In this computation, 220 Btu / lb (512.6 kJ / kg) is the enthalpy of the exhaust gas at 900 F (482.2 C) and (16.65 4.182) is the total energy absorbed by the steam in MM Btu / h (MW). Related Calculations. Note that the exit gas temperature is high. Further, without having done this analytical mathematical analysis, the results could not have been guessed correctly. Minor variations in the efciency will result if one assumes different pinch and approach points. Hence, it is obvious that one cannot assume a value for the exit gas temperaturesay 300 F (148.9 C)and compute the steam generation. The gas / steam temperature prole is also dependent on the steam pressure and steam temperature. The higher the steam temperature, the lower the steam generation rate and the higher the exit gas temperature. Arbitrary assumption of the exit gas temperature or pinch point can lead to temperature cross situations. Table 3 shows the exit gas temperatures for several different steam parameters. From the table, it can be seen that the higher the steam pressure, the higher the saturation temperature, and hence, the higher the exit gas temperature. Also, the higher the steam temperature, the higher the exit gas temperature. This results from the reduced steam generation, resulting in a smaller heat sink at the economizer. This procedure is the work of V. Ganapathy, Heat Transfer Specialist, ABCO Industries, who is the author of several works listed in the references for this section.

TABLE 3 HRSG Exit Gas Temperatures Versus Steam Parameters*

Pressure lb / in2 (gage) (kPa) 100 150 250 400 400 600 600 (689) (1034) (1723) (2756) (2756) (4134) (4134)

Steam temp F ( C) sat sat sat sat 600 sat 750 (170) (186) (208) (231) (316) (254) (399)

Saturation temp F ( C) 338 366 406 448 450 490 492 (170) (186) (208) (231) (232) (254) (256)

Exit gas F ( C) 300 313 332 353 367 373 398 (149) (156) (167) (178) (186) (189) (203)

*Pinch point 20 F (11.1 C); approach 15 F (8.3 C); gas inlet temperature blowdown 0; feedwater temperature 230 F (110 C).

900 F (482.2 C);

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.36


POWER GENERATION

STEAM TURBOGENERATOR EFFICIENCY AND STEAM RATE


A 20,000-kW turbogenerator is supplied with steam at 300 lb / in2 (abs) (2067.0 kPa) and a temperature of 650 F (343.3 C). The backpressure is 1 in (2.54 cm) Hg absolute. At best efciency, the steam rate is 10 lb (25.4 kg) per kWh. (a) What is the combined thermal efciency (CTE) of this unit? (b) What is the combined engine efciency (CEE)? (c) What is the ideal steam rate?
Calculation Procedure:

1. Determine the combined thermal efciency (3413 / wr )(1 / [h1 h2]), where wr (a) Combined thermal efciency, CTE combined steam rate, lb / kWh (kg / kWh); h1 enthalpy of steam at throttle pressure enthalpy of steam at the turbine backpresand temperature, Btu / lb (kJ / kg); h2 sure, Btu / lb (kJ / kg). Using the steam tables and Mollier chart and substituting in this equation, CTE (3413 / 10)(1 / [1340.6 47.06]) 0.2638, or 26.38 percent. 2. Find the combined engine efciency (b) Combined engine efciency, CEE (wi ) / (we ) (weight of steam used by ideal engine, lb / kWh) / (weight of steam used by actual engine, lb / kWh). The weights of steam used may also be expressed as Btu / lb (kJ / kg). Thus, for the ideal h2x engine, the value is 3413 Btu / lb (7952.3 kJ / kg). For the actual turbine, h1 is used, h2x is the enthalpy of the wet steam at exhaust conditions; h1 is as before. Since the steam expands isentropically into the wet region below the dome of the T-S diagram, Fig. 19, we must rst determine the quality of the steam at point 2 either from a T-S diagram or Mollier chart or by calculation. By calculation using S2 0.0914 the method of mixtures and the entropy at each point: S1 (x2)(1.9451). Then x2 (1.6508 0.0914) / 1.9451 0.80, or 80 percent quality. Substituting and summing, using steam-table values, h2x 47.06 0.8(1047.8) 885.3 Btu / lb (2062.7 kJ / kg). (c) To nd the CEE we rst must obtain the ideal steam rate, wi 3413 / (h1 h2x ) 3413 / (1340.6 885.3) 7.496 lb / kWh (3.4 kg / kWh). Now, CEE (7.496 / 10)(100) 74.96 percent. This value is excellent for such a plant and is in a range being achieved today. Related Calculations. Use this approach to analyze the efciency of any turbogenerator used in central-station, industrial, marine, and other plants.

FIGURE 19 T-S diagrams for steam turbine.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.37

TURBOGENERATOR REHEAT-REGENERATIVE CYCLE ALTERNATIVES ANALYSIS


A turbogenerator operates on the reheating-regenerative cycle with one stage of reheat and one regenerative feedwater heater. Throttle steam at 400 lb / in2 (abs) (2756.0 kPa) and 700 F (371.1 C) is used. Exhaust at 2-in (5.08-cm) Hg is taken from the turbine at a pressure of 63 lb / in2 (abs) (434 kPa) for both reheating and feedwater heating with reheat to 700 F (371.1 C). For an ideal turbine working under these conditions, nd: (a) Percentage of throttle steam bled for feedwater heating; (b) Heat converted to work per pound (kg) of throttle steam; (3) Heat supplied per pound (kg) of throttle steam; (d ) Ideal thermal efciency; (e) Other ways to heat feedwater and increase the turbogenerator output. Figure 20 shows the layout of the cycle being considered, along with a Mollier chart of the steam conditions.

Calculation Procedure:

1. Using the steam tables and Mollier chart, list the pertinent steam conditions Using the subscript 1 for throttle conditions, list the key values for the cycle thus: 400 lb / in2 (abs) (2756.0 kPa) 700 F (371.1 C) 1362.2 Btu / lb (3173.9 kJ / kg) 1.6396 1178 Btu / lb (2744.7 kJ / kg) H3 1380.1 Btu / lb (3215.6 kJ / kg) H4 1035.8 (2413.4 kJ / kg) H5 69.1 Btu / lb (161.0 kJ / kg) H6 265.27 Btu / lb (618.07 kJ / kg) P1 t1 H1 S1 H2 2. Determine the percentage of throttle steam bled for feedwater heating (a) Set up the ratio for the feedwater heater of (heat added in the feedwater heater) / (heat supplied to the heater)(100). Or, using the enthalpy data from step 1 above, (H6 H5) / (H2 H5)(100) (265.26 69.1) / (1178 69.1)(100) 17.69 percent of the throttle steam is bled for feedwater heating. 3. Find the heat converted to work per pound (kg) of throttle steam (b) The heat converted to work is the enthalpy difference between the throttle steam and the bleed steam at point 2 plus the enthalpy difference between points 3 and 4 times the percentage of throttle ow between these points. In equation form, heat H1 H2 (1.00 0.1769)(H3 H4) (1362.2 1178) converted to work (0.0823)(1380.1 1035.8) 467.55 Btu / lb (1089.39 kJ / kg). 4. Calculate the heat supplied per pound (kg) of throttle steam (c) The heat supplied per pound (kg) of throttle steam (H1 H6) (H3 H2) (1362.3 265.27) (1380.1 1178) 1299.13 Btu / lb (3026.97 kJ / kg).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.38 Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

FIGURE 20 Cycle layout and TS chart of steam conditions.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.39

5. Compute the ideal thermal efciency (heat converted to work) / (heat (d ) Use the relation, ideal thermal efciency supplied) 467.55 / 1299.13 0.3598, or 35.98 percent. 6. Show other ways to heat feedwater while increasing the turbogenerator output For years, central stations and large industrial steam-turbine power plants shut off feedwater heaters to get additional kilowatts out of a turbogenerator during periods of overloaded electricity demand. When more steam ows through the turbine, the electrical power output increases. While there was a concurrent loss in efciency, this was ignored because the greater output was desperately needed. Today steam turbines are built with more heavily loaded exhaust ends so that the additional capacity is not available. Further, turbine manufacturers place restrictions on the removal of feedwater heaters from service. However, if the steam output of the boiler is less than the design capacity of the steam turbine, because of a conversion to coal ring, additional turbogenerator capacity is available and can be regained at a far lower cost than by adding new generator capacity. Compensation for the colder feedwater can be made, and the lost efciency regained, by using a supplementary fuel source to heat feedwater. This can be done in one of two ways: (1) increase heat input to the existing boiler economizer, or (2) add a separately red external economizer. Additional heat input to a boilers existing economizer can be supplied by induct burners, Fig. 21, from slagging coal combustors, Fig. 22, or from the furnace itself. Since the economizer in a coal-red boiler is of sturdier construction than a heat-recovery steam generator (HRSG) with nned tubing, in-duct burners can be placed closer to the economizer, Fig. 21. Burner ring may be by coal or oil. Slagging coal combustors are under intense development. A low-NOx, low-ash combustor, Fig. 22, supplying combustion gases at 3000 F (1648.9 C) may soon be commercially available. To accommodate any of the changes shown in Fig. 21, a space from 12 (3.66 m) to 15 ft (4.57 m) is needed between the bottom of the primary superheater and the top of the economizer. This space is required for the installation of the in-duct

FIGURE 21 Heat input to the economizer may be increased by the addition of induct burners, by bypassing hot furnace gases into the gas path ahead of the economizer, or by recirculation (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.40


POWER GENERATION

FIGURE 22 Slagging combustors can be arranged to inject hot combustion gases into gas passages ahead of economizer (Power).

H-p turbine

I-p turbine

L-p turbine

Generator

FIGURE 23 Gas-turbine exhaust gases can be used in place of high-pressure heaters, using a compact heat exchanger (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.41

burners or for the adequate mixing of gas streams if the furnace or an external combustor is used to supply the additional heat. Another approach is to install a separately red external economizer in series or parallel with the existing economizer, which could be red by a variety of fuels. The most attractive possibility is to use waste heat from a gas-turbine exhaust, Fig. 23. The output of this simple combined-cycle arrangement would actually be higher than the combined capabilities of the derated plant and the gas turbine. The steam-cycle arrangement for the combined plant is shown in Fig. 23. Feedwater is bypassed around the high-pressure regenerative heaters to an external lowcost, nned-tube heat exchanger, Fig. 24, where waste heat from the gas turbine is recovered. When high-pressure feedwater heaters are shut off, steam ow through the intermediate- and low-pressure turbine sections increases and becomes closer to the full-load design ow. The reheat expansion line moves left on the Mollier chart from its derated position, Fig. 25. With steam ow closer to the design value, the exhaust losses per pound (kg) of steam, Fig. 26, are lower than at the derated load.

FIGURE 24 Gas-turbine heat-recovery nned-tube heat exchanger is simple and needs no elaborate controls (Power).

FIGURE 25 Reheat expansion line is moved to the left on the T-S chart, increasing power output (Power).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.42


POWER GENERATION

FIGURE 26 Heat loss in steam-turbine exhaust is reduced when operating at rated ow (Power).

The data and illustrations in this step 6 are based on the work of E. S. Miliares and P. J. Kelleher, Energotechnology Corp., as reported in Power magazine.

TURBINE-EXHAUST STEAM ENTHALPY AND MOISTURE CONTENT


What is the enthalpy and percent moisture of the steam entering a surface condenser from the steam turbine whose Mollier chart is shown in Fig. 27? The turbine is delivering 20,000 kW and is supplied steam at 850 lb / in2 (abs) (5856.5 kPa) and 900 F (482.2 C); the exhaust pressure is 1.5 in (3.81 cm) Hg absolute. The steam rate, when operating straight condensing, is 7.70 lb / delivered kWh (3.495 kg / kWh) and the generator efciency is 98 percent.

1453 Btu/lb (3385 kJ/kg) 850 psia (5856 kPa) 1.5 in. Hg (3.8 cm Hg)

898 Btu/lb (2092 kJ/kg) 1000 Btu/lb (2330 kJ/kg)

FIGURE 27 Mollier chart for turbine exhaust conditions.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.43

Calculation Procedure:

1. Compute the engine efciency of the turbine 3413 / (ws)(H1 Hc), where Ee engine efciency; ws Use the relation Ee steam rate of the turbine when operating straight condensing in the units given above; enthalpies H1 and Hc are as shown in the Mollier chart. Substituting, Ee 3413 / (7.7)(1453 898) 0.7986 for ideal conditions. 2. Find the Rankine engine efciency for the actual turbine The Rankine engine efciency for this turbine is: (0.7986 / 0.98) 0.814 (H1 Hc ) / (H1 Hc). Solving, (H1 Hc ) 0.814(555) 452.3 Btu / lb (1053.8 kJ / kg). At the end of the actual expansion of the steam in the turbine, Hc 1453 452.3 1000.7 Btu / lb (2331.6 kJ / kg) enthalpy. 3. Determine the moisture of the steam Referring to the Mollier chart where Hc crosses the pressure line of 1.5 in (3.81 cm) Hg, the moisture percent is found to be 9.6 percent. Related Calculations. The Mollier chart can be a powerful and quick reference for solving steam expansion problems in plants of all typesutility, industrial, commercial, and marine.

STEAM TURBINE NO-LOAD AND PARTIAL-LOAD STEAM FLOW RATES


A 40,000-kW straight-ow condensing industrial steam turbogenerator unit is supplied steam at 800 lb / in2 (abs) (5512 kPa) and 800 F (426.7 C) and is to exhaust at 3 in (76 cm) Hg absolute. The half-load and full-load throttle steam ows are estimated to be 194,000 lb / h (88,076 kg / h) and 356,000 lb / h (161,624 kg / h), respectively. The mechanical efciency of the turbine is 99 percent and the generator efciency is 98 percent. Find (a) the no-load throttle steam ow; (b) the heat rate of the unit expressed as a function of the kW output; (c) the internal steam rate of the turbine at 30 percent of full load.

Calculation Procedure:

1. Find the difference between full-load and half-load steam rates and the no-load rate (a) Assume a straight-line rating characteristic and plot Fig. 28a. This assumption is a safe one for steam turbines in this capacity range. Then, the difference between full-load and half-load steam rates is 356,000 194,000 162,000 lb / h (73,548 kg / h). The no-load steam rate will then be (half-load rate) (difference between full-load and half-load rates) 194,000 162,000 32,000 lb / h (14,528 kg / h). 2. Determine the steam rate and heat rate at quarter-load points (b) Using Fig. 28b, we see that the actual turbine efciency, Et 3413 / (ws)(H1 H), ws steam ow, lb / kWh (kg / kWh); H1 enthalpy of entering steam, Btu / lb (kJ / kg); H enthalpy of condensate at the exhaust pressure, Btu / lb (kJ / kg). Further, turbine heat rate 3413 / Et Btu / kWh (kJ / kWh) wk(H1 H), where

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.44


POWER GENERATION

(a) 356,000 lb/hr (161,624 kg/hr)

(b) 194,000 lb/hr (88,076 kg/hr)

FIGURE 28 (a) Straight-line rating characteristic. (b) T-S diagram.

wk the actual steam rate, lb / kWh (kg / kWh) w ws / kW output, where the symbols are as dened earlier. 32,000 no-load throttle ow (difference between full-load Substituting ws 32,000 and half-load throttle ow rate / kW output at half load)(kW output) (162,000 / 20,000)(kW) 32,000 8.1 kW for this turbine-generator set. Also wk (32,000 / kW) 8.1. 1398 Btu / lb (3257.3 kJ / kg); H 83 Using the steam tables, we nd H1 Btu / lb (193.4 kJ / kg). Then, H1 H 1315 Btu / lb (3063.9 kJ / kg). Substituting, heat rate [(1315)(32,000) / (kW)] (1316)(8.1) 10.651.5 (42,080,000 / kW). Computing the steam rate and heat rate for the quarter-load points for this turbine-generator we nd: At full load, ws At 34 load, ws At 2 load, ws At full At 34 At 12 At 14 At 4 load, ws load, heat rate load, heat rate load, heat rate load, heat rate
1 1

8.9 lb / kWh (4.04 kg / kWh) 9.17 lb / kWh (4.16 kg / kWh) 9.7 lb / kWh (4.4 kg / kWh) 11.3 lb / kWh (5.13 kg / kWh) 11,700 Btu / kWh (27,261 kJ / kWh) 12,080 Btu / kWh (28,146 kJ / kWh) 12,770 Btu / kWh (29,754 kJ / kWh) 14,870 Btu / kWh (34,647 kJ / kWh)

3. Determine the internal steam rate of the turbine 3413 / (wk)(H1 Hc), where Ee (c) For the turbine and generator combined, Ee turbine engine efciency; Hc enthalpy of the steam at the condenser; other symbols as given earlier. Since, from the steam tables, H1 1398 Btu / lb (3257.3 912 Btu / lb (2124.9 kJ / kg); then (H1 H c) 486 Btu / lb (1132.4 kJ / kg); Hc kJ / kg). From earlier steps, ws 356,000 lb / h (161,624 kg / h) at full-load; ws 32,000 lb / h (14,528 kg / h) at no-load. For the full-load range the total change is 356,000 32,000 324,000 lb / h (147,096 kg / h). Then, ws at 30 percent load [(32,000) 0.30(324,000)] / 0.30(40,000) 10.77 lb / kWh (4.88 kg / kWh). Then, Ee 3413 / (10.77)(486) 0.652 for combined turbine and generator.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.45

If the internal efciency of the turbine (not including the friction loss) Ei, then Ei 2545 / (wa)(H1 Hc). Thus Ei Ee / (turbine mechanical efciency)(generator 0.652 / (0.99)(0.98) 0.672. Then, the actual steam rate per efciency). Or Ei horsepower (kW) is wa 2545 / (Ei)(H1 Hc) 2545 / (0.672)(486) 7.79 lb / hp (4.74 kg / kW). Related Calculations. Use this approach to analyze any steam turbineutility, industrial, commercial, marine, etc.to determine the throttle steam ow and heat rate.

POWER PLANT PERFORMANCE BASED ON TEST DATA


A test on an industrial turbogenerator gave these data: 29,760 kW delivered with a throttle ow of 307,590 lb / h (139,646 kg / h) of steam at 245 lb / in2 (abs) (1688 kPa) with superheat at the throttle of 252 F (454 C); exhaust pressure 0.964 in (2.45 cm) Hg (abs); pressure at the one bleed point, Fig. 29a, 28.73 in (72.97 cm) Hg (abs); temperature of feedwater leaving bleed heater 163 F (72.8 C). For the corresponding ideal unit, nd: (a) percent throttle steam bled, (b) net work for each pound of throttle steam, (c) ideal steam rate, and (d ) cycle efciency. For the actual unit nd, (e) the combined steam rate, () combined thermal efciency, and (g) combined engine efciency.
Calculation Procedure:

1. Determine the steam properties at key points in the cycle Using a Mollier chart and the steam tables, plot the cycle as in Fig. 29b. Then, S1 1.676; H1 1366 Btu / lb (3183 kJ / kg); H2 1160 Btu / lb (2577 kJ / kg); P2 14.11 lb / in2 (abs) (97.2 kPa); H3 130.85 Btu / lb (304.9 kJ / kg); P3 5.089 lb / 46.92 Btu / lb (109.3 kJ / kg); P4 0.4735 lb / in2 (abs) in2 (abs) (35.1 kPa); H4 (3.3 kPa); H5 177.9 Btu / lb (414.5 kJ / kg). (a) The percent throttle steam bled is found from: 100 (H5 H4) / (H2 H4) 100 (177.9 46.92) / (1106 46.92) 12.41 percent. 2. Find the amount of heat converted to work (b) Use the relation, heat converted to work, hw H1 H2 (1 m2)(H2 H7), percent throttle steam bled, H7 enthalpy of exhaust steam in the where m2 (1366 1106) (1 condenser. Substituting, heat converted to work, hw 0.1241)(1106 924.36) 419.1 Btu / lb (976.5 kJ / kg). 3. Compute the ideal steam rate (c) Use the relation, ideal steam rate, lr 8.14 lb / kWh (3.69 kg / kWh). 3413 Btu / kWhr / hw. Or, lr 3413 / 419.1

4. Find the cycle efciency of the ideal cycle (d ) Cycle efciency, Ce (heat converted into work / heat supplied). Or hw / (H1 H3); substituting, Ce 419.1 / (1366 130.85) 0.3393, or 33.9 percent. 5. Determine the combined steam rate (e) The combined steam rate for the actual unit is Rc lb steam consumed / kWh generated. Or Rc 307,590 / 29,760 10.34 lb / kWh (4.69 kg / kWh).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.46


POWER GENERATION

(a)

(b) 245 psia (1688 kPa) 252F (454C) 0.963 in. Hg (2.45 cm Hg) 28.73 in. Hg (72.97 cm Hg) 163F (72.8C)

FIGURE 29 (a) Cycle diagram with test conditions. (b) T-S diagram for cycle.

6. Find the combined thermal efciency of the actual unit () The combined thermal efciency, TEc 3413 / heat supplied. Or TEc 3413 / 10.34(H1 H3) 35413 / 10.34(1366 130.85) 0.267, or 26.7 percent. 7. Compute the combined engine efciency (g) The combined engine efciency TEc / Cc, or 26.7 / 33.9 0.7876, or 78.76 percent. Related Calculations. Use this general procedure to determine the percent bleed steam, net work of each pound of throttle steam, ideal steam rate, cycle efciency, combined thermal efciency and combined engine efciency for steamturbine installations in central stations, industrial, municipal and marine installations. Any standard set of steam tables and a Mollier chart are sufciently accurate for usual design purposes.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.47

DETERMINING TURBOGENERATOR STEAM RATE AT VARIOUS LOADS


A 100-MW turbogenerator is supplied steam at 1250 lb / in2 (abs) (8612.5 kPa) and 1000 F (537.8 C) with a condenser pressure of 2 in (5.08 cm) Hg (abs). At rated load, the turbine uses 1,000,000 lb (454,000 kg) of steam per hour; at zero load, steam ow is 50,000 lb / h (22,700 kg / h). What is the steam rate in pounds (kg) per kWh at 44, 34, 24, and 14 load?

Calculation Procedure:

1. Write the steam-ow equation for this turbogenerator The curve of steam consumption, called the Willians line, is practically a straight line for steam turbines operating without overloads. Hence, we can assume a straight line for this turbogenerator. If the Willians line is extended to intercept the Y (vertical) axis for total steam ow per hour, this intercept represents the steam required to operate the turbine when delivering no power. This no-load steam ow50,000 lb / h (22,700 kg / h) for this turbineis the ow rate required to overcome the friction of the turbine and the windage, governor and oil-pump drive power, etc., and for meeting the losses caused by turbulence, leakage, and radiation under no-load conditions. Using the data provided, the steam rate equation can be written as [(50 / L) 9.5] (F / L) [50 (1000 50) / 100(L)] / (L), where F full-load steam ow, lb / h (kg / h); L load percent. 2. Compute the steam ow at various loads Use the equation above thus:
Steam rate lb / kWh (kg / kWh) 25 50 50 75 50 100
50 50

Load fraction
1 2

Load, MW 100 100 100 100


1 2

4 4 3 4 4 4

4 4 3 4 4 4

25 50 75 100

9.5 9.5 9.5 9.5

11.5 (5.22) 10.5 (4.77) 10.17 (4.62) 10.00 (4.54)

Related Calculations. The Willians line is a useful tool for analyzing steamturbine steam requirements. As a check on its validity, compare actual turbine performance steam conditions with those computed using this procedure. The agreement is startlingly accurate.

ANALYSIS OF REHEATING-REGENERATIVE TURBINE CYCLE


An industrial turbogenerator operates on the reheating-regenerative cycle with one reheat and one regenerative feedwater heater. Throttle steam at 400 lb / in2 (abs) (2756 kPa) and 700 F (371 C) is used. Exhaust is at 2 in (5.1 cm) Hg (abs). Steam is taken from the turbine at a pressure of 63 lb / in2 (abs) (434 kPa) for both reheating

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.48


POWER GENERATION

and feedwater heating. Reheat is to 700 F (371 C). For the ideal turbine working under these conditions nd: (a) percentage of throttle steam bled for feedwater heating, (b) heat converted to work per pound (kg) of throttle steam, (c) heat supplied per pound (kg) of throttle steam, (d ) ideal thermal efciency, (e) T-S, temperature-entropy, diagram and layout of cycle.
Calculation Procedure:

1. Determine the cycle enthalpies, pressures, and entropies Using standard steam tables and a Mollier chart, draw the cycle and T-S plot, Fig. 400 lb / in2 (abs) (2756 kPa); t1 700 F (371 C); H1 30a and b. Then, P1 1362.3 Btu / lb (3174 kJ / kg); S1 1.6396; H2 1178 Btu / lb (2745 kJ / kg); Hg 1380.1 Btu / lb (3216 kJ / kg); Sg 1.8543. (H6 H5) / (H2 H 5) (196.15 / 1107.9) (a) Percent throttle steam bled 0.1771, or 17.71 percent. 2. Find the amount of heat converted to work per pound (kg) of throttle steam (b) The amount of heat converted to work per pound (kg) of throttle steam (H1 H2) (1 0.1771)(Hg H4) 467.3 Btu / lb (1088.8 kJ / kg). 3. Compute the heat supplied per pound (kg) of throttle steam (c) The heat supplied per pound (kg) of throttle steam (H1 H6) 1299.1 Btu / lb (3026.9 kJ / kg). (Hg H2)

4. Determine the ideal thermal efciency (d ) The ideal thermal efciency (heat recovered per pound [kg] of throttle steam)/ 467.3 / 1299.13 0.3597, or (heat supplied per pound [kg] of throttle steam) 35.97 percent. The T-S diagram and cycle layout can be drawn as shown in Fig. 30a and b.

(a)

(b)

400 psia (2756 kPa) 2 in. Hg (5.1 cm Hg)

700F (371C)

63 psia (434 kPa)

FIGURE 30 (a) Cycle diagram. (b) T-S diagram for cycle in (a).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.49

Related Calculations. This general procedure can be used for any turbine cycle where reheating and feedwater heating are part of the design. Note that the enthalpy and entropy values read from the Mollier chart, or interpolated from the steam tables, may differ slightly from those given here. This is to be expected where judgement comes into play. The slight differences are unimportant in the analysis of the cycle. The procedure outlined here is valid for industrial, utility, commercial, and marine turbines used to produce power.

STEAM RATE FOR REHEAT-REGENERATIVE CYCLE


Steam is supplied at 600 lb / in2 (abs) (4134 kPa) and 740 F (393 C) to a steam turbine operating on the reheat-regenerative cycle. After expanding to 100 lb / in2 (abs) (689 kPa), the steam is reheated to 700 F (371 C). Expansion then continues to 10 lb / in2 (abs) (68.9 kPa) but at 30 lb / in2 (abs) (207 kPa) some steam is extracted for feedwater heating in a direct-contact heater. Assuming ideal operation with no losses, nd: (a) steam extracted as a percentage of steam supplied to the throttle, (b) steam rate in pounds (kg) per kWh; (c) thermal efciency of the turbine, (d ) quality or superheat of the exhaust if in the actual turbine combined efciency is 72 percent, generator efciency is 94 percent, and actual extraction is the same as the ideal.
Calculation Procedure:

1. Assemble the key enthalpies, entropies, and pressures for the cycle Using the steam tables and a Mollier chart, list the following pressures, temperatures, enthalpies, and entropies for the cycle, Fig. 31a: Pl 600 lb / in2 (abs) (4134 740 F (393 C); P2 100 lb / in2 (abs) (689 kPa); t3 700 F (371 C); kPa); t1 Px 30 lb / in2 (abs) (207 kPa); pc 1 lb / in2 (abs) (6.89 kPa); H1 1372 Btu / lb (3197 kJ / kg); S1 entropy 1.605; H2 1188 Btu / lb (2768 kJ / kg); H3 1377 1.802; Hx 1245 Btu / lb (2901 kJ / kg); Hc 1007 Btu / lb (3208 kJ / kg); S3 Btu / lb (2346 kJ / kg); H 70 Btu / lb (163 kJ / kg); Hx 219 Btu / lb (510 kJ / kg). Plot Fig. 31b as a skeleton Mollier chart to show the cycle processes. 2. Compute the percent steam extracted for the feedwater heater (a) The steam extracted for the feedwater heater, x, (Hx H)(Hx 70) / (1245 70) 0.1268, or 12.68 percent. H) (219

3. Find the turbine steam rate (b) For the Rankine-cycle steam rate, ws 3413 / (H1 Hc). For this cycle, ws 3413 / [(H1 H2) x(H3 Hx) (1 x)(H3 Hc)]. Or, ws 3413 / [1372 1188) 0.1268(1377 1245) (1 0.1268)(1377 1007)] 6.52 lb / kWh (2.96 kg / kWh). 4. Calculate the turbine thermal efciency (c) The thermal efciency, Et [(H1 H2) x(H3 [H3 H2) (H1 Hx)]. Or, Et [(1372 1188) Hx) (1 x)(H3 Hc)] / (0.1268)(1377 1245)

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.50


POWER GENERATION

(a)

(b) 600 psia (4134 kPa) 740F (393C) 700F (371C) 100 psia (68.9 kPa) 1188 Btu/lb (2768 kJ/kg) 1372 Btu/lb (3197 kJ/kg) 1245 Btu/lb (2901 kJ/kg) 1 psia (6.89 kPa) 30 psia (207 kPa) 1007 Btu/lb (2346 kJ/kg) 70 Btu/lb (163 kJ/kg) FIGURE 31 (a) Cycle diagram. (b) H-S chart for cycle in (a).

(1 0.1268)(1377 1007)] / [(1377 1188) (1372 219) 0.3903, or 39 percent. It is interesting to note that in an ideal cycle the thermal efciency of the turbine is the same as that of the cycle. 5. Determine the condition of the exhaust (actual turbine combined (d ) The engine efciency of the turbine alone efciency) / actual generator efciency). Or, using the given data, engine efciency of the turbine alone 0.72 / 0.94 0.765. Using the computed engine efciency of the turbine alone and the Mollier chart, Hc ) 0.765(H3 HC) 283. Solving, Hc H3 283 1094 Btu / lb (H3 (2549 kJ / kg). From the Mollier chart, the condition at Hc is 1.1 percent moisture. The exhaust steam quality is therefore 100 1.1 98.9 percent.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.51

Related Calculations. This procedure is valid for a variety of cycle arrangements for industrial, central-station, commercial and marine plants. By using a combination of the steam tables, Mollier chart and cycle diagram, a full analysis of the plant can be quickly made.

BINARY CYCLE PLANT EFFICIENCY ANALYSIS


A binary cycle steam and mercury plant is being considered by a public utility. Steam and mercury temperature will be 1000 F (538 C). The mercury is condensed in the steam boiler, Fig. 32a at 10 lb / in2 (abs) (68.9 kPa) and the steam pressure is 1200 lb / in2 (abs) (8268 kPa). Condenser pressure is 1 lb / in2 (abs) (6.89 kPa). Expansions in both turbines are assumed to be at constant entropy. The steam cycle has superheat but no reheat. Find the efciency of the proposed binary cycle. Find the cycle efciency without mercury.

Calculation Procedure:

1. Tabulate the key enthalpies and entropies for the cycle Set up two columns, thus:
Mercury cycle Hm1 Sm1 Sme Hmf 151.1 Btu / lb (352 kJ / kg) 0.1194 0.0094 22.6 Btu / lb (52.7 kJ / kg) Hs1 Ss1 Hsf Steam cycle 1499.2 Btu / lb (3493 kJ / kg) 1.6293 69.7 Btu / lb (162.4 kJ / kg)

2. Compute the quality of the exhaust for each vapor Since expansion in each turbine is at constant entropy, Fig. 32b, the quality for the mercury exhaust, xm is: 0.1194 0.0299 xm(0.1121); xm 0.798. For the steam cycle, the quality, xs is: 1.6293 0.1326 xs(1.8456); xs 0.81. 3. Find the exhaust enthalpy for each vapor Using the properties of mercury from a set of tables, the enthalpy of the mercury exhaust, Hme 22.6 0.798(123) 120.7 Btu / lb (281.2 kJ / kg). The enthalpy of the condensed mercury, Hmf 22.6 Btu / lb (52.7 kJ / kg). For the exhaust steam, the enthalpy Hse 69.7 0.81(1036.3) 909.1 Btu / lb (2118 kJ / kg), using steam-table data. The enthalpy of the condensed steam, Hsf 69.7 Btu / lb (162.4 kJ / kg). Assuming 98 percent quality steam leaving the mercury condenser, then the 571.7 enthalpy of the wet steam leaving the mercury condenser, Hsw 0.98(611.7) 1171.2 Btu / lb (2728 kJ / kg). 4. Write the heat balance around the mercury condenser The steam heat gain Hsw Hsf 1171.2 69.7 1101.5 Btu / lb (2566.5 kJ / kg). Now, the mercury heat loss Hme Hmf 120.7 98.1 98.1 Btu / lb

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.52


POWER GENERATION

FIGURE 32 (a) Binary cycle. (b) T-S diagram for binary cycle.

(228.6 kJ / kg). The weight of mercury per pound (kg) of steam gain / mercury heat loss 1101.5 / 98.1 11.23.

steam heat

5. Determine the heat input and work done per pound (kg) of steam The heat input per pound of steam is: For mercury (lb Hg / lb steam)(Hm1 Hmf) 11.23(151.1 22.6) 1443.05 Btu (1522.5 J). For steam (Hs1 Hsw) 1499.2 1171.7 327.5 Btu (345.5 J). Summing these two results gives 327.5 1770.55 Btu (1867.9 J) as the heat input per pound (kg) of 1443.05 steam.
Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.53

The work done per pound (kg) of steam is: For mercury (lb Hg / lb steam)(hm1 Hme) 11.23(151.1 120.7) 341.4 Btu (360.2 J). For steam Hc1 Hse 1499.2 909.1 590.1 Btu (622.6 J). Summing, as before, the total work done per pound (kg) of steam 931.5 Btu (982.7 J). 6. Compute the binary cycle efciency The binary cycle efciency (work done per pound (kg) of steam) / (heat input per pound (kg) of steam). Or binary cycle efciency 931.5 / 1770.55 0.526, or 52.6 percent. 7. Calculate the steam cycle efciency without the mercury topping turbine The steam cycle efciency without the mercury topping turbine (work done per Hsf) 590.1 / (1499.2 69.7) 0.4128, or 41.3 pound (kg) of steam) / (Hs1 percent. Related Calculations. Any binary cycle being considered for an installation depends on the effects of the difference in thermodynamic properties of the two pure uids involved. For example, steam works under relatively high pressures with an attendant relatively low temperature. Mercury, by comparison, has the vapor characteristic of operating under low pressures with attendant high temperature. In a mercury-vapor binary cycle, the pressures are selected so the mercury vapor condenses at a temperature higher than that at which steam evaporates. The processes of mercury vapor condensation and steam evaporation take place in a common vessel called the condenser-boiler, which is the heart of the cycle. In the steam portion of this cycle, condenser water carries away the heat of steam condensation; in the mercury portion of the cycle it is the steam which picks up the heat of condensation of the mercury vapor. Hence, there is a great saving in heat and the economies effected reect the consequent improvement in cycle efciency. The same furnace serves the mercury boiler and the steam superheater. Mercury vapor is only condensed, not superheated. And if the condenser-boiler is physically high enough above the mercury boiler, the head of mercury is great enough to return the liquid mercury to the boiler by gravity, making the use of a mercury feed pump unnecessary. To avoid the high cost entailed with using mercury, a number of man-made solutions have been developed for binary vapor cycles. Their use, however, has been limited because the conventional steam cycle is usually lower in cost. And with the advent of the aero-derivative gas turbine, which is relatively low cost and can be installed quickly in conjunction with heat-recovery steam generators, binary cycles have lost popularity. But it is useful for engineers to have a comprehension of such cycles. Why? Because they may return to favor in the future.

Conventional Steam Cycles


FINDING COGENERATION SYSTEM EFFICIENCY VS. A CONVENTIONAL STEAM CYCLE
An industrial plant has 60,000 lb / h (27,240 kg / h) of superheated steam at 1000 lb / in2 (abs) (6890 kPa) and 900 F (482.2 C) available. Two options are being considered for use of this steam: (1) expanding the steam in a steam turbine having a 70 percent efciency to 1 lb / in2 (abs) (6.89 kPa), and (2) expand the steam in a turbine to 200 lb / in2 (abs) (1378 kPa) generating electricity and utilizing the low-

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.54


POWER GENERATION

pressure exhaust steam for process heating. Evaluate the two schemes for energy efciency when the boiler has an 82 percent efciency on a HHV basis.

Calculation Procedure:

1. Determine the enthalpies of the steam at the turbine inlet and after isentropic expansion Cogeneration systems generate power and process steam from the same fuel source. Process plants generating electricity from steam produced in a boiler and using the same steam after expansion in a steam turbine for process heating of some kind are examples of cogeneration systems. Conventional steam-turbine power plants have a maximum efciency of about 40 percent as most of the energy is wasted in the condensing-system cooling water. In a typical cogeneration system the exhaust steam from the turbine is used for process purposes after expansion through the steam turbine; hence, its enthalpy is fully utilized. Thus, cogeneration schemes are more efcient. At 1000 lb / in2 (abs) (6890 kPa) and 900 F (482.2 C), the enthalpy, h1 1448 Btu / lb (3368 kJ / kg) from the steam tables. The entropy of steam at this condition, from the steam tables, is 1.6121 Btu / lb F (6.748 kJ / kg K). At 1 lb / in2 (abs) (6.89 kPa), the entropy of the saturated liquid, s, is 0.1326 Btu / lb F (0.555 kJ / kg K), and the entropy of the saturated vapor, sg is 1.9782 Btu / lb F (8.28 kJ / kg K), again from the steam tables. Now we must determine the quality of the steam, X, at the exhaust of the steam turbine at 1 lb / in2 (abs) (6.89 kPa) from (entropy at turbine inlet condition) (entropy at outlet condition)(X) (1 X)(entropy of the saturated uid at the outlet condition); or X 0.80. The enthalpy of steam corresponding to this quality condition is h2s (enthalpy of the saturated steam at 1 lb / in2 (abs))(X) (enthalpy of the saturated liquid at 1 lb / in2 (abs))(1 X) (1106)(0.80) (1 0.80)(70) 900 Btu / lb (2124 kJ / kg). 2. Compute the power output of the turbine Use the equation P (Ws)(et)(h1 h2s) / 3413, where P electrical power generated, kW; Ws steam ow through the turbine, lb / h (kg / h); et turbine efciency enthalpy of the steam at the turbine inlet, Btu / lb expressed as a decimal; h1 (kJ / kg); h2s enthalpy of the steam after isentropic expansion through the turbine, (60,000)(0.70)(1448 900) / 3413 6743 kW Btu / lb (kJ / kg). Substituting, P (6743)(3413) 23 MM Btu / h (24.26 MM kJ). 3. Find the steam enthalpy after expansion in the cogeneration scheme The steam is utilized for process heating after expansion to 200 lb / in2 (abs) (1378 kPa) in the backpressure turbine. We must compute the enthalpy of the steam after expansion in order to nd the energy available. At 200 lb / in2 (abs) (1378 kPa), using the same procedure as in step 1 above, h2s 1257.7 Btu / lb (2925.4 kJ / kg). Since we know the turbine efciency we can use the equation, (et)(h1 h2s) (h1 h2); or (0.70)(1448 1257.7) (1448 h2); h2 1315 Btu / lb (3058.7 kJ / kg), h2 actual enthalpy after expansion, Btu / lb (kJ / kg). 4. Determine the electrical output of the cogeneration plant Since the efciency of the turbine is already factored into the exhaust enthalpy of the cogeneration turbine, use the relation, P Ws(h1 h2) / 3413, where the symbols are as dened earlier. Or, P 60,000(1448 1315) / 3413 2338 kW.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.55

5. Compute the total energy output of the cogeneration plant Assuming that the latent heat of the steam at 200 lb / in2 (abs) (1378 kPa) is available for industrial process heating, the total energy output of the cogeneration scheme electrical output (steam ow, lb / h)(latent heat of the exhaust steam, Btu / lb). Since, from the steam tables, the latent heat of steam at 200 lb / in2 (abs) (1378 kPa) 834 Btu / lb (1939.9 kJ / kg), total energy output of the cogeneration cycle (2338 kW)(3413) (60,000)(834) 58 MM Btu / h (61.2 MM kJ / h). Since the total energy output of the conventional cycle was 23 MM Btu / h (24.3 MM kJ / h), the ratio of the cogeneration output vs. the conventional output 58 / 23 2.52. Thus, about 2.5 times as much energy is derived from the cogeneration cycle as from the conventional cycle. 6. Find the comparative efciencies of the two cycles The boiler input (weight of steam generated, lb / h)(enthalpy of superheated steam at boiler outlet, Btu / lb enthalpy of feedwater entering the boiler, Btu / lb) / (boiler efciency, expressed as a decimal). Or, boiler input (60,000)(1448 200) / 0.82 91.3 MM Btu / h (96.3 MM kJ / h). The efciency of the conventional cycle is 25 percent. For the cogeneration cycle, the efciency therefore (23 / 91.3)(100) (58 / 91.3)(10) 63.5 percent. Related Calculations. This real-life example shows why cogeneration is such a popular alternative in todays world of power generation. In this study the cogeneration scheme is more than twice as efcient as the conventional cycle63.5 percent vs. 25 percent. Higher efciencies could be obtained if the boiler outlet steam pressure were higher than 1000 lb / in2 (abs) (6890 kPa). However, the pressure used here is typical of todays industrial installations using cogeneration to save energy and conserve the environment. This procedure is the work of V. Ganapathy, Heat Transfer Specialist, ABCO Industries, Inc.

BLEED-STEAM REGENERATIVE CYCLE LAYOUT AND T-S PLOT


Sketch the cycle layout, T-S diagram, and energy-ow chart for a regenerative bleed-steam turbine plant having three feedwater heaters and four feed pumps. Write the equations for the work-output available energy and the energy rejected to the condenser.

Calculation Procedure:

1. Sketch the cycle layout Figure 33 shows a typical practical regenerative cycle having three feedwater heaters and four feedwater pumps. Number each point where steam enters and leaves the turbine and where steam enters or leaves the condenser and boiler. Also number the points in the feedwater cycle where feedwater enters and leaves a heater. Indicate the heater steam ow by m with a subscript corresponding to the heater number. Use Wp and a suitable subscript to indicate the pump work for each feed pump, except the last, which is labeled WpF . The heat input to the steam generator is Qa ; the work output of the steam turbine is We ; the heat rejected by the condenser is Qr .

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.56


POWER GENERATION

FIGURE 33 Regenerative steam cycle uses bleed steam.

2. Sketch the T-S diagram for the cycle To analyze any steam cycle, trace the ow of 1 lb (0.5 kg) of steam through the system. Thus, in this cycle, 1 lb (0.5 kg) of steam leaves the steam generator at point 2 and ows to the turbine. From state 2 to 3, 1 lb (0.5 kg) of steam expands at constant entropy (assumed) through the turbine, producing work output W1 H2 H3, represented by area 1-a -2-3 on the T-S diagram, Fig. 34a . At point 3, some steam is bled from the turbine to heat the feedwater passing through heater 1. The quantity of steam bled, m1 lb is less than the 1 lb (0.5 kg) owing between points 2 and 3. Plot stages 2 and 3 on the T-S diagram, Fig. 34a . From point 3 to 4, the quantity of steam owing through the turbine is 1 m1 lb. This steam produces work output W2 H3 H4. Plot point 4 on the T-S diagram. Then, area 1-3-4-12 represents the work output W2, Fig. 34a . At point 4, steam is bled to heater 2. The weight of this steam is m2 lb. From point 4, the steam continues to ow through the turbine to point 5, Fig. 34a . The weight of the steam owing between points 4 and 5 is 1 m1 m2 lb. Plot point 5 on the T-S diagram, Fig. 34a . The work output between points 4 and 5, W3 H4 H5, is represented by area 4-5-10-11 on the T-S diagram. At point 5, steam is bled to heater 3. The weight of this bleed steam is m3 lb. From point 5, steam continues to ow through the turbine to exhaust at point 6, Fig. 34a . The weight of steam owing between points 5 and 6 is 1 m1 m2 m3 lb. Plot point 6 on the T-S diagram, Fig. 34a . The work output between points 5 and 6 is W4 H5 H6, represented by area 5-6-7-9 on the T-S diagram, Fig. 34a . Area Qr represents the heat given up by 1 lb (0.5 kg) of exhaust steam. Similarly, the area marked Qa represents the heat absorbed by 1 lb (0.5 kg) of water in the steam generator. 3. Alter the T-S diagram to show actual cycle conditions As plotted in Fig. 34a, Qa is true for this cycle since 1 lb (0.5 kg) of water ows through the steam generator and the rst section of the turbine. But Qr is much too large; only 1 m1 m2 m3 lb of steam ows through the condenser. Likewise, the net areas for W2, W3, and W4, Fig. 34a, are all too large, because less than 1

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.57

FIGURE 34 (a) T-S chart for the bleed-steam regenerative cycle in Fig. 10; (b) actual uid ow in the cycle; (c) alternative plot of (b).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.58


POWER GENERATION

lb (0.5 kg) of steam ows through the respective turbine sections. The area for W1, however, is true. A true proportionate-area diagram can be plotted by applying the factors for actual ow, as in Fig. 34b . Here W2, outlined by the heavy lines, equals the similarly m1. The states marked 11 and 12 , labeled area in Fig. 34a, multiplied by 1 Fig. 34b, are not true state points because of the ratioing factor applied to the area for W2. The true state points 11 and 12 of the liquid before and after heater pump 3 stay as shown in Fig. 34a . Apply 1 m1 m2 to W3 of Fig. 34a to obtain the proportionate area of Fig. 34b ; to obtain W4, multiply by 1 m1 m2 m3. Multiplying by this factor also gives Qr . Then all the areas in Fig. 34b will be in proper proportion for 1 lb (0.5 kg) of steam entering the turbine throttle but less in other parts of the cycle. In Fig. 34b, the work can be measured by the difference of the area Qa and the area Qr . There is no simple net area left, because the areas coincide on only two sides. But area enclosed by the heavy lines is the total net work W for the cycle, equal to the sum of the work produced in the various sections of the turbine, Fig. W4, as shaded in Fig. 34b . Then Qa is the alternate area Qr W1 W2 W3 34c . The sawtooth approach of the liquid-heating line shows that as the number of heaters in the cycle increases, the heating line approaches a line of constant entropy. The best number of heaters for a given cycle depends on the steam state of the turbine inlet. Many medium-pressure and medium-temperature cycles use ve to six heaters. High-pressure and high-temperature cycles use as many as nine heaters. 4. Draw the energy-ow chart Choose a suitable scale for the heat content of 1 lb (0.5 kg) of steam leaving the steam generator. A typical scale is 0.375 in per 1000 Btu / lb (0.41 cm per 1000 kJ / kg). Plot the heat content of 1 lb (0.5 kg) of steam vertically on line 2-2, Fig. 35. Using the same scale, plot the heat content in energy streams m1, m2, m3, We, W, Wp, WpF, and so forth. In some cases, as Wp 1, Wp 2, and so forth, the energy stream may be so small that it is impossible to plot it to scale. In these instances, a single thin line is used. The completed diagram, Fig. 35, provides a useful concept of the distribution of the energy in the cycle.

FIGURE 35 Energy-ow chart of cycle in Fig. 33.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.59

Related Calculations. The procedure given here can be used for all regenerative cycles, provided that the equations are altered to allow for more, or fewer, heaters and pumps. The following calculation procedure shows the application of this method to an actual regenerative cycle.

BLEED REGENERATIVE STEAM CYCLE ANALYSIS


Analyze the bleed regenerative cycle shown in Fig. 36, determining the heat balance for each heater, plant thermal efciency, turbine or engine thermal efciency, plant heat rate, turbine or engine heat rate, and turbine or engine steam rate. Throttle steam pressure is 2000 lb / in2 (abs) (13,790.0 kPa) at 1000 F (537.8 C); steamgenerator efciency 0.88; station auxiliary steam consumption (excluding pump work) 6 percent of the turbine or engine output; engine efciency of each turbine or engine section 0.80; turbine or engine cycle has three feedwater heaters and bleed-steam pressures as shown in Fig. 36; exhaust pressure to condenser is 1 inHg (3.4 kPa) absolute.
Calculation Procedure:

1. Determine the enthalpy of the steam at the inlet of each heater and the condenser 1474.5 Btu / lb From a superheated-steam table, nd the throttle enthalpy H2 (3429.7 kJ / kg) at 2000 lb / in2 (abs) (13,790.0 kPa) and 1000 F (537.8 C). Next 1.5603 Btu / (lb F) [6.5 kJ / (kg C)], at the same nd the throttle entropy S2 conditions in the superheated-steam table. Plot the throttle steam conditions on a Mollier chart, Fig. 37. Assume that the steam expands from the throttle conditions at constant entropy constant S to the inlet of the rst feedwater heater, 1, Fig. 36. Plot this constant S expansion by drawing the straight vertical line 2-3 on the Mollier chart, Fig. 37, between the throttle condition and the heater inlet pressure of 750 lb / in2 (abs) (5171.3 kPa). Read on the Mollier chart H3 1346.7 Btu / lb (3132.4 kJ / kg). Since the engine H2 H3 / (H2 H3) 0.8 1474.5 H3 / (1474.5 or turbine efciency ee 1346.7); H3 actual enthalpy of the steam at the inlet to heater 1 1474.5 0.8(1474.5 1346.7) 1372.2 Btu / lb (3191.7 kJ / kg). Plot this enthalpy point on

FIGURE 36 Bleed-regenerative steam cycle.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.60


POWER GENERATION

FIGURE 37 Mollier-chart plot of the cycle in Fig. 36.

the 750-lb / in2 (abs) (5171.3-kPa) pressure line of the Mollier chart, Fig. 37. Read 1.5819 Btu / (lb F) the entropy at the heater inlet from the Mollier chart as S3 [6.6 kJ / (kg C)] at 750 lb / in2 (abs) (5171.3 kPa) and 1372.2 Btu / lb (3191.7 kJ / kg). Assume constant-S expansion from H3 to H4 at 200 lb / in2 (abs) (1379.0 kPa), the inlet pressure for feedwater heater 2. Draw the vertical straight line 3 -4 on the Mollier chart, Fig. 37. By using a procedure similar to that for heater 1, H4 H3 ee (H3 H4) 1372.2 0.8(1372.2 1230.0) 1258.4 Btu / lb (2927.0 kJ / kg). This is the actual enthalpy of the steam at the inlet to heater 2. Plot this enthalpy on the 200-lb / in2 (abs) (1379.0-kPa) pressure line of the Mollier chart, 1.613 Btu / (lb F) [6.8 kJ / (kg C)], Fig. 37. and nd S4 Using the same procedure with constant-S expansion from H4 , we nd H5 1059.5 Btu / lb (2464.4 kJ / kg) at 16 lb / in2 (abs) (110.3 kPa), the inlet pressure to H4 ee (H4 H5) 1258.4 0.8(1258.4 1059.5) heater 3. Next nd H5 1099.2 Btu / lb (2556.7 kJ / kg). From the Mollier chart nd S5 1.671 Btu / (lb F) [7.0 kJ / (kg C)], Fig. 37. Using the same procedure with constant-S expansion from H5 to H6, nd H6 898.2 Btu / lb (2089.2 kJ / kg) at 1 inHg absolute (3.4 kPa), the condenser inlet H5 ee (H5 H6) 1099.2 0.8(1099.2 898.2) 938.4 pressure. Then H6 Btu / lb (2182.7 kJ / kg), the actual enthalpy of the steam at the condenser inlet. Find, on the Mollier chart, the moisture in the turbine exhaust 15.1 percent. 2. Determine the overall engine efciency Overall engine efciency ee is higher than the engine-section efciency because there is partial available-energy recovery between sections. Constant-S expansion

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.61

from the throttle to the 1-inHg absolute (3.4-kPa) exhaust gives H3s, Fig. 37, as 838.3 Btu / lb (1949.4 kJ / kg), assuming that all the steam ows to the condenser. H2 H3S ) 1474.5 938.4 / 1474.5 838.3 Then, overall ee H6 / (H2 0.8425, or 84.25 percent, compared with 0.8 or 80 percent, for individual engine sections. 3. Compute the bleed-steam ow to each feedwater heater For each heater, energy in energy out. Also, the heated condensate leaving each heater is a saturated liquid at the heater bleed-steam pressure. To simplify this calculation, assume negligible steam pressure drop between the turbine bleed point and the heater inlet. This assumption is permissible when the distance between the heater and bleed point is small. Determine the pump work by using the chart accompanying the compressed-liquid table in Keenan and KeyesThermodynamic Properties of Steam, or the ASMESteam Tables. For heater 1, energy in energy out, or H3 m1 H12(1 m 1) H13, where m bleed-steam ow to the feedwater heater, lb / lb of throttle steam ow. (The subscript refers to the heater under consideration.) Then H3 m1 (H11 Wp 2)(1 m1) H13, where Wp 2 work done by pump 2, Fig. 36, in Btu / lb per pound of throttle ow. Then 1372.2m1 (355.4 1.7)(1 m1) 500.8; m1 0.1416 lb / lb (0.064 kg / kg) throttle ow; H1 H13 Wp 1 500.8 4.7 505.5 Btu / lb (1175.8 kJ / kg), where Wp 1 work done by pump 1, Fig. 36. For each pump, nd the work from the chart accompanying the compressed-liquid table in Keenan and KeyesSteam Tables by entering the chart at the heater inlet pressure and projecting vertically at constant entropy to the heater outlet pressure, which equals the next heater inlet pressure. Read the enthalpy values at the respective pressures, and subtract the smaller from the larger to obtain the pump work during passage of the feedwater through the pump from the lower to the higher pressure. Thus, Wp 2 1.7 0.0 1.7 Btu / lb (4.0 kJ / kg), from enthalpy values for 200 lb / in2 (abs) (1379.0 kPa) and 750 lb / in2 (abs) (5171.3 kPa), the heater inlet and discharge pressures, respectively. For heater 2, energy in energy out, or H4 m2 H10(1 m1 m2) H11(1 m1)H4 m2 (H9 Wp 3)(1 m1 m2) H11(1 m1)1258.4m2 (184.4 0.5)(0.8584 m2) 355.4(0.8584)m2 0.1365 lb / lb (0.0619 kg / kg) throttle ow. For heater 3, energy in energy out, or H5 m3 H8(1 m1 m2 m3) H9(1 m1 m2)H5 m3 (H7 Wp 4)(1 m1 m2 m3) H9(1 m1 m2)1099.2m3 (47.1 0.1)(0.7210 m3) 184.4(0.7219)m3 0.0942 lb / lb (0.0427 kg / kg) throttle ow. 4. Compute the turbine work output The work output per section W Btu is W1 H2 H3 1474.5 1372.1 102.3 Btu (107.9 kJ), from the previously computed enthalpy values. Also W2 (H3 H4 )(1 m1) (1372.2 1258.4)(1 0.1416) 97.7 Btu (103.1 kJ); W3 (H4 H5 )(1 m1 m 2) (1258.4 1099.2)(1 0.1416 0.1365) 115.0 Btu (121.3 kJ); W4 (H5 H6 )(1 m1 m2 m3) (1099.2 938.4)(1 0.1416 0.1365 0.0942) 100.9 Btu (106.5 kJ). The total work output of the We W 102.3 97.7 115.0 100.9 415.9 Btu (438.8 kJ). turbine Wp Wp 1 Wp 2 Wp 3 Wp 4 4.7 1.7 0.5 0.1 7.0 The total Wp Btu (7.4 kJ). Since the station auxiliaries consume 6 percent of We, the auxiliary 0.6(415.9) 25.0 Btu (26.4 kJ). Then, net station work w consumption 415.9 7.0 25.0 383.9 Btu (405.0 kJ).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.62


POWER GENERATION

5. Check the turbine work output The heat added to the cycle Qa Btu / lb H2 H1 1474.5 505.5 969.0 Btu (H6 H7)(1 m1 (1022.3 kJ). The heat rejected from the cycle Qr Btu / lb m2 m3) (938.4 47.1)(0.6277) 559.5 Btu (590.3 kJ). Then We Wp Qa Qr 969.0 559.5 409.5 Btu (432.0 kJ). Wp computed earlier, or 415.9 7.0 408.9 Btu Compare this with We (431.4 kJ), or a difference of 409.5 408.9 0.6 Btu (0.63 kJ). This is an accurate check; the difference of 0.6 Btu (0.63 kJ) comes from errors in Mollier chart and calculator readings. Assume 408.9 Btu (431.4 kJ) is correct because it is the lower of the two values. 6. Compute the plant and turbine efciencies Qa / eb, where eb boiler efciency. Then plant energy Plant energy input input 969.0 / 0.88 1101.0 Btu (1161.6 kJ). Plant thermal efciency W / (Qa / eb ) 383.9 1101.0 0.3486. Turbine thermal efciency We / Qa 415.9 / 0.4292. Plant heat rate 3413 / 0.3486 9970 Btu / kWh (10,329.0 kJ / 969.0 Btu / kWh. Turbine heat rate 3413 / 0.4292 7950 Btu / kWh), where 3413 (turbine heat rate) / (H2 kWh (8387.7 kJ / kWh). Turbine throttle steam rate H1) 7950 / (1474.5 505.5) 8.21 lb / kWh (3.7 kg / kWh). Related Calculations. By using the procedures given, the following values can be computed for any actual steam cycle: engine or turbine efciency ee ; steam enthalpy at the main-condenser inlet; bleed-steam ow to a feedwater heater; turbine or engine work output per section; total turbine or engine work output; station auxiliary power consumption; net station work output; plant energy input; plant thermal efciency; turbine or engine thermal efciency; plant heat rate; turbine or engine heat rate; turbine throttle heat rate. To compute any of these values, use the equations given and insert the applicable variables.

REHEAT-STEAM CYCLE PERFORMANCE


A reheat-steam cycle has a 2000 lb / in2 (abs) (13,790-kPa) throttle pressure at the turbine inlet and a 400-lb / in2 (abs) (2758-kPa) reheat pressure. The throttle and reheat temperature of the steam is 1000 F (537.8 C); condenser pressure is 1 inHg absolute (3.4 kPa); engine efciency of the high-pressure and low-pressure turbines is 80 percent. Find the cycle thermal efciency.

Calculation Procedure:

1. Sketch the cycle layout and cycle T-S diagram Figures 38 and 39 show the cycle layout and T-S diagram with each important point numbered. Use a cycle layout and T-S diagram for every calculation of this type because it reduces the possibility of errors. 2. Determine the throttle-steam properties from the steam tables Use the superheated steam tables, entering at 2000 lb / in2 (abs) (13,790 kPa) and 1000 F (537.8 C) to nd throttle-steam properties. Applying the symbols of the T1474.5 Btu / lb (3429.7 kJ / kg); S2 1.5603 S diagram in Fig. 39, we get H2 Btu / (lb F) [6.5 kJ / (kg C)].

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.63

FIGURE 38 Typical steam reheat cycle.

FIGURE 39 Irreversible expansion in reheat cycle.

3. Find the reheat-steam enthalpy Assume a constant-entropy expansion of the steam from 2000 to 400 lb / in2 (13,790 to 2758 kPa). Trace this expansion on a Mollier (H-S ) chart, where a constantentropy process is a vertical line between the initial [2000 lb / in2 (abs) or 13,790 kPa] and reheat [400 lb / in2 (abs) or 2758 kPa] pressures. Read on the Mollier chart H3 1276.8 Btu / lb (2969.8 kJ / kg) at 400 lb / in2 (abs) (2758 kPa). 4. Compute the actual reheat properties The ideal enthalpy drop, throttle to reheat H2 H3 1474.5 1276.8 197.7 Btu / lb (459.9 kJ / kg). The actual enthalpy drop (ideal drop)(turbine efciency) H2 H3 197.5(0.8) 158.2 Btu / lb (368.0 kJ / kg) We 1 work output in the high-pressure section of the turbine. H2 We 1 1474.5 Once We 1 is known, H3 can be computed from H3 158.2 1316.3 Btu / lb (3061.7 kJ / kg).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.64


POWER GENERATION

The steam now returns to the boiler and leaves at condition 4, where P4 400 1000 F (537.8 C); S4 1.7623 Btu / (lb F) [7.4 lb / in2 (abs) (2758 kPa); T4 kJ / (kg C)]; H4 1522.4 Btu / lb (3541.1 kJ / kg) from the superheated-steam table. 5. Compute the exhaust-steam properties Use the Mollier chart and an assumed constant-entropy expansion to 1 inHg (3.4 kPa) absolute to determine the ideal exhaust enthalpy, or H5 947.4 Btu / lb (2203.7 kJ / kg). The ideal work of the low-pressure section of the turbine is then H4 H5 1522.4 947.4 575.0 Btu / lb (1338 kJ / kg). The actual work output of H4 H5 575.0(0.8) 460.8 the low-pressure section of the turbine is We 2 Btu / lb (1071.1 kJ / kg). H4 We 2 1522.4 Once We 2 is known, H5 can be computed from H5 460.0 1062.4 Btu / lb (2471.1 kJ / kg). The enthalpy of the saturated liquid at the condenser pressure is found in the H6 47.1 Btu / lb saturation-pressure steam table at 1 inHg absolute (3.4 kPa) (109.5 kJ / kg). The pump work Wp from the compressed-liquid table diagram in the steam tables is Wp 5.5 Btu / lb (12.8 kJ / kg). Then the enthalpy of the water entering the boiler H1 H6 Wp 47.1 5.5 52.6 Btu / lb (122.3 kJ / kg). 6. Compute the cycle thermal efciency For any reheat cycle, e cycle thermal efficiency (H2 (H2 H3 ) (H4 H5 ) Wp H1) (H4 H3 )

(1474.5 1316.3) (1522.4 1062.4) 5.5 (1474.5 52.6) (1522.4 1316.3) 0.3766, or 37.66 percent Figure 40 is an energy-ow diagram for the reheat cycle analyzed here. This diagram shows that the fuel burned in the steam generator to produce energy ow Qa 1 is the largest part of the total energy input. The cold-reheat line carries the major share of energy leaving the high-pressure turbine.

FIGURE 40 Energy-ow diagram for reheat cycle in Fig. 38.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.65

Related Calculations. Reheat-regenerative cycles are used in some large power plants. Figure 41 shows a typical layout for such a cycle having three stages of feedwater heating and one stage of reheating. The heat balance for this cycle is computed as shown above, with the bleed-ow terms m computed by setting up an energy balance around each heater, as in earlier calculation procedures. By using a T-S diagram, Fig. 42, the cycle thermal efciency is e W Qa Qa Qa Qr 1 Qr Qa 1 Qa 2

FIGURE 41 Combined reheat and bleed-regenerative cycle.

FIGURE 42 (a) T-S diagram for ideal reheat-regenerative-bleed cycle; (b) T-S diagram for actual cycle.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.66


POWER GENERATION

Based on 1 lb (0.5 kg) of working uid entering the steam generator and turbine throttle, Qr Qa 1 Qa 2 (1 (H2 (1 m1 H1) m1)(H4 H3) m2 m3)(H7 H8)

Figure 43 shows the energy-ow chart for this cycle. Some high-pressure plants use two stages of reheating, Fig. 44, to raise the cycle efciency. With two stages of reheating, the maximum number generally used, and values from Fig. 44.

FIGURE 43 Energy ow of cycle in Fig. 41.

FIGURE 44 T-S diagram for multiple reheat stages.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.67

(H2 H3) (H4 H5) (H6 H7) Wp (H2 H1) (H4 H3) (H6 H5)

MECHANICAL-DRIVE STEAM-TURBINE POWEROUTPUT ANALYSIS


Show the effect of turbine engine efciency on the condition lines of a turbine having engine efciencies of 100 (isentropic expansion), 75, 50, 25, and 0 percent. How much of the available energy is converted to useful work for each engine efciency? Sketch the effect of different steam inlet pressures on the condition line of a single-nozzle turbine at various loads. What is the available energy, Btu / lb of steam, in a noncondensing steam turbine having an inlet pressure of 1000 lb / in2 (abs) (6895 kPa) and an exhaust pressure of 100 lb / in2 (gage) (689.5 kPa)? How much work will this turbine perform if the steam ow rate to it is 1000 lb / s (453.6 kg / s) and the engine efciency is 40 percent?
Calculation Procedure:

1. Sketch the condition lines on the Mollier chart Draw on the Mollier chart for steam initial- and exhaust-pressure lines, Fig. 45, and the initial-temperature line. For an isentropic expansion, the entropy is constant 100 percent. The expansion or during the expansion, and the engine efciency condition line is a vertical trace from h1 on the initial-pressure line to h2, on the exhaust-pressure line. Draw this line as shown in Fig. 45. For zero percent engine efciency, the other extreme in the efciency range, h1 h2 and the condition line is a horizontal line. Draw this line as shown in Fig. 45.

FIGURE 45 Mollier chart of turbine condition lines.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.68


POWER GENERATION

Between 0 and 100 percent efciency, the condition lines become more nearly vertical as the engine efciency approaches 100 percent, or an isentropic expansion. Draw the condition lines for 25, 50, and 75 percent efciency, as shown in Fig. 45. For the isentropic expansion, the available energy h1 h2s, Btu / lb of steam. This is the energy that an ideal turbine would make available. h1 (available For actual turbines, the enthalpy at the exhaust pressure h2 h1 h2s for an ideal energy)(engine efciency) / 100, where available energy turbine working between the same initial and exhaust pressures. Thus, the available energy converted to useful work for any engine efciency (ideal available energy, Btu / lb)(engine efciency, percent) / 100. Using this relation, the available energy at each of the given engine efciencies is found by substituting the ideal available energy and the actual engine efciency. 2. Sketch the condition lines for various throttle pressures Draw the throttle- and exhaust-pressure lines on the Mollier chart, Fig. 46. Since the inlet control valve throttles the steam ow as the load on the turbine decreases, the pressure of the steam entering the turbine nozzle is lower at reduced loads. Show this throttling effect by indicating the lower inlet pressure lins, Fig. 46, for the reduced loads. Note that the lowest inlet pressure occurs at the minimum plotted load25 percent of full loadand the maximum inlet pressure at 125 percent of full load. As the turbine inlet steam pressure decreases, so does the available energy, because the exhaust enthalpy rises with decreasing load. 3. Compute the turbine available energy and power output Use a noncondensing-turbine performance chart, Fig. 47, to determine the available energy. Enter the bottom of the chart at 1000 lb / in2 (abs) (6895 kPa) and project vertically upward until the 100-lb / in2 (gage) (689.5-kPa) exhaust-pressure curve is intersected. At the left, read the available energy as 205 Btu / lb (476.8 kJ / kg) of steam. With the available energy, ow rate, and engine efciency known, the work (available energy, Btu / lb)(ow rate, lb / s)(engine efciency / 100) / [550 output

FIGURE 46 Turbine condition line shifts as the inlet steam pressure varies.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.69

FIGURE 47 Available energy in turbine depends on the initial steam state and the exhaust pressure.

ft lb / (s hp)]. [Note: 550 ft lb / (s hp) 1 N m / (W s).] For this turbine, work output (205 Btu / lb)(1000 lb / s)(40 / 100) / 550 149 hp (111.1 kW). Related Calculations. Use the steps given here to analyze single-stage noncondensing mechanical-drive turbines for stationary, portable, or marine applications. Performance curves such as Fig. 47 are available from turbine manufacturers. Single-stage noncondensing turbines are for feed-pump, draft-fan, and auxiliarygenerator drive.

CONDENSING STEAM-TURBINE POWER-OUTPUT ANALYSIS


What is the available energy in steam supplied to a 5000-kW turbine if the inlet steam conditions are 1000 lb / in2 (abs) (6895 kPa) and 800 F (426.7 C) and the turbine exhausts at 1 inHg absolute (3.4 kPa)? Determine the theoretical and actual heat rate of this turbine if its engine efciency is 74 percent. What are the full-load output and steam rate of the turbine?
Calculated Procedure:

1. Determine the available energy in the steam Enter Fig. 48 at the bottom at 1000-lb / in2 (abs) (6895.0-kPa) inlet pressure, and project vertically upward to the 800 F (426.7 C) 1-in (3.4-kPa) exhaust-pressure curve. At the left, read the available energy as 545 Btu / lb (1267.7 kJ / kg) of steam. 2. Determine the heat rate of the turbine Enter Fig. 49 at an initial steam temperature of 800 F (426.7 C), and project vertically upward to the 1000-lb / in2 (abs) (6895.0-kPa) 1-in (3.4-kPa) curve. At the left, read the theoretical heat rate as 8400 Btu / kWh (8862.5 kJ / kWh). When the theoretical heat rate is known, the actual heat rate is found from: (theoretical heat rate, Btu / kWh) / (engine efactual heat rate HR, Btu / kWh ciency). Or, actual HR 8400 / 0.74 11,350 Btu / kWh (11,974.9 kJ / kWh).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.70


POWER GENERATION

FIGURE 48 Available energy for typical condensing turbines.

3. Compute the full-load and steam rate (available energy, Btu / lb of The energy converted to work, Btu / lb of steam steam)(engine efciency) (545)(0.74) 403 Btu / lb of steam (937.4 kJ / kg). For any prime mover driving a generator, the full-load output, Btu (generator kW rating)(3413 Btu / kWh) (5000)(3413) 17,060,000 Btu / h (4999.8 kJ / s). (full-load output, Btu / h) / (work output, Btu / lb) The steam ow 17,060,000 / 403 42,300 lb / h (19,035 kg / h) of steam. Then the full-load steam (steam ow, lb / h) / (kW output at full load) rate of the turbine, lb / kWh 42,300 / 5000 8.46 lb / kWh (3.8 kg / kWh). Related Calculations. Use this general procedure to determine the available energy, theoretical and actual heat rates, and full-load output and steam rate for any stationary, marine, or portable condensing steam turbine operating within the ranges of Figs. 48 and 49. If the actual performance curves are available, use them instead of Figs. 48 and 49. The curves given here are suitable for all preliminary estimates for condensing turbines operating with exhaust pressures of 1 or 3 inHg absolute (3.4 or 10.2 kPa). Many modern turbines operate under these conditions.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.71

FIGURE 49 Theoretical heat rate for condensing turbines.

STEAM-TURBINE REGENERATIVE-CYCLE PERFORMANCE


When throttle steam is at 1000 lb / in2 (abs) (6895 kPa) and 800 F (426.7 C) and the exhaust pressure is 1 inHg (3.4 kPa) absolute, a 5000-kW condensing turbine has an actual heat rate of 11,350 Btu / kWh (11,974.9 kJ / kWh). Three feedwater heaters are added to the cycle, Fig. 50, to heat the feedwater to 70 percent of the maximum possible enthalpy rise. What is the actual heat rate of the turbine? If 10 heaters instead of 3 were used and the water enthalpy were raised to 90 percent of the maximum possible rise in these 10 heaters, would the reduction in the actual heat rate be appreciable?

Calculation Procedure:

1. Determine the actual enthalpy rise of the feedwater Enter Fig. 51 at the throttle pressure of 1000 lb / in2 (abs) (6895 kPa), and project vertically upward to the 1-inHg (3.4-kPa) absolute backpressure curve. At the left, read the maximum possible feedwater enthalpy rise as 495 Btu / lb (1151.4 kJ / kg). Since the actual rise is limited to 70 percent of the maximum possible rise by the (495)(0.70) 346.5 Btu / lb conditions of the design, the actual enthalpy rise (805.9 kJ / kg).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.72


POWER GENERATION

FIGURE 50 Regenerative feedwater heating.

FIGURE 51 Feedwater enthalpy rise.

2. Determine the heat-rate and heater-number correction factors Find the theoretical reduction in straight-condensing (no regenerative heaters) heat rates from Fig. 52. Enter the bottom of Fig. 52 at the inlet steam temperature, 800 F (426.7 C), and project vertically upward to the 1000-lb / in2 (abs) (6895-kPa) 1-inHg (3.4-kPa) back-pressure curve. At the left, read the reduction in straight-condensing heat rate as 14.8 percent. Next, enter Fig. 52 at the bottom of 70 percent of maximum possible rise in feedwater enthalpy, and project vertically to the three-heater curve. At the left, read the reduction in straight-condensing heat rate for the number of heaters and actual enthalpy rise as 0.71.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.73

FIGURE 52 Reduction in straight-condensing heat rate obtained by regenerative heating.

3. Apply the heat-rate and heater-number correction factors (straight-condensing heat rate, Full-load regenerative-cycle heat rate, Btu / kWh (heat-rate correction factor)(heater-number correction factor)] Btu / kWh) [1 (13,350)[1 (0.148)(0.71)] 10,160 Btu / kWh (10,719.4 kJ / kWh). 4. Find and apply the correction factors for the larger number of heaters Enter Fig. 53 at 90 percent of the maximum possible enthalpy rise, and project vertically to the 10-heater curve. At the left, read the heat-rate reduction for the number of heaters and actual enthalpy rise as 0.89. Using the heat-rate correction factor from step 2 and 0.89, found above, we see (11,350)[1 that the full-load 10-heater regenerative-cycle heat rate (0.148)(0.89)] 9850 Btu / kWh (10,392.3 kJ / kWh), by using the same procedure as in step 3. Thus, adding 10 3 7 heaters reduces the heat rate by 10,160 9850 310 Btu / kWh (327.1 kJ / kWh). This is a reduction of 3.05 percent. To determine whether this reduction in heat rate is appreciable, the carrying charges on the extra heaters, piping, and pumps must be compared with the reduction in annual fuel costs resulting from the lower heat rate. If the fuel saving is greater than the carrying charges, the larger number of heaters can usually be justied. In this case, tripling the number of heaters would probably increase the

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.74


POWER GENERATION

FIGURE 53 Maximum possible rise in feedwater enthalpy varies with the number of heaters used.

carrying charges to a level exceeding the fuel savings. Therefore, the reduction in heat rate is probably not appreciable. Related Calculations. Use the procedure given here to compute the actual heat rate of steam-turbine regenerative cycles for stationary, marine, and portable installations. Where necessary, use the steps of the previous procedure to compute the actual heat rate of a straight-condensing cycle before applying the present procedure. The performance curves given here are suitable for rst approximations in situations where actual performance curves are unavailable.

REHEAT-REGENERATIVE STEAM-TURBINE HEAT RATES


What are the net and gross heat rates of a 300-kW reheat turbine having an initial steam pressure of 3500 lb / in2 (gage) (24,132.5 kPa) with initial and reheat steam temperatures of 1000 F (537.8 C) with 1.5 inHg (5.1 kPa) absolute back pressure and six stages of regenerative feedwater heating? Compare this heat rate with that of 3500 lb / in2 (gage) (24,132.5 kPa) 600-mW cross-compound four-ow turbine with 3600 / 1800 r / min shafts at a 300-mW load.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.75

Calculation Procedure:

1. Determine the reheat-regenerative heat rate Enter Fig. 54 at 3500-lb / in2 (gage) (24,132.5-kPa) initial steam pressure, and project vertically to the 300-mW capacity net-heat-rate curve. At the left, read the net heat rate as 7680 Btu / kWh (8102.6 kJ / kWh). On the same vertical line, read the gross heat rate as 7350 Btu / kWh (7754.7 kJ / kWh). The gross heat rate is computed by using the generator-terminal output; the net heat rate is computed after the feedwater-pump energy input is deducted from the generator output. 2. Determine the cross-compound turbine heat rate Enter Fig. 55 at 350 mW at the bottom, and project vertically upward to 1.5-inHg (5.1-kPa) exhaust pressure midway between the 1- and 2-inHg (3.4- and 6.8-kPa) curves. At the left, read the net heat rate as 7880 Btu / kWh (8313.8 kJ / kWh). Thus, the reheat-regenerative unit has a lower net heat rate. Even at full rated load of the cross-compound turbine, its heat rate is higher than the reheat unit. Related Calculations. Use this general procedure for comparing stationary and marine high-pressure steam turbines. The curves given here are typical of those supplied by turbine manufacturers for their turbines. With the price of all commonly used fuels on the rise, nuclear power is increasingly being looked at by engineers worldwide. A number of nationsthe United

FIGURE 54 Full-load heat rates for steam turbines with six feedwater heaters, 1000 F / 1000 F (538 C / 538 C) steam, 1.5-in (38.1-mm) Hg (abs) exhaust pressure.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.76


POWER GENERATION

FIGURE 55 Heat rate of a cross-compound four-ow steam turbine with 3600 / 1800-r / min shafts.

States, Japan, France, England, and Germanyare currently generating portions of their electricity needs by using nuclear energy. Todays nuclear plants use ssion to generate the steam for their turbines. Fusion is now being seriously investigated as the next source of nuclear power. In June 2005, France was selected as the country in which an experimental fusion reactor would be built. Test results will be provided to participating countries. Fusion reactors produce much less nuclear waste than ssion-based reactors. According to an article in The New York Times,* using data from Princeton Plasma Physics Laboratory and the Energy Information Administration, the daily waste from a 1000-MW electric generating plant using 9000 tons of coal per day is 30,000 tons of CO2, 600 tons of SO2, and 80 tons of NO. A nuclear ssion plant using 14.7 lb (6.67 kg) of uranium produces 6.6 lb (2.99 kg) of highly radioactive material. The projected nuclear fusion plant using 1 lb (0.454 kg) of deuterium and 1.5 lb (0.68 kg) of tritium produces 4.0 lb (1.8 kg) of helium. A large demonstration project is expected to begin operating in approximately 2030. The commercial fusion reactor is expected in approximately 2050. Thus, while the fusion reactor has great promise, its commercial utilization is expected to take many years to develop. At this writing, the consensus is that both ssion and fusion nuclear power will nd use during the 21st century.

STEAM TURBINEGAS TURBINE CYCLE ANALYSIS


Sketch the cycle layout, T-S diagram, and energy-ow chart for a combined steam turbinegas turbine cycle having one stage of regenerative feedwater heating and
*The New York Times, June 29, 2005.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.77

one stage of economizer feedwater heating. Compute the thermal efciency and heat rate of the combined cycle.

Calculation Procedure:

1. Sketch the cycle layout Figure 56 shows the cycle. Since the gas-turbine exhaust-gas temperature is usually higher than the bleed-steam temperature, the economizer is placed after the regenerative feedwater heater. The feedwater will be progressively heated to a higher temperature during passage through the regenerative heater and the gas-turbine economizer. The cycle shown here is only one of many possible combinations of a steam plant and a gas turbine. 2. Sketch the T-S diagram Figure 57 shows the T-S diagram for the combined gas turbinesteam turbine cycle. There is irreversible heat transfer QT from the gas-turbine exhaust to the feedwater in the economizer, which helps reduce the required energy input Qa 2. 3. Sketch the energy-ow chart Choose a suitable scale for the energy input, and proportion the energy ow to each of the other portions of the cycle. Use a single line when the ow is too small to plot to scale. Figure 58 shows the energy-ow chart. 4. Determine the thermal efciency of the cycle W / Qa, e Qa Qr / Qa 1 [Qr 1 Since e notation in Figs. 56, 57, and 58. Qr 2 / (Qa 1 Qa 2)], given the

FIGURE 56 Combined gas turbinesteam turbine cycle.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.78


POWER GENERATION

FIGURE 57 T-S charts for combined gas turbinesteam turbine cycle have irreversible heat transfer Q from gas-turbine exhaust to the feedwater.

The relative weight of the gas wg to 1 lb (0.5 kg) of water must be computed wg (H4 H5). by taking an energy balance about the economizer. Or, H7 H6 Using the actual values for the enthalpies, solve this equation for wg . With wg known, the other factors in the efciency computation are Qr 1 Qr 2 Qa 1 Qa 2 wg (H5 (1 H1) H11)

m )(H10 H2) H7

wg (H3 H8

The bleed-steam ow m is calculated from an energy balance about the feedwater heater. Note that the units for the above equations can be any of those normally used in steam- and gas-turbine analyses.

Calculation Procedure:

1. Find the amount of oxygen required for complete combustion of the fuel Eight atoms of carbon in C8 combine with 8 molecules of oxygen, O2, and produce 8 molecules of carbon dioxide, 8CO2. similarly, 9 molecules of hydrogen, H2, in H18 combine with 9 atoms of oxygen, O, or 4.5 molecules of oxygen, to form 9 molecules of water, 9H2O. Thus, 100 percent, or the stoichiometric, air quantity required for complete combustion of a mole of fuel, C8H18, is proportional to 8 12.5 moles of oxygen, O2.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.79

FIGURE 58 Energy-ow chart of the gas turbinesteam turbine cycle in Fig. 56.

2. Establish the chemical equation for complete combustion with 100 percent air 12.5 O2 (3.784 12.5)N2 8CO2 9H2O With 100 percent air: C8H18 47.3N2, where 3.784 is a derived volumetric ratio of atmospheric nitrogen, (N2), to oxygen, O2, in dry air. The (N2) includes small amounts of inert and inactive gases. See Related Calculations of this procedure. 3. Establish the chemical equation for complete combustion with 400 percent of the stoichiometric air quantity, or 300 percent excess air 50 O2 (4 47.3)N2 8CO2 9H2O With 400 percent air: C8H18 189.2N2 (3 12.5)O2. 4. Compute the molecular weights of the components in the combustion process Molecular weight of C8H18 [(12 8) (1 18)] 114; O2 16 2 32; 14 2 28; CO2 [(12 1) (16 2)] 44; H2O [(1 2) N2 (16 1)] 18. 5. Compute the relative weights of the reactants and products of the combustion process Relative weight moles molecular weight. Coefcients of the chemical equation in step 3 represent the number of moles of each component. Hence, for the reac1 114 114; O2 50 32 1600; tants, the relative weights are: C8H18 189.2 28 5298. Total relative weight of the reactants is 7012. For the N2 8 44 352; H2O 9 18 162; products, the relative weights are: CO2 189.2 28 5298; O2 37.5 32 1200. Total relative weight of the N2 products is 7012, also. 6. Compute the enthalpy of the products of the combustion process Enthalpy of the products of combustion, hp mp (h1600 h77), where mp number of moles of the products; h1600 enthalpy of the products at 1600 F (871 C); h77

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.80


POWER GENERATION

enthalpy of the products at 77 F (25 C). Thus, hp (8 37.5)(15,400 3750) 2,839,100 Btu [6,259,100 Btu (SI)].

189.2

7. Compute the air supply temperature at the combustion chamber inlet Since the combustion process is adiabatic, the enthalpy of the reactants hr h p, (relative weight of the fuel its heating value) [relative weight of where hr its specic heat (air supply temperature air source temperature)]. the air Therefore, hr (114 19,100) [(1600 5298) 0.24 (ta 77)] 2,839,100 Btu [6,259,100 Btu (SI)]. Solving for the air supply temperature, ta [(2,839,100 2,177,400 / 1655.5] 77 477 F (247 C). Related Calculations. This procedure, appropriately modied, may be used to deal with similar questions involving such things as other fuels, different amounts of excess air, and variations in the condition(s) being sought under certain given circumstances. 3.784 in step 2, is used to indicate that for each unit of The coefcient, (?) volume of oxygen, O2, 12.5 in this case, there will be 3.784 units of nitrogen, N2. This equates to an approximate composition of air as 20.9 percent oxygen and 79.1 percent atmospheric nitrogen, (N2). In turn, this creates a paradox, because page 200 of Principles of Engineering Thermodynamics, by Kiefer, et al., John Wiley & Sons, Inc., states air to be 20.99 percent oxygen and 79.01 percent atmospheric nitrogen, where the ratio (N2) / O2 (?) 79.01 / 20.99 3.764. Also, page 35 of Applied Energy Conversion, by Skrotski and Vopat, McGrawHill, Inc., indicates an assumed air analysis of 79 percent nitrogen and 21 percent 3.762. On that basis, a formula is presented for the amount oxygen, where (?) of dry air chemically necessary for complete combustion of a fuel consisting of atoms of carbon, hydrogen, and sulfur, or C, H, and S, respectively. That formula is: Wa 11.5C 34.5[H (0 / 8)] 4.32S, lb air / lb fuel (kg air / kg fuel). The following derivation for the value of (?) should clear up the paradox and show that either 3.784 or 3.78 is a sound assumption which seems to be wrong, but in reality is not. In the above equation for Wa, the carbon hydrogen, or sulfur (M O2 / D O2)Mx, where M O2 is the molecular weight of oxygen, coefcient, Cx O2; D O2 is the decimal fraction for the percent, by weight, of oxygen, O2, in dry air containing atmospheric nitrogen, (N2), and small amounts of inert and inactive gases: Mx is the formula weight of the combustible element in the fuel, as indicated by its relative amount as a reactant in the combustion equation. The alternate evaluation of Cx is obtained from stoichiometric chemical equations for burning the O2 (?)N2 CO2 (?)N2; 2H2 combustible elements of the fuel, i.e., C O2 (?)N2 2H2O (?)N2; S O2 (?)N2 SO2 (?)N2. Evidently, Cx [M O2 (?) M N2)] / Mx, where M N2 is the molecular weight of nitrogen, N2, and the other items are as before. Equating the two expressions, Cx [M O2 (? M N2)] / Mx (M O2 / D O2)Mx, reveals that the Mx terms cancel out, indicating that the formula weight(s) of com(1 D O2)[M bustible components are irrelevant in solving for (?). Then, (?) D O2)]. From the above-mentioned book by Kiefer, et al., D O2 O2 / (M N2 0.23188. From Marks Standard Handbook for Mechanical Engineers, McGraw31.9988 and M N2 28.0134. Thus, (?) (1 Hill, Inc., M O2 0.23188)[31.9988 / (28.0134 0.23188)] 3.7838. This demonstrates that the use of (?) 3.784, or 3.78, is justied for combustion equations. By using either of the two evaluation equations for Cx, and with accurate values for Mx, i.e., MC 12.0111; MH 2 2 1.00797 4.0319; MS 32.064, from Marks M.E. Handbook, the more precise values for CC, CH, and CS are found out to be 11.489, 34.227, and 4.304, respectively. However, the actual Cx values, 11.5,

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.81

34.5, and 4.32, used in the formula for Wa are both brief for simplicity and rounded up to be on the safe side.

GAS TURBINE COMBUSTION CHAMBER INLET AIR TEMPERATURE


A gas turbine combustion chamber is well insulated so that heat losses to the atmosphere are negligible. Octane, C8H18, is to be used as the fuel and 400 percent of the stoichiometric air quantity is to be supplied. The air rst passes through a regenerative heater and the air supply temperature at the combustion chamber inlet is to be set so that the exit temperature of the combustion gases is 1600 F (871 C). (See Fig. 59.) Fuel supply temperature is 77 F (25 C) and its heating value is to be taken as 19,000 Btu / lbm (44,190 kJ / kg) relative to a base of 77 F (15 C). The air may be treated in calculations as a perfect gas with a constant-pressure specic heat of 0.24 Btu / (lb F) [1.005 kJ / (kg C)]. The products of combustion have an enthalpy of 15,400 Btu / lb mol) [33,950 Btu / (kg mol)] at 1600 F (871 C) and an enthalpy of 3750 Btu / (lb mol) [8270 Btu / (kg mol)] at 77 F (24 C). Determine, assuming complete combustion and neglecting dissociation, the required air temperature at the inlet of the combustion chamber.
Calculation Procedure:

1. Find the amount of oxygen required for complete combustion of the fuel Eight atoms of carbon in C8 combine with 8 molecules of oxygen, O2, and produce 8 molecules of carbon dioxide, 8CO2. Similarly, 9 molecules of hydrogen, H2, in H18 combine with 9 atoms of oxygen, O, or 4.5 molecules of oxygen, to form 9 molecules of water, 9H2O. Thus, 100 percent, or the stoichiometric, air quantity

FIGURE 59 Gas turbine ow diagram.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.82


POWER GENERATION

required for complete combustion of a mole of fuel, C8H18, is proportional to 8 12.5 mol of oxygen, O2. 2. Establish the chemical equation for complete combustion with 100 percent air 12.5O2 (3.784 12.5)N2 8CO2 9H2O With 100 percent air: C8H18 47.3N2, where 3.784 is a derived volumetric ratio of atmospheric nitrogen (N2) to oxygen O2 in dry air. The N2 includes small amounts of inert and inactive gases. See Related Calculations of this procedure. 3. Establish the chemical equation for complete combustion with 400 percent of the stoichiometric air quantity, or 300 percent excess air With 400 percent air: C8H18 50O2 (4 47.3)N2 8CO2 9H2O 189.2N2 (3 12.5)O2. 4. Compute the molecular weights of the components in the combustion process Molecular weight of C8H18 [(12 8) (1 18)] 114; O2 16 2 32; 14 2 28; CO2 [(12 1) (16 2)] 44; H2O [(1 2) N2 (16 1)] 18. 5. Compute the relative weights of the reactants and products of the combustion process Relative weight moles molecular weight. Coefcients of the chemical equation in step 3 represent the number of moles of each component. Hence, for the reac1 114 114; O2 50 32 1600; tants, the relative weights are C8H18 189.2 28 5298. Total relative weight of the reactants is 7012. For the N2 8 44 352; H2O 9 18 162; products, the relative weights are CO2 189.2 28 5298; O2 37.5 32 1200. Total relative weight of the N2 products is 7012 also. 6. Compute the enthalpy of the products of the combustion process Enthalpy of the products of combustion, hp mp(h1600 h77), where mp number of moles of the products; h1600 enthalpy of the products at 1600 F (871 C); h77 enthalpy of the products at 77 F (25 C). Thus, hp (8 9 189.2 37.5)(15,400 3750) 2,839,100 Btu [6,259,100 Btu (SI)]. 7. Compute the air supply temperature at the combustion chamber inlet Since the combustion process is adiabatic, the enthalpy of the reactants hr hp , (relative weight of the fuel its heating value) [relative weight of where hr its specic heat (air supply temperature air source temperature)]. the air Therefore, hr (114 19,100) [(1600 5298) 0.24 (ta 77)] 2,839,100 Btu [6,259,100 Btu (SI)]. Solving for the air supply temperature, ta [(2,839,100 2,177,400 / 1655.5] 77 477 F (247 C). Related Calculations. This procedure, appropriately modied, may be used to deal with similar questions involving such things as other fuels, different amounts of excess air, and variations in the condition(s) being sought under certain given circumstances. 3.784 in step 2, is used to indicate that for each unit of The coefcient, (?) volume of oxygen, O2, 12.5 in this case, there will be 3.784 units of nitrogen, N2. This equates to an approximate composition of air as 20.9 percent oxygen and 79.1 percent atmospheric nitrogen (N2). In turn, this creates a paradox, because page

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.83

200 of Principles of Engineering Thermodynamics, by Kiefer et al., John Wiley & Sons, Inc., states air to be 20.99 percent oxygen and 79.01 percent atmospheric nitrogen, where the ratio N2 / O2 (?) 79.01 / 20.99 3.764. Also, page 35 of Applied Energy Conversion, by Skrotski and Vopat, McGrawHill, Inc., indicates an assumed air analysis of 79 percent nitrogen and 21 percent oxygen, where (?) 3.762. On that basis, a formula is presented for the amount of dry air chemically necessary for complete combustion of a fuel consisting of atoms of carbon, hydrogen, and sulfur, or C, H, and S, respectively. That formula is Wa 11.5C 34.5[H (0 / 8)] 4.32S, lb air / lb fuel (kg air / kg fuel). The following derivation for the value of (?) should clear up the paradox and show that either 3.784 or 3.78 is a sound assumption which seems to be wrong, but in reality is not. In the above equation for Wa, the carbon, hydrogen, or sulfur (MO2 / DO2)Mx, where MO2 is the molecular weight of oxygen, coefcient, Cx O2; DO2 is the decimal fraction for the percent, by weight, of oxygen, O2, in dry air containing atmospheric nitrogen, (N2), and small amounts of inert and inactive gases: Mx is the formula weight of the combustible element in the fuel, as indicated by its relative amount as a reactant in the combustion equation. The alternate evaluation of Cx is obtained from stoichiometric chemical equations for burning the O2 (?)N2 CO2 (?)N2; 2H2 combustible elements of the fuel, i.e., C O2 (?)N2 2H2O (?)N2; S O2 (?)N2 SO2 (?)N2. Evidently, Cx [MO2 (? MN2)] / Mx, where MN2 is the molecular weight of nitrogen, N2, and the other items are as before. Equating the two expressions, Cx [MO2 (? MN2)] / Mx (MO2 / DO2)Mx, reveals that the Mx terms cancel out, indicating that the formula weight(s) of com(1 bustible components are irrelevant in solving for (?). Then, (?) DO2)[MO2 / (MN2 DO2)]. From the above-mentioned book by Kiefer, et al., 0.23188. From Marks Standard Handbook for Mechanical Engineers, DO2 31.9988 and MN2 28.0134. Thus, (?) (1 McGraw-Hill, Inc., MO2 0.23188)[31.9988 / (28.0134 0.23188)] 3.7838. This demonstrates that the use of (?) 3.784, or 3.78, is justied for combustion equations. By using either of the two evaluation equations for Cx, and with accurate values of Mx, i.e., MC 12.0111; MH 2 2 1.00797 4.0319; MS 32.064, from Marks M.E. Handbook, the more precise values for CC, CH, and CS are found out to be 11.489, 34.227, and 4.304, respectively. However, the actual Cx values, 11.5, 34.5, and 4.32, used in the formula for Wa are both brief for simplicity and rounded up to be on the safe side.

REGENERATIVE-CYCLE GAS-TURBINE ANALYSIS


What is the cycle air rate, lb / kWh, for a regenerative gas turbine having a pressure ratio of 5, an air inlet temperature of 60 F (15.6 C), a compressor discharge temperature of 1500 F (815.6 C), and performance in accordance with Fig. 60? Determine the cycle thermal efciency and work ratio. What is the power output of a regenerative gas turbine if the work input to the compressor is 4400 hp (3281.1 kW)?
Calculation Procedure:

1. Determine the cycle rate Use Fig. 60, entering at the pressure ratio of 5 in Fig. 60c and projecting to the 1500 F (815.6 C) curve. At the left, read the cycle air rate as 52 lb / kWh (23.6 kg / kWh).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.84


POWER GENERATION

FIGURE 60 (a) Schematic of regenerative gas turbine; (b), (c), and (d ) gas-turbine performance based on a regenerator effectiveness of 70 percent, compressor and turbine efciency of 85 percent; air inlet 60 F (15.6 C); no pressure losses.

2. Find the cycle thermal efciency Enter Fig. 60b at the pressure ratio of 5 and project vertically to the 1500 F (815.6 C) curve. At left, read the cycle thermal efciency as 35 percent. Note that this point corresponds to the maximum efciency obtainable from this cycle. 3. Find the cycle work ratio Enter Fig. 60d at the pressure ratio of 5 and project vertically to the 1500 F (815.6 C) curve. At the left, read the work ratio as 44 percent. 4. Compute the turbine power output For any gas turbine, the work ratio, percent 100wc / wt, where wc work input work output of the turbine, hp. Substituting gives 44 to the turbine, hp; wt 100(4400) / wt ; wt 100(4400) / 44 10,000 hp (7457.0 kW). Related Calculations. Use this general procedure to analyze gas turbines for power-plant, marine, and portable applications. Where the operating conditions are

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.85

different from those given here, use the manufacturers engineering data for the turbine under consideration. Figure 61 shows the effect of turbine-inlet temperature, regenerator effectiveness, and compressor-inlet-air temperature on the performance of a modern gas turbine. Use these curves to analyze the cycles of gas turbines being considered for a particular application if the operating conditions are close to those plotted.

FIGURE 61 (a) Effect of turbine-inlet on cycle performance; (b) effect of regenerator effectiveness; (c) effect of compressor inlet-air temperature; (d ) effect of inlet-air temperature on turbinecycle capacity. These curves are based on a turbine and compressor efciency of 85 percent, a regenerator effectiveness of 70 percent, and a 1500 F (815.6 C) inlet-gas temperature.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.86


POWER GENERATION

EXTRACTION TURBINE kW OUTPUT


An automatic extraction turbine operates with steam at 400 lb / in2 absolute (2760 kPa), 700 F (371 C) at the throttle; its extraction pressure is 200 lb / in2 (1380 kPa) and it exhausts at 110 lb / in2 absolute (760 kPa). At full load 80,000 lb / h (600 kg / s) is supplied to the throttle and 20,000 lb / h (150 kg / s) is extracted at the bleed point. What is the kW output?

Calculation Procedure:

1. Determine steam conditions at the throttle, bleed point, and exhaust Steam ow through the turbine is indicated by enter at the throttle, extract at the bleed point, and exit at the exhaust, as shown in Fig. 62a . The steam process is considered to be at constant entropy, as shown by the vertical isentropic line in 400 Fig. 62b . At the throttle, where the steam enters at the given pressure, p1 700 F (371 C), steam enthalpy, lb / in2 absolute (2760 kPa) and temperature, t1 1362.7 Btu / lb (3167.6 kJ / kg) and its entropy, s1 1.6398, as indicated by h1 Table 3, Vapor of the Steam Tables mentioned under Related Calculations of this procedure. From the Mollier chart, a supplement to the Steam Tables, the following conditions are found along the vertical isentropic line where s1 sx s2 1.6398 Btu / (lb F) (6.8655 kJ / kg C): At the bleed point, where the given extraction pressure, px 200 lb / in2 (1380 1284 Btu / lb kPa) and the entropy, sx, is as mentioned above, the enthalpy, hx (2986 kJ / kg) and the temperature tx 528 F (276 C). At the exit, where the given 110 lb / in2 (760 kPa) and the entropy, s2, is as mentioned exhaust pressure, p2 1225 Btu / lb (2849 kJ / kg) and the temperature, t2 above, the enthalpy, h2 400 F (204 C).

FIGURE 62 (a) Turbine steam ow diagram. (b) Temperature-entropy schematic for steam ow.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.87

2. Compute the total available energy to the turbine Between the throttle and the bleed point the available energy to the turbine, AE1 Q1(h1 hx ), where the full load rate of steam ow, Q1 80,000 lb / h (600 kg / s); 80,000 (1362.7 1284) 6.296 other values are as before. Hence, AE1 106 Btu / h (1845 kJ / s). Between the bleed point and the exhaust the available (Q1 Q2)(hx h2), where the extraction ow rate, energy to the turbine, AE2 20,000 lbm / h (150 kg / s); other values as before. Then, AE2 (80,000 Qx 20,000)(1284 1225) 3.54 106 Btu / h (1037 kJ / s). Total available energy to AE1 AE2 6.296 106 (3.54 106) 9.836 106 the turbine, AE Btu / h (172.8 103 kJ / s). 3. Compute the turbines kW output The power available to the turbine to develop power at the shaft, in kilowatts, kW AE / (Btu / kW h ) 9.836 106 / 3412.7 2880 kW. However, the actual power developed at the shaft, kWa kW e, where e is the mechanical efciency of the 0.90, then kWa 2880 0.90 2590 kW turbine. Thus, for an efciency, e (2590 kJ / s). Related Calculations. The Steam Tables appear in Thermodynamic Properties of Water Including Vapor, Liquid, and Solid Phases, 1969, Keenan, et al., John Wiley & Sons, Inc. Use later versions of such tables whenever available, as necessary.

Steam Properties and Processes


STEAM MOLLIER DIAGRAM AND STEAM TABLE USE
(1) Determine from the Mollier diagram for steam (a ) the enthalpy of 100 lb / in2 (abs) (689.5-kPa) saturated steam, (b ) the enthalpy of 10-lb / in2 (abs) (68.9-kPa) steam containing 40 percent moisture, (c ) the enthalpy of 100-lb / in2 (abs) (689.5kPa) steam at 600 F (315.6 C). (2) Determine from the steam tables (a ) the enthalpy, specic volume, and entropy of steam at 145.3 lb / in2 (gage) (1001.8 kPa); (b ) the enthalpy and specic volume of superheated steam at 1100 lb / in2 (abs) (7584.2 kPa) and 600 F (315.6 C); (c ) the enthalpy and specic volume of highpressure steam at 7500 lb / in2 (abs) (51,710.7 kPa) and 1200 F (648.9 C); (d ) the enthalpy, specic volume, and entropy of 10-lb / in2 (abs) (68.9-kPa) steam containing 40 percent moisture.
Calculation Procedure:

1. Use the pressure and saturation (or moisture ) lines to nd enthalpy (a ) Enter the Mollier diagram by nding the 100-lb / in2 (abs) (689.5-kPa) pressure line, Fig. 63. In the Mollier diagram for steam, the pressure lines slope upward to the right from the lower left-hand corner. For saturated steam, the enthalpy is read at the intersection of the pressure line with the saturation curve ce, Fig. 63. Thus, project along the 100-lb / in2 (abs) (689.5-kPa) pressure curve, Fig. 63, until it intersects the saturation curve, point g . From here project horizontally to

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.88


POWER GENERATION

FIGURE 63 Simplied Mollier diagram for steam.

the left-hand scale of Fig. 63 and read the enthalpy of 100-lb / in2 (abs) (689.5-kPa) saturated steam as 1187 Btu / lb (2761.0 kJ / kg). (The Mollier diagram in Fig. 63 has fewer grid divisions than large-scale diagrams to permit easier location of the major elements of the diagram.) (b ) On a Mollier diagram, the enthalpy of wet steam is found at the intersection of the saturation pressure line with the percentage-of-moisture curve corresponding to the amount of moisture in the steam. In a Mollier diagram for steam, the moisture curves slope downward to the right from the saturated liquid line cd, Fig. 63. To nd the enthalpy of 10-lb / in2 (abs) (68.9-kPa) steam containing 40 percent moisture, project along the 1-lb / in2 (abs) (68.9-kPa) saturation pressure line until the 40 percent moisture curve is intersected, Fig. 63. From here project horizontally to the left-hand scale and read the enthalpy of 10-lb / in2 (68.9-kPa) wet steam containing 40 percent moisture as 750 Btu / lb (1744.5 kJ / kg).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.89

2. Find the steam properties from the steam tables (a ) Steam tables normally list absolute pressures or temperature in degrees Fahrenheit as one of their arguments. Therefore, when the steam pressure is given in terms of a gage reading, it must be converted to an absolute pressure before the table can be entered. To convert gage pressure to absolute pressure, add 14.7 to the gage pg 14.7. In this instance, pa 145.3 14.7 160.0 lb / in2 pressure, or pa (abs) (1103.2 kPa). Once the absolute pressure is known, enter the saturation pressure table of the steam table at this value, and project horizontally to the desired values. For 160-lb / in2 (abs) (1103.2-kPa) steam, using the ASME or Keenan and KeyesThermodynamic Properties of Steam, we see that the enthalpy of evaporation hg 859.2 Btu / lb (1998.5 kJ / kg), and the enthalpy of saturated vapor hg 1195.1 Btu / lb (2779.8 kJ / kg), read from the respective columns of the steam tables. The specic volume vg of the saturated vapor of 160-lb / in2 (abs) (1103.2-kPa) steam is, from the tables, 2.834 ft3 / lb (0.18 m3 / kg), and the entropy sg is 1.5640 Btu / (lb F) [6.55 kJ / (kg C)]. (c ) Every steam table contains a separate tabulation of properties of superheated steam. To enter the superheated steam table, two arguments are neededthe absolute pressure and the temperature of the steam. To determine the properties of 1100-lb / in2 (abs) (7584.5-kPa) 600 F (315.6 C) steam, enter the superheated steam table at the given absolute pressure and project horizontally from this absolute pressure [1100 lb / in2 (abs) or 7584.5 kPa] to the column corresponding to the superheated temperature (600 F or 315.6 C) to read the enthalpy of the superheated vapor as h 1236.7 Btu / lb (2876.6 kJ / kg) and the specic volume of the superheated vapor v 0.4532 ft3 / lb (0.03 m3 / kg). (c ) For high-pressure steam use the ASMESteam Table, entering it in the same manner as the superheated steam table. Thus, for 7500-lb / in2 (abs) (51,712.5 kPa) 1200 F (648.9 C) steam, the enthalpy of the superheated vapor is 1474.9 Btu / lb (3430.6 kJ / kg), and the specic volume of the superheated vapor is 0.1060 ft3 / lb (0.0066 m3 / kg). (d ) To determine the enthalpy, specic volume, and the entropy of wet steam having y percent moisture by using steam tables instead of the Mollier diagram, apply these relations: h hg yhg / 100; v vg yvg / 100; s sg ysg / 100, where y percentage of moisture expressed as a whole number. For 10-lb / in2 (abs) (68.9-kPa) steam containing 40 percent moisture, obtain the needed valueshg, hg, vg, vg, sg, and sg from the saturation-pressure steam table and substitute in the above relations. Thus,

Note that Keenan and Keyes, in Thermodynamic Properties of Steam, do not tabulate vg . Therefore, this value must be obtained by subtraction of the tabulated values, or vg vg v. The value vg thus obtained is used in the relation for the volume of the wet steam. For 10-lb / in2 (abs) (68.9-kPa) steam containing 40 percent moisture, vg 38.42 ft3 / lb (2.398 m3 / kg) and v 0.017 ft3 / lb (0.0011 m3 / kg). Then vg 38.42 0.017 28.403 ft3 / lb (1.773 m3 / kg).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.90


POWER GENERATION

In some instances, the quality of steam may be given instead of its moisture content in percentage. The quality of steam is the percentage of vapor in the mixture. In the above calculation, the quality of the steam is 60 percent because 40 1 m, where m percentage of moisture, percent is moisture. Thus, quality expressed as a decimal.

INTERPOLATION OF STEAM TABLE VALUES


(1) Determine the enthalpy, specic volume, entropy, and temperature of saturated steam at 151 lb / in2 (abs) (1041.1 kPa). (2) Determine the enthalpy, specic volume, entropy, and pressure of saturated steam at 261 F (127.2 C). (3) Find the pressure of steam at 1000 F (537.8 C) if its specic volume is 2.6150 ft3 / lb (0.16 m3 / kg). (4) Calculate the enthalpy, specic volume, and entropy of 300-lb / in2 (abs) (2068.5kPa) steam at 567.22 F (297.3 C).

Calculation Procedure:

1. Use the saturation-pressure table Study of the saturation-pressure table shows that there is no pressure value for 151 lb / in2 (abs) (1041.1 kPa) listed. So it will be necessary to interpolate between the next higher and next lower tabulated pressure values. In this instance, these values are 152 and 150 lb / in2 (abs) (1048.0 and 1034.3 kPa), respectively. The pressure for which properties are being found [151 lb / in2 (abs) or 1041.1 kPa] is called the 1194.3 Btu / lb intermediate pressure. At 152 lb / in2 (abs) (1048.0 kPa), hg 2.977 ft3 / lb (0.19 m3 / kg); sg 1.5683 Btu / (lb F) [6.67 (2777.5 kJ / kg); vg kJ / (kg C) / t 359.46 F (181.9 C). At 150 lb / in2 (abs) (1034.3 kPa), hg 1194.1 3.015 ft3 / lb (0.19 m3 / kg); sg 1.5694 Btu / (lb F) Btu / lb (2777.5 kJ / kg); vg [6.57 kJ / (kg C); t 358.42 F (181.3 C). For the enthalpy, note that as the pressure increases, so does hg . Therefore, the enthalpy at 151 lb / in2 (abs) (1041.1 kPa), the intermediate pressure, will equal the enthalpy at 150 lb / in2 (abs) (1034.3 kPa) (the lower pressure used in the interpolation) plus the proportional change (difference between the intermediate pressure and the lower pressure) for a 1-lb / in2 (abs) (6.9-kPa) pressure increase. Or, at any higher pressure, hgi hgl [( pi pl ) / ( ph pl )](hh hl ), where hgi enthalpy enthalpy at the lower pressure used in the inat the intermediate pressure; hgl enthalpy at the higher pressure used in the interpolation; pi terpolation; hh intermediate pressure; ph and pl higher and lower pressures, respectively, used in the interpolation. Thus, from the enthalpy values obtained from the steam table 1194.1 [(151 for 150 and 152 lb / in2 (abs) (1034.3 and 1048.0 kPa), hgi 150) / (152 150)](1194.3 1194.1) 1194.2 Btu / lb (2777.7 kJ / kg) at 151 lb / in2 (abs) (1041.1 kPa) saturated. Next study the steam table to determine the direction of change of specic volume between the lower and higher pressures. This study shows that the specic volume decreases as the pressure increases. Therefore, the specic volume at 151 lb / in2 (abs) (1041.1 kPa) (the intermediate pressure) will equal the specic volume at 150 lb / in2 (abs) (1034.3 kPa) (the lower pressure used in the interpolation) minus the proportional change (difference between the intermediate pressure and the lower interpolating pressure) for a 1-lb / in2 (abs) pressure increase. Or, at any pressure, vgi vgl [( pi p l ) / ( ph pl )](vl vh ), where the subscripts are the same as

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.91

above and v specic volume at the respective pressure. With the volume values obtained from steam tables for 150 and 152 lb / in2 (abs) (1034.3 and 1048.0 kPa), vgi 3.015 [(151 150) / (152 150)](3.015 2.977) 2.996 ft3 / lb (0.19 m3 / kg) and 151 lb / in2 (abs) (1041.1 kPa) saturated. Study of the steam table for the direction of entropy change shows that entropy, like specic volume, decreases as the pressure increases. Therefore, the entropy at 151 lb / in2 (abs) (1041.1 kPa) (the intermediate pressure) will equal the entropy at 150 lb / in2 (abs) (1034.3 kPa) (the lower pressure used in the interpolation) minus the proportional change (difference between the intermediate pressure and the lower interpolating pressure) for a 1-lb / in2 (abs) (6.9-kPa) pressure increase. Or, at any sgl [( pi pl ) / ( ph pl )](sl sh ) 1.5164 [(151 higher pressure, sgi 150) / (152 150)](1.5694 1.5683) 1.56885 Btu / (lb F) [6.6 kJ / (kg C)] at 151 lb / in2 (abs) (1041.1 kPa) saturated. Study of the steam table for the direction of temperature change shows that the saturation temperature, like enthalpy, increases as the pressure increases. Therefore, the temperature at 151 lb / in2 (abs) (1041.1 kPa) (the intermediate pressure) will equal the temperature at 150 lb / in2 (abs) (1034.3 kPa) (the lower pressure used in the interpolation) plus the proportional change (difference between the intermediate pressure and the lower interpolating pressure) for a 1-lb / in2 (abs) (6.9-kPa) increase. tgl [( pi pl ) / ( ph pl )](th tl ) 358.42 Or, at any higher pressure, tgi [(151 150) / (152 150)](359.46 358.42) 358.94 F (181.6 C) at 151 lb / in2 (abs) (1041.1 kPa) saturated. 2. Use the saturation-temperature steam table Study of the saturation-temperature table shows that there is no temperature value of 261 F (127.2 C) listed. Therefore, it will be necessary to interpolate between the next higher and next lower tabulated values. In this instance these values are 262 and 260 F (127.8 and 126.7 C), respectively. The temperature for which properties are being found (261 F or 127.2 C) is called the intermediate temperature.

For enthalpy, note that as the temperature increases, so does hg . Therefore, the enthalpy at 261 F (127.2 C) (the intermediate temperature) will equal the enthalpy at 260 F (126.7 C) (the lower temperature used in the interpolation) plus the proportional change (difference between the intermediate temperature and the lower temperature) for a 1 F (0.6 C) temperature increase. Or, at any higher temperature, hgl [(ti tl ) / (th tl )](hh hl ), where hgl enthalpy at the lower temhgi perature used in the interpolation; hh enthalpy at the higher temperature used in the interpolation; ti intermediate temperature; th and tl higher and lower temperatures, respectively, used in the interpolation. Thus, from the enthalpy values obtained from the steam table for 260 and 262 F (126.7 and 127.8 C), hgi 1167.3 [(261 260) / (262 260)](1168.0 1167.3) 1167.65 Btu / lb (2716.0 kJ / kg) at 260 F (127.2 C) saturated. Next, study the steam table to determine the direction of change of specic volume between the lower and higher temperatures. This study shows that the

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.92


POWER GENERATION

specic volume decreases as the pressure increases. Therefore, the specic volume at 261 F (127.2 C) (the intermediate temperature) will equal the specic volume at 260 F (126.7 C) (the lower temperature used in the interpolation) minus the proportional change (difference between the intermediate temperature and the lower interpolating temperature) for a 1 F (0.6 C) temperature increase. Or, at any higher vgl [(ti tl ) / (th tl )](vl vh ) 11.763 [(261 260) / temperature, vgi 260)](11.763 11.396) 11.5795 ft3 / lb (0.7 m3 / kg) at 261 F (127.2 C) (262 saturated. Study of the steam table for the direction of entropy change shows that entropy, like specic volume, decreases as the temperature increases. Therefore, the entropy at 261 F (127.2 C) (the intermediate temperature) will equal the entropy at 260 F (126.7 C) (the lower temperature used in the interpolation) minus the proportional change (difference between the intermediate temperature and the lower temperature) sgl for a 1 F (0.6 C) temperature increase. Or, at any higher temperature, sgi [(ti tl ) / (hh tl )](sl sh ) 1.6860 [(261 260) / (262 260)](1.6860 1.6833) 1.68465 Btu / (lb F) [7.1 kJ / (kg C)] at 261 F (127.2 C). Study of the steam table for the direction of pressure change shows that the saturation pressure, like enthalpy, increases as the temperature increases. Therefore, the pressure at 261 F (127.2 C) (the intermediate temperature) will equal the pressure at 260 F (126.7 C) (the lower temperature used in the interpolation) plus the proportional change (difference between the intermediate temperature and the lower interpolating temperature) for a 1 F (0.6 C) temperature increase. Or, at any higher pgl [(ti tl ) / (th tl )]( ph pl ) 35.429 [(261 temperature, pgi 260)(262 260)](36.646 35.429) 36.0375 lb / in2 (abs) (248.5 kPa) at 261 F (127.2 C) saturated. 3. Use the superheated steam table Choose the superheated steam table for steam at 1000 F (537.9 C) and 2.6150 ft3 / lb (0.16 m3 / kg) because the highest temperature at which saturated steam can exist is 705.4 F (374.1 C). This is also the highest temperature tabulated in some saturated-temperature tables. Therefore, the steam is superheated when at a temperature of 1000 F (537.9 C). Look down the 1000 F (537.9 C) columns in the superheated steam table until a specic volume value of 2.6150 (0.16) is found. This occurs between 325 lb / in2 (abs) (2240.9 kPa, v 2.636 or 0.16) and 330 lb / in2 (abs) (2275.4 kPa, v 2.596 or 0.16). Since there is no volume value exactly equal to 2.6150 tabulated, it will be necessary to interpolate. List the values from the steam table thus:

Note that as the pressure rises, at constant temperature, the volume decreases. Therefore, the intermediate (or unknown) pressure is found by subtracting from the higher interpolating pressure [330 lb / in2 (abs) or 2275.4 kPa in this instance] the product of the proportional change in the specic volume and the difference in the pressures used for the interpolation. Or, pgi ph [vi vh ) / (vl vh )]( ph pl ), where the subscripts h, l, and i refer to the high, low, and intermediate (or unknown)

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.93

pressures, respectively. In this instance, pgi 330 [(2.615 2.596) / (2.636 2.596)](330 325) 327.62 lb / in2 (abs) (2258.9 kPa) at 1000 F (537.9 kPa) and a specic volume of 2.6150 ft3 / lb (0.16 m3 / kg). 4. Use the superheated steam table When a steam pressure and temperature are given, determine, before performing any interpolation, the state of the steam. Do this by entering the saturation-pressure table at the given pressure and noting the saturation temperature. If the given temperature exceeds the saturation temperature, the steam is superheated. In this instance, the saturation-pressure table shows that at 300 lb / in2 (abs) (2068.5 kPa) the saturation temperature is 417.33 F (214.1 C). Since the given temperature of the steam is 567.22 F (297.3 C), the steam is superheated because its actual temperature is greater than the saturation temperature. Enter the superheated steam table at 300 lb / in2 (abs) (2068.5 kPa), and nd the next temperature lower than 567.22 F (297.3 C); this is 560 F (293.3 C). Also nd the next higher temperature; this is 580 F (304.4 C). Tabulate the enthalpy, specic volume, and entropy for each temperature thus:

Use the same procedures for each propertyenthalpy, specic volume, and entropyas given in step 2 above; but change the sign between the lower volume and entropy and the proportional factor (temperature in this instance), because for superheated steam the volume and entropy increase as the steam temperature increases. Thus

Note: Also observe the direction of change of a property before interpolating. Use a plus or minus sign between the higher interpolating value and the proportional change depending on whether the tabulated value increases ( ) or decreases ( ).

CONSTANT-PRESSURE STEAM PROCESS


Three pounds of wet steam, containing 15 percent moisture and initially at a presC ) to sure of 400 lb / in2 (abs) (2758.0 kPa), expands at constant pressure (P 600 F (315.6 C). Determine the initial temperature T1, enthalpy H1, internal energy E1, volume V1, entropy S1, nal entropy H2, internal energy E2, volume V2, entropy

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.94


POWER GENERATION

S2, heat added to the steam Q1, work output W2, change in initial energy E, change in specic volume V, change in entropy S .

Calculation Procedure:

1. Determine the initial steam temperature from the steam tables Enter the saturation-pressure table at 400 lb / in2 (abs) (2758.0 kPa), and read the saturation temperature as 444.59 F (229.2 C). 2. Correct the saturation values for the moisture of the steam in the initial state Sketch the process on a pressure-volume (P-V ), Mollier (H-S ), or temperature entropy (T-S ) diagram, Fig. 64. In state 1, y moisture content 15 percent. Using the appropriate values from the saturation-pressure steam table for 40 lb / in2 (abs) (2758.0 kPa), correct them for a moisture content of 15 percent:

3. Determine the steam properties in the nal state Since this is a constant-pressure process, the pressure in state 2 is 400 lb / in2 (abs) (2758.0 kPa), the same as state 1. The nal temperature is given as 600 F (315.6 C). This is greater than the saturation temperature of 444.59 F (229.2 C). Hence, the steam is superheated when in state 2. Use the superheated steam tables, entering at 400 lb / in2 (abs) (2758.8 kPa) and 600 F (315.6 C). At this condition, H2 1306.9 1.477 ft3 / lb (0.09 m3 / kg). Then E2 h2g P2V2 / Btu / lb (3039.8 kJ / kg); V2 J 1306.9 400(144)(1.477) / 778 1197.5 Btu / lb (2785.4 kJ / kg). In this equation, the constant 144 converts pounds per square inch to pounds per square foot, absolute, and J mechanical equivalent of heat 778 ft lb / Btu (1 N m / J). From the steam tables, S2 1.5894 Btu / (lb F) [6.7 kJ / (kg C)].

FIGURE 64 Constant-pressure process.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.95

4. Compute the process inputs, outputs, and changes (P1 / J )(V2 V1)m [400(144) / 778](1.4770 0.9900)(3) 108.1 Btu W2 (114.1 kJ). In this equation, m weight of steam used in the process 3 lb (1.4 kg). Then

5. Check the computations The work output W2 should equal the change in internal energy plus the heat input, E1 E2 Q1 550.2 658.5 108.3 Btu (114.3 kJ). This value or W2 very nearly equals the computed value of W2 108.1 Btu (114.1 kJ) and is close enough for all normal engineering computations. The difference can be traced to calculator input errors. In computing the work output, the internal-energy change has a negative sign because there is a decrease in E during the process. Related Calculations. Use this procedure for all constant-pressure steam processes.

CONSTANT-VOLUME STEAM PROCESS


Five pounds (2.3 kg) of wet steam initially at 120 lb / in2 (abs) (827.4 kPa) with 30 C ) to a nal temperature of percent moisture is heated at constant volume (V 1000 F (537.8 C). Determine the initial temperature T1, enthalpy H1, internal energy E1, volume V1, nal pressure P2, enthalpy H2, internal energy E2, volume V2, heat added Q1, work output W, change in internal energy E, volume V, and entropy S.

Calculation Procedure:

1. Determine the initial steam temperature from the steam tables Enter the saturation-pressure table at 120 lb / in2 (abs) (827.4 kPa), the initial pressure, and read the saturation temperature T1 341.25 F (171.8 C). 2. Correct the saturation values for the moisture in the steam in the initial state Sketch the process on P-V, H-S, or T-S diagrams, Fig. 65. Using the appropriate values from the saturation-pressure table for 120 lb / in2 (abs) (827.4 kPa), correct them for a moisture content of 30 percent:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.96


POWER GENERATION

FIGURE 65 Constant-volume process.

3. Determine the steam volume in the nal state 1000 F (537.8 C). Since this is a constant-volume process, We are given T2 V1 2.6150 ft3 / lb (0.16 m3 / kg). The total volume of the vapor equals the V2 product of the specic volume and the number of pounds of vapor used in the process, or total volume 2.6150(5) 13.075 ft3 (0.37 m3). 4. Determine the nal steam pressure The nal steam temperature (1000 F or 537.8 C) and the nal steam volume (2.6150 ft3 / lb or 0.16 m3 / kg) are known. To determine the nal steam pressure, nd in the steam tables the state corresponding to the above temperature and specic volume. Since a temperature of 1000 F (537.8 C) is higher than any saturation temperature (705.4 F or 374.1 C is the highest saturation temperature for saturated steam), the steam in state 2 must be superheated. Therefore, the superheated steam tables must be used to determine P2. Enter the 1000 F (537.8 C) column in the steam table, and look for a superheated-vapor specic volume of 2.6150 ft3 / lb (0.16 m3 / kg). At a pressure of 325 lb / in2 (abs) (2240.9 kPa),

and at a pressure of 330 lb / in2 (abs) (227.4 kPa)

Thus, 2.6150 lies between 325 and 330 lb / in2 (abs) (2240.9 and 2275.4 kPa). To determine the pressure corresponding to the nal volume, it is necessary to inter330 [(2.615 2.596) / polate between the specic-volume values, or P2 (2.636 2.596)](330 325) 327.62 lb / in2 (abs) (2258.9 kPa). In this equation, the volume values correspond to the upper [330 lb / in2 (abs) or 2275.4 kPa], lower [325 lb / in2 (abs) or 2240.9 kPa], and unknown pressures.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.97

5. Determine the nal enthalpy, entropy, and internal energy The nal enthalpy can be interpolated in the same manner, using the enthalpy at 1524.5 [(2.615 2.596) / each volume instead of the pressure. Thus H2 2.596)](1524.5 1524.4) 1524.45 Btu / lb (3545.8 kJ / kg). Since the (2.636 difference in enthalpy between the two pressures is only 0.1 Btu / lb (0.23 kJ / kg) ( 1524.5 1524.4), the enthalpy at 327.62 lb / in2 (abs) could have been assumed equal to the enthalpy at the lower pressure [325 lb / in2 (abs) or 2240.9 kPa], or 1524.4 Btu / lb (3545.8 kJ / kg), and the error would have been only 0.05 Btu / lb (0.12 kJ / kg), which is negligible. However, where the enthalpy values vary by more than 1.0 Btu / lb (2.3 kJ / kg), interpolate as shown, if accurate results are desired. Find S2 by interpolating between pressures, or

6. Compute the changes resulting from the process (E2 E1)m (1365.9 868.9)(5) 2485 Btu (2621.8 kJ); S Here Q1 (S2 S1)m (1.7854 1.2589)(5) 2.6325 Btu / F (5.0 kJ / C). By denition, W 0; V 0; E Q1. Note that the curvatures of the constantvolume line on the T-S chart, Fig. 65, are different from the constant-pressure line, Fig. 64. Adding heat Q1 to a constant-volume process affects only the internal energy. The total entropy change must take into account the total steam mass m 5 lb (2.3 kg). Related Calculations. Use this general procedure for all constant-volume steam processes.

CONSTANT-TEMPERATURE STEAM PROCESS


Six pounds (2.7 kg) of wet steam initially at 1200 lb / in2 (abs) (8274.0 kPa) and C ) to 300 lb / in2 (abs) 50 percent moisture expands at constant temperature (T (2068.5 kPa). Determine the initial temperature T1, enthalpy H1, internal energy E1, specic volume V1, entropy S1, nal temperature T2, enthalpy H2, internal energy E2, volume V2, entropy S2, heat added Q1, work output W2, change in internal energy E, volume V, and entropy S.

Calculation Procedure:

1. Determine the initial steam temperature from the steam tables Enter the saturation-pressure table at 1200 lb / in2 (abs) (8274.0 kPa), and read the saturation temperature T1 567.22 F (297.3 C). 2. Correct the saturation values for the moisture in the steam in the initial state Sketch the process on P-V, H-S, or T-S diagrams, Fig. 66. Using the appropriate values from the saturation-pressure table for 1200 lb / in2 (abs) (8274.0 kPa), correct them for the moisture content of 50 percent:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.98


POWER GENERATION

FIGURE 66 Constant-temperature process.

3. Determine the steam properties in the nal state Since this is a constant-temperature process, T2 T1 567.22 F (297.3 C); P2 300 lb / in2 (abs) (2068.5 kPa), given. The saturation temperature of 300 lb / in2 (abs) (2068.5 kPa) is 417.33 F (214.1 C). Therefore, the steam is superheated in the nal state because 567.22 F (297.3 C) 417.33 F (214.1 C), the saturation temperature. To determine the nal enthalpy, entropy, and specic volume, it is necessary to interpolate between the known nal temperature and the nearest tabulated temperatures greater and less than the nal temperature.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.99

4. Compute the process changes T (S2 S1)m, where T1 Here Q1 (567.22 460)(1.6093 1.0689)(6)

absolute initial temperature, R. So Q1 3330 Btu (3513.3 kJ). Then

Related Calculations. Use this procedure for any constant-temperature steam process.

CONSTANT-ENTROPY STEAM PROCESS


Ten pounds (4.5 kg) of steam expands under two conditionsnonow and steady C ) from an initial pressure of 2000 lb / in2 (abs) owat constant entropy (S (13,790.0 kPa) and a temperature of 800 F (426.7 C) to a nal pressure of 2 lb / in2 (abs) (13.8 kPa). In the steady-ow process, assume that the initial kinetic energy Ek 1 the nal kinetic energy Ek 2. Determine the initial enthalpy H1, internal energy E1, volume V1, entropy S1, nal temperature T2, percentage of moisture y, enthalpy H2, internal energy E2, volume V2, entropy S2, change in internal energy E, enthalpy H, entropy S, volume V, heat added Q1, and work output W2.

Calculation Procedure:

1. Determine the initial enthalpy, volume, and entropy from the steam tables Enter the superheated-vapor table at 2000 lb / in2 (abs) (13,790.0 kPa) and 800 F (427.6 C), and read H1 1335.5 Btu / lb (3106.4 kJ / kg); V1 0.3074 ft3 / lb (0.019 m3 / kg); S1 1.4576 Btu / (lb F) [6.1 kJ / (kg C)]. 2. Compute the initial energy

3. Determine the vapor properties on the nal state Sketch the process on P-V, H-S, or T-S diagrams, Fig. 67. Note that the expanded steam is wet in the nal state because the 2-lb / in2 (abs) (13.8-kPa) pressure line is under the saturation curve on the H-S and T-S diagrams. Therefore, the vapor properties in the nal state must be corrected for the moisture content. Read, from the saturation-pressure steam table, the liquid and vapor properties at 2 lb / in2 (abs) (13.8 kPa). Tabulate these properties thus:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.100


POWER GENERATION

FIGURE 67 Constant-entropy process.

Since this is a constant-entropy process, S2 S1 percentage of moisture in the nal state. Or, y2 1.4576) / 1.7451 0.265, or, 26.5 percent. Then

sg (sg

y2sg . Solve for y2, the S1) / sg (1.9200

4. Compute the changes resulting from the process The total change in properties is for 10 lb (4.5 kg) of steam, the quantity used in this process. Thus,

So Q1 0 Btu. (By denition, there is no transfer of heat in a constant-entropy E 4236 Btu (4469.2 kJ). Steady ow W2 H process.) Nonow W2 4902 Btu (5171.9 kJ).

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.101

Note: In a constant-entropy process, the nonow work depends on the change in internal energy. The steady-ow work depends on the change in enthalpy and is larger than the nonow work by the amount of the change in the ow work.

IRREVERSIBLE ADIABATIC EXPANSION OF STEAM


Ten pounds (4.5 kg) of steam undergoes a steady-ow expansion from an initial pressure of 2000 lb / in2 (abs) (13,790.0 kPa) and a temperature 800 F (426.7 C) to a nal pressure of 2 lb / in2 (abs) (13.9 kPa) at an expansion efciency of 75 percent. In this steady ow, assume Ek 1 Ek 2. Determine E, H, S, V, Q, and W2.
Calculation Procedure:

1. Determine the initial vapor properties from the steam tables Enter the superheated-vapor tables at 2000 lb / in2 (abs) (13,790.0 kPa) and 800 F (426.7 C), and read H1 1335.5 Btu / lb (3106.4 kJ / kg); V1 0.3074 ft3 / lb 1221.6 Btu / lb (2840.7 kJ / kg); S1 1.4576 Btu / (lb F) (0.019 m3 / kg); E1 [6.1 kJ / (kg C)]. 2. Determine the vapor properties in the nal state Sketch the process on P-V, H-S, or T-S diagram, Fig. 68. Note that the expanded steam is wet in the nal state because the 2-lb / in2 (abs) (13.9-kPa) pressure line is under the saturation curve on the H-S and T-S diagram. Therefore, the vapor properties in the nal state must be corrected for the moisture content. However, the actual nal enthalpy cannot be determined until after the expansion efciency [H1 H2(H1 H2s )] is evaluated. To determine the nal enthalpy H2, another enthalpy H2s must be computed by assuming a constant-entropy expansion to 2 lb / in2 (abs) (13.8 kPa) and a temperature of 126.08 F (52.3 C). Enthalpy H2s will then correspond to a constant-entropy expansion into the wet region, and the percentage of moisture will correspond to

FIGURE 68 Irreversible adiabatic process.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.102


POWER GENERATION

the nal state. This percentage is determined by nding the ratio of sg S1 to sg, or y2s sg S1 / sg 1.9200 1.4576 / 1.7451 0.265, where sg and sg are entropies at 2 lb / in2 (abs) (13.8 kPa). Then H2s hg y2s hg 1116.2 0.265(1022.2) 845.3 Btu / lb (1966.2 kJ / kg). In this relation, hg and hg are enthalpies at 2 lb / in2 (abs) (13.8 kPa). H2 / (H1 H2s ) actual The expansion efciency, given as 0.75, is H1 work / ideal work 0.75 1335.5 H2 / (1335.5 845.3). Solve for H2 967.9 Btu / lb (2251.3 kJ / kg). Next, read from the saturation-pressure steam table the liquid and vapor properties at 2 lb / in2 (abs) (13.8 kPa). Tabulate these properties thus:

Since the actual nal enthalpy H2 is different from H2s, the nal actual moisture hg H2 / hg 1116.1 967.9 / y2 must be computed by using H2. Or, y2 1022.2 0.1451. Then

3. Compute the changes resulting from the process The total change in properties is for 10 lb (4.5 kg) of steam, the quantity used in this process. Thus

So Q 0; by denition, W2 process.

3676 Btu (3878.4 kJ) for the steady-ow

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.103

IRREVERSIBLE ADIABATIC STEAM COMPRESSION


Two pounds (0.9 kg) of saturated steam at 120 lb / in2 (abs) (827.4 kPa) with 80 percent quality undergoes nonow adiabatic compression to a nal pressure of 1700 lb / in2 (abs) (11,721.5 kPa) at 75 percent compression efciency. Determine the nal steam temperature T2, change in internal energy E, change in entropy S, work input W, and heat input Q.
Calculation Procedure:

1. Determine the vapor properties in the initial state 341.25 F (171.8 C) at a pressure From the saturation-pressure steam tables, T1 0.8, E1 u x1ug of 120 lb / in2 (abs) (827.4 kPa) saturated. With x1 312.05 0.8(795.6) 948.5 Btu / lb (2206.5 kJ / kg), from internal-energy values s x1sg 0.4916 from the steam tables. The initial entropy is S1 0.8(1.0962) 1.3686 Btu / (lb F) [5.73 kJ / (kg C)]. 2. Determine the vapor properties in the nal state Sketch a T-S diagram of the process, Fig. 69. Assume a constant-entropy compresS1 1.3686 Btu / (lb F) [5.7 sion from the initial to the nal state. Then S2s kJ / (kg C)]. The nal pressure, 1700 lb / in2 (abs) (11,721.5 kPa), is known, as is the nal entropy, 1.3686 Btu / (lb F) [5.7 kJ / (kg C)] with constant-entropy expansion. The T-S diagram (Fig. 69) shows that the steam is superheated in the nal state. Enter the superheated steam table at 1700 lb / in2 (abs) (11,721.5 kPa), project across to an entropy of 1.3686, and read the nal steam temperature as 650 F (343.3 C). (In most cases, the nal entropy would not exactly equal a tabulated value, and it would be necessary to interpolate between tabulated entropy values to determine the intermediate pressure value.) From the same table, at 1700 lb / in2 (abs) (11.721.5 kPa) and 650 F (343.3 C), 1214.4 Btu / lb (2827.4 kJ / kg); V2s 0.2755 ft3 / lb (0.017 m3 / lb). Then H2s

FIGURE 69 Irreversible adiabatic compression process.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.104


POWER GENERATION

E2s H2s P2V2s / J 1214.4 1700(144)(0.2755) / 788 1127.8 Btu / lb (2623.3 kJ / kg). Since E1 and E2s are known, the ideal work W can be computed. Or, W E2s E1 1127.8 948.5 179.3 Btu / lb (417.1 kJ / kg). 3. Compute the vapor properties of the actual compression Since the compression efciency is known, the actual nal internal energy can be found from compression efciency ideal W / actual W E2s E1 / (E2 E1), or 1127.8 948.5 / (E2 948.5); E2 1187.6 Btu / lb (2762.4 kJ / kg). Then 0.75 E (E2 E2)m (1187.6 948.5)(2) 478.2 Btu (504.5 kJ) for 2 lb (0.9 kg) E 478.2 Btu (504.5 kJ). By denition, of steam. The actual work input W Q 0. Last, the actual nal temperature and entropy must be computed. The nal actual (1187.6 Btu / lb (2762.4 kJ / kg) is known. Also, the T-S diainternal energy E2 gram shows that the steam is superheated. However, the superheated steam tables do not list the internal energy of the steam. Therefore, it is necessary to assume a nal temperature for the steam and then compute its internal energy. The computed value is compared with the known internal energy, and the next assumption is adjusted as necessary. Thus, assume a nal temperature of 720 F (382.2 C). This assumption is higher than the ideal nal temperature of 650 F (343.3 C) because the T-S diagram shows that the actual nal temperature is higher than the ideal nal temperature. Using values from the superheated steam table for 1700 lb / in2 (abs) (11,721.5 kPa) and 720 F (382.2 C), we nd E H PV J 1288.4 1700(144)(0.3283) 778 1185.1 Btu / lb (2756.5 kJ / kg)

This value is less than the actual internal energy of 1187.6 Btu / lb (2762.4 kJ / kg). Therefore, the actual temperature must be higher than 720 F (382.2 C), since the internal energy increases with temperature. To obtain a higher value for the internal energy to permit interpolation between the lower, actual, and higher values, assume a higher nal temperaturein this case, the next temperature listed in the steam table, or 740 F (393.3 C). Then, for 1700 lb / in2 (abs) (11,721.5 kPa) and 740 F (393.3 C), E 1305.8 1700(144)(0.3410) 778 1198.5 Btu / lb (2757.7 kJ / kg)

This value is greater than the actual internal energy of 1187.6 Btu / lb (2762.4 kJ / kg). Therefore, the actual nal temperature of the steam lies somewhere between 720 and 740 F (382.2 and 393.3 C). Interpolate between the known internal energies to determine the nal steam temperature and nal entropy. Or, T2 S1 720 1.4333 1178.6 1198.5 1187.6 1198.5 1185.1 (740 1185.1 720) 723.7 F (384.3 C) 1.4333)

1185.1 (1.4480 1185.1 1.3686)(2)

1.4360 Btu / (lb F) [6.0 kJ / (kg C)] S (S2 S1)m (1.4360 0.1348 Btu / F (0.26 kJ / C) Note that the nal actual steam temperature is 73.7 F (40.9 C) higher than that (650 F or 343.3 C) for the ideal compression.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.105

Related Calculations. Use this procedure for any irreversible adiabatic steam process.

THROTTLING PROCESSES FOR STEAM AND WATER


A throttling process begins at 500 lb / in2 (abs) (3447.5 kPa) and ends at 14.7 lb / in2 (abs) (101.4 kPa) with (1) steam at 500 lb / in2 (abs) (3447.5 kPa) and 500 F (260.0 C); (2) steam at 500 lb / in2 (abs) (3447.5 kPa) and 4 percent moisture; (3) steam at 500 lb / in2 (abs) (3447.5 kPa) with 50 percent moisture; and (4) saturated water at 500 lb / in2 (abs) (3447.5 kPa). Determine the nal enthalpy H2, temperature T2, and moisture content y2 for each process.

Calculation Procedure:

1. Compute the nal-state conditions of the superheated steam From the superheated steam table for 500 lb / in2 (abs) (3447.5 kPa) and 500 F (260.0 C), H1 1231.3 Btu / lb (2864.0 kJ / kg). By denition of a throttling process, H1 H2 1231.3 Btu / lb (2864.0 kJ / kg). Sketch the T-S diagram for a throttling process, Fig. 70. To determine the nal temperature, enter the superheated steam table at 14.7 lb / in2 (abs) (101.4 kPa), the nal pressure, and project across to an enthalpy value equal to or less than known enthalpy, 1231.3 Btu / lb (2864.0 kJ / kg). (The superheated steam table is used because the T-S diagram, Fig. 70, shows that the steam is superheated in the nal state.) At 14.7 lb / in2 (abs) (101.4 kPa) there is no tabulated enthalpy value that exactly equals 1231.3 Btu / lb (2864.0 kJ / kg). The next lower value is 1230 Btu / lb (2861.0 kJ / kg) at T 380 F (193.3 C). The next higher value at 14.7 lb / in2 (abs)(101.4 kPa) is 1239.9 Btu / lb (2884.0 kJ / kg) at T 400 F (204.4 C). Interpolate between these enthalpy values to nd the nal steam temperature:

FIGURE 70 Throttling process for steam.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.106


POWER GENERATION

T2

380

1231.3 1239.9

1230.5 (400 1230.5

380)

381.7 F (194.3 C)

The steam does not contain any moisture in the nal state because it is superheated. 2. Compute the nal-state conditions of the slightly wet steam Determine the enthalpy of 500-lb / in2 (abs) (3447.5-kPa) saturated steam from the saturation-pressure steam table: hg 1204.4 Btu / lb (2801.4 kJ / kg) hg 755.0 Btu / lb (1756.1 kJ / kg)

Correct the enthalpy for moisture: H1 hg y1hg 1204.4 0.04(755.0) 1174.2 Btu / lb (2731.2 kJ / kg)

Then, by denition, H2 H1 1174.2 Btu / lb (2731.2 kJ / kg). Determine the nal condition of the throttled steam (wet, saturated, or superheated) by studying the T-S diagram. If a diagram were not drawn, you would enter the saturation-pressure steam table at 14.7 lb / in2 (abs) (101.4 kPa), the nal pressure, and check the tabulated hg . If the tabulated hg were greater than H1, the throttled steam would be superheated. If the tabulated hg were less than H1, the throttled steam would be saturated. Examination of the saturation-pressure steam table shows that the throttled steam is superheated because H1 hg . Next, enter the superheated steam table to nd an enthalpy value of H1 at 14.7 lb / in2 (abs) (101.4 kPa). There is no value equal to 1174.2 Btu / lb (2731.2 kJ / kg). The next lower value is 1173.8 Btu / lb (2730.3 kJ / kg) at T 260 F (126.7 C). The next higher value at 14.7 lb / in2 (abs) (101.4 kPa) is 1183.3 Btu / lb (2752.4 kJ / kg) at T 280 F (137.8 C). Interpolate between these enthalpy values to nd the nal steam temperature: T2 260 1174.2 1183.3 1173.8 (280 1173.8 260) 260.8 F (127.1 C)

This is higher than the temperature of saturated steam at 14.7 lb / in2 (abs) (101.4 kPa)212 F (100 C) giving further proof that the throttled steam is superheated. The throttled steam, therefore, does not contain any moisture. 3. Compute the nal-state conditions of the very wet steam Determine the enthalpy of 500-lb / in2 (abs) (3447.5-kPa) saturated steam from the saturation-pressure steam table. Or, hg 1204.4 Btu / lb (2801.4 kJ / kg); hg 755.0 Btu / lb (1756.1 kJ / kg). Correct the enthalpy for moisture: H1 H2 hg y1hg 1204.4 0.5(755.0) 826.9 Btu / lb (1923.4 kJ / kg)

Then, by denition, H2 H1 826.9 Btu / lb (1923.4 kJ / kg). Compare the nal enthalpy, H2 826.9 Btu / lb (1923.4 kJ / kg), with the enthalpy of saturated steam at 14.7 lb / in2 (abs) (101.4 kPa), or 1150.4 Btu / lb (2675.8 kJ / kg). Since the nal enthalpy is less than the enthalpy of saturated steam at the same hg y2hg, y2 (hg H1) / hg . pressure, the throttled steam is wet. Since H1 With a nal pressure of 14.7 lb / in2 (abs) (101.4 kPa), use hg and hg values at this pressure. Or, y2 1150.4 826.9 970.3 0.3335, or 33.35%

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.107

The nal temperature of the steam T2 is the same as the saturation temperature at the nal pressure of 14.7 lb / in2 (abs) (101.4 kPa), or T2 212 F (100 C). 4. Compute the nal-state conditions of saturated water Determine the enthalpy of 500-lb / in2 (abs) (3447.5-kPa) saturated water from the saturation-pressure steam table at 500 lb / in2 (abs) (3447.5 kPa); H1 h 449.4 Btu / lb (1045.3 kJ / kg) H2, by denition. The T-S diagram, Fig. 70, shows that the throttled water contains some steam vapor. Or, comparing the nal enthalpy of 449.4 Btu / lb (1045.3 kJ / kg) with the enthalpy of saturated liquid at the nal pressure, 14.7 lb / in2 (abs) (101.4 kPa), 180.07 Btu / lb (418.8 kJ / kg), shows that the liquid contains some vapor in the nal state because its enthalpy is greater. Since H1 H2 hg y2hg, y2 (hg H1) / hg . Using enthalpies at 14.7 lb / in2 (abs) (101.4 kPa) of hg 1150.4 Btu / lb (2675.8 kJ / kg) and hg 970.3 Btu / lb (2256.9 kJ / kg) from the saturation-pressure steam table, we get y2 1150.4 449.4 / 970.3 0.723. The nal temperature of the steam is the same as the saturation temperature at the nal pressure of 14.7 lb / in2 (abs) (101.4 kPa), or T2 212 F (100 C). Note: Calculation 2 shows that when you start with slightly wet steam, it can be throttled (expanded) through a large enough pressure range to produce superheated steam. This procedure is often used in a throttling calorimeter to determine the initial quality of the steam in a pipe. When very wet steam is throttled, calculation 3, the net effect may be to produce drier steam at a lower pressure. Throttling saturated water, calculation 4, can produce partial or complete ashing of the water to steam. All these processes nd many applications in power-generation and process-steam plants.

REVERSIBLE HEATING PROCESS FOR STEAM


Subcooled water at 1500 lb / in2 (abs) (10,342.5 kPa) and 140 F (60.0 C), state 1, Fig. 71, is heated at constant pressure to state 4, superheated steam at 1500 lb / in2 (abs) (10,342.5 kPa) and 1000 F (537.8 C). Find the heat added (1) to raise the compressed liquid to saturation temperature, (2) to vaporize the saturated liquid to

FIGURE 71 Reversible heating process.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.108


POWER GENERATION

saturated steam, (3) to superheat the steam to 1000 F (537.8 C), and (4) Q1, and S from state 1 to state 4.

V,

Calculation Procedure:

1. Sketch the T-S diagram for this process Figure 71 is typical of a steam boiler and superheater. Feedwater fed to a boiler is usually subcooled liquid. If the feedwater pressure is relatively high, subcooling must be taken into account, if accurate results are desired. Some authorities recommend that at pressures below 400 lb / in2 (abs) (2758.0 kPa) subcooling be ignored and values from the saturated-steam table be used. This means that the enthalpies and other properties listed in the steam table corresponding to the actual water temperature are sufciently accurate. But above 400 lb / in2 (abs) 2758.0 kPa), the compressed-liquid table should be used. 2. Determine the initial properties of the liquid 107.89 In the saturation-temperature steam table read, at 140 F (60.0 C), h Btu / lb (251.0 kJ / kg); p 2.889 lb / in2 (19.9 kPa); v 0.01629 ft3 / lb (0.0010 m3 / kg); s 0.1984 Btu / (lb F) [0.83 kJ / (kg C)]. Next, the enthalpy, volume, and entropy of the water at 1500 lb / in2 (abs) (10,342.5 kPa) and 140 F (60.0 C) must be found. Since the water is at a much higher pressure than that corresponding to its temperature [1500 versus 2.889 lb / in2 (abs)], the compressed-liquid portion of the steam table must be used. This table shows that three desired properties are plotted for 32, 100, and 200 F (0.0, 37.8, and 93.3 C) and higher temperatures. However, 140 F (60.0 C) is not included. Therefore, it is necessary to interpolate between 100 and 200 F (37.8 and 93.3 C). Thus, at 1500 lb / in2 (abs) (10,342.5 kPa) in the compressed-liquid table:

Each property is interpolated in the following way:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.109

These interpolated values must now be used to correct the saturation data at 140 F (60.0 C) to the actual subcooled state 1 properties. Thus, at 1500 lb / in2 (abs) (10,342.5 kPa) and 140 F (60.0 C).

DETERMINING STEAM ENTHALPY AND QUALITY USING THE STEAM TABLES


What is the enthalpy of 200-lb / in2 absolute (1378 kPa) wet steam having a 70 percent quality? Determine the quality of 160-lb / in2 absolute (1102.4 kPa) wet steam if its enthalpy is 900 Btu / lb (2093.4 kJ / kg). Use the steam tables to determine the needed values.

Calculation Procedure:

1. Compute the enthalpy of the wet steam The enthalpy of wet steam is a function of its quality, or dryness fraction. Thus, 70 percent quality steam will be 70 percent dry and 30 percent wet. In equation form, the enthalpy of wet steam, Btu / lb (kJ / kg), h Xhg (1 X )h, where X steam quality or dryness fraction expressed as a decimal; hg enthalpy of satuenthalpy of saturated water uid, Btu / lb rated steam vapor, Btu / lb (kJ / kg); h (kJ / kg). 0.70(1187.2) Substituting in this equation using steam-table values, h (1 0.70)298.4 920.56 Btu / lb (2141.22 kJ / kg). Note that the enthalpy of wet steam is not a simple product of the dryness factor (i.e. quality) and the enthalpy of the saturated steam. Instead, the enthalpy of the saturated liquid at the saturation pressure must also be included, adjusted for the quality of the steam. 2. Determine the quality of the steam Knowing the absolute pressure and enthalpy of steam we can determine its quality (h h) / (hg h), where the symbols are dened as given above. from, X Substituting, using steam-table values, X (900 335.93) / (1195.1 335.93) 0.6565; say 65.7 percent. Related Calculations. Wet steam is a fact of life in industrial plants of every type. When steam is wet it means that a larger number of pounds (kg) of steam are needed to perform a needed task. Thus, if a process requires 1000 lb (454 kg) of saturated dry steam, it will need 1050 lb (476.7 kg) of steam having a 95 percent quality, i.e. 5 percent more. With the 70 percent quality steam mentioned earlier, the same process would require 1300 lb (590.2 kg) of saturated dry steam. So it is easy to see why it is important to deliver dry saturated steam to a process because the overall steam consumption is reduced. In todays energy-conscious engineering world, wet steam is an undesirable commodity unless the wetness results from doing useful work. Where steam wetness occurs because of poor pipe or equipment insulation, shoddy piping layout, or other engineering or installation errors, energy is being wasted. As the above examples show, steam consumption, and generation cost, can rise as much as 30 percent because of wet steam. Every plant designer should keep wetness in mind when designing industrial steam plants of any type serving chemical, steel, textile, marine, automotive, aircraft, etc. industries.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.110


POWER GENERATION

The procedure given here can be used in any application where steam is a process uid, and this procedure can also be used when measuring steam quality using a calorimeter of any type.

MAXIMIZING COGENERATION ELECTRIC-POWER AND PROCESS-STEAM OUTPUT


An industrial cogeneration plant is being designed for a process requiring electric power and steam for operating the manufacturing equipment in the plant. In the design analysis a steam pressure of 650 lb / in2 (gage) (4478.5 kPa) saturated is being considered for a steam turbine to generate the needed electricity, with the exhaust steam being used in the process sections of the plant at 150 lb / in2 (gage) (1033.5 kPa). If greater process efciencies can be obtained in manufacturing with a higher exhaust temperature, compare the effect of greater turbine inlet pressure and temperature on the resulting exhaust steam temperature and heat content. Use typical pressure and temperature levels met in industrial steam-turbine applications.

Calculation Procedure:

1. Assemble data on typical industrial steam-turbine inlet conditions Using data obtained from steam-turbine manufacturers, list the typical inlet pressures and temperatures used today in a tabulation such as that in Fig. 72. This listing shows typical pressure ranges from 650 lb / in2 (gage) (4478.5 kPa) saturated to 1200 lb / in2 (gage) (8268 kPa) at temperatures from saturated, 498 F (259 C), to 950 F (510 C), at 1200 lb / in2 (gage). 2. Plot the turbine expansion process for each pressure being considered Using an H-s diagram, Fig. 72, plot the expansion from the turbine inlet to exhaust at 150 lb / in2 (gage) (1033.5 kPa). Read the temperature and the enthalpy at the exhaust and tabulate each value as in the gure. 3. Compute the percent increase in the exhaust enthalpy Using data from the H-s chart, we see that with an inlet pressure of 650 lb / in2 (gage) saturated (4487.5 kPa), the exhaust steam has 8 percent moisture and an enthalpy change of 70 Btu / lb (163.1 kJ / kg) with an exhaust temperature of 360 F (182 C). Raising the turbine inlet steam temperature to 750 F (398.9 C) increases the enthalpy change during expansion to 1380 1264 116 Btu / lb (270.28 kJ / kg). 70 46 Btu / lb (107.2 kJ / kg) over the saturatedThis is an increase of 116 steam inlet enthalpy change during expansion from inlet to exhaust. Then, the percent increase in enthalpy change for these two inlet conditions is 100(116 70) / 70 65.7 percent; say 66 percent, as tabulated. Continuing these calculations and tabulating the results shows thatfor the pressures and temperatures consideredan increase of up to 148 percent in the enthalpy change can be obtained. Likewise, an exhaust superheat up to 320 F (160 C) can be obtained. Depending on the process served, a suitable steam pressure and temperature can be chosen for the turbine inlet conditions to maximize the efciency of the process(es) served by this cogeneration plant.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.111

FIGURE 72 H-s plot of expansion in a steam turbine. (Power.)

Related Calculations. Use this general approach for steam cogeneration plant design for industries in any of these eldschemical, petroleum, textile, food, tobacco, agriculture, manufacturing, automobile, etc. While the cogeneration plant considered here exhausts directly to the process mains, condensing turbines can also be used. With such machines, process steam is extracted at a suitable point in the cycle to provide the needed pressure and temperature. Condensing steam turbines with steam extraction for process needs offer a signicant increase in electric-power production. Further, they reduce the effects of seasonal price uctuations for power sales, and potentially lower life-cycle costs. Capital cost of such machines, however, is higher. Turbine suppliers are now also offering efcient, high-speed geared turbogenerators for cogeneration. One such supplier states that the incremental payback for a geared unit can be extremely high in cogeneration applications. Much of the data in this procedure came from Power magazine. SI values were added by the editor.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.112


POWER GENERATION

Economic Analyses of Alternative Energy Sources


CHOICE OF MOST ECONOMIC ENERGY SOURCE USING THE TOTAL-ANNUAL-COST METHOD
A penal institution needs 50,000 MWh of electric energy per year with a maximum demand of 10 MW. This can be purchased from the local utility for $480,000 annually. As an alternate scheme, the penal institution is considering installing a 10-MW steam-turbine plant using equipment purchased at reduced prices. Three different plants are being proposed, as shown in Table 4. The plant will run 24 h / day, with inmate operators working an 8-h day, 5 days per week. The average annual salary for the inmate operators, which includes their prison costs, is $5200. Maintenance costs are estimated at 90 cents per ton of coal burned for all alternative plants. From past experience, the designers found that installed costs for penal institutions exceed estimates by 20 percent; so this allowance is made as a contingency. General operating supplies are estimated as $10,000 annually for all plants being considered. The useful life of each plant is taken as 15 years; the cost of money is 6 percent. Real estate taxes on the real estate for the plant are estimated to be 4 percent; various operating taxes add 1 percent to annual operating costs. Annual insurance costs are 0.2 percent of all equipment costs. Coal fuel costs $6.50 per short ton and has a higher heating value (HHV) of 14,200 Btu / lb (33,086 kJ / kg). Determine which scheme is the economic one, using the total-annual-cost method, assuming equal reliability.
Calculation Procedure:

1. Determine the required boiler capacity for each proposed plant Use the relation: Required boiler capacity, lb / h (kg / h) (plant heat rate, lb / kWh [kg / kWh])(plant capacity, kW). Find the full-load steam rate and plant capacity in Table 4. Then the required boiler capacity, C, for each plant is Plan A: Plan B: Plan C: C C C 11.8(10,000) 118,000, say 120,000 lb / h (54,480 kg / h) 10.5(10,000) 105,000, say 110,000 lb / h (49,940 kg / h) 8.5(10,000) 85,000, say 90,000 lb / h (40,860 kg / h)

The boiler capacity was rounded off to the next-higher standard boiler rating for each plan. This permits purchase of a standardized boiler while providing a nominal amount of extra capacity. Do not, in general, round off to the next-lower capacity because this can result in choosing a boiler with too small a capacity for the fullload output of the turbine. 2. Compute the cost of the boiler and related equipment As noted earlier, this is a plant for a penal institution, and the equipment is being obtained at reduced cost. However, the procedure for computing the cost of the boiler and its related equipment is the same, regardless of the equipment cost and the type of use of the equipment. Hence, use the relation: Installed boiler cost, $ (required boiler capacity, lb / h [kg / h])(boiler cost, $ / lb h capacity). Using the cost data in Table 4, installed boiler cost is

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.113

TABLE 4 Data for Three Plant Options

Plan A Throttle steam conditions: Pressure, psig. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature, F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Station steam rate (full load), lb / kWh . . . . . . . . . . . . . . . Average station heat rate, Btu / kWh . . . . . . . . . . . . . . . . . Unit installation costs: Steam generator and auxiliaries, dollars per lb h capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steam turbine and auxiliaries, dollars per kW capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . Structures and miscellaneous. . . . . . . . . . . . . . . . . . . . . Plant operators per shift . . . . . . . . . . . . . . . . . . . . . . . . . . . 200 550 11.8 16,000 4.08 38.00 $200,000 $200,000 4

Plan B 400 700 10.5 13,500 4.73 42.00 $200,000 $200,000 4

Plan C 900 850 8.5 12,000 6.45 51.00 $200,000 $200,000 4

Plan A: Plan B: Plan C:

120,000($4.08) 110,000($4.73) 90,000($6.45)

$490,000 $520,000 $580,000

3. Compute the cost of the turbine and auxiliaries Use the same procedure as in step 2, except that the plant capacity and turbine costs are substituted in the cost relation. Using the cost tabulated for each plan in Table 4, the installed turbine cost is Plan A: Plan B: Plan C: (10,000 kW)($38) (10,000 kW)($42) (10,000 kW)($51) $380,000 $420,000 $510,000

4. Find the total investment required Tabulate the costs for each plan, as shown in Table 5. Note that the electrical equipment and structures costs are the same for all plans. Once the total estimated cost for each plan is found, apply the 20 percent contingency allowance to nd the total investment required. Summarize the cost for each plan, as shown in Table 5.

TABLE 5 Plant Equipment Costs

Investment Boiler equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . Turbine equipment. . . . . . . . . . . . . . . . . . . . . . . . . . Electrical equipment . . . . . . . . . . . . . . . . . . . . . . . . Structures and miscellaneous . . . . . . . . . . . . . . . . . Total estimated items . . . . . . . . . . . . . . . . . . . . . Contingencies at 20 percent. . . . . . . . . . . . . . . . . . Total investment . . . . . . . . . . . . . . . . . . . . . . . . .

Plan A $490,000 380,000 200,000 200,000 $1,270,000 250,000 $1,520,000

Plan B $520,000 420,000 200,000 200,000 $1,340,000 270,000 $1,610,000

Plan C $580,000 510,000 200,000 200,000 $1,490,000 300,000 $1,790,000

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.114


POWER GENERATION

5. Determine the depreciation and xed-charge rates i / [(1 i)n 1], where i earnings rate or interest that The depreciation rate the investment would yield (6 percent for this plant); n expected life of the capital equipment, years. Or, depreciation rate 0.06 / [(1.06)15 1] 0.0431. (interest rate, depreciation rate, tax rate, and insurance The xed-charge rate rate). Or, xed-charge rate 0.06 0.0431 0.04 0.002 0.1451, or 14.51%. 6. Find the unit and total fuel costs $6.50(10)6 / 2000(14,200) 22.9 cents Unit fuel cost, $ / ton(10)6 / 2000 (HHV) 6 (unit fuel cost, cents / 106 Btu)(annual per 10 Btu. Then total annual fuel cost kWh energy consumption)(average plant heat rate, Btu / kWh). For each plan, total annual fuel cost is Plan A: Plan B: Plan C: 0.229(50)(16,000) 0.229(50)(13,500) 0.229(50)(12,000) $183,200 $154,575 $137,400

7. Compute the annual operating and maintenance costs There are 21 shifts per week ( 3 shifts per day 7 days per week). Any operator 5 working days per week). Then works 5 shifts per week ( 1 shift per day each position requires 21 / 5 4.2 operators to keep the post continuously staffed. Assume that the operators are interchangeable in their posts. Then all plans will need (4 operators per shift)(4.2 people per position) 16.8, or 17, operators. Since each operator earns prison wages and keep costs of $5200 annually, the annual cost of operating labor (17 operators)($5200) $88,400, say, $88,000 per year, average, over the life of the plant. Average annual maintenance cost (tons of coal burned per year)(maintenance (annual total fuel cost / cost per ton of coal)(maintenance cost per ton of coal) cost per ton of coal). For each plan, average annual maintenance cost is Plan A: Plan B: Plan C: $183,200 (0.90) $6.50 $154,575 (0.90) $6.50 $137,400 (0.90) $6.50 $25,366 $21,403 $19,025

8. Calculate the total annual operating cost and the total annual cost Tabulate each operating cost as shown in Table 6. Then add the investment charges to obtain the total annual cost. This gives the results shown at the bottom of Table 6. 9. Analyze the costs and choose the best alternative plan For the given conditions of xed-charge rate (14.51 percent) and fuel costs, plan B incurs the least annual cost of the three plans. However, since the utility can supply electric power for less than any of these private plants, the utility supply would be the logical choice. In certain circumstances, even if the utility service cost $520,000, it might be selected in preference to the private plant plan B. If no utility service were available, plan B would undoubtedly be chosen for this installation. Related Calculations. Use this procedure to determine the most economic energy source for any type of power plantsteam, diesel, gas-turbine, windmill

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.115

TABLE 6 Annual Costs for Each Plant

Annual operating costs Fuel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating labor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Subtotal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating taxes at 1 percent . . . . . . . . . . . . . . . . . . . . . . . Total annual operating costs . . . . . . . . . . . . . . . . . . . . .

Plan A $183,000 88,000 25,000 10,000 $306,000 3,000 $309,000

Plan B $155,000 88,000 21,000 10,000 $274,000 3,000 $277,000

Plan C $138,000 88,000 19,000 10,000 $255,000 3,000 $258,000

Total annual costs Investment charges at 14.5 percent . . . . . . Operating costs . . . . . . . . . . . . . . . . . . . . . . Total annual costs . . . . . . . . . . . . . . . . . .

Plan A $221,000 309,000 $530,000

Plan B $233,000 277,000 $510,000

Plan C $260,000 258,000 $518,000

Utility service

$480,000

serving any type of loadutility, industrial, commercial, institutional, etc. This procedure is the work of B. G. A. Skrotzki and William Vopat.

SEVEN COMPARISON METHODS FOR ENERGY-SOURCE CHOICE


Using the data in the previous calculation procedure, study the following: (1) inuence of xed-charge rate, (2) inuence of annual operating ocsts, (3) rate of return to be realized, (4) return available for xed charges, (5) justiable investment, (6) present worth, and (7) capitalized cost. The variables that must be considered are stated in each calculation procedure.
Calculation Procedure:

1. Compare the total annual costs by using the xed-charge rate Assume the xed-charge rate is 7 percent instead of the 14.51 percent in the previous calculation procedure. Compute investment charges at 7 percent and the total annual operating costs as in step 8 of the previous procedure. Total annual operating costs are then
Total annual costs Investment charges at 7 percent . . . . . . . . . . . . Operating costs . . . . . . . . . . . . . . . . . . . . . . . . . . Total annual cost . . . . . . . . . . . . . . . . . . . . . . Plan A $106,000 309,000 $415,000 Plan B $113,000 277,000 $390,000 Plan C $125,000 258,000 $383,000

Reduction in the xed-charge rate could result from a smaller cost of money, or a longer life span, or both. As the tabulation above shows, plan C is now the optimum

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.116


POWER GENERATION

plan because it is considerably less costly than that of the utility service. From this result an important principle is clear: As the xed-charge rate decreases, the alternatives involving higher capital investment are favored as optimum choices. This means that as the cost of money use decreases, or the life span of the investment increases, more money can be invested to secure greater overall economy. This principle holds only when the annual operating cost of each alternative remains unchanged. 2. Analyze the effect of increased fuel costs In thermal stations, fuel prices control the general magnitude of the annual operating costs. Thus, the fuel purchase price will have a controlling effect on the economic conclusions drawn from nancial comparisons. Assume that the fuel cost doubles to $13 per short ton. Compute the fuel costs as in step 6 of the previous calculation procedure. Tabulate the total annual costs as follows:
Total annual costs Investment charges at 14.5 percent . . . . . . . . . . . . Operating costs with $13 coal . . . . . . . . . . . . . . . . Total annual cost . . . . . . . . . . . . . . . . . . . . . . . . . Plan A $221,000 492,000 $713,000 Plan B $233,000 432,000 $665,000 Plan C $260,000 396,000 $656,000

For this condition, the plan requiring the highest investment again becomes the optimum one. From this a corollary principle may be deduced: As the cost of fuel increases, plans involving higher capital investment are favored as optimum. Thus, as the cost of fuel increases, more money may be invested to gain increased efciency. This holds only when the xed-charge rate is common to all plans and remains constant. 3. Determine the optimum investment based on the earned rate of return Assume the same data as previously, except that the utility service costs $530,000 annually. This price could be obtained by getting a direct quote from the utility. Compute all the items of annual cost except interest and depreciation. Then the difference between the utility service cost of $530,000 and the computed annual costs represents a saving available for the annual interest on the investment and its amortization. The sum of the differences, $A, and the investment from step 4 of the previous calculation procedure will be the principal, $P, for each plan. Solve i / [1 for the interest rate, I, using a calculator, or trial and error, using A / P (1 i) n]. Tabulate the results thus:
Utility service

Plan A Annual operating costs . . . . . . . . . . . . . Annual taxes on capital . . . . . . . . . . . . Annual insurance costs . . . . . . . . . . . . . Annual costs excluding interest and depreciation . . . . . . . . . . . . . . . . . . . . Difference available for annuity A . . . Investment P . . . . . . . . . . . . . . . . . . . . . Ratio A / P . . . . . . . . . . . . . . . . . . . . . . . . Rate of return i, percent . . . . . . . . . . . . $309,000 61,000 3,000 $373,000 $157,000 $1,520,000 0.1033 6.4

Plan B $277,000 64,000 3,000 $344,000 $186,000 $1,610,000 0.1155 7.8

Plan C $258,000 72,000 4,000 $334,000 $196,000 $1,790,000 0.1094 7.0

$530,000 Base

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.117

Note that all the plans yield a greater rate of return than the minimum interest rate of 6 percent. This means it will be desirable to build one of these plants rather than purchase energy at a cost of $530,000 per year from the utility. While plan B yields the maximum rate of return on the investment (7.8 percent), an attractive rate of return can be earned by the higher investment of plan C. The limit of investment is determined by that value where the last additional dollar invested earns at least the minimum rate of return desiredin this case 6 percent. This method investigates the rate of return on increment investments. Use the same procedure as above, but nd the return earned on the differences of investment for the various plans. Solve for the rate of return by using a calculator or trial and error, and tabulate the results thus:
Difference of plans B over A Saving in annual costs, excluding interest and depreciation, A . . Additional capital investment, P. . . . . . . . . . . . . . . . . . . . . . . . . . . . Ratio A / P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rate of return on increment investment,a percent. . . . . . . . . . . . . . .
a

C over B $10,000 $180,000 0.0556 Negative

$29,000 $90,000 0.3222 31.7

By trial solution for i from A P A P i (1

i)

Note that while plan A showed a satisfactory rate of return of 6.4 percent, the additional investment of $90,000 for plan B earns the high rate of return of 31.7 percent, which raises the overall rate of return of plan B to 7.8 percent. The additional investment of $180,000 for plan C over plan B does not earn enough to amortize the extra cost, as indicated by the negative interest rate. This negative return reduces the overall return of plan C to 7.0 percent. Hence, plan B is the optimum scheme for the given conditions. The same conclusion was reached by the total-annual-cost method in the previous calculation procedure. Recognize the importance of thoroughly investigating all possibilities in economic studies by considering the following situation. If plan B had been overlooked, the return of the additional investment for plan C over plan A would have been as follows:
Saving in annual costs, excluding interest and depreciation, A . . . . . . . . . . . . . . . . . . $39,000 Additional capital investment P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $270,000 Ratio A / P . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.1445 Rate of return on increment investment, percent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11.7

Thus, the rate of return on the increment investment would be reduced from 31 to 11 percent. 4. Compute the return available for xed charges This method is popular because it eliminates the trial and error or interpolation required in the rate-of-return method. The xed-charge rate is easily calculated from the desired rate of return and life of the project, including the tax and insurance premium rates. From the proposals studied, determine the savings as a percentage of the corresponding investments that are available to meet the xed charges. Compute and tabulate the investment savings, increment investment, and their ratio; tabulate them thus:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.118


POWER GENERATION

Plan A Annual operating costs . . . . . . . . . . . . . Savings available for investment charges . . . . . . . . . . . . . . . . . . . . . . . . Investment. . . . . . . . . . . . . . . . . . . . . . . . Ratio of savings to investment,a percent . . . . . . . . . . . . . . . . . . . . . . . . Increment savings . . . . . . . . . . . . . . . . . Increment investment . . . . . . . . . . . . . . Ratio of increment savings to increment investment, percenta . . . .
a

Plan B $277,000 $253,000 $1,610,000

Plan C $258,000 $272,000 $1,790,000 15.2

Utility service $530,000 Base 0

$309,000 $221,000 $1,520,000

14.6 $32,000 $90,000 35.6

15.7 $19,000 $180,000 10.6

Rates comparable to xed-charge rate

14.51 percent.

Again, Plan B is the optimum one. This is the same conclusion as drawn from the previous methods of comparison. 5. Determine the maximum justiable investment In this method, the savings available for investment charges are divided by the xed-charge rate to arrive at a justiable maximum investment. Compare the justiable maximum investment with the actual investment required for the given plan. If the actual investment is equal to, or less than, the justiable investment, then the plan may prove satisfactory. Compute the actual increment investment and tabulate thus:
Plan A Annual operating costs . . . . . . . . . . . . . . Savings available for investment charges . . . . . . . . . . . . . . . . . . . . . . . . . . Fixed-charge rate, percent . . . . . . . . . . . . Justiable investment . . . . . . . . . . . . . . . . Active investment needed . . . . . . . . . . . . Increment savings . . . . . . . . . . . . . . . . . . . Fixed-charge rate, percent . . . . . . . . . . . . Justiable added investment . . . . . . . . . . Actual increment investment needed . . . $309,000 Plan B $277,000 Plan C $258,000 Utility service $530,000 Base

$220,000 $253,000 $272,000 14.5 14.5 14.5 $1,525,000 $1,745,000 $1,877,000 $1,520,000 $1,610,000 $1,790,000 $32,000 $19,000 14.5 14.5 $221,000 $131,000 $90,000 $180,000

Actual investments for the three plans, A, B, and C, are less than the maximum justiable investments and hence appear to be satisfactory. Again, plan B is the optimum choice. 6. Compute the total present worth of each alternative The plan having the lowest present worth involves a minimum overall expenditure during the life of the investment and therefore is the desirable, or optimum, plan. Compute the annual taxes on capital and the annual insurance cost. Determine the present-worth factor, PWF, from the relation in step 3 above for 6 percent interest and a 15-year life. Then PWF 0.103. Solve for the present worth of the costs excluding interest and depreciation and add the investment, $P, as in Wp [P (t j)P Co] / PWF, where Wp total present worth of a series of annual expenditures, t tax rate on capital equipment, j insurance rate, Co annual operating expenses. Tabulate the results thus:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.119

Plan A Annual operating costs . . . . . . . . . . . . . Annual taxes on capital . . . . . . . . . . . . Annual insurance costs . . . . . . . . . . . . . Annual costs excluding interest and depreciation . . . . . . . . . . . . . . . . . . . . Present-worth factor . . . . . . . . . . . . . . . Present worth of costs excluding interest and depreciation. . . . . . . . . . Investment P Total present worth Wp . . . . . . . . . . . . . $309,000 61,000 3,000 $373,000 0.103 $3,620,000 1,520,000 $5,140,000

Plan B $277,000 64,000 3,000 $344,000 0.103 $3,340,000 1,610,000 $4,950,000

Plan C $258,000 72,000 4,000 $334,000 0.103 $3,240,000 1,790,000 $5,030,000

Utility service $530,000

$530,000 0.103 $5,150,000 0 $5,150,000

Plan B, having the minimum present worth, entails the least total expenditures over the life of 15 years and is therefore the optimum one, as previously. 7. Determine the total capitalized cost of each alternative Use the relation Wc for the total capitalized cost. (1 i i)n 1 i t j P Co

Wc

Compute the total capitalized cost for each alternative and tabulate thus:
Plan A Annual operating costs . . . . . . . . . . . . . Annual depreciation costs . . . . . . . . . . Annual taxes on capital . . . . . . . . . . . . Annual insurance costs . . . . . . . . . . . . . Annual costs excluding interest. . . . . . Interest rate i . . . . . . . . . . . . . . . . . . . . . Capitalized costs of annual costs excluding interest . . . . . . . . . . . . . . . Investment P Total capitalized cost Wc . . . . . . . . . . . $309,000 66,000 61,000 3,000 $439,000 0.06 $7,310,000 1,520,000 $8,837,000 Plan B $277,000 70,000 64,000 3,000 $414,000 0.06 $6,900,000 1,610,000 $8,517,000 Plan C $258,000 77,000 72,000 4,000 $411,000 0.06 $6,850,000 1,790,000 $8,640,000 Utility service

$530,000 0.06 $8,833,000 0 $8,833,000

Plan B, having the minimum capitalized cost, entails the smallest annual costs and is therefore the optimum alternative, as in all previous analyses. Related Calculations. Use any of, or all, the given comparison methods for any type of energy sourcesteam, diesel, gas-turbine, windmill, etc.serving any type of loadutility, industrial, commercial, institutional, marine, etc.

SELECTION OF PRIME MOVER BASED ON ANNUAL COST ANALYSES


An electrical load in a penal institution has the following annual duration characteristics:

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.120


POWER GENERATION

Kilowatts 5000 4000 2000 1000 500

Hours 200 4000 2000 1000 1560

Two plants, a steam-turbine plant and a diesel-engine plant, are being considered. For the steam plant, coal at $4.50 per short ton with a heating value of 14,000 Btu/ lb (32,620 kJ / kg) is available. For the diesel plant, oil at $2.10 / bbl containing 358 lb (162.5 kg) with a heating value of 18,500 Btu / lb (43,105 kJ / kg) is available. The performance characteristics of the plants are as follows: Steam: I 106 (6 8L 0.111L3); diesel: I 106(9 4L [0.52L2 0.016L3]). The steam plant requires three more operators at a cost of $4000 per person than does the diesel plant. The xed-charge rate is 12 percent for each plant. Which plant should be selected if the steam plant costs $230 / kW installed? No reserve capacity is required. Use the total annual costs as the basis of comparison of the plants.

Calculation Procedure:

1. Compute the unit fuel cost for each prime mover 106 (fuel cost, cents / lb) / The steam-plant unit fuel cost, cents per million Btu 106 (450) / (2000)(14,000) 16.07 cents per (lb / ton)(heating value, Btu / lb) 31.71 cents per 106, 106 / Btu. The diesel unit fuel cost, cents per million Btu using the same method of calculation. 2. Find the total energy input for each plant Use the input-output characteristic for each plant, and compute the total energy for each load tabulated above. Thus, for the steam plant and the load of 5000 kW 5 MW, I 106(6 8 5 0.11 125) 59.9 106 Btu / h (17.55 MW). Tabulate the computed input for each plant for each load on a per-hour basis. Multiply the per-hour input by the number of hours at this load to obtain the total input at each load. Thus, for 200 h at 5 MW, total input (200 h)(59.9 106 Btu/ h) 11.98 109 Btu (12.58 109 kJ). Tabulate these values:
Calculation of Fuel Requirements Steam plant MW h MW Input rate, 106 Btu / h 59.90 45.12 22.89 14.11 10.01 ......... ......... Total input, 109 Btu 11.98 180.48 45.78 14.11 15.62 267.97 11,800 Diesel plant Input rate, 106 Btu / h 40.00 32.30 18.95 13.50 11.13 ......... ......... Total input, 109 Btu 8.00 129.20 37.90 13.50 17.36 205.96 9050

5 200 1,000 4 4,000 16,000 2 2,000 4,000 1 1,000 1,000 1 2 1,560 780 Total . . . 8,760 22,780 Average heat rate, Btu / kWh. .

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.121

Find the heat rate, HR, for each plant by dividing the tabulated total heat input 11,800 Btu / kWh by the total-load energy, MWh. For the steam plant, HR (11,210 kL / kWh). Tabulate the values for each plant. 3. Calculate the total annual cost for each plant The total annual cost is Co Cc Cf Cl, where the subscripts are c capitalfuel cost, and l labor cost. For the steam plant, Cc cost write off, f ($230)(5000)(0.12) $318,000. And Cf (0.1607)(267,970 109) $43,063; Cl 3($4000) $12,000. Then Co $193,063 per year. For the diesel plant, Co $197,310 per year. 4. Choose the most economical prime mover Since the steam plant has a lower total annual cost, choose it in preference to the diesel plant, despite the higher rst cost and greater relative labor cost of the steam plant. These costs are outweighed by the lower fuel cost of the steam plant. 5. Evaluate the effect of relative fuel prices Since fuel prices vary, particularly the price of oil, total-annual-cost comparisons depend on the relative fuel prices at the time of the study. To give a complete picture of the importance of fuel prices in determining plant economics, the cost comparison can be set up to determine the relationship of fuel prices for given conditions of labor costs, thermal efciency, and loan conditions. From the foregoing, the plants are equally desirable when their annual costs are equal, Co,steam Co,diesel. Or, (Cc Cf)steam (Cc Cf)diesel. Substituting previously computed values, ($138,000) [(267,970 106 S) / (2000 14,000)] $12,000 ($132,000) [(205,960 106 D) / (358 18,500)], where S price of coal, $ / ton; D price of oil, $ / bbl. Solving gives D 0.578 0.308S. Thus, for coal 0.578 0.308(4.50) $1.96 / bbl to at $4.50 / ton, oil would have to be D produce equal fuel costs. With oil at $2.10 / bbl, coal would have to be $4.94 / ton for equal fuel costs. Related Calculations. Use this annual-cost procedure to compare any type of prime moversteam, diesel, natural-gas, gas-turbine, windmillserving any type of loadutility, industrial, institutional, or marine. Note that the relative current prices of fuel do not change the steps or methods given here. Hence, use the same steps, inserting todays fuel prices. This procedure is the work of B. G. A. Skrotzki and William Vopat, as reported in their book Power Station Engineering and Economy, McGraw-Hill.

DETERMINING IF A PRIME MOVER SHOULD BE OVERHAULED


A 20-MW steam turbine has been in use for 4 years and generates 105,000,000 kWh annually. The rst year this energy was produced at an average heat rate of 15,000 Btu / kWh (14,250 kJ / kWh). Because of blade erosion the average heat rate increases at the rate of 0.05 percent per 1000 h of operation. This increase is expected to continue for the life of the machine despite adequate routine maintenance. To reblade the turbine and restore its original efciency will cost $35,000. The total life of the turbine is 15 years, and it will be required to produce the same amount of energy annually in the future. If fuel costs 20 cents per million Btu, a

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT 1.122


POWER GENERATION

minimum of 6 percent return is required on an investment, and the turbine operates 6000 h / yr, determine when, and if, the turbine should be rebladed. The rebladed turbine will deteriorate in efciency at the same rate as at present, s.
Calculation Procedure:

1. Calculate the annual fuel-cost increase after the rst year During the rst year, when the heat rate, HR, was 15,000 Btu / h (14,250 kJ / kWh), (total output, kWh)(HR, Btu / kWh)(fuel costs, cents per 106 Btu) fuel cost (105,000,000)(15,000)(0.2 / 106) $315,000. The increase in fuel cost per year, resulting from blade corrosion, is (annual fuel cost, $)(hours of operation per year)(HR increase, percent per 1000 h) ($315,000)(6000)(0.0005 / 1000) $945. 2. Compute, and tabulate, the fuel-cost increase Prepare a tabulation such as that below listing the turbine age in years and the increase in fuel cost resulting from blade erosion. Thus, there is no increase in fuel cost during the rst year. During the second year the fuel cost increases by $945, as computed in step 1 above. During the third year the fuel cost increases by 2($945) $1890. Compute the subsequent annual fuel saving when the turbine is rebladed in a given year, and enter the results in the second column below. In the third column enter the life of the reblading investment 15 year in which the turbine was rebladed.
Turbine Reblading Evaluation Rate of return for subsequent annual saving referred to $35,000 investment, percent Negative Negative Negative Negative 1.5 4.1 6.2 7.5 8.0 6.9 3.2 Negative Negative Negative

Turbine age n, yr 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Subsequent annual saving n when rebladed in given year $ 0 945 1,890 2,835 3,780 4,725 5,670 6,615 7,560 8,505 9,450 10,395 11,340 12,285 13,230

Life of reblading investment m, yr 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

0.06 1.06 0.1076 0.1130 0.1193 0.1268 0.1359 0.1470 0.1610 0.1791 0.2034 0.2374 0.2886 0.3741 0.5454 1.06

Annual interest and amortization of $35,000 invested in year n, i 0.06 $ 3,760 3,960 4,180 4,440 4,750 5,150 5,640 6,270 7,120 8,300 10,100 13,100 19,100 37,100

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT


MODERN POWER-PLANT CYCLES AND EQUIPMENT

1.123

3. Determine the reblading annual interest and amortization rates The factor for computing the annual interest and amortization is i / (1 [1 I] m), desired rate of return; m life of reblading investment, years. Thus, where I with a reblading investment life of 4 years and n 11 years, factor 0.2886, after substituting the above equation. To nd the annual interest and amortization on the $35,000 reblading investment, take the product of the factor and the reblading cost, $10,101. The rate of return on the $35,000 investment is or (0.2886)($35,000) found by setting up the ratio of annual savings, A, to the investment, P, and solving by calculator, or trial and error, the relation A / P i / (1 [1 i] n) for I, the rate of return. For n 9 years, I 8.0 percent. Enter this value in the table above. Computing the other rates of return in the same manner shows that the maximum rate of return occurs when reblading is done in the ninth year. The 8 percent return exceeds the minimum desired 6 percent rate of return. Related Calculations. Use this procedure to compute the timing of and return on investment for any expenditure which improves the efciency of any type of prime moversteam turbine, diesel engine, gasoline engine, gas turbine, hydraulic turbine, windmill, etc., in a stationary, portable or marine installation. This procedure is the work of B. G. A. Skrotzki and William Vopat.

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.

MODERN POWER-PLANT CYCLES AND EQUIPMENT

Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com) Copyright 2006 The McGraw-Hill Companies. All rights reserved. Any use is subject to the Terms of Use as given at the website.