Var V1000-Installation
Var V1000-Installation
1. RECEIVING ................................................................... 23
1.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.2 Model Number and Nameplate Check . . . . . . . . . 25
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.3 Drive Models and Enclosure Types . . . . . . . . . . . 28
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 3
1.4 Component Names . . . . . . . . . . . . . . . . . . . . . . . . 30
IP20/Open-Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
IP20/NEMA Type 1 Enclosure . . . . . . . . . . . . . . . . . . . . . . 32
Front Views . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3. ELECTRICAL INSTALLATION..................................... 51
3.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3.2 Standard Connection Diagram . . . . . . . . . . . . . . . 55
3.3 Main Circuit Connection Diagram . . . . . . . . . . . . 58
Single-Phase 200 V Class (CIMR-V BA0001 ~ 0012) . . . 58
Three-Phase 200 V Class (CIMR-V 2A0001 ~ 0069)
Three-Phase 400 V Class (CIMR-V 4A0001 ~ 0038) . . . 58
3.4 Terminal Block Configuration. . . . . . . . . . . . . . . . 59
3.5 Protective Covers . . . . . . . . . . . . . . . . . . . . . . . . . 60
IP20/Open-Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
IP20/NEMA Type 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
3.6 Main Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . . . 63
Main Circuit Terminal Functions . . . . . . . . . . . . . . . . . . . . . 63
Wire Gauges and Tightening Torque . . . . . . . . . . . . . . . . . 63
Main Circuit Terminal Power Supply and Motor Wiring . . . 66
3.7 Control Circuit Wiring . . . . . . . . . . . . . . . . . . . . . . 69
Control Circuit Terminal Block Functions . . . . . . . . . . . . . . 70
Removable Terminal Block Configuration . . . . . . . . . . . . . 72
4 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Wiring Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
3.8 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Sinking/Sourcing Mode Switch . . . . . . . . . . . . . . . . . . . . . 77
3.9 Main Frequency Reference . . . . . . . . . . . . . . . . . . 79
Terminal A2 Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
3.10 MEMOBUS/Modbus Termination. . . . . . . . . . . . . 81
3.11 Braking Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
3.12 Wiring Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . 84
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 5
4.5 Application Presets . . . . . . . . . . . . . . . . . . . . . . . 111
Application Preset Function (APPL) . . . . . . . . . . . . . . . . . 111
Application Presets: A1-06 . . . . . . . . . . . . . . . . . . . . . . . . 111
User Parameters: A2-01 to A2-32 . . . . . . . . . . . . . . . . . . 120
User Parameter Automatic Selection: A2-33 . . . . . . . . . . 120
4.6 Basic Drive Setup Adjustments . . . . . . . . . . . . . 122
Control Mode Selection: A1-02 . . . . . . . . . . . . . . . . . . . . 122
Initialize Parameter Values: A1-03 . . . . . . . . . . . . . . . . . . 122
Application Presets: A1-06 . . . . . . . . . . . . . . . . . . . . . . . . 123
DWEZ Function Selection: A1-07 . . . . . . . . . . . . . . . . . . . 124
Frequency Reference Source: b1-01 . . . . . . . . . . . . . . . . 124
Run Command Input Selection: b1-02 . . . . . . . . . . . . . . . 127
Stopping Method Selection: b1-03 . . . . . . . . . . . . . . . . . . 129
Acceleration/Deceleration: C1-01 to C1-11 . . . . . . . . . . . 132
Drive Duty Mode and Carrier Frequency Selection:
C6-01 and C6-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Drive Input Voltage Setting: E1-01 . . . . . . . . . . . . . . . . . . 138
V/f Pattern Selection: E1-03 . . . . . . . . . . . . . . . . . . . . . . . 139
Motor Parameters: E2-01 through E2-12
(Manually Entering Parameter Settings) . . . . . . . . . . . . . 142
Digital Outputs H2-01 to H2-03 . . . . . . . . . . . . . . . . . . . . 144
Analog Outputs: H4-01 to H4-03 . . . . . . . . . . . . . . . . . . . 144
Motor Protection: L1-01 and L1-02 . . . . . . . . . . . . . . . . . . 146
Drive Status Monitors: U1-01 to U6-19 . . . . . . . . . . . . . . 150
4.7 Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Powering Up the Drive and Operation Status Display . . . 153
Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
No-Load Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Operating with the Load Connected . . . . . . . . . . . . . . . . . 163
Verifying Parameter Settings and Backing Up Changes . 163
Jog Operation: FJOG/RJOG . . . . . . . . . . . . . . . . . . . . . . 166
Multi-Step Speed Operation (4-Step Speed) . . . . . . . . . . 168
4.8 Test Run Checklist. . . . . . . . . . . . . . . . . . . . . . . . 171
6 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5. TROUBLESHOOTING ................................................ 173
5.1 Section Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
5.2 Motor Performance Fine Tuning . . . . . . . . . . . . . 177
V/f Motor Control Method Tuning . . . . . . . . . . . . . . . . . . 177
Open Loop Vector (OLV) Motor Control Method Tuning 178
Motor Hunting and Oscillation Control Parameters . . . . . 180
5.3 Drive Alarms, Faults, and Errors . . . . . . . . . . . . . 181
Types of Alarms, Faults, and Errors . . . . . . . . . . . . . . . . 181
Alarm and Error Displays . . . . . . . . . . . . . . . . . . . . . . . . 182
5.4 Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Fault Displays, Causes, and Possible Solutions . . . . . . . 187
5.5 Alarm Detection . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Alarm Codes, Causes, and Possible Solutions . . . . . . . . 206
5.6 Operator Programming Errors. . . . . . . . . . . . . . . 217
oPE Codes, Causes, and Possible Solutions . . . . . . . . . 217
5.7 Auto-Tuning Fault Detection . . . . . . . . . . . . . . . . 222
Auto-Tuning Codes, Causes, and Possible Solutions . . 222
5.8 Diagnosing and Resetting Faults . . . . . . . . . . . . 226
Fault Occurs Simultaneously with Power Loss . . . . . . . . 226
If the drive still has power after a fault occurs . . . . . . . . . 226
Viewing Fault Trace Data after Fault . . . . . . . . . . . . . . . 227
Fault Reset Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
5.9 Troubleshooting without Fault Display . . . . . . . 228
Cannot Change Parameter Settings . . . . . . . . . . . . . . . . 228
Motor Does Not Rotate Properly after Pressing
RUN Button or After Entering External Run Command . 228
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 7
6.2 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Recommended Daily Inspection . . . . . . . . . . . . . . . . . . . . 248
Recommended Periodic Inspection . . . . . . . . . . . . . . . . . 249
6.3 Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . 252
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
6.4 Drive Cooling Fans . . . . . . . . . . . . . . . . . . . . . . . 254
Cooling Fan Replacement . . . . . . . . . . . . . . . . . . . . . . . . 254
6.5 Drive Replacement. . . . . . . . . . . . . . . . . . . . . . . . 258
Serviceable Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Terminal Board Overview . . . . . . . . . . . . . . . . . . . . . . . . . 258
Replacing the drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Details on Terminal Board (TB) or Control Board
(CNT) Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
8 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A. SPECIFICATIONS....................................................... 291
A.1 Heavy Duty and Normal Duty Ratings . . . . . . . . 292
A.2 Single/Three-Phase 200 V Class Drive . . . . . . . . 293
A.3 Three-Phase 400 V Class Drives. . . . . . . . . . . . . 296
A.4 Drive Specifications . . . . . . . . . . . . . . . . . . . . . . . 298
A.5 Drive Watts Loss Data . . . . . . . . . . . . . . . . . . . . . 302
A.6 Drive Derating Data . . . . . . . . . . . . . . . . . . . . . . . 305
Carrier Frequency Derating . . . . . . . . . . . . . . . . . . . . . . 305
Temperature Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . 305
Altitude Derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 9
C. NETWORK COMMUNICATIONS................................ 405
C.1 MEMOBUS/Modbus Basic Set-Up . . . . . . . . . . . 406
MEMOBUS/Modbus Communication Configuration . . . . . 406
Communication Specifications . . . . . . . . . . . . . . . . . . . . . 407
Communication Connection Terminal . . . . . . . . . . . . . . . 407
Communication Set-Up Procedure . . . . . . . . . . . . . . . . . . 409
10 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
i
Preface &
General Safety
This section provides safety messages pertinent to this product,
that, if not heeded, may result in fatality, personal injury, or
equipment damage. Yaskawa is not responsible for the
consequences of ignoring these instructions.
I.1 PREFACE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
I.2 GENERAL SAFETY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 11
i.1 Preface
i.1 Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa products remain the responsibility
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a
product manufactured by Yaskawa must be supplied to the end user with appropriate
warnings and instructions as to the safe use and operation of that part. Any warnings
provided by Yaskawa must be promptly provided to the end user. Yaskawa offers an express
warranty only as to the quality of its products in conforming to standards and specifications
published in the Yaskawa manual. NO OTHER WARRANTY, EXPRESS OR IMPLIED, IS
OFFERED. Yaskawa assumes no liability for any personal injury, property damage, losses,
or claims arising from misapplication of its products.
◆ Applicable Documentation
The following manuals are available for V1000 series drives:
(Hz)
V1000 Series AC Drive Quick Start Guide
ജ㔚ᵹ (A)
ജ㔚 (V)
◆ Symbols
NOTE: indicates a supplement or precaution that does not cause drive damage.
12 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
t
i.1 Preface
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 13
i.2 General Safety
WARNING
Read and understand this manual before installing, operating or servicing
this drive. The drive must be installed according to this manual and local
codes.
The following conventions are used to indicate safety messages in this
manual. Failure to heed these messages could result in serious or possibly
even fatal injury or damage to the products or to related equipment and
systems.
DANGER
Indicates a hazardous situation, which, if not avoided, will result in
death or serious injury.
14 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
t
i.2 General Safety
\
WARNING
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in i
minor or moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
NOTICE
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 15
i.2 General Safety
◆ Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries or equipment
damage resulting from failure to heed the warnings in this manual.
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power, resulting in
death or serious injury.
Clear all personnel from the drive, motor and machine area before applying
power. Secure covers, couplings, shaft keys and machine loads before
applying power to the drive.
16 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
t
i.2 General Safety
WARNING
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the
incoming power supply before applying power.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main
body of the drive falling.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 17
i.2 General Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
18 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
t
i.2 General Safety
\
Always heed the warning information listed in Figure i.1 in the position shown in
STOP
V1000
ᵄᢙᜰ (Hz)
ᱜォㅒォㆬᛯ
ജᵄᢙ (Hz)
ജ㔚ᵹ (A)
ജ㔚 (V)
ࡕ࠾࠲
ࡌࡈࠔࠗ
࠶࠻ࠕ࠶ࡊ
ࡄࡔ࠲⸳ቯ
ࠝ࠻࠴ࡘ࠾ࡦࠣ
ෂޓ㒾 ߌ߇㧚ᗵ㔚ߩ߅ߘࠇ߇ࠅ߹ߔޕ
ᝪ߃ઃߌޔㆇォߩ೨ߦߪᔅߕขᛒ⺑ᦠࠍ⺒ߎߣޕ
ㅢ㔚ਛ߅ࠃ߮㔚Ḯㆤᢿᓟ5 ಽએౝߪࡈࡠࡦ࠻ࠞࡃࠍ
ᄖߐߥߎߣޕ
Warning
400V ⚖ࠗࡦࡃ࠲ߩ႐วߪޔ㔚Ḯߩਛᕈὐ߇ធ
ߐࠇߡࠆߎߣࠍ⏕ߔࠆߎߣޕ㧔ޓޓኻᔕ㧕 Display
Figure i.2 Warning Information Position
◆ Warranty Information
■ Restrictions
The V1000 was not designed or manufactured for use in devices or systems that may
directly affect or threaten human lives or health.
Customers who intend to use the product described in this manual for devices or systems
relating to transportation, health care, space aviation, atomic power, electric power, or in
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 19
i.2 General Safety
underwater applications must first contact their Yaskawa representatives or the nearest
Yaskawa sales office.
This product has been manufactured under strict quality-control guidelines. However, if this
product is to be installed in any location where failure of this product could involve or result
in a life-and-death situation or loss of human life or in a facility where failure may cause a
serious accident or physical injury, safety devices must be installed to minimize the
likelihood of any accident.
◆ Quick Reference
Easily Set Application-Specific Parameters
Preset parameter defaults are available for many applications. Refer to 2WOR
Application Presets on page 111
(CP %QPXG[QT
20 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
t
i.2 General Safety
\
Replace the Drive
Perform Auto-tuning
Automatic tuning sets motor parameters. Refer to Auto-Tuning on page 153
Standards Compliance
LISTED
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 21
i.2 General Safety
22 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1
Receiving
This chapter describes the proper inspections to perform after
receiving the drive and illustrates the different enclosure types
and components.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 23
1.1 Section Safety
CAUTION
Do not carry the drive by the front cover.
Failure to comply may cause the main body of the drive to fall, resulting in
minor or moderate injury.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
24 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.2 Model Number and Nameplate Check
Receiving
If the drive appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the wrong model or the drive does not function properly, contact
your supplier.
1
◆ Nameplate
Figure 1.1
+056#..#6+10%#6')14;++ PASS
#UUGODNGFKP75# RoHS
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 25
1.2 Model Number and Nameplate Check
CIMR- V U 2 A 0001 B A A
Drive V1000 Customized Voltage Design
No. No.
Series Specifications Class Revision
A Standard model A IP00 Order
No. Region
Code B IP20
U USA
F IP20
A Japan
Environmental
No.
C Europe Specification *
A Standard
No. Voltage Class M Humidity- and
B 1-phase, 200-240 Vac dust-resistant
N Oil-resistant
2 3-phase, 200-240 Vac S Vibration-resistant
4 3-phase, 380-480 Vac
Single-Phase 200 V
Three-Phase 200 V
26 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.2 Model Number and Nameplate Check
Receiving
0020 5.5 19.6 0020 3.7 17.5
0030 7.5 30 0030 5.5 25
0040 11 40 0040 7.5 33
0056 15 56 0056 11 47
0069 18.5 69 0069 15 60 1
Three-Phase 400 V
* Drives with these specifications do not guarantee complete protection for the specified
environmental condition.
Note: Refer to Component Names on page 30 for differences regarding enclosure protection types and
component descriptions.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 27
1.3 Drive Models and Enclosure Types
Enclosure Type
Voltage Class IP20/Open-Chassis IP20/ NEMA Type1)
CIMR-V CIMR-V
BA0001B BA0001F
BA0002B BA0002F
Single-Phase BA0003B BA0003F
200 V Class BA0006B BA0006F
BA0010B BA0010F
BA0012B BA0012F
2A0001B 2A0001F
2A0002B 2A0002F
2A0004B 2A0004F
2A0006B 2A0006F
2A0010B 2A0010F
2A0012B 2A0012F
Three-Phase
2A0020B 2A0020F
200 V Class
2A0030B 2A0030F
2A0040B 2A0040F
2A0056B 2A0056F
2A0069B 2A0069F
4A0001B 4A0001F
4A0002B 4A0002F
4A0004B 4A0004F
4A0005B 4A0005F
4A0007B 4A0007F
Three-Phase
4A0009B 4A0009F
200 V Class
4A0011B 4A0011F
4A0018B 4A0018F
4A0023B 4A0023F
4A0031B 4A0031F
4A0038B 4A0038F
28 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.3 Drive Models and Enclosure Types
Receiving
1
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 29
1.4 Component Names
◆ IP20/Open-Chassis
■ Single-phase AC200 V CIMR-V BA0001B ~ 00003B
Three-phase AC200 V CIMR-V 2A0001B ~ 0006B
Figure 1.2
A
L
B
K
J
C
I
H
E
G F
30 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.4 Component Names
Receiving
A
B 1
L
K
C
J
I
H
D
E
F
G
A – Fan cover H –
Front cover
B – Mounting hole I –
Terminal cover
C – Heatsink J –
Bottom cover
D – Optional 24 V DC power supply K –
LED operator
connector cover Refer to Using the Digital LED
Operator on page 91
E – Comm port L – Case
Refer to Network Communications
on page 405
F – Terminal board M – Cooling fan
Refer to Table 3.6 on page 70 Refer to Drive Cooling Fans on
page 254
G – Front cover screw
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 31
1.4 Component Names
A
O
B
N
M
L
C
K
J
D
E
F
I G
32 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.4 Component Names
Receiving
P
N O B
M 1
L C
K
J
D
E
F
I G
H
A – Fan cover I – Front cover screws
B – Mounting hole J – Front cover
C – Heatsink K – Terminal cover
D – Cable cover L – Comm port
Refer to Network Communications
on page 405
E – Terminal board M – LED operator
Refer to Table 3.6 on page 70 Refer to Using the Digital LED
Operator on page 91
F – Cover screws N – Case
G – Rubber bushing O – Top cover
H – Bottom cover P – Cooling fan
Refer to Drive Cooling Fans on
page 254
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 33
1.4 Component Names
L
K C
J D
I
E
H
G
34 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
1.4 Component Names
◆ Front Views
Figure 1.7
Receiving
A
I
I A B
H 1
H B
C
C
D D
G G
E
E
F
F
A – Terminal board connector F – Ground terminal
B – DIP switch S1 G – Terminal cover
Refer to Terminal A2 Switch on
page 79
C – DIP switch S3 H – Option card connector
Refer to Sinking/Sourcing Mode Refer to Connecting the Option
Switch on page 77 Card on page 287
D – Control circuit terminal I – DIP switch S2
Refer to Control Circuit Wiring on Refer to MEMOBUS/Modbus
page 69 Termination on page 81
E – Main circuit terminal
Refer to Wiring the Main Circuit Terminal on page 68
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 35
1.4 Component Names
36 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2
Mechanical
Installation
This chapter explains how to properly mount and install the
drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 37
2.1 Section Safety
WARNING
Fire Hazard
Provide sufficient cooling when installing the drive inside an enclosed
panel or cabinet.
Failure to comply could result in overheating and fire.
When multiple drives are placed inside the same enclosure panel, install
proper cooling to ensure air entering the enclosure does not exceed 40 °C.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main
body of the drive falling.
NOTICE
Observe proper electrostatic discharge (ESD) procedures when
handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
38 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.1 Section Safety
NOTICE
Operating the drive in the low-speed range diminishes the cooling
Mechanical Installation
effects, increases motor temperature, and may lead to motor damage
by overheating.
Reduce the motor torque in the low-speed range whenever using a non-
Yaskawa motor. If 100% torque is required continuously at low speed,
consider using a special drive or vector motor. Select a motor that is
compatible with the required load torque and operating speed range.
The motor may require more acceleration torque with drive operation
than with a commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the
machine to be used with the motor.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 39
2.1 Section Safety
NOTICE
The rated input current of submersible motors is higher than the rated
input current of standard motors.
Select an appropriate drive according to its rated output current. When the
distance between the motor and drive is long, use a cable thick enough to
connect the motor to the drive to prevent motor torque reduction.
40 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.2 Mechanical Installation
Mechanical Installation
installation of the drive.
◆ Installation Environment
To help prolong the optimum performance life of the drive, install the drive in the proper
environment. The table below provides description of the appropriate environment for the
drive.
Table 2.1 Installation Environment
2
Environment Conditions
Installation Area Indoors
-10 C to +40 C (IP20/NEMA Type 1)
-10 C to +50 C (IP20/Open-Chassis)
Ambient Drive reliability improves in enviroments without wide temperature fluctuations.
Temperature When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20 C to +60 C
• Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
Surrounding Area • combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude 1000 m or lower
10 to 20 Hz at 9.8 m/s2
Vibration
20 to 55 Hz at 5.9 m/s2
Orientation Install the drive vertically to maintain maximum cooling effects.
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during
installation and project construction. Failure to comply could result in damage to the drive. Place a
temporary cover over the top of the drive during installation. Remove the temporary cover before start-up, as
the cover will reduce ventilation and cause the drive to overheat.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 41
2.2 Mechanical Installation
A B B
A – Correct B – Incorrect
42 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.2 Mechanical Installation
Mechanical Installation
according to Figure 2.3, derating must be considered and parameter L8-35 must be set.
Refer to Parameter List on page 309.
Figure 2.3
A B 2 mm B
C
2
D
NOTICE: When drives with IP20/NEMA Type 1 enclosures are mounted side-by-side, the top covers of all
drives must be removed as shown in the figure below.
Figure 2.4
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 43
2.2 Mechanical Installation
Note: For information on the amount of heat generated by the drive and appropriate cooling methods,
refer to Specifications on page 291.
44 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.2 Mechanical Installation
■ IP20/Open-Chassis Drives
Table 2.3 IP20/Open-Chassis (without an EMC filter)
Mechanical Installation
W1 2-M4 t1
H1
H
2
D1
H2
W
D
Dimensions (in)
Drive Model
Voltage Class CIMR-V Weight
W1 H1 W H D t1 H2 D1
(lb)
BA0001B 2.20 4.65 2.68 5.04 2.99 0.12 0.20 0.26 1.3
Single-Phase
BA0002B 2.20 4.65 2.68 5.04 2.99 0.12 0.20 0.26 1.3
200 V Class
BA0003B 2.20 4.65 2.68 5.04 4.65 0.20 0.20 1.52 2.2
2A0001B 3.78 4.65 4.25 5.04 5.08 0.12 0.20 2.28 1.3
Three-Phase 2A0002B 3.78 4.65 4.25 5.04 5.41 0.12 0.20 2.28 1.3
200 V Class 2A0004B 5.04 4.65 5.51 5.04 5.63 0.12 0.20 2.56 2.0
2A0006B 3.78 4.65 4.25 5.04 5.08 0.12 0.20 2.28 2.4
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 45
2.2 Mechanical Installation
W1 4-M4
H1
H
t1
D1
H2
W
D
Dimensions (in)
Drive Model
Voltage Class CIMR-V Weight
W1 H1 W H D t1 H2 D1 (lb)
BA0006B 3.78 4.65 4.25 5.04 5.41 0.20 0.20 2.28 3.7
Single-Phase
BA0010B 3.78 4.65 4.25 5.04 6.06 0.20 0.20 2.28 4.0
200 V Class
BA0012B 5.04 4.65 5.51 5.04 6.42 0.20 0.20 2.56 5.3
2A0010B 3.78 4.65 4.25 5.04 5.08 0.20 0.20 2.28 3.7
Three-Phase
2A0012B 3.78 4.65 4.25 5.04 5.41 0.20 0.20 2.28 3.7
200 V Class
2A0020B 5.04 4.65 5.51 5.04 5.63 0.20 0.20 2.56 5.3
4A0001B 3.78 4.65 4.25 5.04 3.19 0.20 0.20 0.39 2.2
4A0002B 3.78 4.65 4.25 5.04 3.90 0.20 0.20 1.10 2.6
4A0004B 3.78 4.65 4.25 5.04 5.41 0.20 0.20 2.28 3.7
Three-Phase
4A0005B 3.78 4.65 4.25 5.04 6.06 0.20 0.20 2.28 3.7
400 V Class
4A0007B 3.78 4.65 4.25 5.04 6.06 0.20 0.20 2.28 3.7
4A0009B 3.78 4.65 4.25 5.04 6.06 0.20 0.20 2.28 3.7
4A0011B 5.04 4.65 5.51 5.04 5.63 0.20 0.20 2.56 5.3
46 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.2 Mechanical Installation
Mechanical Installation
W1 2-M4 t1
H6
H2
H1
H
H4
H5
2
D1
W D
H3
Dimensions (in)
Drive Model
Voltage Class CIMR-V Weight
W1 H2 W H1 D t1 H5 D1 H H4 H3 H6 (lb)
BA0001F 2.20 4.65 2.68 5.10 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.5
Single-Phase
BA0002F 2.20 4.65 2.68 5.10 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 1.8
200 V Class
BA0003F 2.20 4.65 2.68 5.10 4.65 0.20 0.20 1.54 5.89 0.79 0.16 0.06 2.4
2A0001F 2.20 4.65 2.68 5.10 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 3.8
Three-Phase 2A0002F 2.20 4.65 2.68 5.10 2.99 0.12 0.20 0.26 5.89 0.79 0.16 0.06 3.8
200 V Class 2A0004F 2.20 4.65 2.68 5.10 4.25 0.20 0.20 1.54 5.89 0.79 0.16 0.06 2.2
2A0006F 2.20 4.65 2.68 5.10 5.04 0.20 0.20 2.32 5.89 0.79 0.16 0.06 3.7
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 47
2.2 Mechanical Installation
W1 4-M4 t1
H6
H2
H1
H
H5
H4
D1
D
H3
Dimensions (in)
Drive Model
Voltage Class CIMR-V Weight
W1 H2 W H1 D t1 H5 D1 H H4 H3 H6 (lb)
BA0006F 3.78 4.65 4.25 5.10 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.8
Single-Phase
BA0010F 3.78 4.65 4.25 5.10 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.8
200 V Class
BA0012F 5.04 4.65 5.51 5.24 6.42 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.3
2A0010F 3.78 4.65 4.25 5.10 5.08 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.3
Three-Phase
2A0012F 3.78 4.65 4.25 5.10 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.5
200 V Class
2A0020F 5.04 4.65 5.51 5.24 5.63 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.3
4A0001F 3.78 4.65 4.25 5.10 3.19 0.20 0.20 0.39 5.89 0.79 0.16 0.06 2.2
4A0002F 3.78 4.65 4.25 5.10 3.90 0.20 0.20 1.10 5.89 0.79 0.16 0.06 2.7
4A0004F 3.78 4.65 4.25 5.10 5.41 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.5
Three-Phase
4A0005F 3.78 4.65 4.25 5.10 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.8
400 V Class
4A0007F 3.78 4.65 4.25 5.10 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.8
4A0009F 3.78 4.65 4.25 5.10 6.06 0.20 0.20 2.28 5.89 0.79 0.16 0.06 3.8
4A0011F 5.04 4.65 5.51 5.24 5.63 0.20 0.20 2.56 6.02 0.79 0.19 0.20 5.3
48 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
2.2 Mechanical Installation
W1 4-d
Mechanical Installation
H6
H2
H1
H
2
t1
H4
H5
W D1
H3
Dimensions (in)
Drive Model
Voltage Class CIMR-V Weight
W1 H2 W H1 D t1 H5 D1 H H4 H3 H6 d (lb)
2A0030B 4.80 9.76 5.51 9.76 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 4.80 8.38
Three-Phase 2A0040B 4.80 9.76 5.51 9.76 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 4.80 8.38
200 V Class 2A0056B 6.30 11.18 7.09 11.18 6.42 0.20 0.51 2.95 11.42 0.59 0.24 0.06 6.30 12.13
2A0069B 7.56 13.23 8.66 13.23 7.36 0.20 0.87 3.07 13.78 0.59 0.28 0.06 7.56 20.28
4A0018B 4.80 9.76 5.51 9.76 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 4.80 8.38
Three-Phase 4A0023B 4.80 9.76 5.51 9.76 5.51 0.20 0.51 2.17 10.00 0.51 0.24 0.06 4.80 8.38
400 V Class 4A0031B 6.30 11.18 7.09 11.18 5.63 0.20 0.51 2.17 11.42 0.59 0.24 0.06 6.30 11.46
4A0038B 6.30 11.18 7.09 11.18 6.42 0.20 0.51 2.95 11.42 0.51 0.24 0.06 6.30 12.13
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 49
2.2 Mechanical Installation
50 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3
Electrical
Installation
This chapter explains proper procedures for wiring the control
circuit terminals, motor and power supply.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 51
3.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
52 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.1 Section Safety
WARNING
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed
Electrical Installation
only by authorized personnel familiar with installation, adjustment, and
maintenance of AC drives.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire
due to overheating of electrical connections.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 53
3.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Check all the wiring to ensure that all connections are correct after
installing the drive and connecting any other devices.
Failure to comply could result in damage to the drive
54 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.2 Standard Connection Diagram
Electrical Installation
NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate
branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of
delivering not more than 18,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac
maximum (400 V Class).
NOTICE: When the input voltage is 480 V or higher or the wiring distance is greater than 100 meters, pay
special attention to the motor insulation voltage or use an inverter duty motor. Failure to comply could lead
to motor insulation breakdown.
NOTICE: Do not connect the AC control circuit ground to the drive enclosure. Improper drive grounding can
cause the control circuit to malfunction. 3
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA. If a circuit requires less
than 10 mA, connect it to a photocoupler output (P1, P2, PC). Improper application of peripheral devices
could result in damage to the photocoupler output of the drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 55
3.2 Standard Connection Diagram
Figure 3.1
_
Terminals +1, +2, , B1, and B2
are for connecting options.
DC reactor
(option) *1 *2
Thermal relay
Never connect power supply
lines to these terminals. (option) Braking resistor Motor
2 MCCB
*3 Jumper (option)
Cooling fan
For single phase 200 V r1 FU
r1
power supply, use
+2 +1 - B1 B2 FV
R/L1 and S/L2. s1 s1 M
FW
1 MCCB MC
t1
V1000 t1
P2 Frequency agree
(photocoupler 2)
Pulse train input
RP
(max. 32 kHz) PC Photocoupler
Setting power supply output common
+V
2 kΩ +10.5 max. 20 mA
MP
*6
Pulse train output
Main speed A1 0 to +10 V (20 kΩ) 0 to 32 kHz
frequency A2 0 to +10 V (20 kΩ) Analog monitor
AM
reference. (0)4 to 20 mA (250 Ω) + output
Multi-function AM
AC 0 to +10 Vdc
programmable AC - (2 mA)
Termination Comm.
DIP Monitor
resistor connector
switch output
Safety switch 120 Ω, 1/2 W
S2 R+
Safe Disable HC
*7
Input R-
Jumper
H1 S+ MEMOBUS/
S- Modbus comm.
RS-485/422
IG
56 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.2 Standard Connection Diagram
Electrical Installation
* 7. Disconnect the wire jumper between HC and H1 when utilizing the safety input.
WARNING! Sudden Movement Hazard. Do not close the wiring for the control circuit unless the
multifunction input terminal parameter is properly set (S5 for 3-wire; H1-05 = “0”). Improper sequencing of
run/stop circuitry could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the
correct state before energizing the drive. Failure to comply could result in death or serious injury from
moving equipment. When programmed for 3-wire control, a momentary closure on terminal S1 may cause
the drive to start.
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control 3
terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up
(default)). If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter
b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at
power up of the drive and may cause injury.
WARNING! When the application preset funcion is executed (or A1-06 is set to any value other than 0) the
drive I/O terminal funcitons change. This may cause unexpected operation and potential damage to
equipment or injury.
Drive
Stop relay (N.C.) Run relay (N.O.)
S1
Run command (run on momentary close)
S2
Stop command (stop on momentary open)
S5 Foward/reverse command
(multi-function input: H1-05 = 0)
SC
Sequence input common
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 57
3.3 Main Circuit Connection Diagram
DC reactor
(option) Braking Resistor
Jumper Unit (option)
㧗2 㧗1 B1 B2
R/L1 Drive
U/T1
V/T2 Motor
S/L2 W/T3
Single-phase
㧙
200 Vac
NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may
damage the drive.
DC reactor Braking
(option) Resistor Unit
Jumper (option)
㧗2 㧗1 B1 B2
R/L1 Drive U/T1
S/L2 V/T2 Motor
T/L3 W/T3
Three phase 200 Vac
㧙
(400 Vac)
58 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.4 Terminal Block Configuration
Electrical Installation
Models CIMR-V BA0006, 0010, 0012 Models CIMR-V BA0001,
CIMR-V 2A0010, 0012, 0020, 0040, 0002, 0003
0056, 0069 CIMR-V 2A0001, 0002,
CIMR-V 4A0001, 0002, 0004, 0005, 0004, 0006
0007, 0009, 0011, 0023, 0031, 0038 3
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 59
3.5 Protective Covers
◆ IP20/Open-Chassis
■ Removing the Protective Covers
Figure 3.6
1. Loosen the screw that locks the front cover in place to remove.
2. Apply pressure to the tabs on each side of the terminal cover. Pull the terminal cover
away from the drive while pushing in on the tabs to pull the cover free.
Figure 3.7
60 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.5 Protective Covers
Figure 3.8
Electrical Installation
Figure 3.8 Reattach the Protective Covers on an IP20/Open-Chassis Drive
◆ IP20/NEMA Type 1
■ Removing the Protective Covers on an IP20/NEMA Type 1 design
3
Figure 3.9
1. Loosen the screw on the front cover to remove the front cover.
2. Loosen the screw on the terminal cover (Figure 3.10, B) to remove the terminal
Figure 3.10
cover and expose the conduit bracket (Figure 3.10, A).
A
B
Figure 3.10 Remove the Terminal Cover on an IP20/NEMA Type 1 Drive
3. Loosen two screws attaching the conduit bracket (Figure 3.11, A) to remove.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 61
3.5 Protective Covers
Figure 3.11
A
Figure 3.11 Remove the Conduit Bracket on an IP20/Open-Chassis Drive
62 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.6 Main Circuit Wiring
Electrical Installation
◆ Main Circuit Terminal Functions
Table 3.1 Main Circuit Terminal Functions
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 63
3.6 Main Circuit Wiring
• Refer to instruction manual TOBPC72060000 for braking unit or braking resistor unit
wire gauges.
• Refer to Standards Compliance on page 413 for information on UL compliance.
■ Single-Phase 200 V Class
Table 3.2 Wire Gauge and Torque Specifications
64 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.6 Main Circuit Wiring
Electrical Installation
2 to 2.5 5.5 to 14 8
M5 Note: 1.
(17.7 to 22.1) (10 to 6) (8)
R/L1,S/L2,T/L3,U/T1,V/ 2 to 2.5 5.5 to 14 14
M5 Note: 1.
T2,W/T3,-,+1,+2 (17.7 to 22.1) (10 to 6) (6)
1.2 to 1.5 2.0 to 5.5 5.5
0040 B1,B2 M4 Note: 1.
(10.6 to 13.3) (14 to 10) (10)
2 to 2.5 5.5 to 14 8
M5 Note: 1.
(17.7 to 22.1) (10 to 6) (8)
R/L1,S/L2,T/L3,U/T1,V/
M6
4 to 6 14 to 22 22
Note: 1.
3
T2,W/T3,-,+1,+2 (35.4 to 53.1) (6 to 4) (4)
2 to 2.5 5.5 to 8 8
0056 B1,B2 M5 Note: 1.
(17.7 to 22.1) (10 to 8) (8)
4 to 6 14 to 22 22
M6 Note: 1.
(35.4 to 53.1) (6 to 4) (4)
R/L1,S/L2,T/L3,U/T1,V/ 9 to 11 8 to 38 38
M8 Note: 1.
T2,W/T3,-,+1,+2 (79.7 to 11.0) (8 to 2) (2)
2 to 2.5 8 to 14 14
0069 B1,B2 M5 Note: 1.
(17.7 to 22.1) (8 to 6) (6)
4 to 6 8 to 22 22
M6 Note: 1.
(35.4 to 53.1) (8 to 4) (4)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 65
3.6 Main Circuit Wiring
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper
application of noise filters could result in damage to the drive.
NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply
could result in death or serious injury by fire as a result of drive damage from line voltage application to
66 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.6 Main Circuit Wiring
output terminals.
Electrical Installation
detection.
Adjust the drive carrier frequency according to the following table. If the motor wiring
distance exceeds 100 m because of the system configuration, reduce the ground currents.
Refer to Carrier Frequency Selection: C6-02 on page 135.
Refer to Table 3.5 to set the carrier frequency to an appropriate level.
Table 3.5 Cable Length Between Drive and Motor
Note: When setting carrier frequency, calculate the cable length as the total distance of wiring to all
connected motors when running multiple motors from a single drive.
■ Ground Wiring
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on
electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause
dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to
100 Ω or less, 400 V Class: Ground to 10 Ω or less). Improper equipment grounding could result in death or
serious injury by contacting ungrounded electrical equipment.
NOTICE: Do not share the ground wire with other devices such as welding machines or large-current
electrical equipment. Improper equipment grounding could result in drive or equipment malfunction due to
electrical interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper
equipment grounding could result in abnormal operation of drive or equipment.
Refer to Figure 3.13 when using multiple drives. Do not loop the ground wire.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 67
3.6 Main Circuit Wiring
Figure 3.13
A A B
A – Correct B – Incorrect
Note: 1. A cover placed over the DC Bus and braking circuit terminals prior to shipment helps prevent
miswiring. Cut away covers as needed for terminals with a needle-nose pliers.
2. The ground terminal screw on IP20/NEMA Type 1 holds the protective cover in place.
Main Circuit Connection Diagram
For drive main power circuit connections, refer to Figure 3.3 and Figure 3.4 on page 58.
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking
resistors to any other terminals. Improper wiring connections could cause the braking resistor to overheat
and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or
drive.
68 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
V1000
*1 Control circuit
Electrical Installation
Forward run/stop S1
Reverse run/stop S2
Option card
External fault S3 connector
P2 Frequency agree
(photocoupler 2)
Pulse train input
RP
(max. 32 kHz) PC Photocoupler
Setting power supply output common
+V
2 kΩ +10.5 max. 20 mA
MP Pulse train output
Main speed A1 0 to +10 V (20 kΩ) 0 to 32 kHz
frequency A2 0 to +10 V (20 kΩ) Analog monitor
AM
reference. (0)4 to 20 mA (250 Ω) + output
Multi-function AM
AC 0 to +10 Vdc
programmable AC - (2 mA)
Termination Comm.
DIP Monitor
resistor connector
switch output
Safety switch 120 Ω, 1/2 W
S2 R+
Safety HC
input R-
Jumper
H1 S+ MEMOBUS/
S- Modbus comm.
RS-485/422
IG
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wire connections can loosen
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 69
3.7 Control Circuit Wiring
over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
A1-06 may change the I/O terminal function automatically from the factory setting. Refer to Application
Presets on page 111. Failure to comply may result in death or serious injury.
NOTICE: Do not switch an input contactor more often than once every 30 minutes. Improper equipment
sequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the drive
I/O should be used to stop and start the motor.
■ Input Terminals
Table 3.6 Control Circuit Input Terminals
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
70 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
Type No. Terminal Name (Function) Function (Signal Level) Default Setting
Electrical Installation
Main +V Analog input power supply +10.5 Vdc (max allowable current 20 mA)
Frequency
Multi-function analog input (frequency Input voltage 0 to +10 Vdc (20 kΩ) resolution 1/
Reference A1
reference) 1000
Input
Input voltage or input current (Selected by DIP
Multi-function analog input (frequency switch S1) 0 to +10 Vdc (20 kΩ) resolution: 1/1000
A2
reference) 4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω)
resolution: 1/500
AC Frequency reference common 0 Vdc 3
■ Output Terminals
Table 3.7 Control Circuit Output Terminals
MA N.O. (fault)
Multi-Function Digital output
MB N.C. output (fault)
Digital Output 30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
MC Digital output common
Connect a suppression diode as shown in Figure 3.15 when driving a reactive load such as a
relay coil. Ensure the diode rating is greater than the circuit voltage.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 71
3.7 Control Circuit Wiring
Figure 3.15
C
A D
R+ R㧙 S+ S㧙 IG
P1 P2 PC A1 A2 +V AC AM AC MP
MA MB MC
R+ R㧙 S+ S㧙 IG S1 S2 S3 S4 S5 S6 S7 HC SC H1 RP
P1 P2 PC A1 A2 +V AC AM AC MP
MA MB MC
S1 S2 S3 S4 S5 S6 S7 HC SC H1 RP
72 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
Table 3.9 Wire Size and Torque Specifications (Same for All Models)
Electrical Installation
MA, MB, 1.5 (24 to 16) 0.25 to 1.0
M3 0.5 to 0.6 4.4 to 5.3 0.75 (18) 0.5 (20)
MC Single: 0.25 to (24 to 18)
1.5 (24 to 16)
S1-S7, SC,
RP, +V, A1, Shielded
A2, AC, HC, Stranded: 0.25 to line, etc.
H1, P1, P2, 1.0 (24 to 18) 0.25 to 0.5
M2 0.22 to 0.25 1.9 to 2.2 0.75 (18) 0.5 (20)
PC, MP, Single: 0.25 to (24 to 20)
AM, AC,
S+, S-, R+,
1.5 (24 to 16)
3
R-, IG
φd1
6 mm
φd2
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 73
3.7 Control Circuit Wiring
◆ Wiring Procedure
This section describes the proper procedures and preparations for wiring the terminal board.
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is
on. Failure to comply could result in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1,
V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction
due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit
lines. Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper
application of peripheral devices could result in drive performance degradation due to improper power
supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and
equipment. Improper wiring practices could result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment
grounding could result in drive or equipment malfunction or nuisance trips.
Wire the terminal board using Figure 3.18 as a guide (control circuit terminal block). Be
sure to prepare the ends of the control circuit wiring as shown in Figure 3.19. Refer to Wire
Gauges and Tightening Torque on page 63 for tightening torque specifications.
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the
terminal block.
NOTICE: Use shielded twisted-pair cables as indicated to prevent operating faults. Improper wiring
practices could result in drive or equipment malfunction due to electrical interference.
74 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
Figure 3.18
D
Preparing wire E
A terminal ends
B
Electrical Installation
C
A D
F C
E
B
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 75
3.7 Control Circuit Wiring
Figure 3.20
B
RP C
2k
+V D
G A1 E
A2 F
AC
Figure 3.20 Wiring the Frequency Reference to the Control Circuit Terminals (External Reference)
76 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.8 I/O Connections
Electrical Installation
Table 3.11 Sinking/Sourcing Mode Setting
Figure 3.21
DIP Switch S3 3
SINK
SOURCE
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 77
3.8 I/O Connections
Figure 3.22
SINK
S1
Forward run/stop
S2
SOURCE Reverse run/stop
S3
Multi-function input
External fault N.O.
S4
Fault reset
S5
Multi-speed step 1
S6
Multi-speed step 2
S7
Jog reference
SINK
+24V
S3
SOURCE
SC
Shielded cable
Drive
SINK
Multi-step speed 2 S6
Jog frequency S7
SINK
+24V
S3
SOURCE
SC
Figure 3.23 Source Mode: Sequence from PNP Transistor (+24 V Common)
78 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.9 Main Frequency Reference
◆ Terminal A2 Switch
The main frequency reference can either be a voltage or current signal input. For voltage
signals both analog inputs, A1 and A2, can be used, for current signals A2 must be used.
Electrical Installation
To use current input at terminal A2, set the DIP switch S1 to "I" (factory setting) and set
parameter H3-09 = “2” or “3” (4-20 mA or 0-20 mA). Set parameter
H3-10 = “0” (frequency reference).
Note: If Terminals A1 and A2 are both set for frequency reference (H3-02 = 0
and H3-10 = 0), the addition of both input values builds the frequency reference.
When using input A2 as voltage input, set the DIP switch S1 to “V” (left position) and
program parameter H3-09 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10 Vdc
without lower limit).
3
Table 3.12 Frequency Reference Configurations
Drive Drive
+10.5 V
+V +10.5 V
20 mA current
+V 20 mA current
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 79
3.9 Main Frequency Reference
Figure 3.24
DIP Switch S1
V I
Setting Default
No. Parameter Name Description Range Setting
Selects the signal level for terminal A2.
0: 0 to +10 V, unipolar input (negative frequency
reference values are zeroed)
Frequency ref. (current)
H3-09 1: 0 to +10 V, bipolar input (negative frequency 0 to 3 2
terminal A2 signal level selection
reference changes the direction)
2: 4 to 20 mA
3: 0 to 20 mA
80 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.10 MEMOBUS/Modbus Termination
Electrical Installation
Table 3.15 MEMOBUS/Modbus Switch Settings
S2 Position Description
ON Internal terminal resistance ON
OFF Internal terminal resistance OFF (no terminal resistance); default setting
Figure 3.25
DIP Switch S2 3
OFF ON
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 81
3.11 Braking Resistor
Note: The braking circuit must be sized properly in order to dissipate the power required to decelerate
the load in the desired time. Ensure that the braking circuit can dissipate the energy for the set
deceleration time prior to running the drive.
Use a thermal overload relay or an over-temperature contact to interrupt input power to the
drive in the event the braking resistor overheats.
In the event of a possible thermal overload, the relay will trigger the input contactor and
prevent the braking resistor from burning up.
◆ Installation
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking
resistor directly to any other terminals. Improper wiring connections could result in death or serious injury by
fire. Failure to comply may result in damage to the braking circuit or drive.
NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring
braking circuits could result in damage to the drive or equipment.
■ Installation Procedure
1. Disconnect all electrical power to the drive and wait at least five minutes before
servicing the drive and any connected components.
2. Remove drive front cover.
3. Use a voltmeter to verify that voltage is disconnected from incoming power
terminals and that the DC bus no longer holds a charge.
82 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.11 Braking Resistor
Figure 3.26
Thermal
relay Braking resistor
Power
supply MCCB MC
R/L1 B1 B2
S/L2 U/T1
T/L3 V/T2 Motor
W/T3
THRX OFF ON MC
Drive
Electrical Installation
SA
MC
THRX
SA
Thermal relay switch for
external braking resistor
MC TRX
SA
TRX
MA MC
Fault contact
4. Follow maufacturer instructions to connect the resistor unit to the drive using proper
3
wire gauge according to local electrical codes.
Power leads for the remote mount resistors generate high levels of electrical noise;
group these signal leads separately.
5. Mount the resistor unit on a noncombustible surface. Maintain minimum side and
top clearances according to resistor manufacturer instructions.
WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could result in death
or serious injury by fire. Attach the drive or braking resistors to metal or other noncombustible material.
■ Adjustments
7. Set parameter L3-04 = “0” or “3” to disable stall prevention during deceleration.
Set parameter L8-01= “1” to enable overheat protection when using Yaskawa
heatsink mounted braking resistor. Set L8-01 = “0” for other braking resistor types.
Set parameter L3-04 = “3” to generate the shortest possible deceleration time.
Table 3.16 Braking Resistor Settings
Parameter Settings
0: Disabled. The drive will not provide overheat
L8-01: Internal Dynamic Braking Resistor Protection
protection. Supply separate means of overheat protection.
selection
1: Enabled. Braking Resistor is protected from overheat.
0: Stall prevention disabled.
L3-04: Stall Prevention During Deceleration <1>
3: Stall prevention enabled with a braking resistor. <2>
■ Operation Check
8. Operate the system and verify the required deceleration rate is obtained during
dynamic braking or stopping.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 83
3.12 Wiring Checklist
8 Properly wire the power supply to drive terminals R/L1, S/L2 and T/L3. 58
Properly wire the drive and motor together.
The motor lines and drive output terminals R/T1, V/T2 and W/T3 should match in order
9 66
to produce the desired phase order. If the phase order is incorrect, the drive will rotate in
the opposite direction.
10 Use 600 Vac vinyl-sheathed wire for the power supply and motor lines. 63
Use the correct wire gauges for the main circuit. Refer to Table 3.2, Table 3.3, or
11 63
Table 3.4.
• When using comparatively long motor cable, calculate the amount of voltage drop.
Motor rated voltage (V) x 0.02 ≥ 63
-3
3 x voltage resistance (Ω/km) x cable length (m) x motor rated current (A) x 10
• If the cable between the drive and motor exceeds 500 m, adjust the carrier frequency 67
(C6-02) accordingly. 135
12 Properly ground the drive. Review page 67. 67
Tightly fasten all terminal screws (control circuit terminals, grounding terminals).
13 63
Refer to Table 3.2, Table 3.3 or Table 3.4.
84 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
3.12 Wiring Checklist
Set up overload protection circuits when running multiple motors from a single drive.
Electrical Installation
MC2 OL2
14 M2
MCn OLn
Mn
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 85
3.12 Wiring Checklist
86 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4
Start-Up Programming
& Operation
This chapter explains the functions of the LED operator and
how to program the drive for initial operation.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 87
4.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may include drives without covers or safety
shields to illustrate details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
88 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.1 Section Safety
WARNING
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed
only by authorized personnel familiar with installation, adjustment and
Operation
Remove all metal objects such as watches and rings, secure loose clothing,
and wear eye protection before beginning work on the drive.
Do not remove covers or touch circuit boards while the power is on. 4
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire
due to overheating of electrical connections.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 89
4.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Check all the wiring to ensure that all connections are correct after
installing the drive and connecting any other devices.
Failure to comply could result in damage to the drive.
90 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.2 Using the Digital LED Operator
Operation
1 11
5
4
2
15
3
14
STOP
7 8
10
4 6
STOP
V1000
Fref : (Hz)
FWD/REV Sel :
Fout : (Hz)
lout : (A)
Mon1 : (V)
Monitor :
Verify :
SetUpGuide :
Program :
Auto-Tuning :
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 91
4.2 Using the Digital LED Operator
1 Data Display Area Displays the frequency reference, parameter number, etc.
6 Down Arrow Key Scrolls down to select parameter numbers, setting values, etc.
11 LO/RE Light Lit while the operator (LOCAL) is selected to run the drive.
92 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.2 Using the Digital LED Operator
Operation
text as it appears on the display screen.
Lit Flashing
4
1 A J S
2 B K T
3 C L U
4 D M V
<1>
5 E N W
<1>
6 F O X none
7 G P Y
8 H Q Z none
<1> Displayed in two digits.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 93
4.2 Using the Digital LED Operator
As
illustrated in
this manual
<1> Refer to the DriveWorksEZ instruction manual for further information.
As shown
<1> For the difference between “flashing” and “flashing in short intervals” of the RUN LED, refer to Figure 4.2, RUN
LED and Drive Operation.
94 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.2 Using the Digital LED Operator
Figure 4.1
1s
ON ON
flashing
ON ON ON ON
quick
Operation
during stop RUN STOP RUN STOP
/ 6 Hz
0 Hz
frequency setting
RUN LED OFF ON ON OFF
4
Flashing
Figure 4.2 RUN LED and Drive Operation
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 95
4.2 Using the Digital LED Operator
:
Turn the power on
* :
*Pressing RUN will start the motor.
Forward Selection Reverse Selection
:
DRV light is on.
:
Output Frequency
Output Current
XX
Monitor Display
XX
XX XX XX
Verify Menu
XX XX XX
*Drive cannot operate the motor.
XX
DRV light is off.
Set Up Mode
XX XX XX
XX
Parameter Setting Mode
XX
Auto-Tuning
XX
96 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
Operation
drive can run even if the mode is switched to the programming mode. When setting b1-08 to 0
(disabled), the mode cannot be switched to the programming mode while the drive is running.
Table 4.3 Summary ofModes
Forward/Reverse
Monitor Display
Verify Function
Auto-Tuning
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 97
4.3 The Drive and Programming Modes
Frequency Reference
This display screen allows the user to monitor and set the frequency
reference while the drive is running. Refer to The Drive and
Power Up Programming Modes on page 97.
Note: The user can select items to display when the drive is first
STOP powered up by setting parameter o1-02.
Default Setting
Drive Mode
98 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
Drive Mode
Monitor Display
Operation
Verify Function
Lists all parameters that have been edited or changed from default
settings. Refer to Verifying Parameter Changes: Verify Menu
on page 102.
4
Parameter Setting
Allows the user to access and edit all parameter settings. Refer
to Parameter List on page 309.
Auto-Tuning
Motor parameters are calculated and set automatically. Refer to
Auto-Tuning on page 153.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 99
4.3 The Drive and Programming Modes
Frequency Reference
Drive Mode Returns to the frequency reference display screen.
Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode,
etc.) other than drive mode while the drive is stopped. However, the drive cannot be operated in
other modes. Return the mode to "Drive Mode" after completing periodic inspection.
Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6
Hz) while in Drive Mode. This example assumes the drive is set to LOCAL.
Figure 4.4
Frequency reference
display at power up
STOP
Press to select LOCAL Press to select the
digit to the right
100 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
Operation
Note: Pressing ENTER from APPL navigates to the Application Preset setting display. When the set
value is changed, the parameter is changed to the optimum value for each application. It is set to
0 (General-purpose) prior to shipment. Refer to Application Presets on page 111.
Figure 4.5 illustrates the keys to press to enter the Setup Group.
In this example, the source of the frequency reference is changed from the control circuit 4
terminals to the LED Operator (i.e., b1-01 is changed from 1 to 0).
Figure 4.5
appears when powered up
*1 Pressing ENTER from APPL navigates to the Application Preset setting display.
When the set value is changed, the parameter is changed to the optimum value for
each application. It is set to 0 (General-purpose) prior to shipment.
*2 Move to the right to change parameter settings. Scroll down to view and check
settings in the Setup Mode
*3 To return to the Top Menu, press . To view or edit other parameters,
press and .
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 101
4.3 The Drive and Programming Modes
Step Display/Result
102 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
Step Display/Result
Operation
Press to enter the list of parameters that have been edited
3. from their original default settings. ⇒
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 103
4.3 The Drive and Programming Modes
Step Display/Result
again.
Parameters used for this drive are classified into A to U. To simplify the drive setup,
frequently used parameters are selected and input into Setup Mode.
104 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
Operation
d1-02 Frequency Reference 2 E2-11 Motor Rate Capacity
d1-03 Frequency Reference 3 H4-02 Terminal FM Gain Setting
d1-04 Frequency Reference 4 L1-01 Motor Protection Function Selection
d1-17 Jog Frequency Reference L3-04 Stall Prevention Selection during Deceleration
4
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 105
4.4 Start-up Flowcharts
106 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.4 Start-up Flowcharts
START
Application Presets
Yes
A1-06 used ?
Operation
TO
No
Set the control mode in parameter A1-02.
For information about the control modes refer to Section 4.5 Refer to section
4.4 Application
Macros
?
?
Set the basic parameters:
b1-01/02 for frequency reference and run command source selection
H1-,H2-,H3-,H4-,H6- for I/O terminal setting
)520
4
? d1- for multi-speed references if used
? C1- and C2- for accel./decel. and S-curve time settings
? C6-01 for heavy/normal duty mode selection
? L3-04 if braking options are used
To To 2: Open Loop To
Flowchart A- Flowchart A- Vector control Flowchart A-
1 2 3
Run the motor without load, check the rotation direction and operation. Verify, external signal
commands to the drive work as desired
Couple the load or machine to the motor. Run the machine and check it operates as desired
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 107
4.4 Start-up Flowcharts
From
Flowchart
A
Energy Savings
(b8-01=1)
or
Speed Estimation
NO Speed Search (b3-24=1)
enabled ? YES
YES
NO
Perform Stationary Auto-Tuning for
terminal resistance (T1-01 = 2)
Return to
Flowchart
A
Figure 4.7 Simple Motor Set-Up with Energy Savings or Speed Search Using V/f Mode
108 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.4 Start-up Flowcharts
From
Operation
NO Possible for motor to
YES
rotate during tuning? *
YES
Return to
Flowchart
A
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 109
4.4 Start-up Flowcharts
From
Flowchart
A
Motorcode is known ?
For parameter E5-01 NO
(for Yaskawa PM motors)
YES Enter “FFFF” to parameter E5-
01
Return to
Flowchart
A
110 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
This drive incorporates a function to set the parameters automatically for the applications
Operation
4: AHU (HVAC) fan 5: Compressor 6: Hoist (elevator)
7: Cranes (traverse, traveling)
Note: For the details of these functions, Refer to Application Presets on page 111.
4
2WOR %QPXG[QT (CP
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 111
4.5 Application Presets
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Setting parameter
A1-06 may change the I/O terminal function automatically from the factory setting. Failure to comply may
result in death or serious injury.
Perform a 2-wire or 3-wire initialization (A1-03 = 2220 or 3330) on the drive before
selecting one of the application presets or before switching between application presets. The
initialization process should reset drive parameters before using an application preset.
Save user-edited parameters to a list by setting o2-03 to “1”. This allows for more immediate
access a specific list of relevant parameters and saves time scrolling through the parameter
menu items.
Set the parameter access level for Preferred Parameters (A1-01 = “1”) to display only the
setup parameters.
The parameters listed in the table below are unaffected by drive initialization:
<1> The control method set to A1-02 is unaffected when performing a 2-wire or 3-wire intialization, but it
automatically changes according to the value set to parameter A1-06.
■ Related Parameters
112 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
■ Application Presets
Operation
Below is a list of application presets and the values automatically assigned to the parameters
as a result of each preset:
Table 4.5 Water Supply Pump Application: Parameters and Settings
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 113
4.5 Application Presets
114 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
Operation
b1-04 Reverse Operation Selection 1: Reverse prohibited
C6-01 Duty Rating 1: Normal Duty
C6-02 Carrier Frequency Selection 3: 8.0 kHz
H2-03 Terminals P2 Function Selection (open-collector) 39: Watt Hour Pulse Output
2: CPU Power Active - Drive will 4
L2-01 Momentary Power Loss Operation Selection restart if power returns prior to
control power supply shut down.
L8-03 Overheat Pre-Alarm Operation Selection 4: Derated operation
2: Carrier frequency derating across
L8-38 Carrier Frequency Reduction
entire frequency range.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 115
4.5 Application Presets
116 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
Operation
L8-41 Current Alarm Selection 1: Enabled (alarm is output)
Note: A sequence to release the brake is needed when the multi-function output photocoupler P2-PC
closes. Refer to Hoist Application Preset Specifics on page 118 for more information.
Note: Perform Auto-Tuning after selecting the Hoist Application Preset.
Table 4.16 Parameters Automatically Saved as Preferred (A2-01 to A2-16) 4
No. Parameter Name No. Parameter Name
A1-02 Control Method Selection d1-02 Frequency Reference 2
b1-01 Frequency Reference Selection d1-03 Frequency Reference 3
b6-01 Dwell Reference at Start E1-08 Mid Output Frequency Voltage (VC)
Terminals MA, MB, and MC Function
b6-02 Dwell Time at Start H2-01
Selection
C1-01 Acceleration Time 1 L1-01 Motor Overload Protection Selection
C1-02 Deceleration Time 1 L4-01 Speed Agreement Detection Level
C6-02 Carrier Frequency Selection L6-02 Torque Detection Level 1
d1-01 Frequency Reference 1 L6-03 Torque Detection Time 1
Note: Read the instructions listed in Hoist Application Preset Specifics on page 118 when using Hoist
Application Preset.
Table 4.17 Crane Application (Travel): Parameters and Settings
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 117
4.5 Application Presets
Note: A sequence to release the brake is needed when the multi-function output photocoupler P2-PC
closes. Hoist Application Preset Specifics on page 118 for more information.
118 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
<1> This setting range is available when using OLV Control. In V/f Control, set the level as the motor rated slip
frequency pulse 0.5 Hz. Not enough motor torque will be created if this value is set too low, and the load may tend
Operation
L4-01
L4-02
Output
Time
Frequency
Frequency ON OFF
4
Detection 2
Sequence Circuit Design for Opening and Closing the Holding Brake
Design the braking sequence as follows:
The brake should release when terminal P2-PC closes in response to the run conditions on
the sequence side.
When a fault signal is output, the brake should close. When an up or down command is
entered, the brake should release.
Figure 4.10
Drive
24 V
Fault Contact Holding brake
MA
auxilary relay coil
UP S1
MB Safety UP
㧔Forward㧕 BR
Circuit
DOWN MC DOWN
S2
㧔Reverse㧕
BR
High speed S6 Frequency Detect 2
㧔Multi-step speed 2) P2 ONBrake energized
Low speed 㧔DC 30V 1A TCVKPI㧕
SC
PC
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 119
4.5 Application Presets
Drive
24 V
Fault Contact Holding brake
MA
auxilary relay coil
UP S1
MB Safety UP
㧔Forward㧕 BR
Circuit
DOWN MC DOWN
S2
㧔Reverse㧕
BR
High speed S6 Frequency Detect 2
㧔Multi-step speed 2) P2 ONBrake energized
Low speed 㧔DC 30V 1A TCVKPI㧕
SC
PC
■ Detailed Description
To save specific parameters to A2-01 to A2-32, first set the access level to allow access to all
parameters (A1-02 = “2”). After selecting the parameters to be saved to A2-01 through A2-
32, set the access level to allow access only to the selected list of User Parameters. Set A1-
01 to “1” to restrict access so users can only set and reference the specific parameters saved
as User Parameters.
120 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.5 Application Presets
■ Detailed Description
0: Do not save history of recently viewed parameters.
Operation
through A2-32. A total of 16 parameters are saved in order, with the most recently edited
parameter set to A2-17.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 121
4.6 Basic Drive Setup Adjustments
122 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
settings. Back up all parameters in the event of accidental initialization. the data with 2-wire
sequence returns all the set parameters to the factory settings. Refer to Backing Up Parameter
Values: o2-03 on page 164.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 123
4.6 Basic Drive Setup Adjustments
124 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Figure 4.12
Drive
0 to 10 V
2 kΩ A1 Main Frequency Reference
(voltage input)
A2 Auxiliary Frequency Reference
(voltage/current input)
AC Frequency Reference
Common
Operation
reference.
• Set the signal level for analog input A2 to current input (H3-09 = “2” for 4 to 20 mA, H3-
09 = “3” for 0 to 20 mA).
• Set the function for analog input A2 to frequency reference (H3-10 = “0”) to command
terminal A2 to be a frequency reference.
4
• Set DIP switch S1 to the I position for a current signal input.
Figure 4.13
DIP switch S1
Drive
V I
㧗V (+10.5 V, 20 mA)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 125
4.6 Basic Drive Setup Adjustments
When the digital input assigned in step 2 is off, terminal A1 is the frequency reference input.
If it is closed, the A2 input value becomes the frequency reference. The active acceleration /
deceleration times are used for the change-over between the values
Figure 4.14
Drive
V (+10.5 V, 20 mA)
126 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
serious injury.
Step Display/Result
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 127
4.6 Basic Drive Setup Adjustments
Step Display/Result
off on
5. Press the STOP key to stop the motor. The RUN light will flash ⇒
until the motor comes to a complete stop. flashing off
Drive
Forward Run
S1
Reverse Run
S2
128 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Figure 4.16
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control
terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up
Operation
(default)). If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter
b1-17 is set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at
power up of the drive and may cause injury.
Note: Refer to Parameter List on page 309 for a list of digital input functions. After performing a 3-
wire initialization (A1-03 = “3”), the drive will automatically assign the forward/reverse
command to terminal S5. 4
CAUTION! The motor will begin rotating as soon as the power is switched on. Proper precautions must be
taken to ensure that the area around the motor is safe prior to powering up the drive. Failure to do so may
result in minor or moderate injury.
Note: Run by Turning on/off the Power Supply. For safety reasons, the drive is initially set up not to
accept a run command at power up (b1-17 = "0"). If a run command is issued at power up, the
RUN indicator LED will flash quickly. To change this and have the run command issued by the
drive, change parameter b1-17 to 1
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 129
4.6 Basic Drive Setup Adjustments
Figure 4.17
Run Command
ON OFF
Output Frequency
Decel Time
(C1-02, etc.)
DC Injection
Current (b2-02)
DC Injection Braking
DC Braking Time at Stop (b2-04)
Run Command
ON OFF
Output Voltage
Motor Rotations
130 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
baseblock time (L2-03). Once the minimum baseblock time has expired, the drive will inject
DC current into the motor windings to lock the motor shaft. The stopping time will be
reduced as compared to coast to stop. The level of DC Injection current is set by parameter
b2-02 (default = 50%). The time for DC Injection Braking is determined by the value set to
b2-04 and by the output frequency at the time the run command is removed.
Note: DC Injection braking cannot be selected as a stopping method in PM Open Loop Vector Control.
Figure 4.19
Run Command
ON OFF
Output Frequency
DC Injection Braking
Operation
DC Injection Braking Time
b2-0410
b2-04
4
Output frequency when
stop command was entered
10% 100%
(Max Output Frequency)
■ Coast to Stop with Timer: Ignoring a Run Command Input within the
Deceleration Time: b1-03 = 3
When b1-03 = 3, a stop command interrupts drive output and the motor coasts to stop. The
drive will not accept the next run command until time “t” has passed. Time “t” is determined
by the output frequency at the moment the stop command was entered and the deceleration
time set to the drive according to Figure 4.20.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 131
4.6 Basic Drive Setup Adjustments
Figure 4.20
Run Command
ON OFF ON OFF ON
Output Frequency
Deceleration time
(C1-02, etc.)
Minimum
Output frequency when
Baseblock Time
stop command was entered
㧔L2-03㧕
Setting
No. Parameter Name Description Range Default
WARNING! Sudden Movement Hazard. Rapid deceleration may cause the drive to fault on an overvoltage
condition, resulting in death or serious injury due to an uncontrolled motor state. Set an acceptable
deceleration time in parameter C1-09 when using the Fast-stop feature.
132 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Setting Description
0 Time is set in units of 0.01 s, making the setting range 0.00 to 600.00 seconds.
1 Time is set in units of 0.1 s, making the setting range 0.0 to 6000.0 seconds.
Operation
Accel/Decel Time 1 Accel/Decel Time 2
H1- =7 H1- = 1A Acceleration Time Deceleration Time
Output Frequency
C1-11
Accel/Decel Time
Switch Frequency
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 133
4.6 Basic Drive Setup Adjustments
Forward Run
Command
Reverse Run
Command
C2-02 C2-04
C2-03
Output
Frequency
C2-01
C2-01 C2-04
C2-02 C2-03
Figure 4.22 S-Curve Characteristics
134 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Overload
150 % Overload
120 %
Rated Load
Rated Load 100 %
100 %
Characteristics
0 100 %
Use HD Rating is designed applications Use ND Rating for applications in which the
requiring a high overload tolerance with torque requirements drop along with the
Application
constant load torque. Such applications speed. Examples include fans or pumps where
include extruders, conveyors and cranes. a high overload tolerance is not required.
Operation
Overload capability 100% continuous, 150% of drive rated 100% continuous, 120% of drive rated current
(OL2) current for 60 s for 60 s
L3-02 Stall
Prevention during 150% 120%
Acceleration
L3-06 Stall
4
Prevention during 150% 120%
Run
Note: By selecting HD/ND motor parameters E2 and E4 are changed to values for the maximum
applicable motors.
Note: Settings 7 through A for parameter C6-02 use a Swing PWM equivalent to a 2 kHz audible
noise. This function turns the motor noise into a less obtrusive white noise.
Note: The upper limit for the carrier frequency is determined by drive capacity.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 135
4.6 Basic Drive Setup Adjustments
Symptom Remedy
Speed and torque are unstable at low speeds.
Noise from the drive is affecting peripheral devices.
Lower the carrier frequency.
Excessive leakage current from the drive.
Wiring between the drive and motor is too long. <1>
Motor acoustic noise is too loud. Increase the carrier frequency or use Swing PWM.
<1> The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below.
Note: When using PM Open Loop Vector control with long cable lengths, set the carrier freqency to 2
kHz (C6-02 = “1”). Use V/f control if the motor cable exceeds 100 m.
User Defined and Variable Carrier Frequency
Set parameter C6-02 to “F” to set carrier frequency values between fixed values.
In Open Loop Vector and PM motor control the desired value can be set in parameter C6-03.
In V/f control the carrier frequency can be set up to change linearly with the output
frequency. In this case the upper and lower limits for the carrier frequency and the carrier
frequency proportional gain (C6-03, C6-04, C6-05) have to be set up like shown
Figure 4.23.
Note: Set both C6-03 and C6-04 to the same value or set C6-05 to 0 to keep the carrier frequency at a
constant level. C6-03 sets the Carrier frequency upper limit.
Figure 4.23
Carrier Frequency
C6-03
Output Frequency
C6-04 × (C6-05) × K
Output Frequency
E1-04
Maximum Output Frequency
* The value of coefficient K is determined by the value of C6-03.
C6-03 ҈ 10.0 kHz㧦K=3
10.0 kHz > C6-03 ҈ 5.0 kHz㧦K=2
5.0 kHz > C6-03㧦K=1
136 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
(kHz) (A) (kHz) (A) (kHz) (A)
2 0006 2 6.0
1.1 kW/ 10 5.0
0.75W 15 4.0
2 0008 2 8.0
1.5 kW/ 8 6.9
1.1 kW 15 5.5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 137
4.6 Basic Drive Setup Adjustments
(Approximate Values)
Setting Value Braking Voltage Level
Voltage of OV Transistor Desired AC for OV
E1-01 Detection Operation UV Detection Level Voltage Suppression,
Level during KEB
Level Stall Prevention
200 V 190 V
all settings 410 V 394 V 240 V 370 V
Class (single-phase=160 V)
400 V setting ≥ 400V 820 V 788 V 380 V 480 V 740 V
Class setting < 400V 740 V 708 V 350 V 440 V 660 V
Note: This data is for an internal dynamic braking resistor of 0.1 to 18.5 kW. For larger units, see
“Dynamic Braking Resistor Unit for VARISPEED-600 Series, TOBPC72060000”
138 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Setting
Operation
1. Set the input voltage for the drive. Refer to Drive Input Voltage Setting: E1-01 on
page 138.
2. Select one of the two following V/f patterns:
• *Select one of the 15 preset V/f patterns (setting = 0 through E)
• **Select the Custom V/f pattern (setting = F) 4
3. In case of * the following parameters are automatically set.
In case of **, the following parameters are adjustable.
E1-04 (Max Output Frequency), E1-05 (Max Voltage), E1-06 (Base Frequency), E1-
07 (Mid Output Frequency), E1-08 (Mid Output Frequency Voltage), E1-09 (Min
Output Frequency), E1-10 (Min Output Frequency Voltage)
Figure 4.24
E1-13
E1-08
E1-10
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 139
4.6 Basic Drive Setup Adjustments
Note: The default setting for the V/f pattern is for a custom V/f pattern (E1-03 = F).
Table 4.20 V/f Patterns
9 50 Hz, high starting torque • High starting should be selected only when:
• Wiring between the drive and motor exceeds
150 m
High starting
A 60 Hz, mid starting torque • Large amount of starting torque is required
torque
• AC reactor is installed
• motor exceeds the largest motor
recommended for that drive used
B 60 Hz, high starting torque
C 90 Hz (with 60 Hz base)
140 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Voltage (V)
Voltage (V)
Voltage (V)
16 16 16 16
12 12 12 12
0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 50 60 0 1.5 3 60 72
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Operation
200 200 200 200
Voltage (V)
Voltage (V)
Voltage (V)
Voltage (V)
35
50
35
50 4
9 9
8 8
0 1.3 25 50 0 1.3 25 50 0 1.5 30 60 0 1.5 30 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 141
4.6 Basic Drive Setup Adjustments
Voltage (V)
Voltage (V)
Voltage (V)
24 24
19 19
13 15
12 12
0 1.3 2.5 50 0 1.3 2.5 50 0 1.5 3 60 0 1.5 3 60
Frequency (Hz) Frequency (Hz) Frequency (Hz) Frequency (Hz)
Voltage (V)
16 16 16
12 12 12
0 1.5 3 60 90 0 1.5 3 60 120 0 1.5 3 60 180
Frequency (Hz) Frequency (Hz) Frequency (Hz)
Note: Setting an improper V/f pattern may result in reduced motor torque or increased current (due to
over excitation).
142 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
Tuning is not possible, contact the motor manufacturer to find out the
resistance between lines (T-lead to T-lead). If using the Motor Test Report,
Motor Line-to-Line
E2-05 calculate resistance between lines as follows:
Resistance
E-Type Insulation: Test Report value for line resistance at 75 °C at 0.92 ohms
B-Type Insulation: Test Report value for line resistance at 75 °C at 0.92 ohms
F-Type Insulation: Test Report value for line resistance at 115 °C at 0.87 ohms 4
Set the amount of voltage drop due to motor leakage inductance at base
frequency and motor rated current.This value should be set when using a high-
Motor Leakage
E2-06 speed motor or another type of motor that has a relatively small amount of
Inductance
inductance. Contact the motor manufacturer to get the motor leakage
inductance, as this information is not usually written on the motor nameplate.
E2-07 Motor Iron-Core
This value is automatically set during rotational Auto-Tuning.
<1> Saturation Coefficient 1
E2-08 Motor Iron-Core
This value is automatically set during rotational Auto-Tuning.
<1> Saturation Coefficient 2
Displayed only when using Open Loop Vector Control. It is not necessary to
set this parameter, but it may require adjustment under the following
circumstances:
E2-09 Motor Mechanical Loss Large amount of torque loss relative to motor bearings
Fan and pump type applications with a large amount of torque loss
The amount of mechanical loss will be reflected in the amount of torque
compensation.
Motor Iron Loss for Displayed only when using V/f Control. Increase the motor iron loss in watts
E2-10
Torque Compensation in order to increase the accuracy of torque compensation.
Sets the motor rated power in kilowatts (kW). This value is automatically set
E2-11 Motor Rated Output
during Auto-Tuning in units of 0.01.
E2-12 Motor Iron-Core Set to the motor iron saturation coefficient at 130% of magnetic flux. This
<1> Saturation Coefficient 3 value is automatically set during rotational Auto-Tuning.
<1> Parameters E2-07 through E2-08 and E2-12 may be difficult to set manually. If Auto-Tuning is not possible,
simply leave these settings at the default values.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 143
4.6 Basic Drive Setup Adjustments
Note: The setting range for H2-01 through H2-03 is 0 to 14D. Refer to Parameter List on page 309 for
more information.
Figure 4.25
MA Fault
MB
MC Fault
PC Open-collector Common
144 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
■ Changing Analog Output Settings
The following example illustrates how to program analog output terminal FM to generate a
signal proportional to drive output current (monitor U1-03). 4
Using H4-01 to Display Monitor Contents
Step Display/Result
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 145
4.6 Basic Drive Setup Adjustments
Step Display/Result
Adjusting the Analog Output Terminal Voltage with H4-02 and H4-03
Note: This example continues from Step 3 in the previous example.
Step Display/Result
Press the key while the drive is stopped and the following
2. voltage is output for adjustment: output voltage = (10 V x Output ⇒
Gain (H4-02) + Output Bias (H4-03). Using this output, adjust
output gain (H4-02) and output bias (H4-03).
Figure 4.26
Output Voltage
10
Gain V
100
(%)
10 V
10
Bias V
100
(%) Monitor
0V Contents
0% 100%
Figure 4.26 Adjusting the Monitor Output
146 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Related Parameters
Parameter
No. Name Description Setting Range Default Setting
Operation
0 to 4 1
Enables or disables motor thermal overload
protection (OL1) Use L1-13 (Continuous Electrothermal
Motor Operation Selection) to select whether
0: Disabled
Overload electronic thermal value is “held” or “not
L1-01
Protection
Selection
1: Protection for general purpose motor
2: Protection for inverter motor held” when the power supply is turned off. 4
3: Protection for vector motor When connecting several motors to one
4: Protection for PM variable torque motor drive, set “0” (disabled) and install a thermal
relay on each motor.
Sets the electronic thermal overload protection
Motor detection time in the motor overload protection
Overload (OL1) function.
L1-02 0.1 to 5.0 1.0 min
Protection This setting rarely needs to be changed and
Time should be set in accordance with the overload
tolerance of the motor.
Note: Executing C6-01 (Duty Cycle) changes motor parameters E2 and E4 including motor rated
current to the values of the maximum applicable motor.
Digital Outputs (H2-01 through H2-03)
Setting Procedure
1. Set E2-01 (Motor Rated Current) and E4-01 (Motor 2 Rated Current) to the motor
rated current.
Note: 1. Values set for the current become the base current for electronic thermal overload protection.
2. These values are automatically set by performing Auto-Tuning.
3. The E4-01 setting is not needed if not using motor 2.
2. Set the proper motor protection level to L1-01.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 147
4.6 Basic Drive Setup Adjustments
The ability of the cooling fan to keep an induction motor cool varies by the speed
control range. Protection characteristics of the electronic thermal overload
protection should be set accordingly. Refer to Table 4.21 for motor types and
overload tolerances.
NOTICE: When connecting multiple motors to one drive, disable the electronic overload protection of the
drive (L1-01 = 0) and protect each motor with its own motor thermal overload. Failure to comply could result
in improper drive operation.
NOTICE: Inadequate motor protection could result in damage to the motor. Configure a motor thermal
overload to disconnect main power to the drive when tripped. When using a thermal relay, disable the motor
protection function (L1-01 = “0”).
Electrothermal
L1-01 Protection
Setting Motor Type Overload Tolerance Cooling Fan Capacity (100% motor
overload)
150
Rated Speed = 100% Speed
60 seconds
Operating continuously
100 General purpose motors are at less than line power
General- 90 designed to operate from frequency can trigger
Torque
150
Rated Speed = 100% Spee
60 seconds
100
Inverter Duty Motor designed to
Continuous operation
Torque
148 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Electrothermal
L1-01 Protection
Setting Motor Type Overload Tolerance Cooling Fan Capacity (100% motor
overload)
150
Rated Speed = 100% Sp
60 seconds
100
Motor capable of effective
Vector motor 90
Continuous operation
Operation
01 100 120 167 200
A: Typical maximum speed for Yaskawa motor frame number 200LJ and greater
B: Typical maximum speed for Yaskawa motor frame numbers 160MJ – 180LJ
C: Typical maximum speed for Yaskawa motor frame number 132MHJ or less
D: Typical maximum speed for Yaskawa motor frame number 132MJ or less
4
Notes on Motor Protection
• Motor protection meeting UL and cUL standards is achieved with the motor overload
protection time (L1-02) set to factory default setting. Normally, L1-02 (Motor Overload
Protection Time) does not require setting. If the motor overload tolerance is clear, set the
ovlerload protection time at hot start according to the motor. To detect overload earlier,
decrease the setting.
Note: Figure 4.27 illustrates motor protection operation time characteristics.
Figure 4.27
10
7
3
Cold Start
1
0.4
Hot Start
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 149
4.6 Basic Drive Setup Adjustments
• In the case of a general purpose (standard) motor, the cooling capability is reduced at a
low speed. Motor overload protection (OL1) may occur in frequencies lower than motor
rated current. Use an exclusive-use or inverter-duty motor to operate the drive at rated
current at low frequency.
Step Display/Result
Refer to Parameter List on page 309 for more details about Drive Status Monitors.
Table 4.22 Drive Status Monitors
150 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.6 Basic Drive Setup Adjustments
Operation
U1-14 Terminal A2 Input Voltage 379 U4-03 Cooling Fan Operation Time 383
U1-16 Output Frequency after SoftStart 379 U4-05 Capacitor Maintenance 383
U1-18 oPE Fault 379 U4-07 IGBT Maintenance 383
U1-19 MEMOBUS/Modbus Error Code 380 U4-09 LED Check 384 4
U1-24 Input Pulse Monitor 380 U4-10 kWH, Lower 4 Digits 384
U1-25 Software Number (Flash) 380 U4-11 kWH, Upper 5 Digits 384
U1-26 Software Number (ROM) 380 U4-13 Peak Hold Current 384
U2-01 Current Fault 380 U4-14 Peak Hold Output Frequency 384
U2-02 Previous Fault 380 U4-16 Motor Overload Estimate (OL1) 384
U2-03 Frequency Reference at Previous Fault 380 U4-18 Frequency Reference Selection Results 384
Freq. Ref. from MEMOBUS/Modbus
U2-04 Output Frequency at Previous Fault 380 U4-19 384
Communications
U2-05 Output Current at Previous Fault 380 U4-20 Option Frequency Reference 384
U2-06 Motor Speed at Previous Fault 381 U4-21 Run Command Selection Results 385
U2-07 Output Voltage at Previous Fault 381 U4-22 MEMOBUS/Modbus Comm. Ref. 385
U2-08 DC Bus Voltage at Previous Fault 381 U4-23 Option Card Reference 385
U2-09 Output Power at Previous Fault 381 U5-01 PID Feedback 386
U2-10 Torque Reference at Previous Fault 381 U5-02 PID Input (feedback) 386
U2-11 Input Terminal Status at Previous Fault 381 U5-03 PID Output 386
U2-12 Output Terminal Status at Prev. Fault 381 U5-04 PID Setpoint 386
U2-13 Drive Operation Status at Pre. Fault 381 U6-01 Torque Reference (Internal) 386
Cumulative Operation Time at
U2-14 381 U6-02 Motor Secondary Current (Iq) 386
Previous Fault
Soft Starter Speed Reference at
U2-15 381 U6-03 Motor Excitation Current (ld) 386
Previous Fault
Output of speed control (ASR) (for
U2-16 Motor q-Axis Current at Previous Fault 381 U6-04 386
Simple V/f PG)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 151
4.6 Basic Drive Setup Adjustments
152 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Operation
Power supply voltage 400 V class: 3-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, T/L3).
(for single-phase 200 V class models, wire only R/L1 and S/L2)
Check for proper grounding of drive and motor.
Drive output terminals Properly wire drive output terminals U/T1, V/T2, and W/T3 with motor terminals U, V, 4
and motor terminals and W.
Control circuit terminals Check control circuit terminal connections.
Drive control terminal
Open all control circuit terminals (off).
status
Status of the load and
Uncouple the motor from the load.
connected machinery
■ Status Display
When the power supply to the drive is turned on, the LED operator lights will appear as
follows:
Normal
Operation The data display area displays the frequency reference. flashes.
◆ Auto-Tuning
Auto-Tuning automatically sets and tunes parameters required for motor operation.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 153
4.7 Test Run
■ Types of Auto-Tuning
There are three types of Auto-Tuning. Refer to Auto-Tuning Selection on page 155 to select
the best type of Auto-Tuning for the application.
Note: Auto-Tuning cannot be performed on permanent magnet motors (IPM, SPM, etc.).
154 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
■ Auto-Tuning Selection
Figure 4.28
START
Operation
E1-03
NO Is the total
Will the application
allow motor rotation
Can the load be
disconnected from
connected load
expected to be less 4
than 30% of the motor
for Auto-Tuning? the motor? rating?
YES NO YES NO
YES NOTICE: Auto-Tuning with
Is the cable a connected load is possible,
between the motor but may result in less than
and drive longer optimum performance.
than 50 m?
V/f Rotational
Auto-Tuning
YES NO
(T1-01 = 3)
Rotational Select V/f Control
Auto-Tuning Mode (A1-02 = “0”)
Stationary Auto-Tuning (T1-01 = 0)
for Terminal Resistance Only for the drive.
(T1-01 = 2) Note: Manually set parameters
when OLV control is needed.
Auto-Tuning finished.
Figure 4.28
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 155
4.7 Test Run
WARNING! When Auto-Tuning a motor that is used on an application in conjunction with a brake, take
special precaution to insure the brake stays applied. Auto-Tuning activates the drive multi-function outputs
per the table below. Therefore, a brake may be released while the motor is uncoupled from the load,
resulting in an unsafe condition. Proper precautions must therefore be taken prior to performing Auto-
Tuning.
Note: It is recommended that Rotational Auto-Tuning be performed with the load disconnected.
Failure to comply could result in improper drive operation. If rotational Auto-Tuning is
performed for a motor coupled to a load, the motor constants will be inaccurate and the motor
may exhibit abnormal operation. Disconnect or decouple the motor from the load.
Rotational Auto-Tuning for V/f Control
• Motor rotates during Auto-Tuning.
• Sets parameters required for torque compensation, slip compensation, energy savings, and
speed search.
• Available only when the drive is set for V/f Control.
• Required to perform Estimation-Type Speed Search when using V/f Control.
Rotational Auto-Tuning for Open Loop Vector Control
• Used only when in Open Loop Vector Control.
• Perform only with the motor uncoupled from the load for applications requiring high
performance over a wide speed range.
• Disconnect the load before Auto-Tuning the drive and motor. Performing Rotational
Auto-Tuning with the load connected will set motor parameters incorrectly, and also be
dangerous because irregular motor rotation will occur.
• It is possible to perform Rotational Auto-Tuning with a connected load if the load is less
than 30% of the rated load.
• Ensure a motor-mounted brake is fully released.
156 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
• Connected machinery should not produce enough power to rotate the motor.
Stationary Auto-Tuning for Terminal Resistance Only
• If the motor cable lead length has been significantly modified after Auto-Tuning has
already been performed, perform Stationary Auto-Tuning with the new cables.
• Perform when using motor cables longer than 50 m with V/f Control.
WARNING! Electrical Shock Hazard. When executing stationary Auto-Tuning for line-to-line resistance only,
the motor does not rotate, however, power is applied. Do not touch the motor until Auto-Tuning is completed.
Failure to comply may result in injury from electrical shock.
Operation
interrupt Auto-Tuning.
Refer to Auto-Tuning Errors on page 186 for more information.
Figure 4.29
A B
4
■ Performing Auto-Tuning
The following example illustrates how to perform Rotational Auto-Tuning.
Note: The following example is shown with the drive in Open Loop Vector Control
(A1-02 = 2).
Selecting the Type of Auto-Tuning
Step Display/Result
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 157
4.7 Test Run
Step Display/Result
Step Display/Result
158 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Step Display/Result
Operation
which could result in death or serious injury. Ensure the area surrounding the drive motor and load are clear
before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when stationary Auto-Tuning
is performed even with the motor stopped, which could result in death or serious injury. Do not touch the
motor until Auto-Tuning has been completed.
4
NOTICE: Auto-Tuning will not function properly if a holding brake is engaged on the load. Failure to comply
could result in improper operation of the drive. Ensure the motor can freely spin before beginning Auto-
Tuning.
NOTICE: Never perform rotational Auto-Tuning for a motor connected to a load. Failure to comply could
result in improper drive operation. If rotational Auto-Tuning is performed for a motor coupled to a load, the
motor constants will be inaccurate and the motor may exhibit abnormal operation. Disconnect or decouple
the motor from the load.
Enter the required information from the motor nameplate. Press to proceed to the
Auto-Tuning start screen.
Step Display/Result
After setting T1-07 as illustrated in the previous section, press
1. ⇒
and confirm the display is as follows:
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 159
4.7 Test Run
Control
No. Name Description Range Def. Mode
V/f OLV
Selects which set of motor parameters are set during Auto-
Tuning. If motor 2 selection (H1- =16) is not selected, this
parameter will not be displayed.
Motor
1: Motor 1 - E1 to E2
T1-00 Selection 1, 2 1 A A
2: Motor 2 - E3 to E4. <1> Enabled when motors 1 and 2 are
1/2
switched to each other (H1- =16).
Displayed only when either multi-function contact output H1-
01 through H1-07 is set to 16.
Selects the Auto-Tuning mode.
0: OLV Rotational Auto-Tuning
Auto- 0
2: Terminal resistance only, Stationary Auto-Tuning
Tuning (“2” in
T1-01 3: V/f Rotational Auto-Tuning. 0, 2, 3 A A
Mode V/f
Only settings 2 and 3 are available when using V/f Control.
Selection mode)
Only setting 2 is available when using motor 2.
Settings 0 and 2 are available when using OLV Control.
Sets the motor rated output power. A set value that can provide
Motor
stable control in the open loop control mode ranges from 50 to 0.00 to 0.40
T1-02 Rated A A
100% of the drive rating. In case of motors that operate above 650.00 kW
Power
base speed, set the value at base speed.
Motor Set the motor base voltage according to the information printed
T1-03 0.0 to 200.0
Rated on the motor nameplate. In case of motors that operate above A A
<2> 255.5 V
Voltage base speed, set the value at base speed.
Enter the motor-rated current as specified on the motor
10 to
nameplate. Det. by
Motor 200% of
For best performance when using OLV select the drive so that o2-04
T1-04 Rated drive A A
the motor represents 50 to 100% of the drive rated current. and
Current rated
Enter the current required at base speed for motors with C6-01
current
extended speed ranges.
Motor Enter the motor base frequency as specified on the motor
0.0 to 60.0
T1-05 Base nameplate. Enter the motor base frequency for extended speed A A
400.0 Hz
Frequency range motors.
Number
T1-06 of Motor Enter number of motor poles indicated on motor nameplate. 2 to 48 4 A A
Poles
Motor Sets the base speed of the motor in revolutions per minute r/min
0 to 1750.
T1-07 Base (RPM). Enter the motor base speed for extended speed range A A
24000 r/min
Speed motors.
160 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Control
No. Name Description Range Def. Mode
V/f OLV
Provides iron loss for determining Energy Saving coefficient.
When power is cycled, the value set to E2-10 will appear (the
Motor 0 to
T1-11 motor iron loss). If T1-02 is changed, an initial value for the 14W A −
Iron Loss 65535
motor capacity will appear that is close to the capacity that was
changed.
Operation
Basic motor nameplate data can be used to auto-tune a motor. However, improved
performance can be achieved by using precise data for base voltage and base frequency. If
the base no-load voltage and frequency are known, enter this data when executing auto-
tuning to improve performance.
4
Parameter Normal Settings Precision Tuning
Enter the no-load voltage when the motor is operating at its
T1-03 Enter the motor rated voltage
rated revolutions per minute
Enter the no-load frequency when the motor is operating at its
T1-05 Enter the motor base frequency
rated revolutions per minute
◆ No-Load Operation
This section explains how to operate the drive with the motor uncoupled from the load
during a test run.
■ Before Starting the Motor
Check the following items before operation:
• Ensure the area around the motor is safe.
• Set the proper motor rated current to T1-04 to prevent overheating or other damage from
motor overload.
• Ensure external emergency stop circuitry is working properly and other safety precautions
have been taken.
■ During Operation
Check the following items during operation:
• The motor should rotate smoothly (i.e., no abnormal noise or oscillation).
• The motor should accelerate and decelerate smoothly.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 161
4.7 Test Run
■ Operation Instructions
The following example illustrates a procedure to run the drive using the digital operator.
Note: Before starting the motor, set the frequency reference to 6 Hz. Refer to The Drive and
Programming Modes on page 97 for instructions.
Step Display/Result
Press RUN to give the drive a run command. RUN will light ⇒
STOP
3.
and the motor will rotate at 6 Hz.
Off On
Motor
Forward
162 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Step Display/Result
Note: To operate the drive, run (forward/reverse) command and frequency (or multi-step speed)
reference are needed. Input these commands and references to the drive.
Operation
After performing a no-load test run, connect the motor and proceed to run the load.
■ Notes on Connected Machinery
• Clear the area around the motor. 4
• The motor should come to a complete stop without problems. Connect the machinery.
• Fasten all installation screws properly. Check that the motor and connected machinery are
held in place.
• Confirm that the Fast-stop circuit or mechanical safety operate correctly.
• Prepare to press the STOP button in the case of an emergency.
■ Checklist Before Operation
• The motor should rotate in the proper direction.
• The motor should accelerate and decelerate smoothly.
• Check U1-03 to ensure there is not overcurrent.
If the application permits running the load in the reverse direction, try changing motor
direction and the frequency reference and watch for abnormal motor oscillation or vibration.
Correct the problem if hunting or oscillation occurs or if there are control-related problems.
Refer to Motor Hunting and Oscillation Control Parameters on page 180.
■ Operating the Motor under Loaded Conditions
Test run the application similarly to the no-load test procedure when connecting the
machinery to the motor.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 163
4.7 Test Run
Save the verified parameter settings. Change the access level or set a password to the drive
to prevent accidental modification of parameter settings.
■ Backing Up Parameter Values: o2-03
Performing the following procedure stores all parameters settings to drive memory where
they can later be recalled if necessary. Set o2-03 to “1” to save parameter changes. This
saves all parameter settings, and then returns o2-03 to 0. The drive can now “recall” the
saved parameters by performing a “user-initialization” (A1-03 = 1110).
Parameter Setting
No. Description Default
Name Range
Selects which parameters are accessible via the digital operator.
0: Operation only (A1-01, -04, and -06 can be set and monitored. U
Access
parameters can be monitored)
A1-01 Level 0 to 2 2
1: User Parameters (Only those recently changed among application
Selection
parameters A2-01 to -16 and A2-17 to -32 can be set and monitored)
2: Advanced Access Level (All parameters can be set and monitored)
164 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Operation
Selection The most recently changed parameter is registered in A2-17. The
second most recently changed parameter is registered in A2-18.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 165
4.7 Test Run
Setting Default
No. Name Description Range Setting
Frequency reference when: “Jog Frequency Reference” is
selected via multi-function input terminals. “Jog Frequency
Jog Frequency Reference” has priority over “Multi-Step Speed Reference 1 to 0.00 to
d1-17 6.00 Hz
Reference 16." Parameter d1-17 is also the reference for the JOG key on 400.00
the digital operator, and the multi-function inputs “Forward
Jog” and “Reverse Jog.”
Setting Name
12 FJOG Command (ON: rotates forward at the Jog frequency set to d1-17)
13 RJOG Command (ON: rotates in reverse at the Jog frequency set to d1-17)
Drive
Three-Phase 200 Vac
(400 Vac) R/L1 U/T1
S/L2 V/T2 M
T/L3 W/T3
S7 (FJ0G)
SC
166 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Figure 4.31
6.0 Hz
Output
Frequency
ON
Jog Reference
(FJ0G)
Operation
command).
Step Display/Result
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 167
4.7 Test Run
Step Display/Result
Turn the power on to the drive. The initial display appears.Note: Set
1. ⇒
the drive to REMOTE.
Motor
With multi-function contact input terminal S7 closed, the motor
2. rotates forwards at 6 Hz. ⇒
Note: No run command is necessary when using the Jog frequency.
■ Digital Input
■ Wiring Example
Set up external switches SW1 and SW2.
168 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.7 Test Run
Figure 4.32
Drive
Three-Phase, 200 Vac R/L1 U/T1
(AC400 V)
S/L2 V/T2 M
T/L3 W/T3
SW1 S5
SW2 S6
SC
Freq Ref 4
Frequency
Reference Freq Ref 3
Operation
Freq Ref 2
Freq Ref 1
Forward/Reverse Run/Stop ON
■ Setting Procedure
Step Display/Result
4. turns on. ⇒
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 169
4.7 Test Run
Step Display/Result
5. Press to select LOCAL. The LO/RE light will turn on. ⇒ STOP
Off On
Press RUN to run the motor at 5 Hz. The RUN light will turn
6. ⇒ STOP
on.
Off On
With SW1 open and SW2 closed, the drive runs the motor at
8. ⇒
Multi-Step 3 (50 Hz).
With both SW1 and SW2 closed, the drive runs the motor at
9. ⇒
Multi-Step 4 (60 Hz).
Press STOP to stop the drive. The RUN light will flash until the
10. ⇒ STOP
Flashing Off
<1> When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.
<2> Set H3-10 (Multi-function Analog Input (current) Terminal A2 Function Selection) to “F” (not used).
Note: When a run command is input from the control circuit terminal, the frequency referenc value is
selected as follows: When b1-01 = 0 and the run command is given, the drive uses the frequency
set to d1-01. When b1-01 = 1 and the run command is given, the drive uses the frequency
reference value input to analog control terminal A1.
170 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
4.8 Test Run Checklist
Check the items that correspond to the control mode being used.
Operation
WARNING! Ensure start/stop and safety circuits are wired properly and in the correct state before
energizing the drive. Failure to comply could result in death or serious injury from moving equipment. When
programmed for 3-wire control, a momentary closure on terminal S1 may cause the drive to start.
4
No. Checklist Page
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 171
4.8 Test Run Checklist
172 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5
Troubleshooting
This chapter provides descriptions of the drive faults, alarms,
errors, related displays, and possible solutions. This chapter can
also serve as a reference guide for tuning the drive during a trial
run.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 173
5.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may illustrate drives without covers or safety
shields to display details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
174 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.1 Section Safety
WARNING
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection and servicing must be performed only
by authorized personnel familiar with installation, adjustment and
maintenance of AC drives.
Troubleshooting
Remove all metal objects such as watches and rings, secure loose clothing
and wear eye protection before beginning work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
5
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire
due to overheating of electrical connections.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 175
5.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Check all the wiring after installing the drive and connecting other
devices to ensure that all connections are correct.
Failure to comply could result in damage to the drive.
176 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.2 Motor Performance Fine Tuning
Default Suggested
Problem Parameter No. Countermeasure Value Setting
Troubleshooting
• If insufficient motor torque relative to the
• Motor hunting and Hunting size of the load causes hunting, reduce the
oscillation at speeds Prevention Gain setting. 1.00 0.50 to 2.00
between 10 and 40 Hz (n1-02) • When motor hunting and oscillation occur
with a light load, increase the setting.
• If the motor noise is too loud, increase the
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 177
5.2 Motor Performance Fine Tuning
<1> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using
parmaeter E1-03. The default setting shown is for V/f Control.
Note: Use slip compensation to improve speed precision in V/f Control. First make sure that the proper
values have been set for the motor rated current to E2-01, motor rated slip (E2-02), and motor
no-load current (E2-03). Next, adjust the slip compensation gain set to C3-01 so that it is
between 0.5 to 1.5.
Default Suggeste
Problem Parameter No. Countermeasure
Value d Setting
• Poor motor torque and speed • If motor torque and speed response are too
response slow, gradually decrease the setting by
AFR Gain
• Control motor hunting and 0.05. 1.00 0.50 to 2.00
(n2-01)
oscillation at speeds between • If motor hunting and oscillation occur,
10 and 40 Hz. gradually increase the setting by 0.05.
• To improve motor torque speed response,
gradually reduce this setting by
10 ms and check the performance.
• Poor motor torque and speed • If motor hunting and oscillation occur as a
response AFR Time result of load inertia, gradually increase
50 to 2000
• Control motor hunting and Constant 1 the setting by 50 ms and check the 50 ms
ms
oscillation at speeds between (n2-02) performance. Note: Ensure that n2-02 ≤
10 and 40 Hz. n2-03. When making adjustments to n2-
02, set C4-02 (Torque Compensation
Primary Delay Time Constant 1)
accordingly.
• If overvoltage trips occur, gradually
increase this setting by 50 ms.
• Overvoltage trips when • If response is slow, gradually reduce this
AFR Time
accelerating, decelerating, or setting by 10 ms. Note: Ensure that n2-02 750 to 2000
Constant 2 750 ms
during sudden speed or load ≤ n2-03. When making adjustments to n2- ms
(n2-03)
changes. 03, increase the value of
C4-06 (Torque Compensation Primary
Delay Time 2) proportionally.
• To improve motor torque speed response,
gradually reduce this setting by 2 ms and
Torque
• Poor motor torque and speed check the performance.
Compensation
response • If motor hunting and oscillation occur, 20 ms 20 to 100
Primary Delay
• Motor hunting and gradually increase this setting by 10 ms. <1> ms
Time Constant 1
oscillation. Note: Ensure that C4-02 ≤ C4-06. When
(C4-02)
making adjustments to C4-02, increase n2-
02 (AFR Time Constant) proportionally.
178 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.2 Motor Performance Fine Tuning
Troubleshooting
setting by 10 ms.
(C3-02)
• If speed is too slow, gradually increase the
Slip
setting by 0.1 ms. 1.0
• Poor speed precision Compensation 0.5 to 1.5
• If speed is too fast, gradually decrease the <1>
Gain (C3-01)
setting by 0.1 ms.
• If there is too much motor noise, the
• Motor noise Carrier
carrier frequency is too high.
• If motor hunting and oscillation occur at
7
0 to the
5
• Control motor hunting and Frequency (Swing
low speeds, reduce the carrier frequency. default
oscillation occur at speeds Selection PWM
• The default setting for the carrier setting
below 10 Hz. (C6-02) 1)
frequency depends on the drive capacity
(o2-04) and Drive Duty Selection (C6-01).
• If motor torque and speed response are too
slow, increase the setting. E1-08:
Mid Output • If the motor exhibits excessive instability 12.0 V
• Poor motor torque at low
Voltage A at start-up, reduce the setting. Note: The
speeds
(E1-08) default value is for 200 V class units. <1>
• Poor speed response Initial ±2 V
Minimum Double this value when using a 400 V E1-10:
• Motor instability at motor
Output Voltage class drive. When working with a 2.5 V
start.
(E1-10) relatively light load, increasing this value
too much can create an excessively high of <1>
a torque reference.
<1> Default settings change when the Control Method is changed (A1-02) or a different V/f pattern is selected using
parmaeter E1-03. The default setting shown is for V/f Control.
When using OLV Motor Control, leave the torque compensation gain (C4-01) at its default
setting of 1.00. To increase speed precision during regeneration in OLV Motor Control,
enable slip compensation during regeneration (C3-04 = “1”).
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 179
5.2 Motor Performance Fine Tuning
180 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.3 Drive Alarms, Faults, and Errors
Troubleshooting
Table 5.4 contains descriptions of the various types of alarms, faults, and errors that may
occur while operating the drive.
Contact Yaskawa in the event of drive failure.
Table 5.4 Types of Alarms, Faults, and Errors
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 181
5.3 Drive Alarms, Faults, and Errors
Option Communication
bUS 187 CPF22 A/D Conversion Error 190
Error
MEMOBUS/Modbus
CE 187 CPF23 PWM Feedback Data Fault 191
Communication Error
CPF02 A/D Conversion Error 188 EF0 Option Card External Fault 191
EF1
to External Fault
CPF03 PWM Data Fault 188 to 192
(input terminal S1 to S7)
EF7
Drive specification
mismatch during Terminal
CPF06 189 FbH Excessive PID Feedback 192
Board or Control Board
replacement
Terminal Board
CPF07 189 FbL PID Feedback Loss 193
Communication Fault
EEPROM Serial
CPF08 189 GF Ground Fault 193
Communications Fault
182 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.3 Drive Alarms, Faults, and Errors
CPF12 FLASH Memory Fault 189 LF2 Output Open Phase 194
Watchdog Circuit
CPF13 189 oC Overcurrent 194
Exception
CPF14 Control Circuit Fault 190 oFA00 Option Card Fault (port A) 195
PG Disconnect
CPF18 Control Circuit Fault 190 PGo 202
(for Simple V/f with PG)
Troubleshooting
CPF19 Control Circuit Fault 190 rH Dynamic Braking Resistor 202
Dynamic Braking
RAM Fault 190 rr 203
Transistor
Too Many Speed Search
CPF20 FLASH Memory Fault 190 SEr
Restarts
203
or or
CPF21 Watchdog Circuit
Exception
190 STO Pull-Out Detection 203
5
Clock Fault 190 UL3 Undertorque Detection 1 203
oL3 Overtorque Detection 1 199 Uv3 Soft Charge Circuit Fault 205
Overspeed
oL4 Overtorque Detection 2 199 oS 200
(for Simple V/f with PG)
Mechanical Weakening
oL5 199 ov Overvoltage 200
Detection 1
Note: If faults CPF11 through CPF19 occur, the LED operator will display or .
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 183
5.3 Drive Alarms, Faults, and Errors
Minor Fault
LED Operator Display Name Output Page
(H2- = 10)
dEv Excessive Speed Deviation (for Simple V/f with PG) YES 208
EF1
to
to External Fault (input terminal S1 to S7) YES 209
EF7
184 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.3 Drive Alarms, Faults, and Errors
Minor Fault
LED Operator Display Name Output Page
(H2- = 10)
Troubleshooting
oS Overspeed (for Simple V/f with PG) YES 213
■ Operation Errors
Table 5.6 Operation Error Displays
oPE01 Drive kVA Setting Error 217 oPE08 Parameter Selection Error 220
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 185
5.3 Drive Alarms, Faults, and Errors
■ Auto-Tuning Errors
Table 5.7 Auto-Tuning Error Displays
Er-03 STOP button Input 222 Er-12 Current Detection Error 224
Line-to-Line Resistance
Er-04 223 End1 Excessive V/f Setting 224
Error
Motor Iron Core Saturation
Er-05 No-Load Current Error 223 End2 224
Coefficient Error
Er-08 Rated Slip Error 223 End3 Rated Current Setting Alarm 225
186 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
• Check for faulty wiring.
The communication cable is faulty • Correct the wiring.
or a short circuit exists. • Check for loose wiring and short circuits. Repair as needed.
• Check the various options available to minimize the effects of noise.
• Counteract noise in control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise and
A communications data error use surge suppressors if required.
occurred due to noise. • Use cables recommended by Yaskawa or another type of shielded line.
Ground the shield on the controller side or on the drive input power side.
5
• Separate all wiring for communications devices from drive input power lines.
Install a noise filter to the input side of the drive input power.
• Replace the option card if there are no problems with the wiring and the error
The option card is damaged.
continues to occur.
• The connector pins on the option card are not properly lined up with the
The option card is not properly
connector pins on the drive.
connected to the drive.
• Reinstall the option card.
LED Operator Display Fault Name
MEMOBUS/Modbus Communication Error
CE
Control data was not received for the CE detection time set to H5-09.
Cause Possible Solution
• Check for faulty wiring.
Faulty communications wiring, or a
• Correct the wiring.
short circuit exists.
• Check for loose wiring and short circuits. Repair as needed.
• Check the various options available to minimize the effects of noise.
• Counteract noise in control circuit, main circuit, and ground wiring.
• Ensure that other equipment such as switches or relays do not cause noise and
A communications data error use surge suppressors if required.
occurred due to noise. • Use Yaskawa-recommended cables, or another type of shielded line. Ground
the shield on the controller side or on the drive input power side.
• Separate all wiring for communications devices from drive input power lines.
Install a noise filter to the input side of the drive input power.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 187
5.4 Fault Detection
188 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
Cause Possible Solution
There is a fault connection between
the terminal board and control Turn the power off and reconnect the control circuit terminals.
board.
LED Operator Display Fault Name
EEPROM Serial Communication Fault
CPF08
EEPROM communications are not functioning properly. 5
Cause Possible Solution
Terminal board or control board is
Turn the power off and check the control terminal connections.
not connected properly.
LED Operator Display Fault Name
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 189
5.4 Fault Detection
190 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
Cause Possible Solution
Hardware is damaged. Replace the drive.
LED Operator Display Fault Name
Speed Deviation (for Simple V/f with PG)
dEv According to the pulse input (RP), the speed deviation is greater than the
Cause
setting in F1-10 for longer than the time set to F1-11.
Possible Solution
5
Load is too heavy. Reduce the load.
Acceleration and deceleration times
Increase the acceleration and deceleration times (C1-01 through C1-08).
are set too short.
The load is locked up. Check the machine.
Parameters are not set appropriately. Check the settings of parameters F1-10 and F1-11.
Motor brake engaged. Ensure the motor brake releases properly.
LED Operator Display Fault Name
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 191
5.4 Fault Detection
192 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
Wiring for PID feedback is
Correct the wiring.
incorrect.
There is a problem with the Check the sensor on the controller side.
feedback sensor. If damaged, replace the sensor.
LED Operator Display Fault Name
Ground Fault
GF • Current shorted to ground exceeded 50% of rated current on output side of the 5
drive.
• Setting L8-09 to 1 enables ground fault detection in models 5.5 kW or larger.
Cause Possible Solution
• Check the insulation resistance of the motor.
Motor insulation is damaged.
• Replace the motor.
• Check the motor cable.
A damaged motor cable is creating a • Remove the short circuit and turn the power back on.
short circuit. • Check the resistance between the cable and the ground terminal .
• Replace the cable.
The leakage current at the drive • Reduce the carrier frequency.
output is too high. • Reduce the amount of stray capacitance.
• The value set exceeds the allowable setting range while the drive
automatically adjusts the current offset (this happens only attempting to
The drive started to run during
restart a PM motor that is coasting to stop).
Current Offset Fault or while
• Enable Speed Search at start (b3-01 = 1).
coasting to a stop.
• Perform Speed Search 1 or 2 (H1-xx = 61 or 62) via one of the external
terminals. Note: Speed Search 1 and 2 are the same when using PM OLV.
Hardware problem. • Replace the drive.
LED Operator Display Fault Name
Output Phase Loss
LF • Phase loss on the output side of the drive.
• Phase Loss Detection is enabled when L8-07 is set to “1” or “2”.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 193
5.4 Fault Detection
194 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
• Calculate the torque needed during acceleration relative to the load inertia and
the specified acceleration time.
The acceleration or deceleration • If the right amount of torque cannot be set, make the following changes:
times are too short. • Increase the acceleration time (C1-01, -03, -05, -07)
• Increase the S-curve characteristics (C2-01 through C2-04)
• Increase the capacity of the drive.
The drive is attempting to operate a • Check the motor capacity.
specialized motor or a motor larger • Ensure that the rated capacity of the drive is greater than or equal to the
than the maximum size allowed. capacity rating found on the motor nameplate.
Magnetic contactor (MC) on the
Set up the operation sequence so that the MC is not tripped while the drive is
output side of the drive has turned
outputting current.
on or off.
• Check the ratios between the voltage and frequency.
V/f setting is not operating as • Set parameter E1-04 through E1-10 appropriately. Set E3-04 through E3-10
expected. when using a second motor.
Troubleshooting
• Lower the voltage if it is too high relative to the frequency.
• Check the amount of torque compensation.
Excessive torque compensation. • Reduce the torque compensation gain (C4-01) until there is no speed loss and
less current.
• Review the possible solutions provided for handling noise interference.
Drive fails to operate properly due to
• Review the section on handling noise interference and check the control
noise interference.
circuit lines, main circuit lines and ground wiring.
• Check if fault occurs simultaneously to overexcitation function operation. 5
Overexcitation gain is set too high. • Consider motor flux saturation and reduce the value of n3-13 (Overexcitation
Deceleration Gain).
• Enable Speed Search at start (b3-01 = “1”).
Run command applied while motor
• Program the Speed Search command input through one of the multi-function
was coasting.
contact input terminals (H1- = “61” or “62”).
The wrong motor code has been
entered for PM Open Loop Vector Enter the correct motor code to E5-01 to indicate that a PM motor is connected.
(Yaskawa motors only).
• Check which motor control method the drive is set to (A1-02).
The motor control method and
• For IM motors, set A1-02 = “0” or “2”.
motor do not match.
• For PM motors, set A1-02 = “5”.
The motor cable is too long. Use a larger drive.
LED Operator Display Fault Name
Option Card Fault (Port A)
oFA00
The option card is incompatible with the drive.
Cause Possible Solution
The option card is incompatible with
Use a compatible option card.
the drive.
LED Operator Display Fault Name
Option Card Fault (Port A)
oFA01
Replace the option card.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 195
5.4 Fault Detection
196 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve
reducing E1-08 and E1-10.
Motor has overheated • Be careful not to lower E1-08 and E1-10 excessively, as this reduces load
tolerance at low speeds.
• Check the motor-rated current.
• Enter the motor-rated current as indicated on the motor nameplate (E2-01). 5
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
LED Operator Display Fault Name
Motor Overheat Fault (PTC Input)
oH4 • The motor overheat signal to analog input terminal A1 or A2 exceeded the
alarm detection level.
• Detection requires that multi-function analog input H3-02 or H3-10 = “E”.
Cause Possible Solution
• Check the size of the load, the accel/decel times and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve
reducing E1-08 and E1-10.Be careful not to lower E1-08 and E1-10
Motor has overheated.
excessively because this reduces load tolerance at low speeds
• Check the motor-rated current.
• Enter the motor-rated current as indicated on the motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.
LED Operator Display Fault Name
Motor Overload
oL1
The electrothermal sensor tripped overload protection.
Cause Possible Solution
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 197
5.4 Fault Detection
198 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Cycle times are too short during Increase the settings for the acceleration and deceleration times (C1-01
acceleration and deceleration. through C1-08).
• Adjust the preset V/f pattern (E1-04 through E1-10). This will mainly involve
Voltage is too high for the V/f reducing E1-08 and E1-10.
characteristics. • Be careful not to lower E1-08 and E1-10 excessively because this reduces
load tolerance at low speeds.
Drive capacity is too small. Replace the drive with a larger model.
• Reduce the load when operating at low speeds.
Overload occurred when operating
• Replace the drive with a model that is one frame size larger.
at low speeds.
• Lower the carrier frequency (C6-02).
Reduce the torque compensation gain (C4-01) until there is no speed loss but
Excessive torque compensation.
less current.
• Check the settings for all Speed Search related parameters.
• Adjust the current used during Speed Search and the Speed Search
Speed Search related parameters are
Troubleshooting
deceleration time (b3-03 and b3-02 respectively).
not set correctly.
• After Auto-Tuning the drive, enable the Speed Search Estimation Type
(b3-24 = “1”).
Output current fluctuation due to
Check the power supply for phase loss.
input phase loss.
LED Operator Display Fault Name
Overtorque Detection 1
oL3 The current has exceeded the value set for torque detection (L6-02) for longer
5
than the allowable time (L6-03).
Cause Possible Solution
Parameter settings are not
Check the settings of parameters L6-02 and L6-03.
appropriate for the type of load.
There is a fault on the machine side Check the status of the load.
(e.g., the machine is locked up). Remove the cause of the fault.
LED Operator Display Fault Name
Overtorque Detection 2
oL4 The current has exceeded the value set for Overtorque Detection 2 (L6-05) for
longer than the allowable time (L6-06).
Cause Possible Solution
Parameter settings are not
Check the settings of parameters L6-05 and L6-06.
appropriate for the type of load.
There is a fault on the machine side Check the status of the load.
(e.g., the machine is locked up). Remove the cause of the fault.
LED Operator Display Fault Name
High-Slip Braking OL
oL7 The output frequency stayed constant for longer than the time set in n3-04
during High-slip Braking.
Cause Possible Solution
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 199
5.4 Fault Detection
200 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
fault restart.)
Estimation Type Speed Search (b3-24 = “1”).
Excessive regeneration when Enable the Overvoltage Suppression function (L3-11 = “1”).
overshoot occurs after acceleration. Lengthen the S-curve at acceleration end.
Drive input power voltage is too • Check the voltage.
high. • Lower drive input power voltage within the limits listed in the specifications.
The dynamic braking transistor is
damaged.
Replace the drive.
5
The braking transistor is wired • Check braking transistor wiring for errors.
incorrectly. • Properly rewire the braking resistor device.
• Review the list of possible solutions provided for controlling noise.
Drive fails to operate properly due to
• Review the section on handling noise interference and check the control
noise interference.
circuit lines, main circuit lines and ground wiring.
• Check the load inertia settings when using KEB, overvoltage suppression or
Load inertia has been set incorrectly. Stall Prevention during deceleration.
• Adjust L3-25 (Load Inertia Ratio) in accordance with the load.
Braking function is being used in
Connect a braking resistor.
PM Open Loop Vector Control.
• Adjust the parameters that control hunting.
• Set the hunting prevention gain (n1-02).
Motor hunting occurs. • Adjust the AFR time constant (n2-02 and n2-03) when in OLV Control.
• Use parameters n8-45 (PM Speed Feedback Detection Suppression Gain) and
n8-47 (Pull-In Current Compensation Time Constant).
LED Operator Display Fault Name
Input Phase Loss
PF Drive input power has an open phase or has a large imbalance of voltage
between phases. Detected when L8-05 = 1 (enabled).
Cause Possible Solution
There is phase loss in the drive input • Check for wiring errors in the main circuit drive input power.
power. • Correct the wiring.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 201
5.4 Fault Detection
202 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Note: The magnitude of the braking load trips the braking resistor overheat alarm, NOT the surface temperature.
Using the braking resistor more frequently than its rating trips the alarm even when the braking resistor surface is not
very hot.
LED Operator Display Fault Name
Dynamic Braking Transistor
rr
The built-in dynamic braking transistor failed.
Cause Possible Solution
The braking transistor is damaged. • Cycle power to the drive and check if the fault reoccurs. Refer to Diagnosing
and Resetting Faults on page 226.
The control circuit is damaged. • Replace the drive if the fault continues.
LED Operator Display Fault Name
Too Many Speed Search Restarts
SEr
The number of speed search restarts exceeded the number set to b3-19.
Troubleshooting
Cause Possible Solution
• Reduce the detection compensation gain during Speed Search (b3-10).
Speed Search parameters are set to • Increase the current level when attempting Speed Search (b3-17).
the wrong values. • Increase the detection time during Speed Search (b3-18).
• Repeat Auto-Tuning.
The motor is coasting in the opposite
Enable Bi-directional Speed Search (b3-14 = “1”).
direction of the run command.
LED Operator Display Fault Name
5
Pull-Out Detection
STO
Motor pull-out has occurred.
Cause Possible Solution
• Enter the correct motor code for the PM being used into E5-01.
The wrong motor code has been set
• For special-purpose motors, enter the correct data to all E5 parameters
(Yaskawa motors only).
according to the Test Report provided for the motor.
• Increase the value set to n8-55 (Load Inertia for PM).
• Increase the value set to n8-51 (Pull-In Current during Accel/Decel for PM).
Load is too heavy.
• Reduce the load.
• Increase the motor or drive capacity.
Load inertia is too heavy. Increase n8-55 (Load Inertia for PM).
Acceleration and deceleration times • Increase the acceleration and deceleration times (C1-01 through C1-08).
are too short. • Increase the S-curve acceleration and deceleration times (C2-01).
LED Operator Display Fault Name
Undervoltage Detection 1
UL3 The current has fallen below the minimum value set for torque detection
(L6-02) for longer than the allowable time (L6-03).
Cause Possible Solution
Parameter settings are not
Check the settings of parameters L6-02 and L6-03.
appropriate for the type of load.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 203
5.4 Fault Detection
There is a fault on the machine side. Check the load for any problems.
LED Operator Display Fault Name
Undertorque Detection 2
UL4 The current has fallen below the minimum value set for torque detection
(L6-05) for longer than the allowable time (L6-06).
Cause Possible Solution
Parameter settings are not
Check the settings of parameters L6-05 and L6-06.
appropriate for the type of load.
There is a fault on the machine side. Check the load for any problems.
LED Operator Display Fault Name
Mechanical Weakening Detection 2
UL5
The operation conditions matched the conditions set to L6-08.
Cause Possible Solution
Undertorque was detected and
matched the condition of mechanical
Check the load side for any problems.
loss detection operation selection
(L6-08).
LED Operator Display Fault Name
DC Bus Undervoltage
One of the following conditions occurred while the drive was stopped:
• Voltage in the DC bus fell below the undervoltage detection level (L2-05).
Uv1 • For 200 V class: approximately 190 V (160 V for single phase drives)
• For 400 V class: approximately 380 V (350 V when E1-01 is less then 400)
The fault is output only if L2-01 = 0 or L2-01 = 1 and the DC bus voltage is
under L1-05 for longer than L2-02.
Cause Possible Solution
• The main circuit drive input power is wired incorrectly.
Input power phase loss.
• Correct the wiring.
• Ensure there are no loose terminals.
One of the drive input power wiring
• Apply the tightening torque specified in this manual to fasten the terminals.
terminals is loose.
Refer to Wire Size and Torque Specifications on page 72
There is a problem with the voltage • Check the voltage.
from the drive input power. • Correct the voltage to within range listed in drive input power specifications.
The power has been interrupted. Correct the drive input power.
Drive internal circuitry has become • Check the maintenance time for the capacitors (U4-05).
worn. • Replace the drive if U4-05 exceeds 90%.
The drive input power transformer is
not large enough and voltage drops Check the capacity of the drive input power transformer.
after switching on power.
Air inside the drive is too hot. Check the drive’s internal temperature.
Problem with the CHARGE
Replace the drive.
indicator.
204 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.4 Fault Detection
Troubleshooting
Undervoltage 3 (Inrush Prevention Circuit Fault)
Uv3
The inrush prevention circuit has failed.
Cause Possible Solution
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
The contactor on the inrush
• Check monitor U4-06 for the performance life of the inrush prevention
prevention circuit is damaged.
circuit.
• Replace the drive if U4-06 exceeds 90%. 5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 205
5.5 Alarm Detection
206 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.5 Alarm Detection
Troubleshooting
Minor Fault (H2-
Cause Possible Solutions
= 10)
Communications wiring is
• Check for wiring errors.
faulty, there is a short circuit,
• Correct the wiring. YES
or something is not connected
• Remove and ground shorts and reconnect loose wires.
properly.
Programming error on the
master side.
Check communications at start-up and correct programming
errors.
YES 5
Communications circuitry is • Perform a self-diagnostics check.
YES
damaged. • Replace the drive if the fault continues to occurs.
The terminal slave drive must have the internal terminal
Terminal resistance setting is resistance switch set correctly. Place DIP switch S2 to the ON
YES
incorrect. position. Refer to MEMOBUS/Modbus Switch Settings on
page 407.
LED Operator Display Minor Fault Name
MEMOBUS/Modbus Communication Error
CE
Control data was not received correctly for two seconds.
Minor Fault (H2-
Cause Possible Solutions
= 10)
• Check options available to minimize the effects of noise.
• Counteract noise in the control circuit wiring, main circuit lines
and ground wiring.
• Reduce noise on the controller side.
• Use surge absorbers on magnetic contactors or other equipment
A data error occurred due to causing the disturbance.
YES
noise. • Use cables recommended by Yaskawa or another type of
shielded line. The shield should be grounded on the controller
side or on the drive input power side.
• Separate all wiring for communications devices from drive
input power lines. Install a noise filter to the input side of the
drive input power.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 207
5.5 Alarm Detection
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
“Drive Enable” is set to a
multi-function contact input
Check the operation sequence. YES
(H1- = 6A) and that
signal was switched off.
LED Operator Display Minor Fault Name
Forward/Reverse Run Command Input Error
EF
Both forward run and reverse run closed simultaneously for over 0.5 s.
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
208 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.5 Alarm Detection
Troubleshooting
There is a problem with the
Check the PLC program and correct problems. YES
PLC program.
LED Operator Display Minor Fault Name
External fault (input terminal S1)
EF1
External fault at multi-function input terminal S1.
External fault (input terminal S2)
EF2
External fault at multi-function input terminal S2. 5
External fault (input terminal S3)
EF3
External fault at multi-function input terminal S3.
External fault (input terminal S4)
EF4
External fault at multi-function input terminal S4.
LED Operator Display Minor Fault Name
External fault (input terminal S5)
EF5
External fault at multi-function input terminal S5.
External fault (input terminal S6)
EF6
External fault at multi-function input terminal S6.
External fault (input terminal S7)
EF7
External fault at multi-function input terminal S7.
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
An external device has Remove the cause of the external fault and reset the
YES
tripped an alarm function. multi-function input value.
• Ensure the signal lines have been connected properly to the
terminals assigned for external fault detection
Wiring is incorrect. YES
(H1- = 20 to 2F).
• Reconnect the signal line.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 209
5.5 Alarm Detection
210 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.5 Alarm Detection
Troubleshooting
(H2- = 10)
• Measure the current flowing through the motor.
Load is too heavy. YES
• Reduce the load or increase the capacity of the drive.
• Calculate the torque required during acceleration and for the
inertia moment.
• If the torque level is not right for the load, take the following
Acceleration and deceleration
steps: YES
times are too short.
• Increase the acceleration and deceleration times 5
(C1-01 through C1-08).
• Increase the capacity of the drive.
A special-purpose motor is
being used, or the drive is • Check the motor capacity.
attempting to run a motor • Use a motor appropriate for the drive. Ensure the motor is YES
greater than the maximum within the allowable capacity range.
allowable capacity.
The current level increased
due to Speed Search after a
The alarm will appear only briefly. There is no need to take
momentary power loss or YES
action to prevent the alarm from occurring in such instances.
while attempting to perform a
fault restart.
LED Operator Display Minor Fault Name
Heatsink Overheat
oH
The temperature exceeded the maximum allowable value.
Minor Fault (H2-
Cause Possible Solutions
= 10)
• Check the surrounding temperature.
Surrounding temperature is • Improve the air circulation within the enclosure panel.
YES
too high • Install a fan or air conditioner to cool surrounding area.
• Remove anything near drive that may cause extra heat.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 211
5.5 Alarm Detection
212 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.5 Alarm Detection
Overtorque 1
oL3 Drive output current (or torque in OLV) was greater than L6-02 for longer than the
time set in L6-03.
Minor Fault (H2-
Cause Possible Solutions
= 10)
Inappropriate parameter
Check parameters L6-02 and L6-03. YES
settings.
There is a fault on the
• Check the status of the machine.
machine side (e.g., the YES
• Remove the cause of the fault.
machine is locked up).
LED Operator Display Minor Fault Name
Overtorque 2
oL4 Drive output current (or torque in OLV) was greater than L6-05 for longer than the
time set in L6-06.
Troubleshooting
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
Parameter settings are not
Check parameters L6-05 and L6-06. YES
appropriate.
There is a fault on the
machine side (e.g., the
• Check the status of the machine being used.
• Remove the cause of the fault.
YES 5
machine is locked up).
LED Operator Display Minor Fault Name
Overspeed (for Simple V/f with PG)
oS
Pulse input (RP) indicates that motor speed feedback exceeded F1-08 setting.
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
• Adjust the gain by using the pulse train input parameters (H6-
02 through H6-05).
Overshoot or undershoot is
Adjust the speed feedback accuracy. YES
occurring.
• Increase the settings for C5-01 (Speed Control Proportional
Gain 1) and reduce C5-02 (Speed Control Integral Time 1).
PG pulse settings are Set the H6-02 (Pulse Train Input Scaling) = 100%, the number
YES
incorrect. of pulses during maximum motor revolutions.
Parameter settings are Check the setting for the overspeed detection level and the
YES
inappropriate. overspeed detection time (F1-08 and F1-09).
LED Operator Display Minor Fault Name
DC Bus Overvoltage
ov The DC bus voltage exceeded the trip point.
For 200 V class: approximately 410 V
For 400 V class: approximately 820 V (740 V when E1-01 < 400)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 213
5.5 Alarm Detection
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
MEMOBUS/Modbus test has
This verifies that the test was successful. No output
finished normally.
LED Operator Display Minor Fault Name
PG Disconnect (for Simple V/f with PG)
PGo
Detected when no PG pulses received for a time longer than setting in F1-14.
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
Pulse input (RP) is
Reconnect the pulse input (RP). YES
disconnected.
Pulse input (RP) wiring is
Correct the wiring. YES
wrong.
Motor brake is engaged. Ensure the brake releases properly YES
LED Operator Display Minor Fault Name
Motor Switch during Run
rUn
A command to switch motors was entered during run.
Minor Fault
Cause Possible Solutions Output
(H2- = 10)
214 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.5 Alarm Detection
A motor switch command was Change the operation pattern so that the motor switch command
YES
entered during run. is entered while the drive is stopped.
LED Operator Display Minor Fault Name
Fault Reset when Run Command Entered
rUnC
Fault reset was being executed when a run command was entered.
Minor Fault (H2-
Cause Possible Solutions
= 10)
Fault reset was being • Ensure that a run command cannot be entered from the external
executed when a run terminals or option card during fault reset. YES
command was entered. • Turn off the run command.
LED Operator Display Minor Fault Name
Undertorque Detection 1
UL3
Drive output current (or torque in OLV) less than L6-02 for longer than L6-03 time.
Troubleshooting
Minor Fault (H2-
Cause Possible Solutions
= 10)
Inappropriate parameter
Check parameters L6-02 and L6-03. YES
settings.
Load has dropped or
• Check for broken parts in the transmission system. YES
decreased significantly.
LED Operator Display Minor Fault Name 5
Undertorque Detection 2
UL4
Drive output current (or torque in OLV) less than L6-05 for longer than L6-06 time.
Minor Fault (H2-
Cause Possible Solutions
= 10)
Inappropriate parameter
Check parameters L6-05 and L6-06. YES
settings.
The load has dropped or
• Check for broken parts in the transmission system. YES
decreased significantly.
LED Operator Display Minor Fault Name
Undervoltage
• One of the following conditions was true when the drive was stopped and a run
command was entered:
Uv • DC bus voltage dropped below the level specified in L2-05.
• Contactor to suppress inrush current in the drive was open.
• Low voltage in the control drive input power. This alarm outputs only if L2-01 is
not 0 and DC bus voltage is under L2-05.
Minor Fault (H2-
Cause Possible Solutions
= 10)
Phase loss in the drive input Check for wiring errors in the main circuit drive input power.
YES
power. Correct the wiring.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 215
5.5 Alarm Detection
216 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.6 Operator Programming Errors
Troubleshooting
Drive Capacity Setting Fault
oPE01
Drive capacity and then value set to o2-04 do not match.
Cause Possible Solutions
The drive capacity setting
(o2-04) and the actual capacity of the drive are not the Correct the value set to o2-04.
same.
LED Operator Display Error Name
5
Parameter Range Setting Error
oPE02 Use U1-18 to find which parameters were set outside the
setting range.
Cause Possible Solutions
Parameters were set outside the possible setting range. Set parameters to the proper values.
Note: Other errors are given precedence over oPE02 when multiple errors occur at the same time.
LED Operator Display Error Name
Multi-Function Input Selection Error
oPE03 A contradictory setting is assigned to multi-function
contact inputs H1-01 through to H1-07.
Cause Possible Solutions
• Ensure all multi-function inputs are assigned to different
• The same function is assigned to two multi-function
functions.
inputs.
• Re-enter the multi-function settings to ensure this does
• Excludes “Not used” and “External Fault.”
not occur.
The Up command was set but the Down command was
not, or vice versa (settings 10 vs. 11). Correctly set functions that need to be enabled in
The Up 2 command was set but the Down 2 command combination with other functions.
was not, or vice versa (settings 75 vs. 76).
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 217
5.6 Operator Programming Errors
218 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.6 Operator Programming Errors
Troubleshooting
The Run command is assigned to an option card
(b1-02 = 3) that is not connected to the drive.
Frequency reference is assigned to the pulse train input
(b1-01 = 4), but terminal RP is not set for pulse train input Set H6-01 to “0”.
(H6-01 is greater than 0).
LED Operator Display Error Name
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function
5
oPE07
analog inputs H3-02 through to H3-10 and PID functions
conflict.
Cause Possible Solutions
Change the settings to H3-02 and H3-10 so that functions
no longer conflict. Note: Both 0 (primary analog
H3-02 and H3-10 are set to the same value.
frequency reference) and F (Not Used) can be set to
H3-02 and H3-10 at the same time.
The following simultaneous contradictory settings:
H3-02 or H3-10 = B (PID Feedback)
H6-01 (Pulse Train Input) = 1 (PID Feedback)
The following simultaneous contradictory settings:H3-02
or H3-10 = C (PID Target Value)
H6-01 = 2 (pulse train input sets the PID target value)
Disable one of the PID selections.
The following simultaneous contradictory settings:H3-02
or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
The following simultaneous contradictory settings:H6-01
or H3-10 = C (PID Target Value)
b5-18 = 1 (enables b5-19 as the target PID value)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 219
5.6 Operator Programming Errors
220 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.6 Operator Programming Errors
Troubleshooting
Upper and lower limits between C6-02 and C6-05
contradict each other.
Pulse Monitor Selection Error
oPE13 Incorrect setting of monitor selection for Pulse Train
(H6-06) .
Cause Possible Solutions
Scaling for the Pulse Train
monitor is set to 0 (H6-07 = Change scaling for the Pulse Train monitor or set H6-06
5
0) while H6-06 is not set to to 101, 102, 105, or 116..
101, 102, 105, or 116.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 221
5.7 Auto-Tuning Fault Detection
The wiring is faulty. • Check the wiring and correct defective connections.
• Check around the machine.
• Check the load.
Load is too heavy.
• Use the information on page 237 to find out what caused the problem.
LED Operator Display Error Name
222 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.7 Auto-Tuning Fault Detection
Troubleshooting
LED Operator Display Error Name
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 223
5.7 Auto-Tuning Fault Detection
Torque limit when motoring is • Check the settings of parameters L7-01 and L7-02).
too low (L7-01 and L7-02). • Increase the setting.
LED Operator Display Error Name
224 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.7 Auto-Tuning Fault Detection
Troubleshooting
5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 225
5.8 Diagnosing and Resetting Faults
226 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.8 Diagnosing and Resetting Faults
Troubleshooting
4. Press and > until U2-02 (Fault History) is displayed. ⇒
Drive
Close then open the fault signal
Resetting via Fault Reset Fault Reset Switch
digital input via terminal S4. S4 is set S4 Fault Reset Digital Input
Digital Input S4
fault reset as default (H1-04 = 12) SC Digital Input Common
ON
If the above methods do not reset the fault, turn off the drive main
power supply. Reapply power after LED operator display is out.
OFF
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 227
5.9 Troubleshooting without Fault Display
228 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Troubleshooting
Set b1-02 so that it corresponds with the correct run command source.
Settings are incorrect for the source that 0: LED/LCD operator
provides the run command. 1: Control circuit terminal (default setting)
2: MEMOBUS/Modbus communications
3: Option card
• Check for a short-circuit between terminals H1 and HC.
One of the Safety Inputs is open. • See if one of the Safety Inputs is open.
• Correct any faulty wiring. 5
• Check the wiring for the control terminal.
There is faulty wiring in the control
• Correct wiring mistakes.
circuit terminals.
• Check the input terminal status monitor (U1-10).
Check parameter b1-01 (Frequency Reference Selection 1).
Set b1-01 to the correct source of the frequency reference.
The drive has been set to accept the 0: LED operator
frequency reference from the incorrect 1: Control circuit terminal (default setting)
source. 2: MEMOBUS/Modbus communications
3: Option card
4: Pulse train input (RP)
The terminal set to accept the main speed
Check DIP switch S1. Next assign the correct input level to terminal A2
reference is set to the incorrect voltage
(H3-09). Refer to Terminal A2 Switch on page 79.
and/or current.
Selection for the sink/source mode is Check DIP switch S3. Refer to Sinking/Sourcing Mode Switch on
incorrect. page 77.
• Check the frequency reference monitor (U1-01).
Frequency reference is too low. • Increase the frequency by changing the maximum output frequency
(E1-09).
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 229
5.9 Troubleshooting without Fault Display
230 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
1
The forward direction for the motor is
set-up incorrectly.
2
• 1. Forward Rotating Motor (looking down the motor shaft)
2. Motor Shaft
The motor is running at almost 0 Hz and
• Disable bi-directional search (b3-14 = “0”) so that Speed Search is
the Speed Search estimated the speed to
performed only in the specified direction.
be in the opposite direction.
Troubleshooting
Note: Check the motor specifications for the forward and reverse directions. The motor specifications
will vary depending on the manufacturer of the motor.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 231
5.9 Troubleshooting without Fault Display
232 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Troubleshooting
• Check the maximum output frequency (E1-04).
• Increase E1-04 if it is set too low.
Check U1-01 for proper frequency reference.
Frequency reference is too low.
Check if a frequency reference signal switch has been set to one of the
multi-function input terminals.
Check for low gain level set to terminals A1 or A2 (H3-03, H3-11).
• Reduce the load so that the output current remains within the
motor-rated current. 5
Load is too heavy. • In extruder and mixer applications, the load will sometimes increase as
the temperature drops.
Check if the mechanical brake is fully releasing as it should.
• Check the torque limit setting. It may be too low. (L7-01 through L7-
The torque limit function is operating in
04).
Open Loop Vector Control.
• Reset the torque limit to its default value (200%).
Check if the acceleration time parameters have been set too long (C1-01,
Acceleration time has been set too long.
-03, -05, -07).
Motor characteristics and drive parameter • Select the correct V/f pattern so that it matches the characteristics of the
settings are incompatible with one motor being used.
another in V/f Control. • Check E1-03 (V/f Pattern Selection).
The right combination of motor
characteristics have not been set in Open Execute Rotational Auto-Tuning.
Loop Vector Control.
• Check the multi-function analog input settings.
• Check if multi-function analog input terminal A1 or A2 is set for
frequency gain (H3-02 or H3-10 = “1”). If so, the frequency reference
Incorrect frequency reference setting.
will be 0 if there is no voltage (current) input provided.
• Ensure H3-02 and H3-10 are set to the proper values.
• Ensure the analog input value is set to the right value (U1-13, U1-14).
• Check the Stall Prevention level during acceleration (L3-02).
The Stall Prevention level during
• If L3-02 is set too low, acceleration will take a fair amount of time.
acceleration and deceleration set too low.
• Increase L3-02.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 233
5.9 Troubleshooting without Fault Display
234 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Troubleshooting
setting. Ensure the torque limit is set to a large enough value.
• Increase the torque limit setting.
Reaching the torque limit.
• If multi-function analog input terminal A1 or A2 is set to torque limit
(H3-02 or H3-10 equals 10, 11, 12, or 15), ensure that the analog input
levels are set to the correct levels.
• Ensure H3-02 and H3-10 are set to the right levels.
• Ensure the analog input is set to the correct value.
Load exceeded the internal torque limit
determined by the drive rated current.
Switch to a larger capacity drive. 5
■ Motor Hunting Occurs When Operating With a Light Load
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 235
5.9 Troubleshooting without Fault Display
236 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Note: The drive may have trouble assessing the status of the load due to white noise generated when
using Swing PWM (C6-02 = 7 to A, or 7 if set for Normal Duty).
■ Oscillation or Hunting
Troubleshooting
• Adjust the following parameters in the order listed to get better gain.
• An increase in gain should be followed with an increase in the primary
delay time constant.
Insufficient tuning in Open Loop Vector C4-02 (Torque Compensation Primary Delay Time)
Control. n2-01 (Speed Feedback Detection Control [AFR] Time Constant 1)
C3-02 (Slip Compensation Primary Delay Time)
• The response for torque compensation and slip compensation will drop
as the time constant is increased. 5
• Perform Auto-Tuning.
Auto-Tuning has not yet been performed
• Set motor parameters after calculating the proper values.
(required for Open Loop Vector Control).
• Change the motor control method to V/f Control (A1-02 = “0”).
• Adjust the following parameters in the order listed to get better gain.
• An increase in gain should be followed with an increase in the primary
delay time constant.
Insufficient tuning in Open Loop Vector C4-02 (Torque Compensation Primary Delay Time)
Control. n2-02 (AFR Time Constant 1)
n1-02 (Hunting Prevention Gain Setting)
• The response for torque compensation and slip compensation will drop
as the time constant is increased.
Gain is too low when using PID control. Check the period of oscillation and adjust P, I, and D settings accordingly.
• Ensure that noise is not affecting the signal lines.
The frequency reference is assigned to an • Separate main circuit wiring and control circuit wiring.
external source. • Use twisted-pair cables or shielded wiring for the control circuit.
• Increase the analog input time filter constant (H3-13).
The cable between the drive and motor is • Perform Auto-Tuning.
too long. • Reduce the length of the cable.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 237
5.9 Troubleshooting without Fault Display
238 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Troubleshooting
Cause Possible Solutions
• If the output current rises too high at low speeds, the carrier frequency
automatically reduces and causes a whining or buzzing sound.
Exceeded 110% of the rated output • If the sound is coming from the motor, disable carrier frequency derating
current of the drive while operating at (L8-38 = “0”).
low speeds. • Disabling the automatic carrier frequency derating increases the chances
of an overload fault (oL2). Switch to a larger capacity motor if oL2 faults
5
occur too frequently.
■ Motor Does Not Operate When the RUN Button on the Digital Operator is
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 239
5.9 Troubleshooting without Fault Display
Pressed
240 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
5.9 Troubleshooting without Fault Display
Troubleshooting
The maximum output voltage of the
drive is determined by its input voltage.
Vector control uses voltage to control the
currents within the motor. If the vector
Use a motor with a lower rated voltage compared to the input voltage, or
control voltage reference value exceeds
change to flux vector control.
the drive output voltage capability, the
speed control accuracy will decrease
because the motor currents cannot be 5
properly controlled.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 241
5.9 Troubleshooting without Fault Display
242 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6
Periodic Inspection
& Maintenance
This chapter describes the periodic inspection and maintenance
of the drive to ensure that it receives the proper care to maintain
overall performance.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 243
6.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
244 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.1 Section Safety
WARNING
Do not perform work on the drive while wearing loose clothing,
jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing,
and wear eye protection before beginning work on the drive.
Maintenance
below 50 Vdc. To prevent electric shock, wait at least five minutes after all
indicators are off and measure the DC bus voltage level to confirm safe
level.
Fire Hazard
6
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire
due to overheating of electrical connections.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 245
6.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Check all the wiring to ensure that all connections are correct after
installing the drive and connecting any other devices.
Failure to comply could result in damage to the drive.
246 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.2 Inspection
6.2 Inspection
Power electronics have limited life and may exhibit changed characteristics or performance
deterioration after years of use under normal conditions. To help avoid such problems, it is
important to perform preventive maintenance and periodic inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semi-conductors,
capacitors, resistors, fans, and relays. The electronics in the drive serve a critical role in
maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance
program.
Note: The drive will require more frequent inspection if it is placed in harsh environments,
such as:
-high ambient temperatures
Maintenance
-excessive vibrations or shock loading
-dust, metal dust, salt, sulfuric acid, chlorine atmospheres
-poor storage conditions.
Perform the first equipment inspection 3 months after installation. 6
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 247
6.2 Inspection
Inspection
Category Inspection Points Corrective Action Checked
248 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.2 Inspection
Maintenance
Inspection Inspection Points Corrective Action Checked
Area
Main Circuit Periodic Inspection
• Overall check of the main power circuit Take appropriate actions
and ground terminals (e.g., tightening loose connections).
• Replace damaged components as
• Inspect equipment for discoloration from required.
6
overheating or deterioration. • The drive has few serviceable parts
• Inspect for damaged or deformed parts. and may require complete drive
replacement.
General
• Inspect enclosure door seal if present.
Replace components if cleaning is not
possible.
• Inspect for dirt, foreign particles, or dust
• Use dry air to clear away foreign
collection on components.
matter. Use a pressure of
39.2 x 104 to 58.8 x 104 Pa
(4 - 6 kg •cm2).
• Inspect wiring and connections for
Conductors and discoloration, damage, or heat stress.
• Repair or replace damaged wiring.
Wiring • Inspect wire insulation and shielding for
wear.
• Inspect terminals for stripped, damaged, • Tighten loose screws and replace
Terminals
or loose connections. damaged screws or terminals.
• Inspect contactors and relays for • Check coil voltage for over or under
Relays and excessive noise during operation. voltage conditions.
Contactors • Inspect coils for signs of overheating • Replace damaged removable relays
such as melted or cracked insulation. contactors or circuit board.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 249
6.2 Inspection
250 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.2 Inspection
Note: Periodic inspections should be performed every one or two years. The drive, however, may
require more frequent inspection due to poor environments or rigorous use.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 251
6.3 Periodic Maintenance
◆ Replacement Parts
Table 6.3 contains the estimated performance life of components that require replacement
during the life of the drive. Only use Yaskawa replacement parts for the appropriate drive
model and revision.
Table 6.3 Estimated Performance Life
NOTICE: Estimated performance life based on specific usage conditions. These conditions are provided for
the purpose of replacing parts to maintain performance. Some parts may require more frequent replacement
due to poor environments or rigorous use.
Usage conditions for estimated performance life:
• Ambient temperature: Yearly average of 40°C
• Load factor: 80% maximum
• Operation time: 24 hours a day
252 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.3 Periodic Maintenance
Maintenance
Parameter Open Open Loop
Operator Display V/f Loop Vector for
Vector PM
o4-03 Cooling Fan Maintenance Setting (Operation Time) A A A
o4-05 Capacitor Maintenance Setting A A A
o4-07 Inrush Prevention Relay (pre-charge) Maintenance Setting A A A 6
o4-09 IGBT Maintenance Setting A A A
NOTICE: After replacing parts, reset the appropriate maintenance parameters (o4-03, o4-05, o4-07, and o4-
09) to 0. If these parameters are not reset, the function will continue to count down the performance life of
the new replaced components.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 253
6.4 Drive Cooling Fans
CAUTION! Burn Hazard. Do not touch a hot drive heatsink. Failure to comply could result in minor or
moderate injury. Shut off the power to the drive when replacing the cooling fan. To prevent burns, wait at
least 15 minutes and ensure the heatsink has cooled down.
254 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.4 Drive Cooling Fans
A
B
A – Fan cover
B – Cooling fan
C – Tab
2. Remove the fan cable carefully, disconnect the pluggable connector and remove the
fan.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 255
6.4 Drive Cooling Fans
1. Install the replacement cooling fan into the drive, ensuring the alignment pins line
up, as shown in the figure below:
Figure 6.2
B
A
A – Label facing up
B – Back
C – Front
2. Ensure the connectors are properly connected and place the cable back into the
recess of the drive.
256 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.4 Drive Cooling Fans
Figure 6.3
Maintenance
6
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 257
6.5 Drive Replacement
◆ Serviceable Parts
The drive contains few serviceable parts. The following parts are considered replacement
parts on the drive:
• Main control board and I/O Terminal board I/O PCBs.
• Cooling fan(s)
• Front cover
Replace the drive if the main power circuitry is damaged. Contact your local Yaskawa
representative before replacing parts if the drive is still under warranty. Yaskawa reserves the
right to replace or repair the drive according to Yaskawa warranty policy.
WARNING! Electrical Shock Hazard. Do not connect or disconnect wiring while the power is on. Failure to
comply can result in serious personal injury. Before servicing the drive, disconnect all power to the
equipment. The internal capacitor remains charged even after the power supply is turned off. The charge
indicator LED will extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at
least five minutes after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
A – Charge LED
B – Terminal Board Screw
C – RemovableTerminal Board
258 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.5 Drive Replacement
WARNING! Electrical Shock Hazard. Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in serious injury. Installation, maintenance, inspection and servicing must be
performed only by authorized personnel familiar with installation, adjustment and maintenance of AC drives.
NOTICE: Damage to Equipment. Observe proper electrostatic discharge procedures (ESD) when handling
the drive and circuit boards. Failure to comply may result in ESD damage to the drive circuitry.
Figure 6.5
1. Loosen the screw on the front of the drive and remove the front cover.
2. Pull the pin on the ground terminal out of the removable terminal block.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 259
6.5 Drive Replacement
Figure 6.6
Terminal
3. Push down the installation pin on the terminal board with a screwdriver
Push down
the
installation
pin with a
screwdriver.
4. While holding down the installation pin from step 3, slide the removable terminal
block in the direction of the arrows in the following figure.
260 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.5 Drive Replacement
Figure 6.7
Maintenance
6
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 261
6.5 Drive Replacement
Figure 6.9
Figure 6.10
2. Ensure the terminal block is firmly fastened to the connector.
Connector
262 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
6.5 Drive Replacement
When replacing the drive, or changing the Control Board or Terminal Board, the following
error codes may be encountered upon application of power:
• oPE04 Drive parameter settings need to be initialized or uploaded from the TB.
• CPF06 Drive specification does not match the replaced drive.
• oPE01 Drive parameter o2-04 kVA requires setting.
Procedural Notes:
1. When replacing the drive, control board or terminal board, make sure to confirm the kVA
setting, parameter o2-04 is correct upon initial power-up.
2. Perform an initialization (via parameter A1-03) to obtain the desired parameter settings.
3. In cases where a previously programmed terminal board is retained, initializing the drive
with a setting of A1-03 = 5550 may be desired to program the drive with previously
programmed settings (settings used prior to replacing the drive or control board).
Figure 6.11
Maintenance
YES “CPF06” Fault is
displayed upon drive
replacement
6
YES
Fault “oPE01”
NO
Fault “oPE04”
YES
NO
Fault “oPE04” drive parameter settings need
to be initialized or uploaded from the TB
Ready
END
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 263
6.5 Drive Replacement
264 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7
Peripheral Devices
& Options
This chapter explains the installation of available peripheral
devices and options for the drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 265
7.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Disconnect all power to the drive, wait at least five minutes after all
indicators are off, measure the DC bus voltage to confirm safe level, and
check for unsafe voltages before servicing to prevent electric shock. The
internal capacitor remains charged even after the power supply is turned
off. The charge indicator LED will extinguish when the DC bus voltage is
below 50 Vdc.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
266 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.1 Section Safety
WARNING
Do not touch any terminals before the capacitors have fully
discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The
internal capacitor remains charged even after the power supply is turned
off. The charge indicator LED will extinguish when the DC bus voltage is
below 50 Vdc. To prevent electric shock, wait at least five minutes after all
indicators are off and measure the DC bus voltage level to confirm safe
level.
Options
Do not perform work on the drive while wearing loose clothing,
jewelry or without eye protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing 7
and wear eye protection before beginning work on the drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 267
7.1 Section Safety
WARNING
Do not change wiring or remove option cards while power is running
through the drive.
Failure to comply could result in death or serious injury.
Disconnect all power to the drive and check for unsafe voltages before
servicing.
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
268 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.2 Peripheral Devices
Name
Surge Protector DIN Rail Attachments
DC Reactor NEMA Type 1 Kit
AC Reactor DriveWizard
Single-Phase 200 V Reactor Connection Cable for Engineering Tools
The following table lists some of the available peripheral devices found in Table 7.2 along
with a picture of the device to help identify and describe situations that may require each
Options
device.
Table 7.2 Specific Peripheral Devices and Purposes
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 269
7.3 Connecting Peripheral Devices
Power
supply
AC reactor Braking
resistor
unit
DC reactor
Ground
+1 +2
Input side
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
noise filter
Output side
noise filter
Motor
Ground
270 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
Options
• Install a 400/200 V transformer when using a 400 V class power supply input.
Figure 7.2
Drive
7
MCCB MC
R/L1
S/L2
T/L3
Three-Phase MC
AC200㨪240 V MB
50/60 Hz SA
Single-Phase MC
AC200㨪240 V
50/60 Hz MC
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 271
7.4 Installing Peripheral Devices
Figure 7.3
Drive
MCCB MC
R/L1
S/L2
T/L3
Three-Phase MC
AC380㨪480 V MB
50/60 Hz SA
MC
MC
400 / 200 V
Transformer
WARNING! Electrical Shock Hazard. Disconnect the MCCB and MC before wiring terminals. Failure to
comply may reslut in serious injury or death.
272 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
switching the MC more than once every 30 minutes. Frequent use can damage the drive. Use the drive to
stop and start the motor.
◆ Connecting an AC or DC Reactor
AC and DC reactors suppress surges in current and improve the power factor on the input
side of the drive.
To better suppress harmonic current, use an AC reactor and DC reactor together.
Use a DC reactor or AC reactor or both:
Options
Note: Use an AC or DC reactor when also connecting a thyristor converter (such as a DC drive) to the
same power supply system, regardless of the conditions of the power supply.
■ Connecting an AC Reactor
Figure 7.4
7
C D
A B
U X R/L1
V Y S/L2
W Z T/L3
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 273
7.4 Installing Peripheral Devices
■ Connecting a DC Reactor
Ensure the jumper between terminals +1 and +2 (terminals are jumpered for shipment) is
removed when connecting a DC reactor. The jumper must be installed if no DC reactor is
used. Refer to Figure 7.5 for an example of DC reactor wiring.
Figure 7.5
C
A B
R/L1
S/L2
T/L3
+1 +2
274 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
Figure 7.6
B C
A MCCB
1 3 R/L1
2 4 S/L2
MCCB
B C
MCCB
A R U R/L1
Options
S/L2
S V
T/L3
T W
E
7
MCCB
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 275
7.4 Installing Peripheral Devices
B C
A MCCB
R/L1 U/T1 1 4
S/L2 V/T2 2 5 D
T/L3 W/T3 3 6
TERMS
Radiated Electromagnetic waves radiated from the drive and cables create noise
noise: throughout the radio bandwidth that can affect devices.
Induced Noise generated by electromagnetic induction can affect the signal line and
noise: may cause the controller to malfunction.
276 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
B
A MCCB
C
R/L1 U/T1
S/L2 V/T2
D
T/L3 W/T3
G
F
Options
The drive, input lines, and output lines generate radio frequency noise. Use noise filters on
input and output sides and install the drive in a metal enclosure panel to reduce radio
frequency noise.
Figure 7.10
Note: The cable running between the drive and motor should be as short as possible. 7
A
B MCCB C D E F
R/L1 U/T1
S/L2 V/T2 G
T/L3 W/T3
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 277
7.4 Installing Peripheral Devices
A D C
U/T1 U
V/T2 V
M
W/T3 W
5. Ground the largest possible surface area of the shield to the metal conduit when
using braided shield cable. Yaskawa recommends using a cable clamp
(Figure 7.12).
278 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
Figure 7.12
C B
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 279
7.4 Installing Peripheral Devices
L3 A
L2
L1
PE
H
B
C
D
L3 L2 L1
J E
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
D
D
I
H F
A
G
280 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
A
L2
L1
PE
B
C
D
L3 L2 L1
D
D
Options
I
F
7
H
A
G
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 281
7.4 Installing Peripheral Devices
282 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.4 Installing Peripheral Devices
Options
Lower the carrier frequency according to Figure 7.15 or correct the motor thermal OL
relay adjustment according the Table 7.3.
Figure 7.15
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 283
7.4 Installing Peripheral Devices
resulting in additional motor heating. Unintentional triggering of the overload device may
also occur. Therefore, do not use high starting torque V/f patterns or use excessive voltage
boost settings unless absolutely necessary.
Correcting Nuisance Tripping Resulting from High AC Drive Carrier Frequency
Thermal overload element heating is influenced by carrier frequency and lead length.
Current waveforms generated by PWM drives tend to create additional temperature rise in
overload relays. Therefore, it may be necessary to increase the trip level setting by the
factors listed in Table 7.3 when encountering nuisance triggering of the relay. Confirm an
actual overload condition is not present prior to increasing the trigger level.
WARNING! Risk of Fire. Confirm an actual motor overload condition is not present prior to increasing the
thermal OL trip setting. Check local electrical codes before making adjustments to motor thermal overload
settings.
Example:A thermal OL relay with an adjustment range of 1.1 to 1.6 A is used with a drive
working with 8 kHz carrier frequency. The motor rated current is 1.2 A. The overload trip
level may be corrected to: 1.2 A x 1.21 = 1.45 A
Table 7.3 shows recommended correction factors for the motor protection device trigger
level based on adjustment range and carrier frequency of the drive.
Table 7.3 Motor Protection Device Correction Factors
284 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.5 Communication Options
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 285
7.6 Connecting an Option Card
A G
B
C
H
D
E
I
F
286 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.6 Connecting an Option Card
2. Remove the terminal cover. Connect the lead from the option card to the drive
ground terminal.
Options
A 7
B
C
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 287
7.6 Connecting an Option Card
Figure 7.19
A – Line up the tab with the mounting B – Line up the tab with the mounting
hole. hole.
E
D A
B
C
A – Drive ground terminal D – Ground lead through-hole
B – Route the lead wire on the inside of E – Ground lead
the lower cover.
C – Ground lead
288 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
7.6 Connecting an Option Card
Figure 7.21
6. Reattach the option card cover.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 289
7.6 Connecting an Option Card
290 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A
Specifications
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 291
A.1 Heavy Duty and Normal Duty Ratings
Setting
Parameter Rated Output Current Overload Tolerance Carrier Frequency
C6-01
0: Heavy Duty HD Rating 2-15 kHz
150% rated output current for 60 s
(default) varies by model <1> varies by model
1: Normal Duty ND Rating 120% rated output current for 60 s.
2 kHz, Swing PWM
(default) varies by model <1> Varies by model <1>
<1> The following pages list information on rating changes based on drive model.
TERMS
HD and ND
• HD refers to applications requiring constant torque output, while ND refers to
applications with variable torque needs.
• The drive allows the user to select HD or ND torque depending on the application.
Fans, pumps, and blowers should use ND (C6-01 = “1”), and other applications
generally use HD (C6-01 = “0”).
Swing PWM
• Swing PWM equivalent to a 2 kHz audible noise. This function turns the motor
noise into a less obtrusive white noise.
Note: Differences between HD ratings and ND ratings for the drive include rated input and output
current, overload capacity, carrier frequency, and current limit. The default setting is for ND
(C6-01=1).
292 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.2 Single/Three-Phase 200 V Class Drive
Item Specification
Three-Phase: CIMR-V 2A 0001 0002 0004 0006 0010 0012 0020
Single-Phase: CIMR-V BA <1> 0001 0002 0003 0006 0010 0012 -
Maximum Motor Size Allowed ND Rating 0.13 0.25 0.5/0.75 1.0/1.5 2.0/3.0 3.0 5.0
(HP) <2> HD Rating 0.13 0.25 0.5/0.75 0.75/1.0 1.5/2.0 3.0 5.0
Three- ND Rating 1.1 1.9 3.9 7.3 10.8 13.9 24.0
Input Current Phase HD Rating 0.7 1.5 2.9 5.8 7.5 11.0 18.9
Input
(A) <3> Single- ND Rating 2.0 3.6 7.3 13.8 20.2 24.0 –
Phase HD Rating 1.4 2.8 5.5 11.0 14.1 20.6 –
Rated Output Capacity ND Rating 0.5 0.7 1.3 2.3 3.7 4.6 7.5
(kVA) <4> HD Rating 0.3 0.6 1.1 1.9 3.0 4.2 6.7
ND
1.2 1.9 3.5 (3.3) 6.0 9.6 12.0 19.6
Output Current (A) Rating <5>
HD Rating 0.8 <6> 1.6 <6> 3.0 <6> 5.0 <6> 8. <7> 11.0 <7> 17.5 <7>
ND Rating: 120% of rated output current for 1 minute
Output HD Rating: 150% of rated output current for 1 minute
Overload Tolerance
(Derating may be required for applications that start and stop
Specifications
frequently)
Carrier Frequency 2 kHz (user-set, 2 to 15 kHz)
Three-phase power: Three-phase 200 to 240 V Single-phase power:
Max Output Voltage (V) Three-phase 200 to 240 V
(both proportional to input voltage)
Max Output Frequency (Hz)
Rated Voltage
400 Hz (user-adjustable)
Three-phase power: Three-phase 200 to 240 V 50/60 Hz
A
Power Rated Frequency Single-phase power: 200 to 240 V 50/60 Hz
Supply Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
Harmonic DC
Optional
Countermeasures Reactor
Three- ND Rating 13.0 17.1 29.4 44.7 77.5 91.7 145.0
Phase HD Rating 11.6 16.7 27.6 43.3 78.6 100.7 153.8
Heat Generation (W)
Single- ND Rating 13.5 17.3 29.0 49.5 81.5 98.4 –
Phase HD Rating 11.7 16.8 27.6 50.5 80.7 104.8 161.9
<1> Drives with single-phase power supply inputs output three-phase power, and cannot run a single-phase motor.
<2> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 293
A.2 Single/Three-Phase 200 V Class Drive
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 230 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency is set to 10 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Item Specification
Three-Phase: CIMR-V 2A 0030 0040 0056 0069
Single-Phase: CIMR-V BA <1> - - - -
ND Rating 10.1 14.8 20.1 24.8
Maximum Motor Size Allowed (HP) <2>
HD Rating 7.4 10.1 14.8 20.1
ND Rating 34.7 50.9 69.4 85.6
Three-Phase
Input Current HD Rating 26.0 35.4 51.9 70.8
Input
(A) <3> ND Rating - - - -
Single-Phase
HD Rating - - - -
Rated Output Capacity ND Rating 11.4 15.2 21.3 26.3
(kVA) <4> HD Rating 9.5 12.6 17.9 22.9
ND Rating <5> 30.0 40.0 56.0 69.0
Output Current (A)
HD Rating 25.0 <7> 33.0 <7> 47. <7> 60.0 <7>
ND Rating: 120% of rated output current for 1 minute
HD Rating: 150% of rated output current for 1 minute
Output Overload Tolerance
(Derating may be required for applications that start and
stop frequently)
Carrier Frequency 2 kHz (user-set, 2 to 15 kHz)
Three-phase power: Three-phase 200 to 240 V
Max Output Voltage (V) Single-phase power: Three-phase 200 to 240 V (both
proportional to input voltage)
Max Output Frequency (Hz) 400 Hz (user-adjustable)
Rated Voltage Three-phase power: Three-phase 200 to 240 V 50/60 Hz
Power Rated Frequency Single-phase power: 200 to 240 V 50/60 Hz
Supply Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
DC
Harmonic Countermeasures Optional
Reactor
ND Rating - - - -
Three Phase
HD Rating 335.3 379.5 509.7 646.2
Heat Generation (W)
ND Rating 303.7 321.3 465.2 589.1
Single Phase
HD Rating - - - -
<1> Drives with single-phase power supply inputs output three-phase power, and cannot run a single-phase motor.
294 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.2 Single/Three-Phase 200 V Class Drive
<2> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<3> Input current rating varies depending on the power supply transformer, input reactor, wiring connections, and
power supply impedance.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<7> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note: Differences between Heavy Duty (HD) ratings and Normal Duty (ND)ratings for the drive
include rated input and output current, overload capacity, carrier frequency, current limit, and
maximum output frequency. Set parameter C6-01 to “0” for HD ratings or “2” for ND ratings.
Default is ND (C6-01 = 1).
Specifications
A
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 295
A.3 Three-Phase 400 V Class Drives
Item Specification
CIMR-V 4A 0001 0002 0004 0005 0007 0009 0011
Maximum Applicable Motor Capacity ND Rating 0.25 0.5/0.75/1.0 1.5/2.0 3.0 3.0 5.0 7.5
(HP) <1> HD Rating 0.25 0.5/0.75 1.0/1.5/2.0 3.0 3.0 5.0 5.0
ND Rating 1.2 2.1 4.3 5.9 8.1 9.4 14.0
Input Input Current (A) <2>
HD Rating 1.2 1.8 3.2 4.4 6.0 8.2 10.4
ND Rating <4> 0.9 1.6 3.1 4.1 5.3 6.7 8.5
Output Current (kVA) <3>
HD Rating <5> 0.9 1.4 2.6 3.7 4.2 5.5 7.0
ND Rating <4> 1.2 2.1 4.1 5.4 6.9 8.8 11.1
Output Current (A)
HD Rating <5> 1.2 1.8 3.4 4.8 5.5 7.2 9.2
ND Rating: 120% of rated output current for 60 s
Output HD Rating: 150% of rated output current for 60 s
Overload Tolerance
(Derating may be required for applications that start and
stop frequently)
Carrier Frequency <3> 2 kHz (user-adjustable from 2 to 15 kHz)
Three-phase: @380 to 480 V (proportional to input
Maximum Output Voltage (V)
voltage)
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
Rated Voltage Rated Frequency Three-phase: 380 to 480 V 50/60 Hz
Power
Allowable Voltage Fluctuation -15 to 10%
Supply
Allowable Frequency Fluctuation ±5%
Harmonic
DC Reactor Optional
Countermeasures
ND Rating 19.6 32.4 47.3 66.3 87.0 95.1 127.7
Heat Generation (W)
HD Rating 30.6 43.8 60.2 96.9 111.7 117.5 148.7
<1> The motor capacity (HP) refers to a NEC 4-pole motor. The rated output current of the drive output amps should
be equal to or greater than the motor rated current.
<2> Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 460 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
296 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.3 Three-Phase 400 V Class Drives
Item Specification
CIMR-V 4A 0018 0023 0031 0038
Maximum Applicable Motor Capacity ND Rating 10.1 14.8 20.1 24.8
(HP) <1> HD Rating 7.4 10.1 14.8 20.1
ND Rating 20.0 24.0 38.0 44.0
Input Input Current (A) <2>
HD Rating 15.0 20.0 29.0 39.0
ND Rating <4> 13.3 17.5 23.6 29.0
Output Current (kVA) <3>
HD Rating <5> 11.3 13.7 18.3 23.6
ND Rating <4> 17.5 23.0 31.0 38.0
Output Current (A)
HD Rating <5> 14.8 18.0 24.0 31.0
ND Rating: 120% of rated output current for 60 s
Output HD Rating: 150% of rated output current for 60 s
Overload Tolerance
(Derating may be required for applications that start and
stop frequently)
Carrier Frequency <3> 2 kHz (user-adjustable from 2 to 15 kHz)
Three-phase: @380 to 480 V (proportional to input
Maximum Output Voltage (V)
voltage)
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
Rated Voltage Rated Frequency Three-phase: 380 to 480 V 50/60 Hz
Specifications
Power
Allowable Voltage Fluctuation -15 to 10%
Supply
Allowable Frequency Fluctuation ±5%
Harmonic
DC Reactor Optional
Countermeasures
ND Rating 261.3 321.1 433.6 475.0
Heat Generation (W)
HD Rating 228.7 285.2 372.8 445.7 A
<1> The motor capacity (kW) refers to a Yaskawa 4-pole motor. The rated output current of the drive output amps
should be equal to or greater than the motor rated current.
<2> .Input current rating varies depending on the power supply transformer, input reactor, wiring conditions, and
power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 440 V.
<4> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<5> Carrier frequency is set to 8 kHz. Current derating is required in order to raise the carrier frequency.
Note: Differences between Heavy Duty ratings and Normal Duty ratings for the drive include rated
input and output current, overload capacity, carrier frequency, current limit, and maximum
output frequency. Set parameter C6-01 to “0” for Heavy Duty ratings or “2” for Normal Duty
ratings. The default is Normal Duty (C6-01 = 1).
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 297
A.4 Drive Specifications
298 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.4 Drive Specifications
Item Specification
The following control methods are available:
Control Method Open Loop Vector Control (current vector), V/f Control, and PM Open Loop
Vector for (for use with SPM and IPM)
Frequency Control
0.01 to 400 Hz
Range
Digital input: within ±0.01% of the max output frequency (-10 to +50 °C)
Frequency Accuracy
Analog input: within ±0.5% of the max output frequency (25°C ±10 °C)
Frequency Setting Digital inputs: 0.01 Hz
Resolution Analog inputs: 1/1000 of maximum output frequency
Output Frequency
1/220 of maximum output frequency
Resolution
Main frequency reference: 0 to +10 Vdc (20 kΩ), 4 to 20 mA (250 Ω), 0 to
Frequency Setting
20 mA (250 Ω)
Signal
Main speed reference: Pulse Train Input (max 33 kHz)
200%/0.5 Hz (Open Loop Vector Control, HD rating, IM of 3.7 kW or
Starting Torque
smaller), 50%/6 Hz (PM Open Loop Vector Control)
Speed Control 1:100 (Open Loop Vector Control), 1:40 (V/f Control), 1:10 (PM Open Loop
Range Vector Control)
Control Speed Control
0.2% in Open Loop Vector Control <1>
Characteristics Accuracy
5 Hz (20 °C ±10 °C) in Open Loop Vector Control
Specifications
Speed Response (excludes temperature fluctuation when performing Rotational Auto-
Tuning)
Torque Limit Open Loop Vector Control only. Adjustable in 4 quadrants.
Accel/Decel Time 0.00 to 6000.0 s (allows four separate settings for accel and decel)
Instananeous Average Decel Torque <2>: 0.1/0.2 kW: over 150%, 0.4/0.75
kW: over 100%, 1.5 kW: over 50%, 2.2 kW and above: over 20%
Braking Torque Continuous Regen Torque: 20%, A
125% with a Braking Resistor Unit <3>: (10% ED) 10 s with an internal
braking resistor.
V/f Characteristics Preset V/f patterns and user-set program available.
Momentary Power Loss Ride-Thru, Speed Search, Overtroque Detection,
Torque Limit, Multi-Step Speed (17 steps max), Accel/Decel Time Switch,
S-Curve Accel/Decel, 3-Wire Sequence, Rotational Auto-Tuning, Stationary
Auto-Tuning of Line-to-Line Resistance, Dwell, Cooling Fan ON/OFF, Slip
Motor Protection
Compensation, Torque Compensation, Frequency Jump, Frequency
Reference Upper/Lower Limit, DC Injection Braking (start and stop), High
Slip Braking, PID Control (with Slip Function), Energy Saving,
MEMOBUS (RS-485/422 Max 115.2 kbps), Fault Reset, Parameter Copy.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 299
A.4 Drive Specifications
Item Specification
Motor Protection
Motor overheat protection via output current sensor
Momentary
Overcurrent
Drives stops when output exceeds 200% of the rated current (Heavy Duty)
Protection
A stop command will be entered after operating at 150% for 60 s (Heavy
Overload Protection
Duty) <4>
Drive stops when DC bus voltage falls below the levels indicated: <5>
Low Voltage
190 V (3-phase 200 V), 160 V (single-phase 200 V), 380 V (3-phase 400 V),
Protection
350 V (3-phase 380 V)
Momentary Power 3 selections available: Ridethru disabled (stops after 15 ms), time base of 0.5
Loss Ride-Thru s, and continue running until power is restored. <6>
Protection Heatsink Overheat
Protected by thermistor
Functions Protection
Braking Resistor
Overheat sensor for braking resistor (Optional ERF-type, 3%ED)
Overheat Protection
Stall prevention is available during acceleration, deceleration, and during
Stall Prevention run. Separate settings for each type of stall prevention determine the current
level at which stall prevention is triggered.
Cooling Fan Failure
Circuit protection (“fan-lock” sensor)
Protection
Electronic circuit protection (triggered by the same levels as momentary
Ground Protection
current protection) <7>
DC Bus Charge
Remains lit until DC bus voltage falls below 50 V
LED
Storage/Installation
Indoors
Area
Ambient -10 to +40 °C (wall-mounted enclosure)
Temperature -10 to +50 °C (open chassis)
Humidity 95 RH% or less with no condensation
Storage Temperature -20 to +60 °C allowed for short-term transport of the product
Altitude 1000 m or less
10 to 20 Hz: 9.8 m/S 2
Shock, Impact
Environment 20 to 55 Hz: 5.9 m/S 2
• Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foriegn materials
• radioactive materials
Surrounding Area • combustible materials
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
Orientation Install the drive vertically to maintain maximum cooling effects
300 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.4 Drive Specifications
Item Specification
Safety Regulations and Standards UL508C, EN954-1 Cat.3
Open chassis (IP20)
Protective Enclosure
Wall-mounted enclosure (NEMA Type 1): available as an option
CIMR-VB0001 to 0006: self-cooled
CIMR-VAB0010 to 0012: cooling fan
CIMR-VA20001 to 0004: self-cooled
Cooling Method
CIMR-VA20006 to 0069: cooling fan
CIMR-VA40001 to 0004: self-cooled
CIMR-VA40005 to 0038: cooling fan
<1> Speed control accuracy varies somewhat according to the type of motor and drive settings. Contact Yaskawa
for more information.
<2> Instantaneous average deceleration torque refers to the torque required to decelerate the motor (uncoupled from
the load) from 60 Hz in the shortest time.
<3> Ensure that Stall Prevention Selection during Deceleration is disabled (L3-04 = 0) or set to 3 when using a
braking resistor or the Braking Resistor Unit. The default setting for the stall prevention function will interfere
with the braking resistor.
<4> Overload protection may be triggered when operating with 150% of the rated output current if the output
frequency is less than 6 Hz.
<5> Parameter settings allow up to 150 V.
<6> A Momentary Power Loss Ridethru Unit is required for 200/400V class drives 7.5 kW and less if the
application needs to continue running during a momentary power loss up to 2 seconds.
<7> Ground protection cannot be provided under the following circumstances when a ground fault is likely in the
motor windings during run: Low ground resistance for the motor cable and terminal block; low ground
resistance for the motor cable and terminal block; or the drive is powered up from a ground short.
Specifications
A
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 301
A.5 Drive Watts Loss Data
Model
Rated Heatsink Interior Unit Total Loss
Drive Duty Fc (kHz) Number
Amps (A) Loss (W) Loss (W) (W)
CIMR-V
BA0001 0.8 28.7 15.5 44.2
BA0002 1.6 38.8 21.9 60.7
BA0003 3.0 52.0 29.5 81.5
8 BA0006 5.0 80.6 43.9 124.5
BA0010 8.0 4.7 12.5 17.2
BA0012 11.0 7.2 13.7 20.9
BA0020 17.5 14.0 18.6 32.6
HD
BA0001 0.8 3.0 7.1 10.1
BA0002 1.6 6.0 8.4 14.4
BA0003 3.0 12.6 10.6 23.2
2 BA0006 5.0 28.7 15.5 44.2
BA0010 8.0 38.8 21.9 60.7
BA0012 11.0 52.0 29.5 81.5
BA0020 17.5 80.6 43.9 124.5
BA0001 1.2 4.7 12.5 17.2
BA0002 1.9 7.2 13.7 20.9
BA0003 3.2 14.0 18.6 32.6
ND 2
BA0006 6.0 35.6 25.6 61.2
BA0010 9.6 48.6 34.5 83.1
BA0012 12.0 57.9 42.6 100.5
302 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.5 Drive Watts Loss Data
Interior
Model Number Rated Heatsink Total
Drive Duty Fc (kHz) CIMR-V Amps (A) Loss (W)
Unit Loss
Loss (W)
(W)
2A0001 0.8 4.3 7.3 11.6
2A0002 1.6 7.9 8.8 16.7
2A0004 3.0 16.1 11.6 27.7
8 2A0006 5.0 27.4 15.9 43.3
2A0010 8.0 54.8 23.8 78.6
2A0012 11.0 70.7 29.9 100.6
2A0020 17.5 110.5 43.3 153.8
HD
2A0001 0.8 3.0 7.0 10.0
2A0002 1.6 6.0 8.3 14.3
2A0004 3.0 12.6 10.6 23.2
2 2A0006 5.0 21.1 14.3 35.4
2A0010 8.0 38.8 19.8 58.6
2A0012 11.0 52.0 25.3 77.3
2A0020 17.5 80.6 35.8 116.4
2A0001 1.2 4.7 11.9 16.6
2A0002 1.9 7.2 13.5 20.7
Specifications
2A0004 3.5 15.1 17.7 32.8
ND 2 2A0006 6.0 26.2 21.4 47.6
2A0010 9.6 48.6 30.5 79.1
2A0012 12.0 57.9 35.9 93.8
2A0020 19.6 93.3 53.0 146.3
A
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 303
A.5 Drive Watts Loss Data
Rated Interior
Model Number Heatsink Total
Drive Duty Fc (kHz) CIMR-V
Amps
Loss (W)
Unit Loss
Loss (W)
(A) (W)
4A0001 1.2 19.2 11.5 30.7
4A0002 1.8 28.9 14.8 43.7
4A0004 3.4 42.3 17.9 60.2
8 4A0005 4.8 70.7 26.2 96.9
4A0007 5.5 81.0 30.7 111.7
4A0009 7.2 84.6 32.9 117.5
4A0011 9.2 107.2 41.5 148.7
HD
4A0001 1.2 8.2 8.6 16.8
4A0002 1.8 13.0 10.9 23.9
4A0004 3.4 21.3 12.6 33.9
2 4A0005 4.8 32.8 16.8 49.6
4A0007 5.5 38.2 20.0 58.2
4A0009 7.2 44.3 22.8 67.1
4A0011 9.2 57.6 29.1 86.7
4A0001 1.2 8.2 14.4 22.6
4A0002 2.1 15.5 18.4 33.9
4A0004 4.1 26.4 21.2 47.6
ND 2 4A0005 5.4 37.5 25.7 63.2
4A0007 6.9 49.7 32.4 82.1
4A0009 8.8 55.7 36.0 91.7
4A0011 11.1 71.9 51.7 123.6
304 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.6 Drive Derating Data
Drive
Rating Carrier Frequency Derating
0&
*&
200 V Class:
80% of HD
400 V Class
60% of HD
Specifications
Carrier(C6-02)
◆ Temperature Derating
As the ambient temperature for the drive is increased above the drive specification the drive A
should be derated. Additionally parameter L8-35 Side-by-Side Selection on page 305 should
be set according to enclosure type and mounting method as illustrated in Figure A.2
Ambient Temperature and Installation Method Derating on page 306.
■ Output Current Derating Due to Ambient Temperature
If the ambient temperature is above the drive specification or if drives are side-by-side
mounted in a cabinet, the parameters L8-12 and L8-35 must be set according to the
installation conditions. The output current is derated as shown in Figure A.2.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 305
A.6 Drive Derating Data
Parameter L8-35 = 1
(Side-by-side installation)
Ambient temp oC
Parameter L8-12
o o o o
Figure A.2 Ambient Temperature and Installation Method Derating
◆ Altitude Derating
Yaskawa recommends referencing two standards when considering altitude derating. These
standards are:
• ANSI/IEEE C 37.40: Service Conditions and Definitions for High Voltage Fuses,
Distributor Enclosed Single Pole Air Switches and Accessories
• IEC 282-1.2: High Voltage Fuse
■ Drive Derating
Power conversion equipment must be de-rated above a certain altitude (usually 1000
meters). Equipment that depends on air for its insulating and cooling medium has a higher
temperature rise and a lower dielectric strength value when operated at altitudes higher than
1000 meters (3300 feet). Application of the correct de-rating factors is necessary to prevent
drive failure.
The effect of high altitudes may eventually result in thermal damage to the power semi-
conductors and related components (reduced effectiveness of the heat sinks) as well as lower
dielectric withstand capabilities. High altitude de-rating is, therefore, an important
consideration during the initial application of the drive. Figure A.3 is provided as a quick
reference to aid in derating the drive above specified altitude.
Note: This derate applies only to the inverter. However, if the inverter is placed in a pressurized cabinet
so that the internal pressure is maintained at the value of atmospheric pressure at 3300ft. then
there is no need for derate. Example: Heatsink is exposed to the outside and is not under
306 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A.6 Drive Derating Data
positive pressure in an enclosed cabinet with forced air cooling or an air-conditioning system. In
such a case, derating is required.
Figure A.3
■ Motor Derating
Specifications
Consult the motor manufacturer for the applicable altitude de-rating factor before applying
the motor. As a general guideline, consult the NEMA standard MG 1-14.04 (Operation of
AC and DC Fractional- and Integral-HP Motors and Generators at Altitudes Above 3,300
feet (1000 meters). However, the motor manufacturer's specific de-rating data is always
preferable.
A
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 307
A.6 Drive Derating Data
308 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B
Parameter List
This chapter contains a full listing of all parameters and settings
available in the drive
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 309
B.1 Parameter Groups
310 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
◆ A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the
parameter Access Level, Motor Control Method, Password, User Parameters and more.
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ P Hex
L
f V M
Parameter List
Resets all parameters to factory default settings. 0 to
0 A A A 103 —
(Initializes the drive then returns A1-03 to 0) 3330
0: No Initialize
Initialize 1110: User Initialize (First set user parameter The following parameters are not
A1-03 reset when the performing
Parameters values must be stored using parameter o2-03)
2220: 2-Wire Initialization initialization:
3330: 3-Wire Initialization A1-00, A1-02, A1-07, and all U2
and U3 monitors.
B
5550: OPE04 Error Reset
0 to
A1-04 Password 1 0 A A A 104 —
9999
0 to
0 A A A 105 —
When the value set into A1-04 does not match the 9999
value set into A1-05, parameters A1-01 thru A1- This parameter is hidden from
03, A1-06, and A2-01 thru A2-32 cannot be view. To access A1-05, first
A1-05 Password 2 changed. display A1-04. Then press the
—
STOP key while holding down
the up arrow key. Parameter
A1-05 will appear.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 311
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets parameters that are commonly used in certain
applications to A2-01 through A2-16 for easier
access.
0: General-purpose (A2 parameters are not
affected)
Application 1: Water supply pump
A1-06 0 to 7 0 A A A 127 —
Preset 2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Crane (Hoist)
7: Crane (Travelling)
0: Disabled
DriveWorksEZ
1: Enabled
A1-07 Function 0 to 2 0 A A A —
2: Multi-function input (enabled when H1- =
Selection
9F)
A2: User Parameters
Use A2 parameters to program the drive.
Parameters that were recently edited are listed here.
A2-01 The user can also select parameters to appear here
User Parameters, b1-01 to -- 106 to
to for quick access. A A A —
1 to 32 o2-08 <16> 125
A2-32 Parameters will be stored here for quick access
when A1-01 = 1.
0: Parameters A2-01 through A2-32 are reserved
User Parameter for the user to create a list of User Parameters.
1
A2-33 Automatic 1: Save history of recently viewed parameters. 0,1 A A A 126 —
<4>
Selection Recently edited parameters will be saved to A2-17
through A2-32 for quick access.
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06
does not = 0.
<16> Default setting value is dependent on parameter A1-06, Application Selection.
<22> Parameter can be changed during run.
◆ b: Application
Application parameters configure the Run Command Source, DC Injection Braking, Speed
Search, Timer functions, PID control, the Dwell function, Energy Savings and a variety of
other application-related settings.
312 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ L P Hex
f M
V
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17.
Frequency Reference
b1-01 1: Terminals - Analog input terminal A1 or A2. 0 to 4 1 S S S 180 124
Selection 1
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Operator - RUN and STOP keys on the
Run Command digital operator.
b1-02 0 to 3 1 S S S 181 127
Selection 1 1: Digital input terminals S1 to S7
2: Memobus communications
3: Option PCB.
Selects the stopping method when the run 0 to 3 0 S S S 182 129
command is removed.
0: Ramp to Stop
Stopping Method DC Injection Braking at Stop
b1-03 1: Coast to Stop
Selection cannot be selected when using
2: DC Injection Braking to Stop
3: Coast with Timer (A new run command is Open Loop Vector for PM motors.
ignored if received before the timer expires)
Parameter List
Permits or prohibits reverse operation.
Reverse Operation
b1-04 0: Reverse enabled. 0,1 0 A A A 183 —
Selection
1: Reverse disabled.
Determines the operation when the Run
command source is switched from LOCAL to
REMOTE or between Run source 1 and 2
b1-07
Local/Remote Run
Selection
while an external Run command is active at the
new source. 0,1 0 A A A 186 — B
0: External Run command has to be cycled at
the new source to be activated.
1: External Run command at new source is
accepted immediately.
0: Run command accepted only in the
Run Command operation menu.
b1-08 Selection while in 1: Run command accepted in all menus. 0 to 2 0 A A A 187 —
Programming Mode 2: Prohibit entering programming mode during
Run
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 313
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the phase order for drive output terminals
U/T1, V/T2 and W/T3.
b1-14 Phase Order Selection 0,1 0 A A A 1C3 —
0: Standard
1: Switch phase order
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-
17.
Frequency
b1-15 1: Terminals - Analog input terminal A1 or A2 0 to 4 0 A A A 1C4 —
Reference 2
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Operator - RUN and STOP keys on the
Run Command digital operator.
b1-16 0 to 3 0 A A A 1C5 —
Source 2 1: Digital input terminals S1 to S7
2: Memobus communications
3: Option PCB
Determines the operation when a Run
Run Command at command is active at power up of the drive.
b1-17 0,1 0 A A A 1C6 —
Power Up 0: Run command not issued, needs to be cycled
1: Run command issued, motor operation start
b2: DC Injection Braking
Use b2 parameters to configure DC Injection Braking operation
Sets the frequency at which DC Injection
DC Injection Braking Braking starts when Ramp to Stop (b1-03 = 0) 0.0 to 0.5
b2-01 A A A 189 —
Start Frequency is selected. If b2-01< E1-09, DC Injection 10.0 Hz
Braking starts at E1-09.
DC Injection Braking Sets the DC Injection Braking current as a
b2-02 0 to 75 50% A A − 18A —
Current percentage of the drive rated current.
DC Injection Braking 0.00
Sets DC Injection Braking time at start. 0.00 to
b2-03 Time/DC Excitation s A A − 18B —
Disabled when set to 0.00 seconds. 10.00
Time at Start <1>
Sets DC Injection Braking time at stop.When
b1-03 = 2, actual DC Injection time is
calculated as follows:
(b2-04) x 10 x (Output Freq) / (E1-04).
DC Injection Braking 0.00 to 0.50
b2-04 When b1-03 = 0, this parameter sets the A A − 18C —
Time at Stop 10.00 s
amount of DC Injection time applied to the
motor at the end of the decel ramp or High Slip
Braking.
Disabled when set to 0.00.
314 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Magnetic Flux Sets the magnetic flux compensation as a
0 to
b2-08 Compensation percentage of the no-load current value 0% − A − 190 —
1000
Capacity (E2-03).
Short Circuit Brake Sets the time for Short-Circuit Brake operation 0.00 to 0.00
b2-12 − − A 1BA —
Time at Start at start. Disabled when set to 0.00. <32> 25.50 s
Sets Short-Circuit Brake operation time at
Short Circuit Brake stop. Used to stop a motor rotating due to 0.00 to 0.50
b2-13 − − A 1BB —
Time at Stop inertia. Disabled when set to 0.00 seconds. 25.50 s
<32>
b3: Speed Search
Use B3 parameters to configure Speed Search function operation.
Enables/disables speed search function at start.
0: Disabled - Speed Search is not automatically
Speed Search
b3-01 performed at start. 0 to 1 0 A A A 191 —
Selection
1: Enabled - Speed Search is automatically
performed at start.
Sets the current level at which the speed is
Speed Search 120
b3-02 assumed to be detected and Speed Search is 0 to 200 A A − 192 —
Deactivation Current <2>
ended. Set in percent of the drive rated current.
Sets the time constant used to reduce the
Speed Search 0.1 to
b3-03 output frequency during speed search. Related 2.0 s A A − 193 —
Deceleration Time 10.0
to a change from max. output frequency to 0.
Parameter List
Delays the speed search operation after a
Speed Search Delay 0.0 to
b3-05 momentary power loss to allow time for an 0.2 s A A A 195 —
Time 100
external output contactor to close.
Sets the current injected to the motor at the
Output Current 1 0.0 to <12
b3-06 beginning of Esitmation type Speed Search. A A − 196 —
during Speed Search 2.0 >
Set as a factor to the motor rated current.
Speed Search
Sets the gain which is applied to the speed
detected by Speed Estimation Speed Search
B
1.00 to
b3-10 Detection before the motor is reaccelerated.Increase this 1.05 A A − 19A —
1.20
Compensation Gain setting if OV occurs when performing speed
search.
Selects if Speed Search detects the motor
rotation direction during speed search.
Bi-Directional Speed
b3-14 0: Disabled–Frequency reference direction 0,1 0 A A − 19E —
Search Selection
used
1: Enabled–Detected direction used
Speed Search Restart Sets the speed search restart current level in 150
b3-17 0 to 200 A A − 1F0 —
Current Level percentag of the drive rated current. %
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 315
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Speed Search Restart Sets the time in seconds for speed search 0.00 to 0.10
b3-18 A A − 1F1 —
Detection Time restart to be detected. 1.00 s
Number of Speed Sets the number of restarts possible for speed
b3-19 0 to 10 3 A A − 1F2 —
Search Restarts search restart operations.
Sets the Speed Search detection mode.
Speed Search Method
b3-24 0: Current Detection Type 0,1 0 A A − 1C0 —
Selection
1: Speed Estimation Type
Speed Search Retry 0 to
b3-25 Sets the wait time before Speed Search restarts. 0.5 s A A A 1C8 —
Interval Time 30.0
b4: Timer Function
Use b4 parameters to configure timer function operation.
Used in conjunction with a multi-function
digital input (H1- = 18) and a multi-
Timer Function function digital output (H2- = 12) 0.0 to
b4-01 0.0 s A A A 1A3 —
On-Delay Time programmed for the timer function. This sets 300.0
the amount of time between digital input
closure and digital output activation.
Used in conjunction with a multi-function
digital input (H1- = 18) and a multi-
Timer Function function digital output programmed for the 0.0 to
b4-02 0.0 s A A A 1A4 —
Off-Delay Time timer function. This sets the amount of time the 300.0
output remains activated after the digital input
is opened.
b5: PID Control
Use b5 parameters to configure the PID control drive function.
Sets the PID control mode.
0: Disabled
1: Enable (Deviation is D-controlled)
2: Enable (Feedback is D-controlled)
b5-01 PID Function Setting 0 to 4 0 A A A 1A5 —
3: Enable (Deviation is D-controlled, PID
outut added to Freq. Ref.)
4: Enable (Feedback is D-controlled, PID outut
added to Freq. Ref.)
b5-02 Proportional Gain Sets the proportional gain of the PID 0.00 to
1.00 A A A 1A6 —
<22> Setting (P) controller. A setting of 0.00 disables P control. 25.00
b5-03 Integral Time Setting Sets the integral time for the PID controller. A 0.0 to
1.0 s A A A 1A7 —
<22> (I) setting of 0.0 s disables integral control. 360.0
b5-04 Sets the maximum output possible from the 0.0 to 100.
Integral Limit Setting A A A 1A8 —
<22> integrator. 100.0 0%
b5-05 Sets D control derivative time. A setting of 0.00 to 0.00
Derivative Time (D) A A A 1A9 —
<22> 0.00 s disables derivative control. 10.00 s
316 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
b5-06 Sets the maximum output possible from the 0.0 to 100.
PID Output Limit A A A 1AA —
<22> entire PID controller. 100.0 0%
-100.0
b5-07 PID Offset 0.0
Applies an offset to the PID controller output. to A A A 1AB —
<22> Adjustment %
+100.0
b5-08 PID Primary Delay Sets the amount of time for the filter on the 0.00 to 0.00
A A A 1AC —
<22> Time Constant output of the PID controller. 10.00 s
Sets the PID controller output direction.
PID Output Level
b5-09 0: Normal Output (direct acting) 0,1 0 A A A 1AD —
Selection
1: Reverse Output (reverse acting)
PID Output Gain 0.00 to
b5-10 Sets the gain applied to the PID output. 1.00 A A A 1AE —
Setting 25.00
Sets the drive operation with negative PID
output.
0: Drive stops with negative PID output
PID Output Reverse
b5-11 1: Rotation direction reverses with negative 0,1 0 A A A 1AF —
Selection
PID output.
When using setting 1 make sure, reverse
operation is permitted by parameter b1-04.
Configures the PID feedback loss detection.
0: Disabled.
1: Feedback loss detected when PID enabled.
Alarm output, operation is continued without
Parameter List
triggering a fault contact.
2: Feedback loss detected when PID enabled.
Fault output, operation is stopped and a fault
contact is triggered.
PID Feedback
3: Feedback loss detection even when PID is
b5-12 Reference Missing 0 to 5 0 A A A 1B0 —
disabled by digital input. No alarm/fault
Detection Selection
output. “PID feedback loss” digital output is
switched,
B
4: PID Feedback error detection even when
PID is disabled by digital input. An alarm is
triggered and the drive continues to run.
5: PID Feedback error detection even when
PID is disabled by digital input. Fault is
triggered and output is shut off.
PID Feedback Loss
b5-13 Sets the PID feedback loss detection level. 0 to 100 0% A A A 1B1 —
Detection Level
PID Feedback Loss Sets the PID feedback loss detection delay time 0.0 to
b5-14 1.0 s A A A 1B2 —
Detection Time in terms of seconds. 25.5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 317
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
PID Sleep Function Sets the sleep function start frequency. 0.0 to 0.0
b5-15 A A A 1B3 —
Start Level Note: Also enabled when PID is not active. 400.0 Hz
PID Sleep Delay Sets the sleep function delay time in units of 0.0 to
b5-16 0.0 s A A A 1B4 —
Time 0.1 seconds. 25.5
PID Accel/Decel Applies an accel/decel time to the PID setpoint 0 to
b5-17 0 s A A A 1B5 —
Time reference. 255
Selects b5-19 as PID setpoint value.
PID Setpoint
b5-18 0: Disabled 0,1 0 A A A 1DC —
Selection
1: Enabled, b5-19 becomes PID target
0.00 to 0.00
b5-19 PID Setpoint Value Sets the PID target value when b5-18 = 1. A A A 1DD —
100.00 %
Sets the units for b5-19, and for parameter
monitors U5-01 (PID Feedback) and U5-04
(PID Setpoint).
b5-20 PID Setpoint Scaling 0: 0.01Hz units 0 to 3 1 A A A 1E2 —
1: 0.01% units (100% = max output frequency)
2: r/min (motor pole number must be set up)
3: User-set (set to b5-38 and b5-39)
-100.0
b5-34 PID Output Lower Sets the minimum output possible from the 0.00
to A A A 19F —
<22> Limit PID controller. %
+100.0
b5-35 Limits the PID control input (deviation signal). 0 to 1000
PID Input Limit A A A 1A0 —
<22> Acts as a bipolar limit. 1000.0 .0%
PID Feedback High 100
b5-36 Sets the PID feedback high detection level. 0 to 100 A A A 1A1 —
Detection Level %
PID Feedback High Sets the PID feedback high level detection 0.0 to
b5-37 1.0 s A A A 1A2 —
Level Detection Time delay time. 25.5
0 to 60000: User-Set Display if b5-20=3
PID Setpoint / User 1 to
b5-38 Set the numbers displayed by designating the <5> A A A 1FE —
Display 60000
maximum PID target.
Sets the number of digits the PID setpoint.
0: No decimal places
PID Setpoint Display
b5-39 1: One decimal places 0 to 3 <5> A A A 1FF —
Digits
2: Two decimal places
3: Three decimal places
318 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
b6: Dwell Function
Use b6 parameters to configure dwell function operation.
Dwell Reference at The Dwell function is used to temporarily hold 0.0 to 0.0
b6-01 A A A 1B6 —
Start the frequency when driving a motor with a 400.0 Hz
heavy load. 0.0 to
b6-02 Dwell Time at Start Parameters b6-01 and b6-02 set the frequency 0.0 s A A A 1B7 —
10.0
to hold and the time to maintain that frequency
Dwell Frequency at at start. 0.0 to 0.0
b6-03 A A A 1B8 —
Stop Parameters b6-03 and b6-04 set the frequency 400.0 Hz
to hold and the time to maintain that frequency
at stop.
Output
Frequency
Run command
10 0.0 to
b6-04 Dwell Time at Stop 0.0 s A A A 1B9 —
10.0
Time
Parameter List
1: Enabled (set b8-04)
b8-02 Sets energy savings control gain when in Open 0.0 to
Energy Saving Gain 0.7 − A − 1CD —
<22> Loop Vector (OLV) control mode. 10.0
Energy Saving
b8-03 Sets energy saving control filter time constant 0.00 to
Control Filter Time 0.50 − A − 1CE —
<22> when in Open Loop Vector control. 10.00
Constant
b8-04
Energy Saving Sets the Energy Saving coefficient and is used 0.0 to <57
A − − 1CF —
B
Coefficient Value to fine adjustments in V/f Control. 655.00 >
Power Detection Sets a filter time for the Power Detection used 0 to 20
b8-05 A − − 1D0 —
Filter Time by Energy Savings in V/f Control. 2000 ms
Sets the limit for the voltage search operation
Search Operation performed by Energy Savings in V/f Control.
b8-06 0 to 100 0% A − − 1D1 —
Voltage Limit Set as a percentage of the motor base voltage.
Disabled when set to 0%.
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 0-V/f Control.
<5> Default setting is dependent on parameter b5-20, PID Setpoint Scaling.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 319
B.2 Parameter Table
◆ C: Tuning
C parameters are used to adjust the acceleration and deceleration times, S-curves, slip- and
torque compensation functions and carrier frequency selections.
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
L
f M
V
C1: Acceleration and Deceleration Times
Use C1 parameters to configure motor acceleration and deceleration.
0.0 to
C1-01 Sets the time to accelerate from 0 to
Acceleration Time 1 6000.0 10.0 s S S S 200 132
<22> maximum frequency.
<6>
0.0 to
C1-02 Sets the time to decelerate from maximum
Deceleration Time 1 6000.0 10.0 s S S S 201 132
<22> frequency to 0.
<6>
Sets the time to accelerate from 0 to 0.0 to
C1-03
Acceleration Time 2 maximum frequency when Accel/Decel 6000.0 10.0 s A A A 202 —
<22>
times 2 are selected by a digital input. <6>
Sets the time to decelerate from maximum 0.0 to
C1-04
Deceleration Time 2 frequency to 0 when Accel/Decel times 2 are 6000.0 10.0 s A A A 203 —
<22>
selected by a digital input. <6>
Acceleration Time 3 Sets the time to accelerate from 0 to 0.0 to
C1-05
(Motor 2 Accel maximum frequency when Accel/Decel 6000.0 10.0 s A A A 204 —
<22>
Time 1) times 3 are selected by a digital input. <6>
Deceleration Time 3 Sets the time to decelerate from maximum 0.0 to
C1-06
(Motor 2 Decel frequency to 0 when Accel/Decel times 3 are 6000.0 10.0 s A A A 205 —
<22>
Time 1) selected by a digital input. <6>
Acceleration Time 4 Sets the time to accelerate from 0 to 0.0 to
C1-07
(Motor 2 Accel maximum frequency when Accel/Decel 6000.0 10.0 s A A A 206 —
<22>
Time 2) times 4 are selected by a digital input. <6>
Deceleration Time 4 Sets the time to decelerate from maximum 0.0 to
C1-08 (Motor 2 Decel frequency to 0 when Accel/Decel times 4 are 6000.0 10.0 s A A A 207 —
Time 2) selected by a digital input. <6>
320 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the time to decelerate from maximum
frequency to 0 for the multi-function input 0.0 to
C1-09 Fast-Stop Time fast-stop function. Note: This parameter is 6000.0 10.0 s A A A 208 —
also used by selecting “Fast-Stop” as a Stop <6>
Method when a fault is detected.
Sets the resolution of C1-01 to C1-09.
Accel/Decel Time
C1-10 0: 0.01 s (0.00 to 600.00 s) 0,1 1 A A A 209 —
Setting Units
1: 0.1 s (0.0 to 6000.0 s)
Sets the frequency for automatic
acceleration/deceleration switching.
Accel/Decel Time Below set frequency: Accel/Decel Time 4 0.0 to 0.0
C1-11 A A A 20A —
Switching Frequency Above set frequency: Accel/Decel Time 1 400.0 Hz Hz
The multi-function input “Accel/Decel Time
1” or “Accel/Decel Time 2” take priority.
C2: S-Curve Characteristics
Use C2 parameters to configure S-curve operation.
S-Curve
The S-curve can be controlled in the four 0.00 to 0.20 s
C2-01 Characteristic at A A A 20B —
points shown below. S-curve is used to 10.00 <2>
Accel Start
run
S-Curve command ON OFF
0.00 to
C2-02 Characteristic at output
0.20 s A A A 20C —
10.0
Accel End frequency C2-02 C2-03
S-Curve
Parameter List
C2-01 C2-04
0.00 to
C2-03 Characteristic at 0.20 s A A A 20D —
10.0
Decel Start time
further soften the starting and stopping ramp.
S-Curve
The longer the S-curve time, the softer the 0.00 to
C2-04 Characteristic at 0.00 s A A A 20E —
starting and stopping ramp. 10.0
Decel End
C3: Slip Compensation
Use C3 parameters to configure the slip compensation function. B
Sets the slip compensation gain. Decides for
C3-01 Slip Compensation what amount the output frequency is boosted 0.0
0.0 to 2.5 A A − 20F —
<22> Gain in order to compensate the slip. <2>
Note: Adjustment is not normally required.
Adjusts the slip compensation function delay
time. Decrease the setting when the slip
2000
Slip Compensation compensation response is too slow, increase 0 to
C3-02 ms A A − 210 —
Primary Delay Time it when the speed is not stable. 10000
<2>
Disabled when Simple V/f Control with PG
(H6-01 = 3) is used.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 321
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the slip compensation upper limit. Set as
Slip Compensation a percentage of motor rated slip (E2-02).
C3-03 0 to 250 200% A A − 211 —
Limit Disabled when Simple V/f Control with PG
(H6-01 = 3) is used.
Selects slip compensation during
regenerative operation.
Slip Compensation 0: Disabled
C3-04 Selection during 1: EnabledUsing the Slip Compensation 0,1 0 A A − 212 —
Regeneration function during regeneration may require a
braking option to handle momentary
increasing regenerative energy.
Selects if the motor magnetic flux is reduced
Output Voltage Limit during output voltage saturation. 0
C3-05 0,1 − A − 213 —
Operation Selection 0: Disabled <2>
1: Enabled
C4: Torque Compensation
Use C4 parameters to configure Torque Compensation function.
V/f control: Sets the gain for the automatic
torque (voltage) boost function and helps to
produce better starting torque.
Increase this setting when using a long motor
cable or when the motor is significantly
smaller than the drive capacity.
C4-01 Torque Compensation 0.00 to
Decrease this setting when motor oscillation 1.00 A A A 215 —
<23> Gain 2.50
occurs. Set the value so that the current at
low speed does not exceeds the drives rated
current.
Open Loop Vector: Sets the torque
compensation function gain. Normally no
change is required.
Sets the torque compensation filter time.
Increase this setting when motor oscillation 200
Torque Compensation 0 to
C4-02 occurs. ms A A A 216 —
Primary Delay Time 60000
Reduce the setting if there is not enough <1>
response from the motor.
Torque Compensation Sets torque compensation at forward start as 0.0 to
C4-03 0.0% − A − 217 —
at Forward Start a percentage of motor torque. 200.0
Torque Compensation Sets torque compensation at reverse start as a -200.0 to
C4-04 0.0% − A − 218 —
at Reverse Start percentage of motor torque. 0.0
322 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the time constant for torque
Torque Compensation compensation at forward start and reverse 0 to 10
C4-05 – A – 219 —
Time Constant start (C4-03 and C4-04). The filter is 200 ms
disabled if the time is set to 4 ms or less.
Sets the torque compensation time 2. When
an OV fault occurs with sudden load changes
or at the and of an acceleration, increase the
Torque Compensation 0 to 150
C4-06 setting. – A – 21AH —
Primary Delay Time 2 10000 ms
Note: Adjustment is not normally required. If
adjusted then AFR time 2 (n2-03) should be
adjusted too.
C5: Speed Control (ASR)
Use C5 parameters to configure the Automatic Speed Regulator (ASR).
C5 parameters are available only when using V/f with Simple PG (H6-01 = 3).
C5-01 ASR Proportional Sets the proportional gain of the speed 0.00 to
0.20 A 21B —
<22> Gain 1 control loop (ASR). 300.00
– –
C5-02 Sets the integral time of the speed control 0.000 to
ASR Integral Time 1 0.200 A 21C —
<22> loop (ASR). 10.000
C5-03 ASR Proportional Sets the speed control gain 2 of the speed 0.00 to
0.02 A − − 21D —
<22> Gain 2 control loop (ASR). 300.00
C5-04 Sets the integral time 2 of the speed control 0.000 to 0.050
ASR Integral Time 2 A 21E —
<22> loop (ASR). 10.000 s
Parameter List
Sets the upper limit for the speed control – –
C5-05 0.0 to
ASR Limit loop (ASR) as a percentage of the maximum 5.0% A 21F —
<22> 20.0
output frequency (E1-04).
C6: Carrier Frequency
Use C6 parameters to configure the carrier frequency drive settings.
Selects the load rating for the drive.
0: Heavy Duty (HD) for constant torque
applications.
B
Normal/Heavy Duty
C6-01 1: Normal Duty (ND) for variable torque 0,1 1 S S S 223 134
Selection
applications.
This setting affects the Rated output current
and overload tolerance of the drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 323
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Selects the carrier frequency
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
Carrier Frequency 6: 15.0 kHz
C6-02 1 to F <3> S S S 224 135
Selection 7: Swing PWM1 (Audible sound 1)
8: Swing PWM2 (Audible sound 2)
9: Swing PWM3 (Audible sound 3)
A: Swing PWM4 (Audible sound 4)
B to E: No setting possible
F: User defined (determined by C6-03
through C6-05)
Carrier Frequency Open Loop Vector: C6-03 defines the fixed 1.0 to
C6-03 <8> A A A 225 —
Upper Limit carrier frequency if C6-02 = F. 15.0
V/f control: C6-03 and C6-04 set upper and
lower limits for the carrier frequency.
carrier frequency
C6-03
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 =
2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 =
0-V/f Control.
<3> Default setting value is dependent on parameters o2-04, Drive/kVA Selection, A1-02, Control Method Selection
and C6-01, Normal/Heavy Duty selection. 351.
<6> Setting range value is dependent on parameter C1-10, Accel/Decel Time Setting Units. When C1-10 = 0 (units of
0.01 seconds), the setting range becomes 0.00 to 600.00 seconds.
<8> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.
324 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
◆ d: References
Reference parameters are used to set the various frequency reference values during
operation.
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ L P Hex
f V M
Parameter List
Frequency reference when digital inputs "Multi- 400.00
d1-06 Frequency 0.00
Step Speed Reference 1, 3 " (H1- = 3 and 5) Hz A A A 285 —
<22> Reference 6 Hz
are on. <11>
Frequency reference when digital inputs "Multi- <19>
d1-07 Frequency 0.00
Step Speed Reference 2, 3" (H1- = 4 and 5) A A A 286 —
<22> Reference 7 Hz
are on.
d1-08 Frequency
Frequency reference when multi-function input
0.00
B
"Multi-Step speed reference 1, 2, 3" (H1- = A A A 287 —
<22> Reference 8 Hz
3, 4, 5) are on.
Frequency reference when multi-function input
d1-09 Frequency 0.00
"Multi-Step Speed Reference 4" (H1- = 32) A A A 288 —
<22> Reference 9 Hz
is on.
Frequency reference when digital input "Multi-
d1-10 Frequency 0.00
Step Speed Reference 1, 4" (H1- = 3 and 32) A A A 28B —
<22> Reference 10 Hz
are on.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 325
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Frequency reference when digital inputs "Multi-
d1-11 Frequency 0.00
Step Speed Reference 2, 4" (H1- = 4 and 32) A A A 28C —
<22> Reference 11 Hz
are on.
Frequency reference when digital inputs "Multi-
d1-13 Frequency 0.00
Step Speed Reference 3, 4" (H1- = 5 and 32) A A A 28E —
<22> Reference 13 Hz
are on.
Frequency reference when digital inputs "Multi-
d1-14 Frequency 0.00
Step Speed Reference 1, 3, 4" (H1- = 3, 5, A A A 28F —
<22> Reference 14 Hz
32) are on.
Frequency reference when digital inputs "Multi- 0.00 to
d1-15 Frequency 0.00
Step Speed Reference 2, 3, 4" (H1- = 4, 5, 400.00 A A A 290 —
<22> Reference 15 Hz
32) are on. Hz
<11>
Frequency reference when digital inputs "Multi-
d1-16 Frequency <19> 0.00
Step Speed Reference 1, 2, 3, 4" (H1- = 3, 4, A A A 291 —
<22> Reference 16 Hz
5, 32) are on.
Frequency reference when digital inputs "Jog
Frequency Reference", "Forward Jog" or
d1-17 Jog Frequency 6.00
"Reverse Jog." are on. "Jog Frequency S S S 292 124
<22> Reference Hz
Reference" has priority over "Multi-Step Speed
Reference 1 to 16”.
d2: Frequency Upper and Lower Limits
Use d2 parameters to configure the frequency reference limits.
Sets the frequency reference upper limit as a
Frequency percentage of maximum output frequency (E1-
0.0 to 100.
d2-01 Reference Upper 04). Output speed is limited to this value even if A A A 289 —
110.0 0%
Limit the frequency reference is higher. This limit
applies to all frequency reference sources.
Sets the frequency reference lower limit as a
Frequency percentage of maximum output frequency (E1-
0.0 to 0.0
d2-02 Reference Lower 04). Output speed is limitedto this value even if A A A 28A —
110.0 %
Limit the frequency reference is lower. This limit
applies to all frequency reference sources.
Sets the minimum frequency reference lower
Master Speed limit if the frequency reference is input using an
0.0 to 0.0
d2-03 Reference Lower analog input. Set as a percentage of maximum A A A 293 —
110.0 %
Limit output frequency (E1-04). The higher of both
values d2-01 and d2-03 will be the lower limit.
326 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
d3: Jump Frequency
Use d3 parameters to configure the drive Jump Frequency settings.
d3-01 to d3-04 allow programming of three 0.0
d3-01 Jump Frequency 1 A A A 294 —
prohibited frequency reference points for Hz
eliminating problems with resonant vibration of 0.0
d3-02 Jump Frequency 2 the motor / machine. This feature does not A A A 295 —
0.0 to Hz
eliminate the selected frequency values, but
400.0
accelerates and decelerates the motor through
the prohibited bandwidth. 0.0
d3-03 Jump Frequency 3 A A A 296 —
The parameters must be according to the rule; Hz
d3-01 ≥ d3-02 ≥ d3-03.
This parameter sets the dead-band width around
Jump Frequency each selected prohibited frequency reference 0.0 to 1.0
d3-04 A A A 297 —
Width point. The bandwidth becomes the designated 20.0 Hz
Jump frequency, plus or minus d3-04.
d4: Frequency Reference Hold
Use d4 parameters to configure the drive frequency reference hold function.
This parameter is used to hold the last frequency
reference in U1-01 (d1-01) when power is
removed.
Frequency 0: Disabled
d4-01 Reference Hold 1: Enabled 0,1 0 A A A 298 —
Function Selection This function is available when the multi-
Parameter List
function inputs “accel/decel ramp hold” or “up/
down” commands are selected
(H1- = A or 10 and 11).
Sets the bias added to the frequency reference
when the Up/Down 2 digital inputs are set.
When set to 0.00 Hz, the bias value is increased
d4-03
<22>
Frequency or decreased according to d4-04. 0.00 to
Reference Bias Step When greater than 0.0 Hz, the bias value d4-03 99.99
0.00
Hz
A A A 2AA — B
(Up/Down 2) is added or subtracted to/from the frequency Hz
reference.
The acceleration or deceleration rate is
ultimately determined by d4-04.
0: Adjusts the bias value according to the
Frequency
d4-04 currently selected accel/decel time.
Reference Accel/ 0,1 0 A A A 2AB —
<22> 1: Adjusts the bias value by Accel/Decel Time 4
Decel (Up/Down 2)
(C1-07 and C1-08).
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 327
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
0: Holds the bias value when Up/Down 2
Frequency reference is on or off.
Reference Bias 1: When the Up 2 reference and Down 2
d4-05
Operation Mode reference are both on or both off, the applied 0,1 0 A A A 2AC —
<22>
Selection bias becomes 0. Currently selected accel/ decel.
(Up/Down 2) times are used.
Enabled only when d4-03 = 0.
100% = Max output frequency (E1-04).
Saves the bias value once the frequency
reference is adjusted.The bias can be set by the
user, but will be disabled under the following
conditions:
When none of the multi-function input terminals
are assigned +0 frequency reference bias
Frequency function.
-99.9 to 0.0
d4-06 Reference Bias When the frequency reference priority has A A A 2AD —
+100.0 %
(Up/Down 2) changed (including multi-step speed).
When both d4-03 = 0 and d4-05 = 1 while the
Up 2 / Down 2 commands are both on or both
off.
When the max output frequency has changed
(E1-04).
When the digital frequency reference has
changed.
• When the Up 2 and Down 2 commands are
enabled, the frequency reference holds the bias
value as the levels for the analog frequency
Analog Frequency
reference or pulse train frequency reference 0.1
d4-07 Reference 1.0
change, accelerating or decelerating to the to A A A 2AE —
<22> Fluctuation Limit %
frequency reference. After frequency agree is +100.0
(Up/Down 2)
achieved, the bias process starts again.
• Enabled only when the analog or pulse train
reference is on.
Frequency
When d4-06 is greater than d4-08, d4-08 0.1
d4-08 Reference Bias 0.0
becomes the bias for the upper limit. Set as a to A A A 2AF —
<22> Upper Limit (Up/ %
percentage of the max output frequency. 100.0
Down 2)
Frequency
When d4-06 is less than d4-09, d4-09 becomes
d4-09 Reference Bias -99.9 0.0
the bias for the lower limit. Set as a percentage A A A 2B0 —
<22> Lower Limit (Up/ to 0.0 %
of the max output frequency.
Down 2)
328 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Selects which value is used as frequency
reference lower limit if the Up/Down function is
Up/Down Frequency used.
d4-10 Reference Limit 0: The lower limit is determined by d2-02 or 0 or 1 0 A A A 2B6 —
Selection analog input (H3-02/10 = 0). The higher of both
values becomes the reference limit.
1: The lower limit is determined by d2-02.
Sets the gain used by the simple positioning stop 0.50 to
d4-12 Stop Position Gain 1.00 A A A 2B8
function to fine adjust the position. 2.55
d7: Offset Frequency
Use d7 parameters to set the offset frequency.
Added to the frequency reference when the -100.0
d7-01 0.0
Offset Frequency 1 digital input “Frequency Offset 1” to A A A 2B2 —
<22> %
(H1- = 44) is switched on. +100.0
Added to the frequency reference when the -100.0
d7-02 0.0
Offset Frequency 2 digital input “Frequency Offset 2” to A A A 2B3 —
<22> %
(H1- = 45) is switched on. +100.0
Added to the frequency reference when the -100.0
d7-03 0.0
Offset Frequency 3 digital input “Frequency Offset 3” to A A A 2B4 —
<22> %
(H1- = 46) is switched on. +100.0
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<19> Range upper limit is dependent on parameters E1-04, Maximum Output Frequency, and d2-01, Frequency
Parameter List
Reference Upper Limit.
<22> Parameter can be changed during run.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 329
B.2 Parameter Table
◆ E: Motor Parameters
Control
Mode
No. Name Description Range Def. O Addr. Pg.
P Hex
V/f L M
V
E1: V/f Pattern Characteristics
Use E1 parameters to set V/f characteristics for the motor.
This parameter must be set to the power
supply voltage. It sets the maximum and base
voltage used by preset V/f patterns (E1-03 = 0
to E) and adjusts levels used by certain
functions. Refer to page 130 for details
E1-01 Input Voltage 155 to
WARNING! Drive input voltage (not motor 200 V S S S 300 138
<24> Setting 255
voltage) must be set in E1-01 for the
protective features of the drive to function
properly. failure to do so may result in
equipment damage and/or death or personal
injury.
Selects a preset V/f pattern.
0: 50 Hz Constant torque 1
1: 60 Hz Constant torque 2
2: 60 Hz Constant torque 3 (50Hz base)
3: 72 Hz Constant torque 4 (60 Hz base)
4: 50 Hz Variable torque 1
5: 50 Hz Variable torque 2
6: 60 Hz Variable torque 3
V/f Pattern 7: 60 Hz Variable torque 4
E1-03 0 to F F A A − 302 —
Selection 8: 50 Hz High starting torque 1
9: 50 Hz High starting torque 2
A: 60 Hz High starting torque 3
B: 60 Hz High starting torque 4
C: 90 Hz (60 Hz base)
D: 120 Hz (60 Hz base)
E: 180 Hz (60 Hz base)
F: Custom V/f. E1-04 through E1-13 settings
define the V/f pattern.
330 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
40.0 to
Max Output 60 Hz
E1-04 400.0 S S S 303 139
Frequency <10>
<21>
E1-05 Max Output These parameters are only applicable when 0.0 to 230 V
E1-03 is set to F. To set linear V/f S S S 304 139
<24> Voltage 255.0 <10>
characteristics, set the same values for E1-07
Base 0.0 to 60 Hz
E1-06 and E1-09. In this case, the setting for E1-08 S S S 305 139
Frequency E1-04 <10>
will be disregarded. Ensure that the four
Mid Output frequencies are set according to these rules: 0.0 to 3.0 Hz
E1-07 A A A 306 —
Frequency E1-04 <2>
Mid Output E1-04 ≥ E1-06> E1-07 ≥ E1-09 18.4 V
E1-08 0.0 to
Frequency VACrms Out(V) <2> A A A 307 —
<24> 255.0
Voltage E1-05
<12>
E1-12 1.5 Hz
Minimum 0.0 to
E1-09 <2> S S S 308 139
Output Freq. E1-13 E1-04
<10>
Minimum 13.8 V
E1-10 0.0 to
Output Freq. <2> A A A 309 —
<24> E1-08 255.0
Voltage <12>
E1-11 Mid Output 0.0 to
0.0 Hz A A A 30A —
<26> Frequency 2 E1-10 E1-04
E1-12 Mid Output E1-09 E1-07 E1-06 E1-11 E1-04 0.0 to
<24> Frequency Frequency (Hz) 0.0 V A A A 30B —
Parameter List
255.0
<26> Voltage 2
E1-13 0.0 to
Base Voltage 0.0 V A S S 30C —
<24> 255.0
E2: Motor Parameters
Use E2 parameters to set motor-related data.
10 to
200% of
B
Sets the motor nameplate full load current in
Motor Rated drive
E2-01 amperes (A). Automatically set during <57> S S − 30E 398
Current rated
Auto-Tuning.
current
<27>
Sets the motor rated slip in Hertz (Hz).
Motor Rated 0.00 to
E2-02 Automatically set during rotational <57> A A − 30F —
Slip 20.00
Auto-Tuning.
Sets the magnetizing current of the motor as a
Motor 0 to less
percentage of the motor rated current (E2-01).
E2-03 No-Load than <57> A A − 310 —
Automatically set during rotational
Current E2-01
Auto-Tuning.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 331
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
Number of Sets the number of motor poles.
E2-04 2 to 48 4 poles A A − 311 —
Motor Poles Automatically set during Auto-Tuning.
Motor 0.000 to
Sets the phase-to-phase motor resistance in
E2-05 Line-to-Line 65.000 <57> A A − 312 —
ohms. Automatically set during Auto-Tuning.
Resistance <37>
Sets the voltage drop due to motor leakage
Motor
inductance as a percentage of motor rated 0.0 to
E2-06 Leakage <57> A A − 313 —
voltage. Automatically set during 40.0
Inductance
Auto-Tuning.
Motor
Sets the motor iron saturation coefficient at
Iron-Core E2-07 to
E2-07 75% of magnetic flux. Automatically set 0.50 − A − 314 —
Saturation 0.50
during Auto-Tuning.
Coefficient 1
Motor
Sets the motor iron saturation coefficient at
Iron-Core [E2-07]
E2-08 75% of magnetic flux. Automatically set 0.75 − A − 315 —
Saturation to 0.75
during during Auto-Tuning.
Coefficient 2
Sets the motor mechanical loss as a
percentage of motor rated power (kW).
Motor
Adjust in the following circumstances: 0.0 to
E2-09 Mechanical 0.0% − A − 316 —
When there is a large amount of torque loss 10.0
Loss
due to motor bearing friction.
When there is a large amount of torque loss.
Motor Iron
Loss for 0 to
E2-10 Sets the motor iron loss in watts (W). <57> A − − 317 —
Torque 65535
Compensation
Sets the motor rated power in kilowatts (kW). 0.40
Motor Rated 0.00 to
E2-11 Automatically set during Auto-Tuning. kW S S − 318 399
Output 650.00
(1HP = 0.746 kW). <12>
Motor Set to the motor iron saturation coefficient at
Iron-Core 130% of magnetic flux. 1.30 to
E2-12 1.30 − A − 328 —
Saturation Automatically set during rotational 5.00
Coefficient 3 Auto-Tuning.
E3: Motor 2 V/f Characteristics
Use E3 parameters to set the V/f pattern for a second motor.
Motor 2
0: V/f Control
E3-01 Control 0 or 2 0 A A − 319 —
2: Open Loop Vector (OLV)
Method
332 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
Motor 2 Max
40.0 to
E3-04 Output 60 Hz A A − 31A —
400.0
Frequency
E3-05 Motor 2 Max 0.0 to
These parameters set the V/f pattern for motor 230 V A A − 31B —
<24> Voltage 255.0
2.
Motor 2 Base 0.0 to
E3-06 To set linear V/f characteristics, set the same 60 Hz A A − 31C —
Frequency E3-04
values for E3-07 and E3-09. In this case, the
Motor 2 Mid setting for E3-08 will be disregarded. Ensure 0.0 to 3.0 Hz
E3-07 A A − 31D —
Output Freq. that the four frequencies are set according to E3-04 <53>
Motor 2 Mid these rules or OPE10 fault will occur: 18.4 V
E3-08 E3-04 ≥ E3-06 > E3-07 > E3-09 0.0 to
Output Freq. <12> A A − 31E —
<24> 255.0
Voltage VACrms Out (V) <53>
Motor 2 Min. E3-05 0.0 to 1.5 Hz
E3-09 E3-12
A A − 31F —
Output Freq. E3-04 <53>
Motor 2 Min. E3-13 13.8 V
E3-10 0.0 to
Output Freq. <12> A A − 320 —
<24> 255.0
Voltage <53>
Motor 2 Mid E3-08
E3-11 0.0 to
Output 0.0 Hz A A − 345 —
<26> E3-04
Frequency 2
E3-10
Motor 2 Mid
E3-12 0.0 to
Output E3-09 E3-07 E3-06 E3-11 E3-04 0.0
Parameter List
<24> 255.0 A A − 346 —
Frequency Frequency (Hz) Vac
<52> <24>
Voltage 2
0.0 to
E3-13 Motor 2 Base 0.0
255.0 A S − 347 —
<24> Voltage Vac
<24>
E4: Motor 2 Parameters
Use E4 parameters to control a second motor operating on the same drive. B
10 to
Sets the motor 2 name plate full load current 200% of
Motor 2 Rated
E4-01 in amperes (A). This value is automatically drive <57> A A − 321 —
Current
set during Auto-Tuning. rated
current
Sets the motor 2 name plate full load current
Motor 2 Rated 0.00 to
E4-02 in amperes (A). Automatically set during <57> A A − 322 —
Slip 20.00
Auto-Tuning.
Sets the magnetizing current of motor 2 in 0 to less
Motor 2 Rated
percentage of full load current (E4-01). than
E4-03 No-Load <57> A A − 323 —
Automatically set during Rotational [E4-01]
Current
Auto-Tuning. <27>
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 333
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
Sets the number of poles of motor 2. This
Motor 2 Motor
E4-04 value is automatically set during 2 to 48 4 poles A A − 324 —
Poles
Auto-Tuning.
Motor 2 0.000 to
Sets the phase-to-phase resistance of motor 2
E4-05 Line-to-Line 65.000 <57> A A − 325 —
in ohms. Automatically during Auto-Tuning.
Resistance <37>
Sets the voltage drop due to motor leakage
Motor 2
inductance as a percentage of rated voltage of 0.0 to
E4-06 Leakage <57> A A − 326 —
motor 2. Automatically set during 40.0
Inductance
Auto-Tuning.
Motor 2 Motor
Set to the motor iron saturation coefficient at
Iron-Core 0.00 to
E4-07 50% of magnetic flux. Automatically set 0.50 − A − 343 —
Saturation 0.50
during Rotational Auto-Tuning.
Coefficient 1
Motor 2 Motor Set to the motor iron saturation coefficient at Setting
Iron-Core 75% of magnetic flux. This value is for
E4-08 0.75 − A − 344 —
Saturation automatically set during Rotational E4-07 to
Coefficient 2 Auto-Tuning. 0.75
Sets the motor mechanical loss as a
percentage of motor rated power (kW)
Motor 2 capacity.
0.00 to
E4-09 Mechanical Adjust in the following circumstances: 0.0 − A − 33F —
10.0
Loss When there is a large amount of torque loss
due to motor bearing friction.
When there is a large amount of torque loss.
Motor 2 Iron 0 to
E4-10 Sets the motor iron loss in watts. <57> − A − 340 —
Loss 65535
Motor 2 Rated Sets the motor rated capacity in kW. 0.00 to
E4-11 <12> A A − 327 —
Capacity Automatically set during Auto-Tuning. 650.00
Motor 2
Set to the motor iron saturation coefficient at
Iron-Core 1.30 to
E4-12 130% of magnetic flux. Automatically set 1.30 − A − 342 —
Saturation 5.00
during Rotational Auto-Tuning.
Coefficient 3
Motor 2 Slip Sets the slip compensation gain for motor 2.
E4-14 0.0
Compensation The function is the same as C3-01 for motor 0.0 to 2.5 A A − 341 —
<22> <53>
Gain 1. Refer to the C3-01 description.
Torque Sets the torque compensation gain for motor
1.00 to
E4-15 Compensation 2. The function is the same as C4-01 for 1.00 A A − 341 —
2.50
Gain - Motor 2 motor 1. Refer to the C4-01 description.
334 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
E5: PM Motor Parameters
Enter the Yaskawa motor code for the PM
motor being used. Various motor parameters
are automatically set based on the value of
this parameter.
Note: Set to FFFF when using a specialized
or custom motor. For all other motors:
0000
Motor voltage
class and
capacity
Motor Code
E5-01 0: Pico motor 0: 1800 r/min 0000 to <12> <
Selection (for − − S 329 398
<25> (SMRA series) series FFFF 38>
PM motor)
1: Derated torque 1: 3600 r/min
IPM motor series
(SSR1 series) 2: 1750 r/min
2: Constant torque series
IPM motor 3: 1450 r/min
(SST4 series) series
4: 1150 r/min
series
F: Custom motor
All motor parameters are re-initialized to
factory settings when this parameter is set.
Parameter List
Motor Rated
E5-02 0.10 to
Capacity (for Sets the rated capacity of the motor. <10> − − S 32A 401
<25> 18.5
PM motor)
10 to
200% of
Motor Rated drive
E5-03 Sets the motor rated current in amps. <4> − − S 32B 401
Current rated
current B
<27>
E5-04
Motor Poles Sets the number of motor poles. 2 to 48 <10> − − S 32C 401
<25>
E5-05 Motor Set the resistance for each motor phase in 0.000 to
<10> − − S 32D 401
<25> Resistance units of 0.001 Ω. 65.000
E5-06 Motor d Axis Sets the d axis inductance in units of 0.00 to
<10> − − S 32E 401
<25> Inductance 0.01 mH. 300.00
E5-07 Motor q Axis Sets the q axis inductance in units of 0.00 to
<10> − − S 32F 401
<25> Inductance 0.01 mH. 600.00
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 335
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O P Addr. Pg.
V/f L M Hex
V
Set the induced phase peak voltage in units of
0.1 mV (rad/min) [electrical angle].
Set this parameter when using a Yaskawa
Motor SSR1 series PM motor with derate torque, or
E5-09 Induction a Yaskawa SST4 series motor with constant 0.0 to
<10> − − S 331 401
<25> Voltage torque. 2000.0
Constant 1 When setting this parameter, E5-24 should be
set to 0. An alarm will be triggered if both E5-
09 and E5-24 are set to 0, or if neither
parameter is set to 0.
Set the induced phase-to-phase rms voltage in
units of 0.1 mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa
SMRA series pico motor.
Motor
When setting this parameter, E5-09 should be
E5-24 Induction 0.0 to 0
set to 0. An alarm will be triggered if both E5- − − S 353 401
<25> Voltage 2000.0 <10>
09 and E5-24 are set to 0, or if neither
Parameter 2
parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0,
however, then an alarm will not be triggered
when both E5-09 and E5-24 are set to 0.
◆ F: Options
F parameters are used to program the drive for PG feedback and to function with option
cards.
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O
L P Hex
f V M
336 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets stopping method when a PG open circuit
fault (PGO) occurs. Refer to parameter F1-14.
0: Ramp to Stop - Decelerate to stop using the
Operation Selection at
active deceleration time.
F1-02 PG Open Circuit 0 to 3 1 A − − 381 —
1: Coast to Stop
(PGO)
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm only - Drive continues operation.
Sets the stopping method when an overspeed
(OS) fault occurs. Refer to F1-08 and F1-09.
0: Ramp to stop - Decelerate to stop using the
Operation Selection at active deceleration time.
F1-03 0 to 3 1 A − − 382 —
Overspeed (OS) 1: Coast to stop
2: Fast - Stop - Decelerate to stop using the
deceleration time in C1-09.
3: Alarm Only - Drive continues operation.
Sets the stopping method when a speed
deviation (DEV) fault occurs. Refer to F1-10
and F1-11.
0: Ramp to stop - Decelerate to stop using the
Operation Selection at
F1-04 active deceleration time. 0 to 3 3 A − − 383 —
Deviation
1: Coast to stop
2: Fast-stop - Decelerate to stop using the
deceleration time in C1-09.
Parameter List
3: Alarm only - Drive continues operation.
Sets the speed feedback level which has to be
exceeded for the time set in F1-09 before an
Overspeed Detection 115
F1-08 OS fault will occur. 0 to 120 A − − 387 —
Level %
Set as a percentage of the maximum output
frequency (E1-04).
F1-09
Overspeed Detection
Sets the time in seconds for which the speed
feedback has to exceed the overspeed detection
0.0 to
1.0 A − − 388 —
B
Delay Time 2.0
level F1-08 before an OS fault will occur.
Sets the allowable deviation between motor
Excessive Speed speed and frequency reference before a speed
F1-10 Deviation Detection deviation fault (DEV) is triggered. 0 to 50 10% A − − 389 —
Level Set as a percentage of the maximum output
frequency (E1-04).
Sets the time in seconds for which a deviation
Excessive Speed
between motor speed and frequency reference 0.0 to
F1-11 Deviation Detection 0.5 s A − − 38A —
has to exceed the speed deviation detection 10.0
Delay Time
level F1-10 before a DEV fault will occur.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 337
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the time for which no PG pulses must be
PG Open-Circuit 0.0 to
F1-14 detected before a PG Open (PGO) fault is 2.0 s A − − 38D —
Detection Time 10.0
triggered.
F6 and F7: Serial Communications Option Card Settings
Use F6 parameters to program the drive for serial communication.
Selects the operation after a communications
error occurred.
Communications
0: Ramp to stop using current accel/decel time
F6-01 Error operation 0 to 3 1 A A A 3A2
1: Coast to stop
Selection
2: Fast Stop using C1-09
3: Alarm only
Sets when an external fault from a comm
External fault from
option is detected.
F6-02 comm. option 0 or 1 0 A A A 3A3
0: Always detected
selection
1: Detection during Run only
Selects the operation after an external fault set
by a communications option (EF0).
External fault from
0: Ramp to stop using current accel/decel time
F6-03 comm. option 0 to 3 1 A A A 3A4
1: Coast to stop
operation selection
2: Fast Stop using C1-09
3: Alarm only
0.0 to
F6-04 Trace Sampling Rate - 2.0 s A A A 3A5
5.0
CC-Link Node Sets the node address if a CC-Link option card
F6-10 0 to 63 0 A A A 3E6
Address is installed
0: 156 Kbps
CC-Link 1: 625 Kbps
F6-11 communications 2: 2.5 Mbps 0 to 4 0 A A A 3E7
speed 3: 5 Mbps
4: 10 Mbps
Selects if a BUS fault can be automatically
F6-14 BUS Error auto reset 0 or 1 0 A A A 3BB
reset.
DeviceNet MAC
F6-20 Selects the drives MAC address for DeviceNet 0 to 63 0 A A A 3C1
Address
0: 125 kbps
Device Net
1: 250 kbps
F6-21 Communications 0 to 3 3 A A A 3C2
2: 500 kbps
Speed
3: Detect automatically
DeciveNet PCA
F6-22 I/O Polled Consuming Assembly Data Instance 0 to 255 0 A A A 3C3
setting
F6-23 DeciveNet PPA setting I/O Polled Producing Assembly Data Instance 0 to 255 0 A A A 3C4
338 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Selects if a fault s is detected during
DeciveNet Idle mode communication idle mode.
F6-24 0 or 1 0 A A A 3C5
fault detection 0: Disabled
1: Enabled
F6-30 Profibus node address Sets the node address for a Profibus option. 0 to 125 0 A A A 3CB
Selects the operation when a "Clear Mode"
Profibus Clear mode command is received.
F6-31 0 or 1 0 A A A 3CC
selection 0: Resets back to zero.
1: Maintains the previous value.
Profibus Map 0: PPO Type
F6-32 0 or 1 0 A A A 3CD
selections 1: Conventional
CANopen Node ID
F6-36 Sets the Node ID for a CANopen option 0 to 127 99 A A A 3D0
selection
0: Auto-adjust
1: 10kbps
2: 20 kbps
CANopen 3: 50 kbps
F6-37 Communications 4: 125 kbps 0 to 8 6 A A A 3D1
speed 5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
F6-40 CompoNet Node ID Sets the Node ID for a CompoNet option. 0 to 63 0 A A A 3D5
Parameter List
0: 93.75kbit/s
1: Reserved
2: 1.5Mbit/s
F6-41 CompoNet Speed 0 to 255 0 A A A 3D6
3: 3Mbit/s
4: 4Mbit/s
5-255: Reserved
F7-01 Ethernet IP Address 1 0 to 255 0 A A A 3E5 B
F7-02 Ethernet IP Address 1 Combining these parameters like F7-01.F7- 0 to 255 0 A A A 3E6
02.F7-03.F7-04 sets the Ethernet IP address.
F7-03 Ethernet IP Address 1 Example: (192.168.1.10) 0 to 255 0 A A A 3E7
F7-04 Ethernet IP Address 1 0 to 255 0 A A A 3E8
F7-05 Subnet Mask 1 0 to 255 0 A A A 3E9
F7-06 Subnet Mask 2 Combining these parameters like F7-05.F7- 0 to 255 0 A A A 3EA
06.F7-07.F7-08 sets the Ethernet Subnet
F7-07 Subnet Mask 3 Mask.Example: (255.255.255.0) 0 to 255 0 A A A 3EB
F7-08 Subnet Mask 4 0 to 255 0 A A A 3EC
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 339
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
F7-09 Gateway Address 1 0 to 255 0 A A A 3ED
F7-10 Gateway Address 2 Combining these parameters like F7-09.F7- 0 to 255 0 A A A 3EE
10.F7-11.F7-12 sets the Ethernet Gateway
F7-11 Gateway Address 3 Address.Example: (192.168.1.1) 0 to 255 0 A A A 3EF
F7-12 Gateway Address 4 0 to 255 0 A A A 3F0
Selects how the Ethernet IP address is set.
0:User defined
F7-13 Dress Mode at Startup 0 to 2 0 A A A 3F1
1:BOOTP
2:DHCP
Sets the password required for setup changes
via the network. 0 to
F7-14 Security password 0 A A A 3F2
0: No password required 9999
1 - 9999: 4 digit password
0:Auto Negotiate
Duplex Mode
F7-15 1:Half Duplex forced 0 to 2 0 A A A 3F3
Selection
2:Full Duplex forced
0:Auto Negotiate
Communication Speed 0, 10,
F7-18 10:10 Mbps speed setting 0 A A A 3F6
Selection 100
100:100Mbps Speed Setting
Selects the mode for modification on the
Ethernet option board Web page settings
F7-19 Web Page Access 0: All access 0 to 2 0 A A A 3F7
1: Only during stop
2: Never
0: Gateway not used
F7-20 Gateway selection 0 or 1 1 A A A 3F8
1: Use Gateway
Communication loss Multiplier for communication loss detection
F7-21 0 to 300 0 A A A 3F9
time out timeout value.
340 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ L P Hex
f M
V
H1: Multi-Function Digital Input
H1 parameters to assign functions to the multi-function digital input terminals. Unused terminals should be set to "F".
Multi-Function Digital Input Terminal
H1-01 40 A A A 438 —
S1 Function Selection
Multi-Function Digital Input Terminal
H1-02 41 A A A 439 —
S2 Function Selection
Multi-Function Digital Input Terminal Selects the function of
H1-03 24 A A A 400 —
S3 Function Selection terminals S1 to S7
Multi-Function Digital Input Terminal Refer to “Multi-Function 1 to 9F
H1-04 14 A A A 401 —
S4 Function Selection Digital Input Selection <40>
Multi-Function Digital Input Terminal Table” for a description of 3(0)
H1-05 setting values. A A A 402 —
S5 Function Selection <18>
Multi-Function Digital Input Terminal 4(3)
H1-06 A A A 403 —
S6 Function Selection <18>
Multi-Function Digital Input Terminal 6(4)
H1-07 A A A 404 —
S7 Function Selection <18>
<18> Parenthetical value is the default when parameter A1-03 = 3330 3-Wire Initialization.
<40> The availability of certain functions depends on the control method used.
Parameter List
H1 Multi-Function Digital Input Selections
Control
H1- Mode
Function Description Pg.
Setting V/ O P
f LV M
Closed: Reverse rotation (only if the drive is set up for 3-
0 3-Wire Sequence
wire sequence)
O O O —
B
Open: Remote, Reference 1 or 2 (b1-01/02 or b1-15/16)
1 Local/Remote Selection O O O —
Closed: Local, LED operator is run and reference source
Open: Run and frequency reference source 1 (b1-01/02)
2 External Reference 1/2 O O O —
Closed: Run and frequency reference source 2 (b1-15/16)
3 Multi-Step Speed Reference 1 O O O —
4 Multi-Step Speed Reference 2 Used to select Multi-Step Speeds set in d1-01 to d1-16 O O O —
5 Multi-Step Speed Reference 3 O O O —
Open: Selected speed reference
6 Jog Reference Selection Closed: Jog Frequency reference (d1-17). Jog has O O O —
priority over all other reference sources.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 341
B.2 Parameter Table
342 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
35 PID Input Switch Closed: Inverses the PID input signal O O O —
Open: Stop
Forward Run Command
40 Closed: Forward run Note: Can not be set together with O O O —
(2-wire sequence)
Settings 42 or 43.
Open: Stop
Reverse Run Command
41 Closed: Reverse run Note: Can not be set together with O O O —
(2-wire sequence)
Settings 42 or 43.
Open: Stop
B
Run Command (2-wire
42 Closed: Run Note: Can not be set together with Settings O O O —
sequence 2)
40 or 41.
Open: Reverse
FWD/REV Command (2-wire
43 Closed: Forward Note: Can not be set together with O O O —
sequence 2)
Settings 40 or 41.
44 Offset Frequency 1 Addition Closed: Adds d7-01 to the frequency reference. O O O —
45 Offset Frequency 2 Addition Closed: Adds d7-02 to the frequency reference. O O O —
46 Offset Frequency 3 Addition Closed: Adds d7-03 to the frequency reference. O O O —
DC Injection Braking
60 Closed: Triggers DC Injection Braking (b2-02) O O - —
Command
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 343
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
L M
f V
344 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Terminal MA, MB and MC
H2-01 E A A A 40B —
Function Selection (relay)
Refer to “Multi-Function Digital
Terminal P1 Function Selection 0 to 192
H2-02 Output Selection Table” for a 0 A A A 40C —
(open-collector) <40>
description of setting values.
Terminal P2 Function Selection
H2-03 2 A A A 40D —
(open-collector)
Sets the display units for one of the
multi-function output terminals that
is assigned to output the watt hours
(H2- = 39) is the value every
200 ms. An output pulse of 200 ms
is provided for every kWh that
occurs. Intended to drive a counter,
H2-06 Watt Hour Output Unit Selection 0 to 4 0 A A A 437 —
meter or PLC for logging kWh.
<40> The availability of certain functions depends on the control method used.
Parameter List
H2 Multi-Function Digital Output Settings
Control
Mode
H2-
Function Description Pg.
Setting V/ O
L P
f V M
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 345
B.2 Parameter Table
346 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
the time set in b5-14.
Closed: PID Feedback Fault.PID feedback value exceeds the level
3F PID Feedback Fault O O O —
set to b5-36 for longer than the time set to b5-37.
4A KEB Operation Closed: KEB is being performed. O O O —
4B Short-Circuit Brake Closed: Short-Circuit Braking is active. − − O —
4C During Fast-stop Closed: Fast-stop command is entered O O O — B
OH Pre-alarm Time
4D Closed: OH Pre-alarm time limit is passed. O O O —
Limit
Reverse the output switching of the multi-function output
functions. Set the last two digits of 1 to reverse the output
H2 Parameter
signal of that specific function.Examples:
100 to Functions Reversed
Setting “108” reverses the output of “During baseblock,” which is O O O —
14D Output Switching of 0
setting value 08.
to 92
Setting “14A” reverses the output of “During KEB operation”,
which is setting “4A”.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 347
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ L P Hex
f M
V
H3: Analog Inputs
Use H3 parameters to set the multi-function analog input terminals.
Sets the input level for terminal A1.
Terminal A1 Signal
H3-01 0: 0 to +10 V (lower limit) 0, 1 0 A A A 410 —
Level Selection
1: 0 to +10 V (no lower limit)
Sets the function of terminal A1. When
Terminal A1 Function 0 to 31
H3-02 terminal A1 is not used or is used as a through 0 A A A 434 —
Selection <40>
terminal, this parameter must be set to “F”.
H3-03 Terminal A1 Gain Sets the level of the input value selected in -999.9 to 100.
A A A 411 —
<22> Setting H3-02 when 10V is input at terminal A1. 999.9 0%
H3-04 Terminal A1 Bias Sets the level of the input value selected in -999.9 to 0.0
A A A 412 —
<22> Setting H3-02 when 0V is input at terminal A1. 999.9 %
Sets the input signal level for terminal A2. 0 to 3 2 A A A 417 —
0: 0 to +10 V (with lower limit) Switch between current or voltage
Terminal A2 Signal
H3-09 1: 0 to +10 V (no lower limit) inputs by using DIP switch S1-2
Level Selection
2: 4 to 20 mA switch on the terminal board. Refer
3: 0 to 20 mA to I/O Connections on page 77.
Sets the function of terminal A2. When
Terminal A2 Function 0 to 31
H3-10 terminal A2 is not used or is used as a through 0 A A A 418 —
Selection <40>
terminal, this parameter must be set to “F”.
Sets the level of the input value selected in
H3-11 Terminal A2 Gain -999.9 to 100.
H3-10 when 10 V (20 mA) is input at terminal A A A 419 —
<22> Setting 1000.0 0%
A2.
Sets the level of the input value selected in
H3-12 Terminal A2 Input -999.9 to 0.0
H3-10 when 0 V (0 or 4 mA) is input at A A A 41A —
<22> Bias 999.- %
terminal A2.
Analog Input Filter Sets the primary delay filter time constant for 0.00 to 0.0
H3-13 A A A 41B —
Time Constant terminals A1 and A2. Used for noise filtering. 2.00 3s
348 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
Parameter List
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
L M
f V
Multi-Function
function analog output terminal AM. Set the
desired monitor parameter to the digits 000 to
B
H4-01 Analog Output available in U-. For example, enter 999 102 A A A 41D —
Terminal AM) “103” for U1-03. <40>
When using this terminal in trough mode or
when not using it at all, set “000” or “031”.
Multi-Function Sets terminal AM output level when selected -999.9
H4-02 100.
Analog Output monitor is at 100%. Maximum output voltage to S S S 41E —
<22> 0%
Terminal AM Gain is 10 V. 999.9
Multi-Function -999.9
H4-03 Sets terminal AM output level when selected 0.0
Analog Output to A A A 41F —
<22> monitor is at 0%. %
Terminal AM Gain 999.9
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 349
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
H5: MEMOBUS/Modbus Communications
Use H5 Parameters to connect the drive to a MEMOBUS/Modbus network.
Selects drive station node number (address) for
H5-01 0 to 20
Drive Node Address MEMOBUS/Modbus terminals R+, R-, S+, S-. 1F A A A 425 —
<39> H
Cycle power for the setting to take effect.
Selects the baud rate for MEMOBUS/Modbus
terminals R+, R-, S+ and S-. Cycle power for
the setting to take effect.
0: 1200 bps
1: 2400 bps
Communication 2: 4800 bps
H5-02 0 to 8 3 A A A 426 —
Speed Selection 3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Selects the communication parity for
MEMOBUS/Modbus terminals R+, R-, S+ and
Communication S-. Cycle power for the setting to take effect.
H5-03 0 to 2 0 A A A 427 —
Parity Selection 0: No parity
1: Even parity
2: Odd parity
Selects the stopping method when a
communication time-out fault (CE) is detected.
Stopping Method
0: Ramp to stop
H5-04 After Communication 0 to 3 3 A A A 428 —
1: Coast to stop
Error
2: Fast-stop
3: Alarm only
Enables or disables the communications time-
out fault (CE) detection.
Communication Fault
H5-05 0: Disabled 0,1 1 A A A 429 —
Detection Selection
1: Enabled - If communication is lost for more
than two seconds, a CE fault will occur.
Drive Transmit Wait Set the wait time between receiving and
H5-06 5 to 65 5 ms A A A 42A —
Time sending data.
Selects "request to send" (RTS) control:
RTS Control
H5-07 0: Disabled - RTS is always on. 0,1 1 A A A 42B —
Selection
1: Enabled - RTS turns on only when sending.
Sets the time required to detect a
0.0 to
H5-09 CE Detection Time communications error. Adjustment may be 2.0 s A A A 435 —
10.0 s
need when networking several drives.
350 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Selects the units used for MEMOBUS/Modbus
Unit Selection for register 0025H (Output Voltage Reference
H5-10 MEMOBUS/Modbus Monitor). 0, 1 0 A A A 436 —
Register 0025H 0: 0.1 V units
1: 1 V units
Select the function for the enter command that
saves parameter data to the drive.
Communications 0: Parameter changes are activated when
H5-11 ENTER Function ENTER command is entered. 0, 1 1 A A A 43C —
Selection 1: Parameter changes are activated
immediately without ENTER command
(compatible with Varispeed VS606-V7).
Run Command 0: FWD/STOP, REV/STOP Method
H5-12 0, 1 0 A A A 43D —
Method Selection 1: RUN/STOP, FWD/REV Method
H6: Pulse Train Input/Output
Use H6 parameters to configure Pulse Train I/O operation.
Selects pulse train input function.
0: Frequency reference
Pulse Train Input 1: PID feedback value
H6-01 Terminal RP Function 2: PID setpoint value 0 to 3 0 A A A 42C —
Selection 3: Simple PG V/f control mode (can be set
only when using motor 1 in the V/f control
mode)
Parameter List
H6-02 Pulse Train Input Sets the number of pulses (Hz) that is equal to 1000 to 1440
A A A 42D —
<22> Scaling 100% of the value selected in H6-01. 32000 Hz
Sets the level of the value selected in H6-01
H6-03 Pulse Train Input 0.0 to 100.
when a frequency with the value set in H6-02 A A A 42E —
<22> Gain 1000.0 0%
is input.
-100.0
H6-04
<22>
Pulse Train Input Bias
Sets the level of the value selected in H6-01
when 0 Hz is input.
to
0.0
%
A A A 42F — B
+100.0
H6-05 Pulse Train Input 0.00 to 0.10
Sets the pulse train input filter time constant. A A A 430 —
<22> Filter Time 2.00 s
000,
Select the pulse train monitor output function
031,
(value of the - part of U-). Refer
101,
Pulse Train Monitor to U: Monitors on page 376 for the list of U
H6-06 102,
Terminal MP monitors. 102 A A A 431 —
<22> 105,
Selection Example: To select U5-01, set “501.”
116,
When not using this parameter or when using
501,
in the through mode, set “000”.
502
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 351
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the pulse output frequency in Hz when the
H6-07 Pulse Train Monitor monitor value is 100%. Set H6-06 to “2” and 0 to 1440
A A A 432 —
<22> Scaling H6-07 to “0”, to make the pulse train monitor 32000 Hz
output equal to the output frequency.
◆ L: Protection Function
L parameters provide protection to the drive and motor, such as: control during momentary
power loss, stall prevention, frequency detection, fault restarts, overtorque detection, torque
limits and other types of hardware protection.
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f VL M
352 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the motor thermal overload protection
(OL1) time. A larger L1-02 time will increase
Motor Overload the time for an OL1 fault to occur. 0.1 to 1.0
L1-02 A A A 481 —
Protection Time This parameter does not typically require 5.0 min
adjustment. Should be set in accordance with
the overload tolerance of the motor.
Sets operation when the motor temperature
analog input (H3-02/10 = E) exceeds the OH3
Motor Overheat alarm level.
L1-03 Alarm Operation 0: Ramp to Stop 0 to 3 3 A A A 482 —
Selection (PTC input) 1: Coast to Stop
2: Fast-stop using C1-09
3: Alarm Only (“oH3” will flash)
Sets stopping method when the motor
temperature analog input (H3-02/10 = E)
Motor Overheat Fault
exceeds the OH4 fault level.
L1-04 Operation Selection 0 to 2 1 A A A 483 —
0: Ramp to Stop
(PTC input)
1: Coast to Stop
2: Fast-stop
This parameter adjusts the filter on the motor
Motor Temperature
temperature analog input (H3-02 or H3-10 = 0.00 to 0.20
L1-05 Input Filter Time A A A 484 —
E). Increase to add stability, decrease to 10.00 s
(PTC input)
improve response.
Parameter List
Determines whether or not to hold the
Continuous electrothermal value when the power supply is
L1-13 Electrothermal interrupted. 0 to 1 1 A A A 46D —
Operation Selection 0: Disabled
1: Enabled
L2: Momentary Power Loss
Use L2 parameters to configure drive functions for momentary power loss conditions.
Enables and disables the momentary power 0 to 2 0 A A A 485
B
loss function.
0: Disabled - Drive trips on (UV1) fault when
Momentary Power power is lost. For a restart to occur, the run
L2-01 Loss Operation 1: Power Loss Ride-Thru Time - Drive will command must be maintained —
Selection restart if power returns within the time set in throughout the ride-thru
L2-02. period.
2: CPU Power Active - Drive will restart if
power returns as long as the CPU is working.
Momentary Power Sets the Power Loss Ride-Thru time. Only 0.0 to
L2-02 <12> A A A 486 —
Loss Ride-Thru Time effective when L2-01 = 1. 25.5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 353
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the minimum wait time for residual motor
Momentary Power voltage decay before the drive output
0.1 to
L2-03 Loss Minimum reenergizes after power loss ride-thru. If L2-03 <57> A A A 487 —
5.0
Baseblock Time is greater than L2-02, operation resumes after
the time set in L2-03.
Momentary Power
Sets the time for the output voltage to return to 0.0 to
L2-04 Loss Voltage <12> A A A 488 —
the preset V/f pattern during speed search. 5.0
Recovery Ramp Time
Sets the DC Bus undervoltage trip level. If this
is set lower than the default setting, additional
AC input impedance or DC bus reactance may
L2-05 Undervoltage 150 to <9>
be necessary. Consult with the manufacturer A A A 489 —
<24> Detection Level (UV) 210 <12>
before changing this parameter setting.
This value is used for KEB activation if L2-01
> 0.
KEB Deceleration Sets the time required to decelerate from the 0.0 to
L2-06 0.0 s A A A 48A —
Time speed when KEB was activated to zero speed. 200.0
Set the time to accelerate to the set speed after
KEB Acceleration 0.0 to
L2-07 recovery from a momentary power loss. If set 0.0 s A A A 48B —
Time 25.5
to 0.0, the active acceleration time is used.
Sets the percentage of output frequency
reduction at the beginning of deceleration
KEB Start Output when a KEB command is input from multi- 100
L2-08 0 to 300 A A A 48C —
Frequency Reduction function input. %
Reduction = (slip frequency before KEB) x
L2-08 x 2
E1-
L2-11 Desired DC Bus Sets the desired value of the DC bus voltage 150 to
01 A A A 461 —
<24> Voltage during KEB during KEB. 400 V
1.22
354 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
L3: Stall Prevention Function
Use L3 parameters to configure the stall prevention function.
Selects the stall prevention method used to
prevent excessive current during acceleration.
0: Disabled - Motor accelerates at active
acceleration rate. The motor may stall if load is
too heavy or accel time is too short.
Stall Prevention 1: General Purpose - When output current
0 to 2
L3-01 Selection during exceeds L3-02 level, acceleration stops. 1 A A A 48F —
<29>
Acceleration Acceleration will continue when the output
current level falls below the L3-02 level.
2: Intelligent - The active acceleration rate is
ignored. Acceleration is completed in the
shortest amount of time without exceeding the
current value set in L3-02.
Used when L3-01 = 1 or 2.
Stall Prevention Level 100% is equal to the drive rated current.
L3-02 0 to 150 <7> A A A 490 —
during Acceleration Decrease the set value if stalling or excessive
current occurs with default setting.
Sets stall prevention lower limit during
Stall Prevention Limit acceleration when operating in the constant
L3-03 0 to 100 50% A A A 491 —
during Acceleration power range. Set as a percentage of the drive's
rated current.
Parameter List
B
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 355
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
When using a braking resistor, use setting "0".
Setting "3" is used in specific applications.
0: Disabled - The drive decelerates at the active
deceleration rate. If the load is too large or the
deceleration time is too short, an OV fault may
occur.
1: General Purpose - The drive decelerates at
the active deceleration rate, but if the main
circuit DC bus voltage reaches the stall
prevention level (380/760 VDC), deceleration
Stall Prevention will stop. Deceleration will continue once the
0 to 4
L3-04 Selection during DC bus level drops below the stall prevention 1 S S S 492 356
<50>
Deceleration level.
2: Intelligent - The active deceleration rate is
ignored and the drive decelerates as fast as
possible without hitting OV fault level.
Range: C1-02 / 10.
3: Stall Prevention with Braking Resistor -
Stall prevention during deceleration is enabled
in coordination with dynamic braking.
4: Overexcitation Deceleration - Decelerates
with the flux level determined by n3-13
(Overexcitation Gain).
Selects the stall prevention method to use to
prevent drive faults during run.
0: Disabled - Drive runs a set frequency. A
heavy load may cause the drive to trip on an
OC or OL fault.
1: Decel Time 1 - The drive will decelerate at
Decel Time 1 (C1-02) if the output current
Stall Prevention exceeds the level set by L3-06. Once the
L3-05 0 to 2 1 A − A 493 —
Selection during Run current level drops below the L3-06 level, the
drive will accelerate back to its frequency
reference at the active acceleration rate.
2: Decel Time 2 - Same as setting 1 except the
drive decelerates at Decel Time 2 (C1-04).
When output frequency is 6 Hz or less, stall
prevention during run is disabled regardless of
the setting in L3-05.
Enabled when L3-05 is set to "1" or "2". 100%
Stall Prevention Level is equal to the drive rated current.Decrease the 30 to
L3-06 <7> A − A 494 —
during Run set value if stalling or excessive current occurs 200
with the default settings.
356 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Enables or disables OV suppression function,
which allows the drive to change the output
frequency as the load changes, thus preventing
an OV fault.
0: Disabled
OV Suppression
L3-11 1: Enabled 0, 1 0 A A - 4C7 —
Function Selection
Note: The frequency reference and motor
speed diverge as the regenerative energy
begins to flow back into the DC bus and
triggers the OV suppression function. Disable
this function when using a braking resistor.
Overvoltage Sets the desired value for the DC bus voltage
370
L3-17 Suppression and Stall during overvoltage suppression and stall 150 to
V A A A 462 —
<24> Prevention Desired prevention during deceleration. Enabled only 400 V
<9>
DC Bus Voltage when L3-04 = 2.
Sets the proportional gain used by KEB, Stall
Main Power Circuit prevention and overvoltage suppression.
0.00 to
L3-20 Voltage Adjustment If OV or UV1 occurs at the beginning of KEB 1.00 A A A 465 —
5.00
Gain deceleration, slowly increase this setting by
0.1.
Sets the proportional gain used to calculate the
deceleration rate during KEB, OV suppression
function and stall prevention during
Accel/Decel Rate 0.00 to
L3-21 deceleration (L3-04 = 2). 1.00 A A A 466 —
Parameter List
Calculation Gain 200.00
This parameter does not typically require
adjustment. Increase the value in steps of 1.0 if
overcurrent and overvoltage occur.
Sets the deceleration time used for stall
Deceleration Time at prevention during acceleration in Open Loop
0.0 to
L3-22 Stall Prevention Vector control for PM motors. 0.0 s − − A 4F9 —
during Acceleration When set to 0, the drive decelerates at the
normal deceleration time.
6000.0
B
0: Sets the stall prevention level throughout the
Automatic Reduction entire frequency range to the value in
Selection for Stall parameter L3-06.
L3-23 0, 1 0 A A Α 4FD —
Prevention during 1: Automatically lowers the stall prevention
Run level in the constant output range. The lower
limit value is 40% of L3-06.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 357
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the time needed to accelerate the
uncoupled motor at rated torque from stop to
Motor Acceleration
the maximum frequency. 0.001 to
L3-24 Time for Inertia <57> A A A 46E —
Setting the drive capacity to parameter o2-04 10.000
Calculations
or changing E2-11 will automatically set this
parameter for a 4-pole motor.
Sets the ratio between the motor and machine 0.0 to
L3-25 Load Inertia Ratio 1.0 A A A 46F —
inertia. 1000.0
L4: Frequency Detection
Use L4 parameters to configure frequency detection operation.
Speed Agreement These parameters configure the multi-function 0.0 to 0.0
L4-01 A A A 499 —
Detection Level output (H2- = 2, 3, 4, 5) settings "Fref/ 400.0 Hz
Fout Agree 1", "Fref/Set Agree 1", "Frequency
Detection 1," and "Frequency detection 2".
Speed Agreement Parameter L4-01 sets the level while parameter 0.0 to 2.0
L4-02 A A A 49A —
Detection Width L4-02 sets the hysteresis for the Speed 20.0 Hz
Detection Output Function.
These parameters configure the Multi-Function -400.0
Speed Agreement 0.0
L4-03 Output (H2- = 13, 14, 15, 16) settings to A A A 49B —
Detection Level (+/-) Hz
"Fref/Fout Agree 2", "Fref/Set Agree 2", +400.0
"Frequency Detection 3," or "Frequency
Detection 4".
Speed Agreement Parameter L4-03 sets the level while parameter 0.0 to 2.0
L4-04 A A A 49C —
Detection Width (+/-) L4-04 sets the hysteresis for the Speed 20.0 Hz
Detection Output Function.
Sets operation when the frequency reference is
lost (reference drops 90% or more of within
Frequency Reference 400 ms).
L4-05 Loss Detection 0: Stop - Drive will stop. 0,1 0 A A A 49D —
Selection 1: Run at L4-06 PrevRef - Drive will run at the
percentage set in L4-06 of the frequency
reference before loss.
Sets the frequency reference when a reference
Frequency Reference 0.0 to 80.0
L4-06 loss was detected and L4-05 = 1. Reference A A A 4C2 —
at Reference Loss 100.0 %
will be: Fref = Fref at time of loss L4-06.
Frequency Detection 0: No detection during baseblock.
L4-07 0 to 1 0 A A A 470H —
Conditions 1: Detection always enabled.
358 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
L5: Fault Reset
Use L5 parameters to configure Automatic Restart after fault.
Sets the counter for the number of times the
drive attempts to restart when the following
faults occur: GF, LF, OC, OV, PF, PUF, RH,
Number of Auto RR, OL1, OL2, OL3, OL4, UV1. If the drive
L5-01 0 to 10 0 A A A 49E —
Restart Attempts faults after an auto restart attempt, the counter
is incremented.
When the drive operates without fault for 10
minutes, the counter will be reset.
Sets fault contact activation during automatic
restart attempts.
Auto Restart
L5-02 0: Fault output (H2-oo = E) not active. 0,1 0 A A A 49F —
Operation Selection
1: Fault output (H2-oo = E) active during
restart attempt.
Sets the amount of time to wait between
Fault Reset Interval 0.5 to 10.0
L5-04 performing fault restarts. Enabled when L5-05 A A A 46C —
Time 600.0 s s
is set to 1.
Selects the method of incrementing the restart
counter.
0: Continuously attempt to restart and
Fault Reset Operation increment counter after successful restart (like
L5-05 0 to 1 0 A A A 467 —
Selection Varispeed VS616-F7/G7)
Parameter List
1: Attempt to restart with the interval time set
in L5-04. Every trial increments the counter.
(like Varispeed VS606-V7)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 359
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
L6: Overtorque Detection
Use L6 parameters to configure overtorque detection.
Selects the overtorque/undertorque operation.
overtorque and undertorque are determined by
the settings in parameters L6-02 and L6-03.
The multi-function output settings (H2- =
B and 17) are also active if programmed.
0: Disabled
1: OL3 at Speed Agree - Alarm (overtorque
detection only active during Speed Agree and
operation continues after detection).
2: OL3 at RUN - Alarm (overtorque detection
is always active and operation continues after
detection).
3: OL3 at Speed Agree - Fault (overtorque
detection only active during Speed Agree and
Torque Detection drive output will shut down on an OL3 fault).
L6-01 0 to 8 0 A A A 4A1 —
Selection 1 4: OL3 at RUN - Fault (overtorque detection is
always active and drive output will shut down
on an OL3 fault).
5: UL3 at Speed Agree - Alarm (undertorque
detection is only active during Speed Agree
and operation continues after detection).
6: UL3 at RUN - Alarm (undertorque detection
is always active and operation continues after
detection).
7: UL3 at Speed Agree - Fault (undertorque
detection only active during Speed Agree and
drive output will shut down on an OL3 fault).
8: UL3 at RUN - Fault (undertorque detection
is always active and drive output will shut
down on an OL3 fault).
Sets the overtorque/undertorque detection
Torque Detection level. 100% is equal to the motor rated current 150
L6-02 0 to 300 A A A 4A2 —
Level 1 in V/f control and the motor rated torque in %
Open Loop Vector control.
Sets the length of time an overtorque/
Torque Detection 0.0 to
L6-03 undertorque condition must exist before 0.1 s A A A 4A3 —
Time 1 10.0
Torque Detection 1 is triggered.
360 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the response to an overtorque/undertorque
condition. overtorque and undertorque are
determined by the settings in parameters L6-05
and L6-06. The multi-function output settings
(H2- = 18 and 19).
0: Disabled
1: OL4 at Speed Agree - Alarm (overtorque
Detection only active during Speed Agree and
Operation continues after detection).
2: OL4 at RUN - Alarm (overtorque Detection
is always active and operation continues after
detection).
3: OL4 at Speed Agree - Fault (overtorque
Detection only active during Speed Agree and
Torque Detection drive output will shut down on an OL4 fault).
L6-04 0 to 8 0 A A A 4A4 —
Selection 2 4: OL4 at RUN - Fault (overtorque Detection
is always active and drive output will shut
down on an OL4 fault).
5: UL4 at Speed Agree - Alarm (undertorque
Detection is only active during Speed Agree
and operation continues after detection).
6: UL4 at RUN - Alarm (undertorque
Detection is always active and operation
continues after detection).
7: UL4 at Speed Agree - Fault (undertorque
Parameter List
Detection only active during Speed Agree and
drive output will shut down on an OL4 fault).
8: UL4 at RUN - Fault (undertorque Detection
is always active and drive output will shut
down on an OL4 fault).
Sets the overtorque/undertorque detection
L6-05
Torque Detection
Level 2
level. 100% is equal to the motor rated current
in V/f control and the motor rated torque in
0 to 300
150
%
A A A 4A5 — B
Open Loop Vector control.
Sets the length of time an overtorque/
Torque Detection 0.0 to
L6-06 undertorque condition must exist before torque 0.1 s A A A 4A6 —
Time 2 10.0
detection 2 is recognized by the drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 361
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
This function can detect an over/undertorque in
a certain speed range as a result of machine
fatigue. It is triggered by a certain operation
time and uses the OL1 detection settings (L6-
01 to L6-03)
0: Mechanical Weakening Detection disabled.
1: Continue running if the speed (signed) is
greater than L6-09 (alarm only).
2: Continue running if the speed (not signed) is
greater than L6-09 (alarm only).
3: Interrupt drive output when the motor speed
(signed) is greater than L6-09 (protection
Mechanical
operation).
L6-08 Weakening (OL5) 0 to 8 0 A A A 468 —
4: Interrupt drive output when the motor speed
Detection Operation
(not signed) is greater than L6-09 (protection
operation).
5: Continue running if the speed (signed) is
less than L6-09 (alarm only).
6: Continue running if the speed (not signed) is
less than L6-09 (alarm only).
7: Interrupt drive output when the motor speed
(signed) is less than L6-09 (protection
operation).
8: Interrupt drive output when the motor speed
(not signed) is less than L6-09 (protection
operation).
• Sets the speed that triggers mechanical
-110.0
Mechanical weakening detection.
to 110
L6-09 Weakening Detection • When L6-08 is set for an unsigned value, the A A A 469 —
+110.0 %
Speed Level absolute value is used even if the setting is
%
negative.
Mechanical
Sets the time a mechanical weakening has to be 0.0 to
L6-10 Weakening Detection 0.1 s A A A 46A —
detected before an Alarm/Fault is triggered. 10.0 s
Time
Mechanical Sets the operation time (U1-04) that has to be
0 to
L6-11 Weakening Detection passed before Mechanical weakening detection 0 A A A 46B —
65535
Start Time is active.
362 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
L7: Torque Limit
Use L7 parameters to configure the torque limit function.
Sets the torque limit value as a percentage of 200
L7-01 Forward Torque Limit 0 to 300 − A − 4A7 —
the motor rated torque. Four individual %
quadrants can be set. 200
L7-02 Reverse Torque Limit 0 to 300 − A − 4A8 —
output torque %
Forward Regenerative positive torque 200
L7-03 L7-01 0 to 300 − A − 4A9 —
Torque Limit L7-04 motor
%
regeneration r/min
REV FWD
Reverse Regenerative regeneration 200
L7-04 0 to 300 − A − 4AA —
Torque Limit L7-03 %
L7-02
negative torque
Torque Limit Integral Sets the integral time constant for the torque 5 to 200
L7-06 − A − 4AC —
Time Constant limit. 10000 ms
Selects the method of torque limit control
during accel/decel.
0: Proportional Control (change to integral
controls at fixed speeds). Use this setting when
Torque Limit Control acceleration to the desired speed has priority
L7-07 Method Selection over torque limitation. 0, 1 0 − A − 4C9 —
during Accel/Decel 1: Integral Control. Use this setting if the
Parameter List
torque limitation has priority.
When torque limit is applied to the motor,
accel/decel time may increase and motor speed
may not meet the speed reference.
L8: Hardware Protection
Use L8 parameters to configure hardware protection functions.
Internal Dynamic
Selects the Braking resistor when using a 3%
duty cycle heatsink mounted Yaskawa braking
B
Braking Resistor resistor. This parameter does not enable or
L8-01 0,1 0 A A A 4AD —
Protection Selection disable the braking transistor of the drive.
(ERF type) 0: Resistor overheat protection disabled
1: Resistor overheat protection enabled
When the heatsink temperature exceeds the
Overheat Alarm 50 to
L8-02 value set in this parameter, an Overheat Alarm <12> A A A 4AE —
Level 130
(OH) will occur.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 363
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the drive operation when an overheat
alarm OH is detected.
0: Ramp to Stop using the active decel time.
1: Coast to Stop.
2: Fast-stop using the time set in C1-09.
Overheat Pre-Alarm 3: Alarm Only. Drive continues running, but
L8-03 0 to 4 3 A A A 4AF —
Operation Selection displays an alarm.
4: Reduced Speed Operation. Drive continues
to run with reduced frequency reference as
specified in L8-19.
Settings 0 through 2 trigger a fault relay if the
heatsink becomes too hot.
Selects the detection of input current phase
loss, power supply voltage imbalance, or main
Input Phase Loss 1
L8-05 circuit electrolytic capacitor deterioration. 0,1 A A A 4B1 —
Protection Selection <56>
0: Disabled
1: Enabled
Selects the output phase loss detection.
0: Disabled
1: Enabled (triggered by a single phase loss).
2: Enabled (triggered when two phases are
Output Phase Loss lost).Output phase loss is detected when
L8-07 0 to 2 0 A A A 4B3 —
Protection operating with less than 5% of the drive rated
current. Detection can mistakenly occur if the
motor is too small relative to the drive capacity
rating (this parameter should be disabled in
such cases).
Selects the output ground fault detection.
Output Ground Fault
L8-09 0: Disabled 0,1 <12> A A A 4B5 —
Detection Selection
1: Enabled
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only
Heatsink Cooling Fan when the drive is running and for L8-11
L8-10 0,1 0 A A A 4B6 —
Operation Selection seconds after stop.
1: Fan always on - Cooling fan operates
whenever the drive is powered up.
Heatsink Cooling Fan This parameter sets the delay time for the
L8-11 Operation Delay cooling fan to shut off after the run command 0 to 300 60 s A A A 4B7 —
Time is removed when L8-10 = 0.
Ambient Temperature Used to input the ambient temperature. This -10 to 40
L8-12 A A A 4B8 —
Setting value adjusts the drives OL2 detection level. 50 °C
364 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the OL2 characteristics at output
OL2 Characteristics frequencies below 6 Hz.
L8-15 Selection at Low 0: No OL2 level reduction below 6Hz. 0,1 1 A A A 4BB —
Speeds 1: OL2 level is reduced linearly below 6 Hz. It
is halved at 0 Hz.
Selects the software current limit function.
Typically no adjustment is required.
L8-18 Soft CLA Selection 0,1 1 A A − 4BE —
0: Disabled
1: Enabled
Frequency Reduction
Specifies the frequency reference reduction 0.1 to
L8-19 Rate during OH 0.8 A A A 4BF —
gain at overheat prealarm when L8-03 = 4. 1.0
Pre-Alarm
Selects the detection of unbalanced output
currents caused by faulty devices in the output
Current Unbalance
L8-29 circuit. 0 to 1 1 − − A 4DF —
Detection (LF2)
0: Disabled
1: Enabled
Selects the installation type:
0: Standard installation of Open Chassis drive
Side-by-Side <12>
L8-35 1: Side-by-Side installation with top cover 0 to 2 Α Α A 4ECH —
Selection <25>
removed
2: Standard Installation of NEMA Type 1 drive
Provides protection to the IGBTs by reducing
Parameter List
the carrier frequency at low speeds.
Carrier Frequency
L8-38 0: Disabled 0 to 2 0 A A A 4EF —
Reduction
1: Enabled below 6Hz
2: Enabled for the whole speed range
Sets the time for that the drive continues
running with reduced carrier frequency after
L8-40
Carrier Frequency
Reduction Time
the carrier reduction condition has gone (see
also L8-38).
0.00 to
2.00
0.50 A A A 4F1 B
A setting of 0.00 s disables the carrier
frequency reduction time.
Configures an alarm when the output current
Current Alarm exceeds 150% of the drive rated current.
L8-41 0,1 0 A A A 4F2 —
Selection 0: Alarm disabled.
1: Alarm enabled (alsarm is output).
<1> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 2-OLV control.
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02
= 0-V/f Control.
<7> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 365
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
L
f M
V
n1: Hunting Prevention
Use n1 parameters to configure hunting prevention operation.
If the motor vibrates while lightly loaded,
Hunting Prevention may reduce the vibration.
Hunting Prevention 0: Disabled
n1-01 0,1 1 A − − 580 —
Selection 1: Enabled
When quick response is needed disable
Hunting Prevention.
Sets the gain for the Hunting Prevention
Function.
If the motor vibrates while lightly loaded and
Hunting Prevention 0.00 to
n1-02 n1-01 = 1, increase the gain by 0.1 until 1.00 A − − 581 —
Gain Setting 2.50
vibration ceases.
If the motor stalls while n1-01 = 1, decrease
the gain by 0.1 until the stalling ceases.
Hunting Prevention Sets the time constant used for hunting <12
n1-03 0 to 500 A − − 582 —
Time Constant prevention. >
Sets the gain used for Hunting Prevention.
Hunting Prevention 0.00 to
n1-05 When set to 0, the gain n1-02 is used for 0.00 A − − 530 —
Gain while in Reverse 2.50
operation in reverse direction.
366 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
n2: Speed Feedback Detection Control Function
Use n2 parameters to configure the Speed Feedback Detection Control function operation.
Sets the internal speed feedback detection 0.00 to
1.00 − A − 584 —
control gain in the automatic frequency 10.00
Speed Feedback regulator (AFR).
n2-01 Detection Control This parameter does not typically require
(AFR) Gain adjustment. Adjust this parameter as follows: Adjust the setting by 0.05 units at a
If hunting occurs, increase the set value. time, while checking the response.
If response is low, decrease the set value.
Speed Feedback
0 to 50
n2-02 Detection Control Sets the AFR time constant 1. − A − 585 —
2000 ms
(AFR) Time Constant
Speed Feedback Sets the AFR time constant 2. Increase the
Detection Control setting if overvoltage occurs during sudden 0 to 750
n2-03 − A − 586 —
(AFR) Time Constant load changes or the speed overshoots during 2000 ms
2 fast acceleration.
n3: High-Slip Braking
Use n3 parameters to configure the high-slip braking function.
Sets the output frequency reduction step width
High-Slip Braking when the drive stops the motor using high-slip
n3-01 Deceleration braking (HSB). 1 to 20 5% A − − 588 —
Frequency Width If Overvoltage (OV) faults occur during HSB,
this parameter may need to be increased.
Parameter List
Sets the current limit during HSB. Higher
High-Slip Braking n3-02 settings will shorten motor stopping 100 to 150
n3-02 A − − 589 —
Current Limit times but increase the motor current, and 200 %
therefore motor heating.
Sets the time the drive will run with minimum
frequency (E1-09) at the end of deceleration.
n3-03
High-Slip Braking
Dwell Time at Stop
If this time is set too low, the machine inertia
0.0 to
10.0
1.0 s A − − 58A — B
can cause the motor to rotate slightly after
HSB completion.
Sets the time required for an HSB overload
fault (OL7) to occur when the drive output
High-Slip Braking 30 to
n3-04 frequency does not change during an HSB 40 s A − − 58B —
Overload Time 1200
stop. This parameter does not typically require
adjustment.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 367
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Applies a gain to the V/f pattern during
deceleration (L3-04=4). Returns to normal
Overexcitation values after ramp to stop or at re-acceleration. 1.00 to
n3-13 1.10 A A − 531 —
Deceleration Gain To improve the braking power of 1.40
overexcitation, increase the gain by 1.25 to
1.30.
If overcurrent or overload occur during
High-Slip
high-slip deceleration, reduce the high-slip 100
n3-21 Suppression Current 0 to 150 A A − 579 —
suppression current level. Set as a percentage %
Level
of the drive rated current.
0: Disabled
Overexcitation
n3-23 1: Enabled only when rotating forward 0 to 2 0 A A − —
Operation Selection
2: Enabled only when in reverse
n6: Online Tuning of Resistance between Motor Lines
Use n6 parameters to adjust the motor line-to-line resistance while the drive is online.
Tunes the line-to-line motor resistance
Line-to-Line Motor
continuously during operation.
n6-01 Resistance Online 0,1 1 − A − 570 —
0: Disabled
Tuning
1: Enabled
n8: Permanent Magnet (PM) Motor Control
Use n8 parameters to control the PM motor control.
Sets the gain for internal speed feedback
Speed Feedback detection control. This parameter does not
0.0 to
n8-45 Detection Control typically require adjustment. 0.8 − − A 538 —
10.0
Gain Increase this setting if hunting occurs.
Decrease to lower the response.
Sets the time constant to make the pull-in
current and actual current value agree.
Pull-In Current
Decrease the value if the motor begins to 0.0 to
n8-47 Compensation Time 5.0 s − − A 53A —
oscillate. 100.0 s
Constant
Increase the value if it takes too long for the
current reference to equal the output current.
Defines the amount of current provided to the
motor during no load operation at a constant
speed. 20 to
n8-48 Pull-In Current 30% − − A 53B —
Set as a percentage of the motor rated current. 200%
Increase this setting when hunting occurs while
running at a constant speed.
Sets the amount of d-axis current when using -200.0
n8-49 Load Current 0% − − A 53C —
Energy Saving control. to 0.0%
368 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
Sets the pull-in current during acceleration as a
Acceleration Pull-In percentage of the motor rated current (E5-03). 0 to
n8-51 50% − − A 53E —
Current Set to a high value when more starting torque 200%
is needed.
Sets the time constant for voltage error
compesation. Adjust the value when
• hunting occurs at low speed.
Voltage Error
• hunting occurs with sudden load changes. 0.00 to 1.00
n8-54 Compensation Time − − A 56D —
Increase in steps of 0.1 or disable the 10.00 s s
Constant
compensation by setting n8-45 to 0.
• oscillations occur ar start. Increase the value
in steps of 0.1.
Sets the ratio between motor and machine
inertia.
0: less than 1:10.
n8-55 Load Inertia 0 to 3 0 − − A 56E —
1: between 1:10 to 1:30.
2: between 1:30 to 1:50.
3: higher than 1:50.
Sets the limit for the output voltage.
n8-62 Adjustment is normally needed only if the 0.0 to 200
Output Voltage Limit - - A 57D —
<24> input voltage is below the n8-62 set value. In 230.0 Vac
this case set n8-62 to the input voltage.
Parameter List
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 369
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ L P Hex
f M
V
o1: Display Settings
Use o1 parameters to configure the digital operator display.
Selects which monitor will be displayed in the 104 to
106 A A A 500 —
operation menu upon power-up when 621
o1-01 Drive Mode Unit o1-02 = 5. The monitor parameter number is
<22> Monitor Selection entered into the spaces provided: U-. Set to U1-06 as a default
For example, set “403” to display monitor —
(Output Voltage Reference).
parameter U4-03.
Selects the monitor to display upon power-up.
1: Frequency Reference (U1-01)
User Monitor
o1-02 2: Forward/Reverse
Selection After Power 1 to 5 1 A A A 501 —
<22> 3: Output Frequency (U1-02)
Up
4: Output Current (U1-03)
5: User Monitor (set by o1-01)
Sets the units to display the frequency
reference and output frequency.
0: Hz
Digital Operator
o1-03 1: % (100% = E1-04) 0 to 3 0 A A A 502 —
Display Selection
2: r/min (enter the number of motor poles into
E2-04/E4-04/E5-04)
3: User defined by parameters o1-10 and o1-11
Frequency Reference These settings define the display values when
1 to
o1-10 Setting and User-Set o1-03 is set to 3. <11> A A A 520 —
60000
Display o1-10 sets display values when operating at the
maximum output frequency.
o1-11 sets the position of the decimal
positions.
غغغغغغ
Frequency Reference
o1-11 Setting / Decimal o1-10: Sets the first five 0 to 3 <11> A A A 521 —
Display digits of the value,
disregarding the
decimal point.
o1-11: Sets the number
of digits past the
decimal point
370 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
o2: Operator Keypad Functions
Use o2 parameters to configure LED digital operator key functions.
Enables/Disables the digital operator LOCAL/
LOCAL/REMOTE
REMOTE key.
o2-01 Key Function 0,1 1 A A A 505 —
0: Disabled
Selection
1: Enabled
Enables/Disables the operator panel STOP key
when the drive is operated form external
STOP Key Function
o2-02 sources (not operator). 0,1 1 A A A 506 —
Selection
0: Disabled
1: Enabled
Allows storing of parameter settings as a User
Initialization Selection (value 1110 for A1-03).
The value returns to 0 after entering 1 or 2.
User Parameter 0: No Change
o2-03 0 to 2 0 A A A 507 —
Default Value 1: Set Defaults - Saves current parameter
settings as user initialization.
2: Clear All - Clears the currently saved user
initialization.
Sets the kVA of the drive.
This parameter only needs to be set when
o2-04 Drive/kVA Selection 0 to FF <12> A A A 508 —
installing a new control board. Do not change
for other reason.
Parameter List
Selects if the ENTER key must be pressed
when inputting the frequency reference by the
operator keypad.
Frequency Reference
0: Data/Enter key must be pressed to enter a
o2-05 Setting Method 0,1 0 A A A 509 —
frequency reference.
Selection
1: Data/Enter key is not required. The
frequency reference is adjusted by the “up” and
“down” arrow keys. B
Sets drive action when the digital operator is
Operation Selection
removed in Local mode or with b1-02 = 0.
when Digital
o2-06 0: The drive will continue operation 0,1 0 A A A 50A —
Operator is
1: The drive will trigger a fault (OPR) and the
Disconnected
motor will coast to stop
0: Forward
Motor Direction at
1: Reverse
o2-07 Power Up when 0 to 1 0 A A A 527 —
This parameter requires that drive operation be
Using Operator
assigned to the digital operator.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 371
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
o4: Maintenance Period
Use o4 parameters to perform maintenance.
Accumulated
Sets the starting value for the cumulative 0 to
o4-01 Operation Time 0 A A A 50B —
operation time of the drive in units of 10h. 9999
Setting
Sets this parameter to log the cumulative
Accumulated operation time (U4-01).
o4-02 Operation Time 0: Logs power-on time 0 to 1 0 A A A 50C —
Selection 1: Logs operation time when the drive output is
active (output operation time).
Cooling Fan
Used to resets the Cooling Fan operation time 0 to
o4-03 Operation Time 0 A A A 50E —
counter U1-04. 9999
Setting
Capacitor Resets the capacitor maintenance time monitor
o4-05 0 to 150 0% A A A 51D —
Maintenance Setting U4-05.
Inrush Prevention
Resets the Inrush Prevention Relay
o4-07 Relay Maintenance 0 to 150 0% A A A 523 —
Maintenance monitor U4-06.
Setting
IGBT Maintenance Resets the counter that logs the IGBTs usage
o4-09 0 to 150 0% A A A 525 —
Setting time. Refer to U4-07 (IGBT Maintenance).
Selects if U2-oo (Fault Trace) , U3-oo (Fault
History) monitors are reset at drive
U2, U3 Initialize
o4-11 initialization. 0 to 1 0 A A A 510 —
Selection
0: Saves the fault monitor data
1: Resets the fault monitor data
Selects if U4-10 and U4-11 (kWh monitor) are
kWh Monitor reset at drive initialization.
o4-12 0 to 1 0 A A A 512 —
Initialize Selection 0: Saves the U4-10 and U4-11 monitor data.
1: Resets the U4-10 and U4-11 monitor data.
Selects if the Run command counter (U4-02) is
Number of Run
reset at drive initialization.
o4-13 Commands Initialize 0 to 1 0 A A A 528 —
0: Saves the number of Run commands
Selection
1: Resets the number of Run commands
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
<11> Default setting value is dependent on parameter o1-03, Digital Operator Display Selection.
<12> Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
<22> Parameter can be changed during run.
372 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
◆ r: DWEZ Parameters
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ P Hex
L
f V M
DWEZ Connection 0 to
r1-01 Parameter 1 for connecting DWEZ (upper). 0 – A A 1840 —
Parameter 1 (upper) FFFFH
DWEZ Connection 0 to
r1-02 Parameter 1 for connecting DWEZ (lower). 0 – A A 1841 —
Parameter 1 (lower) FFFFH
DWEZ Connection 0 to
r1-03 Parameter 2 for connecting DWEZ (upper). 0 – A A 1842 —
Parameter 2 (upper) FFFFH
DWEZ Connection 0 to
r1-04 Parameter 2 for connecting DWEZ (lower). 0 – A A 1843 —
Parameter 2 (lower) FFFFH
DWEZ Connection 0 to
r1-05 Parameter 3 for connecting DWEZ (upper). 0 – A A 1844 —
Parameter 3 (upper) FFFFH
DWEZ Connection 0 to
r1-06 Parameter 3 for connecting DWEZ (lower). 0 – A A 1845 —
Parameter 3 (lower) FFFFH
DWEZ Connection 0 to
r1-07 Parameter 4 for connecting DWEZ (upper). 0 – A A 1846 —
Parameter 4 (upper) FFFFH
DWEZ Connection 0 to
r1-08 Parameter 4 for connecting DWEZ (lower). 0 – A A 1847 —
Parameter 4 (lower) FFFFH
DWEZ Connection 0 to
r1-09 Parameter 5 for connecting DWEZ (upper). 0 – A A 1848 —
Parameter 5 (upper) FFFFH
Parameter List
DWEZ Connection 0 to
r1-10 Parameter 5 for connecting DWEZ (lower). 0 – A A 1849 —
Parameter 5 (lower) FFFFH
DWEZ Connection 0 to
r1-11 Parameter 6 for connecting DWEZ (upper). 0 – A A 184A —
Parameter 6 (upper) FFFFH
DWEZ Connection 0 to 184B
r1-12 Parameter 6 for connecting DWEZ (lower). 0 – A A —
Parameter 6 (lower) FFFFH H
r1-13
DWEZ Connection
Parameter 7 for connecting DWEZ (upper).
0 to
0 – A A 184C —
B
Parameter 7 (upper) FFFFH
DWEZ Connection 0 to
r1-14 Parameter 7 for connecting DWEZ (lower). 0 – A A 184D —
Parameter 7 (lower) FFFFH
DWEZ Connection 0 to
r1-15 Parameter 8 for connecting DWEZ (upper). 0 – A A 184E —
Parameter 8 (upper) FFFFH
DWEZ Connection 0 to
r1-16 Parameter 8 for connecting DWEZ (lower). 0 – A A 184F —
Parameter 8 (lower) FFFFH
DWEZ Connection 0 to
r1-17 Parameter 9 for connecting DWEZ (upper). 0 – A A 1850 —
Parameter 9 (upper) FFFFH
DWEZ Connection 0 to
r1-18 Parameter 9 for connecting DWEZ (lower). 0 – A A 1851 —
Parameter 9 (lower) FFFFH
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 373
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
DWEZ Connection 0 to
r1-19 Parameter 10 for connecting DWEZ (upper). 0 – A A 1852 —
Parameter 10 (upper) FFFFH
DWEZ Connection 0 to
r1-20 Parameter 10 for connecting DWEZ (lower). 0 – A A 1853 —
Parameter 10 (lower) FFFFH
DWEZ Connection 0 to
r1-21 Parameter 11 for connecting DWEZ (upper). 0 – A A 1854 —
Parameter 11 (upper) FFFFH
DWEZ Connection 0 to
r1-22 Parameter 11 for connecting DWEZ (lower). 0 – A A 1855 —
Parameter 11 (lower) FFFFH
DWEZ Connection 0 to
r1-23 Parameter 12 for connecting DWEZ (upper). 0 – A A 1856 —
Parameter 12 (upper) FFFFH
DWEZ Connection 0 to
r1-24 Parameter 12 for connecting DWEZ (lower). 0 – A A 1857 —
Parameter 12 (lower) FFFFH
DWEZ Connection 0 to
r1-25 Parameter 13 for connecting DWEZ (upper). 0 – A A 1858 —
Parameter 13 (upper) FFFFH
DWEZ Connection 0 to
r1-26 Parameter 13 for connecting DWEZ (lower). 0 – A A 1859 —
Parameter 13 (lower) FFFFH
DWEZ Connection 0 to
r1-27 Parameter 14 for connecting DWEZ (upper). 0 – A A 185A —
Parameter 14 (upper) FFFFH
DWEZ Connection 0 to
r1-28 Parameter 14 for connecting DWEZ (lower). 0 – A A 185B —
Parameter 14 (lower) FFFFH
DWEZ Connection 0 to
r1-29 Parameter 15 for connecting DWEZ (upper). 0 – A A 185C —
Parameter 15 (upper) FFFFH
DWEZ Connection 0 to
r1-30 Parameter 15 for connecting DWEZ (lower). 0 – A A 185D —
Parameter 15 (lower) FFFFH
DWEZ Connection 0 to
r1-31 Parameter 16 for connecting DWEZ (upper). 0 – A A 185E —
Parameter 16 (upper) FFFFH
DWEZ Connection 0 to
r1-32 Parameter 16 for connecting DWEZ (lower). 0 – A A 185F —
Parameter 16 (lower) FFFFH
DWEZ Connection 0 to
r1-33 Parameter 17 for connecting DWEZ (upper). 0 – A A 1860 —
Parameter 17 (upper) FFFFH
DWEZ Connection 0 to
r1-34 Parameter 17 for connecting DWEZ (lower). 0 – A A 1861 —
Parameter 17 (lower) FFFFH
DWEZ Connection 0 to
r1-35 Parameter 18 for connecting DWEZ (upper). 0 – A A 1862 —
Parameter 18 (upper) FFFFH
DWEZ Connection 0 to
r1-36 Parameter 18 for connecting DWEZ (lower). 0 – A A 1863 —
Parameter 18 (lower) FFFFH
DWEZ Connection 0 to
r1-37 Parameter 19 for connecting DWEZ (upper). 0 – A A 1864 —
Parameter 19 (upper) FFFFH
374 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
DWEZ Connection 0 to
r1-38 Parameter 19 for connecting DWEZ (lower). 0 – A A 1865 —
Parameter 19 (lower) FFFFH
DWEZ Connection 0 to
r1-39 Parameter 20 for connecting DWEZ (upper). 0 – A A 1866 —
Parameter 20 (upper) FFFFH
DWEZ Connection 0 to
r1-40 Parameter 20 for connecting DWEZ (lower). 0 – A A 1867 —
Parameter 20 (lower) FFFFH
◆ T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal
performance
Control
Mode
No. Name Description Range Def. O Addr. Pg.
V/ P Hex
L
f V M
Parameter List
1: 1st Motor - E1 to E2
2: 2nd Motor - E3 to E4 (this selection is not
displayed if motor 2 has not been selected)
Selects the Auto-Tuning mode. 2 or 3
0: Rotational Auto-Tuning in V/f
2: Stationary Auto-Tuning, Terminal resistance 0 or 2
Auto-Tuning 0, 2, 3
in OLV A A −
T1-01
Mode Selection
only,
3: Rotational Auto-Tuning for V/f control
<54>
2 for
701 —
B
(necessary for Energy Savings and Speed Motor
Estimation type speed search) 2
Sets the motor rated power in kilowatts (kW).
Motor Rated Note: If motor power is given in horsepower, 0.00 to 0.40
T1-02 A A − 702 —
Power power in kW can be calculated using the following 650.00 kW
formula: kW = HP x 0.746.
T1-03 Motor Rated 0.0 to 200.0
Sets the motor rated voltage in volts (V). A A − 703 —
<24> Voltage 255.5 V
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 375
B.2 Parameter Table
Control
Mode
No. Name Description Range Def. Addr. Pg.
V/ O P Hex
f L M
V
10 to
200% of
Motor Rated
T1-04 Sets the motor rated current in amperes (A). drive <12> A A − 704 —
Current
rated
current
Motor Base 0.0 to 60.0
T1-05 Sets the base frequency of the motor in Hertz (Hz). A A − 705 —
Frequency 400.0 Hz
Number of
T1-06 Sets the number of motor poles. 2 to 48 4 A A − 706 —
Motor Poles
Motor Base Sets the base speed of the motor in revolutions per 0 to 1750
T1-07 A A − 707 —
Speed minute r/min (RPM). 24000 r/min
Provides the iron loss for determining the Energy 14W A − − 70B —
Saving coefficient. The value set to E2-10 (motor These values differ
Motor Iron 0 to
T1-11 iron loss) when the power is cycled. If T1-02 is depending on the motor
Loss 65535
changed, an initial value valid for the selected code value and motor
capacity will be shown. parameter settings.
◆ U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other
information about drive operation.
Control
Analog Mode
No. Name Description Output Unit Addr.
V/ O
Level L P Hex
f V M
376 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
10 V: Drive 0.01
U1-03 Output Current Displays the output current. A A A 42
rated current A
Control method set in A1-02.
No output
0: V/f without PG
U1-04 Control Mode signal – A A A 43
2: Open Loop Vector (OLV)
available
5: PM Open Loop Vector (PM)
10 V:
Displays the motor speed feedback. 0.01
U1-05 Motor Speed Maximum – A A 44
Display units are determined by o1-03. Hz
speed
10 V: 200
Output Voltage 0.1
U1-06 Displays the output voltage. Vrms A A A 45
Reference V
(400 Vrms)
10 V: 400 V
U1-07 DC Bus Voltage Displays the DC bus voltage. 1V A A A 46
(800 V)
10 V:
Drive
capacity
Displays the output voltage (this value is <27
U1-08 Output Power (kW) A A A 47
determined internally). >
(max. motor
capacity
allowed)
Monitor of internal torque reference value for 10 V: Motor
U1-09 Torque Reference – – A –
Open Loop Vector (OLV) control rated torque
Parameter List
B
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 377
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Displays the input terminal status.
U1-09=0 0 0 0 0 0 0
1: FWD run
command
(terminal S1
enabled)
1: REV run
command
(terminal S2
enabled)
1: Multi-Function
Digital
Input 1 (terminal
S3 enabled) No output
U1-10 Input Terminal Status 1: Multi-Function signal – A A A 49
Digital available
Input 2 (terminal
S4 enabled)
1: Multi-Function
Digital
Input 3 (terminal
S5 enabled)
1: Multi-Function
Digital
Input 4 (terminal
S6 enabled)
1: Multi-Function
Digital
Input 5 (terminal
S7 enabled)
U1-11=0 0 0
1: Multi-Function
Digital Output (fault)
(terminal MA/MB-MC) No output
Output Terminal
U1-11 signal – A A A 4A
Status 1: Multi-Function available
Digital Output 1
(terminal P1) enabled
1: Multi-Function
Digital Output 2
(terminal P2) enabled
378 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Verifies the drive operation status.
U1-12=0 0 0 0 0 0 0 0
1: During run
1: During
zero-speed
1: During REV
1: During fault
reset No output
U1-12 Drive Status signal input signal – A A A 4B
1: During speed available
agree
1: Drive ready
1: During alarm
detection
1: During fault
detection
Parameter List
Terminal A2 Input Displays the analog input A2 input level. 0.1
U1-14 10 V: 100% A A A 4F
Voltage 100% when the input is 10 V / 20 mA %
Displays the output frequency including
Output Frequency 10 V: Max 0.01
U1-16 ramp times, S-curves. Units are determined A A A 53
after Soft Start frequency Hz
by o1-03.
Displays the parameter number for oPE No output
U1-18 OPE Fault Parameter or Err (operator error) where the error
occurred.
signal
available
– A A A 61 B
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 379
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Displays the contents of a MEMOBUS/
Modbus error.
U1-18=0 0 0 0 0 0 0 0
1: CRC error
1: Data length
error
Not used
(normally 0) No output
MEMOBUS/Modbus
U1-19 1: Parity error signal – A A A 66
Error Code
available
1: Overrun error
1: Framing error
1: Timed out
Not used
(normally 0)
U1-24 Input Pulse Monitor Displays the Pulse Train input RP frequency. 32000 7D
No signal
U1-25 Software No. (Flash) Yaskawa Flash ID output 4D
available
No signal
U1-26 Software No. (ROM) Yaskawa ROM ID output 5B
available
U2: Fault Trace
Use U2 monitor parameters to view fault trace data.
No signal
U2-01 Current Fault Display of the current fault. – A A A 80
output avail.
No signal
U2-02 Previous Fault Display of the previous fault. – A A A 81
output avail.
Frequency Reference Displays the frequency reference at the No signal 0.01
U2-03 A A A 82
at Previous Fault previous fault. output avail. Hz
Output Frequency at Displays the output frequency at the previous No signal 0.01
U2-04 A A A 83
Previous Fault fault. output avail. Hz
Output Current at Displays the output current at the previous No signal
U2-05 A A A 84
Previous Fault fault. output avail.
380 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Motor Speed at Displays the motor speed at the previous No signal 0.01
U2-06 − A − 85
Previous Fault fault. output avail. Hz
Output Voltage at Displays the output voltage at the previous No signal 0.1
U2-07 A A A 86
Previous Fault fault. output avail. V
DC Bus Voltage at Displays the DC bus voltage at the previous No signal
U2-08 1V A A A 87
Previous Fault fault. output avail.
Output Power at Displays the output power at the previous No signal 0.1
U2-09 A A A 88
Previous Fault fault. output avail. kW
Torque Reference at Displays the torque reference at the previous No signal 0.1
U2-10 − Α − 89
Previous Fault fault. output avail. %
Input Terminal Status Displays the input terminal status at the No signal
U2-11 – A A A 8A
at Previous Fault previous fault. Displayed as in U1-10. output avail.
Output Terminal Displays the output status at the previous No signal
U2-12 Status at Previous fault. Displays the same status displayed in output – A A A 8B
Fault U1-11. available
Drive Operation Displays the operation status of the drive at No signal
U2-13 Status at Previous the previous fault. Displays the same status output – A A A 8C
Fault displayed in U1-12. available
Cumulative Operation No signal
Displays the cumulative operation time at the
U2-14 Time at Previous output 1H A A A 8D
previous fault.
Fault available
Parameter List
Soft Starter Speed No signal
Displays the speed reference for the soft 0.01
U2-15 Reference at Previous output A A A 7E0
starter at the previous fault. %
Fault available
Motor q-Axis Current Displays the q-axis current for the motor at No signal 0.10
U2-16 − A A 7E1
at Previous Fault the previous fault. output avail. %
Motor d-Axis Current Displays the d-axis current for the motor at No signal 0.10
U2-17 − A A 7E2
at Previous Fault the previous fault.
U3: Fault History
output avail. %
B
Use U3 parameters to display fault data.
No signal 90
U3-01 Most Recent Fault Displays the most recent fault. – A A A
output avail. (800)
2nd Most Recent No signal 91
U3-02 Displays the second most recent fault. – A A A
Fault output avail. (801)
No signal 92
U3-03 3rd Most Recent Fault Displays the third most recent fault. – A A A
output avail. (802)
No signal
93
U3-04 4th Most Recent Fault Displays the fourth most recent fault. output – A A A
(803)
available
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 381
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
No signal
U3-05 5th Most Recent Fault Displays the fifth most recent fault. output – A A A 804
available
No signal
U3-06 6th Most Recent Fault Displays the sixth most recent fault. output – A A A 805
available
No signal
U3-07 7th Most Recent Fault Displays the seventh most recent fault. output – A A A 806
available
No signal
U3-08 8th Most Recent Fault Displays the eighth most recent fault. output – A A A 807
available
No signal
U3-09 9th Most Recent Fault Displays the ninth most recent fault. output – A A A 808
available
No signal
10th Most Recent
U3-10 Displays the tenth most recent fault. output – A A A 809
Fault
available
Cumulative Operation No signal
Displays the cumulative operation time at the 94
U3-11 Time at Most Recent output 1h A A A
most recent fault. (80A)
Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the 95
U3-12 Time at 2nd Most output 1h A A A
second most recent fault. (80B)
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the 96
U3-13 Time at 3rd Most output 1h A A A
third most recent fault. (80C)
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the 97
U3-14 Time at 4th Most output 1h A A A
fourth most recent fault. (80D)
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-15 Time at 5th Most output 1 h A A A 80E
fifth most recent fault.
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-16 Time at 6th Most output 1h A A A 80F
sixth most recent fault.
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-17 Time at 7th Most output 1 h A A A 810E
seventh most recent fault.
Recent Fault available
382 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-18 Time at 8th Most output 1 h A A A 811E
eighth most recent fault.
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-19 Time at 9th Most output 1h A A A 812
ninth most recent fault.
Recent Fault available
Cumulative Operation No signal
Displays the cumulative operation time at the
U3-20 Time at 10th Most output 1h A A A 813
tenth most recent fault.
Recent Fault available
U4: Maintenance Monitors
Use U4 parameters to display drive maintenance information.
Displays the cumulative operation time of the
drive. The value for the cumulative operation
time counter can be set in parameter o4-01.
Use parameter o4-02 to determine if the
Accumulated No signal
U4-01 operation time should start as soon as the 1h A A A 4C
Operation Time output avail.
power is switched on or only while the run
command is present. The maximum number
displayed is 99999, after which the value is
reset to 0.
Displays the number of times the run
command is entered. Reset the number of run
Number of Run No signal
U4-02 commands using parameter o4-13. This value A A A 76
Parameter List
Commands output avail.
will reset to 0 and start counting again after
reaching 65535.
Displays the cumulative operation time of the
cooling fan. The default value for the fan
Cooling Fan No signal
U4-03 operation time is set to parameter o4-03. This 1H A A A 67
Operation Time output avail.
value will reset to 0 and start counting again
after reaching 65535. B
Displays main circuit capacitor usage time in
Capacitor No signal
U4-05 in percent of their expected performance life. 1% A A A 7C
Maintenance output avail.
Parameter o4-06 resets this monitor.
Displays IGBT usage time as a percent of
expected performance life. One of the multi-
function contact outputs can be set to close
when the value reaches 50% (H2- = 2F),
No signal
U4-07 IGBT Maintenance triggering an alarm. One of the multi- 1% A A A 7D7
output avail.
function contact outputs can be set to close
when the value reaches 90% (H2- = 10),
triggering an alarm. Parameter o4-09 resets
this monitor.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 383
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Lights all segments of the LED to verify that No signal
U4-09 LED Check – A A A 3C
the display is working properly. output avail.
U4-10 kWH, Lower 4 Digits Monitors the drive output power. The value is kWh A A A 5C
shown as a 9 digit number displayed across
two monitor parameters, U4-10 and U4-11.
Example: No signal
U4-11 kWH, Upper 5 Digits 12345678.9 kWh is displayed as: output avail. MW A A A 5D
U4-10: 678.9 kWh h
U4-11: 12345 MWh
Analog monitor: No output signal available.
10 V: Motor 0.01
U4-13 Peak Hold Current Displays the peak hold current during run. A A A 7CF
rated current A
Peak Hold Output Displays the output frequency when 10 V: Max 0.01
U4-14 A A A 7D0
Frequency operating at the peak hold current. frequency Hz
100% = OL1
Motor Overload 0.1
U4-16 100% = OL1 detection level detection A A A 7D8
Estimate (OL1) %
level
Displays the source for the frequency
reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Operator (d1-01)
Frequency Reference
U4-18 1-01 = Analog (terminal A1) A A A 7DA
Source Selection
1-02 = Analog (terminal A2)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus comm.
4-01 = Option
5-01 = Pulse Input
6-01 = CASE
7-01 = DWEZ
Frequency Reference
Displays the frequency reference provided by
U4-19 from MEMOBUS/ A A A 7DB
MEMOBUS/Modbus (decimal)
Modbus Comm.
Option Frequency Displays the frequency reference input by an
U4-20 A A A 7DD
Reference option card (decimal).
384 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Displays the source for the Run command as
XY-nn.
X: Indicates which Run source is used:
1 = Reference 1 (b1-02)
2 = Reference 2 (b1-16)
Y: Input power supply data
0 = Operator
1 = External terminals
2 = Not used
3 = MEMOBUS/Modbus communications
4 = Option
5 = Not used
6 = CASE
7 = DWEZ
nn: Run command limit status data
00: No limit status.
Run Command
U4-21 01: Run command was left on when stopped A A A 7DD
Source Selection
in the PRG mode.
02: Run command was left on when
switching from local to remote operation.
03: Waiting for the soft charge bypass
contactor after the power is switched on (UV
or UV1 flashes after 10 seconds).
04: Waiting for “Run Command Prohibited”
time period to end.
Parameter List
05: Fast-stop (digital input (H1- = 15),
operator)
06: b1-17 (run command given at power-up).
07: During Baseblock while coast to stop
with timer
08: Frequency reference is below minimal
reference during base block
09: Waiting for Enter command B
Displays the drive control data set by
MEMOBUS/Modbus
MEMOBUS/Modbus communications
U4-22 Communications A A A 7DE
register No. 0001H as a 4 digit hexadecimal
Reference
number.
Option Card Displays drive control data set by an option
U4-23 A A A 7DF
Reference card as a 4 digit hexadecimal number.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 385
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
U5: Application Monitor
Use U5 parameters to view application-specific settings.
0.01
U5-01 PID Feedback Displays the PID feedback value in. A A A 57
%
Displays the amount of PID input (deviation 0.01
U5-02 PID Input A A A 63
between PID target and feedback). %
0.01
U5-03 PID Output Displays PID control output. A A A 64
%
10V: 100%
(max. freq.) 0.01
U5-04 PID Setpoint Displays the PID setpoint. A A A 65
%
PID differential Displays the 2nd PID feedback value if 0.01
U5-05 A A A
feedback differential feedback is used. %
Displays the subtraction value of both
PID Adjusted 0.01
U5-06 feedback values if differential feedback is A A A
Feedback %
used.
U6: Application Monitor
Use U6 parameters to display drive control information.
10 V: Motor
Motor Secondary Displays the value of the motor secondary rated 0.1
U6-01 A A A 51
Current (Iq) current (Iq). secondary %
current
10 V: Motor
Displays the value calculated for the motor
Motor Excitation rated 0.1
U6-02 excitation current (Id) as a percentage of the − A A 52
Current (ld) secondary %
motor rated secondary current (Iq).
current
Displays the ASR input value if Simple PG is 10V: 100% 0.1
U6-03 ASR Input A − −
used in V/f control. (max. freq.) %
Displays the ASR output value if Simple PG 10V: 100% 0.1
U6-04 ASR Output A − − 55
is used in V/f control. (max. freq.) %
Output voltage 10 V: 200 V 0.1
U6-05 Output voltage reference (Vq). (q-axis) − A A 59
reference (Vq) (400 V) Vac
Output Voltage 10 V: 200 V 0.1
U6-06 Output voltage reference (Vd). (d-axis) − A A 5A
Reference (Vd) (400 V) Vac
Displays the current control (ACR) output of 0.1
U6-07 q-axis ACR Output 10 V: 100% − A − 5F
for the motor secondary current (Iq). %
Displays the current control (ACR) output of 0.1
U6-08 d-Axis ACR Output 10 V: 100% − A − 60
for the motor excitation current (Id). %
Frequency Reference Displays the bias value used to adjust the 10 V: max. 0.1
U6-20 A A A 7D4
Bias (Up/Down 2) frequency reference. frequency %
386 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Control
Analog Mode
No. Name Description Output Unit Addr.
Level V/ O P Hex
f L M
V
Offset Displays the frequency added to the main 10 V: max. 0.1
U6-21 A A A 7D5
Frequency frequency reference. frequency %
U8: Custom Monitors for DriveWorksEZ
U8 parameters are reserved for DriveWorksEZ
0.01
U8-01 – Reserved for DriveWorksEZ, Monitor 1. – Α A Α 1950
%
0.01
U8-02 – Reserved for DriveWorksEZ, Monitor 2. – A A A 1951
%
0.01
U8-03 – Reserved for DriveWorksEZ, Monitor 3. – A A A 1952
%
0.01
U8-04 – Reserved for DriveWorksEZ, Monitor 4. – A A A 1953
%
0.01
U8-05 – Reserved for DriveWorksEZ, Monitor 5. – A A A 1954
%
0.01
U8-06 – Reserved for DriveWorksEZ, Monitor 6. – A A A 1955
%
0.01
U8-07 – Reserved for DriveWorksEZ, Monitor 7. – A A A 1956
%
0.01
U8-08 – Reserved for DriveWorksEZ, Monitor 8. – A A A 1957
%
0.01
U8-09 – Reserved for DriveWorksEZ, Monitor 9. – A A A 1958
Parameter List
%
0.01
U8-10 – Reserved for DriveWorksEZ, Monitor 10. – A A A 1959
%
<27> Setting units for this parameter are determined by o2-04, Drive/kVA Selection. Less than 11 kW: 2 decimal
points, 11 kW and above: 1 decimal point.
B
◆ Control Mode Dependent Parameter Default Values
The tables below list parameters that depend on the control mode selection (A1-02 for motor
1, E3-01 for motor 2). These parameters are initialized to the shown values if the control
mode is changed.
Table B.1 A1-02 (Motor 1 Control Mode) Dependent Parameters and Default Values
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 387
B.2 Parameter Table
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive/kVA Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Table B.2 E3-01 (Motor 2 Control Mode) Dependent Parameters and Default Values
388 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
Parameter List
E1-07 Hz 2.5 3.0 3.0 3.0 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
0 0 0 0
E1-08 16. 16. 16. 16. 35. 50. 35. 50. 19. 24. 19. 24. 16. 16. 16. 16.
V 18.4 13.8
<24> 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
E1-09 Hz 1.3 1.5 1.5 1.5 1.3 1.3 1.5 1.5 1.3 1.3 1.5 1.5 1.5 1.5 1.5 1.5 1.5 0.5
E1-10 12. 12. 12. 12. 12. 13. 12. 15. 12. 12. 12. 12.
V 8.0 9.0 8.0 9.0 13.8 2.9
<24> 0 0 0 0 0 0 0 0 0 0 0 0
B
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<55> Used as default settings for E1-04 to E1-10 and E2-04 to E2-10
Table B.4 E1-03 V/f Pattern Settings for Drive Capacity: CIMR-VUBA0012 to CIMR-
VUBA0020; CIMR-VU2A0012 to CIMR-VU2A0069; CIMR-VU4A0007 to CIMR-VU4A0038
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 389
B.2 Parameter Table
<24> Vaaaaalues shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<55> Used as default settings for E1-04 to E1-10 and E2-04 to E2-10
390 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
No. Description Unit Default Settings
− Model CIMR-Vo − BA0006 BA0010 BA0012 BA0018
C6-01 Normal/Heavy Duty − HD HD ND HD ND HD
−
o2-04
E2-11
kVA Selection 51 (33H) 52 (34H) 53 (35H) 55 (37H)
B
(E4-11, Motor rated power kW 0.75 1.1 1.5 2.2 2.2 3.0 3.7
T1-02)
b3-06 Speed Search current 1 − 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b8-04 Energy saving coefficient − 223.7 169.4 169.4 156.8 156.8 136.4 122.9
C6-02 Carrier frequency − 4 7 3 7 3 7 3
E2-01
(E4-01, Motor rated current A 3.3 6.2 6.2 8.5 8.5 11.4 14.0
T1-04)
E2-02
Motor rated slip Hz 2.5 2.6 2.6 2.9 2.9 2.7 2.73
(E4-02)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 391
B.2 Parameter Table
392 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
Momentary power loss
L2-04 s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
voltage recovery time
L2-05 UV detection voltage V dc 190 190 190 190 190 190 190 190
L3-24 Motor acceleration time s 0.166 0.145 0.145 0.145 0.145 0.154 0.154 0.168
L8-02 Overheat alarm level ×C 100 100 100 100 110 110 110 110
L8-09 Ground fault selection
Enclosure/Mounting
− 0 0 0 0 0 0 0 0
B
L8-35 − 0 0 0 0 0 0 0 0
selection
Carrier frequency reduction
L8-38 − 1 1 1 1 1 1 1 1
selection
Hunting Prevention Time
n1-03 ms 10 10 10 10 10 10 10 10
Constant
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 393
B.2 Parameter Table
394 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
E5-01 Motor Code hex FFFF FFFF FFFF FFFF 0002 0002 0003 0003 0005 0005
Momentary power loss
L2-02 s 0.1 0.1 0.1 0.1 0.1 0.1 0.2 0.2 0.3 0.3
ride-through time
Momentary power loss base
L2-03 s 0.2 0.2 0.2 0.2 0.2 0.3 0.3 0.4 0.4 0.5
block time
L2-04
Momentary power loss
s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
B
voltage recovery time
L2-05 UV detection voltage V dc 190 190 190 190 190 190 190 190 190 190
L3-24 Motor acceleration time s 0.178 0.178 0.178 0.178 0.178 0.142 0.142 0.142 0.166 0.145
L8-02 Overheat alarm level ×C 110 110 110 110 115 115 100 100 100 100
L8-09 Ground fault selection − 0 0 0 0 0 0 0 0 0 0
Carrier frequency reduction
L8-38 − 1 1 1 1 1 1 1 1 1 1
selection
Hunting Prevention Time
n1-03 ms 10 10 10 10 10 10 10 10 10 10
Constant
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 395
B.2 Parameter Table
396 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
Momentary power loss
L2-02 s 1.0 1.0 2.0 2.0 2.0 2.0
ride-through time
Momentary power loss base
L2-03 s 0.8 0.9 0.9 1.0 1.0 1.0
block time
Momentary power loss
L2-04 s 0.3 0.3 0.3 0.3 0.6 0.6
voltage recovery time
L2-05 UV detection voltage V dc 190 190 190 190 190 190
B
L3-24 Motor acceleration time s 0.175 0.265 0.265 0.244 0.244 0.317
L8-02 Overheat alarm level ×C 121 121 120 120 120 120
L8-09 Ground fault selection − 1 1 1 1 1 1
Carrier frequency reduction
L8-38 − 2 2 2 2 2 2
selection
Hunting Prevention Time
n1-03 ms 10 10 10 10 10 10
Constant
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 397
B.2 Parameter Table
398 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
Momentary power loss
L2-02 s 0.5 0.5 0.5 0.5 0.5 0.5 0.8 0.8
ride-through time
Momentary power loss base
L2-03 s 0.5 0.5 0.5 0.6 0.6 0.7 0.7 0.8
block time
Momentary power loss
L2-04 s 0.3 0.3 0.3 0.3 0.3 0.3 0.3 0.3
voltage recovery time
L2-05 UV detection voltage V dc 380 380 380 380 380 380 380 380
B
L3-24 Motor acceleration time s 0.145 0.145 0.145 0.154 0.154 0.154 0.168 0.175
L8-02 Overheat alarm level ×C 100 100 100 100 100 100 110 110
L8-09 Ground fault selection − 0 0 0 0 0 0 1 1
Carrier frequency reduction
L8-38 − 1 1 1 1 1 1 2 2
selection
Hunting Prevention Time
n1-03 ms 10 10 10 10 10 10 10 10
Constant
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 399
B.2 Parameter Table
400 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Parameter List
E1-09 Minimum output voltage Hz 6 6 6 6 6
L3-24 Motor acceleration time s 0.064 0.066 0.049 0.051 0.044
n8-49 Pull-in current % 0 0 0 0 0
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 401
B.2 Parameter Table
402 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
B.2 Parameter Table
Table B.11 400 V, 1750 rpm Type Yaskawa SSR1 Series Motor
Parameter List
Motor Code − 1232 1233 1235 1236 1238
Voltage class 400 Vac 400 Vac 400 Vac 400 Vac 400 Vac
E5-01 −
Rated power 0.4 kW 0.75 kW 1.5 kW 2.2 kW 3.7 kW
Rated speed min-1 1750 1750 1750 1750 1750
E5-02 Motor rated power kW 0.4 0.75 1.5 2.2 3.7
E5-03 Motor rated current A 0.83 1.49 2.75 4.05 6.80
B
E5-04 Motor pole number – 6 6 6 6 6
E5-05 Motor winding resistance W 32.932 9.136 6.004 3.297 1.798
E5-06 d-axis inductance mH 219.36 92.08 68.32 40.39 32.93
E5-07 q-axis inductance mH 256.40 119.56 85.56 48.82 37.70
E5-09 Induction voltage constant 1 mVsec/rad 466.0 459.0 501.8 485.7 498.7
E5-24 Induction voltage constant 2 mV/min-1 0.0 0.0 0.0 0.0 0.0
E1-04 Maximum output frequency Hz 87.5 87.5 87.5 87.5 87.5
E1-05 Maximum output voltage V 380.0 380.0 380.0 380.0 380.0
E1-06 Base voltage Hz 87.5 87.5 87.5 87.5 87.5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 403
B.2 Parameter Table
404 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
C
Network
Communications
This appendix details the specifications, connections, and
programming of the drive for MEMOBUS/Modbus
communication.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 405
C.1 MEMOBUS/Modbus Basic Set-Up
Master
Slaves
406 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
C.1 MEMOBUS/Modbus Basic Set-Up
◆ Communication Specifications
The MEMOBUS/Modbus communication specifications are explained in Table C.1.
Table C.1 MEMOBUS/Modbus Communication Specifications
Item Specifications
Interface RS-422, RS-485
Communications Cycle Asynchronous (Start-stop synchronization)
Baud rate: Select from 1200 to 115200 bps.
Data length: 8 bits fixed
Communications Parameters
Parity: Select from even, odd, or none.
Stop bits: 1 bit selected
Communications Protocol MEMOBUS/Modbus RTU
Number of Connectable Units 31 units maximum
S+ +
-
Communications
S-
RS-422A
or RS-485 R+
Network
Switch
R- 1
S2 Position Description
ON Internal terminal resistance ON
OFF Internal terminal resistance OFF (no terminal resistance); default setting
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 407
C.1 MEMOBUS/Modbus Basic Set-Up
Figure C.3
A
B C
A – DIP switch S2 C – ON
B – OFF D –
408 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
C.1 MEMOBUS/Modbus Basic Set-Up
Figure C.4
R+ R㧙 S+ S㧙 IG
P1 P2 PC A1 A2 +V AC AM AC MP
MA MB MC
S1 S2 S3 S4 S5 S6 S7 HC SC H1 RP
Communications
◆ Communication Set-Up Procedure
Network
Use the following procedure to communicate with the PLC.
1. Turn OFF the input to the drive power and connect the communication cable
2.
between the PLC (or other master device) and the drive.
Turn ON the input power to the drive. C
3. Set the required communication parameters (H5-01 to H5-07) using the Digital
Operator.
4. Turn OFF the input to the drive power, and check that the Digital Operator display
has completely extinguished.
5. Turn ON the input power to the drive once again.
6. Perform communication with the master device.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 409
C.1 MEMOBUS/Modbus Basic Set-Up
Parameter Name
Parameter Digital Operator Setting Factory
No. Description Range Setting
Display
Selects the frequency reference input source.
0: Operator - Digital preset speed U1-01 or d1-01 to d1-17.
Frequency 1: Terminals - Analog input terminal A1 (or terminal A2
Reference based on parameter H3-09).
b1-01 0 to 4 1
Selection 2: Serial Com - MEMOBUS/Modbus RS-422/485 terminals
Reference Source R+, R-, S+ and S-.
3: Option PCB
4: Pulse Input (Terminal RP)
Selects the run command input source.
0: Operator - RUN and STOP keys on the digital operator.
Run Command
1: Terminals - Contact closure on terminals S1 or S2.
b1-02 Selection 0 to 3 1
2: Serial Com - MEMOBUS/Modbus RS-422/485 terminals
Run Source
R+, R-, S+ and S-.
3: Option PCB.
Selects drive station node number (address) for MEMOBUS/
Drive Node Address 0 to 20
H5-01 Modbus terminals R+, R-, S+, S-. Cycle power for the 1F
Serial Comm Adr Hex
setting to take effect.
Selects the baud rate for MEMOBUS/Modbus terminals R+,
R-, S+ and S-. Cycle power for the setting to take effect.
0: 1200 bps
1: 2400 bps
Communication
2: 4800 bps
Speed
H5-02 3: 9600 bps 0 to 4 3
Selection
4: 19200 bps
Serial Baud Rate
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Selects the communication parity for MEMOBUS/Modbus
Communication terminals R+, R-, S+ and
Parity S-. Cycle power for the setting to take effect.
H5-03 0 to 2 0
Selection 0: No parity
Serial Com Sel 1: Even parity
2: Odd parity
Selects the stopping method when a communication time-out
Stopping Method
fault (CE) is detected.
After
0: Ramp to stop
H5-04 Communication 0 to 3 3
1: Coast to stop
Error
2: Fast-stop
Serial Fault Sel
3: Alarm only
410 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
C.1 MEMOBUS/Modbus Basic Set-Up
Note: An OR operation is performed between the multi-function command input from the master
device and the command input from multi-function digital input terminals S3 to S8.
Communications
Network
C
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 411
C.1 MEMOBUS/Modbus Basic Set-Up
412 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D
Standards
Compliance
This chapter explains the guidelines and criteria for maintaining
CE and UL standards.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 413
D.1 Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety
shields to show details. Be sure to reinstall covers or shields before
operating the drives and run the drives according to the instructions
described in this manual.
414 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.1 Section Safety
WARNING
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed
only by authorized personnel familiar with installation, adjustment and
maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
WARNING
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire
Standards Compliance
due to overheating of electrical connections.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 415
D.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when
handling the drive and circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive
is outputting voltage.
Improper equipment sequencing could result in damage to the drive.
Check all the wiring to ensure that all connections are correct after
installing the drive and connecting other devices.
Failure to comply could result in damage to the drive.
416 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.2 European Standards
Standards Compliance
■ Area of Use
Do not use drives in areas with pollution higher than severity 2 and overvoltage category 3
in accordance with IEC664.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 417
D.2 European Standards
418 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.2 European Standards
Standards Compliance
in combination with this drive also comply with EMC guidelines.
1. Install an EMC noise filter to the input side specified by Yaskawa for compliance
with European standards.
2. Place the drive and EMC noise filter in the same enclosure.
3. Use braided shield cable for the drive and motor wiring or run the wiring through a
metal conduit.
4. Keep wiring as short as possible. Ground the shield on both the drive side and the
motor side.
D
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 419
D.2 European Standards
Figure D.2
A D C
U/T1 U
V/T2 V
M
W/T3 W
5. Ground the largest possible surface area of the shield to the metal conduit when
using braided shield cable. Yaskawa recommends using a cable clamp.
Figure D.3
C B
420 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.2 European Standards
L3 A
L2
L1
PE
H
B
C
D
L3 L2 L1
J E
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
D
D
I
H F
Standards Compliance
A
G
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 421
D.2 European Standards
A
L2
L1
PE
B
C
D
L3 L2 L1
J
E
R/L1 S/L2 T/L3 U/T1 V/T2 W/T3
D
D
I
H F
A
G
422 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.2 European Standards
■ EMC Filters
The drive should be installed with the EMC filters listed below in order to comply with the
EN 61800-3, category C1 requirements.
Table D.2 EN 61800-3 Category C1 Filters
Standards Compliance
2A0030 FS 5973-35-07 35 1.4 141 × 330 × 46 115 × 313 M4 M5
2A0040 FS 5973-60-07 60 3.0 206 × 355 × 60 175 × 336 M5 M6
2A0056 FS 5973-60-07 60 3.0 206 × 355 × 60 175 × 336 M5 M6
2A0069 FS 5973-100-07 100 4.9 236 × 408 × 80 205 × 390 M8 M8
200 V Three-Phase Units
4A0001 FS 5857-5/07 5 0.5 111 × 169 × 45 91 × 156 M4 M5
4A0002 FS 5857-5/07 5 0.5 111 × 169 × 45 91 × 156 M4 M5
4A0004 FS 5857-10/07 10 0.75 111 × 169 × 45 91 × 156 M4 M5
D
4A0005 FS 5857-10/07 10 0.75 111 × 169 × 45 91 × 156 M4 M5
4A0007 FS 5857-10/07 10 0.75 111 × 169 × 45 91 × 156 M4 M5
4A0009 FS 5857-20/07 20 1.0 144 × 174 × 50 120 × 161 M4 M5
4A0011 FS 5857-20/07 20 1.0 144 × 174 × 50 120 × 161 M4 M5
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 423
D.2 European Standards
W H
Y
LINE
X
L
LOAD
A
PE
■ DC Reactors
Table D.3 DC Reactors for Harmonics Reduction
Note: Contact Yaskawa for information about DC reactors for other models.
424 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.3 UL Standards
D.3 UL Standards
The UL/cUL mark applies to products in the United States and Canada indicates that UL has
performed product testing and evaluation and determined that their stringent standards for
product safety have been met. For a product to receive UL certification, all components
inside that product must also receive UL certification.
Figure D.7
C UL
R US
LISTED
Figure D.7 UL/cUL Mark
◆ UL Standards Compliance
This drive is tested in accordance with UL standard UL508C and complies with UL
requirements. The following conditions must be met to maintain compliance when using this
drive in combination with other equipment:
■ Installation Area
Do not install the drive to an area greater than pollution severity 2 (UL standard).
■ Main Circuit Terminal Wiring
Yaskawa recommends using UL-listed copper wires (rated at 75°C) and closed-loop
connectors or CSA-certified ring connectors sized for the selected wire gauge to maintain
proper clearances when wiring the drive. Use the correct crimp tool to install connectors per
manufacturer recommendation. Table D.4 lists a suitable closed-loop connector
Standards Compliance
manufactured by JST Corporation.
Table D.4 Closed-Loop Crimp Terminal Size (JIS C 2805)
(same for 200 V and 400 V)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 425
D.3 UL Standards
<1> Use the specified crimp terminals (Model 14-NK5) when using CIMR-V 2A0030, V 2A0040, V 4A0023
with 14 mm2 (6 AWG).
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should
have a continuous maximum allowable temperature of 75°C 600 Vac UL-approved vinyl-
sheathed insulation.
Table D.5 Recommended Input Fuse Selection
Time Delay/
Drive Model CIMR-V Class RK5 Fuses Fuse Ampere Rating
600 Vac, 200 kAIR
200 V Class Single-Phase Drives
BA0001 TRS5R 5
BA0002 TRS10R 10
BA0003 TRS20R 20
BA0006 TRS35R 35
BA0010 TRS50R 50
BA0012 TRS60R 60
200 V Class Three-Phase Drives
2A0001 TRS5R 5
426 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.3 UL Standards
Time Delay/
Drive Model CIMR-V Class RK5 Fuses Fuse Ampere Rating
600 Vac, 200 kAIR
2A0002 TRS5R 5
2A0004 TRS10R 10
2A0006 TRS15R 15
2A0010 TRS25R 25
2A0012 TRS35R 35
2A0020 TRS60R 60
2A0030 70
2A0040 100
Contact Yaskawa
2A0056 150
2A0069 200
400 V Class Three-Phase Drives
4A0001 TRS2.5R 2.5
4A0002 TRS5R 5
4A0004 TRS10R 10
4A0005 TRS20R 20
4A0007 TRS20R 20
4A0009 TRS20R 20
4A0011 TRS30R 30
4A0018 50
4A0023 60
Contact Yaskawa
4A0031 70
4A0038 80
Standards Compliance
■ Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local
codes for wiring. Use a class 2 (UL regulations) power supply for the control circuit
terminal.
Table D.6 Control Circuit Terminal Power Supply
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 427
D.3 UL Standards
Setting Description
0 Disabled
1 Std Fan Cooled (< 10:1 motor) (factory default)
2 Standard Blower Cooled (10:1 motor)
3 Vector Motor (1000:1 motor)
428 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.3 UL Standards
Setting Description
4 PM motor
Disable the electronic overload protection (L1-01 = 0: Disabled) and wire each motor with
its own motor thermal overload when connecting the drive to more than one motor for
simultaneous operation.
Enable the motor overload protection (L1-01 = “1”, “2”, or “3”) when connecting the drive
to a single motor unless there is another means of preventing motor thermal overload. The
electronic thermal overload function causes an OL1 fault, which shuts off the output of the
drive and prevents additional overheating of the motor. The motor temperature is continually
calculated as long as the drive is powered up.
Setting L1-01 = 1 selects a motor with limited cooling capability below rated (base) speed
when running at 100% load. The OL1 function derates the motor when it is running below
base speed.
Setting L1-01 = 2 selects a motor capable of cooling itself over a 10:1 speed range when
running at 100% load. The OL1 function derates the motor when it is running at 1/10 or less
of its rated speed.
Setting L1-01 = 3 selects a motor capable of cooling itself at any speed — including zero
speed — when running at 100% load. The OL1 function does not derate the motor at any
speed.
Setting L1-01 = 4 selects protection for a PM motor.
■ L1-02 Motor Overload Protection Time
Setting Range: 0.1 to 20.0 Minutes
Factory Default: 8.0 Minutes
The L1-02 parameter sets the allowed operation time before the OL1 fault occurs when the
Standards Compliance
drive is running at 60 Hz and 133% of the full load amp rating (E2-01) of the motor.
Adjusting the value of L1-02 can shift the set of OL1 curves up the Y-axis of the diagram
below but will not change the shape of the curves.
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 429
D.3 UL Standards
Figure D.8
10H z 60H z
10
8
1
6
430 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.4 Safe Disable Input Precautions
◆ Installation
• If the Safe Disable function is utilized, the wire link between the terminals HC and H1,
which is preinstalled at the shipment, has to be removed entirely.
• Connect the drive to an EN954-1, Safety Category 3 interrupting device so that in case of
a safe stop request the connection between the terminals HC and H1 is opened.
Figure D.9
Power Supply
Drive
EN954-1 Safety
Cat, 3 Device
HC Controller
Standards Compliance
H1
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 431
D.4 Safe Disable Input Precautions
432 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.5 User Setting Table
Standards Compliance
b1-07 Local/Remote Run Selection L3-01 Stall Prevention Selection during Accel.
Run Command Selection while in
b1-08 L3-02 Stall Prevention Level during Accel.
Programming Mode
b1-14 Phase Order Selection L3-03 Stall Prevention Limit during Accel.
Stall Prevention Selection during
b1-15 Frequency Reference 2 L3-04
Deceleration
b1-16 Run Command Source 2 L3-05 Stall Prevention Selection during Run
b1-17 Run Command at Power Up L3-06 Stall Prevention Level during Run D
b2-01 DC Injection Braking Start Frequency L3-11 OV Suppression Function Selection
Overvoltage Suppression and
b2-02 DC Injection Braking Current L3-17 Deceleration Stall (Desired DC Bus
Voltage during Motor Stall)
DC Injection Braking Time/DC Main Power Circuit Voltage Adjustment
b2-03 L3-20
Excitation Time at Start Gain
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 433
D.5 User Setting Table
434 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.5 User Setting Table
Standards Compliance
b6-02 Dwell Time at Start L8-38 Carrier Frequency Reduction
b6-03 Dwell Frequency at Stop L8-41 Current Alarm Selection
b6-04 Dwell Time at Stop n1-01 Hunting Prevention Selection
b8-01 Energy Saving Control Selection n1-02 Hunting Prevention Gain Setting
b8-02 Energy Saving Gain n1-03 Hunting Prevention Time Constant
Energy Saving Control Filter Time Hunting Prevention Gain while in
b8-03 n1-05
Constant Reverse
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 435
D.5 User Setting Table
C2-03 S-Curve Characteristic at Decel Start n8-51 Acceleration Time Pull-In Current
436 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.5 User Setting Table
Standards Compliance
d1-10 Frequency Reference 10 r1-04 DWEZ Connection Parameter 2 (lwr.)
d1-11 Frequency Reference 11 r1-05 DWEZ Connection Parameter 3 (upr.)
d1-12 Frequency Reference 12 r1-06 DWEZ Connection Parameter 3 (lwr.)
d1-13 Frequency Reference 13 r1-07 DWEZ Connection Parameter 4 (upr.)
d1-14 Frequency Reference 14 r1-08 DWEZ Connection Parameter 4 (lwr.)
d1-15 Frequency Reference 15 r1-09 DWEZ Connection Parameter 5 (upr.)
d1-16 Frequency Reference 16 r1-10 DWEZ Connection Parameter 5 (lwr.)
d1-17 Jog Frequency Reference r1-11 DWEZ Connection Parameter 6 (upr.) D
d2-01 Frequency Reference Upper Limit r1-12 DWEZ Connection Parameter 6 (lwr.)
d2-02 Frequency Reference Lower Limit r1-13 DWEZ Connection Parameter 7 (upr.)
d2-03 Master Speed Reference Lower Limit r1-14 DWEZ Connection Parameter 7 (lwr.)
d3-01 Jump Frequency 1 r1-15 DWEZ Connection Parameter 8 (upr.)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 437
D.5 User Setting Table
438 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.5 User Setting Table
Standards Compliance
E3-12 Motor 2 Mid Output Freq. Voltage 2 U1-14 Terminal A2 Input Voltage
E3-13 Motor 2 Base Voltage (VBASE) U1-16 Output Frequency after Soft Start
E4-01 Motor 2 Rated Current U1-18 OPE Fault Parameter
E4-02 Motor 2 Rated Slip U1-19 MEMOBUS/Modbus Error Code
E4-03 Motor 2 Rated No-Load Current U1-24 Input Pulse Monitor
E4-04 Motor 2 Motor Poles U1-25 Software No. (Flash)
E4-05 Motor 2 Line-to-Line Resistance U1-26 Software No. (ROM) D
E4-06 Motor 2 Leakage Inductance U2-01 Current Fault
Motor 2 Motor Iron-Core Saturation
E4-07 U2-02 Previous Fault
Coefficient 1
Motor 2 Motor Iron-Core Saturation
E4-08 U2-03 Frequency Reference at Previous Fault
Coefficient 2
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 439
D.5 User Setting Table
440 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
D.5 User Setting Table
Standards Compliance
(open-collector)
H2-06 Watt Hour Output Unit Selection U4-02 Number of Run Commands
H3-01 Terminal A1 Signal Level Selection U4-03 Cooling Fan Operation Time
H3-02 Terminal A1 Function Selection U4-05 Capacitor Maintenance
H3-03 Terminal A1 Gain Setting U4-07 IGBT Maintenance
H3-04 Terminal A1 Bias Setting U4-09 LED Check
H3-09 Terminal A2 Signal Level Selection U4-10 kWH, Lower 4 Digits
H3-10 Terminal A2 Function Selection
H3-11 Terminal A2 Gain Setting
U4-11 kWH, Upper 5 Digits
U4-13 Peak Hold Current
D
Frequency Reference (Current)
H3-12 U4-14 Peak Hold Output Frequency
Terminal A2 Input Bias
H3-13 Analog Input Filter Time Constant U4-16 Motor Overload Estimate (OL1)
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 441
D.5 User Setting Table
442 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
A2-01 to A2-32 . . . . . . . . . . . . . . . . . . . 312, 433
A2-32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
A2-33. . . . . . . . . . . . . . . . . . 113, 165, 312, 433
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 443
Control). . . . . . . . . . . . . . . . . . . . . . . . . 323, 437 b3-10 . . . . . . . . . . . . . . . . . . . . . . .203, 315, 434
ASR Proportional Gain 2 (for Simple PG V/f b3-14 . . . . . . . . . . . . . . . . . . . . . . .203, 315, 434
Control). . . . . . . . . . . . . . . . . . . . . . . . . 323, 437 b3-17 . . . . . . . . . . . . . . . . . . . . . . .203, 315, 434
Auto Restart Operation Selection . . . . . 359, 434 b3-18 . . . . . . . . . . . . . . . . . . . . . . .203, 316, 434
Automatic Reduction Selection for Stall b3-19 . . . . . . . . . . . . . . . . . . 201, 203, 316, 434
Prevention during Run . . . . . . . . . . . . . 357, 434 b3-24 . . . . . . . . . . . . . . 198, 199, 201, 316, 434
Auto-Tuning153, 155, 156, 157, 159, 161, 162 b3-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
Auto-Tuning Codes. . . . . . . . . . . . . . . . . . . . . 222 b4 Timer Function . . . . . . . . . . . . . . . . . . . . . 316
Auto-Tuning Fault Codes . . . . . . . . . . . . . . . . 157 b4-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
Auto-Tuning Fault Detection . . . . . . . . . . . . . 222 b4-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
Auto-Tuning Fault Solutions . . . . . . . . . . . . . 222 b5 PID Control. . . . . . . . . . . . . . . . . . . . . . . . 316
Auto-Tuning for V/f Control . . . . . . . . . . . . . 154 b5-01 . . . . . . . . . . . . . . 218, 220, 241, 316, 434
Auto-Tuning Mode Selection . . . . 160, 375, 438 b5-02 . . . . . . . . . 316, 317, 318, 319, 434, 435
Auxiliary Frequency Reference 1. . . . . . . . . . 349 b5-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
b5-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
B b5-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 316, 434
b1 Operation Mode Selection . . . . . . . . . . . . . 313 b5-06 . . . . . . . . . . . . . . . . . . . . . . . . . . . 317, 434
b1-01 . 124, 126, 170, 229, 313, 410, 411, 433 b5-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . 317, 434
b1-02 127, 128, 200, 219, 229, 313, 410, 411, b5-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 317, 434
433 b5-09 . . . . . . . . . . . . . . . . . . . . . . .238, 317, 434
b1-03 . . . . . . . . . . . . . . . . . . .129, 130, 131, 220 b5-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 317, 434
b1-04 . . . . . . . . . . . . . . . . . . . . . . . 231, 240, 313 b5-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . 317, 434
b1-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 433 b5-12 . . . . . . . . . . . . . . . . . . . . . . .193, 317, 435
b1-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 313, 433 b5-13 . . . . . . . . . . . . . . . . . . 193, 210, 317, 435
b1-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . 314, 433 b5-13 and b5-14. . . . . . . . . . . . . . . . . . . . . . . 193
b1-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . 314, 433 b5-14 . . . . . . . . . . . . . . . . . . 193, 210, 317, 435
b1-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . 314, 433 b5-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b1-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . 314, 433 b5-16 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2 DC Injection Braking. . . . . . . . . . . . . . . . . 314 b5-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-01 . . . . . . . . . . . . . . . . . . . . . . . 129, 314, 433 b5-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-02 . . . . . . . . . . . . . . 129, 236, 238, 314, 433 b5-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-03 . . . . . . . . . . . . . . . . . . . . . . . 238, 314, 433 b5-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-04 . . . . . . . . . . . . . . . . . . .129, 238, 314, 434 b5-34 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 315, 434 b5-35 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b2-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . 315, 434 b5-36 . . . . . . . . . . . . . . . . . . 192, 210, 318, 435
b2-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 434 b5-36 and b5-37. . . . . . . . . . . . . . . . . . . . . . . 193
b3 Speed Search . . . . . . . . . . . . . . . . . . . . . . . 315 b5-37 . . . . . . . . . . . . . . . . . . 192, 210, 318, 435
b3-01 . . . . . . . . . . . . . . . . . . . . . . . 238, 315, 434 b5-38 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b3-02 . . . . . . . . . . . . . . . . . . .198, 201, 315, 434 b5-39 . . . . . . . . . . . . . . . . . . . . . . . . . . . 318, 435
b3-03 . . . . . . . . . . . . . . . . . . .198, 201, 315, 434 b6 Dwell Function . . . . . . . . . . . . . . . . . . . . . 319
b3-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 315, 434 b6-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 319, 435
444 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
b6-01 through b6-04 . . . . . . . . . . . . . . . . . . . . 180 C1-03 . . . . . . . . . . . . . . . . . . . . . . .233, 320, 436
b6-02. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-04 . . . . . . . . . . . . . . . . . . . . . . .235, 320, 436
b6-03. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
b6-04. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-06 . . . . . . . . . . . . . . . . . . . . . . .235, 320, 436
b8 Energy Saving . . . . . . . . . . . . . . . . . . . . . . 319 C1-07 . . . . . . . . . . . . . . . . . . . . . . .233, 320, 436
b8-01. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-08 . . . . . . . . . . . . . . . . . . . . . . .235, 320, 436
b8-02. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-09 . . . . . . . . . . . . . . . . . . . . . . .132, 321, 436
b8-03. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-10 . . . . . . . . . . . . . . . . . . . . . . .132, 321, 436
b8-04. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C1-11 . . . . . . . . . . . . . . . . . . . . . . .133, 321, 436
b8-05. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C2 S-Curve Characteristics . . . . . . . . . . . . . . 321
b8-06. . . . . . . . . . . . . . . . . . . . . . . . . . . .319, 435 C2-01 . . . . . . . . . . . . . . . . . . . . . . .203, 321, 436
Base Frequency . . . . . . . . . . . . . . . . . . . . . . . 198 C2-01 through C2-04. . . . . . . . . . . . . . . 180, 195
Base Frequency (FA) . . . . . . . . . . . . . . .331, 438 C2-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 321, 436
Base Voltage (VBASE) . . . . . . . . . . . . .331, 438 C2-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 321, 436
Baseblock . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206 C2-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 321, 436
Baseblock 2 . . . . . . . . . . . . . . . . . . . . . . . . . . 347 C3 Slip Compensation. . . . . . . . . . . . . . . . . . 321
Baseblock Command (N.C.). . . . . . . . . . . . . . 342 C3-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 177, 179
Baseblock Command (N.O.) . . . . . . . . . . . . . 342 C3-02 . . . . . . . . . . . . . . . . . . 179, 237, 321, 436
Baseblock Signal Input. . . . . . . . . 184, 210, 211 C3-03 . . . . . . . . . . . . . . . . . . . . . . .234, 322, 436
Basic Drive Operation . . . . . . . . . . . . . . . . . . 122 C3-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 322, 436
bb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184, 206 C3-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 322, 436
Bi-Directional Speed Search Selection .315, 434 C4 Torque Compensation . . . . . . . . . . . . . . . 322
Braking Resistor . . . . . . . . . . . . . . . . . . . . . . . . 82 C4-01 . . . . . . . . . . . . . . . . . . 177, 195, 199, 230
Braking Resistor Adjustments . . . . . . . . . . . . . 83 C4-02 . . . . . 177, 178, 220, 237, 239, 322, 436
Braking Resistor Fault . . . . . . . . . . . . . . . . . . 346 C4-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 322, 436
Braking Resistor Overheat . . . . . . . . . . . . . . . 202 C4-05 . . . . . . . . . . . . . . . . . . . . . . .322, 323, 436
Braking Resistor, Installation . . . . . . . . . . . . . . 82 C4-06 . . . . . . . . . . . . . . . . . . . . . . .178, 179, 220
bUS . . . . . . . . . . . . . . . . . . . . 182, 184, 187, 206 C5 Speed Control (ASR). . . . . . . . . . . . . . . . 323
Buzzing Sound from Motor at 2 kHz . . . . . . . 239 C5-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 200, 213
C5-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 200, 213
C C6 Carrier Frequency . . . . . . . . . . . . . . . . . . 323
C Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 C6-01 . . . . . . . . . . . . . . . . . . . . . . .177, 323, 437
C1 Acceleration and Deceleration Times. . . . 320 C6-02 . 84, 177, 179, 196, 199, 235, 236, 237,
C1-01 . . . . .103, 132, 223, 224, 233, 320, 436 241, 324, 437
C1-01 through C1-08 .191, 197, 198, 199, 202, C6-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 324, 437
203, 208, 211, 212 C6-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 324, 437
C1-01 through C1-11 . . . . . . . . . . . . . . . . . . . 180 C6-05 . . . . . . . . . . . . . . . . . . . . . . .237, 324, 437
C1-01, -03, -05, -07 . . . . . . . . . . . . . . . . . . . . 195 Cable Length Between Drive and Motor . . . . 67
C1-02 . . . . . . . . . . . . . 132, 188, 235, 320, 436 CALL. . . . . . . . . . . . . . . . . . . . . . . . . . . 184, 207
C1-02, -04, -06 and -08 . . . . . . . . . . . . . . . . . 200 Cannot Change Parameter Settings . . . . . . . . 228
C1-02, -04, -06, -08 . . . . . . . . . . . . . . . . . . . . 200 Capacitor Maintenance . . . . . . . . . . . . . 151, 383
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 445
Capacitor Maintenance Setting. . . . . . . 372, 437 Copy Allowed Selection . . . . . . . . . . . . . . . . 437
Carrier Frequency Lower Limit . . . . . . 324, 437 Copy Function Selection . . . . . . . . . . . . . . . . 437
Carrier Frequency Proportional Gain . . 324, 437 Copy Mode Selection . . . . . . . . . . . . . . . . . . 437
Carrier Frequency Reduction . . . . . . . . 365, 435 CPF02 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 188
Carrier Frequency Selection .177, 179, 324, 437 CPF03 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 188
Carrier Frequency Setting Error . . . . . . 186, 221 CPF06 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Carrier Frequency Upper Limit . . . . . . 324, 437 CPF07 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 189
CE . . . . . . . . . . . . . . . . . . . . .182, 184, 187, 207 CPF08 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 189
CE Detection Time . . . . . . . . . . . . . . . . 350, 442 CPF11 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 189
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 417 CPF12 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 189
CF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 188 CPF13 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 189
CI-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 240 CPF14 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
clock error. . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 CPF16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Clock Fault . . . . . . . . . . . . . . . . . . . . . . 183, 190 CPF17 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
Coast to Stop. . . . . . . . . . . . . . . . . . . . . . . . . . 130 CPF18 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
Coast to Stop with Timer . . . . . . . . . . . . . . . . 131 CPF19 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
Communication Fault Detection Selection. . 350, CPF20 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
442 CPF21 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 190
Communication Parity Selection . . . . . 350, 442 CPF22 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 190
Communication Speed Selection . . . . . 350, 442 CPF23 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 191
Communications ENTER Function Selection351, CPF24 . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 191
442 Cumulative Operation Time at 10th Most Recent
Communications Test Mode . . . . . . . . . . . . . . 344 Fault . . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
Connected Machinery Vibrates When Motor Cumulative Operation Time at 2th Most Recent
Rotates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236 Fault . . . . . . . . . . . . . . . . . . . . . . . .150, 382, 441
Constant Torque . . . . . . . . . . . . . . . . . . . . . . . 140 Cumulative Operation Time at 3th Most Recent
Control Circuit Connection Diagram . . . . . . . . 69 Fault . . . . . . . . . . . . . . . . . . . . . . . .150, 382, 441
Control Circuit Fault. . . . . . . . . . . . . . . 183, 190 Cumulative Operation Time at 4th Most Recent
Control Circuit Input Terminals . . . . . . . . . . . . 70 Fault . . . . . . . . . . . . . . . . . . . . . . . .150, 382, 441
Control Circuit Output Terminals . . . . . . . . . . . 71 Cumulative Operation Time at 5th Most Recent
Control Circuit Terminal Block Configuration72, Fault . . . . . . . . . . . . . . . . . . . . . . . .150, 382, 441
409 Cumulative Operation Time at 6th Most Recent
Control Circuit Terminal Block Functions . . . . 70 Fault . . . . . . . . . . . . . . . . . . . . . . . .151, 382, 441
Control Fault. . . . . . . . . . . . . . . . . . . . . 182, 188 Cumulative Operation Time at 7th Most Recent
Control Method Selection. . . . . . . . . . . 311, 433 Fault . . . . . . . . . . . . . . . . . . . . . . . .151, 382, 441
Control Mode . . . . . . . . . . . . . . . . 150, 377, 439 Cumulative Operation Time at 8th Most Recent
Control Power Supply Undervoltage . . . . . . . 183 Fault . . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
Cooling Fan Maintenance Setting (Operation Cumulative Operation Time at 9th Most Recent
Time). . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 Fault . . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
Cooling Fan Operation Time . . . . 151, 383, 441 Cumulative Operation Time at Most Recent Fault
Cooling Fan Replacement. . . . . . . . . . . . . . . . 254 150, 382, 441
446 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Cumulative Operation Time at Previous Fault151, d4-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 328, 438
381, 440 d4-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . 328, 438
Current Alarm. . . . . . . . . . . . . . . . . . . . .185, 211 d7 Offset Frequency . . . . . . . . . . . . . . . . . . . 329
Current Alarm Selection. . . . . . . . . . . . .365, 435 d7-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 329, 438
Current Detection Error . . . . . . . . . . . . .186, 224 d7-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 329, 438
Current Fault. . . . . . . . . . . . . . . . . 151, 380, 439 d-Axis ACR Output. . . . . . . . . . . .152, 386, 442
Current Offset Fault . . . . . . . . . . . . . . . . . . . . 188 DC Bus Overvoltage . . . . . . . . . . . . . . . . . . . 213
Current Unbalance Detection (LF2). . . .365, 435 DC Bus Undervoltage . . . . . . . . . . . . . . 204, 346
DC Bus Voltage . . . . . . . . . . . . . . .151, 377, 439
D DC Bus Voltage at Previous Fault .151, 381, 440
d References . . . . . . . . . . . . . . . . . . . . . . . . . . 325 DC Injection Braking . . . . . . . . . . . . . . . . . . 236
d1 Frequency Reference . . . . . . . . . . . . . . . . . 325 DC Injection Braking at start. . . . . . . . . . . . . 238
d1-01. . . . . . . . . . . . . . 168, 170, 325, 326, 437 DC Injection Braking at Stop . . . . . . . . . . . . 238
d1-02. . . . . . . . . . . . . . . . . . . . . . . 168, 325, 437 DC Injection Braking Command. . . . . . . . . . 343
d1-03. . . . . . . . . . . . . . . . . . . . . . . 168, 325, 437 DC Injection Braking Current . . . .238, 314, 433
d1-04. . . . . . . . . . . . . . . . . . . . . . . 168, 325, 437 DC Injection Braking Current 2 . . . . . . . . . . 434
d1-05. . . . . . . . . . . . . . . . . . . . . . . . . . . .325, 437 DC Injection Braking Start Frequency . 314, 433
d1-07. . . . . . . . . . . . . . . . . . . . . . . . . . . .325, 437 DC Injection Braking Time/DC Excitation Time at
d1-09. . . . . . . . . . . . . . . . . . . . . . . . . . . .325, 437 Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314, 433
d1-10. . . . . . . . . . . . . . . . . . . . . . . . . . . .325, 437 DC Injection Braking to Stop . . . . . . . . . . . . 130
d1-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . .326, 437 Deceleration Rate Calculation Gain . . . 357, 434
d1-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 Deceleration Takes Too Long With Dynamic
d1-15. . . . . . . . . . . . . . . . . . . . . . . . . . . .326, 437 Braking Enabled . . . . . . . . . . . . . . . . . . . . . . 235
d1-16. . . . . . . . . . . . . . . . . . . . . . . . . . . .326, 437 Deceleration Time 1 . . . . . . . . . . .132, 320, 436
d1-17. . . . . . . . . . . . . . . . . . . . . . . 166, 326, 437 Deceleration Time 2 . . . . . . . . . . . . . . . 320, 436
d2 Frequency Upper and Lower Limits . . . . . 326 Deceleration Time 3 (Motor 2 Decel Time 1)320,
d2-01. . . . . . . . . . . . . . . . . . . . . . . 239, 326, 437 436
d2-02. . . . . . . . . . . . . . . . . . . . . . . . . . . .326, 437 Deceleration Time 4 . . . . . . . . . . . . . . . 320, 436
d2-03. . . . . . . . . . . . . . . . . . . . . . . . . . . .326, 437 Deceleration Time at Stall Prevention during
d3 Jump Frequency. . . . . . . . . . . . . . . . . . . . . 327 Acceleration. . . . . . . . . . . . . . . . . . . . . . 357, 434
d3-01. . . . . . . . . . . . . . . . . . . . . . . 237, 327, 437 Derated Torque . . . . . . . . . . . . . . . . . . . . . . . 141
d3-01 through d3-03 . . . . . . . . . . . . . . . . . . . . 239 Derivative Time. . . . . . . . . . . . . . . . . . . 316, 434
d3-01 through d3-04 . . . . . . . . . . . . . . . . . . . . 180 dEv. . . . . . . . . . . . . . . . . . . . 182, 184, 191, 208
d3-02. . . . . . . . . . . . . . . . . . . . . . . . . . . .327, 438 Differential PID Feedback. . . . . . . . . . . . . . . 349
d3-03. . . . . . . . . . . . . . . . . . . . . . . . . . . .327, 438 Digital Operator Connection Fault . . . . . . . . 200
d3-04. . . . . . . . . . . . . . . . . . . . . . . 237, 327, 438 Digital Operator Display Selection . . . . 370, 436
d4 Frequency Reference Hold . . . . . . . . . . . . 327 DIP Switch S1 . . . . . . . . . . . . . . . . . . . . . . . . . 80
d4-01. . . . . . . . . . . . . . . . . . . . . . . . . . . .327, 438 dnE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184, 208
d4-04. . . . . . . . . . . . . . . . . . . 327, 328, 329, 438 Down 2 Command. . . . . . . . . . . . . . . . . . . . . 344
d4-06. . . . . . . . . . . . . . . . . . . . . . . . . . . .328, 438 Down Command . . . . . . . . . . . . . . . . . . . . . . 342
d4-07. . . . . . . . . . . . . . . . . . . . . . . . . . . .328, 438 Drive Baseblock . . . . . . . . . . . . . . . . . . . . . . 184
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 447
Drive Capacity Setting Fault . . . . . . . . . . . . . 217 Dynamic Braking Transistor . . . . . . . . . 183, 203
Drive Capacity Signal Fault . . . . . . . . . 182, 191
Drive Cooling Fans. . . . . . . . . . . . . . . . . . . . . 254 E
Drive Disabled . . . . . . . . . . . . . . . . . . . 184, 208 çÝëÂìKópÉÇÅ . . . . . . . . . . 293, 294, 296, 297
Drive Does Not Allow Selection of Rotational E1 V/f Pattern Characteristics . . . . . . . . . . . . 330
Auto-Tuning . . . . . . . . . . . . . . . . . . . . . . . . . . 232 E-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Drive Enable . . . . . . . . . . . . . . . . . . . . . 344, 347 E1-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 138, 438
Drive Input Voltage Setting . . . . . . . . . . . . . . 138 E1-03 .139, 140, 230, 233, 235, 330, 389, 438
Drive Intended Use . . . . . . . . . . . . . . . . . . . . . . 12 E1-03 V/F Pattern Settings . . . . . . . . . . . . . . 389
Drive kVA Setting Error . . . . . . . . . . . . . . . . . 185 E1-03 V/F Pattern Settings for Drive Capacity
Drive Mode. . . . . . . . . . . . . . . .97, 98, 100, 347 200/400 V . . . . . . . . . . . . . . . . . . . . . . . . 389
Drive Mode Unit Monitor Selection. . . 370, 436 E1-04 139, 220, 233, 235, 239, 241, 331, 389,
Drive Models and Types . . . . . . . . . . . . . . . . . . 44 438
Drive Motor Overload Protection. . . . . . . . . . 428 E1-04 through E1-10 . . 195, 197, 198, 199, 212
Drive Node Address . . . . . . . . . . . . . . . 350, 442 E1-05 . . . . . . . . . . . . . . 139, 331, 389, 390, 438
Drive Operation Status at Previous Fault151, 381, E1-06 .140, 150, 198, 235, 331, 389, 390, 438
440 E1-07 . . . . . . . . . 140, 220, 331, 389, 390, 438
Drive Overheat . . . . . . . . . . . . . . . . . . . . . . . . 185 E1-08 139, 177, 179, 197, 198, 199, 230, 331,
Drive Overheat Alarm (OH2). . . . . . . . . . . . . 342 389, 390, 438
Drive Overheat Warning. . . . . . . . . . . . . . . . . 212 E1-08 and E1-10 . . . . . . . . . . . . . . . . . . . . . . 212
Drive Overload . . . . . . . . . . . . . . . . . . . 183, 198 E1-09 139, 220, 229, 230, 240, 331, 389, 390,
Drive Ready . . . . . . . . . . . . . . . . . . . . . . . . . . 346 438
Drive Replacement . . . . . . . . . . . . . . . . . . . . . 258 E1-10 140, 177, 179, 197, 198, 199, 230, 235,
Drive Short-Circuit Rating . . . . . . . . . . . . . . . 428 331, 389, 438
Drive Status. . . . . . . . . . . . . . . . . . 151, 379, 439 E1-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . 331, 438
Drive Status Monitors. . . . . . . . . . . . . . . . . . . 150 E1-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . 331, 438
Drive Transmit Wait Time . . . . . . . . . . 350, 442 E2 Motor Parameters . . . . . . . . . . . . . . . . . . . 331
Drive Watts Loss Data . . . . . . . . . . . . . . . . . . 302 E2-01 .142, 147, 177, 197, 198, 331, 428, 438
Drive/kVA Selection . . . . . . . . . . . . . . . 371, 436 E2-02 . . . . . . . . . . . . . . . . . . 143, 177, 331, 438
During Baseblock . . . . . . . . . . . . . . . . . . . . . . 346 E2-03 . . . . . . . . . . . . . . 143, 177, 222, 331, 438
During Fast-stop . . . . . . . . . . . . . . . . . . . . . . . 347 E2-04 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 438
During Run . . . . . . . . . . . . . . . . . . . . . . . . . . . 345 E2-05 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 439
During Run 2, Motor Switch Command Input185 E2-06 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 439
During Torque Limit. . . . . . . . . . . . . . . . . . . . 347 E2-07 . . . . . . . . . . . . . . . . . . 143, 224, 332, 439
Duty Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 E2-08 . . . . . . . . . . . . . . . . . . 143, 224, 332, 439
Dwell Frequency at Stop. . . . . . . . . . . . 319, 435 E2-09 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 439
Dwell Function . . . . . . . . . . . . . . . . . . . . . . . . 180 E2-10 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 439
Dwell Reference at Start . . . . . . . . . . . . 319, 435 E2-11 . . . . . . . . . . . . . . . . . . . . . . .143, 332, 439
Dwell Time at Start. . . . . . . . . . . . . . . . 319, 435 E2-12 . . . . . . . . . . . . . . . . . . 142, 143, 332, 439
Dwell Time at Stop . . . . . . . . . . . . . . . . 319, 435 E3 Motor 2 V/f Characteristics . . . . . . . . . . . 332
Dynamic Braking Resistor . . . . . . . . . . . . . . . 183 E3-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 332, 439
448 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
E3-04 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 EF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-04 through E3-10 . . . . . . . . . . . . . . . . . . . 195 EF3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-05 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 EF4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-06 . . . . . . . . . . . . . . . . . . . . . . 220, 333, 439 EF5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-07 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 EF6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-08 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 EF7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209
E3-09 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 Electrical Thermal Motor Protection. . . . . . . 146
E3-10 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 EMC Guidelines . . . . . . . . . . . . . . . . . . . . . . 417
E3-11 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 End1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 224
E3-12 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 End2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 224
E4 Motor 2 Parameters. . . . . . . . . . . . . . . . . . 333 End3. . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 225
E4-01 . . . . . . . . . . . . . . . . . . . . . . 147, 333, 439 Energy Saving Coefficient Value . . . . . 319, 435
E4-02 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 Energy Saving Control Filter Time Constant 319,
E4-03 . . . . . . . . . . . . . . . . . . . . . . . . . . .333, 439 435
E4-04 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 439 Energy Saving Control Selection . . . . . 319, 435
E4-05 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 439 Energy Saving Gain. . . . . . . . . . . . . . . . 319, 435
E4-06 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 439 Energy Savings Coefficient Calculation Value . .
E4-07 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 439 152, 442
E4-08 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 439 Er-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 222
E4-09 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 222
E4-10 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 222
E4-11 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 223
E4-12 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 223
E4-14 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 223
E4-15 . . . . . . . . . . . . . . . . . . . . . . . . . . .334, 440 Er-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 223
E5 PM Motor Parameters . . . . . . . . . . . . . . . . 335 Er-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 224
E5-01 . . . . . . . . . . . . . . . . . . 195, 203, 220, 239 Er-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 224
E5-02 . . . . . . . . . . . . . . . . . . . . . . . . . . .335, 440 Err . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
E5-03 . . . . . . . . . . . . . . . . . . . . . . 220, 335, 440 European Standards . . . . . . . . . . . . . . . . . . . . 417
E5-04 . . . . . . . . . . . . . . . . . . . . . . . . . . .335, 440 Excessive Motor Oscillation and Erratic Rotation
E5-06 . . . . . . . . . . . . . . . . . . . . . . . . . . .335, 440 236
E5-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220 Excessive PID Feedback . . . 182, 184, 192, 210
E5-24 . . . . . . . . . . . . . . . . . . . . . . 220, 336, 440 Excessive Speed Deviation (for Simple V/f with
EEPROM Data Error . . . . . . . . . . . . . . . . . . . 189 PG). . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 184
EEPROM Serial Communication Fault . . . . . 189 Excessive Speed Deviation Detection Delay Time
EEPROM Serial Communications Fault . . . . 182 (for Simple PG V/f Control) . . . . . . . . . . . . . 440
EEPROM Write Error . . . . . . . . . . . . . . . . . . 192 Excessive Speed Deviation Detection Level (for
EF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .184, 208 Simple PG V/f Control). . . . . . . . . . . . . . . . . 440
EF0 . . . . . . . . . . . . . . . . . . . . 182, 184, 191, 209 Excessive V/f Setting . . . . . . . . . . . . . . 186, 224
EF1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .192, 209 External Fault . . . . . . . . . . . . . . . . . . . . 192, 210
EF1 to EF7 . . . . . . . . . . . . . . . . . . . . . . .182, 184 External Fault (input terminal S1 to S7) 182, 184
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 449
External Fault (user selection possible) . . . . . 343 FLASH Memory Fault. . . . . . . . . . . . . . 183, 189
External Search Command 1 . . . . . . . . . . . . . 344 FMAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
External Search Command 2 . . . . . . . . . . . . . 344 FMIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Forward Jog . . . . . . . . . . . . . . . . . . . . . . . . . . 342
F Forward Regenerative Torque Limit . . . 363, 434
F1 Simple PG V/f Parameters. . . . . . . . . . . . . 336 Forward Run Command (2-wire sequence). . 343
F1-02. . . . . . . . . . . . . . . . . . . . . . . . . . . 337, 440 Forward Torque Limit . . . . . . . . . . . . . . 363, 434
F1-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 337, 440 Forward/Reverse Run Command Input Error 208
F1-04. . . . . . . . . . . . . . . . . . . . . . . . . . . 337, 440 Fref/Fout Agree 1 . . . . . . . . . . . . . . . . . . . . . 345
F1-08. . . . . . . . . . . . . . . . . . .200, 213, 337, 440 Fref/Fout Agree 2 . . . . . . . . . . . . . . . . . . . . . 346
F1-08 and F1-09 . . . . . . . . . . . . . . . . . . . . . . . 200 Fref/Fset Agree 1 . . . . . . . . . . . . . . . . . . . . . . 345
F1-09. . . . . . . . . . . . . . . . . . . . . . . 213, 337, 440 Fref/Fset Agree 2 . . . . . . . . . . . . . . . . . . . . . . 346
F1-10. . . . . . . . . . . . . . . . . . .191, 208, 337, 440 Frequency (FOUT) Detection 1. . . . . . . . . . . 345
F1-10 and F1-11 . . . . . . . . . . . . . . . . . . . . . . . 191 Frequency (FOUT) Detection 2. . . . . . . . . . . 345
F1-11 . . . . . . . . . . . . . . . . . . .191, 208, 337, 440 Frequency Bias (A1) . . . . . . . . . . . . . . . . . . . 348
F1-14. . . . . . . . . . . . . . . . . . .202, 214, 338, 440 Frequency Detection 3. . . . . . . . . . . . . . . . . . 346
F6 and F7 Serial Communications Option Card Frequency Detection 4. . . . . . . . . . . . . . . . . . 346
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338 Frequency Gain . . . . . . . . . . . . . . . . . . . . . . . 349
F6-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 192, 209 Frequency Reduction Rate during OH Pre-Alarm
FA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 365, 435
Fast-stop (N.C.) . . . . . . . . . . . . . . . . . . . . . . . 342 Frequency Reference . . . . . . . . . . .150, 376, 439
Fast-Stop (N.O.) . . . . . . . . . . . . . . . . . . . . . . . 342 Frequency Reference (Current) Terminal A2 Input
Fast-stop Time . . . . . . . . . . . . . . . . . . . 321, 436 Bias . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348, 441
Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346 Frequency Reference 1 . . . . . . . . .168, 325, 437
Fault Causes and Solutions. . . . . . . . . . . . . . . 187 Frequency Reference 10 . . . . . . . . . . . . 325, 437
Fault Detection . . . . . . . . . . . . . . . . . . . . . . . . 187 Frequency Reference 11 . . . . . . . . . . . . 326, 437
Fault Displays . . . . . . . . . . . . . . . . . . . . . . . . . 187 Frequency Reference 12 . . . . . . . . . . . . . . . . 437
Fault History . . . . . . . . . . . . . . . . . . . . . 226, 227 Frequency Reference 13 . . . . . . . . . . . . 326, 437
Fault Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . 342 Frequency Reference 14 . . . . . . . . . . . . 326, 437
Fault Reset Example . . . . . . . . . . . . . . . . . . . . 227 Frequency Reference 15 . . . . . . . . . . . . 326, 437
Fault Reset Interval Time . . . . . . . . . . . 359, 434 Frequency Reference 16 . . . . . . . . . . . . 326, 437
Fault Reset Operation Selection . . . . . . 359, 434 Frequency Reference 2168, 236, 314, 325, 433,
Fault Reset when Run Command Entered . . . 215 437
Fault Trace Example . . . . . . . . . . . . . . . . . . . . 227 Frequency Reference 3 . . . . . . . . .168, 325, 437
Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . 181, 182 Frequency Reference 4 . . . . . . . . .168, 325, 437
FB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140 Frequency Reference 5 . . . . . . . . . . . . . 325, 437
FbH . . . . . . . . . . . . . . . . . . . .182, 184, 192, 210 Frequency Reference 6 . . . . . . . . . . . . . 325, 437
FbL . . . . . . . . . . . . . . . . . . . .182, 184, 193, 210 Frequency Reference 7 . . . . . . . . . . . . . 325, 437
Feedback Detection Control Time Constant 2 232 Frequency Reference 8 . . . . . . . . . . . . . 325, 437
FJOG/RJOG . . . . . . . . . . . . . . . . . . . . . . . . . . 166 Frequency Reference 9 . . . . . . . . . . . . . 325, 437
FLASH memory error. . . . . . . . . . . . . . . . . . . 190 Frequency Reference Accel/Decel (Up/Down 2)
450 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
327, 438 Ground Fault Interrupter Activates When Drive is
Frequency Reference at Previous Fault 151, 380, Running . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
439 Ground Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 67
Frequency Reference at Reference Loss 358, 434
Frequency Reference Bias (Up/Down 2)152, 328,
H
386, 438, 442 H1 Multi-Function Digital Input . . . . . . . . . . 341
Frequency Reference Bias Operation Mode H1 Multi-Function Digital Input Selections . 341
Selection (Up/Down 2). . . . . . . . . . . . . .328, 438 H1-01. . . . . . . . . . . . . . . . . . 104, 166, 341, 441
Frequency Reference Bias Step (Up/Down 2) 327 H1-01 through H1-07 . . . . . . . . . . . . . . . . . . 230
Frequency Reference Bias Step(Up/Down 2) 438 H1-01 through H1-10 . . . . . . . . . . . . . . . . . . 228
Frequency Reference from MEMOBUS/Modbus H1-01 through to H1-07 . . . . . . . . . . . . . . . . 217
Communications. . . . . . . . . . . . . . . . . . .151, 442 H1-02. . . . . . . . . . . . . . . . . . . . . . . . . . . 341, 441
Frequency Reference Hold Function Selection . H1-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 341, 441
327, 438 H1-04. . . . . . . . . . . . . . . . . . . . . . . . . . . 341, 441
Frequency Reference Loss Detection Selection . H1-05. . . . . . . . . . . . . . . . . . . 57, 168, 341, 441
358, 434 H1-06. . . . . . . . . . . . . . . . . . . . . . .168, 341, 441
Frequency Reference Lower Limit (Up/Down 2) H1-07. . . . . . . . . . . . . . 104, 166, 167, 341, 441
328, 438 H2 Multi-Function Digital Output Settings. . 345
Frequency Reference Selection . . . . . . .313, 433 H2 Multi-Function Digital Outputs. . . . . . . . 344
Frequency Reference Selection 1 . . . . . . . . . . 229 H2-0. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Frequency Reference Selection Results 151, 384, H2-01. . . . . . . . . . . . . . 144, 147, 236, 345, 441
442 H2-01 to H2-03 . . . . . . . . . . . . . . . . . . . . . . . 206
Frequency Reference Setting / Decimal Display H2-02. . . . . . . . . . . . . . . . . . . . . . .144, 345, 441
370, 436 H2-03. . . . . . . . . . . . . . . . . . . . . . .147, 345, 441
Frequency Reference Setting and User-Set Display H2-06. . . . . . . . . . . . . . . . . . . . . . . . . . . 345, 441
370, 436 H3 Analog Inputs . . . . . . . . . . . . . . . . . . . . . 348
Frequency Reference Setting Method Selection . H3 Multi-Function Analog Input Settings. . . 348
371, 437 H3-01. . . . . . . . . . . . . . . . . . . . . . . . . . . 348, 441
Frequency Reference Upper Limit . . . . .326, 437 H3-02. . . . . . 79, 197, 233, 235, 238, 348, 441
Frequency Reference Upper Limit (Up/Down 2) H3-02 and H3-10. . . . . . . . . . . . . . . . . . . . . . 219
328, 438 H3-02 or H13-10 . . . . . . . . . . . . . . . . . . . . . . 212
Frequency Reference Wiring . . . . . . . . . . . . . . 76 H3-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 233, 234
FWD Torque Limit . . . . . . . . . . . . . . . . . . . . . 349 H3-04. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
FWD/REV Command (2-wire sequence 2) . . 343 H3-09. . . . . . . . . . . . . . . . 79, 80, 229, 348, 441
FWD/REV Torque Limit . . . . . . . . . . . . . . . . 349 H3-09 Details . . . . . . . . . . . . . . . . . . . . . . . . . 80
H3-10. . . . . . . . . . . . . . . 79, 197, 233, 235, 238
G H3-11 . . . . . . . . . . . . . . . . . . . . . . .233, 234, 238
General Safety Information . . . . . . . . . . . . . . . 14 H3-13. . . . . . . . . . . . . . . . . . . . . . . . . . . 180, 237
General-purpose motor. . . . . . . . . . . . . . . . . . 148 H4 Multi-Function Analog Outputs . . . . . . . 349
GF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .182, 193 H4-01. . . . . . . . . . . . . . . . . . . . . . .145, 349, 442
Ground Fault. . . . . . . . . . . . . . . . . . . . . .182, 193 H4-02. . . . . . . . . . . . . . . . . . 145, 146, 349, 442
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 451
H4-03 . . . . . . . . . . . . . . . . . .145, 146, 349, 442 High-Slip Braking Dwell Time at Stop . 367, 436
H5 MEMOBUS/Modbus Communications . . 350 High-slip Braking OL . . . . . . . . . . . . . . . . . . 199
H5-01 . . . . . . . . . . . . . . . . . . . . . . 350, 410, 442 High-Slip Braking Overload Time . . . . 367, 436
H5-01 to H5-07. . . . . . . . . . . . . . . . . . . . . . . . 409 High-slip Braking Overload Time . . . . . . . . . 200
H5-02 . . . . . . . . . . . . . . . . . . . . . . 350, 410, 442 High-Slip Suppression Current Level . . 368, 436
H5-03 . . . . . . . . . . . . . . . . . . . . . . 350, 410, 442 Hunting Prevention Gain . . . . . . . . . . . . . . . . 177
H5-04 . . . . . . . . . . . . . . . . . . . . . . 350, 410, 442 Hunting Prevention Gain Setting. .237, 366, 435
H5-05 . . . . . . . . . . . . . . . . . . . . . . 350, 411, 442 Hunting Prevention Gain while in Reverse . .366,
H5-06 . . . . . . . . . . . . . . . . . . . . . . 350, 411, 442 435
H5-07 . . . . . . . . . . . . . . . . . . . . . . 350, 411, 442 Hunting Prevention Selection . . . . . . . . 366, 435
H5-09 . . . . . . . . . . . . . . . . . . . . . . 208, 350, 442 Hunting Prevention Time Constant . . . . 366, 435
H5-10 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442
H5-11 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442
I
H5-12 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . 77
H6 Pulse Train Input/Output. . . . . . . . . . . . . . 351 IGBT Maintenance . . . . . . . . . . . .151, 383, 441
H6-01 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442 IGBT Maintenance Setting . . . . . . . . . . 372, 437
H6-02 . . . . . . . . . . . . . . . . . .200, 213, 351, 442 Initial Operation. . . . . . . . . . . . . . . . . . . . . . . 106
H6-02 through H6-05 . . . . . . . . . . . . . . 200, 213 Initialize Parameters . . . . . . 112, 122, 311, 433
H6-03 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442 Input Fuses. . . . . . . . . . . . . . . . . . . . . . . 418, 426
H6-04 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442 Input Phase Loss . . . . . . . . . . . . . . . . . . 183, 201
H6-06 . . . . . . . . . . . . . . . . . . . . . . . . . . 351, 442 Input Phase Loss Protection Selection. . 364, 435
H6-07 . . . . . . . . . . . . . . . . . . . . . . . . . . 352, 442 Input Pulse Monitor . . . . . . . . . . . .151, 380, 439
Hardwire Baseblock . . . . . . . . . . . . . . . . . . . . . 70 Input Terminal Status. . . . . . . . . . .151, 378, 439
Hbb . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184, 210 Input Terminal Status at Previous Fault 151, 381,
HbbF . . . . . . . . . . . . . . . . . . . . . . . . . . . 184, 211 440
HCA . . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 211 Input Terminals . . . . . . . . . . . . . . . . . . . . . . . 104
Heatsink Cooling Fan Operation Delay Time364, Input Voltage Setting . . . . . . . . . . .138, 330, 438
435 Inrush Prevention Circuit Fault . . . . . . . . . . . 205
Heatsink Cooling Fan Operation Selection . 364, Inrush Prevention Relay Maintenance Setting372,
435 437
Heatsink Overheat . . . . . . . .183, 185, 196, 211 Inspection. . . . . . . . . . . . . . . 247, 248, 249, 250
Heavy Duty Ratings . . . . . . . . . . . . . . . . . . . . 292 Installation Environment . . . . . . . . . . . . . . . . . 41
Heavy Load Current Level (for PM) . . . . . . . 436 Installation Orientation . . . . . . . . . . . . . . . . . . 42
High Performance Control Selection . . . . . . . 436 Installation Spacing . . . . . . . . . . . . . . . . . . . . . 42
High Slip Braking . . . . . . . . . . . . . . . . . . . . . . 344 Installing Multiple Drives . . . . . . . . . . . . . . . . 43
High Slip Braking OL. . . . . . . . . . . . . . . . . . . 183 Integral Limit Setting. . . . . . . . . . . . . . . 316, 434
High Starting Torque . . . . . . . . . . . . . . . . . . . 142 Integral Time Setting (I) . . . . . . . . . . . . 316, 434
High-slip Braking . . . . . . . . . . . . . . . . . . . . . . 200 Internal Dynamic Braking Resistor Protection 83
High-Slip Braking Current Limit . . . . . 367, 436 Internal Dynamic Braking Resistor Protection
High-Slip Braking Deceleration Frequency Width Selection (ERF type) . . . . . . . . . . . . . . . 363, 435
367, 436 Inverter Duty motor . . . . . . . . . . . . . . . . . . . . 148
452 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
J L3-01 through L3-06 . . . . . . . . . . . . . . . . . . . 180
Jog Frequency Reference . . . . . . . 166, 326, 437 L3-02 . . . . . . . . . . . . . . . . . . 233, 239, 355, 433
L3-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 355, 433
Jog Function . . . . . . . . . . . . . . . . . . . . . . . . . . 166
L3-04 . . . . . . . . . . .83, 198, 200, 235, 356, 433
Jog Operation . . . . . . . . . . . . . . . . . . . . . . . . . 166
Jog Reference Selection . . . . . . . . . . . . . . . . . 341 L3-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 356, 433
L3-06 . . . . . . . . . . . . . . . . . . 180, 234, 356, 433
Jump Frequency . . . . . . . . . . . . . . . . . . . . . . . 180
L3-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Jump Frequency 1. . . . . . . . . . . . . . . . . .327, 437
Jump Frequency 2. . . . . . . . . . . . . . . . . .327, 438 L3-11 . . . . . . . . . . . . . . . . . . 180, 201, 357, 433
L3-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . 357, 433
Jump Frequency 3. . . . . . . . . . . . . . . . . .327, 438
L3-20 . . . . . . . . . . . . . . . . . . . . . . . . . . . 357, 433
Jump Frequency Width. . . . . . . . . . . . . .327, 438
L3-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . 357, 434
K L3-22 . . . . . . . . . . . . . . . . . . . . . . . . . . . 357, 434
KEB Deceleration Time . . . . . . . . . . . . .354, 433 L3-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . 357, 434
KEB Operation . . . . . . . . . . . . . . . . . . . . . . . . 347 L3-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . 358, 434
KEB Ride-thru (N.C.). . . . . . . . . . . . . . . . . . . 344 L3-25 . . . . . . . . . . . . . . . . . . . . . . .201, 358, 434
KEB Ride-thru (N.O.) . . . . . . . . . . . . . . . . . . 344 L4 Frequency Detection . . . . . . . . . . . . . . . . 358
KEB Ride-thru 2 (N.C.) . . . . . . . . . . . . . . . . . 344 L4-01 . . . . . . . . . . . . . . . . . . . . . . .236, 358, 434
KEB Ride-thru 2 (N.O.) . . . . . . . . . . . . . . . . . 344 L4-02 . . . . . . . . . . . . . . . . . . . . . . .236, 358, 434
kWH Monitor Initial Value Selection. . .372, 437 L4-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 358, 434
kWH, Lower 4 Digits . . . . . . . . . . 151, 384, 441 L4-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 358, 434
kWH, Upper 5 Digits . . . . . . . . . . 151, 384, 441 L4-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 358, 434
L4-06 . . . . . . . . . . . . . . . . . . . . . . . . . . . 358, 434
L L5 Fault Reset . . . . . . . . . . . . . . . . . . . . . . . . 359
L Protection Function . . . . . . . . . . . . . . .352, 373 L5-01 . . . . . . . . . . . . . . . . . . . . . . .214, 359, 434
L1 Motor Protection Functions . . . . . . . . . . . 352 L5-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 359, 434
L1-01 147, 148, 149, 198, 352, 428, 429, 442 L5-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 359, 434
L1-02 . . . . . . . . . . . . . . . . . . 147, 353, 429, 442 L5-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 359, 434
L1-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 L6 Overtorque Detection. . . . . . . . . . . . . . . . 360
L1-04 . . . . . . . . . . . . . . . . . . . . . . . . . . .353, 433 L6-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 360, 434
L1-05 . . . . . . . . . . . . . . . . . . . . . . . . . . .353, 433 L6-02 . . . . . . . . . . . . . . 199, 203, 213, 360, 434
L2 Momentary Power Loss . . . . . . . . . . . . . . 353 L6-02 and L6-03 . . . . . . . . . . . . . . . . . . 203, 215
L2-01 . . . . . . . . . . . . . . . . . . . . . . . . . . .353, 433 L6-03 . . . . . . . . . . . . . . 199, 203, 213, 360, 434
L2-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 L6-04 . . . . . . . . . . . . . . . . . . . . . . . . . . . 361, 434
L2-03 . . . . . . . . . . . . . . . . . . . . . . 130, 354, 433 L6-05 . . . . . . . . . . . . . . 199, 204, 213, 361, 434
L2-04 . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 L6-05 and L6-06 . . . . . . . . . . . . . .204, 213, 215
L2-05 . . . . . . . . . . . . . . . . . . . . . . 204, 354, 433 L6-06 . . . . . . . . . . . . . . 199, 204, 213, 361, 434
L2-06 . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 L6-08 . . . . . . . . . . . . . . . . . . . . . . . . . . . 362, 434
L2-07 . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 L6-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . 362, 434
L2-08 . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 L6-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 362, 434
L3 Stall Prevention Function . . . . . . . . . . . . . 355 L6-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . 362, 434
L3-01 . . . . . . . . . . . . . . . . . . . . . . . . . . .355, 433 L7 Torque Limit . . . . . . . . . . . . . . . . . . . . . . 363
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 453
L7-01. . . . . . . . . . . . . . . . . . . . . . . 224, 363, 434 LOCAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
L7-01 through L3-04 . . . . . . . . . . . . . . . . . . . 180 Local/Remote. . . . . . . . . . . . . . . . . . . . . . . . . 346
L7-01 through L7-04 . . . . . .188, 230, 233, 235 LOCAL/REMOTE Key Function Selection .371,
L7-02. . . . . . . . . . . . . . . . . . . . . . . 224, 363, 434 436
L7-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 363, 434 Local/Remote Run Selection . . . . . . . . . 313, 433
L7-04. . . . . . . . . . . . . . . . . . . . . . . . . . . 363, 434 Local/Remote Selection. . . . . . . . . . . . . . . . . 341
L7-06. . . . . . . . . . . . . . . . . . . . . . . . . . . 363, 435 Loss of Reference . . . . . . . . . . . . . . . . . . . . . 346
L7-07. . . . . . . . . . . . . . . . . . . . . . . . . . . 363, 435 Low Voltage Directive. . . . . . . . . . . . . . . . . . 417
L8 Low Voltage Wiring. . . . . . . . . . . . . . . . . . . . 427
Hardware Protection . . . . . . . . . . . . . . . . 363 M
L8-01. . . . . . . . . . . . . . . . . . . .83, 202, 363, 435
Magnetic Flux Compensation Capacity 314, 315,
L8-02. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
434
L8-03. . . . . . . . . . . . . . . . . . . . . . . . . . . 364, 435
Main Circuit Connection Diagram . . . . . . 58, 68
L8-04. . . . . . . . . . . . . . . . . . . . . . . . . . . 364, 435
Main Circuit Terminal Functions. . . . . . . . . . . 63
L8-05. . . . . . . . . . . . . . . . . . . . . . . . . . . 201, 202
Main Circuit Terminal Power Supply . . . . . . . 66
L8-07. . . . . . . . . . . . . . . . . . . . . . . 193, 364, 435
Main Circuit Terminal Wiring . . . . . . . . . 68, 425
L8-09. . . . . . . . . . . . . . . . . . . . . . . 193, 364, 435
Main Circuit Terminals Connection . . . . . . . . 58
L8-10. . . . . . . . . . . . . . . . . . . . . . . . . . . 364, 435
Main Frequency Reference . . . . . . . . . . . . . . . 79
L8-11. . . . . . . . . . . . . . . . . . . . . . . . . . . 364, 435
Main Frequency Reference Input . . . . . . . . . . 71
L8-12. . . . . . . . . . . . . . . . . . . . . . . 305, 364, 435
Main Power Circuit Voltage Adjustment Gain357,
L8-15. . . . . . . . . . . . . . . . . . . . . . . . . . . 365, 435
433
L8-18. . . . . . . . . . . . . . . . . . . . . . . . . . . 365, 435
Main/Aux. . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
L8-29. . . . . . . . . . . . . . . . . . . . . . . 306, 365, 435
Maintenance. . . . . . . . . . . . . . . . . . . . . . 252, 253
L8-38. . . . . . . . . . . . . . . . . . . . . . . 239, 365, 435
Master Speed Reference Lower Limit. . 326, 437
L8-41. . . . . . . . . . . . . . . . . . . . . . . . . . . 365, 435
Max Output Frequency (FMAX). . . . . . 331, 438
LCD Contrast . . . . . . . . . . . . . . . . . . . . . . . . . 436
Max Voltage (VMAX). . . . . . . . . . . . . . 331, 438
LED Check . . . . . . . . . . . . . . . . . . 151, 384, 441
Mechanical Weakening (N.O.) . . . . . . . . . . . 347
LED Operator . . . . . . . . . . . . . . .91, 92, 93, 127
Mechanical Weakening Detection Operation 362,
LF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182, 193
434
LF2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 194
Mechanical Weakening Detection Speed Level .
Line-to-Line Motor Resistance Online Tuning . .
362, 434
368, 436
Mechanical Weakening Detection Start Time362,
Line-to-Line Resistance Auto-Tuning . . . . . . 230
434
Line-to-Line Resistance Error . . . . . . . 186, 223
Mechanical Weakening Detection Time 362, 434
LO/RE. . . . . . . . . . . . . . . . . . . . . . . 94, 104, 162
MEMOBUS/Modbus Communication Error.182,
Load Current. . . . . . . . . . . . . . . . . . . . . 368, 436
184, 187, 207
Load Falls When Brake is Applied (Hoist-Type
MEMOBUS/Modbus Communication Set-up 406
Applications). . . . . . . . . . . . . . . . . . . . . . . . . . 236
MEMOBUS/Modbus Communications Reference
Load Inertia. . . . . . . . . . . . . . . . . . . . . . 369, 436
151, 385, 442
Load Inertia for PM . . . . . . . . . . . . . . . . . . . . 203
MEMOBUS/Modbus Communications Test Mode
Load Inertia Ratio . . . . . . . . . . . . . 201, 358, 434
454 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Complete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214 Motor 2 Mid Output Frequency 2 . . . . . 333, 439
MEMOBUS/Modbus Error Code. . . . . . . . . . 151 Motor 2 Mid Output Frequency Voltage (VC)333,
Memobus/Modbus Error Code . . . . . . . .380, 439 439
MEMOBUS/Modbus Switch Settings . . .81, 407 Motor 2 Mid Output Frequency Voltage 2 . . 333,
MEMOBUS/Modbus Termination . . . . . . . . . . 81 439
MEMOBUS/Modbus Test Mode Complete . . 185 Motor 2 Minimum Output Frequency (FB) . 333,
Mid Output Frequency (FB). . . . . . . . . .331, 438 439
Mid Output Frequency 2 . . . . . . . . . . . .331, 438 Motor 2 Minimum Output Frequency (FMIN) . .
Mid Output Frequency Voltage (VC) . . .331, 438 333, 439
Mid Output Frequency Voltage 2 . . . . . .331, 438 Motor 2 Minimum Output Frequency Voltage
Mid Output Voltage A . . . . . . . . . . . . . .177, 179 (VMIN) . . . . . . . . . . . . . . . . . . . . . . . . . 333, 439
Minimum Frequency Gain at KEB Start . . . . 354 Motor 2 Motor Iron-Core Saturation Coefficient 1
Minimum Output Frequency . . . . . . . . . . . . . 240 334, 439
Minimum Output Frequency (FMIN) . .331, 438 Motor 2 Motor Iron-Core Saturation Coefficient 2
Minimum Output Frequency Voltage (VMIN) . 334, 439
331, 438 Motor 2 Motor Poles . . . . . . . . . . . . . . . 334, 439
Minimum Output Voltage. . . . . . . . . . . .177, 179 Motor 2 Rated Capacity . . . . . . . . . . . . 334, 440
Minor Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 184 Motor 2 Rated Current . . . . . . . . .147, 333, 439
Minor Fault. . . . . . . . . . . . . . . . . . . . . . . . . . . 222 Motor 2 Rated No-Load Current . . . . . . 333, 439
Minor Faults . . . . . . . . . . . . . . . . . . . . . .181, 184 Motor 2 Rated Slip . . . . . . . . . . . . . . . . 333, 439
Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97 Motor 2 Selection . . . . . . . . . . . . . . . . . 342, 347
Momentary Power Loss Minimum Baseblock Motor 2 Torque Compensation Gain. . . 334, 440
Time . . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 Motor Acceleration Time for Inertia Calculations
Momentary Power Loss Operation Selection 353, 358, 434
433 Motor Armature Resistance (for PM motor). 335,
Momentary Power Loss Ride-thru Time353, 354, 440
433 Motor Base Frequency . . . . 159, 160, 376, 439
Momentary Power Loss Voltage Recovery Ramp Motor Base Speed . . . . . . . . . . . . .160, 376, 439
Time . . . . . . . . . . . . . . . . . . . . . . . . . . . .354, 433 Motor d Axis Inductance (for PM motor)335, 440
Monitor Output. . . . . . . . . . . . . . . . . . . . . . . . . 71 Motor Data Error . . . . . . . . . . . . . . . . . . 186, 222
Most Recent Fault. . . . . . . . . . . . . 152, 381, 440 Motor Data for Auto-Tuning . . . . . . . . . . . . . 160
Motor 2 Base Frequency (FA) . . . . . . . .333, 439 Motor d-Axis Current at Previous Fault152, 381,
Motor 2 Base Voltage (VBASE) . . . . . .333, 439 440
Motor 2 Control Method Selection. . . . . . . . . 439 Motor Direction at Power Up when Using Operator
Motor 2 Iron Loss. . . . . . . . . . . . . . . . . .334, 440 371, 437
Motor 2 Iron-Core Saturation Coefficient 3 . 334, Motor Does Not Operate When an External Run
440 Command is Input . . . . . . . . . . . . . . . . . . . . . 240
Motor 2 Leakage Inductance . . . . . . . . .334, 439 Motor Does Not Operate When the RUN Button on
Motor 2 Line-to-Line Resistance . . . . . .334, 439 the Digital Operator is Pressed . . . . . . . . . . . 239
Motor 2 Max Voltage (VMAX) . . . . . . .333, 439 Motor Does Not Rotate . . . . . . . . . . . . . . . . . 228
Motor 2 Mechanical Loss. . . . . . . . . . . .334, 440 Motor Excitation Current (ld) . . . .151, 386, 442
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 455
Motor Hunting and Oscillation Control Parameters 442
180 Motor Parameters . . . . . . . . . . . . . . . . . . . . . 142
Motor Hunting Occurs at Low Speeds . . . . . . 232 Motor Poles . . . . . . . . . . . . . . . . . . . . . . . . . . 159
Motor Hunting Occurs When Operating With a Motor Poles (for PM motor) . . . . . . . . . 335, 440
Light Load . . . . . . . . . . . . . . . . . . . . . . . . . . . 235 Motor Produces Insufficient Torque . . . . . . . 238
Motor Induction Voltage Constant 1 (for PM Motor Protection Function. . . . . . . . . . . . . . . 198
motor) . . . . . . . . . . . . . . . . . . . . . . . . . . 336, 440 Motor protection operation time . . . . . . . . . . 149
Motor Induction Voltage Parameter 2 (for PM Motor q Axis Inductance (for PM motor) . . . 440
motor) . . . . . . . . . . . . . . . . . . . . . . . . . . 336, 440 Motor q-Axis Current at Previous Fault151, 381,
Motor Iron Core Saturation Coefficient Error 186 440
Motor Iron Loss . . . . . . . . . . . . . . 161, 376, 439 Motor r/min Reset . . . . . . . . . . . . . . . . . . . . . 437
Motor Iron Loss for Torque Compensation . 143, Motor Rated Capacity (for PM motor) . 335, 440
332, 439 Motor Rated Current . 143, 147, 159, 160, 331,
Motor Iron-Core Saturation Coefficient . . . . . 224 376, 428, 438
Motor Iron-Core Saturation Coefficient 1 . . 143, Motor Rated Current (for PM motor) . . 335, 440
332, 439 Motor Rated Output. . . . . . . . . . . .143, 332, 439
Motor Iron-Core Saturation Coefficient 2 . . 143, Motor Rated Power . . . . . . . . . . . .160, 375, 438
332, 439 Motor Rated Slip . . . . . . . . . . . . . .143, 331, 438
Motor Iron-Core Saturation Coefficient 3332, 439 Motor Rated Voltage . . . . . . 159, 160, 375, 438
Motor Iron-Core Saturation Coefficients . . . . 143 Motor Rotates After the Drive Output is Shut Off
Motor is Too Hot . . . . . . . . . . . . . . . . . . . . . . 231 238
Motor Leakage Inductance . . . . . . 143, 332, 439 Motor Rotates Faster Than the Frequency
Motor Line-to-Line Resistance. . . 143, 332, 439 Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Motor Mechanical Loss . . . . . . . . 143, 332, 439 Motor Rotates in One Direction Only . . 231, 240
Motor No-Load Current . . . . . . . . 143, 331, 438 Motor Secondary Current (Iq) . . . .151, 386, 442
Motor Operates at a Higher Speed than the Speed Motor Selection 1/2 . . . . . . . . . . . .160, 375, 438
Command . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241 Motor Speed . . . . . . . . . . . . . . . . .150, 377, 439
Motor Overheat. . . . . . . . . . . . . . . . . . . 185, 212 Motor Speed at Previous Fault . . .151, 381, 440
Motor Overheat 1 (PTC input) . . . . . . . . . . . . 183 Motor Speed Error . . . . . . . . . . . . . . . . . . . . . 186
Motor Overheat 2 (PTC input) . . . . . . . . . . . . 183 Motor Speed Fault . . . . . . . . . . . . . . . . . . . . . 224
Motor Overheat Alarm (PTC Input) . . . . . . . . 197 Motor Stalls During Acceleration or With Large
Motor Overheat Alarm Operation Selection (PTC Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
input). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 353 Motor Stops During Acceleration or When a Load
Motor Overheat Fault (PTC Input) . . . . . . . . . 197 is Connected . . . . . . . . . . . . . . . . . . . . . . . . . 240
Motor Overheat Fault Operation Selection (PTC Motor Switch during Run . . . . . . . . . . . . . . . 214
input). . . . . . . . . . . . . . . . . . . . . . . . . . . 353, 433 Motor Temperature (PTC input) . . . . . . . . . . 349
Motor Overload . . . . . . . . . . . . . . . . . . 183, 197 Motor Temperature Input Filter Time (PTC input)
Motor Overload Estimate (OL1) . 151, 384, 441 353, 433
Motor Overload Protection Selection . . 147, 352, Motor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 66
428, 442 Multi-Function Analog 1 (Terminal AM Monitor
Motor Overload Protection Time 147, 353, 429, Selection) . . . . . . . . . . . . . . . . . . . .145, 349, 442
456 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Multi-Function Analog 1 (Terminal AM Output n1-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 366, 435
Bias) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 442 n2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
Multi-Function Analog 1 (Terminal AM Output n2 Speed Feedback Detection Control Function .
Gain) . . . . . . . . . . . . . . . . . . . . . . . 145, 349, 442 367
Multi-Function Analog Input Selection Error186, n2-01 . . . . . . . . . . . . . . 178, 235, 237, 367, 435
219 n2-02 . . . . . 178, 201, 220, 232, 235, 367, 435
Multi-Function Analog Outputs . . . . . . . . . . . 144 n2-03 . . . . . . . . . .178, 201, 220, 232, 367, 435
Multi-Function Contact Input. . . . . . . . . . . . . 168 n3 High Slip Braking. . . . . . . . . . . . . . . . . . . 367
Multi-Function Contact Input Terminals . . . . 166 n3-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 367, 436
Multi-Function Contact Output . . . . . . . . . . . 144 n3-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 367, 436
Multi-Function Contact Outputs. . . . . . . . . . . 147 n3-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 367, 436
Multi-Function Digital Input Terminal S1 Function n3-04 . . . . . . . . . . . . . . . . . . 199, 200, 367, 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n3-13 . . . . . . . . . . . . . . . . . . 195, 198, 368, 436
Multi-Function Digital Input Terminal S2 Function n3-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . 368, 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n3-23 . . . . . . . . . . . . . . . . . . . . . . .198, 368, 436
Multi-Function Digital Input Terminal S3 Function n6 Online Tuning of Resistance between Motor
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368
Multi-Function Digital Input Terminal S4 Function n6-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 368, 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n8 Permanent Magnet (PM) Motor Control . 368
Multi-Function Digital Input Terminal S5 Function n8-45 . . . . . . . . . . . . . . . . . . 201, 239, 368, 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n8-47 . . . . . . . . . . . . . . 201, 239, 368, 369, 436
Multi-Function Digital Input Terminal S6 Function n8-48 . . . . . . . . . . . . . . . . . . . . . . . . . . . 368, 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n8-49 . . . . . . . . . . . . . . . . . . . . . . . . . . . 368, 436
Multi-Function Digital Input Terminal S7 Function n8-50 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Selection . . . . . . . . . . . . . . . . . . . . . . . . .341, 441 n8-51 . . . . . . . . . . . . . . . . . . . . . . .203, 369, 436
Multi-Function Digital Inputs. . . . . . . . . . . . . . 70 n8-55 . . . . . . . . . . . . . . . . . . . . . . .203, 369, 436
Multi-Function Digital Output . . . . . . . . . . . . . 71 n8-56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436
Multi-Function Input Selection Error. . . . . . . 217 NEMA Type 1 . . . . . . . . . . . . . . . . . . .47, 48, 49
Multi-Function Input Setting Error . . . . . . . . 185 Noise From the Drive or Output Lines When the
Multi-Function Photocoupler Output . . . . . . . . 71 Drive is Powered On . . . . . . . . . . . . . . . . . . . 236
Multiple Drive Wiring . . . . . . . . . . . . . . . . . . . 68 No-Load Current Error . . . . . . . . . . . . . 186, 223
Multi-Step Speed Operation (4-Step Speed) . 168 No-Load Operation . . . . . . . . . . . . . . . . . . . . 161
Multi-Step Speed Reference. . . . . . . . . . . . . . 341 Normal Duty Ratings. . . . . . . . . . . . . . . . . . . 292
Multi-Step Speed Reference 4 . . . . . . . . . . . . 343 Number of Auto Restart Attempts. . . . . 359, 434
Number of Motor Poles143, 160, 332, 376, 438,
N 439
n Advanced Performance Set Up . . . . . . . . . . 366 Number of Run Commands. . . . . .151, 383, 441
n1 Hunting Prevention . . . . . . . . . . . . . . . . . . 366 Number of Speed Search Restarts . . . . . 316, 434
n1-01. . . . . . . . . . . . . . . . . . . . . . . 235, 366, 435
n1-02. . . . . . . . . . . . . . 177, 201, 237, 366, 435 O
n1-03. . . . . . . . . . . . . . . . . . . . . . . . . . . .366, 435 o Operator Related Parameters . . . . . . . . . . . 370
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 457
o1 Display Settings . . . . . . . . . . . . . . . . . . . . . 370 oH1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 196
o1-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 370, 436 oH2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 212
o1-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . 370, 436 oH3 . . . . . . . . . . . . . . . . . . . 183, 185, 197, 212
o1-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . 370, 436 oH4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 197
o2 Multi-Function Selections . . . . . . . . . . . . . 371 oL1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 197
o2-01 . . . . . . . . . . . . . . . . . . . . . . . 229, 371, 436 oL2. . . . . . . . . . . . . . . . . . . . . . . . .183, 198, 239
o2-02 . . . . . . . . . . . . . . . . . . . . . . . 230, 371, 436 OL2 Characteristics Selection at Low Speeds365,
o2-03 . . . . . . . . . . . . . . 113, 122, 164, 371, 436 435
o2-04 . . . . . . . . . . . . . . 177, 196, 217, 371, 436 oL3. . . . . . . . . . . . . . . . . . . . 183, 185, 199, 213
o2-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 371, 437 oL4. . . . . . . . . . . . . . . . . . . . 183, 185, 199, 213
o2-06 . . . . . . . . . . . . . . . . . . . . . . . 200, 371, 437 oL7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 199
o2-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . 371, 437 OPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
o3-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 oPE Fault . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
o3-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 OPE fault constant . . . . . . . . . . . . . . . . . . . . . 217
o3-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 OPE Fault Parameter . . . . . . . . . . . . . . . 379, 439
o4 Maintenance Period . . . . . . . . . . . . . . . . . . 372 oPE01. . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 217
o4-01 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE02. . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 217
o4-02 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE03. . . . . . . . . . . . . . . . . . . . . . .185, 217, 218
o4-03 . . . . . . . . . . . . . . 196, 197, 212, 372, 437 oPE05. . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 219
o4-05 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE07. . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 219
o4-07 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE08. . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 220
o4-09 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE09. . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 220
o4-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 437 oPE10. . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 220
o4-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 oPE11. . . . . . . . . . . . . . . . . . . . . . . . . . . 186, 221
o4-12 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 Open Loop Vector . . . . . . . . . . . . . . . . . . . . . 224
o4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . 372, 437 Open Loop Vector Control 109, 122, 142, 156,
oC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 194 179, 188, 201, 230, 232, 233, 234, 237, 238
oFA00 . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 195 Open Loop Vector Control Mode Tuning . . . 178
oFA01 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195 Open Loop Vector Control Mode Tuning
oFA03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
oFA04 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196 Open-Chassis IP20 . . . . . . . . . . . . . . . . . . 45, 46
Offset Frequency. . . . . . . . . . . . . . 152, 387, 442 Operating with the Load Connected . . . . . . . 163
Offset Frequency 1 . . . . . . . . . . . . . . . . 329, 438 Operation Errors . . . . . . . . . . . . . . . . . . 181, 185
Offset Frequency 1 Addition . . . . . . . . . . . . . 343 Operation Selection at Deviation (for Simple PG
Offset Frequency 2 . . . . . . . . . . . . . . . . 329, 438 V/f Control) . . . . . . . . . . . . . . . . . . . . . . 337, 440
Offset Frequency 2 Addition . . . . . . . . . . . . . 343 Operation Selection at Overspeed (OS) (for Simple
Offset Frequency 3 . . . . . . . . . . . . . . . . 329, 438 PG V/f) . . . . . . . . . . . . . . . . . . . . . . . . . 337, 440
Offset Frequency 3 Addition . . . . . . . . . . . . . 343 Operation Selection at PG Open Circuit (PGO) .
oH . . . . . . . . . . . . . . . . . . . . .183, 185, 196, 211 337, 440
OH Pre alarm . . . . . . . . . . . . . . . . . . . . . . . . . 347 Operation Selection when Digital Operator is
OH Pre-alarm Time Limit. . . . . . . . . . . . . . . . 347 Disconnected . . . . . . . . . . . . . . . . . . . . . 371, 437
458 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Operator Connection Fault . . . . . . . . . . . . . . . 183 Output voltage reference (Vq). . . .152, 386, 442
Operator Programming Errors . . . . . . . . . . . . 217 ov . . . . . . . . . . . . . . . . . . . . . 183, 185, 200, 213
oPr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 200 OV Occurs When Starting a Fan or Motor Speed
Option Card Communications Error . . . . . . . 184 Loss Occurs . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Option Card External Fault . 182, 184, 191, 209 OV Suppression Function Selection . . . 357, 433
Option Card Fault (Port A). . . . . . . . . . . . . . . 195 Overcurrent . . . . . . . . . . . . . . . . . . . . . . 183, 194
Option Card Fault (port A) . . . . . . . . . . .183, 196 Overexcitation Deceleration Gain .195, 368, 436
Option Card Reference . . . . . . . . . 151, 385, 442 Overexcitation Operation Selection . . . 368, 436
Option Communication Error. . . . 182, 187, 206 Overheat 1 (Heatsink Overheat) . . . . . . . . . . 196
Option Frequency Reference . . . . 151, 384, 442 Overheat Alarm Level . . . . . . . . . . . . . . 363, 435
Option Reference . . . . . . . . . . . . . . . . . . . . . . 346 Overheat Pre-Alarm Operation Selection364, 435
Option/Drive Selection. . . . . . . . . . . . . . . . . . 341 Overload OL1 (OL1 Alarm) . . . . . . . . . . . . . 347
oS . . . . . . . . . . . . . . . . . . . . . 183, 185, 200, 213 Overspeed (for Simple V/f with PG). . 183, 185,
Oscillation or Hunting . . . . . . . . . . . . . . . . . . 237 213
Output Current . . . . . . . . . . . . . . . 150, 377, 439 Overspeed (Simple V/f with PG) . . . . . . . . . 200
Output Current at Previous Fault . 151, 380, 440 Overspeed Detection Delay Time (for Simple PG
Output current imbalance . . . . . . . . . . . . . . . . 194 V/f Control) . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Output Frequency . . . . . . . . . . . . . 150, 376, 439 Overspeed Detection Level (for Simple PG V/f
Output Frequency after Soft Start. . . . . .379, 439 Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 440
Output Frequency after SoftStart . . . . . . . . . . 151 Overtorque 1 . . . . . . . . . . . . . . . . . . . . . 185, 213
Output Frequency at Previous Fault151, 380, 440 Overtorque 2 . . . . . . . . . . . . . . . . . . . . . 185, 213
Output Frequency is not as High as Frequency Overtorque Detection 1 . . . . . . . . . . . . . 183, 199
Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239 Overtorque Detection 2 . . . . . . . . . . . . . 183, 199
Output Ground Fault Detection Selection364, 435 Overtorque/Undertorque Detection Level. . . 349
Output of speed control (ASR) (for Simple V/f PG) Overvoltage . . . . . . . . . . . . . . . . . .183, 185, 200
151, 386, 442 Overvoltage Occurs When Running at a Constant
Output Open Phase . . . . . . . . . . . . . . . . . . . . . 183 Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Output Phase Loss . . . . . . . . . . . . . . . . .182, 193 Overvoltage Suppression. . . . . . . . . . . . . . . . 201
Output Phase Loss Protection. . . . . . . . .364, 435 Overvoltage Suppression and Deceleration Stall
Output Power . . . . . . . . . . . . . . . . 151, 377, 439 (Desired DC Bus Voltage during Motor Stall) 433
Output Power at Previous Fault . . 151, 381, 440
Output Terminal Status. . . . . . . . . 151, 378, 439
P
Output Terminal Status at Previous Fault. . . 151, Parameter Range Setting Error . . . . . . . . . . . 217
381, 440 Parameter Selection Error . . . . . . . . . . . 185, 220
Output Voltage at Previous Fault . 151, 381, 440 Parameter Setting Range Error . . . . . . . . . . . 185
Output Voltage Bias . . . . . . . . . . . . . . . . . . . . 349 Parameter Settings. . . . . . . . . . . . . . . . . . . . . 102
Output Voltage Limit Operation Selection . . 322, PASS . . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 214
436 Password 1. . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Output Voltage Reference. . . . . . . 150, 377, 439 Password 2. . . . . . . . . . . . . . . . . . . . . . . 311, 433
output voltage reference . . . . . . . . . . . . . . . . . 150 Password Settings . . . . . . . . . . . . . . . . . . . . . 165
Output Voltage Reference (Vd) . . 152, 386, 442 Peak Hold Current . . . . . . . . . . . . . . . . . 151, 384
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 459
Peak Hold Output Frequency . . . . 151, 384, 441 PID Output Reverse Selection . . . . . . . . 317, 434
Performance Life . . . . . . . . . . . . . . . . . . . . . . 252 PID Primary Delay Time Constant . . . . 317, 434
Peripheral Devices Affected by Drive Operation . PID Set Point . . . . . . . . . . . . . . . . . . . . . . . . . 349
241 PID Setpoint . . . . . . . . . . . . . . . . .151, 386, 442
Permanent Magnet Motor Control . . . . . . . . . 110 PID Setpoint / User Display . . . . . . . . . 318, 435
PF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 201 PID Setpoint and Display Digits . . . . . . 318, 435
PG Disconnect (for Simple V/f with PG) . . . 183, PID Setpoint Scaling . . . . . . . . . . . . . . . 318, 435
185, 202, 214 PID Setpoint Selection. . . . . . . . . . . . . . 318, 435
PG Open-Circuit Detection Time (for Simple PG PID Setpoint Value . . . . . . . . . . . . . . . . 318, 435
V/f Control) . . . . . . . . . . . . . . . . . . . . . 338, 440 PID Sleep Delay Time . . . . . . . . . . . . . . 318, 435
PGo . . . . . . . . . . . . . . . . . . . .183, 185, 202, 214 PID Sleep Function Start Level . . . . . . . 318, 435
Phase Order Selection. . . . . . . . . . . . . . 314, 433 PID Soft Starter . . . . . . . . . . . . . . . . . . . . . . . 343
PID Accel/Decel Time . . . . . . . . . . . . . 318, 435 PM Open Loop Vector Control . . .110, 122, 134
PID Adjusted Feedback . . . . . . . . . . . . 152, 442 PM Speed Feedback Detection Suppression Gain
PID Control Selection Error . . . . . . . . . . . . . . 185 201
PID Control Selection Fault . . . . . . . . . . . . . . 220 Poor Speed Control Accuracy . . . . . . . . . . . . 234
PID Differential Feedback . . . . . . . . . . 152, 442 Poor Speed Control Accuracy Above Base Speed
PID Disable. . . . . . . . . . . . . . . . . . . . . . . . . . . 342 in Open-loop Vector Motor Control Method . 241
PID Feedback . . . . . . . . . . . .151, 349, 386, 442 Power Detection Filter Time . . . . . . . . . 319, 435
PID Feedback Fault . . . . . . . . . . . . . . . . . . . . 347 Power Specifications 200 V Class Models . .293,
PID Feedback High Detection Level . . 318, 435 294, 296, 297
PID Feedback High Level Detection Time. . 318, Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
435 Preferred Parameter Automatic Selection . . . 165
PID Feedback Loss . . . 182, 184, 193, 210, 347 Preferred Parameters . . . . . . . . . . . . . . . . . . . 165
PID Feedback Loss Detection Level . . 317, 435 Previous Fault . . . . . . . . . . . . . . . .151, 380, 439
PID Feedback Loss Detection Time . . . 317, 435 Program Lockout . . . . . . . . . . . . . . . . . . . . . . 342
PID Feedback Reference Missing Detection Programming Mode . . . . . . . . . . . . . .97, 99, 101
Selection . . . . . . . . . . . . . . . . . . . . . . . . 317, 435 Proportional Gain Setting (P) . . . . . . . . 316, 434
PID Function Setting . . . . . . . . . . . . . . 316, 434 Protective Covers, NEMA Type 1 . . . . . . . . . . 61
PID Input (feedback) . . . . . . . . . . 151, 386, 442 Protective Covers, Open-Chassis . . . . . . . . . . 60
PID Input Limit. . . . . . . . . . . . . . . . . . . 318, 435 Protective Covers, Reattaching . . . . . . . . . . . . 62
PID Input Switch . . . . . . . . . . . . . . . . . . . . . . 343 Protective Covers, Removing . . . . . . . . . . 60, 61
PID Integral Hold . . . . . . . . . . . . . . . . . . . . . . 343 Pull-In Current. . . . . . . . . . . . . . . . . . . . 368, 436
PID Integral Reset. . . . . . . . . . . . . . . . . . . . . . 343 Pull-In Current Compensation Time Constant201,
PID Offset Adjustment . . . . . . . . . . . . . 317, 434 239, 368, 436
PID Output . . . . . . . . . . . . . . . . . . 151, 386, 442 Pull-In Current during Accel/Decel for PM . 203
PID output fault . . . . . . . . . . . . . . . . . . . . . . . 238 Pull-Out Detection . . . . . . . . . . . . . . . . . 183, 203
PID Output Gain Setting. . . . . . . . . . . . 317, 434 Pulse Train Input Bias . . . . . . . . . . . . . . 351, 442
PID Output Level Selection . . . . . . . . . 317, 434 Pulse Train Input Filter Time. . . . . . . . . 351, 442
PID Output Limit . . . . . . . . . . . . . . . . . 317, 434 Pulse Train Input Gain. . . . . . . . . . . . . . 351, 442
PID Output Lower Limit . . . . . . . . . . . 318, 435 Pulse Train Input Scaling. . . 200, 213, 351, 442
460 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Pulse Train Input . . . . . . . . . . . . . . . . . . . . . . 126 Run Command Selection. . . . . . . .229, 313, 433
Pulse Train Monitor Scaling. . . . . . . . . .352, 442 Run Command Selection during Program. . . 313,
PWM Data Error. . . . . . . . . . . . . . . . . . . . . . . 188 433
PWM Data Fault. . . . . . . . . . . . . . . . . . . . . . . 182 Run Command Selection Error . . . . . . . 186, 219
PWM Feedback Data Fault . . . . . . . . . . . . . . 182 Run Command Selection Results .151, 385, 442
PWM Feedback Fault . . . . . . . . . . . . . . . . . . . 191 Run Command Source 2 . . . . . . . . . . . . 314, 433
rUnC . . . . . . . . . . . . . . . . . . . . . . . . . . . 185, 215
Q
q-axis ACR Output . . . . . . . . . . . . 152, 386, 442 S
S1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
R S2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
RAM Fault . . . . . . . . . . . . . . . . . . . . . . .182, 183 Safety Hazard Definitions . . . . . . . . . . . . . . . . 14
RAM fault. . . . . . . . . . . . . . . . . . . . . . . . . . . . 190 Safety Information. . . . . . . . . . . . . . . . . . . . . . 14
Ramp to Stop . . . . . . . . . . . . . . . . . . . . . . . . . 129 S-Curve Characteristic at Accel End. . . 321, 436
Rated Current Setting Alarm . . . . . . . . .186, 225 S-Curve Characteristic at Accel Start . . 321, 436
Rated Output Operation . . . . . . . . . . . . . . . . . 142 S-Curve Characteristic at Decel End. . . 321, 436
Rated Slip Error . . . . . . . . . . . . . . . . . . .186, 223 S-Curve Characteristic at Decel Start . . 321, 436
Reference Sample Hold . . . . . . . . . . . . . . . . . 342 S-Curve Characteristics. . . . . . . . . . . . . 134, 180
Regenerative Torque Limit. . . . . . . . . . . . . . . 349 Search Operation Voltage Limit . . . . . . 319, 435
REMOTE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103 SEr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 203
Replacement Parts . . . . . . . . . . . . 252, 305, 306 Serial Communication Terminals . . . . . . 72, 408
Reset Command Active . . . . . . . . . . . . . . . . . 346 Serial Communication Transmission Error . . 184,
Restart Enabled. . . . . . . . . . . . . . . . . . . . . . . . 347 207
REV Torque Limit . . . . . . . . . . . . . . . . . . . . . 349 Setup Mode . . . . . . . . . . . . . . . . . . . . . . 101, 104
Reverse Direction . . . . . . . . . . . . . . . . . . . . . . 346 Shielded Twisted-Pair Cables . . . . . . . . . . . . . 75
Reverse Jog. . . . . . . . . . . . . . . . . . . . . . . . . . . 342 Short Circuit Brake Time at Start . . . . . 315, 434
Reverse Operation Selection . . . . . . . . . . . . . 313 Short-Circuit Brake . . . . . . . . . . . . . . . . . . . . 347
Reverse Regenerative Torque Limit . . . .363, 434 Short-Circuit Brake (N.C.) . . . . . . . . . . . . . . 344
Reverse Run Command (2-wire sequence) . . 343 Short-Circuit Brake (N.O.) . . . . . . . . . . . . . . 344
Reverse Torque Limit . . . . . . . . . . . . . . .363, 434 Side-by-Side Setup . . . . . . . . . . . . . . . . . . . . . 43
rH . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 202 Simple V/f with PG . . . . . . . . . . . . . . . . . . . . 220
Rotational Auto-Tuning . . . . . . . . 154, 156, 230 Sinking/Sourcing Mode Switch. . . . . . . . . . . . 77
rr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 203 Slip Compensation Gain . . . . . . . .179, 321, 436
RTS Control Selection . . . . . . . . . . . . . .350, 442 Slip Compensation Limit. . . . . . . . . . . . 322, 436
rUn . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185, 214 Slip Compensation Primary Delay Time321, 436
Run command. . . . . . . . . . . . . . . . . . . . . . . . . 130 Slip Compensation Primary Delay Time Constant
Run Command (2-wire sequence 2) . . . . . . . . 343 179
Run Command at Power Up. . . . . . . . . .314, 433 Slip Compensation Selection during Regeneration
Run Command Input Error. . . . . . . . . . . . . . . 184 322, 436
Run Command Input Selection . . . . . . . . . . . 127 Soft Charge Circuit Fault . . . . . . . . . . . . . . . 183
Run Command Reset . . . . . . . . . . . . . . . . . . . 185 Soft CLA Selection . . . . . . . . . . . . . . . . 365, 435
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 461
Soft Starter Speed Reference at Previous Fault . . Stall Prevention Selection during Acceleration .
151, 381, 440 355, 433
Software No. (Flash). . . . . . . . . . . . . . . 380, 439 Stall Prevention Selection during Deceleration .
Software No. (ROM) . . . . . . . . . . . . . . 380, 439 356, 433
Software Number (Flash) . . . . . . . . . . . . . . . . 151 Stall Prevention Selection during Run. . 356, 433
Software Number (ROM) . . . . . . . . . . . . . . . . 151 Standard Connection Diagram. . . . . . . . . . 55, 56
Speed Agreement Detection Level . . . . 358, 434 Stationary Auto-Tuning . . . . . . . . . . . . . . . . . 157
Speed Agreement Detection Level (+/-) 358, 434 STO . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183, 203
Speed Agreement Detection Width . . . 358, 434 STOP Button Input . . . . . . . . . . . . . . . . . . . . 222
Speed Agreement Detection Width (+/-)358, 434 STOP button Input. . . . . . . . . . . . . . . . . . . . . 186
Speed Control Integral Time 1 . . . . . . . 200, 213 STOP Key Function Selection. . . . . . . . 371, 436
Speed Control Proportional Gain 1. . . . 200, 213 Stopping Method . . . . . . . . . . . . . . . . . . . . . . 129
Speed Deviation (for Simple V/f with PG). . 191, Stopping Method After Communication Error .
208 350, 442
Speed Estimation Type Speed Search. . . . . . . 201 Stopping Method Selection . . . . . . . . . . 313, 433
Speed Feedback Detection Control (AFR) Gain . Suppression Diode Connection . . . . . . . . . . . . 72
367, 435
Speed Feedback Detection Control (AFR) Time
T
Constant . . . . . . . . . . . . . . . . . . . . . . . . 367, 435 T Motor Tuning . . . . . . . . . . . . . . . . . . . . . . . 375
Speed Feedback Detection Control (AFR) Time T1-00 . . . . . . . . . . . . . . . . . . . . . . .160, 375, 438
Constant 2 . . . . . . . . . . . . . . . . . . . . . . . 367, 435 T1-01 . . . . . . . . . . . . . . . . . . 154, 160, 375, 438
Speed Feedback Detection Control Gain368, 436 T1-02 . . . . . . . . . . . . . . 158, 160, 222, 375, 438
Speed Feedback Detection Suppression Gain 239 T1-03 . . . . . . . . . 159, 160, 161, 224, 375, 438
Speed Search. . . . . . . . . . . . . . . . . . . . . 203, 347 T1-04 . . . . . 159, 160, 161, 222, 225, 376, 438
Speed Search Deactivation Current . . . 315, 434 T1-05 . . . . . 159, 160, 161, 222, 224, 376, 439
Speed Search Deceleration Time . . . . . 315, 434 T1-06 . . . . . . . . . . . . . . . . . . 159, 160, 376, 439
Speed Search Delay Time. . . . . . . . . . . 315, 434 T1-07 . . . . . . . . . . . . . . 159, 160, 222, 376, 439
Speed Search Estimation Type . . . . . . . . . . . . 199 T1-11 . . . . . . . . . . . . . . . . . . . . . . .161, 376, 439
Speed Search Method Selection . . . . . . 316, 434 Terminal A1 Bias Setting. . . . . . . . . . . . 348, 441
Speed Search Restart Current Level . . . 315, 434 Terminal A1 Gain Setting . . . . . . . . . . . 348, 441
Speed Search Restart Detection Time . 316, 434 Terminal A1 Input Voltage . . . . . .151, 379, 439
Speed Search Retry Interval Time . . . . 316, 434 Terminal A1 Signal Level Selection . . . 348, 441
Speed Search Selection. . . . . . . . . . . . . 315, 434 Terminal A2 Enable. . . . . . . . . . . . . . . . . . . . 342
Stall Prevention. . . . . . . . . . . . . . . . . . . 180, 201 Terminal A2 Function Selection . . . . . . 348, 441
Stall Prevention During Deceleration . . . . . . . . 83 Terminal A2 Gain Setting . . . . . . . . . . . . . . . 348
Stall Prevention during Deceleration . . . . . . . 198 Terminal A2 Input Voltage . . . . . .151, 379, 439
Stall Prevention Level during Acceleration . 355, Terminal A2 Signal Level Selection . . . 348, 441
433 Terminal A2 Switch. . . . . . . . . . . . . . . . . . . . . 79
Stall Prevention Level during Run . . . . 356, 433 Terminal AM Bias Setting . . . . . . . . . . . . . . . 145
Stall Prevention Limit during Acceleration . 355, Terminal AM Monitor Selection . . . . . . . . . . 145
433 Terminal Block Configuration. . . . . . . . . . . . . 59
462 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Terminal Board . . . . . . . . . . . . . . . . . . . . . . . . 258 Torque Detection Time 2. . . . . . . . . . . . 361, 434
Terminal Board Communication Fault. . . . . . 182 Torque Limit Control Method Selection during
Terminal Board Communications Error . . . . . 189 Accel/Decel . . . . . . . . . . . . . . . . . . . . . . 363, 435
Terminal Board Wiring Guide . . . . . . . . . . . . . 75 Torque Limit Integral Time Constant . . 363, 435
Terminal FM Monitor Selection . . . . . . . . . . . 145 Torque Limits . . . . . . . . . . . . . . . . . . . . . . . . 180
Terminal M1 thru M2 Function Selection (relay) Torque Reference . . . . . . . . . . . . .151, 377, 439
144 Torque Reference (Internal) . . . . . . . . . 151, 442
Terminal MA, MB and MC Function Selection Torque Reference at Previous Fault151, 381, 440
(relay) . . . . . . . . . . . . . . . . . . . . . . 144, 345, 441 Torque Specifications, Single Phase 200 V Class
Terminal P1 Function Selection (open-collector) 64
144, 345, 441 Torque Specifications, Three Phase 200 V Class.
Terminal P2 Function Selection (open-collector) 64
144, 345, 441 Torque Specifications, Three Phase 400 V Class.
Test Run . . .153, 155, 156, 157, 158, 159, 162 65
Tightening Torque . . . . . . . . . . . . . . . . . . . . . . 63 Transistor Input Signal . . . . . . . . . . . . . . . 77, 78
Time Constant 1 . . . . . . . . . . . . . . . . . . . . . . . 237 Tuning Errors. . . . . . . . . . . . . . . . . . . . . . . . . 182
Timer Function . . . . . . . . . . . . . . . . . . . . . . . . 342
Timer Function Off-Delay Time. . . . . . .316, 434 U
Timer Function On-Delay Time . . . . . . .316, 434 U Monitors . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Timer Output . . . . . . . . . . . . . . . . . . . . . . . . . 346 U1 Operation Status Monitors. . . . . . . . . . . . 376
Timing Fault . . . . . . . . . . . . . . . . . . . . . .183, 190 U1-01. . . . . . . . . . . . . . 150, 229, 233, 376, 439
Too Many Speed Search Restarts . . . . . .183, 203 U1-02. . . . . . . . . . . . . . . . . . . . . . .150, 376, 439
Torque Compensation at Forward Start .322, 436 U1-03. . . . . . . . . . . . . . . . . . . . . . .150, 377, 439
Torque Compensation at Reverse Start .322, 436 U1-04. . . . . . . . . . . . . . . . . . . . . . .150, 377, 439
Torque Compensation Gain . . . . . 177, 322, 436 U1-05. . . . . . . . . . . . . . . . . . . . . . .150, 377, 439
Torque Compensation Gain - Motor 2 . .334, 440 U1-06. . . . . . . . . . . . . . . . . . . . . . .150, 377, 439
Torque Compensation Primary Delay Time . 177, U1-07. . . . . . . . . . . . . . . . . . 151, 228, 377, 439
237, 239, 322, 436 U1-08. . . . . . . . . . . . . . . . . . . . . . .151, 377, 439
Torque Compensation Primary Delay Time U1-09. . . . . . . . . . . . . . . . . . 151, 229, 377, 439
Constant 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . 178 U1-10. . . . . . . . . . . . . . . . . . . . . . .151, 378, 439
Torque Compensation Primary Delay Time U1-11 . . . . . . . . . . . . . . . . . . . . . . .151, 378, 439
Constant 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . 179 U1-12. . . . . . . . . . . . . . . . . . . . . . .151, 379, 439
Torque Compensation Time Constant . .323, 436 U1-13. . . . . . . . . . . . . . . . . . . . . . .151, 379, 439
Torque Detection 1 (N.O.) . . . . . . . . . . . . . . . 346 U1-14. . . . . . . . . . . . . . . . . . . . . . .151, 379, 439
Torque Detection 2 (N.C.) . . . . . . . . . . . . . . . 346 U1-16. . . . . . . . . . . . . . . . . . . . . . .151, 379, 439
Torque Detection 2 (N.O.) . . . . . . . . . . . . . . . 346 U1-18. . . . . . . . . . . . . . . . . . . . . . .151, 379, 439
Torque Detection Level 1 . . . . . . . . . . . .360, 434 U1-19. . . . . . . . . . . . . . . . . . . . . . .151, 380, 439
Torque Detection Level 2 . . . . . . . . . . . .361, 434 U1-24. . . . . . . . . . . . . . . . . . . . . . .151, 380, 439
Torque Detection Selection 1 . . . . . . . . .360, 434 U1-25. . . . . . . . . . . . . . . . . . . . . . .151, 380, 439
Torque Detection Selection 2 . . . . . . . . .361, 434 U1-26. . . . . . . . . . . . . . . . . . . . . . .151, 380, 439
Torque Detection Time 1 . . . . . . . . . . . .360, 434 U1-34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 463
U2 Fault Trace . . . . . . . . . . . . . . . . . . . . . . . . 380 U4
U2, U3 Initial Value Selection . . . . . . . 372, 437 Maintenance Monitors . . . . . . . . . . . . . . 383
U2-01 . . . . . . . . . . . . . . . . . . . . . . 151, 380, 439 U4-01 . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
U2-02 . . . . . . . . . . . . . 151, 226, 227, 380, 439 U4-02 . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
U2-03 . . . . . . . . . . . . . . . . . . . . . . 151, 380, 439 U4-03 . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
U2-03 through U2-17 . . . . . . . . . . . . . . 226, 227 U4-04 . . . . . . . . . . . . . . . . . . . . . . .151, 197, 383
U2-04 . . . . . . . . . . . . . . . . . . . . . . 151, 380, 440 U4-05 . . . . . . . . . . . . . . . . . . . . . . .202, 204, 216
U2-05 . . . . . . . . . . . . . . . . . . . . . . 151, 380, 440 U4-06 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
U2-06 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-07 . . . . . . . . . . . . . . . . . . . . . . .151, 383, 441
U2-07 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-09 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 441
U2-08 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-10 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 441
U2-09 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-11 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 441
U2-10 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-13 . . . . . . . . . . . . . . . . . . . . . . . . . . . 151, 384
U2-11 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-14 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 441
U2-12 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-16 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 441
U2-13 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-18 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 442
U2-14 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-19 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 442
U2-15 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-20 . . . . . . . . . . . . . . . . . . . . . . .151, 384, 442
U2-16 . . . . . . . . . . . . . . . . . . . . . . 151, 381, 440 U4-21 . . . . . . . . . . . . . . . . . . . . . . .151, 385, 442
U2-17 . . . . . . . . . . . . . . . . . . . . . . 152, 381, 440 U4-22 . . . . . . . . . . . . . . . . . . . . . . .151, 385, 442
U3 Fault History . . . . . . . . . . . . . . . . . . . . . . . 381 U4-23 . . . . . . . . . . . . . . . . . . . . . . .151, 385, 442
U3-01 . . . . . . . . . . . . . . . . . . . . . . 152, 381, 440 U5 Application Monitor . . . . . . . . . . . . . . . . 386
U3-02 . . . . . . . . . . . . . . . . . . . . . . 152, 381, 440 U5-01 . . . . . . . . . . . . . . . . . . . . . . .151, 386, 442
U3-03 . . . . . . . . . . . . . . . . . . . . . . 152, 381, 440 U5-02 . . . . . . . . . . . . . . . . . . . . . . .151, 386, 442
U3-04 . . . . . . . . . . . . . . . . . . . . . . 152, 381, 440 U5-03 . . . . . . . . . . . . . . . . . . . . . . .151, 386, 442
U3-05 . . . . . . . . . . . . . . . . . . . . . . 152, 382, 440 U5-04 . . . . . . . . . . . . . . . . . . . . . . .151, 386, 442
U3-06 . . . . . . . . . . . . . . . . . . . . . . 152, 382, 440 U6 Application Monitor . . . . . . . . . . . . 386, 387
U3-07 . . . . . . . . . . . . . . . . . . . . . . 152, 382, 440 U6-01 . . . . . . . . . . . . . . . . . . 151, 386, 387, 442
U3-08 . . . . . . . . . . . . . . . . . . . . . . 152, 382, 440 U6-02 . . . . . . . . . . . . . . . . . . 151, 386, 387, 442
U3-09 . . . . . . . . . . . . . . . . . . . . . . 152, 382, 440 U6-03 . . . . . . . . . . . . . . . . . . . . . . . . . . . 151, 442
U3-10 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-04 . . . . . . . . . . . . . . . . . . . . . . .151, 386, 442
U3-11 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-05 . . . . . . . . . . . . . . . . . . . . . . .152, 386, 442
U3-12 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-06 . . . . . . . . . . . . . . . . . . . . . . .152, 386, 442
U3-13 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-07 . . . . . . . . . . . . . . . . . . . . . . .152, 386, 442
U3-14 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-08 . . . . . . . . . . . . . . . . . . . . . . .152, 386, 442
U3-15 . . . . . . . . . . . . . . . . . . . . . . 150, 382, 441 U6-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . 152, 442
U3-16 . . . . . . . . . . . . . . . . . . . . . . 151, 382, 441 U6-18 . . . . . . . . . . . . . . . . . . . . . . . . . . . 152, 442
U3-17 . . . . . . . . . . . . . . . . . . . . . . 151, 382, 441 U6-19 . . . . . . . . . . . . . . . . . . . . . . . . . . . 152, 442
U3-18 . . . . . . . . . . . . . . . . . . . . . . 151, 383, 441 U6-20 . . . . . . . . . . . . . . . . . . . . . . .152, 386, 442
U3-19 . . . . . . . . . . . . . . . . . . . . . . 151, 383, 441 U6-21 . . . . . . . . . . . . . . . . . . . . . . .152, 387, 442
U3-20 . . . . . . . . . . . . . . . . . . . . . . 151, 383, 441 UL Standards . . . . . . . . . . . . . . . . . . . . . . . . . 425
464 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
UL3. . . . . . . . . . . . . . . . . . . . 183, 185, 203, 215 W
UL4. . . . . . . . . . . . . . . . . . . . 183, 185, 204, 215 Watchdog Circuit Exception . . . . . . . . . 183, 189
Undertorque 1. . . . . . . . . . . . . . . . . . . . .185, 215
watchdog circuit exception . . . . . . . . . . . . . . 190
Undertorque 2. . . . . . . . . . . . . . . . . . . . .185, 215
Watt Hour Output Unit Selection . . . . . 345, 441
Undertorque Detection 1 . . . . . . . . . . . . . . . . 183 Watt Hour Pulse Output. . . . . . . . . . . . . . . . . 347
Undertorque Detection 2 . . . . . . . . . . . .183, 204
Watts Loss 200 V Class Single Phase Models 302
Undervoltage . . . . . . . . . . . . . . . . 183, 185, 215
Watts Loss 200 V Class Three Phase Models 303
Undervoltage 3 . . . . . . . . . . . . . . . . . . . . . . . . 205 Watts Loss 400 V Class Three Phase Models 304
Undervoltage Detection 1. . . . . . . . . . . . . . . . 203
Wire Gauge, Single Phase 200 V Class. . . . . . 64
Undervoltage Detection Level (UV) . . .354, 433
Wire Gauge, Three Phase 200 V Class . . . . . . 64
Unexpected Noise from Connected Machinery237 Wire Gauge, Three Phase 400 V Class . . . . . . 65
Unit Selection for Memobus/Modbus Register
Wire Gauges . . . . . . . . . . . . . . . . . . . . . . . . . . 63
0025H . . . . . . . . . . . . . . . . . . . . . . . . . . .351, 442
Wiring Checklist . . . . . . . . . . . . . . . . . . . . . . . 84
Unstable Motor Speed when Using PM . . . . . 239 Wiring Procedure. . . . . . . . . . . . . . . . . . . . . . . 74
Up 2 Command. . . . . . . . . . . . . . . . . . . . . . . . 344
Up Command . . . . . . . . . . . . . . . . . . . . . . . . . 342 Z
User Monitor Selection After Power Up 370, 436 Zero Speed. . . . . . . . . . . . . . . . . . . . . . . . . . . 345
User Parameter Automatic Selection . . 113, 312,
433
User Parameter Default Value113, 164, 371, 436
User Parameters, 1 to 32. . . . . . . . . . . . .312, 433
Uv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185, 215
Uv1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 204
Uv2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 205
Uv3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183, 205
V
V/f Control . . . . . . . . . . . . . . . . . . 122, 139, 156
V/f Control Mode Tuning. . . . . . . . . . . . . . . . 177
V/f Control Mode Tuning Parameters . . . . . . 177
V/f Data Setting Error . . . . . . . . . . . . . .185, 220
V/f Pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
V/f Pattern Selection. . . . . . . . . . . 233, 330, 438
V/F patterns When in V/F Control Mode. . . . 389
VC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Vector motor . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Verify Menu . . . . . . . . . . . . . . . . . . . . . . . . . . 102
VMAX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
VMIN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual 465
466 YASKAWA ELECTRIC TOEP C710606 22A YASKAWA AC Drive - V1000 Installation & Start-Up Manual
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of
the back cover.
MANUAL NO.ޓTOEP C710606 22A
Printed in Japan April 2007 07-4
Date of
printing Date of original
publication
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture
thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade Regulations. Therefore, be
sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
© 2007 YASKAWA ELECTRIC CORPORATION. All rights reserved.