Session2 Distance Protection in Distribution - PRNT

The document discusses zone setting for distance protection on short lines and cables, highlighting the importance of managing R/X ratios to avoid measurement errors and wrong trips. It also addresses challenges related to single and double earth faults in systems with earth fault compensation, emphasizing the need for additional protective measures. Lastly, it covers considerations for mixed feeders comprising overhead lines and cables, including blocking auto reclosing for cable faults.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views18 pages

Session2 Distance Protection in Distribution - PRNT

The document discusses zone setting for distance protection on short lines and cables, highlighting the importance of managing R/X ratios to avoid measurement errors and wrong trips. It also addresses challenges related to single and double earth faults in systems with earth fault compensation, emphasizing the need for additional protective measures. Lastly, it covers considerations for mixed feeders comprising overhead lines and cables, including blocking auto reclosing for cable faults.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

EXPERT WORKSHOP SERIES

Session 2: Distance Protection


on short lines and cables
Unrestricted | © Siemens 2025 | SI EA
Zone Setting
for Short Lines

Page 2 Unrestricted | © Siemens 2025 | SI EA


Example: Setting for a Short Cable

x This shape of zone 1


cable 240mm2, 1km with Rzone1/Xzone1 = 10
110kV/20kV r‘ = 0.125/km
may lead
uk=12% x‘ = 0.128 /km
to measurement issues!

Shape of zone 1 with X


Xzone1 = 80% XL = 0.1
and
Rzone1 = 1:
ZC
1
R

Page 3 Unrestricted | © Siemens 2025 | SI EA


Zone Setting: Influence of the Angle Error

X To visualize the problem, a high angle


1.1%
error of 5 is shown
X
ZL,F
9%
Measured impedance
with 5 angle error

Measured impedance
ZC,F with 5 angle error

R R

For a metallic fault on a transmission line (L=85), For a metallic fault on a cable (C=45), the resulting
even this high angle error will only lead to a small measuring error for the reactance is higher.
measuring error for the reactance
Example: ∆meas = 1 → ∆X/X = 0,14% Example: ∆meas = 1 → ∆X/X = 1,7%

Page 4 Unrestricted | © Siemens 2025 | SI EA


Zone Setting: Issues with High R/X-Ratios

X ∆X/X = 14%
RF

ZC,F ZF
7 1
Measured impedance R
with 1 angle error

To avoid problems from these reactance measuring errors,


we recommend
• To limit the setting ratio Rzone1/Xzone1 < 3, or
• To set a slope for the upper limit of zone 1, which avoids wrong trips

Page 5 Unrestricted | © Siemens 2025 | SI EA


Zone Setting: How to Avoid Wrong Trips

X X
∆X/X = 6%

ZF ZF

R R

Limit the Rzone1/Xzone1 ratio to 3: Tilting the upper limit of the zone can give additional
Example: cable feeder; Rzone1/Xzone1 = 3 security against wrong trips

∆meas = 1 → ∆X/X = 6%

Page 6 Unrestricted | © Siemens 2025 | SI EA


High Source Impedance Ratio

ZS ZL,F I
A
x  
cable 240mm2, 1km
110kV/20kV
uk=12%
r‘ = 0.125/km
x‘ = 0.128 /km
 Umeas

ZS
A high source impedance ratio (SIR) leads SIR = = 18,8
ZL
to a low measuring voltage at the zone limit:
100𝑉 𝑍𝐿,80% 100𝑉 0.1024Ω
Umeas = ∙ = ∙ = 2.4V
3 𝑍𝐿,80% +𝑍𝑆 3 0.1024Ω+2.4Ω
Calculation shown for 3 phase
Recommendation: The measured voltage at the zone faults and secondary values
limit should not be less than 1V (SIR < 60)

Page 7 Unrestricted | © Siemens 2025 | SI EA


Systems with Earth
Fault Compensation
or Isolated Neutral

Page 8 Unrestricted | © Siemens 2025 | SI EA


Systems with Earth Fault Compensation or Isolated Neutral:
Phase to Ground Faults

Single phase-to-ground faults are no short circuits.


The distance protection does not react on single phase-to-ground faults:

L1
L2 Fault inception:
L3 Transient currents after fault inception
Petersen Ires
may lead to a pickup of the distance
coil protection: This is normally supressed
by a time delays

Earth fault compensation

Single phase earth faults must be detected by other protection functions


Consequence
(sensitive directional earth fault protection)

Page 9 Unrestricted | © Siemens 2025 | SI EA


Systems with Earth Fault Compensation or Isolated Neutral:
Double Earth Faults (1)

During an earth fault situation, the ph-e-voltages of the healthy phases


increase by 3. The ph-ph-voltages are not affected.

This leads to an increased risk for a second earth fault


• On a different phase
• At a different location
Result: Double earth fault (cross country fault → short circuit)

→ Special treatment of double earth faults required

Page 10 Unrestricted | © Siemens 2025 | SI EA


Systems with Earth Fault Compensation or Isolated Neutral:
Double Earth Faults (2)

Double earth fault situation leads Double earth fault situation only leads
to a phase-phase-earth pick up to a single phase-to-earth pickup

It is sufficient to trip only one earth fault! In this case, a trip on a persistent single
• Operation can be continued with one earth fault phase-to-ground pickup is required
• The remaining earth fault must be detected Time delay for single phase-to-ground pickup
by the sensitive earth fault function should be cancelled.
Problem: Which earth fault should be tripped?
→ Phase preference
setting required

Page 11 Unrestricted | © Siemens 2025 | SI EA


Mixed Lines
(Overhead Lines & Cables)

Page 12 Unrestricted | © Siemens 2025 | SI EA


Example: Mixed Feeder (Cable & Overhead Line)

x x
Overhead line Cable
6km 2km

Topic 1: setting of distance zone 1 Topic 2: blocking of auto reclosing for cable faults
• Total impedance from the relay Options:
to the end of zone 1 must be calculated • Blocking by the fault locator
• Residual compensation factors must be calculated • Use of a differential protection across the cable
for the same point (without circuit breaker at the connection point
to the overhead line; CT required at this point)

Page 13 Unrestricted | © Siemens 2025 | SI EA


Mixed Feeder (Cable & Overhead Line): Setting of Distance Zone 1

r‘1,OHL, x‘1,OHL r‘1,Ca, x‘1, Ca


r‘0,OHL, x‘0,OHL r‘0, Ca, x‘0, Ca
x x
Overhead line Cable
6km 2km

Xzone1 setting (grading factor 80%)


• Total positive impedance of the feeder: Xfeeder = 6km  x‘1,OHL+ 2km  x‘1,Ca
• Xzone1 = 0.8  Xfeeder; caution: the zone reach is not 80% of the feeder length!
Residual compensation factors kx, kr
• Residual compensation factors must be calculated for the zone limit
• Zone limit (in km behind OHL end): lZL= (Xzone1 - XOHL) / x‘1, Ca
• Total zero sequence reactance inside zone 1: X0,Zone 1= 6km  x‘0,OHL+ lZL  x‘0, Ca
1 𝑋
• kx=3 ∙ 𝑋0,𝑍𝑜𝑛𝑒1 − 1 ; similar calculation for kr
𝑧𝑜𝑛𝑒1

Page 14 Unrestricted | © Siemens 2025 | SI EA


Mixed Feeder (Cable & Overhead Line): Blocking of Auto Reclosing for Cable
Faults

x x
Overhead line Cable
6km 2km

Option 1: Blocking by fault locator Option 2: Use of a differential protection


• The “fault locator plus” can be used to block • Use of a differential protection across the cable
the auto reclose function for cable faults (without circuit breaker at the connection point
• The use of the double-ended fault locator function to the overhead line)
increases the accuracy. This requires a protection • This requires a device installation
communication interface and a communication at the connection point and communication links.
channel

Page 15 Unrestricted | © Siemens 2025 | SI EA


Conclusion:
For distance protection on short or mixed lines
and in systems with earth fault compensation,
some additional considerations are required.

Page 16 Unrestricted | © Siemens 2025 | SI EA


Thank you for attending the webinar

Watch our past webinars

If you are interested in our upcoming


Watch
our past
or past webinars register for free here:
webinars https://www.siemens.com/electrification-automation-webinars

Subscribe

Stay up to date with subscriptions?


www.siemens.com/ea-subscriptions
Subscribe

Visit our trainings

Looking for trainings?


Visit our http://www.siemens.com/poweracademy
trainings

Page 17 Unrestricted | © Siemens 2025 | SI EA


Contact/Disclaimer
Published by Siemens 2025
Smart Infrastructure
Electrification & Automation
Mozartstraße 31 C
91052 Erlangen
Germany

For the U.S. published by


Siemens Industry Inc.
3617 Parkway Lane
Peachtree Corners, GA 30092
United States

© Siemens 2025
Subject to changes and errors. The information given in this
document/video only contains general descriptions and/or performance
features which may not always specifically reflect those described,
or which may undergo modification in the course of further development
of the products. The requested performance features are binding only
when they are expressly agreed upon in the concluded contract.
All product designations may be trademarks or other rights of Siemens,
its affiliated companies or other companies whose use by third parties
for their own purposes could violate the rights of the respective owner.

Unrestricted | © Siemens 2025 | SI EA