Trilogy with Smartpack S
DC Power System
The Eltek Trilogy DC power system, powered by the
Flatpack2 line of power modules, brings 250A − 600A to
applications where space is limited. Use of the highly-
efficient and reliable Flatpack2 rectifier, remarkably
flexible distribution, and the advanced Smartpack S
controller make for optimal system design and cost-
effective deployment.
TRILOGY WITH SMARTPACK S
DC POWER SYSTEM
Doc 370145.DS3 Issue 1.2
APPLICATIONS PRODUCT DESCRIPTION KEY FEATURES
• COMPACT DESIGN
The Eltek Trilogy system is a high- The Trilogy system is designed for use in
Small overall dimensions are ideal for
efficiency power solution with an optimal rack spaces and cabinets. Both 19" and both rack and cabinet solutions.
footprint for 250A to 600A applications 23" rack widths are available.
• CONFIGURABLE DISTRIBUTION
where space is limited − both in typical Circuit breakers can be assigned at-
racks and some cabinet installations. Powered by Flatpack2 HE rectifier will to one of two output buses and
modules, typical efficiency exceeds 95% an LVD contactor can be included.
The Trilogy system can power both single- at both 24 VDC and 48 VDC output. • DIGITAL CONTROLLERS
voltage telecommunication infrastructure Flatpack2 DC-to-DC converters can also be The Smartpack S digital controller
(such as −48V LTE or +24V legacy TDMA), added within the same system footprint. system provides comprehensive
monitoring and regulation by utilizing
as well as dual-voltage sites (e.g., where a variety of specialized data
both −48V and +24V equipment coexist). The distribution section features unique collection devices.
DC-to-DC converters are available for circuit breaker holders that facilitate at- • HEAT MANAGEMENT
converting 24V to 48V (or vice-versa) will assignment in the field to one of two Flatpack2 modules feature front-to-
within a single Trilogy system. output buses. Bulk cable connections are back airflow and chassis-integrated
available in the rear of the distribution. All heat-sinks, supplementing high-
efficiency energy conversion with
cabling is vertical, further reducing
excellent heat management.
horizontal space demands.
• COST-EFFICIENCY
A true plug-and-play system, the
Trilogy system reduces both time-to-
install and overall costs.
Eltek— 2925 E Plano Pkwy, Plano, TX 75074, USA Phone: 469-330-9100 Eltek © 2021 – www.eltek.com 1(2)
TRILOGY WITH SMARTPACK S
INPUT SPECIFICATIONS
Rated Input Voltage Range 100 – 277 VAC1; 80 – 400 VDC1
1
See datasheet for input specifications of specific modules.
Input Connections Terminal Block2
MATE-N-LOK™3
2 Default configuration is one rectifier per input; jumper straps are included for powering two rectifiers from one input.
3
Input cables sold separately; options include one cable per rectifier, or one cable with two MATE-N-LOK connectors to power two
rectifiers per line cord.
OUTPUT SPECIFICATIONS
Rated Voltage 0 – 56 V
Rated Current 600A
PHYSICAL ATTRIBUTES
Nominal rack sizes 19" / 23" (For 19" systems, inside width of relay rack must meet EIA-310-D standards, which
specify an inside dimension of 17.72”.)
Depth 18.5" (AMP connections); 19.25" (terminal block connections)
Height 5 RU to 13 RU, depending on number of distributions, rectifier shelves, and converter shelf.
DC DISTRIBUTION OPTIONS (VARY BY SYSTEM)
Distribution configurations* Top bus options include converter or LVLD.
*For additional details see the Trilogy Product Bottom bus is the primary load bus.
Guide, Doc. No. EDM0000409215.
Bulk battery bus
Available breaker positions; 19" systems – 20 breaker positions per panel.*
positions are configurable in the 23" systems – 24 breaker positions per panel.*
field for top or bottom bus. *Up to two panels
Bulk battery connections Eight (8) ⅜-16 studs, 1" center-to-center
Low voltage disconnect options None, battery (LVBD), both LVBD and load (LVLD),
Breaker sizes Single pole, 0 – 100A
Double pole, 125 –200A
Triple pole, 250A
CONTROLLER
Monitoring Unit Smartpack S Panel Mount
Inputs/Outputs 6 configurable inputs*: 1-3, temperature (battery or ambient); 4, factory-wired for converter
breaker/LVLD open alarm; 5, normally open or normally closed; 6, factory-wired for LVBD
alarm
Additional external battery breaker alarm
6 outputs: dry contact (Normally Open/Normally Closed)
* See Smartpack S Panel Mount datasheet for more details (Doc. No. 242100.415.DS3).
MODULES (SOLD SEPARATELY)
241115.105 Flatpack2 48V, 2000W HE Rectifier
241119.105 Flatpack2 48V, 3000W HE Rectifier
241115.205 Flatpack2 24V, 1800W HE Rectifier
241115.600 Flatpack2 24V, 1350W Converter
241115.602 Flatpack2 48V, 1350W Converter
241115.650 Flatpack2 48V, 1500W Solar Charger
241119.650 Flatpack2 48V, 3200W Solar Charger
OTHER SPECIFICATIONS
Operating temperature −40 to +65°C (-40 to +149°F), de-rates above 45°C (113°F)*
* See datasheet for specific module’s temperature specifications..
Storage temperature -40 to +70°C (-40 to +158°F)
APPLICABLE STANDARDS
Electrical Safety UL/CSA 60950-1, 2nd edition
IEC 60950-1, 2nd edition
EMI/EMC GR-1089-CORE
Environment GR-63-CORE, NEBS LEVEL 3
Doc 370145.DS3 Issue 1.2 Specifications are subject to change without notice
Eltek— 2925 E Plano Pkwy, Plano, TX 75074, USA Phone: 469-330-9100 Eltek © 2021 – www.eltek.com 2(2)