Ep 3
Ep 3
Indirect waste pipe does not connect directly with the drainage system
Airgap unobstructed ver cal distance. For food, water li , expansion tank, cooling jacket,
sterile equipment
Airbreak physical separa on into open floor sink. For air condi oning etc.
Indirect waste swimming pool, pipes from boilers, (drinking fountain may) shall discharge to __
1.5m to 4.6m indirect waste pipes ___ shall be directly trapped but not needed to be vented
4.6m indirect waste pipe less than __ in length need not be larger in diameter than the
tailpiece of the fixture served
0.45m to 0.8m height of standpipe receptor above its trap for clotheswashers
0.15 to 0.45m height of trap above floor for clotheswashers. No trap shall be below the floor
Dishwasher airgap fi ng necessary for the connec on of dishwashing machine to a food waste disposer
Steam pipe no __ shall directly connect to any part of a plumbing or drainage system
60 dec c max temp to discharge under pressure directly into drainage system
152mm deep seal trap shall extend within __ of the bo om of the taank for
boilers
Siphon breaker 19mm opening on the highest point of the deep seal trap to serve as __
3.2mm thickness of chemical resistant glass lined pipe, silicon iron, lead pipe
Trap a fi ng that provides liquid seal which prevents the backflow of foul air
Trap arm por on of a fixture drain between a trap and the vent
Trap seal the max ver cal depth of liquid that trap will retain
Seal the ver cal distance between the dip and the crown weir of a trap
Page 1 of 4
Episode 3
1 trap maximum trap permi ed on a trap arm
Developed length measured from the trap weir to the inner edge of the vent
90 deg a change in direc on of trap arm which does not exceed __ does not
require a cleanout
76mm, 22-1/2” for trap arms __ in diameter and larger with an change of direc on
greater than __, a cleanout is required at the bend
1.8m max developed length bet trap of a water closet from top of closet ring to
inner edge of vent
Gauge 17 b&s or 1.1mm thickness for exposed and readily accessible drawn brass tubing trap, excl
urine
Manufacturers name and gauge shall be stamped on the metal of the trap
Backwater valve when floor drain is subject to reverse flow, it shall be equipped with __
Deep seal p-trap 7.5cm to 10cm (3”-4”) deep water seal. For extreme heat, turbulent
atmospheric, and when total ven la on cannot be obtained
Page 2 of 4
Episode 3
direct or self-siphoning occur in unven lated traps which serve as oval bo om fixtures like
lavatories or slop sink
self-siphoning created when rapid flow of water passes through the pipe
indirect or momentum siphoning result of minus pressure in the pipe created by heavy discharge of water
from a fixture installed on a line serving another fixture at a lower floor
backpressure caused by plus pressure. when large amount flow drops downward
rapidly forming a slug like, the air inside the pipe will be compressed
downward
evapora on minor problem and less probable to drain water inside the trap. this
happens on floor drains not regularly used to admit water
wind effect wind velocity passing over the top of the soil pipe may affect the trap seal
capillary ac on the kind of trap seal loss that seldom happens and is rarely experienced
by homeowners. draining of water seal caused by foreign objects like
thread or string suspended and extended over the outlet arm of the trap
grease trap retains grease from 1 to 4 fixtures. may be installed in restaurants, cafes,
hotels, school kitchens
grease interceptor at least 3 cu.m serving one or more fixtures and which is remotely
located
individual dwelling units grease trap is not required for __ or any private living quarters
flow control shall be installed in the visible loca on (tail piece or drain outlet)
0.75m max ver cal tailpipe or drain bet fixture outlet and grease trap
152mm water seal for interceptors for sand and similar heavy solids
sand interceptors required whenever the discharge may contain solids heavier than water
that would be harmful to the drainage system
76mm min inlet and outlet pipe size. outlet = inlet pipe
50% of inlet sec on outlet sec on shall have min area of ___
Page 4 of 4