0% found this document useful (0 votes)
9 views9 pages

2

The document outlines the material specifications and calculations for the separator foundation at the Bekasap Surface Facility Upgrade project. It details the concrete types, structural steel, and rebar specifications, as well as site conditions including earthquake zone and ground water levels. Additionally, it includes design and stability analysis for shallow foundations, considering loads from the building's self-weight, live loads, and wind loads based on ASCE 7-16 standards.

Uploaded by

xaziordon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views9 pages

2

The document outlines the material specifications and calculations for the separator foundation at the Bekasap Surface Facility Upgrade project. It details the concrete types, structural steel, and rebar specifications, as well as site conditions including earthquake zone and ground water levels. Additionally, it includes design and stability analysis for shallow foundations, considering loads from the building's self-weight, live loads, and wind loads based on ASCE 7-16 standards.

Uploaded by

xaziordon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION

(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA


SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1

9. MATERIAL SPECIFICATIONS
9.1 Concrete
The concrete used has a compressive strength proven by a cylinder test at 28 days after casting in field, unless otherwise
stated, is as follows :

f 'c f 'c Cement


Function
Type
(psi) (MPa)
2000 15 I Lean Concrete
3000 21 I Nonstructural Concrete
4000 21 I Structural Concrete
4000 21 I Bored Pile

9.2 Structural Steel


Min. yield stress, 𝑓 = 240 MPa

9.3 Steel Reinforcement / Rebar


Undeformed min. yield strength, 𝑓 = 280 MPa
Deformed min. yield strength, 𝑓 = 420 MPa

9.3 Material Unit Weight


3
Rinforced concrete, 𝛾 = 2.400 ton/m
3
Structural steel, 𝛾 = 7.850 ton/m
3
Steel rebar, 𝛾 = 7.850 ton/m
3
Water, 𝛾 = 1.000 ton/m

10. SITE CONDITION


Elevation
Ground level elevation about EL.+0.000
Earthquake Zone
Bekasap Surface Facilities Upgrade project located at the Bekasap Street, Bengkalis Regency, Riau, Indonesia. Based on
SNI 726-2019 is an earthquake area with peak ground acceleration (PGA) on soft soil for a probability of exceeding 0.1812 g.
Ground Water Level (GWL)
Ground level elevation about EL.+0.000

Page 1 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1

1. DESIGN AND STABILITY ANALYSIS OF SHALLOW FOUNDATION


HIDE THIS CELL!!!
INPUT DATA
Material
Concrete
Concrete Compressive Strength, 𝑓′ = 28.00 MPa
3
Concrete Unit Weight, 𝛾 = 2400.00 kg/m
Pedestal Width, 𝐵 = 400.00 mm
Footing Dimensions
Footing Length, 𝐿 = 400.00 mm
Footing Width, 𝐵 = 400.00 mm

Pedestal Dimensions
Pedestal Length, 𝐿 = 400.00 mm
Pedestal Width, 𝐵 = 400.00 mm
Footing Dimensions
Footing Length, 𝐿 = 400.00 mm
Footing Width, 𝐵 = 400.00 mm

Roof slope case 1, 𝜃 = 9.00 degree

1.1. Shallow Foundation Dimensions


Pedestal
Pedestal Length, 𝐿 = 400.00 mm
Pedestal Width, 𝐵 = 400.00 mm
Building width, 𝐵 = 1.00 m
Roof slope case 1, 𝜃 = 9.00 degree
Dead Load ( D ) that applied on this structure consists of:
1. Building's Self-Weight
Building's self-weight is calculated automatically by the STAAD pro program using the SELFWEIGHT feature.
2. Grating
The self-weight due to the grating is determined based on the Table A255MS Grating Load/Deflection. The dead load
of the grating is applied along the one-way beam.
Grating Specification :
Grating size = 32.00 mm
Load per distance of 900 mm = 32.00 mm
Allowable deflection per distance of 900 mm = 32.00 mm
Weight of grating = 33.60 kg/m2
3. Handrail
Weight of handrail = 20.00 kg/m

13.2 Live Load ( L )

Page 2 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1
Live Load ( L ) that applied on this structure refer to (ASCE 7-16 - "American Society of Civil Engineer" Minimum Design
Loads for Building and Other Structures). Live Load ( L ) that applied on this structure consists of:
1. Walkway
The live load on the grating is applied along the one-way beam.
Walkway Live Load = 500.00 kg/m2 (ASCE 7-16 Table 1)
2. Grating
3. Handrail
Weight of handrail = 20.00 kg/m

13.3 Wind Load ( W )


Wind Load ( W ) calculation procedure refer to (ASCE 7-16 - "American Society of Civil Engineer" Minimum Design Loads
for Building and Other Structures). The calculation procedure of the wind load is as follows:

The velocity pressure (qz) evaluated at height z above the ground shall be calculated by the following equation:
2
𝑞 = 0.613 × 𝐾 × 𝐾 × 𝐾 × 𝐾 × 𝑉 (N/m ) (ASCE 7-16 Section 26.10-1.si)
Description :
𝐾 = Velocity pressure exposure coefficient evaluated at height z = h (ASCE 7-16 Table 26.10-1)
𝐾 = Topographic factor (ASCE 7-16 Section 26.8.2)
𝐾 = Wind directionality factor (ASCE 7-16 Table 26.6-1)
𝐾 = Ground elevation factor (ASCE 7-16 Section 26.9)
𝑉 = Basic wind speed (m/s) (Design Civil Basis PHR-SP-CI-GG-002)
𝑞 = Velocity pressure at height z = h (ASCE 7-16 Section 26.5)

Input Data
Basic wind speed, 𝑉 = 71.58 mph
= 32.00 m/s (Design Civil Basis PHR-SP-CI-GG-002)
Structure's exposure categories, = C (ASCE 7-16 Section 26.7.3)
Structure type :
Solid Freestanding Walls, Roof Top Equipment, and Solid Freestandings and Attached Signs (ASCE 7-16 Table 26.6-1)
Structure's enclosure classification, = Open buildings (ASCE 7-16 Table 26.13-1)
Structure's roof type, = Gable Roof

Gable Roof Case 1 Gable Roof Case 2

Page 3 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1

Hip Roof Case 1 Hip Roof Case 2

Figure 13-1 Building Dimensions for Wind Load

Dimension of structure :
Structure height, ℎ = 4.00 m
Building length, 𝐿 = 7.45 m
Building width, 𝐵 = 1.00 m
Roof slope case 1, 𝜃 = 9.00 degree
Roof slope case 2, 𝜃 = 9.00 degree (If Gable Roof, input 0)

Output Data
Velocity pressure exposure coefficient, 𝐾 = 0.85 (ASCE 7-16 Table 26.10-1)
Topographic factor, 𝐾 = 1.00 (ASCE 7-16 Section 26.8.2)
Wind directionality factor, 𝐾 = 0.85 (ASCE 7-16 Table 26.6-1)
Ground elevation factor, 𝐾 = 1.00 (ASCE 7-16 Section 26.9)
2
Calculated velocity pressure, 𝑞 = 453.52 N/m (ASCE 7-16 Section 26.10-1.si)
2
= 46.23 kg/m
2
Minimum velocity pressure, 𝑞 , = 0.77 kN/m (ASCE 7-16 Section 27.1.5)
2
= 78.49 kg/m
2
Velocity pressure used, 𝑞 , = 78.49 kg/m

The design wind pressure (PW) for the buildings of all heights shall be calculated by the following equation:
P = 𝑞. 𝐺. 𝐶𝑝 − 𝑞 . (𝐺𝐶 ) (ASCE 7-16 Section 27.3.1)
Description :
𝑞 = qz for windward walls evaluated at height z = h above the ground (ASCE 7-16 Table 26.10-1)
𝑞 = qz for leeward walls, sidewalls, and roofs evaluated at height z = h (ASCE 7-16 Section 26.8.2)
𝐺 = Gust-effect factor (ASCE 7-16 Section 26.11.1)
𝐶 = External pressure coefficient (ASCE 7-16 Figures 27.3-1)
𝐺𝐶 = Internal pressure coefficient (ASCE 7-16 Table 26.13-1)

Design Wind Pressure for Case 1


Gust-effect factor, 𝐺 = 0.85 (ASCE 7-16 Section 26.11.1)
Internal pressure coefficient, 𝐶 = 0.00 (ASCE 7-16 Table 26.13-1)
/

Page 4 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1
Building length to width ratio, 𝐿/𝐵 = 7.45
Building length to width ratio, ℎ/𝐿 = 0.54
Roof slope case 1, 𝜃 = 9.00 degree
Table of external pressure coefficient (Cp) (ASCE 7-16 Figures 27.3-1)
Surface External Pressure Coefficient (Cp)
Wall
Windward Wall 0.80
Leeward Wall -0.20
Sidewall -0.70
Roof q ≥ 10 °
Windward Roof Max -
Windward Roof Min -
Leeward Roof Max -
Leeward Roof Min -
Roof q < 10°
Windward Roof Max (0 to 0.5h) -0.93
Windward Roof Min (0 to 0.5h) -0.18
Windward Roof Max (0.5h to h) -0.89
Windward Roof Min (0.5h to h) -0.18
Windward Roof Max (h to 2h) -0.51
Windward Roof Min (h to 2h) -0.18
Windward Roof Max (>2h) -0.33
Windward Roof Min (>2h) -0.18

Table calculation of design wind pressure for case 1


𝑷𝒆𝒙𝒕 𝑷𝒊𝒏𝒕 𝑷𝒎𝒊𝒏 𝑷𝒎𝒂𝒙
𝒒𝒛 𝑮 𝑪𝒑 𝑮𝑪𝒑𝒊
Surface (𝒒. 𝑮. 𝑪𝒑 ) (𝒒𝒊 . 𝑮𝑪𝒑𝒊 ) (𝑷𝒆𝒙𝒕 − 𝑷𝒊𝒏𝒕 ) (𝑷𝒆𝒙𝒕 + 𝑷𝒊𝒏𝒕 )
(m) (kg/m2) (kg/m2) (kg/m2) (kg/m2)
Wall
Windward wall 78.49 0.85 0.80 0.00 53.37 0.00 53.37 53.37
Leeward wall 78.49 0.85 -0.20 0.00 -13.34 0.00 -13.34 -13.34
Sidewall 78.49 0.85 -0.70 0.00 -46.70 0.00 -46.70 -46.70
Roof
Windward Roof Max (0 to 0.5h) 78.49 0.85 -0.93 0.00 -62.02 0.00 -62.02 -62.02
Windward Roof Min (0 to 0.5h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (0.5h to h) 78.49 0.85 -0.89 0.00 -59.06 0.00 -59.06 -59.06
Windward Roof Min (0.5h to h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (h to 2h) 78.49 0.85 -0.51 0.00 -34.34 0.00 -34.34 -34.34
Windward Roof Min (h to 2h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (>2h) 78.49 0.85 -0.33 0.00 -21.99 0.00 -21.99 -21.99
Windward Roof Min (>2h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Note:
(+) Value of design wind pressure indicates windward / compression wind pressure
(-) Value of design wind pressure indicates leeward / suction wind pressure
Design Wind Pressure for Case 2
Gust-effect factor, 𝐺 = 0.85 (ASCE 7-16 Section 26.11.1)
Internal pressure coefficient, 𝐶 = 0.00 (ASCE 7-16 Table 26.13-1)
/

Page 5 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1
Building length to width ratio, 𝐵/𝐿 = 0.13
Building length to width ratio, ℎ/𝐵 = 4.00
Roof slope case 2, 𝜃 = 9.00 degree
Table of external pressure coefficient (Cp) (ASCE 7-16 Figures 27.3-1)
Surface External Pressure Coefficient (Cp)
Wall
Windward Wall 0.80
Leeward Wall -0.50
Sidewall -0.70
Roof q ≥ 10 °
Windward Roof Max -
Windward Roof Min -
Leeward Roof Max -
Leeward Roof Min -
Roof q < 10°
Windward Roof Max (0 to 0.5h) -1.30
Windward Roof Min (0 to 0.5h) -0.18
Windward Roof Max (0.5h to h) -0.70
Windward Roof Min (0.5h to h) -0.18
Windward Roof Max (h to 2h) -0.70
Windward Roof Min (h to 2h) -0.18
Windward Roof Max (>2h) -0.70
Windward Roof Min (>2h) -0.18

Table calculation of design wind pressure for case 2


𝑷𝒆𝒙𝒕 𝑷𝒊𝒏𝒕 𝑷𝒎𝒊𝒏 𝑷𝒎𝒂𝒙
𝒒𝒛 𝑮 𝑪𝒑 𝑮𝑪𝒑𝒊
Surface (𝒒. 𝑮. 𝑪𝒑 ) (𝒒𝒊 . 𝑮𝑪𝒑𝒊 ) (𝑷𝒆𝒙𝒕 − 𝑷𝒊𝒏𝒕 ) (𝑷𝒆𝒙𝒕 + 𝑷𝒊𝒏𝒕 )
(m) (kg/m2) (kg/m2) (kg/m2) (kg/m2)
Wall
Windward wall 78.49 0.85 0.80 0.00 53.37 0.00 53.37 53.37
Leeward wall 78.49 0.85 -0.50 0.00 -33.36 0.00 -33.36 -33.36
Sidewall 78.49 0.85 -0.70 0.00 -46.70 0.00 -46.70 -46.70
Roof
Windward Roof Max (0 to 0.5h) 78.49 0.85 -1.30 0.00 -86.73 0.00 -86.73 -86.73
Windward Roof Min (0 to 0.5h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (0.5h to h) 78.49 0.85 -0.70 0.00 -46.70 0.00 -46.70 -46.70
Windward Roof Min (0.5h to h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (h to 2h) 78.49 0.85 -0.70 0.00 -46.70 0.00 -46.70 -46.70
Windward Roof Min (h to 2h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Windward Roof Max (>2h) 78.49 0.85 -0.70 0.00 -46.70 0.00 -46.70 -46.70
Windward Roof Min (>2h) 78.49 0.85 -0.18 0.00 -12.01 0.00 -12.01 -12.01
Note:
(+) Value of design wind pressure indicates windward / compression wind pressure
(-) Value of design wind pressure indicates leeward / suction wind pressure

13.3 Seismic Load ( V )


Seismic Load ( V ) calculation procedure refer to (SNI 1726 - 2019 - Tata Cara Perencanaan Ketahanan Gempa untuk
Struktur Bangunan Gedung dan Non Gedung). Seismic load can be calculated with following procedure :

Page 6 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1
Struktur Bangunan Gedung dan Non Gedung). Seismic load can be calculated with following procedure :
Input Data
Earthquake Parameters Symbol Value Unit Reference
Site class - SE -
Mapped MCEG peak ground acceleration 𝑃𝐺𝐴 0.4048 g (https://rsa.ciptakarya.pu.go.id/2021)
Mapped MCER spectral response acceleration 𝑆 0.3962 g (https://rsa.ciptakarya.pu.go.id/2021)
parameter at short periods (5% damped)
Mapped MCER spectral response acceleration 𝑆 0.4048 g (https://rsa.ciptakarya.pu.go.id/2021)
parameter at a period of 1 s (5% damped)
Design spectral response acceleration parameter at 𝑆 0.3962 g (https://rsa.ciptakarya.pu.go.id/2021)
short periods (5% damped)
Design spectral response acceleration parameter at a 𝑆 0.4048 g (https://rsa.ciptakarya.pu.go.id/2021)
period of 1 s (5% damped)
Long-period transition period 𝑇 20 s (https://rsa.ciptakarya.pu.go.id/2021)
Risk category - III - (SNI 1726-2019 Table 3)
Importance factor 𝐼 1.25 - (SNI 1726-2019 Table 4)
X direction
Seismic force-resisting systems Steel special truss moment (SNI 1726-2019 Table 4)
frames

Response modification coefficient 𝑅 7 - (SNI 1726-2019 Table 12)


Overstrength factor Ω , 3 - (SNI 1726-2019 Table 12)
Response modification coefficient 𝐶 , 5.5 - (SNI 1726-2019 Table 12)
Z direction
Seismic force-resisting systems Steel special moment (SNI 1726-2019 Table 4)
frames

Response modification coefficient 𝑅 8 - (SNI 1726-2019 Table 12)


Overstrength factor Ω , 3 - (SNI 1726-2019 Table 12)
Response modification coefficient 𝐶 , 5.5 - (SNI 1726-2019 Table 12)

Seismic response coefficient (Cs) shall be calculated by the following equation:


𝐶 = 2
(N/m ) (SNI 1726-2019 Eq. 31)

Description :
𝑆 = Design spectral response acceleration parameter at short periods (5% (https://rsa.ciptakarya.pu.go.id/2021)
damped)
𝑅 = Response modification coefficient (SNI 1726-2019 Table 12)
𝐼 = Importance factor (SNI 1726-2019 Table 4)

Minimum seismic response coefficient (Cs,min) shall be calculated by the following equation:
𝐶, = 0.44. S . I ≥ (SNI 1726-2019 Eq. 34)
Description :
𝑆 = Design spectral response acceleration parameter at short periods (5% (https://rsa.ciptakarya.pu.go.id/2021)
damped)
𝐼 = Importance factor (SNI 1726-2019 Table 4)

Page 7 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1
Seismic response coefficient (Cs) :
X-direction
𝐶, = 0.07 < 𝐶 , = 0.22 → 𝐶 , = 0.22
Z-direction
𝐶, = 0.06 < 𝐶 , = 0.22 → 𝐶 , = 0.22

4.2 Contractor / Consultant


The company is PT. PERTAMINA HULU ROKAN as the owner and end user of the facilities.
4.3 Project
The company is PT. PERTAMINA HULU ROKAN as the owner and end user of the facilities.
4.4 Vendor
The company is PT. PERTAMINA HULU ROKAN as the owner and end user of the facilities.

Page 8 of 21
FEED OPLL SLO STAGE 6 CALCULATION FOR SEPARATOR FOUNDATION
(BEKASAP SURFACE FACILITY UPGRADE) BEKASAP AREA
SLON-GATHBKSP000-CIV-CAL-PHR-2031-00
Rev. A1

Page 9 of 21

You might also like