PRC3601 Study Guide
PRC3601 Study Guide
PRC3601/1/2021
70716226
InDesign
Florida
PR_Tour_Style
Page
1
1
1.1 Introduction, outcome and assessment criteria 1
1.2 Basic concepts 1
1.2.1 Chemical process 1
1.2.2 Process control systems 1
1.3 The purpose of control systems 1
1.3.1 Minimising process variability 1
1.3.2 Maximising process efficiency 1
1.3.3 Process safety 1
1.3.4 Profit 1
1.4 The process control loop 2
1.5 Instrumentation 4
1.5.1 Instrumentation for pressure measurement 1
1.5.2 Instumentation for temperature measurement 1
1.5.3 Instrumentation for level measurement 1
1.5.4 Instrumentation for chemical composition measurement 1
1.6 Control system documentation 7
1.6.1 Process flow diagram 1
1.6.2 Piping and instrumentation diagram 1
1.7 Piping and connections 9
1.8 Summary 9
1.9 References 1
1.10 Problems
11
2.1 Introduction outcome and assessment criteria 11
2.2 Basic role of a control system 11
2.3 Control system terminology 11
2.4.1 Open-loop control 1
2.4.2 Closed-loop control 1
2.4.3 Combined feedforward and feedback control 1
2.5 Control systems 13
2.5.1 Manual control systems 1
2.5.2 Automated control systems 1
2.6 Controllers 14
2.6.1 ON/OFF controllers (discrete control systems) 1
2.6.2 Programmable logic controllers (PLCs) 1
2.6.3 Distrubted control systems (DCSs) 1
2.6.4 Analogue controllers 1
2.6.5 Digital controllers 1
2.6.6 Emergency shutdown controllers (ESDs) 1
2.7 Communication signals for controllers 1
2.7.1 Analogue signals 1
2.7.2 Discrete signals 1
2.7.3 Digital signals 1
2.8 Advantages and disadvantages of communication signals 15
2.9 Digital communication standards 16
2.9.1 HART communication 1
2.9.2 Fieldbus 1
2.9.3 Ethernet 1
2.9.4 Qireless communication 1
2.10 Transfer function 16
2.10.1 The algebra of a process block diagram 1
2.10.2 The summing point types of a closed control loop 1
2.10.3 Algebraic operations of control loop block diagrams 1
2.11 Transfer function for open-loop control systems 17
2.12 Transfer function for closed-loop control systems 17
2.13 Multi-loop/closed-loop systems 17
2.14 Summary 1
2.15 References 1
2.16 Problems 1
18
3.1 Introduction, outcome and assessment criteria 18
3.2 Process controller algorithms 18
3.2.1 Discrete controllers 1
3.2.2 Multi-step controllers 1
3.2.3 Continuous controllers 1
3.3 Controller modes 18
3.3.1 Proportional control mode 1
3.3.2 Integral control mode 1
3.3.3 Derivative control mode 1
3.3.4 Proportional + integral (PI) control mode 1
3.3.5 Proportional + derivative (PD) control mode 1
3.3.6 Proportional + integral + derivative (PID) control mode 1
3.4 Digital implementation of the PID algorithm 19
3.5 Process controller selection 20
3.6 Control loop performance 20
3.6.1 Definition of control quality 1
3.6.2 Measurement of quality 1
3.7 Control loop performance monitoring 20
3.7.1 Control loop diagnostics 1
3.7.2 Control loop stability 1
3.8 Control system tuning 21
3.8.1 Closed loop tuning: Ziegler-Nichols 1
3.8.2 Open-loop tuning 1
3.8.3 Lambda or IMC tuning 1
3.8.4 Auto-tuning 1
3.8.5 Trial and error tuning 1
3.9 Summary 21
3.10 References 22
3.11 Problems 23
26
4.1 Introduction, outcome and assessment criteria 26
4.2 Control loop classification 26
4.2.1 Single variable control loops 1
4.2.2 Multi-variable control loops 1
4.3 Feedback and feedforward conrol systems 26
4.3.1 Feedback control systems 1
4.3.2 Feedforward control systems 1
4.3.3 Feedforward + feedback control systems 1
4.4 Advanced process control loops 26
4.4.1 Cascade control loops 27
4.4.2 Batch control systems 27
4.4.3 Ratio control 27
4.4.4 Selective control 28
4.4.5 Fuzzy control 28
4.5 Final control operation 30
4.5.1 Controller signal conversion 1
4.5.2 Actuators 1
4.5.3 The final control element 1
4.5.4 General operation of control valves 1
4.5.5 Types of control valves 1
4.6 Globe valve 32
4.6.1 Fail-safe control design 1
4.6.2 Fail-safe control valves 1
4.6.3 Control characteristics 1
4.7 Valve sizing and selection 32
4.7.1 The valve flow equation 1
4.7.2 Algorithm for valve sizing and selection 1
4.7.3 Case study 1
4.8 Summary 1
4.9 References 1
4.10 Problems 1
Process control engineering is a feature of a number of engineering disciplines,
such as chemical, electrical, and mechanical engineering. It is also applied in a
wide range of physical systems, from electrical circuits to guided missiles and
robots. This engineering science involves basic principles particularly useful to
chemical engineers when applied to physicochemical systems such as chemical
reactors, heat exchangers, and mass transfer equipment [10]. A typical chemical
plant is a complex combination of various processing units (distillation columns,
reactors, pumps, absorbers and heat exchangers, etc.) arranged systematically
in order to operate efficiently and effectively (see figure 1).
Operating a chemical plant safely is very important for ensuring the well-being
of the plant workers, the surrounding community and the economic viability of
the overall process. Consequently, maintaining process variables (temperature,
concentrations of chemicals, pressure etc.) within recommended limits is a
primary requirement during plant operation [6].
To preserve the environment and ensure public health, laws governing the
chemical composition and rate of emissions from chemical plants must be
respected at all times.
The key aspects required for a chemical plant to operate successfully are
summarised in figure 2 below [6].
The requirements listed above mean that the process variables of the plant
have to be constantly monitored. This is accomplished through process control
and instrumentation, which I will say a bit more about below [6].
Your next question might well be: What is process control? Also, what does
instrumentation entail?
This study guide is divided into four chapters, which deal with the fundamentals
of process control and instrumentation.
To facilitate the learning process and to provide appropriate and simple practical
examples, basic chemical engineering concepts are generally introduced
through steady-state physical systems. However, when we observe a chemical
boiling and viscous material being extruded, with process parameters changing
continuously. This shows that chemical processes are dynamic and that
regardless of their size or complexity, they exhibit transient behaviour – and
this is the key reason why process control is necessary [6].
In the chemical industry, the term “process” refers to the methods or means
of refining or converting raw materials into desired end products. During the
process, energy is provided from an external source and raw materials are used
in either a liquid, gaseous, or slurry (a mix of solids and liquids) state and can
be measured, mixed, cooled, heated, filtered, transferred, handled or stored
so as to produce the desired end product (see figures 1.1 and 1.2) [6; 7].
• Batch processes,
• Continuous processes and
• Discrete manufacturing processes [7].
Process control aims to reduce variability in the final product, which guarantees
a consistently high-quality end product. Without control, end product quality
will vary. As a result, the plant will manufacture either a final product that is
of a higher grade and more expensive than its market value, or a lower-grade
final product for a higher market price (see figures 1.4 and figure 1.5) [6].
Reducing end product variability can prevent the need for product padding to
meet required product specifications. Padding is the process of upgrading end
product quality to meet market specifications. Variability in the final product
(i.e., poor process control) forces manufacturers to pad the product to ensure
that specifications are met, which adds to the production cost. With accurate,
dependable process control, the set point (desired or optimal point) can be
moved closer to the actual product specification and thus minimise total
production cost. For instance, in blending and batching operations, control
systems are central to maintaining the proper ratio of ingredients to deliver a
product of desired quality consistently. For example, let’s consider the process
of cobalt production. Cobalt is a mineral used in several industries, including
the battery industry and the electroplating industry [6; 7].
Precise process control is necessary mainly to ensure the safety of the staff,
environmental safety and equipment safety. The safety of the workers and the
surrounding community is of primary concern in the operation of any chemical
plant. The consequences of poor control of all of the process variables during
any chemical process operation can be catastrophic. For example, maintaining
proper boiler pressure is very important to prevent the boiler from exploding,
as this could endanger the staff. Examples of safety equipment incorporated
into process control systems include temperature switches, pressure switches
and pressure relief valves [6].
Once product quality and safety requirements have been met, the objectives
of the control system can then be focused on profit. Profit is made when
product quality is not compromised, and that means operating the chemical
plant within the process constraints. The more closely to these constraints the
process is operated, the higher the profit. However, the most difficult element
of process control is maintaining the operation of the chemical plant near the
constraints safely without compromising the quality of the end product [6].
•
•
•
•
•
•
(a) The range – this consists of the lowest and highest values a sensor can
measure within its specification. For example, a temperature sensor can
have a measuring range of –260 °C to +600 °C.
(b) The span – this is the high end of the range minus the low end of the
range of a sensor. For example, a sensor with a range of –260 °C to
+600 °C would have a span of 860 °C.
(c) The resolution – this is the smallest amount of input signal change an
instrument can detect effectively [3].
(d) Accuracy – this describes how close the measurement approaches the
true value of the measured process variable. Accuracy of a measurement
is generally expressed as a percentage error (% error) or an absolute error
over a range [3].
The rise time of an instrument refers to the time it takes for the instrument
to generate a signal representing 100% of the value of the process variable
it is measuring after a step change in the variable. The instrument dead
time is the time period required for an instrument to start reacting to
process change [8].
New instruments have various other characteristics that could also be considered
when needed. These include averaging or storing measurement values. These
features should only be considered when they are required for efficient control
of the process plant; in other cases, they are generally ignored when selecting
an instrument. In chemical processing plants, the most common measurements
are pressure, temperature, flow and level [8].
In all chemical processing plants pressure measurement, either as a fundamental
measurement or as an implied measurement of level and flowrate, plays
a significant role in the efficient operation of the process plant. Pressure
measurements can be divided into four main categories [4; 5]:
(a) Gauge pressure – This is the pressure measured above the local atmospheric
pressure which generally changes according to weather conditions
and altitude. Therefore, if the pressure measurement instrument is not
connected to a pressure source, the pressure reading will be zero. When
the instrument is configured appropriately, the pressure measurements
obtained below the local atmospheric pressure are read negatively [4].
(b) Absolute pressure – The pressure reading obtained in this case is known
as absolute pressure measurement. Except in a complete vacuum
environment, the measuring instrument will always generate a reading.
In this case, pressure measured below the atmospheric pressure will be
read as positive absolute pressure [4].
Absolute pressure and gauge pressure are related through the following
mathematical expression:
In the past, Bourdon tubes were the basis of pressure gauges commonly used
in chemical plants (see figure 1.9). In these devices, the sensing element is a
simple coiled metal tube. The measuring process consists of displacing the
pointer on the gauge by an acting force generated by the increase in pressure
inside the tube. Nowadays these instruments are still used in portable devices
such as car tyre inflators. Even though these instruments are cheap, they are
not commonly used in modern chemical plants because the transmission of the
readings obtained to remote locations such as control rooms is quite difficult [4].
Recent pressure sensor devices come in a package including the sensor, signal
conditioning and a transmitter. Of all the types of pressure sensors, the following
two are the most popular [4; 5]:
(a) Thermocouples
The two wires are joined at each end. During temperature measurement,
a small voltage generated by the feedback effect and proportional to the
difference between the temperatures at the two ends of the thermocouple
device is detected (see figures 1.12 and 1.13) [5].
In the past, the cold end of the thermocouple was maintained at a fixed
temperature by keeping it in an ice or water bath at all times. In the new
thermocouple devices, the cold end is simulated using an electronic chip made
of a thermistor and complex electronics. This complex electronic system also
serves to intensify the mV output of the thermocouple to generate something
more useful in the rest of the instrument [5].
Because thermistors can come in very small sizes and are able to measure
temperature very fast, they are nowadays used more often when rapid
temperature measurement is needed. For example, thermistors can be used
effectively to detect vortices in some vortex shedding flowmeters [5].
One end of the device is connected to the bottom of the container of the liquid
via a nearby tapping. This end is referred to as the high-pressure connection.
The other end is connected to a tapping at the top and, most important, in the
vapour space above the liquid. Because the differential pressure obtained is
actually the measurement of the hydrostatic head in the container, knowing
the density will enable you to calculate the level of the liquid in the vessel [5].
The disadvantage of the use of this technique is revealed when the liquid either
contains solid particles or is likely to form solid particles. This has to do with the
fact that the high-pressure tapping can become clogged with solid materials.
This can happen with any slurry containing a significant quantity of solids.
If the high-pressure end is partially clogged with solids, the response of the
pressure difference measuring instrument will become slower and slower as it
gets more and more clogged. When the tapping point is completely clogged,
no pressure measurement is possible [5].
The increase or decrease in the level of the liquid will induce a change in
the capacitance measurement. This change can be calibrated to provide the
measurement of the level of liquid in the vessel (see figures 1.18 and 1.19) [5].
(a) pH meters
Online chemical analysers are not popular in industry because of the numerous
disadvantages associated with their use. The first step of the analysis process
consists of collecting the sample of the material to be analysed. This step on
its own involves piping, pumps, valves and control gear. The sampling session
also induces time delay or dead time in the overall measuring process. The
presence of significant dead time in a control system might cause various
problems for the system controllers [5].
Moreover, the fact that chemical analysers are made specifically for the
measurement of particular chemical substances makes them quite expensive;
because they cannot be used for a general purpose and for different materials, the
corresponding analyser would have to be calibrated for that particular material.
Some of the commonly used modern analysis techniques are Raman scattering,
microwave acoustic, UV-visible, mass spectrometry and chromatography (see
figure 1.22) [4; 5].
The use of online chemical analysers is very expensive and associated with
various technical difficulties, which is why they are only rarely used across
process industries. Effective and more affordable chemical analysers are
being developed. Meanwhile, most process industries monitor and control
chemical composition in processing plants through well scheduled sampling
and laboratory analysis combined with inferential control. Inferential control
is a control technique that uses the measurements of other process parameters
to infer the measurement of a variable of interest. In this case measurement
of other process parameters is used to infer chemical compositions. As an
example of a simple inferential control system, the temperature of the tray
near the top of a distillation column can be utilised to infer the compositions
of the compounds present at the top of the distillation column. To improve the
accuracy of the control system, numerous measurements of related process
variables can be coupled with an appropriate process mathematical model
to generate the desired composition. Considering the distillation column
mentioned previously, a more complex inferential control system might involve
the measurement of the tray temperature, the knowledge of equilibrium data
and the measurement of the column pressure combined with the application
of an appropriate process modelling to infer the compound compositions at
the top of the distillation column. Regardless of the types of inferential systems,
process results are based on assumptions. Therefore, the systems should be
calibrated on a routine basis using periodic laboratory analysis [5].
Like any living language, the documentation (symbols and their applications)
used to describe modern control systems has been improved constantly over
many years to meet modern challenges while maintaining the primary objective
of efficiently and clearly communicating important points about a specific
process to the trained reader. These documents include [1; 2]:
For the purposes of this module, we will focus mainly on PFDs and P&IDs.
A PFD is a type of diagram usually used in chemical engineering and process
engineering to illustrate the relationships between major components of
chemical plants (see figure 1.23).
P&IDs are the master design documents that use symbols and words to describe
the equipment, piping, instrumentation and control system for a process.
They are also the key to finding additional information about any specific
device or equipment on many other documents relating to the processing
plant. Developing P&IDs for manufacturing plants is a very interactive process
requiring the input of many specialists. These include experts in the fields of
electrical and mechanical equipment design, control systems, piping, and
even civil and structural design. Information is added progressively by each
group of engineers in a standardised way. When properly done, P&IDs serve
as records of the history of the plant design of any manufacturing facility. They
are also a great training tool for process operations. Because P&IDs are primary
coordination documents for design, it is very important to use the appropriate
equipment symbols and instrument tag numbers. An example of a typical
P&ID of a chemical processing plant is illustrated in figure 1.24 below [1; 2].
The instrument tag number consists of a few letters that briefly convey the
function of the device, plus a combination of a number and letters that uniquely
identify the device. Usually these numbers are associated with a particular
control loop (see figure 1.26) [1].
Identification letters on the instrument symbols indicate [1; 2]:
Other connection symbols are hydraulic signal lines, capillary tubing for filled
systems (e.g. remote diaphragm seals) and guided electromagnetic or sonic
signals [1; 2].
Good control design makes it possible to achieve a hierarchy of control
operating objectives of the plant. Process control reduces variation and results
in consistently high product quality that closely approaches the theoretical
manufacturing plant are the devices used to control the essential variables
that enable the conditions of a process to be determined at any time t [9; 10].
In this chapter, I set out the basic principles of process control and instrumentation.
I also presented an overview of the control loop and its elements. We will
talk about these topics in detail in later chapters, and you will gain a more
quantitative understanding of the basic concepts of control systems and their
application [10].
1.6 At the bottom of a tank containing liquid methyl ethyl ketone, a gauge
pressure of 2500 Pa is measured. At that specific location the atmospheric
pressure is equal to 101 325 Pa. Determine the absolute pressure measure
at the bottom of the tank.
1.7 State the functions that the following symbols represent in a chemical
processing plant:
Productivity and the improvement of the quality of end products in most industries
is achieved through the use of advanced control systems adopting complex
control strategies for both non-critical and critical applications. Generally, these
contemporary industrial control systems are made to produce one or more
control actions based on the application implemented. Imagine that you are
sitting in the seating area of your home on a cold winter evening, with a small
fire burning in the fireplace. Because you are feeling very cold, you put another
log on the fire. This is a typical example of a basic control strategy applied
in everyday life. The controlled or process variable (temperature) in the loop
of your control system fell below the set point (the temperature at which you
are comfortable), and you corrected the fluctuation to bring the process back to
the desired condition by taking the action of adding fuel to the fire. Afterwards
the control system remains inert until the temperature again deviates from the
set point (the temperature at which you are comfortable) [1; 2].
This chapter describes the basic types of control strategies commonly used
in industrial control systems. Some basic concepts of control strategies are
presented, and the fundamental principles required to understand more complex
control processes and algorithms that we will be discussing later are provided.
Additional terms and concepts relating to process control are also defined.
After studying all the sections of this chapter and completing the activities and
exercises you should be able to:
• Differentiate between the three tasks necessary for process control to occur:
– Measurement
– Comparison
– Adjustment
Regardless of the type of industrial process, process control loops work in the
same way, requiring that three tasks be carried out. These are:
• measurement
• comparison
• adjustment
The state of the process being controlled is key in order to select the appropriate
control system. There are two main states that can be used to describe a
process [3; 4]:
(a) Steady state of the process: This is a constant state of the process. It does
not vary with time – in other words, all the process variables remain
constant all the time.
(b) Transient state of the process: In this case, the state of the process changes
with time – in other words, the process variables change every time.
There are certain terms that are used consistently in relation to a typical control
system to describe the control mechanism taking place during the operation
of the system. These are summarised in table 2.1 [4; 5]:
Real industrial processing plants always operate in the presence of disturbances.
Consequently, they require the implementation of effective control systems.
Fundamentally, there are two types of control loop: open-loop (feedforward)
control and closed-loop (feedback) control. In rare cases a strategy involving
the combination of both open-loop (feedforward) control and closed-loop
(feedback) control is utilised [4].
(a) Advantages
(1) It is simple, good for slow systems, and reduces control system complexity.
(2) It acts before the effect of the disturbance has been felt by the process.
(3) It does not involve control loop instability.
(b) Disadvantages
Feedback control loop systems are quite effective, as they are based on
the measurement of the process output. The measured variable is often the
process variable that needs to be controlled. Controllers that utilise feedback
mechanisms are classified as closed-loop control systems. The feedback
information is used to decide on the corrective changes that need to be sent
to the control signal driving the plant [7; 8].
There are a large number of closed-loop controls, such as the cruise control
in a car, elevator drives and thermostats. For instance, if your car is going too
fast, the cruise control system temporarily reduces the amount of fuel fed
to the engine. Similarly, a feedback mechanism (thermostat) indicates that
the temperature in a room is above the set point, and this switches the air-
conditioning device on until the room is at the desired temperature [8]. The
block diagram of a basic closed-control loop system is given in figure 2.6.
Positive feedback – this is the situation in which the controller drives the
controlled variable farther away from the set point. The error in this case is
calculated as follows:
(a) Advantages
(b) Disadvantages
(1) It only starts operating once the effect of the disturbance has been
felt by the system.
(2) It can create instability in the control loop.
(3) This kind of system is not suitable for slow systems.
These are among the most elementary types of controllers, and have been in
use for a number of years. They are called ON/OFF control systems because
the final control element has only two states: on and off. As a result, the
controller output is also required to have only two equivalent states (see figure
2.12). They are the simplest and least expensive types of controllers, and they
are often used where cycling can be reduced to an acceptable level. ON/OFF
controllers are quite effective when the overall system has a relatively long
response time. However, this will result in instability if the process under control
has a rapid response time. These types of controllers are sometimes termed
two-step controllers, and they are essentially a switch which is activated by the
error signal entering the process to provide an ON/OFF corrective signal [6; 7].
These controllers exist when all variables in the system are analogue
representations of another variable. You can see the layout of the interior of
a typical analogue controller in figure 2.15 below.
Consider the process illustrated in figure 2.16 below, in which a furnace is used
to control temperature in a house, and assume in this case that the furnace is
operated by means of electricity.
(b) Direct digital control (DDC) – Nowadays computers have become more
reliable and much smaller, and as a result they are taking over the controller
function, which means that the analogue processing loop is no longer
necessary. Figure 2.18 below illustrates the layout of typical micro-devices
used in DDC systems [6].
These are designed to minimise the consequences of emergency situations
typically associated with the escape of hydrocarbons, uncontrolled flooding or
outbreak of fire in hydrocarbon carrying areas or areas which may otherwise
be hazardous. Emergency shutdown equipment for a process control system
consists of an emergency shutdown (ESD) valve and an associated valve
actuator. The controller provides output signals to the ESD valve in the event of
a failure in the process control system. This type of control system is required
in processing plants where a high safety integrity level is required (see figure
2.19) [7].
Process control systems are implemented in industrial plants as part of an
information processing network – they are the centre of communication of the
processing plant. To put it simply, from the various instruments, they gather
information regarding the actual state of the plant process. The information
gathered is then compared with a set of standards incorporated into the system.
This comparison enables the system to produce the appropriate action required
to shift the process towards the desired state [8].
These types of signals are continuous. They are referred to as analogue signals
because the intensity of the communication signal is directly equivalent to the
value that is being conveyed or communicated. Analogue signals can handle
any value that is within the range between their minimum and maximum
acceptable values. Various types of analogue signals are commonly used
as communication signals within control systems in chemical processing plants
[6]. Some of the most popular of these are:
Solution
For the past decade, serial communication has by default increasingly become
the transmitting mode of digital signals in most industrial applications. However,
the parallel mode of digital signal communication is generally much faster than
the serial mode. Because a significantly larger number of wires is required for
the parallel mode, this limits its application from an economic point of view,
and as a result the slower serial communicating approach is more often used
instead [7].
Fieldbus is the generic name given to a number of standards that have been
established since the year 1990. The latest iteration of these standards is
known as Foundation Fieldbus, and it is a standard for complete processing
plant digital communications. This is the largest installed base of all standards.
This standard utilises series of digital lines called buses connected to multiple
transmission devices, and each device attached to a line has an address. These
addresses are used to convey operating instructions to the appropriate device.
A controller obtains a measurement from an instrument on a fieldbus according
to the following protocol [6; 7]:
(a) Initially the controller uses the instrument line address to convey an
instruction requesting measurement from the device.
(b) Afterwards, the instrument takes the requested measurement and finally
transmits the measurement recorded to the controller also using that
line’s address.
All devices connected to the bus lines constantly monitor the bus lines; however,
each one responds only to instructions directed to its address.
Summing point
This comparison element used in feedback control-loop systems can add signals
together. In this case a plus (+) symbol is used to indicate that the device is a
summing element or a “summer” (positive feedback). It can also subtract signals
Summing points can be cascaded together in order to sum more than one
signal at any given point of the control loop [8; 9]. Although summing points
can have more than one input signal for either addition or subtraction, they
can have only one output signal, which is the algebraic summation of the
input signals [9].
The blocks forming the diagrams of control loops are interconnected via signals.
Below are examples of the most common algebraic operations performed on
signals of control loop block diagrams [8; 9]:
(b) Branching
The basic derivable transformation techniques used when deriving the transfer
function of a control loop from its block diagram are summarised as follows [8]:
(a) The combination of blocks in cascade
The transfer function of a single unit process depicted in the block diagram
above can be expressed as follows [11]:
The overall transfer function is obtained as the product of the transfer function
of each individual process unit of the block diagram only if the units are
connected in series [11].
G= G1 G2
Block G1 represents, in the forward pathway, the open-loop gains of the control
system or controller. Block H represents, in the feedback pathway, the gain
of the sensor, transducer or measurement system. The transfer function of the
closed loop above is derived by calculating the output signal in terms of the
input signal. The equations of the block diagram provided can be written as
follows [10; 11]:
The output signal from the process can be determined as: Output = G1 Error
In this case, note that the error signal is also an input to the feedforward block,
G. Therefore, the output signal from the summing point is equal to: Error =
Input – G2 Output
Eliminating the error term from the expression of the output signal from the
system results in the following equation: Output = G1 (Input – G2 Output)
The plus sign (+) in the denominator of the derived transfer function equation
of the closed-loop system indicates negative feedback. A positive feedback
system would be represented by a minus sign (–) in the denominator, and the
equation above would be written as [11]:
When G2 = 1 (unity feedback) and G1 is very large, the equation of the transfer
function approaches unity:
Moreover, in the case of unity feedback and the steady state of the system, a
decrease in the system gain G1 will result in a much slower decrease in the
This simply means that the system is fairly insensitive to variations in the
system gain (G1), which is one of the main advantages of a closed-loop control
system [11].
Afterwards, blocks of the inner loop can be reduced to yield the following
block diagram [11]:
Further application of the algebraic reduction technique to the inner loop
results in the diagram of a single loop with two blocks in series [11].
The above block diagram can further be reduced to a final block diagram
which resembles that of the previous single-loop closed-loop system [11].
Hence, the transfer function of this complex multi-loop system can be expressed
as follows [11]:
The basis of an efficient control system including the feedback and the
feedforward control of process variables is regulatory controls. Effective control
of process variables such as temperature, load level and pressure is vital, as they
have a tremendous impact on the quality of the final product manufactured by
the processing plant. The introduction of regulatory control at each successive
unit operations varies as a function of quality, which accumulates throughout
the manufacturing cycle and is reflected in the overall production cost and
specifications of the final product [1–11].
2.1 Briefly describe the operation of (i) a feedback control system and (ii) a
feedforward control system. List the advantages and disadvantages of
both control strategies.
2.2 Briefly define the following terms:
(a) Control system, control system lag, dead time and capacity
(b) Control algorithm
(c) Process upset, process load, process demand, steady and transient state
(d) Load disturbance and response
(e) Set point and disturbance change
2.3 List the three fundamental tasks required for process control to occur.
2.4 Use block diagram algebra to simplify and determine the overall transfer
functions of the following block diagrams of control systems:
(a)
(b)
(c)
2.6 List and briefly describe the commonly used process plant
digital communication standards.
2.7 List and describe the different transmission approaches of digital signals.
What are the advantages and disadvantages of each?
2.8 List and briefly describe the different type of controller communication
signals.
2.9 How many kinds of analogue signals are commonly used in industrial
plants? Give a brief description of each kind.
We have already spoken about the fundamentals of process control and
instrumentation in chapters 1 and 2 of this study guide. The aim of process
control has been explicitly defined; the basic control loop and its characteristics
elements have been described; the role of instruments in ensuring effective
process control has been highlighted, and finally the symbology used as a
means of communication in engineering drawings has been presented and
discussed. However, very simple types of control loops have been used thus
far [1].
In this chapter, we will talk about the most common strategies and methods
used in complex process control loops. We will also discuss the characteristics
of these techniques, along with various applications. After completing the
chapter, you should be able to:
– Proportional action
– Integral action
– Derivative action
The process error (e), which is the difference between the process variable (PV)
and the desired value or set point (SP), is generated from the reference element.
Based on the magnitude and sign of the error produced, the control component
will generate an appropriate control action in order to bring the process variable
as close as possible to the desired value or set point. The control action can
be initiated in many different ways by the control component of the controller.
Based on the process error calculated by the reference element, the following
are the most common ways to generate the control action [2]:
• mechanically
• electrically
• digitally
• using analogue signal
• with or without auxiliary energy
These various means of generating the controller action do not have any
influence on the type of action produced. They are factors to consider purely
during the selection of the controller device. Based on the roles and properties
of the control mechanisms of industrial controllers, they can be classified as
either (see figure 3.2) [2].
Each type of controller is suitable for meeting the specifications of its corresponding
applications, and has its own particular advantages and disadvantages. Depending
on the type of controller, the control signal can be either continuous or discontinuous
[2].
These regulators derive the energy necessary to help the control system to
generate the appropriate corrective action. Conventional controllers are rugged,
cost effective and popular nowadays for pressure flow, pressure differential and
temperature control. They are fairly effective in applications where the distance
between the point of measurement and the point of change is relatively short.
They can also be very useful in systems where process fluctuations caused by
energy withdrawal are acceptable [2].
These types of controllers are the simplest, and have only two control modes
or control positions: on and off. For this reason, they are sometimes referred
to as two-step controllers. Discrete controllers do not steadily keep the process
variable at the desired set point. They generally maintain the process variable
near the set point in a region known as the dead zone (see figure 3.3). A
household heating system is a typical example of a discrete control system [2].
At the moment that the temperature of the water in the tank reaches the desired
value, the heat supplying device turns off. As soon as the temperature of the
water in the tank starts to fall below the set point, the heating device turns on.
As soon as the water reaches the set point temperature again, the cycle will
begin again. Discrete controllers can be very useful in domestic applications
such as the typical household heating system described above. However, in
industrial process applications, where there is generally a large number of
individual controllers involved, the continuous oscillating nature of the response
of this ON and OFF controller is not desirable [2].
A transducer measures the level of liquid in the tank and transfers the value
of the measurement to a control system whose objective is to ensure that the
level of liquid in the tank is constantly at some pre-set or set point value. The
controller continuously operates according to certain control principles and
algorithms to maintain the level of the liquid in the tank, despite numerous
fluctuations generated by external influences. Therefore, if the flow of the liquid
out of the tank increases, the control system will increase the opening of the
input valve to counteract the effect of the disturbance by increasing the input
flow rate, hence balancing and regulating the level of liquid in the tank [1; 2].
This type of control system is classified as a continuous variable control system,
because both the level of liquid in the tank and the valve opening setting can
vary over a range. Although the controller operates in an OPEN/CLOSED mode
when it comes to the input valve, and this induces the oscillation of the level
of the liquid in the tank as the input valve is constantly opened and closed to
eliminate the effects of disturbances such as output flow variations, there is
still variable regulation [2].
A negative error simply indicates that the process measurement is below the
set point, while a positive error indicates that the measurement is above the
set point [2].
Controller modes, also known as control principles, are the different ways in
which controllers react to error changes in any process. They can also be defined
as the ways in which a control system makes corrections relative to process
deviations. From a control instrumentation point of view, the mode of control
is the way in which a controller changes its output action relative to process
deviations. The three most popular controller modes are the proportional
(P), derivative (D) and integral (I) control modes. Each of these three modes
responds differently to the error. The amplitude of the response produced by
each control mode is adjustable by changing the controller’s inherent settings [3].
The algorithms of the proportional (P), derivative (D) and integral (I) control
modes were developed for the first time by an engineer in charge of the design
of the automatic steering system of a US navy ship. When the captain gave a
human helmsman a bearing to steer, the engineer observed that the human
helmsman considered the following three factors when adjusting the position
of the ship’s wheel [3]:
(1) How far the current bearing was from the desired bearing: Because a
huge difference would lead to a significant change in wheel position,
the corrective action is considered to be proportional to the difference
in bearing.
(2) How long the current bearing had been different from the desired bearing:
If a variation in bearing persisted, then the human helmsman would turn
the wheel further; the corrective action effectively integrated the detected
error.
(3) How quickly the actual bearing was fluctuating: If the actual bearing
varied quickly towards the desired bearing, then the human helmsman
would observe that the time-based derivative was too high, and would
adjust the wheel accordingly.
The proportional control action is the most basic control mode, and is also, in
most cases, the primary driving force in a controller. It changes the controller
output in proportion to the error input signal to the controller. This simply
means that detecting a bigger error will result in a corrective action of higher
amplitude. This is common sense, because large errors will obviously require
corrective actions of greater intensity [3].
This elementary control mode reacts without delay to any deviation from the set
point or to any measured disturbance or load change with the sole purpose of
keeping the process variable (PV) within an acceptable range around a desired
system set point (SP). The adjustable settings for the proportional mode are
expressed as follows [3]:
• proportional gain
• proportional band
where:
The proportional control band (PB) is another way of expressing the same
information. It is basically the change in the input required to produce a full
range of change in the output due to the proportional control action. It is
also referred to in simple terms as the percentage change of the input signal
required to change the output signal from 0% to 100%. The proportional band
answers the following question: “What percentage of change of the controller
input span will cause a 100% change in controller output?”
This adjustable setting of the proportional control mode can also be expressed
mathematically using the following formula [3]:
For 100% full span, the controller gain can be directly converted into the
proportional band using the following mathematical expression [3]:
The relationship between the controller gain and the proportional band is
further demonstrated in figure 3.6 and table 3.1 below [3].
Example 1:
Solution
Example 2:
Solution
=2
Gain
2 = 20%
Every process control loop has a critical or natural frequency. This is the
frequency at which cycling may exist. This critical frequency is determined
by all of the loop components. The control loop gain should not be either
too high or too low. At high proportional band, the loop gain is too high; the
process variable will cycle around the desired set point and cause instability
in the control loop (see figure 3.10). However, the process variable is still not
on set point. When the proportional band is high, the control loop gain is low.
This results in a very stable loop, but an error remains between the process
variable and the desired set point (see figure 3.11) [3; 4].
However, the use of this type of linear control mode has several drawbacks [4]:
• An extremely small controller gain could cause the final control valve not
to fully open or fully close.
• An extremely high controller gain would induce instability in the process
control loop.
• The proportional control action does not return the process control variable
exactly to the desired set point. It does, however, bring the process-controlled
variable back to a value that falls within a well-defined span (proportional
band) around the desired set point.
• Steady-state error (also known as offset) occurs when disturbances occur.
Offset is defined as a sustained error that cannot be eliminated by proportional
control, since it only responds to a change in the magnitude of the error
entering the system.
To fully understand the last disadvantage associated with the use of a proportional
only controller, consider the example of a control system monitoring the level
of a process liquid in a storage tank illustrated in figure 3.5 [4]. A proportional
only controller is used. The level of the process liquid in the storage tank remains
constant if the process liquid flows out of the storage tank at a constant rate. If
the flow of process liquid out of the storage tank begins to increase, the level of
the liquid in the tank will start to drop because of the lack of balance between
the inflow and outflow of the process fluid. This will generate a process error.
As the level of the process liquid drops in the storage tank, the error entering
the proportional controller increases. As a result, a greater controller output
proportional to the error entering the control system is produced.
Subsequently, the final control element, which in this case is the valve controlling
the inflow of the process liquid into the storage tank, opens wider to enable
more liquid to flow into the storage tank. The valve controlling the inflow of
the liquid into the storage tank will continue to open wider as the level of the
process liquid continues to decrease, until a point is reached where the inflow
of process liquid into the storage tank is equal to the outflow of the process
liquid from the storage tank [3; 4].
At this stage the tank level is not at the desired set point, but it remains constant,
meaning that a constant process error is now entering the control system.
Because a constant error enters the control system, the proportional controller
generates a constant controller output as a response to the constant error. This
causes the control valve to also hold its position and the system now remains
balanced, although the tank level remains below the desired set point. This
residual sustained error is called the offset, and it cannot be eliminated by the
proportional controller [3; 4].
Under proportional only control, the offset can only be eliminated manually.
This is done by an operator who manually changes the bias on the controller
output to reduce the offset to zero. Generally, the operator has to switch the
controller to manual mode first, in order to change the controller’s settings
manually until the steady-state error is reduced to zero. Afterwards the operator
can return the controller to automatic mode. This procedure is known as the
manual resetting of the proportional controller [3; 4].
For how long has the error existed in the controlled process? The controller
output action from the integral mode is directly dependent on the duration
of the error. In this control mode the control system has the unique ability to
return the process variable to the exact desired set point by acting in such a
way that the control effort produced is proportional to the integral of the error.
The integral only controller in this case behaves as an integrator [4].
The integral control action is basically used to fully remediate system deviations
at any operating point. The integral only controller will generate an output signal
causing the manipulated variable to change as long as the error is non-zero.
The control process is considered balanced either when the desired set point
and the controlled variable are equally large, or when the manipulated variable
reaches its system-specific limit value (i.e., maximum allowable value) [3; 4].
The development of the automatic reset or the integral control mode, as it is
currently known, was inspired by the need to manually reset proportional only
controllers. As long as the process variable is not equal to the desired set point
(system error present), the integral control mode will continuously increase or
decrease the controller’s output action in order to reduce the system error to
the greatest extent possible. After a sufficient period of time, the action of the
integral only controller will drive the output far enough so as to completely
eliminate the system error (see figure 3.12) [4].
A fast controller output response is obtained when the system error is large, and
a slower output action is generated for a smaller system error. The controller’s
integral time variable (tI) sets, for a specific system error, the speed of the
integral action. A long integral time is characterised by a large value of tI and
results in a slow controller integral action. By contrast, a short integral time is
represented by a small value of tI, resulting in a fast integral action [4].
The integral time setting is an essential factor of the integral only controller.
If it is set too long, the controller will be sluggish. If it is set too short, the
process control loop will begin to oscillate and become unstable. The time
interval required to execute the controller algorithm is sometimes known as
the sampling time or scan time. Integral only controllers use integral time in
minutes as the standard unit of measure for integral control. Other controllers
use integral time in seconds as the standard unit of measure for integral control.
In the algorithm for the integral only controller, the integral gain is defined as
the repeats per minute or repeats per second (see table 3.1) [3; 4].
Mathematically the actions of the integral only controller are expressed by the
equation below: the value of the manipulated variable is changed proportionally
to the integral of the system error e [4].
where K I is the integral action coefficient and I(0) is the bias value.
From the mathematical expression above it is then clear that the magnitude of
the increment or decrement of the manipulated variable is directly dependent on
the system error e and the integral time tI (the reciprocal of the integral action
coefficient KI; in other words, a long integral time is equivalent to a small integral-
action coefficient). The higher the integral action coefficient K I, the greater the
integral action of an integral only controller; hence the lower the integral time
value tI. Conversely, the lower the integral action coefficient K I, the weaker the
action of the integral only controller; therefore, the higher the value of the integral
time tI [4].
In this control scheme, the purpose of the integral action is to return the
process variable to the desired set point. The integral only controller achieves
this by continuously repeating the proportional mode correction action for
as long as the error continues to exist in the system. Consequently, except
in some electronic controller devices, the integral or reset control algorithm
is usually combined with the proportional control algorithm. The controller
integral or reset action is sometimes characterised in terms of either repeats
per minute (how many times the proportional action is repeated each minute)
or minutes per repeat (how many minutes are required for one repeat to occur)
[4; 5].
(b) Analysis of integral control action in close loop
Process control systems involving a closed loop in the integral or reset algorithm
add one more gain component to the control loop. The faster the reset or integral
action, the greater the gain. Consider the example illustrated in figure 3.14. The
control loop appears to be stable because at the control loop critical frequency,
the total value of the control loop gain is not too high. In this example you
can see that the process variable reaches set point due to the reset action [5].
In the case where the value of the total control loop gain is too high at the
critical frequency of the control loop, the controller reset action will be too
fast. As a result, the process variable will be cycling around the desired set
point (see figure 3.15) [5].
(c) Windup
where
• At high integral time values the integral only controller generates a sluggish
output response [6].
• At small integral time the control loop tends to oscillate, which may induce
instability in the process control loop [6].
• Integral saturation/reset windup; in a real system there are lowest and
highest limits on the range of any manipulation that can be applied on
a process final control element. For example, a control valve cannot go
beyond fully closed or fully open – in other words, the valve cannot be
more open than fully open or more closed than fully closed. However, this
cannot be detected by an integral only controller. As long as the system
error is detected, the controller will continue to integrate the error even
though the controller output has reached its lowest or highest limits. This
state of the integral only controller is known as output saturation. When
the system error magnitude reduces, miscalculations occur in the controller.
The large error integral that has been built up will hold the controller output
against the limit for a considerable period of time. As a result, the measured
value significantly overshoots the desired set point. This behaviour of the
controller is termed integral saturation or (reset) windup. In extreme cases
reset windup can drive the controller output to oscillate between its lowest
and highest limits [6].
Example 1:
Solution
Consequently, the derivative only controller is not useful at all when it comes to
reducing errors in a controlled system, and is never used alone. The derivative
mode is sometimes called the rate, and has an adjustable setting called derivative
time (tD). The larger the derivative time setting, the more derivative action is
produced. Two units of measurement are used for the derivative setting time
of a derivative only controller, namely minutes and seconds [6].
Basically, the derivative only controller generates a corrective output change
that is proportional to the rate of change of the error detected in the controlled
process. If the detected error in the controlled process increases rapidly, a
large and positive derivative of the error will be calculated. In this case the
derivative algorithm will make a large positive change in the control action.
This will generate an effort of great magnitude that will then attempt to reduce
the future error detected in the controlled process [5; 6].
On the other hand, if the error detected in the system is decreasing rapidly, a
large and negative change will be implemented in the control action by the
derivative algorithm of the error. This could probably be attributed to an excess
control action that has already been applied, causing the measured value of
the process variable to significantly overshoot the desired set point. With the
large negative derivative value of the error, the derivative action generated will
induce a large negative change in the control action, with the main purpose
of reducing the rate of approach of the desired set point value [6].
For instance, in the control system of temperatures in large tanks, the noise
frequency is generally a multiple of the unit hertz, which is different from the
noise of the vessel real time constants of several hours. Therefore, it is possible
to completely eliminate the noise without really affecting the process signal.
However, in faster control systems such as flow control, the noise and real
time measurement frequencies change at relatively the same rate. As a result,
it is not possible to completely remove the noise without seriously damaging
the process measurement signal. In this situation, the use of derivative control
action is not recommended [6].
To study the effect of the rate of the derivative action, a time setting of 1
minute is considered. Initially at time t = 0, a fairly large controller response is
obtained, inducing a high output spike as a result of the rate of the derivative
action (see figure 3.18). It is important at this stage to remember that the change
in the output of the controller caused by the rate of the derivative action is
directly dependent on the rate at which the system error changes, which is in
a step nearly infinite [6].
(a)
(b)
However, adding the derivative action rate only is not sufficient to cause the
process variable to match the desired set point. Now let’s imagine that the
derivative action setting time is increased to 10 minutes. This implies that the
controller gain is now much higher. As a result, the process variable will not
settle at the exact desired set point, and will start cycling. This is why it is
imperative to add a reset action, in order to bring the process variable back
to the exact desired set point (see figure 3.19) [6; 7].
Proportional + integral controllers are by far the most common type of feedback
controllers utilised in the chemical process industry. The combination of
both control modes is obtained simply by connecting one proportional only
controller and one integral only controller in parallel, in that way generating
a proportional + integral only algorithm. The total output of the controller is
the sum of the output of the two individual control models (proportional +
integral). The proportional + integral only algorithm can be mathematically
expressed by the following expression [7]:
In this combined control algorithm, the controller gain affects both the
proportional and integral components of the process controller. The integral
time tI is the adjustable setting in this case when it is necessary to change the
relative balance between the two control modes. The dynamic behaviour of
the control loop is characterised by the proportional-action coefficient KP and
the reset/integral time tI (see figure 3.20). In the proportional + integral control
algorithm, the proportional action generates a fast and immediate response
to errors detected in the system and the manipulated variable is promptly
adjusted accordingly. P(0) is the bias or adjustable value of the controller [7].
Meanwhile, the integral action starts to gain influence only after some time
and eliminates any remaining steady-state error present in the system. In
proportional + integral controllers, the reset time represents the time required
until the integral component of the controller produces a control amplitude
that is equal to the one generated by the proportional component from the
beginning. Similarly to the integral only controller, the reset or integral time in
a proportional + integral controller must be reduced in order to generate an
amplified integral action component of the combined modes controller [7].
PID controllers are used to process control loops with second- or higher-order
systems that require fast stabilisation and do not tolerate residual steady-state
error. The controller output response in PID controllers is advantageous in
higher-order controlled systems made up of components storing large amounts
of energy. This is because these systems require very rapid control action and
do not tolerate steady-state error [7].
Of the types of controllers we have already discussed, the PID controller exhibits
the most sophisticated control response. The controlled variable reaches the
desired set point promptly and stabilises within a very short period of time,
and oscillation occurs only slightly about the set point. The three control
parameters, namely proportional gain, integral time constant and derivative time
constant, offer tremendous versatility in terms of adjusting the control response
in accordance with amplitude and control dynamics (see figure 3.22) [7].
(a)
(b)
In some controllers using the PID algorithm, a number of both minor and
significant tweaks need to be made. The derivative action can be tailored to
be based on the derivative of the measured process variable instead of the
system error. This overcomes the issue associated with the standard derivative
control algorithm (derivative of system error) in situations where a step change
in the desired set point is introduced (infinite error derivative!) [7].
The proportional control action can also be tailored. Sometimes use of the
square of the error is considered. However, it significantly increases the change
when large system errors are involved, and reduces the proportional control
action when dealing with smaller system errors. As a result, this generates a
non-linear control algorithm that can be quite complex to tune [7].
To successfully implement the classical PID algorithm in digital control systems,
some alterations are required. The operation of digital control systems is
based on sampling the process. This simply means that the measurements are
numbers representing snapshots at precise time intervals of the process state.
The analogue PID algorithm can be converted into two digital equivalents [8]:
(a) The velocity algorithm – this is the most commonly utilised digital
equivalent of the PID analogue algorithm. It is represented by the following
mathematical expression [8]:
where
COk and COk-1 = controller output at the current kth and (k-1)th samples
respectively
ek and ek-1 = system error at current kth and (k-1)th samples respectively
ts
= sample interval time between successive snapshots for the controller
In any industrial process, the ultimate goal is to generate a final product that
meets the desired specifications. Consequently, various process control loops
are implemented within the process to ensure that it operates in accordance
with the design criteria in order to convey the desired characteristics to the
end product. The evaluation of the performance of a process control system is
based entirely on whether or not the control delivers a product that is within
design specifications. The entire process will be pointless if the desired quality
of the end product is not achieved [9].
In brief, assuming that in any real industrial situation the control system
always delivers a final product that meets the design specifications, it is
nevertheless essential to understand how well the system performs the task.
It is also fundamental to study the fluctuations in process parameters and the
percentage of rejected production batches associated with routine operations.
The performance of a control system is evaluated by measuring the quality of
the controller’s response to system disturbances and then analysing how the
control loop characteristics influence these measurements. There is no absolute
conclusion when analysing the performance of a control system, because a
control system that is considered suitable for one industrial process might be
unsatisfactory for another [9].
Because a typical control system has the main purpose of generating regulating
actions in order to prevent disturbances in the system from causing significant
fluctuation of the controlled variable from the desired set point value, the
quality of the process-control system can be defined by the extent to which
the fluctuations that are induced by the disturbances are minimised.
Three basic kinds of disturbances can usually occur in a typical control system.
These are:
Universally, the best control quality obtained from any system is referred to as
optimum control. When disturbances are introduced into the process, the most
negative influence involves the deviation of the process-controlled variable from
either the process load or the desired set point. Therefore, the main purpose
of setting the control system is the provision of optimum control. The control
would not necessarily be perfect, but should be as good as it can be. For this
reason, the ability of the system to reach optimum control can represent the
control quality of this system. The following three effects resulting from set
point and process load changes can be used to define the control quality of
the system [9]:
• stability
• minimum deviation
• minimum duration
The quality of control provided by a control system is arrived at through the
evaluation of stability, minimum deviation, and minimum duration following
a disturbance of the dynamic controlled variable [9].
(c) Stability
(a) Overdamped
In this case, after a disturbance is introduced into the process, the deviation
approaches the desired set point value gradually without oscillations. However,
minimum duration and minimum deviation are not successfully achieved. This
type of control response is considered safe, as it ensures that no instabilities
occur in the process-control loop and that rare cases of maximum deviation
never take place [8; 9].
(c) Underdamped
Although controllers are meant to operate successfully for quite a while after
being properly tuned, it is very common for their effectiveness to decrease
with time. Phenomena such as catalyst degradation in reactors or fouling
can completely modify the originality of the process. As a result, the gains
and dynamic parameters of the process controller response may no longer be
suitable. It will then be necessary to change the controller’s tuning parameters in
order for them to be appropriate for the new process conditions. Furthermore,
other factors such as change in production rate, change in final product grade
or change in properties of raw material(s) can also completely redefine process
conditions [8; 9].
These changes in process conditions would initially affect the gains and dynamic
parameters of the controller and reduce control system performance gradually.
However, the effects will be noticeable only at high intensity. For this reason,
modern scanning control and data acquisition (SCADA) systems are designed
in such a manner that they are able to monitor the performance of the control
loop in a chemical plant and generate warning alerts when potential problems
arise. SCADA systems generally monitor the following features of typical control
loops implemented in most manufacturing plants [8; 9]:
• The length of time the loop remains in automatic mode. When the loop
remains in manual mode for a fairly long time, this is a clear indication that
the performance of the control loop is unsatisfactory [9].
• All process controllers can potentially reach saturation. Saturation happens
when the controller output response reaches the system’s design limit. As
soon as the controller is saturated, it is no longer able to monitor the process.
Consequently, if the controller remains accurate for an extended period
of time, the control response action is no longer accurate for the specific
process. In this case it is possible that the final control element (valve) may
need cleaning or resizing [9].
• The number of oscillations in the output response of the controller can be
determined using a standard unit of measurement known as the oscillation
index. Significant changes in the oscillation index are a straightforward
indication that some disturbances are driving the control loop out of tune [9].
• Various evaluation techniques, such as standard deviation calculation, can
be used to measure the inconsistency of the process manipulation and
controlled variable over an estimated period of time. Because any process
is generally assumed to operate at approximately constant conditions, any
changeability of the controlled variable is a strong indication of the presence
of disturbances in the process-control loop [9].
• Process steady time period can also assist when evaluating the consistency
of the controlled variable. However, this measuring method is effective
only for processes operating at roughly constant conditions over time [9].
• Recording the activities of plant operators could also be considered as a
technique for evaluating the performance of the process-control loop. If the
process set point has been adjusted multiple times and the controller has
been switched over from automatic mode to manual mode, the increasing
attention given to the control loop is a clear suggestion of the existence of
potential disturbances in the process-control loop [9].
In theory it is often assumed that the loop response is stable for the application
of process control principles. In practice, a great deal of expertise in multiple
engineering fields is applied in the design and development of process-control
loops to achieve this stability [8].
(a) Source of instability – Occasionally, the transfer function of the process-
control loop is such that feedback to the error summer actually increases the
system error because of the phase shift and the gain of the control loop. If there is
any frequency for which this condition exists, then oscillations will undoubtedly
start and grow at that frequency. The control system is therefore unstable, and
something like random noise will eventually maintain the control system into
growing oscillation. Consequently, in the design of a process-control system,
emphasis should be placed on its ability to regulate the process-controlled
variable without instability occurring in the control loop [8].
This simply means that at the frequency at which the system’s gain is greater
than one and the phase shift is –180°, the system is considered unstable.
From this reasoning, in order to determine when the control loop is stable,
the following two basic rules have been developed [8; 9]:
• A process control system is stable if and only if the system gain is less than
one (unity) at the frequency for which the phase shift (lag) is –180°.
• A process control system is stable if the phase shift (lag) is more positive
than –180° at the frequency for which the gain is one (unity).
CE = 1 + G(s)K
where
In practice, the process controllers are tuned to determine the following [10]:
(1) It is quite important to define the direction of the control action. The
direction of the control action is usually directly dependent on the process
gain and the type of final control valve. Regardless, the control switch in
the controller in place should be set appropriately (in either the “direct”
or “reverse” position).
(2) Of the three available control modes, the most useful to the particular
process needs to be selected. The simplest choice would be a proportional
control action; however, there is an issue of residual offset. The residual
offset issue can be overcome with a PI controller, but this controller is
rather complex to tune. The best control results can be obtained easily
with the PID controller. However, a noise filtering system should be
implemented. If derivative control action is a component of the controller,
then extreme care needs to be taken with regard to the system noise
before tuning takes place.
(3) The parameters of the controller need to be appropriately adapted to the
controlled process. Low proportional gain usually results in high process
gain. An integral time constant of a high value will generate long time
constants in the controlled process. A controller is generally tuned by
means of the trial-and-error method.
Regardless of the type of controller, a tuning approach that is commonly used
is a method first proposed by Ziegler and Nichols, known as the ultimate
tuning technique. It makes possible simple tuning that can be applied in many
controlled systems that allow sustained oscillation of the controlled variable.
During tuning using the Ziegler-Nichols method, the values of the proportional,
integral and derivative parameters of the controller are determined from the
ultimate gain and the ultimate period of the process control loop. To determine
these ultimate parameters, the closed control loop is disturbed; the disturbance
response of the system is investigated, and the values of the ultimate constants
are extracted [9; 10].
Basically, the controller must first be switched to automatic mode and set up
for proportional only control. After this, a series of slight set point changes
are introduced into the system and the control loop response is examined.
The primary objective is to obtain a sustained oscillation as the control loop
response by fluctuating the controller gain. If a set point change causes the
oscillation of the loop’s response to disappear, the controller gain should be
increased. As new oscillations start growing (meaning that the control loop
is starting to be unstable), the controller gain should be decreased rapidly.
As soon as sustained oscillations are achieved, the controller gain is noted as
“ultimate gain” and the period of oscillation can also be measured as “ultimate
period”. The steps below should be carefully followed when applying the
Ziegler-Nichols tuning procedure [9; 10]:
• At the controller, set KP and tD to the lowest value and tI to the highest value
because it has the smallest possible influence on the controller output.
• Adjust the controlled system manually to the desired set point and start up
the process-control loop.
• Set the manipulated variable of the controller to the manually adjusted value
and switch the controller to automatic operating mode.
• Increase the value of the proportional gain until the point of instability
is reached and sustained oscillations occur in the control loop (constant
amplitude limit cycle takes place).
• Determine the ultimate time period tu and the ultimate control loop gain
Ku from the constant amplitude limit cycle. The ultimate time period tu is
obtained by determining the time span for one full oscillation amplitude and,
when necessary, by taking the time of several oscillations and calculating
their average.
• Most processes have slower dynamics and it usually takes longer to obtain
substantial oscillation patterns for use in evaluating whether they are growing,
shrinking, or steady and consistent.
• All chemical processes are always subject to random disturbances, which
will after a while definitely interfere with the control process.
• Because the technique is based mostly on inducing instability in the control
process, without proper monitoring it can cause serious problems in the
control loop.
When we are dealing with an open-loop control system, the information for
tuning can be obtained by conducting a step test. This is achieved by switching
the controller over to manual mode and inducing a small step change in the
controller’s output. This results in a controller output response from which
the process gain kp, process time constant and process dead time td can be
extracted. Therefore, the controller’s parameters can be calculated using the
mathematical expressions set out in table 3.5 [9; 10].
tI =
where Kc = controller gain
tI = integral time constant
= lambda
Kp = process gain
= process time constant
td = process dead time
The lambda tuning method has the following advantages [9; 10]:
• Because of the slow set point response, the changes in set point have a
negligible effect on other control loops in the process. This feature of the
lambda tuning technique has made it very popular in the paper industry.
• With the lambda tuning method it is possible to synchronise multiple control
loops in order to obtain similar closed-loop responses.
• By allocating smaller values of to important control loops, precedence
can be given to them.
• The lambda tuning technique is robust and tolerates fairly poor process
testing and model fitting.
However, various drawbacks are also associated with the application of this
tuning procedure [9; 10]:
Like the manual tuning methods used in closed loops and open loops, the
mathematical expressions used to calculate controller parameters from response
constants are not guaranteed to give the best results in all situations. In process
industries, interacting systems (systems with multiple manipulations and
controlled variables) are very common. The various manipulations in these
systems can affect the numerous controlled variables. Therefore, the changes
in controller behaviour will depend on whether the controller is in automatic
or manual mode. Unfortunately, automatic tuning does not take such situations
into consideration [9; 10].
Special considerations are required for derivative control. For the adjustment
of the controller gain and integral time constant in step 4, the map below (see
figure 3.24) could be quite useful [9].
From the given tuning map, you can see clearly that the ideal tuning is located
at the centre of the map. This region of the map is characterised by fast rise
time, settling time and quarter decay ratio. At the bottom left of the map
the controller gain is too low, and as a result the sudden change in output
response to set point change is small. Meanwhile, the integral time is too long
– in other words, it takes too long for the controlled variable to rise to the set
point. The controller gain at the top left of the map is too high. This indicates
that instability has been introduced and that the process has been driven into
sustained oscillations. However, the integral time constant is still too long, and
so the centre of the oscillations takes a long time to centre around the new
desired set point. The right side of the tuning map can be clearly interpreted [9].
In practice, chemical plants are complicated systems, usually with numerous
control loops operating simultaneously. The selection of an effective controller
has a significant influence on the successful operation of the control system.
Therefore, the suitability of a certain type of controller must be thoroughly
investigated to accommodate the process it controls [1–4].
Usually, most process control tasks can be achieved with this type of controller.
However, when the system requires as fast a speed of response from the
controller as possible despite the presence of significant lag, a proportional +
integral + derivative controller will be more suitable. Proportional + integral +
derivative controllers are quite useful when it is necessary to eliminate significant
lag in the controlled system as quickly as possible. The derivative component of
the controller improves the control dynamics obtained with just the proportional
+ integral controller, while the integral component completely eliminates
any residual steady-state errors in the system. The operating properties and
characteristic equation of the various controllers are summarised in tables 3.4
and 3.5 below [8–10].
The control system is the central point of any chemical plant. It provides sensing,
analysis, and control of the various processes taking place in the plant. When
the control system is properly tuned, the effects of process disturbances are
reduced, efficiency is maximised, operating costs are minimised, and production
rates are increased. Controller tuning refers to the process of selecting suitable
tuning parameters to ensure the best controller output response [9; 10]. When
the tuning procedure is too slow, the controller’s output response becomes
almost inactive, making the controller unable to handle upsets, and the system
takes longer to reach the desired set point. Conversely, if the tuning process is
too aggressive, the control loop overshoots and becomes unstable. Controller
tuning can be achieved rapidly and accurately using efficient techniques.
However, in practice engineers often believe that controller tuning is “part art,
part science”. For this reason, many engineers and technicians combine proven
scientific tuning methods to the “tune by feel” conventional practice [9; 10].
– State the typical control system used and explain why it is used
– Identify and explain considerations for equipment selection (e.g., speed,
noise)
– Identify typical equipment requirements
– Draw the schematic diagram of the process control loop using ISA
symbology
– Cascade
– Batch
– Ratio
– Selective
– Fuzzy
Typical process control loops can be divided into two main categories: single
variable loops and multiple variable loops [1; 2].
The single variable control loop is the most elementary process-control loop.
The operation of the control loop is based on monitoring and maintaining
control of a specific process variable at the desired set point by manipulating a
controlling variable, irrespective of the other process parameters. This family of
process-control loops can also be divided into various subcategories, depending
on the type of process single variable [1; 2].
This is attributed to the fact that with the change in the amount of process fluid
in the tank or the flow rate of the process fluid into the tank, the temperature
system should now adjust to the new conditions by readjusting the rate of
heat input to accommodate the load change and return the temperature to the
desired set point value. For this reason, the two loops are said to be interactive
with each other. This simply means that any sort of instability in the flow-
control loop would induce instability in the temperature system because of
this interaction between the two loops. In practice, almost all processes where
numerous variables are under control present control loops that interact [2].
(c) Compound variable – This refers to the situation in which the single
process control loop is used to monitor and control the relationship between
two or more process variables. In the case where measurements from two
sensors represent the input to the controller of a process control system, a
signal conditioning system can be used to scale the measurements from the
two sensors and add them before their input into the process controller for
evaluation and generation of the corrective action. These systems can become
quite complex to analyse. A good illustration of this type of control system is
in a section of a manufacturing plant where a chemical reaction occurs and
it is necessary to monitor the ratio of two reactants [1; 2].
The procedure usually consists in letting one reactant flow into the reactor
without any adjustment; however, the flow rate should be measured at all
time. This allows the adjustment of the flow rate of the second reactant after
its measurement in order to constantly obtain the desired ratio of reactants (set
point) (see figure 4.3). The flow rate of the reactant flowing uncontrollably is
measured and added, with appropriate scaling, to the measurement of the flow
rate of the controlled reactant and the resulting signal is sent to the controller,
which reacts by adjusting the control valve of the controlled reactant input
line [1; 2].
(d) Examples of single control loops
Modern flow transmitters are equipped with filters with a damping function
that eliminates signal noises. In some cases, the filters are installed between
the transmitter and the control system. The temperature of the process fluid
has a direct influence on its density, and so the temperature of the process
fluid is also measured when flow measurements are taken and fluctuations in
temperature readings are compensated for during flow calculations [2].
Changing the temperature of a process fluid takes a fairly long time. Consequently,
temperature-feedback control loops are regarded as quite slow. To increase
the speed of the temperature-control loop response, feedforward control
strategies are usually preferred. Although temperature could be directly wired
to the input interface of the system controller in some cases, the control system
usually involves temperature transmitters and controllers (see figure 4.6).
Thermocouples or resistance temperature detectors (RTDs) are the temperature
sensors that are typically used. The final control element for a temperature-
control loop is generally the valve of the fuel line to a burner or a valve to a
specific type of heat exchanger. A cool process fluid can also be added to the
process to maintain temperature (cooling operation) [2].
(iv) Pressure-control loops
The primary controller basically manipulates the set point value of the secondary
controller in order to maintain the primary process controlled variable, which
in this case is the temperature of the process fluid in the tank at the desired set
point value. The multi-variable control system described previously assumes the
controlled variables to be predetermined, which is not in fact the case. In real
plants, the identification of the process variables to be controlled, especially
when we are dealing with multi-variable control systems, is one of the first
tasks of the control system designer. In chemical engineering the degree of
freedom in a system is defined as all the possible ways the system can be
tuned without violating any design constraint. Consequently, the number of
variables that could be controlled is obviously limited by the existing degree
of freedom (DOF) in the system under control. The fundamental definition of
DOF encountered when learning the basics and fundamentals of chemical
engineering is represented mathematically by the following equation [2; 3]:
In process control the disturbances to the process, which are external factors
that cannot be controlled, represent additional limitations to the DOF of the
system. In this case, the DOF can be expressed mathematically as follows [2; 3]:
The tuning process for multiple variable loops is quite different from the standard
tuning procedure for a single control loop. However, it consists in tuning the
secondary loop before tuning the primary loop, because alterations made to
the secondary loop have an immediate effect on the primary loop, whereas
adjustments made to the primary loop have no influence on the secondary loop
tuning. The primary process control loop is referred to as the master control
loop, and the secondary process control loop is known as the slave loop. For
this reason, you need to apply a very efficient technique when combining the
multiple disturbances, manipulation and controlled outputs in a multi-variable
control loop. Unfortunately, no universal method to develop multi-variable
control systems with outstanding performance has been reported so far.
The most commonly used technique involves eliminating the worst control
loop combinations using the following rules of thumb [3]:
We have already discussed the fact that in a single control loop, an operator
inputs a set point into the controller and, based on the set point, a response
is generated by the controller in order to drive the final control element
appropriately. Meanwhile, a cascade control system involves two or more
controllers. In a cascade loop, the output response generated by one controller
represents the set point of another controller. The controller generating the
set point is referred to as the primary, master or outer controller, while the
controller obtaining the driven set point is referred to as the secondary, slave
or inner controller. Let’s consider the classic example of a level-control system.
In a single loop control, a level transmitter sends a signal to the controller
that compares it with its set point before generating an appropriate signal that
will drive the final control element (a control valve) to keep the level at its set
point (refer to figure 4.4) [5].
However, the cascade control arrangement for the same process consists
of a primary controller (level controller) that generates an output response
representing the set point of a slave controller (flow controller), which will then
adjust the control valve so that the flow corresponds to the set point driven by
the level controller in order to keep the level of the process fluid at its design
set point (see figure 4.12) [5].
The main advantage of the cascade control arrangement is its ability to isolate
the response of the slow control loop from non-linearities in the final control
element. In the level control scenario above, the faster flow control loop is
utilised to prevent or/and minimise the control valve problems that could arise as
a result of the relatively slow level control loop. For instance, the control valve
might have a static friction problem. This type of valve problem arises when
the internals of the valve are sticky, and it usually causes the valve to stick in
one position. This can lead to the level-control loop continuously oscillating
in a stick–slip cycle with slow periods, which is very likely to have a negative
effect on the process downstream. The problem of the sticky control valve
will also cause the fast flow control loop to oscillate. However, because of
the inherently fast dynamic behaviour of a well-tuned flow control loop, the
oscillation will be much faster and could be attenuated by the downstream
process without generating much of a negative effect on it [5].
Another valve crisis that can occur relates to non-linear flow characteristics of
the valve. This makes the control loop driving the valve sluggish or unstable,
and so this control loop must be detuned as a way to maintain stability across
the available range of flow rates. If the faulty valve was driven by the level
controller, the detuning process required to maintain stability would probably
lead to very poor level control. Fortunately, in a cascade control loop the
valve is generally driven by the flow controller, which in this case will be
detuned to maintain stability. Consequently, very poor flow control will be
obtained. However, because the flow-control loop is dynamically much faster
than the level-control loop, the level-control loop will barely be affected
negatively. Because of these characteristics of the cascade control system,
it is recommended for use where processes that are dynamically slow, such
as composition, humidity, level and temperature, have to be controlled through
the manipulation of dynamically fast processes such as liquid and gas-flow [5].
Three main drawbacks are generally associated with the use of the cascade
control arrangement. The first disadvantage involves the need for additional
measurement such as flow rate in order for the control strategy to work. The
second limitation is the need to tune an additional controller, and the final
drawback relates to the fact that the engineer and operators have to deal with
a more complex control technique. So, before deciding whether or not this
control system should be implemented, engineers need to assess these various
disadvantages against the predicted improvement that the control system
will provide. For example, the cascade control arrangement is beneficial
only when the inner loop is dynamically much faster than the outer loop. If
the dynamics of the inner loop are not at least three time faster than those
of the outer loop, the improved performance obtained will not be worth the
added complexity of the system. Furthermore, when the inner loop in the
cascade control arrangement is not that much faster than the outer loop, there
is a significant risk of interaction between the two loops, and this could result
in major instability in the system. The situation is worsened when the inner
loop is tuned quite violently [5].
When tuning a cascade arrangement, it is best to tune the innermost loop first.
After this tuning process is complete, the loop should be placed in external
set point mode, also known as cascade control mode. The next step involves
tuning the loop driving the set point of the previous loop. When tuning control
loops in a cascade arrangement, use of the quarter-amplitude-damping tuning
techniques such as the unmodified Ziegler-Nichols or the Cohen-Coon tuning
techniques is not recommended. This is because of the risk of instability if the
process dynamics of the inner and outer loops are similar [5].
This type of control system involves a controller that receives measurement input
from a flow reading instrument on an unregulated flow to a specific process
unit. The controller performs the relevant calculations in terms of the ratio
of the process raw materials. Afterwards an output signal from the controller
carrying the desired set point is sent to another controller that adjusts the flow
of the second fluid into the process unit so that the desired proportion of the
second fluid stream is added to the unit operation [5; 6].
(b) Ratio relay controller – This ratio control method is basically similar to
the flow fraction controller technique; however, the control algorithm entails
measuring one flow rate, for instance d and using the measurement signal
obtained to compute what the flow rate of the other process variable (d in
this case) should be to maintain the design ratio R constant. The output of the
ratio relay, which is equal to usp = d/R, is then utilised as the set point for the
controller. Once the controller receives the measurement signal of the flow
rate of the other process variable u, it compares it with the given set point usp
= d/R and adjusts the generated output appropriately to keep the flow of the
manipulated stream at the desired set point, hence keeping the ratio R constant.
Sophisticated ratio control systems have become increasingly popular. The
control algorithm of these control designs can be based either on feedback
control of the load-stream flow rate or the analysis of the composition of the
mixed stream, because it could have a feedback effect on the constant ratio
R of the ratio relay [6].
Because the control algorithm of the system calculates the actual ratio of process
variables, some of the advantageous key features of ratio control systems are [6]:
However, the major disadvantage associated with the use of this control is the
fact that a divider element must be included in the control loop, and this causes
the process gain to fluctuate in a non-linear way. Because of this significant
drawback it is preferable to implement the ratio relay control technique in
most cases [6].
•
•
•
•
•
The final control operation converts the control signal produced by the controller
into proportional action on the process itself. For instance, in order to convert
a characteristic 4–20 mA control signal generated to rectify the large flow rate
of a system, some final adjustments would certainly be required. It would
be necessary to generate enough power to actuate changing the state of the
controlled-process state and to convert the control signal (4–20 mA). The
following diagram illustrates the various stages involved in the final control
operation and the sequencing of the operation [7; 8].
From the control signal to the process, each stage plays a fundamental role in
efficiently applying the corrective action generated by the controller in order
to eliminate the error detected in the process [8].
• Pneumatic actuators
• Electrical actuators such as stepper motors, relays and solenoids
• Hydraulic actuators
The control element (usually a valve) is a designed integral part of the process
itself and it has a direct effect on the process variable. For instance, if the flow
of a process stream is to be monitored, a suitable control element would be a
valve to be installed directly within the flow system of the process plant. In the
case where the temperature of a certain process is the variable to be controlled,
it is necessary to implement an appropriate mechanism in the process so that
the control element directly regulating the temperature will be involved in the
control system algorithm. The control element could be a heater or a cooler,
or a combination of both a heater and cooler that is electrically operated by
pneumatic valves or relays [8].
Any type of valve can be manufactured with different trim designs, and each
design is meant to regulate and “shape” the flow according to its specific
intrinsic characteristics. The mechanical and geometry characteristics of these
various flow control modes are discussed later in the chapter. However the
three most common ways in which the valve opens, in other words, the three
most common ways in which it strokes or travels according to the flow of the
process stream to be controlled, are summarised in table 4.1 below [8].
Now that we have briefly discussed the most common types of valve control,
we need to talk about the various types of valves commonly utilised in the
field of process control. There is an extremely wide variety of categories of
valve available for implementation in manufacturing systems. However, the
most commonly used ones in manufacturing processes are those summarised
in table 4.2 below [8].
Some more information about these valves and their various applications is
summarised in table 4.3 below [8].
In most chemical processing plants, the globe valve is the type of valve
most commonly used to regulate the flow of process fluids in pipelines. It
generally consists of a moveable disk-shaped element and a stationary ring seat
in a spherical body. Like ball valves, where the plug is moved in and out of
the globe, globe valves can also have a stem or a cage (see figure 4.14) [7; 8].
The plug is generally designed in such a way that the flow of process fluids can
be properly controlled. Potential leakages through the valve can be prevented
by means of a seal. These valves have design features such as a cover that can
be easily removed, exposing the plug and seal and making it easy to maintain
the equipment. These valves are very efficient for ON/OFF flow control and
when accurate throttling is required. Moreover, the use of these types of valves
is particularly suitable where cavitation and noise are factors to consider. A
typical example of the use of a globe valve is to control the cold and hot water
flows to a kitchen sink or bathroom basin [7; 8].
There are two categories of fail-safe control valves used to ensure fail-safe
operation. These are air to open/fail closed and air to close/fail open control
valves. The design algorithm of these valves is fundamentally the reverse of
the process-control loop. Consequently, the type of valve used has a direct
effect on the required output action of the process controller. Moving from
one class of fail-safe control valves to the other basically entails changing
the output manipulation of the process controller from one direction to the
opposite direction. In the event of a plant instrument air failure it is essential
for all control valves to fail in a safe position. For instance, it is important that
the feed valves or possibly just one of the feed valves of an exothermic reactor
should fail closed (air to open) and its coolant system valves should fail open
(air to close) in the event of a failure in the system [7; 8].
The air to close/fail open valve, denoted AC/FO, is a control valve that is
designed to switch to the open position when a control or air failure signal
is generated. This type of control valve is generally denoted as FO in most
process flow diagrams. The valve is basically held by a spring, and needs air
pressure to move it towards the closed position. The valve is designed such that
the valve is fully open when there is no signal produced by the controller or
when there is no air pressure. However, as the controller generates a signal or
the air pressure gradually increases, the valve closes progressively. The output
of the controller needs to increase in order for the valve to close further [7; 8].
Air to open/fail closed valves are normally held closed by a spring and require
air pressure or the output signal from a controller to open them. They are
denoted FC on most process flow diagrams. They are designed such that they
open gradually as the air pressure increases or the output signal generated by
the controller increases [7; 8].
The other important thing you need to understand is the direction of control
action. Generally, the output response from the process controller is directly
dependent on the action of the process under control. Most of the time the
primary purpose of the output signal generated by the controller is to counteract
the current situation detected in the system under control. For example, when
the measured flow of a process increases beyond the design set point, the
output response generated by the controller has the objective of reducing the
flow of the process fluid. The action of the process controller can be defined
in two different ways [7; 8]:
(b) Reverse acting – In this case the output response from the process controller
decreases as the results of the process measured variable increase. In a reverse
acting situation, the operating force of the control valve is derived from
the compressed air pressure which is exerted on the flexible diaphragm of
the control valve. The actuator of the control valve is designed in such a way
that the force generated from the compressed air pressure, multiplied by the
area of the diaphragm, overcomes the force applied in the opposite direction
by the springs of the valve [7; 8].
The various control (globe) valves are categorised based on the link between
the position of the stem of the valve and the flow rate obtained through the
control valve. Consequently, there are three main types of control (globe)
valve [7; 8]:
(a) Linear valve – As indicated by its name, the flow rate generated by this
kind of globe valve varies linearly on the basis of the position of the stem. In
this case everything is perfectly set and designed for the pressure drop to be
solely dependent on the valve. For this reason this type of valve is commonly
utilised when it is necessary to maintain a constant pressure across the valve
and its travel is directly proportional to its stroke action. The relationship
between the stem position of the valve and the flow rate generated can be
mathematically expressed by the following equation [7; 8]:
where Q is the flow rate generated by the valve (m3/s); Qmax is the maximum
flow rate that can be generated by the valve (m3/s); S is the stem position (m)
and Smax is the maximum stem position (m).
(b) Quick opening valve – This family of valves is most suitable for full ON/
full OFF industrial control applications, because in quick opening valves, high
flow rates are achieved with only a small change in valve stroke. They can,
for instance, generate 90% of the maximum flow rate with just 30% travel of
the stem [7; 8]. A quick opening valve is very useful for safety where a quick
opening action is required. It is also known as the square root trim, according
to the following equation below:
(c) Equal percentage valve – This type of valve plays a very important role in
flow control application due to its characteristic of inducing a change in the
outflow rate which is equivalent in percentage to the change in stem position of
the valve. This simply means that equal increments of the stem travel generate
an equal percentage in flow change. These valves are designed in such a way
that they do not completely shut off the flow of fluid when the stem is positioned
at one of its travelling limits. Hence, Qmin denotes the minimum flow rate
produced when the stem is at one of its travelling limits. At its other travelling
limit, the valve generates a flow Qmax, which represents the maximum open
valve flow rate. For this type of valve, the characteristic rangeability, denoted
as R, is the ratio of the maximum flow rate and the minimum flow rate. It is
expressed by the following equation [7; 8]:
Solution
The rangeability of the valve can be calculated from the information provided
in the problem statement.
The task of determining the correct valve size for a specific control system is
essential, and requires the consideration of various operating factors. However,
the capacity parameter of the valve or the flow coefficient, denoted CV, is the
most important characteristic to take into consideration when selecting the
valve for a control system. This characteristic is used to evaluate how efficient
a valve is at allowing a fluid to flow through it [8; 9].
The flow coefficient of the valve CV is the number of US gallons of water per
minute that flows through a fully open valve with a pressure differential of 1
pascal per square inch. It is generally determined experimentally. However,
most valve manufacturers provide customers with the CV chart of the valve
they manufacture. Another technique used to estimate the values of the flow
coefficient when sizing an appropriate valve needed for a specific system is
through the valve flow equation [8; 9].
The task of valve sizing relies on the following four fundamental characteristics
[8; 9]:
The volumetric flow Q through the control valve can be calculated as follows
[8; 9]:
In the case of existing design specifications such as maximum flow rate through
the valve and maximum pressure drop allowable, the following form of the
equation is utilised to calculate the flow rate across the valve [8; 9]:
PV is
the pressure drop across the valve measured in pascals per square inch; CV is
the valve coefficient; SG is the specific gravity compared with water and f(x) is
the fraction of the total area of the valve. The table below represents a typical
CV chart usually provided by the valve manufacturer [8; 9].
Before we follow the standard algorithm for control valve (globe) sizing and
selection, we need to identify the type of control valve (globe). The following
key variables need to be carefully considered [8; 9]:
Some other considerations for valve sizing and selection are [8; 9]:
• It is not advisable to use a control valve that is less than half the pipe size.
• It is not advisable to use the lower 10% of the valve stroke and the upper
20% of the valve stroke. The globe valve is much easier to control within
the 10–80% stroke range. One of the common rules of thumb is that the
selected control valve should handle 10–15% of the total pressure drop or
10 psi, whichever is greater.
The following steps are followed when sizing and selecting a control valve
(globe) [8; 9]:
Step 1: Calculate CV at the design maximum flow rate using the flow equation
for a control valve.
Step 2: Perform preliminary valve selection using the chart provided and
taking into consideration all key sizing and selection criteria. At this
stage it is necessary to determine which valve is suitable to provide
the design maximum flow rate and ensure that the valve position is
within 80 to 85% travel.
Step 3: Calculate CV at the design minimum flow rate using the flow equation
for a control valve.
Step 4: Verify that the stroke percentage for minimum flow does not fall
below 10% at the design minimum flow rate. If it does, it is advisable
to choose a smaller valve, especially if the valve is likely to operate
near the minimum flow rate for long periods of time.
Step 5: Check the gain across applicable flow rates and remember that the
gain should never be less than 0.5.
Solution
1 – Calculating the CV at the maximum flow rate using the flow equation for
a control valve.
Flow equation:
From the flow equation we can make CV the subject of the formula and obtain:
Before we begin the calculations, we need to determine the pressure drop
allowable across the valve. For this case study, 10% of the total pressure drop
is equal to 16 psi, which is higher than 10 psi. Therefore, the valve selected
should be able to handle a pressure of 16 psi.
Looking at the values from the chart provided (table 4.2), we can see that a
two-inch valve appears to be quite suitable for the calculated value of CV (40)
at maximum design flow rate. A valve size of 3/2 inches will not be suitable
for this maximum flow rate because at a stroke percentage of 100% the value
of CV is only 35.8.
The valve of size 2 inches has a CV value of 25.4 at a stroke percentage of 70%
and a CV value of 59.7 at a stroke percentage of 100%. Using the interpolation
technique we approximate from the given parameters that the calculated CV
value of 40 corresponds to a stroke percentage of 83%, which falls within
the recommended range of 80–85% for maximum design flow rate. For this
reason, at this stage we select a valve size of 2 inches.
4 – Verifying that the stroke percentage for minimum flow does not fall below
10% at the design minimum flow rate
Looking at the value of CV calculated while referring to the valve chart (for size
2 inches), we observe that it corresponds to a stroke percentage of between
30 and 40%. Using the interpolation technique, we see that the calculated
value of CV obtained at minimum flow (7) corresponds approximately with the
valve size of 2 inches preselected to a stroke percentage of 35%. This is above
the lowest limit of 10% recommended. Consequently, this size is certainly still
acceptable for the design minimum flow rate.
It is usually almost impossible to determine the perfect valve size. However, the
selection criteria mentioned above make it possible to determine a valve that
will operate well most of the time. For this reason, we need good judgement
skills. For instance, during valve sizing and selection, it is essential to understand
whether the system is more likely to operate closer to the minimum design
flow rate than to the maximum flow rate, or whether the system is designed
to operate near the maximum design flow rate for extended periods of time.
A maximum pressure drop of 16 psi has been used in all our calculations.
However, at flow rates lower than the maximum allowable flow rate, the
pressure drop across the valve will actually be lower, and so by using the
maximum pressure drop, we are considering the worst case scenario. For
the preselected valve size (2 inches), even a CV value of approximately 1.5
at minimum design flow rate would not really be an issue. The preselected
valve has a CV value of 1.66 at a stroke percentage of 10%. In our calculations
we used the maximum pressure drop, and looking at the flow equation, we
notice that at lower pressure drops the calculated values of CV increase, which
is advantageous, in that our estimation remains acceptable.
5 – Calculating the gain across applicable flow rates
(a) Calculating the valve coefficient at the operating design flow rate:
Using the chart values in table 4.2 and the interpolation technique, we find that
the value of CV calculated above corresponds to a travel percentage of 74%.
(b) Calculating gain across applicable flow
The gain of the system is mathematically defined as:
The three design flow rates for this specific system are as follows:
Qmin = 30 gpm
Qop = 120 gpm
Qmax = 160 gpm
From all the calculated parameters above, the following table can be constructed:
We can see that none of the gains calculated is less than 0.5, which follows
the rule mentioned previously.
Final control devices are elements of the control system that gather the flow
of information from the controller in the form of output signals and convert
it into a desired action that is able to physically and appropriately influence
the behaviour of the plant. The most commonly used final control element
in the chemical industries is the control valve. However, other final control
elements, such as agitator speed controls and conveyor belt speed controllers,
are also sometimes used [8; 9].
4.1 Consider the process flow diagram provided below. The objective of the
process is to heat the oil from temperature T0 to a desired temperature TD
using process steam. In this case, what is the fail-safe design of the valve?
4.2 Study the automated cooling system for a large power-generating engine
illustrated by the process flow diagram presented below. What is the fail-
safe design of the valve?
4.3 Clearly describe the valve fail-safe design for the following process in the
event of utility failure.
(a) 5 mm
(b) 200 mm
4.9 Calculate the pressure drop across the valve when the flow rate is given
as Q = 90 gpm and the flow coefficient is given as CV = 51.
4.10 Calculate the flow rate generated if the pressure drop across the valve is
10 ft and the flow coefficient is given as CV = 51.
4.11 Consider the process flow diagram below. Determine the size of the valve
required to control the liquid water flow when the maximum flow rate
is 63 gpm. The pressure of the heat exchanger and the total pressure of
the system are 6 and 49.4 psi, respectively. Size the valve to be used.