PSlab Exp 2
PSlab Exp 2
N0:1 (B)
DATE:
Is-CVg+DlR
ABCD PARAMETERS
TYPE METHOD
A-D=1; B-Z; C-0.
Short
NominalT Method A-D=1+YZ2;
Medium
B-Z(1+YZI4);
C-Y;
Nominal a Method A-D=1+YU2:
B-Z;
C-Y(1+YI4);
Rigorous Method A-D-cos h(yC);
Long B-Z, sin h(y¬):
C=1/Z, sin h(yl);
y-V(ZY);
Z-V(ZY);
Equivalent z Method A-D=1+YZ2;
B-Z;
C-Y(1+YIA);
Z-Z sin h(yey yl;
Y=Y tan h(yt/2)/ (ylr2);
-V(ZY);
Z=V(ZY);
Equivalent T Method A-D=1+YZ2;
B-Z;
C-Y(1+YUA);
Z-Z tan h(yU2y (y/2);:
Y=Y sin h(ye) ye;
-(ZY);
Z-V(ZY);
PROCEDURE:
1. Enter the command window of the MATLAB.
2.Create a new M- file by selecting File - New -M-File
3. Type and save the program in the editor window.
4. Execute the program by either pressing Tools - Run.
5. View the results.
Page 21 of 155
I An overhead 3 phase trans)ission line del1vers 4000KW at IIKVat 0.8 pf lagging. The
reSIstance and reactance of each conductor are I.592 and 492 per phase. Deterimine the l1ne
performance.
SHORIJIRANSMISSION LINE
PROGRAM:
clc:
clear all;
R-input(Resistance
XL-input('Ihductive Reactance :):
XC=input(Capacitive Reactance :):
G-input(Conductance :);
length=input(Length of Transmission Line :);
f-input(Frequency
ZI= (R+j*XL)$length;
:);
Yl= (G+j*XC)*length;
A= 1;
B= Z1:
C=0;
D =1;
TM- [AB; CD];
VRL-input(ENTER RECEIVEING END VoTAGE :);
VRP-VRJ(sqrt(3):
PR = input('ENTER RECEIVING END LOAD IN MW :);
P¾-input(ENTER THE RECEIVING END LOAD POWER FACTOR :);
h-acos(P);
SR-PRPf;
SR=SR*(cos(h) +j*sin(h));
QR-imag(SR);
R-conj(SRY(3*conj(VRP);
SM-TMVRP;R];
VS-SM(1,1);
IS-SM(2,1);
Pfs-cos(angle(VS)-angle(IS));
SS=3*VS*conj(1S);
VSA-angle(VS)*(180/pi);
ISA-angle(1S)$(180/pi);
VS-sqrt(3)*abs(VS);
S-abs(IS)*1000;
VREG{(vS/(abs(TM(1,1)-VRIL/VRL)*100;
PS-real(SS);
QS=imag(SS);
eff-PR/PS*100;
PL-PS-PR;
Page 22 of 155
QL-QS-QR:
TM
tprintf'SENDING END LINE VOLTAGE og at og degrees n'.VS.VSA):
fprintf 'SENDINGEND LINECURRENT'og at °og degrees n.IS.ISA;
fprintf 'SENDINGEND POWER FACTOR °og n',Pfs);
fprintf('SENDING END REAL POWER %g n'.PS);
fprintf 'SENDINGEND REACTIVE POWER °ogn'.QS):
fprintf(PERCENTAGE VOLIAGE REGULATION °og n',VREG);
fprintf("REAL POWER LOSS °ogn'.PL);
fprintf( REACTIVE POWER LOSs ogn'.QL);
fprintf('EFFICIENCY %G, eff);
QUTPUT:
Resistance :15
Inductive Reactance :4
Capacitive Reactance :0
Conductance :0
Length of Transmission Line :1
:50
Frequency
ENTER RECEIVEING END VOLTAGE :11
ENTER RECEIVING ENDLOAD N MW :4
ENTER THE RECEIVING END LOAD POWER FACTOR :0.8
Zl=
1.5000 -+ 4.0000i
Yl=
TM=
Page 23 of 155
2 Abalanced 3plhase loadof 30 MW is supplied at I32KV. 5OHz and 0.85 pf lag by means
of a line. The series inpedance is 20-j5292 and total admittance is 315* 10°U.Using
NormalT methoddetermine A.,B.C.D parameters and regulation.
MEDIUM TRANSMISSIONILINE
PROGRAM:
clc;
clear all;
R-input(Resistance
XL-input('Ihductive Reactance
XC=input(Capacitive Reactance :):
G-input(Conductance :);
length=input('Length of Transmission Line :);
finput(Frequency :);
ZI- (Rtj*XL)*length;
YI-(Gtj*XC)*length;
m-menu(ENTER THE TYPE OF NETWORK,NOMINAL T', NOMINAL PI);
switch m
case {1}
A = 1+(Zi*YI2);
B-Z1*(1+(ZI*Y1/4);
C=Yl;
D-A;
otherwise
A- 1+(Z1*Yi2);
B-Z1;
C-Y1(1ZI*YI/4);
D-A;
end
TM-[A B; CD);
VRL-input(ENTER RECEIVEING END VOLTAGE :);
VRP-VRJ(sqrt(3);
PR input(ENTER RECEIVINGEND LOAD IN MW
Pf-input( ENTERTHE RECEIVNG END LOAD POWER FACTOR :);
h=acos(Pf);
SR-PR/Pf;
SR-SR*(cos(h)+j* sin(h));
QR-imag(SR);
R-conj(SRY(3*conj(VRP));
SM-TM*VRP;IR];
VS-SM(1,1);
IS=SM(2,1);
Pfs-cos(angle(VS)-angle(IS);
SS-3*VS*conj(IS);
Page 24 of 155
TSA-angle(VS)*(80 p):
ISA-angle IS)*(180 pi):
\'S-sqrt(3)*abs(V'S):
IS-abs( IS)*1000;
VREG-(VS (abs(TMl.))-VRL)VRL)* 100:
PS=real(SS):
QS=imag(SS):
eff-PRPS*100;
PL-PS-PR:
QL-QS-QR:
YI
TM
fprintf('SENDING END LINE VOLTAGE °og at "og degrees n';VS,VSA);
fprintf("'SENDING END LINE CURRENT °og at ag degrees n,IS,ISA);
fprintf("'SENDING END POWER FACTOR ogn.Pfs);
fprintf('SENDING END REALPOWER %gn.PS);
fprintf("SENDING END REACTIVE POWER %gin,QS);
fprintf("PERCENTAGE VOLTAGE REGULATION %ga,VREG);
fprintf(REAL POWER LOSS %g'n'PL);
fprintf(REACTIVEPOWER LOSS %g'n:QL);
fprintf( EFFICENCY%G, eff);
Page 25 of 155
NOMI LI
QUPU:
Resistance : 20
Inductive Reactance :52
Capacitive Reactance :315*104-6)
Conductance :0
Length of Transmission Line :1
Frequency :50
ENTER RECEIVENG END VOLTAGE :132
ENTER RECEVING END LOAD IN MW :30
ENTER THE RECEIVING END LOAD POWER FACTOR :0.85
ZI =
20.0000 +52.0000i
Yl=
0+3.1500e-004i
TM =
0.9918 + 0.003li 19.8362 +51.81861
0+0.00031 0.9918+ 0.0031i
SENDING END LINE VOLTAGE 143.035 at 3.76761 degrees
SENDING END LINE CURRENT 142.007 at -23.3284 degrees
SENDING END POWER FACTOR0.890244
SENDING END REAL POWER 31.3199
SENDING END REACTIVE POWER 16.0243
PERCENTAGE VOLTAGEREGULATION 9.25407
REALPOWER LOSS 1.31989
REACTIVE POWER LOSS -2.56785
EFFICIENCY 95.7858
Page 26 of 155
reactance
line has total impedance of 35Q.
3.A S0Hz. 3 phase. 100km transn1ission 220KV, 0,9 pf lag
0f 140Q andshunt admittance of 930*10°0.It delivers 40MW at
pf. P, Q..1.
.Using nominal z determine A.B.C.DV,. VSA.kA.
NOMINAL PI
QUTPUT:
Resistance : 20
Inductive Reactance :52
Capacitive Reactance :315*10^-6)
Conductance :0
Length of Transmission Line :1
:50
Frequency
ENTER RECEIVEING END VOLTAGE : 132
ENTER RECEIVING END LOAD IN MW :30
:0.85
ENTER THE RECEIVING END LOAD POWER FACTOR
ZI =
20.0000 +52.0000i
Yl=
0 +3.1500e-004i
TM =
Page 27 of 155
1. A3 phase 50 Hz.240KV lne is 200m long. The line parameters are R-0.0172 ph km:
L-0.94nH ph km: C-0.011luF ph km.Calculate Iine perfornance when load is 500MW. 0.9
pf lag at 220KV.
Page 28 of 155
IR-conj(SR)(3*conj(VRP):
SM-TM*[VRP:R].
VS-SM(1:
IS-SM(2.):
Pfs-cos(angle(VS)- an gle( S)):
SS-3*VS*conj( S):
VSA-angle(V'S)*(180 pi):
ISA-angle(IS)*(180pi):
VS=sqrt(3)*abs(VS ):
IS-abs(IS)*1000:
VREG-((VS/(abs(TM(I.1)-VRL)VRL)*100;
PS-real(SS):
QS=imag(ss);
eff-PR/PS*100;
PL-PS-PR;
QL-QS-QR;
ZC
Z
Y
TM
fprintf(SENDING END VOLTAGE %g at og degrees n',VS,VSA);
fprintf(SENDING END CURRENT %g at 6g degrees n',IS, ISA);
fprintf(SENDING END POWER FACTOR %gn'Pfs);
fprintf("SENDING END REAL POWER %gn,PS);
fprintf("SENDING END REACTIVE POWER %gn',QS);
fprintf(PERCENTAGE VOLTAGE REGULATION %gn,VREG);
fprintf(REAL POWER LOSS %gn',PL);
fprintf(REACTIVE POWER LOSS %gn',QL);
fprintf(EFFICIENCY %G,eff);
Page 29 of 155
EQUVALENTPLVE JHOD
Resistance :0.0170
Inductance :0.94
Capacitane 0.01|1
Conductance :0
Length of Transmission Line :200
frequencys0
ENTER RECEVEING END VOLTAGE : 220
ENTER RECEVING END LOAD IN MW :500
ENTER THE RECEIVING END LOAD POWER FACTOR :0.9
Z =
0.0170+ 0.2953i
y=
0 +3.4872e-006i
ZC=
2.9113e+002 -8.3727e+000i
Z=
0.0168 + 0.2933i
Y=
1.3896e-007 +6.9984e-004i
TM =
Page 30 of 155
EQUVALENIIWIEIHOD
Resistalce 0.0170
Inductance 0.94
0.01||
Capacitance
Conductance 0
Length of Transnission Line : 200
frequencys0
ENTER RECEIVEING END VOLTAGE :220
ENTER RECEIVNGEND LOAD IN MW : 500
ENTER THE RECEVING END LOAD POWER FACTOR :0.9
0.0170 + 0.2953i
y=
0 +3.4872e-006i
ZC =
2.9113e+002 -8.3727e+000i
Z=
0.0171 + 0.2963i
Y=
1.3896e-007 +6.9984e-004i
TM =
Page 31 of 155
$ The tollowing datarefers to a3phase overhead transmsson lme. The voltage is 220K\'
Totalseries mpedance ph-200L 30°. Total shunt
admittance ph- 0.0013 L 900. Load delivers is 100MWat 0.8pf lag. Using rigorous
method detemine line performance.
Page 32 of 155
QL-QS-QR.
7
TM
fprintfi 'SENDINGEND VOLIAGE °og at og degrees n.VS,VSA);
fprintf 'SENDING END CURRENT °og at "og degrees n.S, SA);
fprintf('SENDING END POWER FACTOR °ogn. Pfs):
fprintf("'SENDINGEND REALPOWER ogn.PS):
fprintf("SENDING END REACTIVE POWER °%gn'.QS):
fprintf PERCENTAGE VOLTAGE REGULATION °og n,VREG):
fprintf( REALPOWER LOSS °ogn'",PL);
fprintf( REACTIVEPOWER LOSS %gn',QL);
fprintf( EFFICIENCY %G, eff):
Page 33 of 155
OUUPUI
Res1stance :35
lnductive Reactance 197
Capacitive Reactance :0.0013
Conductance :0
Length of Transmission Line :1
Frequency 50
ENTER RECEIVENG END VOLTAGE :220
ENTER RECEIVING END LOAD N MW : 100
ENTER THE RECEIVING END LOAD POWER FACTOR :0.8
Z=
3.5000e+001 +1.9700e+002i
y=
0+0.00131
ZC =
3.9080e+002 -3.4446e+001i
Z=
3.2069e+001 +1.8895e+002i
Y=
0.0000 + 0.00131
TM =
1.0e+002 *
0.0087+ 0.0002i 0.3207 + 1.Sel9si
-0.0000 +0.0000i 0.0087 + 0.0002i
SENDING END VOLTAGE 282.874 at 16.3752 degrees
SENDING END CURRENT 232.732 at -2.03335 degrees
SENDING END POWER FACTOR 0.948829
SENDING END REAL POWER 108.192
SENDING END REACTIVE POWER 36.0088
PERCENTAGE VOLTAGE REGULATION 46.9731
REALPOWER LOSS 8.19239
REACTIVE POWER LOSS -38.9912
EFFICIENCY 92.4279
RESULT:
Thus the line modeling of different types of transmission lines was done.