Liebert Pex Product Application User Manual
Liebert Pex Product Application User Manual
3.0 OPERATION
3.1 Single Unit Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.1 Unit/Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1.2 General Compressor Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.1.3 Compressor Timing—Units With Two Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1.4 Compressor Sequencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Temperature Control—Single Source Cooling (No Extra Cooling Coil) . . . . . . . . . . . . . . . . 16
3.2.1 Temperature Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.2 Compressor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.3 Chilled Water Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3 Temperature Control—Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.1 Electric Reheat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.2 Humidity Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.3.3 Humidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
3.3.4 Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
3.4 Control Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.1 Temperature and Humidity Control Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.4.2 Humidity Sensor Reading Control Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.4.3 Supply Limit—Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.4 High and Low, Temperature and Humidity Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.5 User Inputs / Customer Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.4.6 Event Types and Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.5 Possible Event Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
3.6 Next Maintenance Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.6.1 Calculation of Next Maintenance and Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
i
4.0 TEAMWORK
4.1 Teamwork Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1.1 Application of Teamwork Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1.2 No Teamwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1.3 Teamwork Mode 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1.4 Teamwork Mode 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1.5 Standby – Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
ii
LIST OF FIGURES
Figure 1 Liebert iCOM components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Figure 2 Liebert iCOM controller general arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Figure 3 Liebert iCOM display components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Figure 4 Status menu, large display, graphical view. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 5 Liebert iCOM default screen symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Figure 6 Menu tree—Small display, stand-alone or networked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Figure 7 Menu tree—Large display, stand-alone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Figure 8 Menu tree—Large display, networked. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 9 User menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 10 Service menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Figure 11 Start-stop priority switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 12 Temperature proportional band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 13 Two single-step compressors or one compressor with HGBP (two-step) . . . . . . . . . . . . . . . . . . . . 17
Figure 14 Modulating actuator control (example: cooling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 15 Electric staged heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 16 Humidity proportional band. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 17 Teamwork Mode 1 with two cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 18 Connecting two cooling units, each with a small display using a crossover Ethernet cable . . . . 36
Figure 19 Wiring a small display for stand-alone operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 20 Wiring a small display for U2U network operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 21 Wiring a large display for stand-alone operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 22 Wiring a large display for U2U network operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Figure 23 Liebert iCOM input-output control board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 24 Liebert vNSA with optional large graphic display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 25 Liebert iCOM display dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
iii
LIST OF TABLES
Table 1 Keyboard icons and functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 2 User menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 3 Service menu icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 4 Parameters for infrared humidifier control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 5 Parameters for immersed electrode humidifier control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Table 6 Dehumidification With Comp settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 7 Customer inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 8 Event Behaviour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 9 Possible event settings—some events not available in all units . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 10 Event notifications—large or small display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 11 Sample Liebert iCOM network configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 12 Ports available for connecting Liebert iCOM control devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Table 13 Setpoints parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 14 Spare part list parameters—large display only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 15 Event log parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Table 16 Graphics parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 17 View network parameters—large display only* . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 18 Set alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Table 19 Sensor data parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 20 Active alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Table 21 Display setup parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 22 Total run hours parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Table 23 Timer parameters—Sleep Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 24 Service contacts parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Table 25 Setpoints parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Table 26 Unit diary parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Table 27 Maintenance / wellness settings parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 28 Standby settings / lead-lag parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Table 29 Diagnostics / service mode parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Table 30 Set alarms parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Table 31 Set alarms parameters (continued) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Table 32 Sensor calibration / setup parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Table 33 Network setup parameters — SYSTEM (large display only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Table 34 Network setup parameters - UNIT (I/O board) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Table 35 Options setup parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Table 36 Service contacts parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
iv
Introduction
1.0 INTRODUCTION
The Liebert iCOM™ control offers the highest capabilities in unit control, communication and moni-
toring of Liebert mission-critical cooling units.
Liebert iCOM may be used to combine multiple cooling units into a team that operates as a single
entity, enhancing the already-high performance and efficiency of Liebert’s units.
Liebert iCOM is available as a factory-installed assembly or may be retrofitted on existing products
with CEMS100 controls. Large graphic display wall-mount versions of the control are available for
remote operation and monitoring of cooling units.
1.1 Features
Large and Small Displays
The Liebert iCOM control is available with either a large or small liquid crystal display.
• The Liebert iCOM with small display has a 128 x 64 dot matrix screen that simultaneously shows
two menu icons, along with descriptive text. This display is capable of controlling only the unit it
is directly connected to.
• The Liebert iCOM with large display has a 320 x 240 dot matrix screen that shows up to 16 menu
icons at a time, as well as descriptive text. This display can be used to control a single cooling unit
or any cooling unit on a network, regardless of how it is connected—either integrated into a cool-
ing unit or simply connected to the network and mounted remotely.
Liebert iCOM’s menu-driven display is used for all programming functions on each connected cooling
unit. The Status menu shows the status of the conditioned space, such as room temperature and
humidity, temperature and humidity setpoints, alarm status and settings, event histories and the
current time.
Figure 1 Liebert iCOM components
1
Introduction
CAN
RIBBON CABLE
CABLES
INTELLISLOT
POWER SUPPLY INTELLISLOT 1
P2 P1
INTELLISLOT 2 P66
CAN
P3 P65
USED
(Connect to P65 for SiteScan) CAN
CABLE
P61 P63 E5
P64
P18 P65
P67
P40
P32
P66
P8
P12
P11 P13
P33
iCOM
P7
P34
MICROPROCESSOR AND
I/O BOARD
P36
P35
P43
P54 TB1 E1 E2 E3 E4
P22 P38 P39 P53 P52 P51 P4
P64 P66
U2U CAN
T1 UNIT CONTROL
TRANSFORMER T6 ISOLATION
TRANSFORMER
P4 P43 P44 P24
E1
OPTIONAL LARGE
P42
CONTROL
GRAPHICS DISPLAY
FUSE
(REAR VIEW)
P41
BOARD
24VAC NOMINAL
CAN
INTERNAL T/H CABLE
SENSOR
HUMIDIFIER
ISOLATION
P66
BOARD
LEGEND
P1
Factory supplied
wiring
Wiring included in
options
2
Liebert iCOM Display Components and Functions
ESC
?
On/Off Key Help Key Left Arrow Key Enter Key Right Arrow Key
ESC
Escape Key Down Arrow Key
NOTE
The Help key may be pressed at any time for a brief explanation of what is being viewed.
3
Liebert iCOM Display Components and Functions
Increase Key
Moves upward in a menu or increases the value of a selected parameter.
(Up Arrow)
Decrease Key
Moves downward in a menu or reduces the value of a selected parameter.
(Down Arrow)
4
Liebert iCOM Display Components and Functions
5
Liebert iCOM Display Components and Functions
NOTE
Settings are readable without a password, but changing settings requires a password.
6
Liebert iCOM Display Components and Functions
NOTE
The User menu password is 1490.
To enter a password:
1. Navigate to the menu that contains the parameter to be changed.
2. Select Password in the submenu by pressing the Enter key
3. Press the Enter key to move your cursor to the right side of the screen to select the question
marks.
4. Use the arrow keys to enter the numeral for the password’s first digit (the up arrow key moves
from 1 to the next digit).
5. Use the right arrow key to move to the next question mark and repeat Step 4 to enter all digits in
the password.
6. After entering the password, press enter.
If the password is correct, the Actual Level shown to the right of Password will change
from 0 to 1 or 2. The menu will remain locked if the password was incorrect.
NOTE
Returning to the Status menu will require re-entering a password to make changes.
Status Menu
Unit 1 View
7
Liebert iCOM Display Components and Functions
Status Menu
Unit 1 View
8
Liebert iCOM Display Components and Functions
9
Liebert iCOM Display Components and Functions
°C / °F
View and change temperature and humidity
% RH Setpoints
setpoints
Small & Large
SET
EVENT
Event Log Contains last 400 events Small & Large
LOG
SET
Set Alarms Allows enable, disable and settings for alarms Small & Large
ALARMS
12
Change settings for display: language, time,
9 3 Display Setup
simple or graphic view
Small & Large
SET 6
10
Liebert iCOM Display Components and Functions
12
Allows setback settings for non-peak
9 3 Sleep Mode Small & Large
operation
6
11
Liebert iCOM Display Components and Functions
°C / °F
% RH Setpoints To view and change temperature and humidity setpoints Small & Large
SET
Standby Settings/
Allows lead/lag setup when multiple units are connected Small & Large
Lead-Lag
SERVICE
SET
Set Alarms Allows enable, disable and settings for alarms Small & Large
ALARMS
Sensor
Allows calibration of sensors Small & Large
+/- Calibration/Setup
NETWORK
System/Network
Allows setup and U2U communication for multiple units Large only
Setup
12
Operation
3.0 OPERATION
The Liebert iCOM display for your Liebert cooling unit features an easy-to-use, menu-driven liquid
crystal display (LCD). All unit settings and parameters can be viewed and adjusted through three
menus: User, Service and Advanced. All active alarms are displayed on the LCD and annunciated.
The control is shipped from the factory with default selections for all necessary settings. Adjustments
can be made if the defaults do not meet your requirements.
References to menu items in this manual are followed by the main menu and the submenu where they
can be found.
For example:
• Temperature Setpoint (User Menu, Setpoints) - The Temperature Setpoint parameter is located
in the User menu under the Setpoints submenu.
• High Return Humidity (Service Menu, Set Alarms) - The High Return Humidity alarm is located
in the Service menu under the Set Alarms submenu.
NOTE
Customer switches: remote On/Off (if used) and display On/Off switches are in series. A
cooling unit will start only if both switches are On; if one of these switches is Off, the unit will
stop. Safety devices within the unit are also in series and will shut the unit down if required.
NOTE
If Remote On/Off is not used, a jumper is inserted to bypass the switch.
13
Operation
Auto Restart
When there is a loss of power to the cooling unit and power comes back, the unit will return to its pre-
vious operating status—on if it was on before the power off, off if it was off.
When power returns, the autorestart time—time-selectable: Single Unit Auto Restart (Service Menu,
Options Setup)—controls the start of the unit. The autorestart time runs in a loop, starting the next
unit each time when elapsed, starting with Unit # 1.
NOTE
Loss of power alarm will be activated only on units that had the fan on before power was lost.
NOTE
When the Main Fan Overload alarm is active, the Loss of Airflow alarm is masked out.
NOTE
Low-pressure condition could be read through contacts or through pressure transducers with
threshold setting.
14
Operation
Once the compressor is locked off, it will not come back on until the HP Alarm Counters (Service
Menu, Diagnostics) are reset to 0. Setting the counter to 0 will auto-reset the alarm without the need
of pressing the reset button on the display. Even if the pressure in the system drops below the alarm
point, the compressor will remain off until the system is reset.
NOTE
If the unit is equipped with manual reset high head pressure switches, or if the auto reset
high head pressure switches don’t reset, the compressor will not be turned back on, but there
will be a 30-second delay from when the high head pressure situation occurs and when the
alarm is annunciated.
NOTE
The Auto setting attempts to maintain equal run times between compressors.
15
Operation
Without Deadband
Heating Cooling
- Temp + Temp
½ Proportional Band ½ Proportional Band
- 100 % 0% + 100%
Heating Setpoint Cooling
With Deadband
Dead-
Heating band Cooling
- Temp + Temp
½ Proportional Band ½ Proportional Band
- 100% 0% 0% + 100%
Heating Setpoint Cooling
When the return air temperature deviates from the setpoint it begins to penetrate one of the propor-
tional band halves, cooling or heating. If the return air temperature increases, the control calls for 0%
(none) to 100% (full) cooling capacity based on how far the temperature penetrates the cooling portion
of the proportional band. If the return air temperature decreases, the control calls for 0% (none) to -
100% (full) heating capacity based on how far the temperature penetrates the heating portion of the
proportional band.
When the return air temperature reaches the end of the proportional band, either 100% or -100%, full
cooling or full heating capacity is provided. No operation is performed when a 0% call is calculated.
The control varies the call for cooling and heating in 1% increments as the return air temperature
moves through the proportional band halves.
The deadband range is used to widen the setpoint. When the return air temperature falls within the
deadband, the control operates the same as if the temperature equaled the setpoint exactly. This set-
ting helps maximize component life by preventing excessive component cycling. The Temperature
Proportional Band and Temperature Deadband parameters are in the Service menu under the Set-
points submenu. The Temperature Setpoint parameter is in both the User menu and Service Menu
under Setpoints.
There is a parameter AutoSet Enable (Service Menu, Setpoints), which automatically sets the propor-
tional bands for temperature and humidity, and both the integration time factors according to the
type of unit (Chilled Water, single or double compressor), with influence of the selected Teamwork
Mode. See 4.1 - Teamwork Modes for more on using this feature.
16
Operation
1/2 Deadband
Increasing Temperature
17
Operation
Requested
actuator position
Cooling
0% - Closed
Increasing Temperature
Decreasing Temperature
18
Operation
Without Deadband
Humidification Dehumidification
- Hum + Hum
- 100% ½ Proportional Band 0% ½ Proportional Band
Setpoint + 100%
humidification
Dehumidification
With Deadband
Dead-
Humidification band
- Hum Dehumidification + Hum
- 100% ½ Proportional Band 0% 0% ½ Proportional Band + 100%
Humidification Setpoint Dehumidification
When the return air humidity deviates from the setpoint, it begins to penetrate one of the propor-
tional band halves, either dehumidification or humidification. If the return air humidity increases,
the control calls for 0% (none) to 100% (full) dehumidifying capacity, based on how far the humidity
penetrates the dehumidification portion of the proportional band. If the return air humidity
decreases, the control calls for 0% (none) to -100% (full) humidifying capacity based on how far the
humidity penetrates the humidification portion of the proportional band.
When the return air humidity reaches the end of the proportional band, either 100% or -100%, full
dehumidification or full humidification capacity is provided. No operation is performed when a 0%
call is calculated. The control varies the call for dehumidifying and humidifying in 1% increments as
the return air humidity moves through the proportional band halves.
The deadband range is used to widen the setpoint. When the return air humidity falls within the
deadband, the control operates the same as if the humidity equaled the setpoint exactly. This setting
helps maximize component life by preventing excessive component cycling. The Humidity Propor-
tional Band and Humidity Deadband parameters are in the Service menu under the Setpoints sub-
menu. The Humidity Setpoint parameter is in both the User menu and Service menu under
Setpoints.
19
Operation
3.3.3 Humidification
Infrared Humidifier (Standard)
There are two types of infrared humidifiers: small pan (IFS) and large pan (IFL). The operating mode
of each is similar, however, some of the variables or timings differ.
Infrared humidifiers are started at 100% humidification request, and stopped at 0%. Infrared humid-
ifiers cannot be driven in proportional mode.
Table 4 Parameters for infrared humidifier control
Parameter IFS Default IFL Default
Humidity in Last xx Hours 15 hours 15 hours
Prefill Time 30 seconds 60 seconds
Fill Time 4 minutes 7 minutes
Humidifier On Time 8 or 10 minutes 10 minutes
Flush Rate 150% 150%
An autoflush system automatically controls a water makeup valve to maintain proper levels in the
infrared humidifier water pan during humidifier operation. If humidification is needed and 15 hours
have elapsed since the last time the humidifier was on, then the humidifier is not turned on until the
valve completes an initial fill of the humidifier pan. This pre-fill is about 30 seconds for a small pan
and 60 seconds for a large pan. The valve continues to fill and flush the pan for about 4-1/2 minutes
for a small pan or 7-1/2 minutes for a large pan. Pan size is selected based on unit specifications and
is preset at the factory.
During humidifier operation, with the flush rate set at the default of 150%, the valve is opened peri-
odically to add water to the pan (about 45 seconds every 7 minutes of humidifier operation for a small
pan, or 80 seconds every 10 minutes of operation for a large pan). This adds enough water to the pan
to cause about a third of the total water used to be flushed out of the overflow standpipe located in the
humidifier pan. This action helps to remove solids from the pan. The flush rate is adjustable from
110% to 500% in 10% intervals. Default is 150%. If the water quality is poor, it may be desirable to
increase the water flushing action above the normal 150% rate. Also, if the supply water pressure is
low, the flush rate adjustment can be increased so that sufficient water level is maintained during
humidification. The flush rate parameter, Infrared Flush Rate (Service Menu, Options Setup), is
adjustable from 110%-500%.
Water level is automatically controlled by a sensor located in the overflow pipe. During a call for
humidification, the humidifier make-up valve energises whenever the level sensor breaks contact
with the water for more than 5 seconds and de-energises after 1 second of making contact. If water is
not detected within 1 minute after energising the make-up valve, both humidifier and make-up valve
outputs are de-energised for 4 minutes. This cycle repeats until the level sensor is satisfied. A ‘low
hum water’ alarm is generated after 5 continuous cycles and the humidifier and make-up valve out-
puts are ‘locked out’.
20
Operation
An automatic flush cycle occurs whenever the humidifier current draw equals or exceeds the current
set value. The make-up valve is energised for the bottle flush time duration. Refer Table 5. The
humidifier output is de-energised during the flush cycle and re-energised 5 seconds afterwards.
Should the humidifier current draw exceed the current set value by 50%, an alarm will be activated
(Humidifier High Amps) and the humidifier will be latched out.
In the event of a water under floor alarm, the humidifier operation will be latched out until 5 minutes
after the alarm is reset.
3.3.4 Dehumidification
The Dehumidification Enable parameter (Service Menu, Options Setup) allows for enabling/disabling
the dehumidification function.
A call for dehumidification is calculated in the same way as a cooling request. The components
(valves, compressors) will follow this dehumidification request as soon as it is higher than the request
for cooling.
NOTE
Dehumidification will be allowed to restart when the return temperature exceeds setpoint.
21
Operation
! WARNING
If the electrical service to the unit is not properly sized, it could trip the building circuit
breakers (or fuses) or, in extreme cases, damage the building wiring. This Warning applies
only when the Dehumidification With Comp is set to BOTH and the Electric Reheat
Operation is set to Staged. Consult factory before making any changes to the default settings.
NOTE
The actual return air temperature sensor reading is always displayed on the Status menu.
The value displayed for the return air humidity sensor reading depends on the Humidity
Sensor Control Type (see - ).
22
Operation
NOTE
The historical humidity sensor graphs will display the real (unadjusted) sensor readings, no
matter which Humidity Control Sensor Type is selected. The graphical sensor data is in the
User menu under Graphics.
23
Operation
NOTE
The Supply Limit is calculated on each unit, independent of the other sensor readings on the
network.
NOTE
There is an auto-reset of the event messages if the temperature/humidity constantly stays 1°C
(1.8°F)/ 2% RH below or above the threshold for a time of one minute.
24
Operation
NOTE
To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event
Types on page 26.
Table 7 Customer inputs
Setting Reaction
Smoke Event Only
Water Alarm Event Only
C PMP Alarm Event Only
Flow Alarm Event Only
Stdby G Pmp Event Only
Stdby Unit Event Only
C-Input 1 Event Only
C-Input 2 Event Only
C-Input 3 Event Only
C-Input 4 Event Only
Rht Lockout Event + Electrical Heaters Disabled
Hum Lockout Event + Humidifier Disabled
Rht+Hum Lock Event + Electrical Heaters and Humidifier Disabled
Comp Lockout Event + Compressor(s) Disabled w/o Pump Down
Call Service Event Only
High Temp Event Only
Air Loss Event Only
FC Lockout Event + Free Cooling Disabled
Heater Alarm Event + Heaters Off
Flow AL SD Event + Shut Down the Unit
Flow AL LC Event + Lockout Compressors, No Pump Down (enabled only if at
least one compressor is on; auto-reset depends on input status)
Comp Lock PD Event + Compressor(s) Disabled w/ Pump Down
Enable FC Forces Free Cooling to On
HTRJ VFD Activates the HEAT REJ VFD ALARM; no other function
HTRJ TVSS Activates the HEAT REJ TVSS ALARM; no other function
Fire Alarm Event + Shut Down the Unit
2nd Setpoint Changes setpoint to second setpoint value
No Power Event + Compressor(s), Heaters, Humidifiers Disabled; Fan ON
Cond 1 Fail Event Only
Cond 2 Fail Event Only
25
Operation
NOTE
Not all critical event properties can be adjusted.
Event Types
• Message: If this event occurs, it will only be entered into the event log.
• Warning: If this event occurs, a warning will be generated and entered into the event log. The
general alarm relay will be activated only if parameter WARNING ACTIVATES ALARM RELAY
located in the Service menu under Alarm Setup is set to Yes (Yes is the default setting from the
factory)
• Alarm: If this event occurs, an alarm will be generated and entered into the event log. An alarm
does not necessarily switch off the whole cooling unit; it depends on which alarm occurs. If a
standby unit is set, any alarm will stop the faulty unit and ask the standby unit to start. Standby
activation is achieved on alarms ONLY; messages or warnings will not start the standby unit. For
more on standby units, see 4.0 - Teamwork.
Message No No Yes No
Note: Default. Set Alarm parameter available to change to NO
Time Delay
Delays the event reaction once it is triggered. The time delay applies to safety functions and is
entered in seconds.
Enable or Disable
Disabled events do not show up in the event log, on the display or on monitoring devices. Also, the
common alarm relay will not be activated if a disabled alarm occurs. Safety functions, such as lockout
compressor in case of high pressure are still performed.
NOTE
Once a disabled event (set to Warn or to Alarm) becomes active, it will lock itself. Disabled
events may be reset only through the menu item Reset Disabled Alarms.
NOTE
The value of the external delay includes the internal delay:
external delay = selectable delay + internal delay.
The minimum setting of the external delay is the value of the internal delay. This is valid only
for values marked with *.
26
Operation
27
Operation
28
Operation
29
Operation
30
Teamwork
4.0 TEAMWORK
Unit-2-Unit (U2U) Communications via a private network will allow the following functions to be
placed into operation when the requirement exists. The user must install the correct hardware
(see 5.0 - Installing a Liebert iCOM Unit-to-Unit Network) and properly program the units for the
selected functionality.
The Liebert iCOM network can perform the following functions:
The Teamwork Mode functions allow for multiple stages of cooling/heating and humidification/dehu-
midification. Teamwork Mode can be used to prevent environmental units from “fighting,” where one
environmental unit might be cooling while another unit is heating.
The Standby (Lead/Lag) function allows one or more units to be set as “Running” and “Standby” for
activation in case of an alarm. This function also allows the units to be programmed in a rotation to
help ensure “Standby” unit operation.
The Cascade Operation function allows additional units to be staged-on based on the temperature or
humidity requirement.
4.1.2 No Teamwork
All cooling units work independently, responding to their own sensors.
Standby function and unit rotation are possible, but cascading is not (see Standby and Cascade on
page 33). Autoset will not adjust the proportional band in Teamwork mode No.
31
Teamwork
NOTE
1. Proportional actuators (eg. chilled water valves) are driven in parallel in all units.
2. Low limit during dehumidification and low supply limit control air local functions are
managed from each unit independently.
Figure 17 shows how two cooling units work together in Teamwork Mode 1. Since Unit 1 and Unit 2
are available to operate, the master unit, Unit 1, averages the temperature and humidity sensor read-
ings from each unit.
The master unit determines that a 60% call for cooling is required for the system. Since there are two
available cooling units, each unit makes up half of the system proportional band; Unit 1 handles 0-
50% system call for cooling and Unit 2 handles 51-100%. For every 1% system call for cooling, each
unit provides 2% of its total cooling capacity.
The 60% system call for cooling exceeds the 50% Unit 1 can provide, so Unit 1 operates at full capac-
ity. The remaining 10% system call for cooling (60% - 50% = 10%) is handled by Unit 2. Unit 2
responds by operating at 20% cooling capacity (50% ÷ 10% = 20%).
System
Proportional Heating Cooling
Band +
- Temp ½ Proportional Band ½ Proportional Band Temp
- 100 % 0% + 100 %
Setpoint
32
Teamwork
NOTE
In Teamwork Mode 2, all units must have the same setpoints. The units’ proportional band,
deadband and related settings may differ.
NOTE
Before entering standby mode, units will operate the fan only for 3 minutes to cool the
electrical heaters, remove steam from the unit, etc.
NOTE
Cascaded units are not included in the calculation of the average temperature / humidity.
33
Installing a Liebert iCOM Unit-to-Unit Network
NOTE
The maximum number of cooling units that may be interconnected is 32.
34
Installing a Liebert iCOM Unit-to-Unit Network
35
Installing a Liebert iCOM Unit-to-Unit Network
Figure 18 Connecting two cooling units, each with a small display using a crossover Ethernet cable
Three or more units with small displays: To network three or more cooling units, each equipped with
a small display, connect a straight-through CAT5e Ethernet cable from the P64 connector on each
cooling unit’s Liebert iCOM input/output board to a common network switch (see Figure 20).
Large Displays
A network switch is required to enable Ethernet communication on one or more cooling units with
large displays. Each cooling unit with a large display requires two straight-through Ethernet cables
from a network switch. One cable connects to port P64 on the Liebert iCOM input/output board and
the other cable connects to port P64 on the back of the large display (see Figure 22).
36
Installing a Liebert iCOM Unit-to-Unit Network
P66
CAN
STANDARD SMALL
GRAPHICS DISPLAY
(REAR VIEW)
P61 P63 E5
P64
P65
P67
P66
iCOM
I/O BOARD
P12
P11 P13
P7
CAN CABLE
P66
CAN
CUSTOMER CONNECTION
POINTS, SEE NOTE 1
STANDARD SMALL
GRAPHICS DISPLAY LEGEND
(REAR VIEW) Factory wiring
Field/customer wiring
P61 P63 E5
P64 U2U NETWORKING SWITCH
P65
P67
(FIELD SUPPLIED)
P66
iCOM
P12
P11
I/O
BOARD
P13
TO / FROM OTHER
P7
37
Installing a Liebert iCOM Unit-to-Unit Network
ETHERNET
CROSSOVER P64 P66
U2U CAN
CABLE (RED)
SEE NOTE 2
OPTIONAL LARGE
GRAPHICS DISPLAY
(REAR VIEW)
P61 P63 E5
P64
P65
P67
P66
iCOM
P12
P11
I/O
BOARD
P13
P7
CAN CABLE
P64 P66
U2U CAN
SEE NOTE 2
CUSTOMER CONNECTION
POINTS, SEE NOTE 3
OPTIONAL LARGE
GRAPHICS DISPLAY
(REAR VIEW) LEGEND
Factory wiring
Field/customer wiring
P61 P63 E5
P64
P65 U2U NETWORKING SWITCH
P67
(FIELD SUPPLIED)
P66
iCOM
P12
P11
I/O
BOARD
P13
P7
TO / FROM OTHER
STRAIGHT NETWORKED UNITS
THROUGH (64 nodes total; maximum of 32
ETHERNET CABLES input/output boards)
CONNECT TO P64
ON DISPLAY AND I/O
BOARD
38
Installing a Liebert iCOM Unit-to-Unit Network
P67
P66
39
Installing a Liebert iCOM Unit-to-Unit Network
Liebert vNSA
The Liebert vNSA is designed to connect multiple Liebert iCOM control devices. The Liebert vNSA
contains either one or two powered industrial rail switches. An optional remote large display can be
attached to the front door as well. All models have a power supply that requires connection to a single
phase 230V or 120VAC power source. The enclosure features a key lock for security.
The Liebert vNSA supports autonegotiation, autopolarity and autocrossing, allowing for the use of
standard network cables for connection to each port, rather than special crossover cables. The switch
detects and makes adjustments for the network's speed and transmission mode, polarity and trans-
mit-and-receive pins. See the Liebert vNSA user manual, SL-18840, for more details.
The number of ports available for connecting Liebert iCOM control devices varies by model as shown
in Table 12. Models with a remote large display attached to the front door utilize one of the available
Ethernet ports in the Liebert vNSA. Models with two switches utilize two ports to connect the
switches.
Table 12 Ports available for connecting Liebert iCOM control devices
Liebert
vNSA With Number of Ports Number of Ports Number of Ports
Remote Used to Connect Used to Available to
Large Total Number Remote Large Interconnect Connect Liebert iCOM
Model Display of Ports Display Switches Control Devices
Liebert vNSA8-Liebert 8 1 - 7
iCOM
Yes
Liebert vNSA16- 16 1 2 13
Liebert iCOM
Liebert vNSA8 8 - - 8
No
Liebert vNSA16 16 - 2 14
3.298"
(84mm)
12"
(305mm)
14.25"
(362mm)
DPN001136
Rev. 0
40
Installing a Liebert iCOM Unit-to-Unit Network
41
Mounting a Large Display on a Wall
Mounting Instructions
1. See Figure 25 for dimensions and mounting arrangements. Mark the wall where screws or bolts
will be inserted to support the large display.
Either of two mounting methods may be used:
a. Secure the back of the large display to the wall by inserting screws or bolts through the
elliptical slots (recommended mounting method), or
b. Insert screws in the wall and use the keyhole-shaped holes on the back of the housing
2. Route the factory-supplied power supply cable and field-supplied CAT5e Ethernet cable through
the wall to the mounting location for connection to the rear of the Liebert iCOM wall-mount
display (see Figure 25).
3. Remove the back of the display by prying it away from the front half of the housing using the coin
slots along the seam.
4. Insert the power and Ethernet cables through slots in the rear of the display (slots are marked).
Leave adequate slack for connections and mounting.
To relieve strain on the connections to the display circuit board:
a. Use the strain-relief slots above the connections on the upper part of the recessed area to hold
the cables.
b. Use a twist tie to secure the cables to the small bridge on the back of the display.
5. Position the display and use either of the following methods to attach the display to the wall:
a. Elliptical Slot Mounting: Insert the #10 pan head screws or bolts through the elliptical slots
and screw into the wall or wall anchors. Tighten firmly.
OR
b. Keyhole Slot Mounting: Insert the #10 pan head screws or bolts into the wall, leaving space
between the screw head and wall to permit hanging the display.
6. Connect the power and Ethernet cables to the display circuit board (the board is marked).
7. Attach the front of the display to the mounted rear panel of the assembly—unit snaps together.
42
Mounting a Large Display on a Wall
AC Adaptor/Plug
230V/50Hz-12VDC
3.05m (10ft.) routed
through wall to back of
display housing 12V DC PWR SW/U2U
(provided by Emerson)
36mm 80mm
(1.40") (3.14")
224mm
(8.83")
115mm
(4.52") 105mm
(4.13")
43
User Menu Parameters
44
User Menu Parameters
45
User Menu Parameters
Active Alarms
Permits viewing all current, active alarms.
Table 20 Active alarms parameters
!
Function
ACTIVE
Read/ Range Default
ALARMS Large Display Small Display Write Metric (Imperial) Setting
Page 1 of 1
Active Alarms ACTIVE ALARMS R - -
46
User Menu Parameters
47
User Menu Parameters
9
12
3
Table 23 Timer parameters—Sleep Mode
6
Function
Read/ Range Default
Large Display Small Display Write Metric (Imperial) Setting
Page 1 of 1
Password PASSWORD W - -
Sleep On: - - - -
Mon MON W No, Yes No
Tue TUE W No, Yes No
Wed WED W No, Yes No
Thu THU W No, Yes No
Fri FRI W No, Yes No
Sat SAT W No, Yes No
Sun SUN W No, Yes No
Sleep Every Day (1) - - - -
START1 / START1 / 00:00
From / To W Time (hh:mm)
STOP1 / STOP1 00:00
Sleep Every Day (2) - - - -
START2 / START2 / 00:00
From / To W Time (hh:mm)
STOP2 / STOP2 00:00
48
Service Menu Parameters
Page 2 of 5
Password PASSWORD W - -
Humidity Setpoint HUM SET W 20-80% 50%
Relative, Compensated,
Humidity Control Type HUM CTRL W Predictive
Predictive
Humidity Proportional Band HUM PB W 1-20% 10%
Humidity Integration Time HUM INT W 0-15 min 0
Humidity Deadband HUM DB W 0-50% 0
LO LIM 1 -5.5 to -1.1K
Dehum/Heat Low Limit 1 W -
-9.9°F to -2.0°F
LO LIM 2 -5.5 to -1.1K
Dehum/Heat Low Limit 2 W -3.0K (-5.4°F)
-9.9°F to -2.0°F
Page 3 of 5
Password PASSWORD W - -
Supply Limit SUP LIM W Enabled, Disabled Disabled
Supply Limit Temp Value SUP TEMP W 5-25°C (41-77°F) 5°C (41°F)
FC: Value;
DT between Room / FC Type FC TYPE W No, Contact, Value
DX,CW: No
DT between Room Air/ FC Fluid FC DT W 0 - 20K (0-36°F) 5K (8°F)
FC: Yes
Minimum CW Temp MIN CW W No, Yes
DX,CW: No
Minimum CW Temp Value MIN CW W 0-20°C (32-68°F) 7°C (45°F)
49
Service Menu Parameters
°C / °F
Table 25 Setpoints parameters
% RH Function
Read/ Range Default
SET Large Display Small Display Write Metric (Imperial) Setting
Page 4 of 5
Password PASSWORD W - -
VSD Fanspeed FANSPEED W Auto, Manual, Economy Auto
DX =100%
VSD Setpoint STD VSD SET W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint MIN VSD MIN W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint Dehum VSD DEH W 60 to 100%
CW = 60%
DX =100%
VSD Setpoint No Power VSD NOP W 60 to 100%
CW = 60%
Page 5 of 5
Password PASSWORD W - -
SCR Control Type SCR TYPE W Tight, Standard Tight
Start Compressor 1 At CO1 ON W -150 to +100% 0%
Stop Compressor 1 At CO1 OFF W -200 to +50% -200%
Compressor 1 Stop Delay CO1 TD W 0-30 min 20 min
Start Compressor 2 At CO2 ON W -150 to +100% 100%
Stop Compressor 2 At CO2 OFF W -200 to +50% 0%
Compressor 2 Stop Delay CO2 TD W 0-30 min 0 min
Cycle Time CYCLET R 1.0 – 200.0 sec -
SCR Factor SCRFACT W 1.0 to 10.0 1.0
Actual SCR Request ACT SCR R 0-100% -
50
Service Menu Parameters
See 3.6.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
Table 28 Maintenance / wellness settings parameters
WELLNESS Function
Read/ Range Default
Large Display Small Display Write Metric (Imperial) Setting
Basic Settings (Page 1 of 8)
Password PASSWORD W - -
Maintenance Frequency Per Year FREQ/YR W 0-12 per year 1
Max Bonus BONUS W 0-12 0
Max Penalty PENALTY W 0-12 0
Last Maintenance LAST PM W Date -
Service Engineer SERVICE W Name -
Confirm PM CONFIRM W No, Yes -
Calculated Next Maintenance NEXT PM W Date -
51
Service Menu Parameters
52
Service Menu Parameters
53
Service Menu Parameters
Page 2 of 7
Password PASSWORD W - -
Manual Mode MANUAL W No, Yes -
Motor(s) MOTOR(S) W Off, On -
Compressor 1 COMP1 W Off, On -
Compressor 1 C1 MODE W Run, Evacuate, Charge -
Compressor 1 Capacity C1 CAP W Off, On -
Compressor 1 Cycle Ramp C1 CYCLE W 0-100% -
Compressor 1 LLSV LLSV 1 W Off, On -
Compressor 2 COMP2 W Off, On -
Compressor 2 C2 MODE W Run, Evacuate, Charge -
Compressor 2 Capacity C2 CAP W Off, On -
Compressor 2 Cycle Ramp C2 CYCLE W 0-100% -
Compressor 2 LLSV LLSV 2 W Off, On -
Page 3 of 7
Password PASSWORD W - -
Electric Heat 1 (or HG/HW) EL HEAT1 W Off, On -
Electric Heat 2 (or E.Heat 1) EL HEAT2 W Off, On -
Electric Heat 3 (or E.Heat 2) EL HEAT3 W Off, On -
BV Control BV CTRL W Manual, Auto -
LWD Value LWD Val R 0-100 -
Humidfier Fill HUM FILL W Off, On -
Humidifier HUM W Off, On -
Humidfier Drain H DRAIN W Off, On -
Humidifier Current HUM.C. R 0,00 - 99,99A -
54
Service Menu Parameters
Page 5 of 7
Status Remote Shutdown RSD R On, off -
Status Airflow Loss AIR LOSS R OK, Act -
Status Motor Overload MOTOR OL R OK, Act -
Status Filter FILTER R OK, Act -
Status Customer Input 1 CUSTOM 1 R OK, Act -
Status Customer Input 2 CUSTOM 2 R OK, Act -
Status Customer Input 3 CUSTOM 3 R OK, Act -
Status Customer Input 4 CUSTOM 4 R OK, Act -
-
Page 6 of 7
Status HP1 HP1 R OK, Act -
Status LP1 LP1 R OK, Act -
Status C1 OL C1 OL R OK, Act -
Status HP2 HP2 R OK, Act -
Status LP2 LP2 R OK, Act -
Status C2 OL C2 OL R OK, Act -
55
Service Menu Parameters
LWD Value R -
56
Service Menu Parameters
57
Service Menu Parameters
58
Service Menu Parameters
59
Service Menu Parameters
Page 2 of 3
Password PASSWORD W - -
Temperature Sensor A TEMP A W ±9.9°C (±18°F) -
Calibrated Temperature Sensor A CAL A R 0-50°C (32-122°F) -
Humidity Sensor A HUM A W ±9.9%rH -
Calibrated Humidity Sensor A CAL A R 20-80%rH -
Temperature Sensor B TEMP B W ±9.9°C (±18°F) -
Calibrated Temperature Sensor B CAL B R 0-50°C (32-122°F) -
Humidity Sensor B HUM B W ±9.9%rH -
Calibrated Humidity Sensor B CAL B R 20-80%rH -
Page 3 of 3
Password PASSWORD W - -
Freecool Sensor PTC or NTC FC SNSR W PTC, NTC NTC
Freecool Sensor FC SNSR W ±9.9°C (±18°F) -
Calibrated Freecool Sensor CAL FC R -15-45°C (4-113°F) -
Supply Sensor PTC or NTC SUP SNSR W PTC, NTC NTC
Supply Sensor SUP TEMP W ±9.9°C (±18°F) -
Calibrated Supply Sensor CAL SUP R 0-50°C (32-122°F) -
Temperature Sensor C TEMP C W ±9.9°C (±18°F) -
Calibrated Temperature Sensor C CAL C R 0-50°C (32-122°F) -
Humidity Sensor C HUM C W ±9.9%rH -
Calibrated Humidity Sensor C CAL C R 20-80%rH -
60
Service Menu Parameters
NETWORK
Table 33 Network setup parameters — SYSTEM (large display only)
Function
Read/ Range Default
Large Display Small Display Write Metric (Imperial) Setting
Page 1 of 2
Password PASSWORD W - -
Number of Connected —
W 1-32 -
Units
Teamwork Mode — W No,1,2 No
-
Page 2 of 2
Password PASSWORD W - -
IP Address — W IP Range -
Netmask — W Netmask Range -
Gateway — W Gateway Range -
MAC — R MAC Range -
U2U Protocol — W GBP -
U2U Address — W 33-64 -
U2U Group — W 1-99 -
-
— Not Available, Invalid, OK,
Bootloader Variables R -
Changed, Updating
Bootloader Variables — W No, Save+Reboot No
61
Service Menu Parameters
NETWORK
Table 34 Network setup parameters - UNIT (I/O board)
Function
Read/ Range Default
Large Display Small Display Write Metric (Imperial) Setting
Page 1 of 2
Password PASSWORD W - -
Monitoring Address MON ADD W 3
Page 2 of 2
Password PASSWORD W - -
Monitoring Protocol MON PROT W No, Velocity, Hironet, IGM -
IP Address IP #1, IP #2, IP #3, IP #4 W IP Range -
NM #1, NM #2, NM #3,
Netmask W Netmask Range -
NM #4
GW #1, GW #2, GW #3,
Gateway W Gateway Range -
GW #4
MAC MAC R MAC Range -
U2U Protocol U2U PROT W GBP -
U2U Address U2U ADD W 33-64 -
U2U Group — W 1-99 -
Not Available, Invalid, OK,
Bootloader Variables BL STAT R -
Changed, Updating
Bootloader Variables BL CTRL W No, Save+Reboot No
Not Available, Invalid, OK,
Static RAM SR STAT R -
Changed, Updating
Static RAM SR CTRL W No, Clear+Reboot No
62
Service Menu Parameters
Page 2 of 3
Password PASSWORD W - -
Humidification Enabled HUM ENAB W No, Yes Yes
Infrared Flush Rate IR FLUSH W 110-500% 150%
Humidifier Steam Rate R 0-100% -
Humidifier Bottle Flush Time HumFlush W 5-30 sec 5
Humidifier Bottle Manual Flush ManFlush W Yes, No No
Dehumidification Enabled DEHUM EN W No, Yes Yes
Auto Restart Enabled W No, Yes Yes
Single Unit Auto Restart RESTART W 0-999 sec 5
On-Off Enabled ONOFF EN W Yes, No Yes
Page 3 of 3
Password PASSWORD W - -
CW Flush CW FLUSH W 0-99 hours 0
Freecooling Flush FC FLUSH W 0-99 hours 0
Hot Water Flush HW FLUSH W 0-99 hours 0
63
Service Menu Parameters
64
Service Menu Parameters
Notes
65
Service Menu Parameters
66
Ensuring The High Availability
0f Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologies—including Liebert power and cooling www.liebert.com
technologies—that protect and support business-critical systems. Monitoring
800-222-5877
Liebert solutions employ an adaptive architecture that responds
[email protected]
to changes in criticality, density and capacity. Enterprises benefit Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and Single-Phase UPS
reduced capital equipment and operating costs. 800-222-5877
[email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
[email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of Asia
this information or for any errors or omissions. 7/F, Dah Sing Financial Centre
© 2007 Liebert Corporation 108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice. Hong Kong
® Liebert and the Liebert logo are registered trademarks of Liebert 852 2572220
Corporation. All names referred to are trademarks Fax: 852 28029250
or registered trademarks of their respective owners.
051536_REV0_05-08
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.
©2007 Emerson Electric Co.