Unit 1 - 03032025
Unit 1 - 03032025
Introduction
1
1.1 NEED FOR PROTECTIVE SYSTEMS
An electrical power system consists of generators, transformers, transmission and
distribution lines, etc. Short circuits and other abnormal conditions often occur on a
power system. The heavy current associated with short circuits is likely to cause dam-
age to equipment if suitable protective relays and circuit breakers are not provided for
the protection of each section of the power system. Short circuits are usually called
faults by power engineers. Strictly speaking, the term ‘fault’ simply means a ‘defect’.
Some defects, other than short circuits, are also termed as faults. For example, the
failure of conducting path due to a break in a conductor is a type of fault.
If a fault occurs in an element of a power system, an automatic protective device
is needed to isolate the faulty element as quickly as possible to keep the healthy sec-
tion of the system in normal operation. The fault must be cleared within a fraction of
a second. If a short circuit persists on a system for a longer, it may cause damage to
some important sections of the system. A heavy short circuit current may cause a fire.
It may spread in the system and damage a part of it. The system voltage may reduce
to a low level and individual generators in a power station or groups of generators
in different power stations may lose synchronism. Thus, an uncleared heavy short
circuit may cause the total failure of the system.
A protective system includes circuit breakers, transducers (CTs and VTs), and
protective relays to isolate the faulty section of the power system from the healthy
sections. A circuit breaker can disconnect the faulty element of the system when it
is called upon to do so by the protective relay. Transducers (CTs and VTs) are used
to reduce currents and voltages to lower values and to isolate protective relays from
the high voltages of the power system. The function of a protective relay is to detect
and locate a fault and issue a command to the circuit breaker to disconnect the faulty
element. It is a device which senses abnormal conditions on a power system by con-
stantly monitoring electrical quantities of the systems, which differ under normal and
abnormal conditions. The basic electrical quantities which are likely to change dur-
ing abnormal conditions are current, voltage, phase-angle (direction) and frequency.
Protective relays utilise one or more of these quantities to detect abnormal conditions
on a power system.
Protection is needed not only against short circuits but also against any other
abnormal conditions which may arise on a power system. A few examples of other
abnormal conditions are overspeed of generators and motors, overvoltage, under-
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 3
Sometimes, circuit breakers may trip due to errors in the switching operation, test-
ing or maintenance work, wrong connections, defects in protective devices, etc.
Certain faults occur due to the poor quality of system components or because
of a faulty system design. Hence, the occurrence of such faults can be reduced by
improving the system design, by using components and materials of good quality and
by better operation and maintenance.
Winding Faults
All types of faults discussed above also occur on the alternator, motor and trans-
former windings. In addition to these types of faults, there is one more type of fault,
namely the short circuiting of turns which occurs on machine windings.
Introduction 5
From Table 1.1, it is evident that 50% of the total faults occur on overhead lines.
Hence it is overhead lines that require more attention while planning and designing
protective schemes for a power system.
Table 1.2 shows the frequency of occurrence of different types of faults (mainly
the different types of short circuits) on overhead lines. From the table it is evident that
the frequency of line to ground faults is more than any other type of fault, and hence
the protection against L-G fault requires greater attention in planning and design of
protective schemes for overhead lines.
In the case of cables, 50% of the faults occur in cables and 50% at end junctions.
Cable faults are usually of a permanent nature and hence, automatic reclosures are
not recommended for cables.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 7
Magnetic amplifiers were also used in protective relays in the past. A magnetic
amplifier consists of a transformer and a separate dc winding. As the transformer
action is controlled by the dc winding, the device is also known as transductor. This
type of relay is rugged but slow in action. At present, such relays are not used.
Hall crystals were also used to construct phase comparators. Because of their low
output and high-temperature errors, such relays have not been widely adopted except
in Russian countries.
The first transistorised relay was developed in 1949, soon after the innova-
tion of the transistor. Various kinds of static relays using solid-state devices were
developed in the fifties. Multi-input comparators giving quadrilateral characteristics
were developed in the sixties. Static relays possess the advantages of low burden on
the CT and VT, fast operation, absence of mechanical inertia and contact troubles,
long life and less maintenance. As static relays proved to be superior to electrome-
chanical relays, they were used for the protection of important lines, power stations
and sub-stations. But they did not replace electromechanical relays. Static relays were
treated as an addition to the family of relays. In most static relays, the output or slave
relay is a polarised dc relay which is an electromechanical relay. This can be replaced
by a thyristor circuit, but it is used because of its low cost. Electromechanical relays
have continued to be used because of their simplicity and low cost. Their mainte-
nance can be done by less qualified personnel, whereas the maintenance and repair
of static relays requires personnel trained in solid-state devices. Static relays using
digital techniques have also been developed.
Static relays appeared to be the technology poised to replace the electromechani-
cal counterparts in the late sixties when researchers ventured into the use of comput-
ers for power system protection. Their attempts and the advances in the Very Large
Scale Integrated (VLSI) technology and software techniques in the seventies led to
the development of microprocessor-based relays that were first offered as commer-
cial devices in 1979. Early designs of these relays used the fundamental approaches
that were previously used in the electromechanical and static relays.
In spite of the developments of complex algorithms for implementing protection
functions, the microprocessor-based relays marketed in the eighties did not incor-
porate them. These relays performed basic functions, took advantage of the hybrid
analog and digital techniques, and offered a good economical solution. At present,
in microprocessor-based relays, different relaying algorithms are used to process the
acquired information. Microprocessor/Microntroller-based relays are called numeri-
cal relays specifically if they calculate the algorithm numerically.
The modern power networks which have grown both in size and complexity
require fast accurate and reliable protective schemes to protect major equipment
and to maintain system stability. Increasing interest is being shown in the use of
on-line digital computers for protection. The concept of numerical protection
employing computers which shows much promise in providing improved perfor-
mance has evolved during the past three decades. In the beginning, the numerical
protection (also known as digital protection) philosophy was to use a large computer
system for the total protection of the power system. This protection system proved
to be very costly and required large space. If a computer is required to perform other
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 9
work in this area includes feedback systems in which relays continuously monitor
the operating state of the power system and automatically reconfigure themselves
for providing optimal protection.
Generator protection
Circuit breaker
HV Switchgear protection
Transformer protection
Introduction 11
the simplest form of back-up protection and is a widely used back-up protection for
transmission lines. It is most desirable because of the fact that it will not fail due to
the factors causing the failure of the primary protection.
an auxiliary relay. Thus, we see that a protective relay must be able to discriminate
between those conditions for which instantaneous tripping is required and those for
which no operation or a time-delay operation is required.
1.9.2 Reliability
A protective system must operate reliably when a fault occurs in its zone of protection.
The failure of a protective system may be due to the failure of any one or more ele-
ments of the protective system. Its important elements are the protective relay, circuit
breaker, VT, CT, wiring, battery, etc. To achieve a high degree of reliability, greater
attention should be given to the design, installation, maintenance and testing of the
various elements of the protective system. Robustness and simplicity of the relaying
equipment also contribute to reliability. The contact pressure, the contact material of
the relay, and the prevention of contact contamination are also very important from
the reliability point of view. A typical value of reliability of a protective scheme is
95%.
1.9.3 Sensitivity
A protective relay should operate when the magnitude of the current exceeds the
preset value. This value is called the pick-up current. The relay should not operate
when the current is below its pick-up value. A relay should be sufficiently sensitive
to operate when the operating current just exceeds its pick-up value.
1.9.4 Stability
A protective system should remain stable even when a large current is flowing through
its protective zone due to an external fault, which does not lie in its zone. The con-
cerned circuit breaker is supposed to clear the fault. But the protective system will
not wait indefinitely if the protective scheme of the zone in which fault has occurred
fails to operate. After a preset delay the relay will operate to trip the circuit breaker.
Introduction 13
begin to operate. They do not initiate tripping if the primary relays operate correctly.
Information regarding operation of these back-up relays is not available when they
do not trip. The back-up relay operates, if due to any reason the primary relay fails
to operate. Though several primary relays are employed in many protection sys-
tems, but frequently only one of the relays actually initiates tripping of the circuit
breaker. There may be no direct evidence regarding the other relays being in a correct
operating mode.
The performance of the protective relay is documented by those relays that
provide direct or specific evidence of operation. Relay performance is generally clas-
sified as
(i) Correct operation
(ii) Incorrect operation
(iv) No conclusion
1.10.1 Correct Operation
Correct operation of the relay can be either wanted or unwanted. The correct opera-
tion gives indication about (i) correct operation of atleast one of the primary relays,
(ii) operation of none of the back-up relays to trip for the fault, and (iii) proper isola-
tion of the trouble area in the expected time.
Almost all relay operations are corrected and wanted, i.e., the operation is as per
plan and programme. There are the few cases of the correct but unwanted operation.
If all relays and associated equipment perform correctly when their operation is not
desired or anticipated, it is called “correct but unwanted operation.”
1.10.3 No Conclusion
When one or more relays have or appear to have operated, such as the tripping of the
circuit breaker, but no cause of operation can be found, it is the case of ‘no conclu-
sion’. Neither any evidence of a power system fault or trouble, nor apparent failure
of the equipment, causes and extremely frustrating situation. Thus the cases of no
conclusion involves considerable concern and thorough investigation. It is suspected
that many of the cases of ‘no conclusion’ may be the result of personnel involvement
which is not reported. Modern oscillographs and data-recording equipment which
are being used nowaday in many power systems often provide direct evidence or
clues regarding the problem, as well as indicating possibilities that could not have
occurred.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 15
either a slave relay or a thyristor circuit. The slave relay is an electromagnetic relay
which finally closes the contact. A static relay containing a slave relay is a semi-static
relay. A relay using a thyristor circuit is a wholly static relay. Static relays possess
the advantages of having low burden on the CT and VT, fast operation, absence of
mechanical inertia and contact trouble, long life and less maintenance. Static relays
have proved to be superior to electromechanical relays and they are being used for
the protection of important lines, power stations and sub-stations. Yet they have not
completely replaced electromechanical relays. Static relays are treated as an addi-
tion to the family of relays. Electromechanical relays continue to be in use because
of their simplicity and low cost. Their maintenance can be done by less qualified
personnel, whereas the maintenance and repair of static relays requires personnel
trained in solid state devices.
Numerical Relays
Numerical relays are the latest development in this area. These relays acquire the
sequential samples of the ac quantities in numeric (digital) data form through the
data acquisition system, and process the data numerically using an algorithm to cal-
culate the fault discriminants and make trip decisions. Numerical relays have been
developed because of tremendous advancement in VLSI and computer hardware
technology. They are based on numerical (digital) devices, e.g., microprocessors,
microcontrollers, Digital Signal Processors (DSPs), etc. At present microprocessor/
microcontroller-based numerical relays are widely used. These relays use different
relaying algorithms to process the acquired information. Microprocessor/micro-
controller-based relays are called numerical relays specifically if they calculate the
algorithm numerically. The term ‘digital relay’ was originally used to designate a
previous-generation relay with analog measurement circuits and digital coincidence
time measurement (angle measurement) using microprocessors. Now a days the term
‘numerical relay’ is widely used in place of ‘digital relay’. Sometimes, both terms are
used in parallel. Similarly, the term ‘numerical protection’ is widely used in place of
‘digital protection’. Sometimes both these terms are also used in parallel.
The present downward trend in the cost of Very Large Scale Integrated (VLSI)
circuits has encouraged wide application of numerical relays for the protection of
modern complex power networks. Economical, powerful and sophisticated numeri-
cal devices (e.g., microprocessors, microcontrollers, DSPs, etc) are available today
because of tremendous advancement in computer hardware technology. Various effi-
cient and fast relaying algorithms which form a part of the software and are used to
process the acquired information are also available today. Hence, there is a growing
trend to develop and use numerical relays for the protection of various components
of the modern complex power system. Numerical relaying has become a viable alter-
native to the traditional relaying systems employing electromechanical and static
relays. Intelligent numerical relays using artificial Intelligence techniques such as
Artificial Neural Networks (ANNs) and Fuzzy Logic Systems are presently under
active research and development stage.
The main features of numerical relays are their economy, compactness, flexibility
reliability, self-monitoring and self-checking capability, multiple functions, low bur-
den on instruments transformers and improved performance over conventional relays
of electromechanical and static types.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 17
Introduction 19
feeding from its charger, and connected to its own complement of relays. Since the
severe transients produced by the electromechanical relays on the battery loads dur-
ing their operation may cause maloperation of other sensitive relays in the substation,
or may even damage them, it is common practice, as far as practicable, to separate
electromechanical and static equipment by connecting them to different batteries.
winding of a machine. The outputs of their secondaries are applied to the relay coils.
The relay compares the current entering a machine winding and leaving the same.
Under normal conditions or during any external fault, the current entering the wind-
ing is equal to the current leaving the winding. But in the case of an internal fault
on the winding, these are not equal. This difference in the current actuates the relay.
Thus, the relay operates for internal faults and remains inoperative under normal
conditions or during external faults. In case of bus zone protection, CTs are placed
on the both sides of the bus bar.
Introduction 21
the protective relays also have the same current rating. The current transformers are
designed to withstand fault currents (which may be as high as 50 times the full load
current) for a few seconds. Protective relays require reasonably accurate reproduc-
tion of the normal and abnormal conditions in the power system for correct sens-
ing and operation. Hence the current transformers should be able to provide current
signals to the relays which are faithful reproductions of the primary currents. The
measure of a current transformer performance is its ability to accurately reproduce
the primary current in secondary.
The requirements of CTs used for relaying are quite different from those of meter-
ing (CTs for measuring instruments). CTs used for instrumentation are required to be
accurate over the normal working range of currents, whereas CTs used for relaying
are required to give a correct ratio up to several times the rated primary current. The
CTs used for metering may have very significant errors during fault conditions, when
the currents may be several times their normal value for a very short time. Since
metering functions are not required during faults, this is not significant. CTs used
for relaying are designed to have small errors during fault conditions, whereas their
performance during normal steady state condition, when the relay is not required to
operate, may not be as accurate.
The accuracy of a current transformer is expressed in terms of the departure of its
ratio form its true ratio. This is called the ratio error, and is expressed as:
[ ]
NIs – Ip
Percent error = _______ × 100
Ip
where, N = Nominal CT ratio
Rated primary current
= ____________________
Rated secondary current
Number of secondary turns
= _______________________
Number of primary turns
Is = Secondary current, and
Ip = Primary current
The ratio error of a CT depends on its exciting current.
Current transformers are of electromagnetic, opto-electronic and Rogowski coil
types. The electromagnetic type CTs which are magnetically coupled, multi-winding
transformers can be classified into two categories: toroidal or bar primary CTs and
wound primary CTs. Toroidal or bar-primary-type CTs, donot contain a primary
winding and instead a straight conductor, (wire) which is a part of the power system
and carries the current, acts as the primary. The conductor (wire) that carries the cur-
rents is encircled by a ring-type iron core on which the secondary winding is wound
over the entire periphery. Wound-type CTs consist of a primary winding of fewer
turns wound on the iron core and inserted in series with the conductor that carries the
measured-current.
An opto-electronic or optical CT uses two light beams travelling through an opti-
cal fiber to measure the magnetic field around a current-carrying conductor, which
Dr. Raju Chintakindi EEE Vaagdevi
gives a measure of the current flowing in the conductor. The phase displacement
between the two beams is proportional to the level of current in the conductor.
The Rogowski Coil (RC) is a helical coil of wire with the lead from one end
returning through the centre of the coil to the other end, so that both are at the same
end of the coil. The whole assembly is then wrapped around the straight conduc-
tor whose current is to be measured. Since the voltage that is induced in the coil is
proportional to the rate of change (derivative) of current in the conductor, the output
of the Rogowski coil is usually connected to an electrical (or electronic) integrator
circuit to provide an output signal that is proportional to the current.
Current transformers are described in detail in Chapter 3.
(
KVs – Vp
)
Percent ratio error = ________ × 100
Vp
where, K = Nominal voltage ratio
Rated primary voltage
= ____________________
Rated secondary voltage
Number of primary turns
= _______________________
Number of secondary turns
Vs = Secondary voltage, and
Vp = Primary voltage
Ideally a VT should produce a secondary voltage which is exactly proportional and
in phase opposition to the primary voltage. But, in practice, this cannot be achieved
owing to the voltage drops in the primary and secondary windings due to magnitude
and power factor of the secondary burden. Thus, ratio and phase angle errors are
introduced.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 23
Setting: The value of the actuating quantity at which the relay is set to operate.
Seal-in relay: This is a kind of an auxiliary relay. It is energised by the contacts of
the main relay. Its contacts are placed in parallel with those of the main relay and is
designed to relieve the contacts of the main relay from their current carrying duty. It
remains in the circuit until the circuit breaker trips. The seal-in contacts are usually
heavier than those of the main relay.
Reinforcing relay: This is a kind of an auxiliary relay. It is energised from the con-
tacts of the main relay. Its contacts are placed in parallel with those of the main relay
and it is also designed to relieve the main relay contacts from their current carrying
duty. The difference between a reinforcing relay and a seal-in relay is that the latter
is designed to remain in the circuit till the circuit breaker operates. But this is not
so with the reinforcing relay. The reinforcing relay is used to hold a signal from the
initiating relay (main relay) for a longer period. As the contacts of the main relay are
not robust, they are closed for a short time.
Back-up relay: A back-up relay operates after a slight delay, if the main relay fails
to operate.
Back-up protection: The back-up protection is designed to clear the fault if the
primary protection fails. It acts as a second line of defence.
Primary protection: If a fault occurs, it is the duty of the primary protective scheme
to clear the fault. It acts as a first line of defence. If it fails, the back-up protection
clears the fault.
Measuring relay: It is the main protective relay of the protective scheme, to which
energising quantities are applied. It performs measurements to detect abnormal con-
ditions in the system to be protected.
Auxiliary relays: Auxiliary relays assist protective relays. They repeat the opera-
tions of protective relays, control switches, etc. They relieve the protective relays of
duties like tripping, time lag, sounding and alarm, etc. They may be instantaneous or
may have a time delay.
Electromagnetic relay: A relay which operates on the electromagnetic principle,
i.e., an electromagnet attracts magnetic moving parts (e.g.,) plunger type moving
iron type, attracted armature type). Such a relay operates principally by action of an
electromagnetic element which is energized by the input quantity.
Electromachanical relay: An electrical relay in which the designed response is
developed by the relative movement of mechanical elements under the action of a
current in the input circuit. Such relay operates by physical movement of mechanical
parts resulting from electromagnetic or electrothermic forces created by the input
quantities.
Electrodynamic relay: A relay which has two or more coils and- operates due to
interaction of fluxes produced by the individual coils
Ferrodynamic relay: A relay in which the electrodynamic action is reinforced by
pieces of ferromagnetic material placed in the path of magnetic lines of force.
Static relays: These are solid state relays and employ semiconductor diodes, tran-
sistors, thyristors, logic gates, ICs, etc. The measuring circuit is a static circuit and
there are no moving parts. In some static relays, a slave relay which is a dc potarised
relay is used as the tripping device.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 25
Analog relay: An analog relay is that in which the measured quantities are con-
verted into lower voltage but similar signals, which are then combined or compared
directly to reference values in level detectors to produce the desired output.
Digital relay: A digital relay is that in which the measured ac quantities are manipu-
lated in analog form and subsequently converted into either square-wave voltages or
digital form. Logic circuits or microprocessors compare either the phase relation-
ships of the square waves or the magnitudes of the quantities in digital form to make
a trip decision.
Numerical relay: A numerical relay is that in which the measured ac quanti-
ties are sequentially sampled and converted into numerical (digital) data form. A
microprocessor or a microcontroller processes the data numerically (i.e., performs
mathematical and/or logical operations on the data) using an algorithm to calculate
the fault discriminants and make trip decisions.
Microprocessor-based relay: A microprocessor is used to perform all functions
of a relay. It measures electrical quantities, makes comparisons, performs computa-
tions, and sends tripping signals. It can realise all sorts of relaying characteristics,
even irregular curves which cannot be reslised by electromechanical or static relays
easily.
Microcontroller-based relay: A microcontroller is used for performing all the
function of the relay. It measures the electrical quantities by acquiring them in digital
form through a data acquisition system, makes comparisons, processes the digital
data to calculate the fault discriminants and make trip decisions. It can realise all
sorts of relaying characteristics.
DSP-based relay: A Digital Signal Processor (DSP) is used to perform all the func-
tions of a relay.
FPGA-based relay: A Field Programmable Gate Array (FPGA) is used to perform
all the functions of a relay. It acquires the signals, processes them to calculate the
fault discriminants and make trip decisions.
ANN-based relay: An Artificial Neural Network (ANN) is used for processing the
relaying signals (current and voltage signals) and making trip decisions.
Overcurrent relay: A relay which operates when the actuating current exceeds a
certain preset value (its pick-up value).
Undervoltage relay: A relay which operates when the system voltage falls below a
certain preset value.
Directional or reverse power relay: A directional relay is able to detect whether
the point of fault lies in the forward or reverse direction with respect to the relay loca-
tion. It is able to sense the direction of power flow, i.e. whether the power is flowing
in the normal direction or the reverse direction.
Polarised relay: A relay whose operation depends on the direction of current or
voltage.
Flag or target: Flag is a device which gives visual indication whether a relay has
operated or not.
Time-lag relay: A time-lag relay operates after a certain preset time lag. The time
lag may be due to its inherent design feature or may be due to the presence of a time-
Dr. Raju Chintakindi EEE Vaagdevi
delay component. Such relays are used in protection schemes as a means of time
discrimination. They are frequently used in control and alarm schemes.
Instantaneous relay: An instantaneous relay has no intentional time delay in its
operation. It operates in 0.1 second. Sometimes the terms high set or high speed
relays are also used for the relays which have operating times less than 0.1 second.
Inverse time relay: A relay in which the operating time is inversely proportional to
the magnitude of the operating current.
Definite time relay: A relay in which the operating time is independent of the mag-
nitude of the actuating current.
Inverse Definite Minimum Time (IDMT) Relay: A relay which gives an inverse
time characteristic at lower values of the operating current and definite time charac-
teristic at higher values of the operating current.
Induction relay: A relay which operates on the principle of induction.
Examples are induction disc relays, induction cup relays etc.
Moving coil relay: This type of a relay has a permanent magnet and a moving coil.
It is also called a permanent magnet d.c. moving coil relay. The actuating current
flows in the moving coil.
Moving iron relay: This is a dc polarised, moving iron type relay. There is an elec-
tromagnet, permanent magnet and a moving armature in its construction.
Printed disc relay: This relay operates on the principle of a dynamometer. There is
a permanent magnet or an electromagnet and a printed disc. Direct current is fed to
the printed circuit of the disc.
Thermal relay: This relay utilises the electrothermal effect of the actuating current
for its operation.
Distance relay: A relay which measures impedance or a component of the imped-
ance at the relay location is known as a distance relay. It is used for the protection of a
transmission line. As the impedance of a line is proportional to the length of the line,
a relay which measures impedance or its component is called a distance relay.
Impedance relay: A relay which measures impedance at the relay location is called
an impedance relay. It is a kind of a distance relay.
Modified impedance relay: It is an impedance relay having shifted characteristics.
The voltage coil includes some current biasing.
Reactance relay: A relay which measures reactance at the relay location is called a
reactance relay. It is a kind of a distance relay.
MHO relay (admittance or angle admittance): This is a kind of a distance relay.
Z
It measures a particular component of the impedance, i.e. _________, where f is the
cos (f – q)
power factor angle and q is the design angle to shift MHO characteristic on the R-X
diagram. Its characteristic on the R-X diagram is a circle passing through the origin.
It is a directional relay. It is also known as an admittance or angle admittance relay.
Conduction relay: This is a MHO relay whose diameter (passing through the ori-
gin) lies on the R-axis.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 27
Primary relay: A relay which is directly connected to the protected circuit without
interposing instrument transformers or shunt.
Secondary relay: A relay connected to the protected circuit through current and
voltage transformers.
Sequential relay: A relay which instantaneously transfers its contact position from
a particular combination of ‘off’ and ‘on’ position to another combination, every time
it picks up or drops off, according to a predetermined programme which may or may
not be adjustable and repetitive
Indicating relay: A measuring or auxiliary relay which displays a signal on
energisation
Reclosing relay: This relay establishes a closing sequence for a circuit breaker fol-
lowing tripping by protective relays.
Supervisory relay: A measuring relay or a combination of measuring and auxiliary
relays in a unit with a definite purpose of supervision.
Change over relay: An auxiliary relay with two positions either of which cannot
be designated as ‘on’ and ‘off’ but which transfers the contact circuits from one con-
nection to the other.
Two-step relay: A relay with two sets of contacts, one of them operates at a cer-
tain value of the characteristic quantity and the other after a further change of the
quantity.
Current unbalance relay: This relay operates when the currents in a polyphase
system are unbalanced by a predetermined amount.
Voltage unbalanced relay: This relay operates when the voltages in a poly phase
system are unbalanced by a predetermined amount.
Ferraris relay: This relay moves by the interaction of the magnetic field of a coil
and the currents induced in a metal body (disc or cup)
Protective zone: A power system is divided into a number of zones from the pro-
tection point of view. Each element of the power system has a separate protective
scheme for its protection. The elements which come under a protective scheme are
said to be in the zone of protection of that particular scheme. Similarly, a protective
relay has its own zone of protection.
Reach: This term is mostly used in connection with distance relays. A distance relay
operates when the impedance (or a component of the impedance) as seen by the relay
is less than a preset value. This preset impedance (or a component of impedance) or
corresponding distance is called the reach of the relay. In other words, it is the maxi-
mum length of the line up to which the relay can protect.
Overreach: Sometimes a relay may operate even when a fault point is beyond its
present reach (i.e. its protected length).
Underreach: Sometimes a relay may fail to operate even when the fault point is
within its reach, but it is at the far end of the protected line. This phenomenon is
called underreach.
Selectivity or discrimination: It is the ability of a relay to discriminate between
faulty conditions and normal conditions (or between a fault within the protected
section and outside the protected section). In other words, it is the quality of the
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 29
current and time grading of the relays of several zones. In this situation, all relays
may respond to a given fault. Examples of non-unit system of protection are dis-
tance protection and time graded, current graded or both time and current graded
protection.
Restricted earth fault protection: This is an English term which may be misunder-
stood in other countries. It is used in the context of transformer or alternator. It refers
to the differential protection of transformers or alternators against ground faults. It is
called restricted because its zone of protection is restricted only to the winding of the
alternator or transformer. The scheme responds to the faults occurring within its zone
of protection. It does not respond to faults beyond its zone of protection.
Unrestricted protection: A protection system which has no clearly defined zone of
operation and which achieves selective operation only by time grading.
Protective gear or equipment: It includes transducers (CTs and VTs), protective
relays, circuit breakers and ancillary equipment to be used in a protective system.
Protective system: It is a combination of Protective gear equipment to
secure isolation of the faulty element under predetermined conditions, usually
abnormal or to give an alarm signal or both.
Protective scheme: A protective scheme may consist of several protective systems.
It is designed to protect one or more elements of a power system.
Residual current: It is the algebraic sum of all currents in a multiphase
system. It is denoted by Ires. In a 3-phase system Ires = IA + IB + IC.
Transducers or instrument transformers: Current and voltage transformers (CTs
and VTs) are collectively known as transducers or instrument transformers. They are
used to reduce currents and voltages to standard lower values and to isolate protective
relays and measuring instruments from the high voltages of the power system.
Switchgear: It is a general term covering switching and interrupting devices and
their combination with associated control, metering, protective and regulating
devices, also assemblies of these devices with associated inter-connections, accesso-
ries, enclosures and supporting structures used primarily in connection with genera-
tion, transmission, distribution, and conversion of electric power.
Circuit breaker: It is a mechanical switching device capable of making, carrying
and breaking currents under normal circuit conditions and also making, carrying for a
specified time, and automatically breaking currents under specified abnormal circuit
conditions such as those of short circuit. The medium in which circuit interruption
is performed may be designated by suitable prefix, such as, oil-circuit breaker, air-
blast circuit breaker, air-break circuit breaker, sulphur hexafluoride circuit breaker,
vacuum circuit breaker, etc.
Adaptive relaying: Adaptive relaying is defined as the protection system whose
settings can be changed automatically so that it is attuned to the prevailing power
system conditions.
Pilot wire: An auxiliary conductor used in connection with remote measuring
devices or for operating apparatus at a distant point.
Pilot protection: A form of line protection that uses a communication channel as a
means to compare electrical conditions at the terminals of a line.
Dr. Raju Chintakindi EEE Vaagdevi
Introduction 31
Pilot wire protection: Pilot protection in which a metallic circuit is used for the
communicating means between relays at the circuit terminals.
EXERCISES
1. Explain the nature and causes of faults. Discuss the consequences of faults
on a power system.
2. What are the different types of faults? Which type of fault is most
dangerous?
3. Discuss briefly the role of protective relays in a modern power system.
4. What do you understand by a zone of protection? Discuss various zones of
protection for a modern power system.
5. Explain what you understand by primary and back-up protection. What is
the role of back-up protection? What are the various methods of providing
back-up protection?
6. Explain what you understand by pick-up and reset value of the actuating
quantity.
7. Discuss what you understand by selectivity and stability of protective relay.
8. Discuss the essential qualities of a protective relay.
9. How is the relay performance classified? What indication the correct opera-
tion of the relay gives? What do you mean by “correct but unwanted opera-
tion”?
10. What do you understand by incorrect operation of the protective relay? What
are the reasons of incorrect operation?
11. Discuss the classification of protective relays based on their speed of opera-
tion.
12. Differentiate between a digital relay and a numerical relay.
13. What is a numerical relay? Discuss its advantages over conventional relays
of electromechanical and static types. How can an intelligent numerical relay
be developed.
14. What are the various components of a protection system? Briefly describe
their functions with the help of an schematic diagram.
15. Differentiate between a protective system and a protective scheme.
16. What do you understand by adaptive relaying? How can a relay be made
adaptive?
17. Briefly describe the following types of relay.
(i) Monitoring relay (ii) Regulating relay (iii) Auxiliary relay (iv) Synchroniz-
ing relay, and (v) Biased relay.
Dr. Raju Chintakindi EEE Vaagdevi
Bus bar
3-f Line
Station battery
VT
CB Trip
coil
CB- Circuit breaker
Contact CT- Current transformer
VT- Voltage transformer
CC- Current coil of the
relay
VC- Voltage coil of the
CT CC VC relay
Relay
Protective relays are broadly classified into the following three categories
depending on the technologies they use for their construction and operation.
(i) Electromechanical relays
(ii) Static relays
(iii) Numerical relays
There are various types of protective relays in each category, depending on the
operating principle and application.
Electromagnet
Coil
I C
Armature R Armature
I
(a) (b)
Fig. 2.2 (a) Hinged armature-type relay (b) Modi ied hinged armature-type relay
The actuating quantity of the relay may be either ac or dc. In dc relay, the electro-
magnetic force of attraction is constant. In the case of ac relays, sinusoidal current
flows through the coil and hence the force of attraction is given by
1
F = K I2 = K (Imax sin wt)2 = __ K (I2max – I2max cos 2wt)
2
From the above expression, it is evident that the electromagnetic force consists
of two components. One component is constant and is equal to ½ K I2max. The other
component is time dependent and pulsates at double the frequency of the applied ac
quantity. Its magnitude is ½ K I2max cos 2wt. The total force is a double frequency
pulsating force. This may cause the armature to vibrate at double the frequency.
Consequently, the relay produces a humming sound and becomes noisy. This
difficulty can be overcome by making the pole of the electromagnet of shaded
construction. Alternatively, the electromagnet may be provided with two coils. One
coil is energised with the actuating quantity. The other coil gets its supply through a
phase shifting circuit.
Dr. Raju Chintakindi EEE Vaagdevi
The restraining force is provided by a spring. The reset to pick-up ratio for
attracted armature type relays is 0.5 to 0.9. For this type of a relay, the ratio for
ac relays is higher as compared to dc relays. The VA burden is low, which is
0.08 W at pick-up for the relay with one contact, 0.2 W for the relay with four
contacts. The relay is an instantaneous relay. The operating speed is very high. For a
modern relay, the operation time is about 5 ms. It is faster than the induction disc and
cup type relays. Attracted armature relays are compact, robust and reliable. They are
affected by transients as they are fast and operate on both dc and ac. The fault current
contains a dc component in the beginning for a few cycles. Due to the presence of dc
transient, the relay may operate though the steady state value of the fault current may
be less than its pick-up. A modified construction as shown in Fig. 2.2(b) reduces the
effect of dc transients.
Plunger-Type Relays
Figure 2.3 shows a plunger-type relay.
In this type of a relay, there is a solenoid Solenoid
and an iron plunger which moves in and
Plunger
out of the solenoid to make and break the
contact. The movement of the plunger Contacts
is controlled by a spring. This type of
Spring
construction has however become obsolete
as it draws more current.
Fig. 2.3 Plunger-type relay
Balanced Beam Relays
Figure 2.4 shows a balanced beam relay which is also a kind of attracted armature
type relay. As its name indicates, it consists of a beam carrying two electromagnets
at its ends. One gives operating torque while the other retraining torque. The beam
is supported at the middle and it remains horizontal under normal conditions. When
the operating torque exceeds the restraining torque, an armature fitted at one end of
the beam is pulled and its contacts are closed. Though now obsolete, this type of a
relay was popular in the past for constructing impedance and differential relays. It
has been superseded by rectifier bridge comparators and permanent magnet moving
coil relays. The beam type relay is robust and fast in operation, usually requiring only
1 cycle, but is not accurate as it is affected by dc transients.
Contacts
Ir Pivote Io
Shading
ring
I
Disc
N Brake
S magnet
Disc
I
N S
S N
Plug setting
(PS) Brake
magnet
In wattmetric type of construction, two electromagnets are used: upper and lower
one. Each magnet produces an alternating flux which cuts the disc. To obtain a phase
displacement between two fluxes produced by upper and lower electromagnets, their
coils may be energised by two different sources. If they are energised by the same
source, the resistances and reactances of the two circuits are made different so that
there will be sufficient phase difference between the two fluxes.
Induction disc type construction is robust and reliable. It is used for overcurrent
protection. Disc type units gives an inverse time current characteristic and are slow
Dr. Raju Chintakindi EEE Vaagdevi
compared to the induction cup and attracted armature type relays. The induction disc
type is used for slow-speed relays. Its operating time is adjustable and is employed
where a time-delay is required. Its reset/pick-up ratio is high, above 95% because its
operation does not involve any change in the air gap. The VA burden depends on its
application, and is generally of the order of 2.5 VA. The torque is proportional to the
square of the actuating current if single actuating quantity is used.
Relay
coil
Secondary
coil
Disc
N To trip circuit
S
against a backstop. The position of the backstop is adjustable and therefore, the dis-
tance by which the moving contact of the relay travels before it closes contacts, can
be varied. The distance of travel is adjusted for the time setting of the relay.
The rotor (disc) carries an arm which is attached to its spindle. The spindle is
supported by jewelled bearings. The arm bridges the relay contacts. In earlier
constructions, there were two contacts which were bridged when the relay operated.
In modern units however, there is a single contact with a flexible lead-in.
Current Setting
In disc type units, there are a number of tapping provided on coil to select the desired
pick-up value of the current. These tapping are shown in Fig. 2.10. This will be
discussed in the next chapter.
Time Setting
The distance which the disc travels before it closes the relay contact can be adjusted
by adjusting the position of the backstop. If the backstop is advanced in the normal
direction of rotation, the distance of travel is reduced, resulting in a shorter operating
time of the relay. More details on time-setting will be discussed in the next chapter.
Printed Disc Relay
Figure 2.11 shows the construction of a printed disc inverse time relay. Its operating
principle is the same as that of a dynamometer type instrument.
Trip
Torque
There is a permanent magnet to produce a magnetic field. The current from the
CT is fed to the printed disc through a rectifier. When a current carrying conductor is
placed in a magnetic field, a force is developed, thereby a torque is exerted on it. On
this very principle, torque is produced in a printed disc relay.
Figure 2.12 shows the construction of a printed disc extremely inverse time relay
(I2t = K relay). To obtain I2t = K characteristic, an electromagnet and a printed disc
are used. The electromagnet is energised from the CT through a rectifier.
Printed disc relays give a much more accurate time characteristic. They are also
very efficient. A printed disc relay is 50 to100 times more efficient than the induction
Dr. Raju Chintakindi EEE Vaagdevi
disc type. The maximum efficiency that an induction disc relay can have is only
about 0.05%, which is extremely poor. Characteristics other than inverse time-
current characteristic can be obtained by including a non-linear network in between
the printed circuit of the disc and the rectified current input.
Trip
N N
S
S
Torqu
e
and produces a steady non-vibrating torque. Its parasitic torques due to current or
voltage alone are small. Its operating time is to the order of 0.01 second. Thus with
its high torque/inertia ratio, it is quite suitable for higher speeds of operation.
Magnetic saturation can be avoided by proper design and the relay can be made to
have its characteristics linear and accurate over a wide range with very high reset to
pick-up ratio. The pick-up and reset values are close together. Thus this type is best
suited where normal and abnormal conditions are very close together. It is inherently
self compensating for dc transients. In other words, it is less sensitive to dc transients.
The other system transients as well as transients associated with CTs and relay cir-
cuits can also be minimised by proper design. However, the magnitude of the torque
is affected by the variation in the system frequency. Induction cup type relays were
widely used for distance and directional relays. Later, however, they were replaced
by bridge rectifier type static relays.
Theory of Induction Relay Torque
Fluxes f1 and f2 are produced in a disc type construction by shading technique. In
watt-metric type construction, f1 is produced by the upper magnet and f2 by the
lower magnet. A voltage is induced in a coil wound on the lower magnet by trans-
former action. The current flowing in this coil produces flux f2. In case of the cup
type construction, f1 and f2 are produced by pairs of coils, as shown in Fig. 2.13. The
theory given below is true for both disc type and cup type induction relays. Figure
2.14 shows how force is produced in a rotor which is cut by f1 and f2. These fluxes
are alternating quantities and can be expressed as follows.
f1 = f1m sin wt f2 = f2m sin (wt + q)
where q is the phase difference between f1
and f2. The flux f2 leads f1 by q. f2 f1
Voltages induced in the rotor are: i2 i1
df1 i2
e1 μ ___ F2
dt i1 F1
μ f1m cos wt
df2
e2 μ ___
dt Fig. 2.14 Torque produced in an
μ f2m cos (wt + q) induction relay
As the path of eddy currents in the rotor has negligible self-inductance, with negli-
gible error it may be assumed that the induced eddy currents in the rotor are in phase
with their voltages.
i1 μ f1m cos wt
i2 μ f2m cos (wt + q)
The current produced by the flux interacts with other flux and vice versa. The
forces produced are:
F1 μ f1 i2
μ f1m sin wt ◊ f2m cos (wt + q)
μ f1m f2m cos (wt + q) ◊ sin wt
Dr. Raju Chintakindi EEE Vaagdevi
F2 μ f2 i1
μ f2m sin (wt + q) ◊ f1m cos wt
μ f1m f2m sin (wt + q) ◊ cos wt
As these forces are in opposition, the resultant force is
F = (F2 – F1)
μ f1m f2m [sin (wt + q) cos wt – cos (wt + q) ◊ sin wt]
μ f1m f2m sin q
The suffix m is usually dropped and the expression is written in the form of
F = Kf1 f2 sin q. In this expression, f1 and f2 are rms values.
If the same current produces f1 and f2 the force produced is given by
F = K I2 sin q
where q is the angle between f1 and f2. If two actuating currants M and N produce
f1 and f2, the force produced is
F = KMN sin q
Heater coil
(a) (b)
To trip
circuit
Heating Unimetallic
element strip
(c)
Fig. 2.15 (a) Bimetallic thermal relay (b) Bimetallic spiral type thermal relay
(c) Unimetallic thermal relay
discussed in Chapter 5. They are also used in control and alarm circuits to allow time
for the required sequence of operations to take place. The principle of producing time
delays will be discussed later (see sec. 2.2.6).
Alarm Relays
An alarm relay gives both an audible and a visual indication. At a substation, it is
sufficient to provide a trip alarm and one non-trip alarm, which is common to the
whole substation. In the control room of a generating station, the trip alarm and non-
trip alarm should be separate for each primary circuit. There is an arrangement for
alarm cancellation by pressing a button. The alarm circuit is interrupted on pushing
this button. When the relay is de-energised, the initiating contact of the cancellation
mechanism is reset so that it can receive another alarm.
Repeat Contactors
A repeat contactor repeats the operation of a protective relay. It is sometimes needed
because a protective relay may not have a sufficient number of contacts. It may also
be required to take over the operation from the initiating relay if the contacts of
the latter are not designed for carrying current for long periods. Its most important
requirements are that it should be fast and absolutely reliable. It should also be robust
and compact. It is usually mounted in the same case as the relay for which it is
required to repeat the operation.
Repeat contactors operate on the attracted armature principle. It may be connected
either in series or in parallel with the relay. It contains a number of contacts which
are placed in parallel. However, having more than three contacts in parallel is usually
not pratical.
Flag or Target
When a relay operates, a flag is indicated to show its operation. When on a relay
panel there are several relays, it is the flag that indicates, the relay that has operated.
This helps the operator to know the cause of the tripping of the circuit breaker. It is
also called the target or indicator. Its coil is connected in series with the trip coil of
the circuit breaker, as shown in Fig. 2.16. The resetting of a flag indicator is usually
manual. There is a button or knob outside the relay case to reset the flag indicator. A
flag indicator may either be electrical or mechanical. In a mechanical flag indicator,
the movement of the armature of the relay pushes a small shutter to expose the flag.
In an electrically operated flag indicator there is a solenoid which is energised when
relay contacts are closed. Electrical flags being more reliable are preferred.
Auxiliary Switch
An auxiliary switch is connected in series with the trip-coil circuit, as shown in
Fig. 2.16. It is mechanically interlocked with the operating mechanism of the circuit
breaker so that the auxiliary switch opens when the circuit breaker opens. The open-
ing of the auxiliary switch prevents unnecessary drainage of the battery.
When the trip-coil of the circuit breaker is energised, it actuates a mechanism of
the circuit breaker, which causes the operating force to come into action to open the
circuit breaker.
Dr. Raju Chintakindi EEE Vaagdevi
Fig. 2.16 Circuit breaker trip coil circuit (a) With seal-in relay (b) With holding coil
section to the other and bridges the contacts. The flow of mercury is impeded by a
construction between the two sections of the tube. The time setting is fixed by the
design of the tube. It is not possible to have a range of time settings on a particular
mercury switch. Toothed gears or cams are also used to produce time delay.
Thermal Time-delay
Thermal devices employing expansion of bimetal strip or spiral, unimetal (brass)
strips, etc. are also used to produce time-delay.
Electrical Time-delay
Time delay can be produced by employing a short-circuiting ring around a solenoid
pole; a circuit containing reactance, capacitance or non-linear resistance; a resonant
circuit, etc.
Short-circuiting Ring
A short-circuiting copper band is fitted around the pole piece of an attracted arma-
ture hinged-type relay. This arrangement provides eddy current path for damping. To
obtain a time-delay on pick-up, the band is placed at the armature end of the core. By
this technique, a delay of about 0.1 s can be produced in pick-up with a large arma-
ture gap, and a stiff restraining spring. To obtain a delayed reset, the band is placed at
the frame end of the solenoid. A delay up to 0.5 s in drop out can be obtained with a
short lever arm and a light spring load. Time-delay can also be produced by employ-
ing a copper tube inside the coil.
Capacitance
A capacitor which is connected in parallel with the relay coil is changed through a
resistor, as shown in Fig. 2.17(a). A longer time-delay is obtained by this technique.
A delay of up to 0.5 s can be obtained on pick-up with a capacitor of reasonable size.
For ac applications, a rectifier should be included.
Resonant Circuit
A resonant circuit, as shown in Fig. 2.17(b) can be employed to produce a delay of
up to 3 cycles.
C
C L
R
(a) (b)
Fig. 2.17 (a) Capacitor charge delay (b) Resonance build-up delay
Dr. Raju Chintakindi EEE Vaagdevi
Ballistic Resistance
This technique is based on the principle of To trip circuit
delaying the build-up of operating voltage. This
includes thermistors or filament lamps. Figure
2.17(c) shows a metal filament lamp connected
across the relay coil. A resistance is also placed
in the circuit as shown in the figure. The hot
resistance of the lamp filament is 10 times its
cold resistance. The relay coil is short-circuited
by the lamp, thereby keeping the magnetic
flux to zero for a short time until the filament
a.c. or d.c.
becomes incandescent.
Alternatively, a thermistor or a carbon fila- Fig. 2.17 (c) Lamp filament
ment can be placed in series with the relay coil. heating delay
The thermistor resistance being high at room
temperature limits the coil current. As the current drawn by the relay coil heats the
thermistor, its resistance decreases until the relay current becomes sufficient for
pick-up.
Synchronous Motor
A synchronous motor, geared to a reduced speed can be also used on ac to produce
more precise, long time delays.
Electronic Time Delay
Longer time delays are obtained with R-C circuits. R-C circuits are also used with
electromagnetic relays, as shown in Fig. 2.17(a). Longer time delays can be obtained
with R-C circuits when used with electronic relays rather than with electromagnetic
relays. This is due to the face that a smaller current is needed with electronic relays,
which in turn takes longer time to charge the capacitor.
Figure 2.18 shows a time-delay circuit employing a transistor. A constant dc volt-
age is applied to an R-C network to charge the capaci- tor C through resistor R. When
the voltage of capacitor C reaches a suitable VCC
value, the transis- tor starts conducting. A realy
+
is placed in the collector circuit. This relay oper-
ates when the transistor starts conducting. The
time delay depends on the value of the capacitor R
and the magnitude of the charging current. As
Relay
the charging current is small in a transistor cir-
cuit, a delay of several minutes can be obtained C
with a capacitor of only few microfarads. Delays
–
of several hours can be obtained with tantalum
capacitors of a few hundred microfarads. Fig. 2.18 Static time delay circuit
Counter
For obtaining even more accurate time-delays, electronic counters are used. A crystal
oscillator or some suitable electronic circuitry is employed to generate a train of high
frequency pulses. Counters are used as frequency dividers. A number of counters
Dr. Raju Chintakindi EEE Vaagdevi
may be connected in cascade and different time-lags may be obtained from different
stages of the cascaded counters.
2.2.7 Bearings
The pivot and jewel bearing is commonly used for precision relays. Spring-mounted
jewels are used in modern relays. The design is such that shocks are taken on a shoul-
der and not on a jewel.
For high sensitivity and low friction, a single ball bearing between two cup-shaped
sapphire jewels is used.
Multi-ball bearings provide friction as low as the jewel bearings and have greater
resistance to shock. They are also capable of combining side-thrust and end-thrust in a
single bearing. Miniature bearings less than 1.6 mm in diameter are now available.
Knife-edge bearings, pin bearings or resilient strips are used in hinged armature
relays.
2.2.8 Backstops
When the moving part of the relay is stationary, it rests against a backstop. The mate-
rial of a backstop should be chosen carefully so that it should not be sticky. To avoid
magnetic adherence, the material should be non-metallic. The molecular adherence
can be overcome using a hard surface rounded to a large radius. Smooth backstops
made of agate or nylon are used.
2.2.9 Contacts
The reliability of protective relays depends on their contact performance. The follow-
ing are the requirement of good contacts.
(i) Low contact resistance
(ii) High contact pressure
(iii) Freedom from corrosion
(iv) Bounce free
(v) Self-clearing action
(vi) Freedom from sparking
(vii) Dust proof
Silver is the most commonly used material for relay contacts. It has the lowest
resistance. Copper is not used because of its higher resistance. Silver cadmium oxide
is used where high currents are to be handled. It has low resistance like silver but
does not weld or become sticky. An alloy consisting of 67% gold, 26% silver and 7%
platinum is used for small currents and very light contact pressure. Non-corroding
materials like gold, palladium or rhodium can be used for sensitive relays where the
contact pressure needs to be very low. These materials are not recommended for
protective relays where high contact pressure is required.
The most reliable relay contact are cylindrical contacts at right angles, as they give
the optimum high pressure, bounce-proof contacts, hard smooth contact surfaces and
dust proof relay cases minimise the maintenance of protective relays.
Dr. Raju Chintakindi EEE Vaagdevi
On silver contacts silver oxide does not form readily. Even when formed, its
thickness does not exceed 10 Å and hence can easily be moved aside by high pres-
sure or wiping action. Humid sulphurous and high temperature atmosphere causes
corrosion. In polluted atmospheres where coal fires are used, silver sulphide is formed
readily, especially in the presence of heat and humidity. It is not breakable like oxides
but it is soft and thus can be squeezed aside by high pressure. A thin petrolatum coat-
ing can reduce corrosion of contacts without increasing their resistance. It is helpful
in polluted atmospheres.
A dust-proof casing is usually used for modern relays. A filter is provided at the
back to trap any dust and to allow the relay to breathe. A relay with such a casing is
quite suitable for a dusty or otherwise dirty atmosphere. In a relay with poor ventila-
tion, particularly in a sealed relay, high resistance polymers may appear on contacts.
This is due to organic emanations from the coil insulation material. All insulating
materials, except teflon give off organic vapour to a certain degree. Phenolic resin
gives off organic vapours more than others. Polyester and epoxide varnishes now
available have good performance and are quite satisfactory for coil insulation. Relay
casings with good ventilation and having dust filters minimise the collection of high
resistance polymers on the contacts. Encapsulated contacts as in the case of reed
relays provide the best solution to the problem. Alternatively, the relay coil can also
be encapsulated.
An electromechanical relay used with comparators is usually of a small rating.
When such relays control auxiliary relays and timing units, they are to be protected
with spark quenching circuits. A series resistor and capacitor connected across the
contacts is a simple spark quenching circuit.
2.3.2 Comparators
When faults occur on a system, the magnitude of voltage and current and phase
angle between voltage and current may change. These quantities during faulty con-
ditions are different from those under healthy conditions. The static relay circuitry
is designed to recognise the changes and to distinguish between healthy and faulty
conditions. Either magnitudes of voltage/current (or corresponding derived quanti-
ties) are compared or phase angle between voltage and current (or corresponding
derived quantities) are measured by the static relay circuitry and a trip signal is sent
to the circuit breaker when a fault occurs. The part of the circuitry which compares
the two actuating quantities either in amplitude or phase is known as the comparator.
There are two types of comparators—amplitude comparator and phase comparator.
Amplitude Comparator
An amplitude comparator compares the magnitudes of two input quantities, irrespec-
tive of the angle between them. One of the input quantities is an operating quantity
and the other a restraining quantity. When the amplitude of the operating quantity
exceeds the amplitude of the restraining quantity, the relay sends a tripping signal.
The actual circuits for comparators will be discussed in subsequent chapters.
Dr. Raju Chintakindi EEE Vaagdevi
Phase Comparator
A phase comparator compares two input quantities in phase angle, irrespective of
their magnitudes and operates if the phase angle between them is £ 90°.
M (M + N )
Amplitude Output Amplitude Output
Inputs Inputs
comparator comparator
N (M – N )
(a) (b)
Fig. 2.19 (a) Amplitude comparator (b) Amplitude comparator used for
phase comparison
M–N M M+N
M–N M M+N
f
f
M–N M M+N
f
–N f < 90° N
Comparison: (M + N ) > (M – N )
Fig. 2.20 Phasor diagram for amplitude comparator used for phase comparison
Dr. Raju Chintakindi EEE Vaagdevi
M (M + N )
Phase Output Phase Output
Input Input
comparator comparator
N (M – N )
Fig. 2.21 (a) Phase comparator (b) Phase comparator used for amplitude comparison
Figure 2.20 shows three phasor diagrams for an amplitude comparator. The phase
angle between the original inputs M and N is f. Now the inputs to the amplitude com-
parator are changed to (M + N) and (M – N) and its behaviour is examined with the
help of three phasor diagrams. The three phasor diagrams are with phase angle f (i)
greater than 90°, (ii) equal to 90° and (iii) less than 90°, respectively. When f is less
than 90°, |M + N| become greater than |M – N| and the relay operates with the modi-
fied inputs. When f is equal to 90° or greater than 90°, the relay does not operate.
The phasor diagrams show that |M + N| becomes greater than |M – N| only when f
is less than 90°. This will be true irrespective of the magnitude of M and N. In other
words, this will be true whether |M| = |N| or |M| > |N| or |M| < |N|. The figures have
been drawn with |M| = |N|. The reader can draw phasor diagrams with |M| < |N| or
|M| > |N|. The results will remain the same. This shows that with changed inputs, the
amplitude comparator is converted to a phase comparator for the original inputs.
Figure 2.22 shows three phasor diagrams for a phase comparator. The original
inputs are M and N. Now the inputs of the phase comparators are changed to (M + N)
and (M – N), and its behavior is examined with the help of three phasor diagrams
drawn for (i) |M| < |N|, (ii) |M| = |N| and (iii) |M| > |N|. The angle between (M + N)
and (M – N) is l. The angle l becomes less than 90° only when |M| > |N|. As the
comparator under consideration is a phase comparator, the relay will trip. But for the
original inputs M and N, the comparator behaves as an amplitude comparator. This
will be true irrespective of the phase angle f between M and N. The figure has been
drawn with f less than 90°. The reader can check it by drawing phasors with f = 90°
or f > 90°. The result will remain the same.
M–N M M+N
l l
–N N –N N
M < N M = N
M–N M M+N
–N N
M>N
Io
Ir
Aux/ CTs
Isolating
Io Ir
C
To thyristor
CT CT
Io Ir
–120° –120°
– –120° – –120°
M N
As both input signals to the relay are smoothed out before they are compared, a con-
tinuous output signal is obtained. The operating time depends on the time constant of
the slowest arm of the phase-splitting circuit and the speed of the output device.
Sampling Comparators
In sampling comparators, one of the inputs is rectified and it is compared with the
other input at a particular moment. The instantaneous value of the other input is
sampled at a particular desired moment. Such comparators are used to realise
reactance and MHO relay characteristics as discussed in Chapter 6 Section 6.7.1 and
6.7.2.
M N
(a)
Y
f
Trip
(b)
Block
pulses. We get a square wave output during the period of coincidence and no output
for the rest of the period of a cycle,. as shown in Fig. 2.25 (b).
M – 45° M M –– 45°
N – 45°
N
f N – – 45°
(a)
Phase M – 45°
M shifting
circuit M – – 45°
AND Trip
Figure 2.27(a) shows the block diagram of a phase comparator. The sinusoidal
inputs are first converted into square waves and then are applied to an AND gate.
The output of the AND gate is a chain of pulses as shown in Fig. 2.27(b). This is for
f < 90°, i.e. y > 90°. The relay will provide a trip output. The output of the AND gate
is applied to an integrator. The output of the integrator is shown in Fig. 2.27(c). This
output is applied to a level detector which finally gives a TRIP signal. The integrating
circuit may be employed as shown in Fig. 2.28. The level detector may be a thyristor
circuit.
Dr. Raju Chintakindi EEE Vaagdevi
Figure 2.27(d) and (e) show the outputs of the AND gate and the integrator,
respectively. This situation is for y = 90° and is the limiting condition. The relay
may be set to operate at y = 90°.
Sine to
square wave
converter
Inputs Integrator Level
AND
detector Trip
Sine to
square wave Coincidence
converter detector
(a)
(b) V
10 ms
Operate
(c) reset
Output of
coincidence
(d) Detector at
the boundary
10 ms
Operate
reset
(e) Output of
integrator
(f)
10 ms
Operate
Reset
(g)
Figure 2.27(f) and (g) show the outputs of the AND gate and the integrator, respec-
tively, for y < 90°. For this condition, the relay does not operate.
+VCC
R C
To thyristor
Input
Polarised
M
relay
R R
N
Polarised relay
N
(a) (b)
M N
|M + N |
IR P.R.-polarised
M
relay
|M – N |
P.R.
M N
N
(c)
through a delay circuit. The delay circuit gives a delayed output. The output is delayed
by an angle d from the staring point of the block as shown in Fig. 2.30(b) and (c). The
delay d is kept 90°. If the block and pulse (output of the delay circuit) still coincide.
the second AND gate will give an output, as shown in Fig. 2.30(b). If the block and
pulse do not coincide, the second AND gate does not give any output as shown in
Fig. 2.30(c). This means that the output of the first gate has to persist for a period d so
that the second gate may operate and send a tripping signal. This technique is more
suitable for multi-input comparators. However, it is subject to false tripping by a false
transient signal whereas phase comparators discussed earlier are not.
M
AND d AND Trip
N
Pulse
(a)
M N M N
y y
f f
d d
(b) (c)
numerically using an algorithm to calculate the fault discriminants and make trip
decisions. With the continuous reduction in digital circuit costs and increases in their
functionality, considerable cost-benefit improvement ensues. At present micropro-
cessor/microcontroller-based numerical relays are widely used. There is a growing
trend to develop and use numerical relays for the protection of various components
of the modern complex power system. Numerical relaying has become a viable alter-
native to the traditional relaying systems employing electromechanical and static
relays. Intelligent numerical relays using artificial intelligence techniques such as
artificial neural networks (ANNs) and Fuzzy Logic Systems are presently under
active research and development stage.
The main features of numerical relays are their economy, compactness, flexibility,
reliability, self-monitoring and self-checking capability, adaptive capability, multiple
functions, metering and communication facilities, low burden on transducers (instru-
ment transformers) and improved performance over conventional relays.
The schematic diagram of a typical numerical relay is shown in Fig. 2.31
Signal S/H
I CT Microprocessor
conditioner CKt
system
Analog
Multiplexer ADC
Signal S/H
V VT Microcomputer/
conditioner CKt
Microcontroller
Trip signal
The levels of voltage and current signals of the power system are reduced by
voltage and current transformers (VT and CT). The outputs of the CT and VT (trans-
ducers are applied to the signal conditioner which brings real-world signals into digi-
tizer. The signal conditioner electrically isolates the relay from the power system,
reduces the level of the input voltage, converts current to equivalent voltage and
remove high frequency components from the signals using analog filters. The output
of the signal conditioner are applied to the analog interface, which includes sample
and hold (S/H) circuits, analog multiplexer and analog-to-digital (A/D) converters.
These components sample the reduced level signals and convert their analog levels
to equivalent numbers the are stored in memory for processing.
The signal conditioner, and the analog interface (i.e., S/H CKt, analog multiplexer
and A/D converter) constitute the data acquisition system (DAS).
The acquired signals in the form of discrete numbers are processed by a numeri-
cal relaying algorithm to calculate the fault discriminants and make trip decisions. If
there is a fault within the defined protective zone, a trip signal is issued to the circuit
breaker.
Dr. Raju Chintakindi EEE Vaagdevi
EXERCISES
1. Draw a neat sketch of an induction disc relay and discuss its operating
principle.
2. For what type of protective relay will you recommend (i) an induction disc
type (ii) induction cup type construction? What measures are taken to minimise
the overrun of the disc?
3. What are the merits of induction cup construction over the induction disc
construction?
4. Derive an expression for torque produced by an induction relay.
5. Discuss the working principle of a permanent magnet moving coil relay with
a neat sketch. State the area of its applications.
6. Describe the operating principle of a moving iron type dc polarised relay.
Suggest some suitable area of its applications.
7. What are the different types of electromagnetic relays? Discuss their field of
applications.
8. Explain why attracted armature type relays are noisy. What measures are taken
to minimize the noise?
9. Discuss why the ratio of reset to pick up should be high.
10. Discuss the working principle, types and applications of thermal relays.
11. What are the advantages of static relays over electromechanical relays?
12. Explain what are amplitude and phase comparators.
13. Discuss how an amplitude comparator can be converted to a phase comparator,
and vice versa.
14. Discuss the operating principle of a rectifier bridge phase comparator.
15. Discuss the principle of a coincidence circuit for phase comparator.
16. With a neat sketch, describe the principle of a reed relay. Where is it used?
17. What is a numerical relay? What are its advantages over conventional type
relays?
18. Draw the schematic diagram of a numerical relay and briefly describe the
functions of its various components.
19. Compare a numerical relay with an electromechanical relay.
Dr. Raju Chintakindi EEE Vaagdevi
Current and
Voltage Transformers
3
3.1 INTRODUCTION
Current and voltage transformers (CTs and VTs) are collectively known as trans-
ducers or instrument transformers. They are used to transform the power system
currents and voltages to lower magnitudes and to provide isolation between the high-
voltage power system and the relays and other measuring instruments (meters) con-
nected to the secondary windings of the transducers. In order to achieve a degree of
interchangeability among different manufacturers of relays and meters, the ratings
of the secondary windings of the transducers are standardized. The standard current
ratings of the secondary windings of the current transformers (CTs) are 5 or 1
ampere. The secondary windings of the voltage transformers (VTs) are rated at 110
V line to line. The current and voltage ratings of the protective relays and meters are
same as the current and voltage ratings of the secondary windings of the CTs an VTs
respectively. The transducers should be able to provide current and voltage signals to
the relays and meters which are faithful reproductions of the corresponding primary
quantities. Although in most of the cases the modern transducers are expected to
do so, but they can’t be ideal and free from the errors of transformation. Hence the
errors of transformation introduced by the transducers must be taken into account,
so that the performance of the relays can be assessed in the presence of such errors.
As the operating time of modern protective relays has reduced to the order of few
milliseconds, the transient behavior of current transformers and voltage transformers
require more attention.
electromagnetic induction but there are considerable differences in their design and
operation. A power transformer is a shunt-operated device while a CT is a series-
operated device. Current transformers are connected with their primaries in series
with the power system (protected circuit) and, because the primary currents are so
large, the primary winding has very few turns.
The VA rating of current transformers is small as compared with that of a
power transformer. Though the nominal (Continuous) current ratings of the sec-
ondary windings of the CTs are 5A or 1A but they must be designed to toler-
ate higher values for short time of few seconds under abnormal system condi-
tions, e.g., fault conditions. Since the fault currents may be as high as 50 times
full-load current, current transformers are designed to withstand these high cur-
rents for a few seconds. Protective relays require reasonably accurate repro-
duction of the normal and abnormal conditions in the power system for correct
sensing and operation. Hence, the current transformers should be able to provide
current signals to the relays and meters which are faithful reproductions of the
primary currents. The measure of a current transformer performance is its ability to
accurately reproduce the primary current in secondary amperes. Ideally, the current
transformer should faithfully transform the current without any error. But, in prac-
tice, there is always some error. The error is both in magnitude and in phase angle.
These errors are known as ratio error and phase angle error. The exciting current is
the main source of these errors of a CT.
Depending on application, CTs are broadly classified into two categories:
(1) measuring CTs, and (2) protective CTs. CTs used in conjunction with measuring
instruments (meters) are popularly termed as measuring (metering) CTs’ and those
used in conjunction with protective devices are termed as protective CTs.
3.2.1 Difference Between Measuring and Protective CTs
CTs which are used to step down the primary currents to low values suitable for the
operation of measuring instruments (meters) are called measuring or metering CTs.
Secondary of the measuring CTs are connected to the current coils of ammeters,
wattmeters, energy meters, etc. Since the measurements of electrical quantities are
performed under normal conditions and not under fault conditions, the performance
of measuring CTs is of interest during normal loading conditions. Measuring CTs are
required to give high accuracy for all load currents upto 125% of the rated current.
These CTs may have very significant errors during fault conditions, when the cur-
rents may be several times their normal value for a short time. This is not significant
because metering functions are not required during faults. The measuring CTs should
get saturated at about 1.25 times the full-load current so as not to reproduce the fault
current on the secondary side, to avoid damage to the measuring instruments.
CTs used in association with protective devices i.e. relays, trip coils, pilot wires
etc. are called protective CTs. Protective CTs are designed to have small errors dur-
ing fault conditions so that they can correctly reproduce the fault currents for sat-
isfactory operation of the protective relays. The performance of protective relays
during normal conditions, when the relays are not required to operate, may not be as
accurate. When a fault occurs on a power system, the current tends to increase and
Dr. Raju Chintakindi EEE Vaagdevi
voltage tends to collapse. The fault current is abnormal and may be 20 to 50 times the
full-load current. It may have dc offset in addition to ac component. The fault current
for a CT secondary of 5A rating could be 100 to 250 A. Therefore, the CT secondary
having a continuous current rating of 5A should have short-time current rating of
100 to 250 A, so that the same is not damaged. Since the ac component in the fault
current is of paramount importance for the relays, the protective CT should correctly
reproduce it on the secondary side in spite of the dc offset in the primary winding.
Hence the dc offset should also be considered while designing the protective CT. The
protective CT should not saturate upto 20 to 50 times full-load current.
1.0
High-nickel steel
0.5
0 1 2 3
Exciting Force (At/cm)
Hot-rolled silicon steel has the lowest permeability. So it is not suitable for CTs.
In order to achieve the desired characteristics, composite cores made of laminations
of two or more materials are also used in CTs.
Dr. Raju Chintakindi EEE Vaagdevi
3.2.3 CT Burden
The CT burden is defined as the load connected across its secondary, which is usually
expressed in volt amperes (VA). It can also be expressed in terms of impedance at the
rated secondary current at a given power factor, usually 0.7 lagging. From the given
impedance at rated secondary current, the burden in VA can be calculated. Suppose
the burden is 0.5 W at 5 A secondary current. Its volt amperes will be equal to I2R =
52 × 0.5 = 1.25 VA. The total burden on the CT is that of the relays, meters, connect-
ing leads and the burden due to the resistance of the secondary winding of the CT.
The relay burden is defined as the power required to operate the relay. The burden
of relays and meters is given by the manufactures or it can be calculated from the
manufacturer’s specifications as the burden depends on their type and design. The
burden of leads depends on their resistance and the secondary current. Lead resis-
tance is appreciable if long wires run from the switchyard to the relay panels placed
in the control room. Lead burden can also be reduced using low secondary currents.
Usually secondary current of 5 A are used, but current of 2 A or even 1 A can be used
to reduce the lead burden. Suppose, the lead resistance is 5 W. Then lead burden at
5 A will be 52 × 5 = 125 VA. The burden at 1 A is only 12 × 5 = 5 VA. The economy
in CT cost and space requirement demands shorter lead runs and sensitive relays. The
rating of a large CT is 15 VA. For a 5 A secondary current, the corresponding burden
is 0.6 W, and for a 1 A secondary current it is 15 W.
If rated burden be PVA at rated secondary current IS amperes, the ohmic imped-
ance of the burden Zb can be calculated as follows:
P
Zb = __2 ohms (3.1)
Is
If burden power factor is cos f, the values of resistance and reactance of the bur-
den can be calculated as follows:
Rb = Zb cos f (3.2)
_______
Xb = ÷Z2b – R2b (3.3)
The impedance of the relay coil changes with current setting. The values of power
consumption of relays, trip coil etc. are given by their manufacturers. The CT of
suitable burden can be selected after calculating the total burden on the CT.
When the relay is set to operate at current different from the rated secondary cur-
rent of the CT, the effective burden of the relay can be calculated as follows:
()Is 2
Pe = Pr __
Ir
(3.4)
Connecting
load resistance
0.008 W 5 A Relay
7.5 VA
() (
Is 2
Pe = Pr __
Ir
5
= 4 × ____
3.75 ) = 7.11 VA
2
(iv) Actual transformation ratio The ratio of the actual primary current to the
actual secondary current.
(v) Burden The value of the load connected across the secondary of CT, ex-
pressed in VA or ohms at rated secondary current.
(vi) Rated burden The value of the load to be connected across the secondary of
CT including connecting lead resistance expressed in VA or ohms on which
accuracy requirement is based.
(vii) Rated short-time current The r.m.s value of the a.c. component of the
current which the CT is capable of carrying for the rated time without being
damaged by thermal or dynamic effects.
(viii) Rated short-time factor The ratio of rated short-time current to the rated
current.
(ix) Rated accuracy limit primary current The highest value of primary current
assigned by the CT manufacturer, upto which the limits of composit error are
complied with.
(x) Rated accuracy limit factor The ratio of rated accuracy limit primary current
to the rated primary current.
(xi) Composit error The r.m.s. value of the difference (N is – ip), given by
__________
÷
T
100 1
Composit error = ____ __ Ú (Nis – ip) (3.5)
Ip T 0
Where N = Rated transformation ratio
Ip = r.m.s value of the primary current
ip = Instantaneous values of the primary current
is = Instantaneous values of the secondary current
T = Time period of one cycle in seconds
(xii) Knee-point voltage The sinusoidal voltage of rated frequency (system
frequency) applied to the secondary terminals of CT, with all other winding
being open-circuited, which when increased by 10 per cent, causes the exciting
current to increase by 50 per cent. Minimum knee point voltage is specified
by the following expression.
Vk = KI (RCT + Zs) (3.6)
Where K = A parameter to be specified by the purchaser depending on the
system fault level and the characteristic of the relay intended to be used.
I = Rated relay current (1 A or 5 A)
RCT = Resistance of CT secondary winding corrected to 75° C
Zs = Impedance of the secondary circuit (to be specified by
the purchaser)
(xiii) Rated short-circuit current The r.m.s. value of primary current which the
CT will withstand for a rated time with its secondary winding short-circuited
without suffering harmful effects.
Dr. Raju Chintakindi EEE Vaagdevi
(xiv) Rated primary saturation current The maximum value of primary current
at which the required accuracy is maintained
(xv) Rated saturation factor The ratio of rated primary saturation current to rated
primary current.
Ip = NI¢p
I p¢ = Ip /N I p¢
1:N
Io
R p¢ X p¢ RS XS
IC Im
RC ES VS Zb
Xm
Ideal CT for
ratio only
Practical CT
An ideal (perfect) transformer shown in Fig. 3.3 is to provide the necessary ratio
change, it has no loss or impedance. All the quantities are referred to the secondary
side. In an ideal CT, the primary ampere-turns (AT) is exactly equal in magnitude
to the secondary AT and is in precise phase opposition to it. But in practical (actual)
CTs errors are introduced both in magnitude and in phase angle. These errors are
known as ratio error and phase angle error. The exciting current I0 is the main source
of these errors. Practical CTs do not reproduce the primary currents exactly in mag-
nitude and phase due to these errors.
The errors of practical CTs can best be considered through the study of the phasor
diagram shown in Fig. 3.4
In the equivalent circuit of Fig. 3.3 and phasor diagram of Fig. 3.4,
N = Nominal (rated) transformation ratio or Nominal (rated) CT ratio
Rated primary current Number of secondary turns
= ____________________ = _______________________
Rated secondary current Number of primary turns
Rp, Xp = Primary resistance and leakage reactance respectively.
Rs and Xs = secondary resistance and leakage reactance
R¢p and X¢p = Primary resistance and leakage reactance as referred to the
secondary side
Dr. Raju Chintakindi EEE Vaagdevi
90°
Io
Ip NIS
NIS
– Ep
b qS
IC
a Io IC
Im fm
r
d
qS
IS
VS
S
R
IS
ES
IS XS
If the angle qs which is usually fairly small, is assumed zero, then the actual ratio
is
Ic
Na = N + __ (3.10)
Is
Phase-angle Error
The angle by which the secondary current phasor, when reversed, differs in phase
from the primary current phasor, is the phase angle error of the current transformer.
From the phasor diagram of Fig. 3.4
I0 sin [90° – (a + qs)]
tan b = _______________________
NIs + I0 cos [90° – (a + qs)]
I0 cos (a + qs)
= ________________
NIs + I0 sin (a + qs)
Since the phase angle error b is very small, in practice tan b = b
Hence, from above expression
I0 cos (a + qs)
b = ________________ (3.11)
NIs + I0 sin (a + qs)
I0 (cos a ◊ cos qs – sin a ◊ sin qs)
or b = ___________________________
NIs + Io sin (a + qs)
Im cos qs – Ic sin qs
________________
NIs
Since I0 sin (a + qs) is small compared with NIs. Hence phase-angle error b is
given by
Im cos qs – Ic sin qs
b = ________________ (3.12)
NIs
If the angle qs, which is usually fairly small is assumed zero, then the phase angle
eror is
Im
b = ___ (3.13)
NIs
3.2.6 CT Errors
In an ideal (perfect) CT, the secondary current is given by
Ip
Is = __
N
But in a practical (actual) CT, it is
Ip
Is = __ – I0 (3.13a)
N
Thus, the actual CT does not reproduce the primary current exactly in secondary
side both in magnitude and phase due to exciting current I0. The exciting current I0 is
the main source of errors in both measuring and Protective CTs. The error in magni-
tude is due to error in CT ratio which is called “ratio error” and the error in phase is
called “phase-angle error.”
Dr. Raju Chintakindi EEE Vaagdevi
[ ]
NIs – Ip
Per cent error = _______ × 100
Ip
rated primary current
N = Nominal ratio = ___________________
rated secondary current
Is = Secondary current
Ip = Primary current
The ratio error of a CT depends on its exciting current. When the primary cur-
rent increases, the CT tries to produce the corresponding secondary current, and
this needs a greater secondary emf, core flux density and exciting current. A stage
comes when any further increase in primary current is almost wholly absorbed in an
increased exciting current, and thereby the secondary current hardly increases at all.
At this stage, the CT becomes saturated. Thus the ratio error depends on saturation.
An accuracy of about 2% to 3% of the CT is desirable for distance and differential
relays, whereas for many other relays, a higher percentage can be tolerated.
According to standards followed in U.K., protective CTs are classified as S, T and
U type. The errors of these types of CT s are shown in Table 3.1.
Dr. Raju Chintakindi EEE Vaagdevi
When the primary current increases, at a certain value the core commences to
saturate and the error increases. The value of the primary current at which the error
reaches a specified limit is known as its accuracy limit primary current or satura-
tion current. The maximum value of the primary current for a given accuracy limit
is specified by the manufacturer. The CT will maintain the accuracy at the specified
maximum primary current at the rated burden. This current is expressed as a multiple
of the rated current. The ratio of accuracy limit primary current and rated primary
current is known as the rated accuracy limit factor or saturation factor, the standard
values of which are 5, 10, 15, 20 and 30. The performance of a CT is given at certain
multiples of the rated current. According to BSS 3938, rated primary currents of CTs
are up to 75 kA and secondary currents 5 A or 1 A.
3.2.8 Transient Behaviour of CTS
For fast relaying (within one or two cycles after the fault inception), it is very essen-
tial to know the behaviour of the CT during the first few cycles of a fault, when it
carries the transient component in addition to the steady-state component of the fault
current. For calculation of the fault current, the power system is considered as a
lumped R, L series circuit, and the effect of shunt admittance is neglected.
When a fault occurs on a power system, the fault current is given by
Vpm Vpm
ip = ____ sin (wt + a – fp) + e–(Rp/Lp)t ◊ ____ sin (fp – a) (3.17)
Zp Zp
where, the subscript p indicates the primary side of the CT.
wLp
( )
fp = tan–1 ____ is the phase angle of the primary circuit. The fault is assumed to
Rp
occur at t = 0. The parameter a controls the instant on the voltage wave at which the
fault occurs.
In Eq. 3.17 for the fault current, the first term is the sinusoidal steady-state current
which is called the symmetrical ac component, while the second term is the unidirec-
tional transient component which starts at a maximum and decays exponentially and
is called the dc offset current. The dc offset current causes the total fault current to be
unsymmetrical till the transient decays. The waveform of the fault current is shown
in Fig. 3.5.
Dr. Raju Chintakindi EEE Vaagdevi
The dc offset current (the transient current) will have a maximum value when fp
– a = p/2 radians and Eq. (3.17) reduces to
ip = Ipm [– cos wt + e–(Rp/Lp)t] (3.18)
Vpm __________
where Ipm = ____, and Zp = ÷R2p + (wLp)2
Zp
Normally, as the system rated voltage rises above 100 kV, the circuit becomes
highly inductive with negligibly small resistance and the phase angle fp tending to
p/2 rad (or 90°) and a tending to be zero. In the limit where fp = p/2 rad, fault at
zero voltage (for a = 0) gives rise to the maximum fault current asymmetry (current
doubling).
The primary fault current referred to the secondary side is
( )
Np
i¢p = ip ___
Ns
and let ( )
Np
I¢pm = Ipm ___
Ns
where Np and Ns are the number of turns in the primary and secondary, respectively.
In order to estimate the transient flux in the core, the magnetizing current will be
neglected as this is one of the worst cases and Eq. (3.18) will be used, i.e. the case of
maximum transient primary current.
The secondary voltage is
vs = zs is = Ns (df/dt) (3.19)
where, the subscript s indicates the secondary side of the CT and Zs is the CT
burden.
From Eq. (3.19), the maximum core flux is given by
( )
1
fm = ___ Ú vs dt
Ns
(3.20)
Thus, for the steady-state component of is, and integrating over a quarter cycle
p/2w
1
( )
fm = – ___
Ns
Ú
t=0
Zs I¢pm cos wt dt
Dr. Raju Chintakindi EEE Vaagdevi
( )
Zs I¢pm
= – _____
Nsw
(3.21)
1
( )
fm = ___ Zs I¢pm
•
Ú e
( ) dt
Rp
– ___ t
Lp
Ns t=0
( )( )
Zs I¢pm
= _____
Ns w
wL
____p
Rp
( )( )
Zs I¢pm
= _____
Ns w
X
___p
Rp
(3.22)
Therefore, the component of the core flux due to the transient component of the
fault current is Xp/Rp times the component of the core flux due to the steady-state
component of the fault current. Considering the worst case of a fault near a large
power station, Xp/Rp could be as high as 30, corresponding to a primary-circuit time
constant of Lp/RP = 0.1 s, or about 5 cycles.
Assuming that the two fluxes can be added numerically (the worst case), the total
core flux is equal to the steady-state component multiplied by the factor
()
Xp 2p f Lp
1 + ___ = 1 + ______ = 1 + 2pTp
Rp Rp
where Tp is the primary circuit time-constant in cycles. The flux waveforms are
shown in Fig. 3.6
Total flux
Transient component
Flux
Steady-state component
1 2 3 4 5
Cycles
The value of Xp/Rp increases with the system voltage because of the increased
spacing of the conductors. The component of the core flux due to transient dc off-
set current increases Xp/Rp times the flux due to the symmetrical (steady-state) ac
Dr. Raju Chintakindi EEE Vaagdevi
current. Therefore, it is clear that there is a large transient flux swing in the magnetic
core of the CT. With this large flux-swing during the transient period, the magnetic
core of the CT of conventional design will get saturated causing undesirable effects
on the performance of the protective relays connected to the secondary of the CT.
In current transformers of conventional design, saturation of the cores due to the
transient dc component of the fault current is possible within a few milliseconds,
after which their secondary current is fully distorted, resulting in an inaccurate mea-
surement of the fault current by the relay. In order to prevent an adverse effect upon
the performance of the relays, the current transformer cores must be greatly enlarged
or air-gaps should be provided in the cores.
The choice of the appropriate current transformer design depends upon the protec-
tive system requirement. Where the operation of the protective system is not affected
by the CT core saturation, as in the case of a plain overcurrent relay, the conven-
tional type of CT may be used. But where a saturation-free current transformation
is essential for correct and rapid working of the system protection, the dimension of
the CT core must be greatly increased. The increase of core section in such cases
leads us to unreasonable core sizes with the use of iron-enclosed cores in high-power
systems. Therefore, for such cases, cores having air-gaps, called linear cores have
been developed. By providing such air gaps, the time constant of the CT is reduced
to a great extent since the current main flux density is diminished. Generally, the flux
due to the dc component assumes smaller values, if the CT time constant is reduced.
Therefore, CT cores with air gaps are almost free from the problem of saturation and
consequent distortion of the secondary current.
The linear cores provide an entirely new solution to a wide range of protective
system providing saturation free transformation of transient phenomena with dc off-
set components of great time constants.
3.2.9 Linear Couplers
The CT core may be of iron or non-ferrous material, usually air or plastic. An iron-
cored CT has substantial power output which is adequate for electromagnetic relays.
A CT having non-ferrous material as core has low power output which is suitable for
static relays but is inadequate for electromagnetic relays. An air or plastic-cored CT
has a linear characteristic and is called a linear coupler. Such CTs have no saturation
limit and hence show no transient errors, i.e ratio and phase angle errors which arise
due to saturation. Problems caused by dc transients are also reduced to a great extent.
Such CTs do not have lead resistance problem. A CT with a small air gap in its iron
core has also linear characteristic, and has no transient errors. Such CTs are called
transactors.
3.2.10 Classi ication of CTs
Current transformers can be classified in various ways depending on the technology
used for their construction and operation, their application, their location, etc.
Classification of CTs Based on Technology
CTs can be broadly classified into the following categories, depending on the tech-
nology they use for their construction and operation
Dr. Raju Chintakindi EEE Vaagdevi
Relay
C.T.
This type of construction has a negligible leakage flux of both primary and
secondary and hence, possesses low reactance. As there is only one primary turn, the
primary current should be high enough (about 400 A) to produce sufficient exciting
ampere-turns (AT) to give reasonable output. A bushing CT is a sub-class of the bar
primary type CT. It is placed over an insulator bushing enclosing a straight conduc-
tor. The bushing CT has comparatively more exciting current and a large magnetic
path owing to the large diameter of the bushing.
Wound Primary CTs
Wound primary CTs have the primary and secondary windings arranged concentri-
cally, the secondary winding invariably being the inner winding. The core is com-
posed either of hot-rolled silicon steel stampings or, in recent most technique, of cold
rolled grain-oriented steel or of nickel-iron alloy. Cores are usually assembled from
stampings of E, I, L or C shape depending on whether the core is a simple rectangle
or of the three-limb shell-type. Cores of grain-oriented materials should be arranged
as far as possible with the flux direction along the grain.
The primary windings of wound primary CTs usually take the form of edge-
wound copper strip because this method of winding results in coils best capable of
withstanding the electromagnetic forces produced by high values of the primary cur-
rent. Secondary windings are usually wound from round section enamelled copper
wire.
Vin R
Conductor –
Vout
+
Vcoil
Rogowski coil
Fig 3.12 An active integrator using
Fig. 3.11 Rogowski coil wrapped around op-amp
the straight conductor
Each turn of the Rogowski coil produces a voltage proportional to the rate of
change of the magnetic flux through the turn. Assuming a uniform magnetic flux
density throughout the turn, the rate of change of magnetic flux is equal to the rate
of change of magnetic flux density (B) times the cross-sectional area (A) of the turn
(one of the smallest loops).
The voltage induced in one turn of the Rogowski coil is given by
df dB
vturn = ___ = A ___ (3.23)
dt dt
For a coil with N turns, the voltage induced in the coil is
dB
vcoil = NA ___ (3.24)
dt
The flux density B at radial distance r due to a long straight conductor carrying
current i is
m0i
B = ____ (3.25)
2pr
Where r is the perpendicular radial distance from the conductor to the point at
which the magnetic flux (field) density is calculated. The direction of the magnetic
field being perpendicular to the current i and the radius r, and determined by using
the right hand rule.
By substituting the value of B from Eq. (3.25) in Eq. (3.24), the voltage of the
whole coil is given by
NA m0 di
vcoil = ______ __ (3.26)
2pr dt
where N = Number of turns on the coil
A = Cross-sectional area of the turn (one of the smallest loops) in m2
m0 = 4p × 10–7 H/m is the permeability of the free space
r = Radius of the coil in m
di
__ = Rate of change of the current
dt
Equation (3.26) can also be written in the following form
di
vcoil = m0 nA __ (3.27)
dt
N N
where n = ____ = __ is the turns per unit length of the winding (coil) in turns/m as
2pr l
l = 2pr is the length of the winding (circular coil)
In order to get an output voltage proportional to the current, the output voltage of
the Rogowski coil must be integrated.
An active integrator, using an operational amplifier is shown in Fig. 3.12.
The output of the integrator is given by
1
vout = ___ Ú vin dt (3.28)
Rc
where vin = vcoil
After integrating the signal of Eq. (3.27) the total output voltage is
m0 nA
vout = _____ i (3.29)
Rc
The r.m.s value of the output voltage (vout) is given by
Dr. Raju Chintakindi EEE Vaagdevi
PCB 1 PCB 2
i
i
V
v
(a) (b)
Fig. 3.13 Recent design of Rogowski coil: (a) Front view (b) Side view
limited in the volume of cores and windings which can be accomodated without the
diameter of the porcelain insulator becoming uneconomically large, but for two or
three cores and secondary windings of modest output it offers a compact arrangement.
In Type C, the cores and secondary windings are housed in the helmet or live-
tank and the earthed secondary leads brought down the insulator. This form of con-
struction is particularly suitable for use when high primary currents are involved as
it permits the use of a short bar primary conductor with consequent easing of the
electrodynamics and flux leakage problems. The major insulation may be wholly on
the secondary windings and cores or partially on the primary conductor, while the
secondary leads require insulating to withstand the system voltage where they pass
through the bases of the live-tank and down the porcelain bushing.
The major insulation used in such CTs is usually oil-impregnated paper. An alter-
native method of insulating for high voltages employs sulphur-hexafluoride (SF6) gas,
usually at a pressure in the region of two to three times the atmospheric pressure.
3.2.17 Open-circuiting of the Secondary Circuit of a CT
If a current transformer has its secondary circuit opened when current is flowing
in its primary circuit, there is no secondary mmf (ampere-turns) to oppose that due
to the primary current and all the primary mmf acts on the core as a magnetizing
quantity. The unopposed primary mmf produces a very high flux density in the core.
This high-flux density results in a greatly increased induced voltage in the secondary
winding. With rated primary current flowing this induced voltage may be few hun-
dred volts for a small CT but may be many kilovolts for a large high ratio protective
CT. With system fault current flowing, the voltage would be raised in nearly direct
proportion to the current value.
Such high voltages are dangerous not only to the insulation of the CT and con-
nected apparatus but more important, to the life of the operator. Hence, the secondary
circuit of a CT should never be opened while current is flowing in its primary circuit.
If the secondary circuit has to be disconnected while primary current is flowing, it
is essential first to short-circuit the secondary terminals of the CT. The conductor
used for this purpose must be securely connected and of adequate rating to carry the
secondary current, including what would flow if a fault occurs in the primary system.
Most of the current transformers have a short circuit link or a switch at secondary
terminals for short-circuiting purpose.
3.2.18 Modern Trends in CT Design
High-voltage CTs are the oil-filled type. At a system voltage of 400 KV and above
there is a severe insulation problem. CTs for this range of system voltage become
extremely expensive. Their performance is also limited due to the large dimensional
separation of the secondary winding from the primary winding. These problems are
overcome using SF6(gas) and clophen (liquid) as insulation, thus reducing the size
and cost of CTs.
A new trend is to use opto-electronic CTs and Rogowski coil current sensors to
tackle this problem occuring in Extra High Voltage (EHV) and Ultra High Voltage
(UHV) systems. A Rogowski coil and a linear coupler encircle the EHV conductor.
A signal proportional to the secondary current is generated and transmitted via the
communication channel. Light beem, laser beam and radio frequency are being used
to transmit this signal.
Dr. Raju Chintakindi EEE Vaagdevi
It is seen that the secondary voltage supply seldom creates any problem but prob-
lems with secondary current supply arise frequently.
3.3 VOLTAGE TRANSFORMERS (VTS)
Voltage transformers (VTs) were previously known as potential transformers (PTs).
They are used to reduce the power system voltages to standard lower values and to
physically isolate the relays and other instruments (meters) from the high voltages
of the power system. The voltage ratings of the secondary windings of the VTs have
been standardized, so that a degree of interchangeability among relays and meters of
different manufacturers can be achieved. The standard voltage rating of __ the second-
ary windings of the VTs used is practice is 110 V line to line or 110/÷3 volts line to
neutral. Therefore, the voltage ratings of the voltage (pressure) coils of protective
__
relays and measuring instrument (meters) are also 110 V line to line or 110/÷3 V line
to neutral. The voltage transformers should be able to provide voltage signals to the
relays and meters which are faithful reproductions of the primary voltages.
The accuracy of voltage transformers is expressed in terms of the departure of its
ratio from its true ration.
3.3.1 Theory of Voltage Transformers
Theory of voltage transformers (VTs) is essentially the same as that of the ordinary
power transformer. An ideal (perfect) VT is that in which when rated burden is con-
nected across its secondary, the ratio of voltage applied across the primary to the sec-
ondary terminal voltage is equal to the ratio of primary turns to secondary turns and
furthermore the two terminal voltages are in precise phase opposition to each other.
But in practical (actual) VTs, the above relation doesn’t hold good and errors are
introduced both in ratio and in phase angle. This can best be explained by the equiva-
lent circuit and phasor diagram for a VT shown in Fig. 3.16 and 3.17 respectively.
Ip Ip
Io
Rp X p IC Im R ¢S X ¢S
IC
Vp RC Xm Ep V ¢S Z b¢
The equivalent circuit of Fig. 3.16 is as viewed from primary side and all
quantities are referred to that side.
The symbols used in the equivalent circuit and phasor diagram are as follows.
K = Nominal (rated) transformation ratio or Nominal (rated) voltage ratio
Rated primary voltage Number of primary turns
= ____________________ = _______________________
Rated secondary voltage Number of secondary turns
vp = Primary terminal voltage
Ep = Primary induced voltage
vs = Secondary terminal voltage
Dr. Raju Chintakindi EEE Vaagdevi
¢
Vp Is
¢
reactance respectively
s
Rs, Xs = Secondary resistance, and leak- R
¢
Is
¢
age reactance. V ¢s = KVs
Is
V¢s = Secondary terminal voltage
Xs
Es
referred to the primary side =
kVs Fig. 3.17 Phasor diagram of a voltage
I¢s = Secondary current referred to transformer
primary side = Is/K
R¢s = Secondary resistance referred to primary side = K2 Rs
X¢s = Secondary leakage reactance referred to primary side = K2 Xs
Z¢b = Secondary burden referred to primary
= K2 Zb, f = Phase angle of the burden
b = Phase angle error
= Angle between Vp and reversed secondary voltage, V¢s
q = Angle between V¢s and Ip
fm = Core flux
The secondary terminal voltage is generated from induced voltage in secondary Es
after pahsor subtraction of voltage drops due to secondary winding’s resistance and
reactance. Secondary current Is lags Vs by the phase angle of burden. The primary
resistive and reactive drops (Ip Rp and Ip Xp) are supplied by applied voltage Vp and
are subtracted from Vp to derive primary induced voltage Ep. Ep is in opposition to
Es. The angle between Vp and reversed secondary voltage V¢s is termed as the phase
angle of transformer denoted by b.
3.3.2 VT Errors
The errors introduced by the use of voltage transformers are, in general, less serious
than those introduced by current transformers. It is seen from the phasor diagram
that, like current transformers, voltage transformers introduce an error, both in mag-
nitude and in phase, in the measured value of the voltage.
The voltage applied to the primary circuit of the VT cannot be obtained correctly
simply by multiplying the voltage across the secondary by the turns ratio K of the
transformer.
Dr. Raju Chintakindi EEE Vaagdevi
The divergence of the actual (true) ratio Vp/Vs from nominal (rated) ratio K depends
upon the resistance and reactance of the transformer windings as well as upon the
value of the exciting current of the transformer.
Ratio Error (Voltage Error)
The ratio error for VTs is defined as the error due to a difference in the actual trans-
formation ratio and the nominal (rated) transformation ratio.
In percentage, it is expressed as
Norminal ratio – Actual ratio
Percent ratio error = ________________________ × 100
Actual ratio
K – Ka K – Vp/Vs
= ______ × 100 = ________ × 100
Ka Vp/Vs
KVs – Vp
or Percent ratio error = ________ × 100 (3.31)
Vp
Number of primary turns
where K = Nominal voltage ratio = _______________________
Number of secondary turns
Vp
Ka = ___ = Actual transformation ratio
Vs
Vs = Secondary voltage, and
Vp = Primary voltage
Phase Angle Error
The phase difference between the primary voltage and the reversed secondary pha-
sors is the phase angle error of the VT. In order to keep the overall error within the
specified limits of accuracy, the winding must be designed to have:
(i) the internal resistance and reactance to an appropriate magnitude, and
(ii) mininum magnetizing and loss components of the exciting current required
by the core.
Limits of VT Errors for Protection
The accuracy of VTs used for meters and instruments is only important at normal
system voltages, where as VTs used for protection require errors to be limited over
a wide range of voltages under fault conditions. This may be about 5% to 150% of
nominal voltage. The ratio error and phase angle error for VTs required for protection
according to ISS : 3156 (Part III) 1966 are given in Table 3.2.
Table 3.2 Limits of Voltages and Phase Angle Errors for VTs
0.05 to 0.9 times rated primary voltage
0.25 to 1.0 times rated output at unity p.f.
Class Ratio Error Phase Angle Error (in Degrees)
3.0 ± 3% 2
5.0 ± 5% 5
of capacitor type VTs can be reduced by reducing its burden. It is due to the fact that
the series connected capacitors perform the function of a potential divider if the cur-
rent drawn by the burden is negligible compared to the current flowing through the
capacitors connected in series.
An electronic amplifier having high input impedance and VA output high enough
to supply the VA burden can be included in the capacitor type VT arrangement. Such
an arrangement gives a good transient response.
Finally, it can be concluded that the secondary voltage supply seldom creates any
problem but problems with secondary current supply arise frequently.
Opto-Electronic VTs
The operation of an opto-electronic VT is based on the fact that the voltage differ-
ence between the conductor and the ground manifests in an electric field between the
two electrodes. The opto-electronics send a circular polarized light beam that travels
through an optical fiber up the column. The light beam passes through three strategi-
cally placed Pockels cells on the return path. The circular polarization changes to
elliptical polarization as the light passes through a cell. The elliptical polarized lights
from each cell are sent back to the opto-electronics at the ground level. The weighted
measurements of the change of polarization in the three cells is used to determine the
voltage difference between the conductor and the ground.
IB N
N+
N
IY
(a) (b) (c)
Fig. 3.19 (a) Summation transformer (b) Phasor diagram of 3-phase input current
(c) Phasor diagram of summated output for 3-phase balanced input current
Dr. Raju Chintakindi EEE Vaagdevi
Using the derived equation, Ioutput can be calculated for different types of faults.
Table 3.4 shows the constants K1, K2 and K0 for various types of faults for a summa-
tion transformer.
Table 3.4 Constants for different types of faults for summation transformer
Type of Fault K0 K1 K2
R-G, Y-B, Y-B-G 3(N + 1) 2 + a2 2+a
Y-G, B-R, B-R-G 3(N + 1) a(2 + a2) a2(2 + a)
B-G, R-Y, R-Y-G 3(N + 1) a2(2 + a2) a(2 + a)
To CTs
R
–ve Phase Y Mixing
sequence filter K2I2 network K1I1 + K2I2
B
N
(a) (b)
Fig. 3.20 (a) Phase sequence ilter network (b) (K1 I1 + K2 I2) type phase sequence
f lter network
Dr. Raju Chintakindi EEE Vaagdevi
Ioutput = K0 I0 + K1 I1 + K2 I2 (3.34)
The constants K0, K1 and K2 depend on the device which is used to derive a single-
phase quantity from the 3-phase quantities.
The phase-sequence filter giving an output in the form of I1 – KI2 gives the most
uniform response for any type of fault. The value of K may be 5 or 6. Fig. 3.20(b)
shows a phase sequence filter of this type. Table 3.5 shows the values of constants for
general type phase sequence network and I1 – KI2 type phase-sequence filter.
Table 3.5 Value of Constants K0, K1 and K2, output of phase-sequence f lter
Type of Faults Any Summation Device (K1 – KI2) Type Device
K0 K1 K2 Output
R-G, Y-B, Y-B-G KZ Kp KN I1 – KI2
Y-G, B-R, B-R-G KZ aKP a2KN aI1 – a2KI2
B-G, R-Y, R-Y-G KZ a2KP aKN a2I1 – aKI2
K = 5 or 6
Kz = constant for zero-sequence component
KP = Constant for +ve sequence component
KN = Constant for –ve sequence component
EXERCISES
1. What are transducers? Why are they required in protection systems?
2. Explain the difference between a CT used for instrumentation and CT used for
protection.
3. Explain CT burden. How is it specified?
4. Discuss how saturation affects the accuracy of CTs. Explain the accuracy limit
factor or saturation factor.
5. Define the terms: (i) Rated short-time current (ii) Short-time factor (iii) Composit
error (iv) Knee point voltage (v) Rated short-circuit current
6. Discuss the theory of CT with the help of equivalent circuit and phasor diagram
and derive the expressions for actual transformation ratio and phase angle error.
7. Discuss the causes of ratio and phase angle errors in CTs. How can these errors
be minimized?
8. What do you mean by ratio correction factor in CTs? Derive an expression for
the same.
9. Discuss the various classification of CTs. Describe the construction of electro-
magnetic CTs.
10. What is an opto-electronic CT? Discuss its operation.
11. What is Rogowski coil current sensor? Describe its construction and operation
and derive the expression for the voltage induced. How can the voltage proportion
to the current be obtained?
12. Describe the characteristics of the Rogowski coil current sensor.
13. What is an auxiliary CT? Where is it used?
14. What is a linear coupler? Where is it used?
15. Discuss the different types of VTs with their areas of application.
16. What is a summation transformer? Where is it used?