JCX 161

The JCX-161 Bridge Navigational Watch Alarm System (BNWAS) Installation Manual provides detailed guidelines for the installation, operation, and maintenance of the system. It includes safety warnings, specifications, installation instructions for various components, and wiring diagrams. The manual emphasizes the importance of adhering to safety precautions to prevent electrical shocks, equipment malfunctions, and fires.

Uploaded by

Uday Liker
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views134 pages

JCX 161

The JCX-161 Bridge Navigational Watch Alarm System (BNWAS) Installation Manual provides detailed guidelines for the installation, operation, and maintenance of the system. It includes safety warnings, specifications, installation instructions for various components, and wiring diagrams. The manual emphasizes the importance of adhering to safety precautions to prevent electrical shocks, equipment malfunctions, and fires.

Uploaded by

Uday Liker
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 134

JCX-161

Bridge Navigational Watch Alarm System

INSTALLATION
MANUAL

For further information,contact:

Not use the asbestos

URL http://www.jrc.co.jp
Marine Service Department
Telephone : +81-3-3492-1305
Facsimile : +81-3-3779-1420
e-mail : [email protected]
AMSTERDAM Branch
Telephone : +31-20-658-0750
Facsimile : +31-20-658-0755
e-mail : [email protected]
SEATTLE Branch
Telephone : +1-206-654-5644
Facsimile : +1-206-654-7030
e-mail : [email protected]
CODE No.7ZPNA4321 01ETM ISO 9001, ISO 14001 Certified
OCT. 2013 Edition 1 JRC Printed in Japan
Revision history
JCX-161 BNWAS Installation Manual
Revision history

Revision Content Date

--- Initial version 2013-07-19

i
7ZPNA4321
Attention in use
JCX-161 BNWAS Installation Manual

Warning Symbols
In this Installation Manual and on the product, we use various pictorial indications to
handle the product safely and correctly and to prevent you from harming yourself and
other people or damaging those properties beforehand.

Meanings of the indications are shown below. Understand the meanings of signs
before proceeding to read the main text.
This indication is shown where any person is supposed to be in danger of
DANGER being killed or seriously injured if this indication is neglected or equipment is
not operated correctly.

This indication is shown where any person is supposed to be in


WARNING danger of being killed or seriously injured if this indication is neglected
or equipment is not operated correctly.

This indication is shown where any person is supposed to be injured


CAUTION or any property damage is supposed to occur if this indication is
neglected or equipment is not operated correctly.

Examples
marks indicate CAUTION (including DANGER and WARNING).
Detailed contents of CAUTION (“Electric Shock” in the example on left)
are shown in the mark.
Electrical Shock

marks indicate prohibition.


Detailed contents of prohibited actions (“Disassembling Prohibited” in
the example on left) are shown in the mark.
Disassembly
Prohibited

●marks indicate a specific action that must be followed or instruction.


Detailed contents of instructions (“Ensure the ground wire is connected
to a grounded terminal” in the example to the left.)
For Warning Label
The warning label is sticked on the top panel of the control unit (NCK-175). Do not remove,
damage, or modefy the waring label.

ii
7ZPNA4321
Attention in use
JCX-161 BNWAS Installation Manual

Do not disassemble or modify this equipment.


It may result in a fire, electrical shock, or equipment malfunction.

Do not use a power supply voltage other than the one specified.
It may result in a fire, electrical shock, or equipment malfunction.

Turn off the power supply switch before connecting or disconnecting cables to any
external equipment. Not turning it off may result in a fire or electrical shock.

If the power supply cable is damaged, ask for an exchange from the Japan Radio Co.,
Ltd (JRC) sales department, a nearby branch office, business office, or any JRC
agents.
The use of damaged cables may result in a fire or electrical shock.

If water leaks into the equipment, shut off the power, disconnect the plug from the
outlet, and contact the JRC sales department, a nearby branch office, business office,
or any JRC agents. Continued use of water-damaged equipment may result in a fire,
electrical shock, or equipment malfunction.

Do not attempt inspections or repairs on internal parts of the equipment.


Ask for internal inspections or equipment repairs by contacting the JRC sales
department, a nearby branch office, business office, or any JRC agents.
Inspections or repairs by non-qualified maintenance personnel may result in a fire or
electrical shock.

If equipment malfunctions, shut off the power and contact the JRC sales department, a
nearby branch office, business office, or any JRC agents. Continued use of the
equipment may result in a fire or electrical shock.

Do not attempt to exchange of the fuse by yourself.


For an exchange of the fuse, contact the JRC sales department, a nearby branch
office, business office, or any JRC agent.
Exchange by non-qualified maintenance personnel may result in a fire, electrical
shock, or equipment malfunction.

iii
7ZPNA4321
Attention in use
JCX-161 BNWAS Installation Manual

When disposing of this unit, abide by local laws and regulations.

Do not insert or drop any foreign objects such as metals into air vents or orifices. A fire,
electric shock or malfunction may occur.

If a strange smell, smoke, or unusual heat is emitted from any equipment, shut off the
power immediately and disconnect the power cable. Then contact the JRC sales
department, a nearby branch office, business office, or any JRC agent. Continued use
of the equipment may result in a fire or electrical shock.

Do not allow any loose wires or metal objects to fall inside of equipment. This may
result in a fire, electrical shock, or equipment malfunction.

CAUTION
Do not install the system near to a water source or in the area with humidity,
steam, dust, oil or smoke.
A fire, electric shock or machine failure may occur.

Do not touch the system with a hand or glove wet with fresh water or sea water.
Otherwise, An electrical shock or machine failure may occur.

When disconnecting the power cable, make sure to grab the plug.
Pulling on the cable may damage the cable, resulting in a fire or electrical
shock.

Do not connect or disconnect the power cable with a wet hand.


An electrical shock may occur.

iv
7ZPNA4321
Attention in use
JCX-161 BNWAS Installation Manual

CAUTION
When the system is exposed to fresh water or seawater, wipe it immediately.
Otherwise, a failure or malfunction may occur.

When cleaning the system surface, do not use any organic solvent such as
thinner or benzine; these solvents damage the surface coating.
To clean the surface, remove dust and debris and then wipe it with a clean dry
cloth.

Connect the ground wire to a grounded terminal. Otherwise, an electric shock


may occur as the result of a failure or earth leakage.

Avoid sharing a power source with a system (such as an air conditioner) that
generates a large amount of electronic noise. The system may not function
properly because of short - time voltage drop or noise carried from power
source.

Do not place the system on an unstable place such as a wobbly rack or incline.
The system may drop or fall, resulting in personal injuries and/or equipment
failure.

Do not place the system in a place exposed to direct sunlight. Otherwise it may
cause damage on the paint or seal on the surface.

Do not install the equipment near any radio equipment. Otherwise it may cause
a signal reception affected.

v
7ZPNA4321
Attention in use
JCX-161 BNWAS Installation Manual

CAUTION
Do not bring the system into a warm room while it is cool. Dew condensation
may occur inside, leading to a machine failure.

Before turning on the power switch again, make sure that the screen of the
display unit goes out. If the power switch is turnd on immediately after turned
off, it may cause malfunction.

Do not touch the system if your hand is wet.


An electrical shock may occur.

Do not press buttons of the reset button units and the display unit by
unnecessary strong force. Equipment malfunction may occur.

Do not rub absolutely with hard things such as screw drivers, files, etc. at
cleaning. Wipe the surface lightly with a soft cloth. Otherwise it may cause
damage on the paint or seal on the surface.

vi
7ZPNA4321
Contents
JCX-161 BNWAS Installation Manual

Contents
1 Specifications ................................................................................................................................1
1.1 Functions.................................................................................................................................1
1.1.1 Purpose of the system .....................................................................................................1
1.1.2 Operational mode .............................................................................................................1
1.1.3 Operation sequence of displays and alarms .................................................................2
1.2 Features ...................................................................................................................................3
1.2.1 Versatile functions with standard configuration............................................................3
1.2.2 Various reset devices and number of inputs .................................................................3
1.2.3 Output to external device ................................................................................................3
1.2.4 Remote maintenance function ........................................................................................4
1.3 Composition ............................................................................................................................5
1.4 Spare parts...............................................................................................................................6
1.4.1 Fuse for Control unit (NCK-175)......................................................................................6
1.4.2 Fuse for LCD Display unit (NWZ-4650) ...........................................................................7
1.5 Connection Diagram...............................................................................................................8
1.6 Vocabularies............................................................................................................................9
1.7 General specifications..........................................................................................................10
1.7.1 IEC60945 environment specification ............................................................................10
1.7.2 Power supply ..................................................................................................................10
1.7.3 Compass safe distance.................................................................................................. 11
1.8 Unit specifications ................................................................................................................12
1.8.1 Control unit (NCK-175)...................................................................................................12
1.8.2 LCD Display unit (NWZ-4650) ........................................................................................13
1.8.3 Reset button unit (NCJ-895) ..........................................................................................13
1.8.4 Reset button unit (Waterproof) (NCJ-896) ....................................................................14
1.8.5 Buzzer unit (NVS-785) ....................................................................................................14
1.8.6 Motion sensor (NYG-5)...................................................................................................15
1.8.7 LED warning lamp unit (NCD-2257) ..............................................................................15
2 Installation....................................................................................................................................16
2.1 Guidelines for BNWAS Installation......................................................................................16
2.2 Control unit (NCK-175) .........................................................................................................17
2.2.1 Installation space ...........................................................................................................17
2.2.2 Installation ......................................................................................................................18
2.3 LCD Display unit (NWZ-4650)...............................................................................................19

vii
7ZPNA4321
Contents
JCX-161 BNWAS Installation Manual

2.3.1 Installation space and installation position..................................................................19


2.3.2 Desktop installation .......................................................................................................21
2.3.3 Flush mounting installation...........................................................................................22
2.3.4 Removing the LCD Display unit for flash mounting installation ................................23
2.4 Reset button unit (NCJ-895).................................................................................................24
2.4.1 Installation ......................................................................................................................24
2.4.2 Flush mounting installation...........................................................................................24
2.4.3 Wall mounting installation .............................................................................................25
2.5 Reset button unit (Waterproof) (NCJ-896)...........................................................................27
2.5.1 Installation outline..........................................................................................................27
2.5.2 Installation ......................................................................................................................27
2.6 Buzzer unit (NVS-785)...........................................................................................................28
2.6.1 Installation ......................................................................................................................28
2.6.2 Flush mounting installation...........................................................................................28
2.6.3 Wall mounting installation .............................................................................................29
2.7 Motion sensor (NYG-5) .........................................................................................................31
2.7.1 Installation space ...........................................................................................................31
2.7.2 Installation ......................................................................................................................33
2.8 LED warning lamp unit (NCD-2257) .....................................................................................35
2.8.1 Installation ......................................................................................................................35
2.8.2 Flush mounting installation...........................................................................................35
2.8.3 Wall mounting installation .............................................................................................36
3 Wiring ...........................................................................................................................................38
3.1 Interconnection wiring..........................................................................................................38
3.2 Wiring cable...........................................................................................................................41
3.3 Control unit (NCK-175) .........................................................................................................42
3.3.1 Arrangement figure of terminal blocks.........................................................................42
3.3.2 Setting of DIP switch......................................................................................................45
3.3.3 Power supply terminal block (CBJ-165 TB1) ...............................................................46
3.3.4 Visual indication (LED warning lamp unit) / audible alarm (buzzer unit) connection
terminal block (CDJ-2486 TB1)...............................................................................................48
3.3.5 Reset button unit connection terminal block (CDJ-2486 TB2) ...................................51
3.3.6 Reset button unit / motion Sensor / external navigation equipment connection
terminal block (CDJ-2486 TB3)...............................................................................................53
3.3.7 External navigation equipment/ CAS (Central Alarm System)/ VDR connection
terminal block (CDJ-2486 TB4)...............................................................................................54
3.3.8 LCD Display unit connection terminal block (CDJ-2486 TB5) ....................................55

viii
7ZPNA4321
Contents
JCX-161 BNWAS Installation Manual

3.4 LCD Display unit (NWZ-4650)...............................................................................................56


3.5 Reset button unit (NCJ-895 TB1) .........................................................................................62
3.6 Reset button unit (Waterproof) (NCJ-896 TB1)...................................................................66
3.7 Buzzer unit (NVS-785 TB1) ...................................................................................................71
3.8 Motion sensor (NYG-5 TB1) .................................................................................................76
3.9 LED warning lamp unit (NCD-2257 TB1) .............................................................................79
4 Installation setting .......................................................................................................................82
4.1 Changing to maintenance mode..........................................................................................83
4.2 Setting BUZZER CH ..............................................................................................................84
4.3 Setting NMEA COMM (COMMUNICATION)..........................................................................85
4.4 Setting RMS OUTPUT ...........................................................................................................87
4.5 MAINTENANCE function ......................................................................................................88
4.5.1 EXTERNAL INPUT function ...........................................................................................88
4.5.2 INPUT DATA function .....................................................................................................89
4.5.3 Self-diagnosis (DIAGNOSIS) function ..........................................................................90
4.5.4 Firmware version and serial number display function................................................91
4.5.5 Password reset function................................................................................................93
4.6 MASTER RESET function.....................................................................................................93
4.7 SOFT UPDATE function........................................................................................................95
4.7.1 Updating ..........................................................................................................................95
4.7.2 Software update procedure ...........................................................................................96
5 Operation check ........................................................................................................................106
5.1 Operation check of the control unit (NCK-175) ................................................................106
5.1.1 Operation check by voltage.........................................................................................106
5.2 Operation check of other units ..........................................................................................108
5.3 Operation check with external equipment ........................................................................109
5.3.1 VDR output....................................................................................................................109
5.3.2 Navigation equipment alarm ....................................................................................... 113
6 Outline drawing ......................................................................................................................... 114
6.1 Control unit (NCK-175) ....................................................................................................... 114
6.2 LCD Display unit (NWZ-4650)............................................................................................. 115
6.3 Reset button unit (NCJ-895)............................................................................................... 116
6.4 Reset button unit (Waterproof) (NCJ-896) (Option).......................................................... 117
6.5 Buzzer unit (NVS-785)......................................................................................................... 118
6.6 Motion sensor (NYG-5) (Option) ........................................................................................ 119
6.7 LED warning lamp unit (NCD-2257) (Option) ....................................................................120

ix
7ZPNA4321
Contents
JCX-161 BNWAS Installation Manual

x
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1 Specifications
1.1 Functions
The system is a Bridge Navigational Watch Alarm System (BNWAS) consisting of a control unit, a
display unit, buzzer units, and reset devises. It is designed to prepare for any contingency in
which a duty officer is disabled to fulfill his duties due to a nap, health problem, or other reason.
Upon such an event, the system alerts other officers.

1.1.1 Purpose of the system

The purpose of the Bridge Navigational Watch Alarm System (BNWAS) is to monitor the motions
of the duty officer in the bridge and detect any his behavior disorder that may lead to a marine
accident.
To achieve the purpose, dormant period is set. If no reset operation is performed within the
dormant period, the system recognizes that the duty officer cannot fulfill his duties and outputs an
alarm in the bridge. If no response is given even after that, it alerts the captain or other qualified
officer for its situation.

1.1.2 Operational mode

BNWAS includes the following operation modes.


1) Auto Mode (Automatic mode)
While the ship's heading control system or the track control system is active, the
dormant period count down operates automatically. When their systems are not
activated, the countdown will not operate.

2) Manual On
The dormant period countdown operates continuously.

3) Manual Off
The dormant period countdown does not operate.
The Manual Off only stops the dormant period countdown. It operates the emergency
call, other call functions, and the bridge alarm transfer function.

Except in anchorage or in-bay navigation, operate the unit with “Manual On”.

1
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.1.3 Operation sequence of displays and alarms

Depending on the operation mode, the unit is activated and the dormant period countdown
starts. When the countdown ends, the following displays and alarms are triggered.

1) Visual Indication
At the end of this dormant period, the alarm system initiates a visual indication on the
bridge. The visible display is a blinking manner.

2) First Stage Bridge audible alarm (1st Stage Bridge audible alarm)
If not reset within 15 seconds since the visual indication is initiated, the BNWAS
additionally sounds a 1st stage bridge audible alarm on the bridge.

3) Second Stage Remote audible alarm (2nd Stage Remote audible alarm)
If not reset within 15 seconds since the 1st stage bridge audible alarm is initiated, the
BNWAS additionally sounds a 2nd stage remote audible alarm in the back-up officer's
and/or Master's location.

4) Third Stage Remote audible alarm (3rd Stage Remote audible alarm)
If not reset within 90 seconds (which can be set 0s, or between 90 ~ 180s) since the 2nd
stage remote audible alarm is initiated, the BNWAS additionally sounds a 3rd stage
remote audible alarm at the locations of further crew members.

Alarm sequence without acknowledgements

2
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.2 Features

1.2.1 Versatile functions with standard configuration

1) BNWAS function
When dormant period are measured, and the confirmation is not done, warning is
output with the visual indication and the alarms according to the sequence of 1.1.3.
2) Support of emergency call function and bridge alarm transfer function
The emergency call function is offered without optional equipment. The bridge alarm
can transfer an unacknowledged alarm with the serial interface that uses the
IEC61162-1 ALR sentence.

1.2.2 Various reset devices and number of inputs

1) Reset devices
A maximum of 6 pushbutton reset devices (NCJ-895 and NCJ-896) can be provided so
that the dormant period can be reset within 15 s in anywhere since the visual indication
starts. The reset function is equipped also in the LCD Display unit (NWZ-4650).

2) Motion sensor type reset device (option)


The motion sensor (NYG-5) which performs automatic reset by human presence and
motions can be installed.

3) Reset by external unit


The system supports the reset signal from other navigational equipment. The reset
signal can be input via. an IEC 61162 serial interface or a contact input.

1.2.3 Output to external device

1) System Failure output by contact signal


The system can output the System Failure to CAS by contact signal.

2) VDR output by serial interface


The system can output machine status or alarm situation to VDR by the serial interface
using the IEC61162-1 ALR sentence.

3
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.2.4 Remote maintenance function

When connected with a VDR provided remote maintenance from our company, the unit allows
you to monitor its status from a remote place.

4
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.3 Composition

Component list of bridge navigational watch alarm system (BNWAS)

No. Item Model Q'ty Mass (kg) Remarks


(exp.)
Standard configuration

1 Control unit NCK-175 1 4.5

Attached the operation


card (7ZPNA4319) ,power
2 LCD Display unit NWZ-4650 1 0.6 cable(CFQ-5766B),data
cable(CFQ-5951B),Fuse(1
A, 2piece)

3 Buzzer unit NVS-785 8 0.2

4 Reset button unit NCJ-895 3 0.2

Option

5 Motion sensor NYG-5 1 0.4

6 LED warning lamp unit NCD-2257 1 0.2

Reset button unit


7 NCJ-896 1 0.5 IP56
(Waterproof)

8 Instruction manual 7ZPNA4317 1 0.3

Fuse for NCK-175


9 Spare parts 7ZXNA4012 1 0.04
(2A, 1A, 1 piece each)
Fuse for NWZ-4650
10 Spare parts 7ZXNA4013 1 0.04
(1A, 2piece )
External Navigational
11 equipment connection CFQ-5767 1 0.1
cable

5
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.4 Spare parts

1.4.1 Fuse for Control unit (NCK-175)

Ship
Standard spare part Device name Qty
No.
Model: JCX-161 BNWAS (Bridge Navigational Watch Alarm System)
Qty Remarks
Service qty Spec. Spare
Item Outer dimension
No. part
name diagram (mm) Qty/ Qty/ Spare box
JRC code
device ship No.

Fuse φ6.4 MF60 NR 250V 2


1 1 1
30 (5ZFGD00010)

Fuse φ6.4 MF60 NR 250V 1


2 1 1
30 (5ZFGD00205)

Spare
Manufacturer JAPAN RADIO CO.,LTD. 7ZXNA4012
part code

6
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.4.2 Fuse for LCD Display unit (NWZ-4650)

Ship
Standard spare part Device name Qty
No.
Model: NWZ-4650 BNWAS (Bridge Navigational Watch Alarm System)
Qty Remarks
Service qty Spec. Spare
Item Outer dimension
No. part
name diagram (mm) Qty/ Qty/ Spare box
JRC code
device ship No.

Fuse φ6.4 MF60 NR 250V 1


1 2 6
30 (5ZFGD00205)

Spare
Manufacturer JAPAN RADIO CO.,LTD. 7ZXNA4013
part code

7
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual
1.5 Connection Diagram

8
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.6 Vocabularies

Reset This is a function to notify the control unit with pressing the reset
button on the reset button unit, etc. that an OOW (Officer Of
Watch) is not abnormal.
Visual Indication Before the alarm sounds, the system alerts to an OOW by
flashing the LCD screen on the display unit, the LED indicator on
the reset button unit, etc.
1st Stage Bridge When an OOW does not reset this system during visual
audible alarm indications, a 1st stage bridge audible alarm occurs.
At the 1st stage bridge alarm, the audible alarms sound in the
bridge.
2nd Stage Remote At a 2nd stage remote audible alarm, the audible alarms sound in
audible alarm setting backup officer’s rooms.
3rd Stage Remote At a 3rd stage remote audible alarm, all the audible alarms sound.
audible alarm

9
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.7 General specifications

1.7.1 IEC60945 environment specification

Operation temperature: -15 to 55°C


-25 to 55°C (NCJ-896 Reset button unit (Waterproof))
Relative humidity: 93% (at 40°C, without condensation)
Vibration: 2 to 13.2Hz amplitude ±1.0mm/ 13.2 to 100Hz acceleration 0.7m/s2

1.7.2 Power supply

Normal power supply: 100 to 120V AC / 200 to 240V AC ±10%, 50/60Hz


Emergency power supply: 24V DC ±10%
Maximum power consumption: 23.0W (100V AC), 22.7W (220V AC), 20.5W (24V DC)

Note 1: Maximum electric power consumption depends on the system configuration.


Example composition: NCK-175 x1, NWZ-4650 x1, NCJ-895 x1, NCJ-896 x2,
NVS-785 x8
Power consumption: 13.0W (max)
100V AC 0.13A (max)
220V AC 0.06A (max)
24V DC 0.54A (max)
Note 2: Emergency power supply must have enough capacity to supply an electric power for 6
hours after main power supply stops.

10
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.7.3 Compass safe distance

Unit: (m)
Compass safe distance
Standard Steering compass
Specimen
compass Standby steering compass
Emergency compass
LCD Display Unit Energized condition 0.3 0.2
NWZ-4650 Not energized condition 0.3 0.2
Control Unit Energized condition 1.0 0.6
NCK-175 Not energized condition 0.8 0.5
Reset Button Unit Energized condition < 0.1 < 0.1
NCJ-895 Not energized condition < 0.1 < 0.1
Reset Button Unit (W.P.) Energized condition < 0.1 < 0.1
NCJ-896 Not energized condition < 0.1 < 0.1
Buzzer Unit Energized condition < 0.1 < 0.1
NVS-785 Not energized condition < 0.1 < 0.1
Motion Sensor Unit Energized condition < 0.1 < 0.1
NYG-5 Not energized condition < 0.1 < 0.1
LED Warning Lamp Unit Energized condition < 0.1 < 0.1
NCD-2257 Not energized condition < 0.1 < 0.1

11
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.8 Unit specifications

1.8.1 Control unit (NCK-175)

1) Contact input Non-voltage contact input, 1 port (AUTO PILOT signal


input)
Rating: 12 V DC, 8 mA
2) Contact output - Relay contact output, 1 port (SYSTEM FAIL signal
output)
Rating: 125 V AC, 1 A; 110 V DC, 1 A
3) Serial - RS-422
communication Communication speed: 4.8 kbps (fixed)
- RS-485
Communication speed: 19.2 kbps (fixed)
130 [ohms] terminal
- RS-232C
Communication speed: 115.2 kbps (fixed)
4) Power consumption 2.5 W (MAX) (NCK-175 unit only)

12
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.8.2 LCD Display unit (NWZ-4650)

1) Serial communication - RS-485 Communication speed: 19.2 kbps


for communication with NCK-175
- RS-422C Communication speed: 4.8 kbps
for interface of external navigation equipment
2) Reset inputting function Pushbutton switch is used.
3) Alarm output function - Audible alarm
None
- Visual indication
Illumination of the LCD provides visual indication.
4) Setting - Backup officer selection / name
- Operational mode selection
- Time Interval
- Buzzer sound (continuous / intermittent)
(for NCJ-895/896, NVS-785)
- Password change
- Contrast, Dimmer, click sound, back light color
- Buzzer connection ON/OFF
- RMS output ON/OFF
5) Max. connections 1 unit
6) Power consumption 4W

1.8.3 Reset button unit (NCJ-895)

1) Reset input function The membrane switch is used.


2) Alarm output function - Audible alarm
75 dB(A) to 85 dB(A) (both inclusive)
The buzzer sound level (High/Low) can be changed.
The buzzer continuous/intermittent sound can be
changed from NWZ-4650.
- Visual indication
Illuminated section of membrane switch provides
visual indication.
3) Setting - Dimmer (3 levels)
4) Power consumption 0.6 W

13
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.8.4 Reset button unit (Waterproof) (NCJ-896)

1) Reset input function The membrane switch is used.


2) Alarm output function - Audible alarm
75 dB(A) to 85 dB(A) (both inclusive)
The buzzer sound level (High/Low) can be changed.
The buzzer continuous/intermittent sound can be
changed from NWZ-4650.
- Visual indication
Illuminated section of membrane switch provides
visual indication.
3) Setting - Dimmer (3 levels)
4) Waterproof spec. IP56
5) Power consumption 0.6 W

1.8.5 Buzzer unit (NVS-785)

1) Alarm output function - Audible alarm


75 dB(A) to 85 dB(A) (both inclusive)
The buzzer sound level (High/Low) can be changed.
The buzzer continuous/intermittent sound can be
changed from NWZ-4650.
2) Power consumption 0.4 W
3) Connected Number MAX. 23 units (MAX. 5 units / 1CH)

14
7ZPNA4321
1. Specification
JCX-161 BNWAS Installation Manual

1.8.6 Motion sensor (NYG-5)

1) Sensor type Infrared sensor


Detection range
Horizontal: 100 degrees
Vertical: 81 degrees
Distance: 2 to 4 m
2) Output specifications Open collector output
Rating: 50 V DC, 150 mA
3) Power consumption 0.4 W

4) Re-detection time Approx. 3 sec

※When a crew member detected his/her motion and then stopped its motion, this delay time is
that the motion sensor can detect motion again.

1.8.7 LED warning lamp unit (NCD-2257)

1) Light color Red


2) Setting Dimmer (3 levels)
3) Check function Lamp test can be performed from NWZ-4650.
4) Power consumption 0.5 W
5) Connected Number 1 unit

15
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2 Installation
2.1 Guidelines for BNWAS Installation
Guidelines for BNWAS Installation is shown below.
Moreover, refer to "1.5 Connection Diagram" and “3.1 Interconnection wiring” for the example of
installation.

[Guidelines for BNWAS Installation] (Example: case of Class NK)


(1) Reset devices:
(i) At least one reset device should be provided near each conning position in the
wheelhouse(W/H).
More reset devices may be provided to the workstations for navigation, manoeuvering
and monitoring in order for safe and effective operation, if desired.
A reset function may be initiated by motion sensors and navigational equipment such as
radar, auto-pilot, ECDIS, INS, etc.
(ii) One reset device should be provided to each bridge wing.
Where it is easy to reset a first stage alarm by a reset device located nearby in the
wheelhouse(W/H), reset devices are not required to be fitted at bridge wings.
(2) Visual indicators and First stage audible alarms
(i) A visual indicator and first stage audible alarm are to be provided in the wheelhouse(W/H).
When they are combined with a reset device, individual visual indicators and first stage
alarms are not required.
(ii) A visual indicator and first stage audible alarm are to be provided in the bridge wings.
Where a reset device is not provided in the case of 1(ii) above, the following functions
are required:
- Flashing indicator in the wheelhouse(W/H) should be visible from an operational position on
the bridge wing; and
- First audible alarm in the wheelhouse(W/H) should be audible from an operational position
on the bridge wing.
(3) Second stage audible alarms and Third stage audible alarms
(i) Second stage audible alarms should be located in the Captain's bedroom and Deck
officer's cabins.
In cases where there are three deck officers on board, one deck officer for duty may be
selected from the main panel and the alarm in the Captain's bedroom may be changed to
a third stage one.
(ii) Third stage alarms should be located in the Officer's Mess room, Saloon, Recreation
room and Ship's office.

16
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.2 Control unit (NCK-175)

2.2.1 Installation space

The space shown in the figure below shall be required for cooling and installation.

17
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.2.2 Installation

Decide the installation position, secure it with 4 screws.

40
280
200
(40)

18
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.3 LCD Display unit (NWZ-4650)

2.3.1 Installation space and installation position

NWZ-4650 has two different installation methods, desktop or flush mount.

For desktop installation, the installation space and attachment hole positions as shown in the
figure below are required.

Required installation space for desktop installation

Mount (bottom)

(Unit: mm)

19
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

For flush mounting installation, the installation space and attachment hole positions as shown in
the figure below are required.

Required installation space for flush mount

Provide maintenance space

142

Attachment hole

※ As shown in the above


figure, you may process the
corner C11 with φ25.

(Unit: mm)

20
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.3.2 Desktop installation

Install in the following procedure.

(1) Fix the desk rack at the required installation position by using screws (provided by the
shipyard).
(2) Insert the front panel into the main unit.
(3) Attach the rotational washer on the each side of the main unit.
(4) Attach the rotational washer on the each side of the desk rack.
(5) Assemble the main unit on the desk rack, insert the knob metal washer between the each side
of the desk rack and the each knob bolt, and fix the main unit by tightening the knob bolts.

(provided by the shipyard)

21
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.3.3 Flush mounting installation

Install in the following procedure.


Do not tighten a screw too much. Doing so may result in damage of installation holes.

(1) Insert the main unit in the installation location.


(2) Fix the main unit using screws (provided by the shipyard).
The sizes of the heads of the screws that are used are restricted as follows including the
washers.
• Diameter: Up to φ8 mm
• Height: Up to 4.5 mm
(3) Insert the front panel into the main unit

22
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.3.4 Removing the LCD Display unit for flash mounting installation

Remove the LCD Display unit in the following procedure.

(1) Insert a hexagonal wrench into a one of the 2 holes at the bottom of the front panel.
(2) Remove the front panel by pressing down the hexagonal wrench.

Mounting wall

Front panel

Press down

Prepare a board to protect Hexagonal wrench


the wall from being damaged. (provided by the shipyard)
Recommended size: 3 mm

23
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.4 Reset button unit (NCJ-895)

2.4.1 Installation

When installing it in a console panel, cut out the panel surface in the shape as shown in the
following figure.
When installing it by flush mounting, remove a lower grommet.
Or when installing it on the wall, remove the bracket from the Unit.

2.4.2 Flush mounting installation

Attach by the panel cut of the following figure.

24
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.4.3 Wall mounting installation

Install in the following procedure.

(1) Remove the 4 screws on the front panel.


(2) Remove the inside 4 screws.
(3) Remove the bracket for flash mount.
(4) Insert and tighten the screws removed in the first step to the screw holes.

(1) (2)

(3) (4)

25
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

Attach by the panel cut of the following figure.

26
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.5 Reset button unit (Waterproof) (NCJ-896)


There is a gasket between the top cover and the case. Because the gasket is the consumables,
tighten the screw of the top cover after completing confirming the operation.

2.5.1 Installation outline

NCJ-896 can be installed on a wall only. The space shown in the figure below is required for
installation.
After cable connection, fasten a cable ground well for waterproofing.

2.5.2 Installation

Attach by the panel cut of the following figure.

4- φ5.5 or M4

88

27
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.6 Buzzer unit (NVS-785)

2.6.1 Installation

When installing it in a console panel, cut out the panel surface in the shape as shown in the
following figure.
When installing it by flush mounting, remove a lower grommet.
Or when installing it on the wall, remove the bracket from the Unit.

2.6.2 Flush mounting installation

Attach by the panel cut of the following figure.

28
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.6.3 Wall mounting installation

Install in the following procedure.

(1) Remove the 4 screws on the front panel.


(2) Remove the inside 4 screws.
(3) Remove the bracket for flash mount.
(4) Insert and tighten the screws removed in the first step to the screw holes.

(1) (2)

(3) (4)

29
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

Attach by the panel cut of the following figure.

30
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.7 Motion sensor (NYG-5)

2.7.1 Installation space

NYG-5 can be installed on a wall only. The space shown in the figure below is required on the
right and left of the unit for angle adjustment. The detection range of the sensor is 50 degrees
for the right and left respectively.

Right-and-left
space

Sensor detection range

Horizontal direction Vertical direction

2.9

2.31

40.4°
1.73

1.15

0.58
5.1m

0.58

1.15

1.73
40.4°

2.31

2.9

3m

31
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

Range of detection (ambient air temperature +20°C)


a) Horizontal angle : 100°
b) Vertical angle : 81°
c) Distance : 2~4m

The motion sensor reacts to infrared ray radiated from a human body. Therefore, it does not
react to curtains but should not be located near a swaying incandescent lamp.
In addition, it must be noted that the sensor may react to small animals such as birds, dogs
and cats because any living organism radiates infrared ray.

Do not install NYG-5 in the following rapid temperature change place. Also do not close the
following heat radiating things to NYG-5:
a) Sunlight or another light strikes the NYG-5 directly.
b) Its installed place is above a heating appliance such as a stove, or blowing from or near a
ventilation mouth of an air-conditioner.
c) Something which causes a rapid temperature change is in detection range of NYG-5.
d) There is swaying or moving thing (with especially a temperature change) near or in the
detection range of NYG-5.
e) 50cm or less from lighting
f) Near radio antennas

And, once it perceives (reset), it will not be detected for about 3 seconds.

32
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.7.2 Installation

Turn the right and left screws counterclockwise to separate the sensor main unit and the stand.

Install the stand on a wall. Observe the following dimensions for installation.
The stand can be adjusted in angle by loosening the screws and rotating the stand even after
installed.

33
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

Install the sensor main unit with the screws removed in the previous step.

34
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.8 LED warning lamp unit (NCD-2257)

2.8.1 Installation

When installing it in a console panel, cut out the panel surface in the shape as shown in the
following figure.
When installing it by flush mounting, remove a lower grommet.
Or when installing it on the wall, remove the bracket from the Unit.

2.8.2 Flush mounting installation

Attach by the panel cut of the following figure.

35
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

2.8.3 Wall mounting installation

install in the following procedure.

(1) Remove the 4 screws on the front panel.


(2) Remove the inside 4 screws.
(3) Remove the bracket for flash mount.
(4) Insert and tighten the screws removed in the first step to the screw holes.

(1) (2)

(3) (4)

36
7ZPNA4321
2. Installation
JCX-161 BNWAS Installation Manual

Attach by the panel cut of the following figure.

37
7ZPNA4321
DISPLAY UNIT
NWZ-4650
(Flush mount TYPE)
3. Wiring

DC12V
DATA1 DATA 2
3 Wiring
DATA

7ZPNA4321
3.1 Interconnection wiring
JCX-161 BNWAS Installation Manual

CABLE CLAMP CABLE CLAMP

38
1 2 3 4 6 7 1 2

RS422
RS-485
TB4 TB4
TB5
DISPLAY VDR OUT AUTO MODE IN

SYS.FAIL OUT TB1


TB4
DC IN AC IN

3 4 5 1 2 4 5 TERMINAL BOARD

CONTROL UNIT (NCK-175)


E

*MAIN POWER
*DPYC-1.5 *WIRE
(SHIP’S MAIN)
AC100/220V 1PH

*DPYC-1.5 *BACK-UP POWER


CENTRAL ALARM SYSTEM
DC24V

*DOCK SUPPLY
BNWAS (JCX-161): INTERCONNECTION WIRING (1/3)
7ZPNA4321
39
RESET BUTTON UNIT:
1 *MPYC-7 1 NCJ-895
12V(+) +12V (W/H)
2 2
E(-) E
3 3
RS RS
TB2
TB1

4 4
VI VI
RESET1

5 5
1 2 3 4 5
1 2 3 4 5

BZ BZ
TERMINAL BOARD

RESET BUTTON UNIT:


1 *MPYCY-7 6 NCJ-896 (W.P.)
12V(+) +12V
CONTROL UNIT (NCK-175)

2 7 (PORT WING)
E(-) E
3 8
RS RS
TB2
TB1

4 9
VI VI
RESET2

5 10
1 2 3 4 5

BZ BZ
6 7 8 9 10

RESET BUTTON UNIT:


1 *MPYCY-7 11 NCJ-896 (W.P.)
12V(+) +12V
2 12 (STBD WING)
E(-) E
3 13
RS RS
TB2
TB1

4 14
VI VI
RESET3

5 15
1 2 3 4 5

BZ BZ
1112131415

MOTION SENSOR UNIT:


1 *MPYC-4 16 NYG-5
12V(+) +12V
2 17 (W/H)
E(-) E
TB1

3 18
1 2 3

RS RS
TB2

VI
RESET4

BZ
1617181920

MOTION SENSOR UNIT:


1 *MPYC-4 21 NYG-5
12V(+) +12V
2 22 (W/H)
E(-) E
TB1

3 23
1 2 3

RS RS
TB2

VI
RESET5

BZ
2122232425

*MPYC-2 *AUTO PILOT


12V(+)
E(-) [TIMER RESET SIGNAL]
RS
TB3
VI

RESET6
BZ 1 2 3 4 5
X-BAND RADAR
*MPYC-2 JMA-9122-6XA (JRC)
12V(+)
E(-) [TIMER RESET SIGNAL]

TB3
6 7 8
RS

RESET7
S-BAND RADAR
*MPYC-2 JMA-9132-SA (JRC)
12V(+)
E(-) [TIMER RESET SIGNAL]

TB3
RS

9 1011

RESET8
No.1 ECDIS
*MPYC-2 JAN-901B/701B/2000 (JRC)
RS

TB3
G

1213
[TIMER RESET SIGNAL]

RESET9
No.2 ECDIS
*MPYC-2 JAN-901B/701B/2000 (JRC)
RS

TB3
G

1415
[TIMER RESET SIGNAL]

RESET10

*DOCK SUPPLY
BNWAS (JCX-161): INTERCONNECTION WIRING (2/3)
JCX-161 BNWAS Installation Manual
3. Wiring
3RD AUDIBLE ALARM 2ND AUDIBLE ALARM
2ND/3RD 1ST AUDIBLE VISUAL
ALARM INDICATION
CH8 CH7 CH6 CH5 CH4 CH3 CH2 CH1

W/H
(NAV. BRI. DK)
WARNING
3. Wiring

TB1 TB1 TB1 TB1 TB1 TB1 TB1 TB1


TERMINAL LAMP UNIT:
1617 1415 1213 1011 8 9 6 7 4 5 1 2 3 BOARD NCD-2257
TB1_1
1 12V(+)
TB1_2
2 E(-) VISUAL INDICATION
TB1_3
CONTROL UNIT 3 VI

7ZPNA4321
(NCK-175)
<CH1> *MPYC-4

(OFFICER DK)
CAPTAIN’S BED RM CAPTAIN’S DAY RM
BUZZER UNIT: BUZZER UNIT:
NVS-785 NVS-785
<CH3> *MPYC-2 TB1_6 3
1 +12V 1 +12V
TB1_7 4
2 BZ(E) 2 BZ(E)
1
3 +12V OUT 3 +12V OUT
2
4 BZ(E) OUT 4 BZ(E) OUT

CHIEF OFFICER’S RM
BUZZER UNIT:
NVS-785
JCX-161 BNWAS Installation Manual

<CH4> *MPYC-2 TB1_8


1 +12V
TB1_9
2 BZ(E)
3 +12V OUT
4 BZ(E) OUT
2ND/3RD STAGE REMOTE
AUDIBLE ALARM
2ND OFFICER’S RM 2nd Stage Remote audible
BUZZER UNIT: alarm transfer to
NVS-785 selected back-up officer.
<CH5> *MPYC-2 TB1_10 MAX. 23 Units
1 +12V
TB1_11
2 BZ(E) (MAX. 5 Units / 1CH)

40
3 +12V OUT
4 BZ(E) OUT

3RD OFFICER’S RM
BUZZER UNIT:
NVS-785
<CH6> *MPYC-2 TB1_12
1 +12V
TB1_13
2 BZ(E)
3 +12V OUT
4 BZ(E) OUT

OFFS’ MESS RM OFFS’ LOUNGE RM SHIP’S OFFICE (PUBLIC DK)


BUZZER UNIT: BUZZER UNIT: BUZZER UNIT:
NVS-785 NVS-785 NVS-785
<CH7> *MPYC-2 TB1_14 3 3
1 +12V 1 +12V 1 +12V 3RD STAGE REMOTE
TB1_15 4 4
2 BZ(E) 2 BZ(E) 2 BZ(E) AUDIBLE ALARM
1 1
3 +12V OUT 3 +12V OUT 3 +12V OUT
2 2
4 BZ(E) OUT 4 BZ(E) OUT 4 BZ(E) OUT

*DOCK SUPPLY
BNWAS (JCX-161): INTERCONNECTION WIRING (3/3)
3. Wiring
JCX-161 BNWAS Installation Manual

3.2 Wiring cable


Cross section
No. Type Cable type Remarks
area
MAIN POWER –
1 AC power supply cable 2 x 1.5 mm2 DPYC-1.5
NCK-175
BACK-UP POWER
2 DC power supply cable 2 x 1.5 mm2 DPYC-1.5
– NCK-175
NWZ-4650 –
3 Power supply cable 2 x AWG22 CFQ-5766B NCK-175 or
Junction Box
NWZ-4650 –
4 Communication cable 2 x AWG26 CFQ-5951B NCK-175 or
Junction Box
Junction Box –
5 Power supply cable 2 x 1 mm2 MPYC-2
NCK-175
Junction Box –
6 Communication cable 2 x 0.75 mm2 TTYCS-1
NCK-175
NWZ-4650 --
7 Communication cable 4 x AWG22 CFQ-5767 Junction Box (--
External Device)
NCJ-895 –
8 I/O cable 5 x 1 mm2 MPYC-7 NCK-175
(MAX. 150m)
9 I/O cable 3 x 1 mm2 MPYC-4 NYG-5 – NCK-175
NCD-2257 –
10 I/O cable 3 x 1 mm2 MPYC-4
NCK-175
NVS-785 –
2
11 I/O cable 2 x 1 mm MPYC-2 NCK-175
(MAX. 150m)
NCJ-896 –
12 I/O cable 5 x 1 mm2 MPYCY-7 NCK-175
(MAX. 150m)
13 I/O cable 2 x 0.75 mm2 TTYCS-1 VDR – NCK-175
Junction Box --
14 Communication cable 4 x 0.75 mm2 TTYCS-1Q
External Device

41
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3 Control unit (NCK-175)

3.3.1 Arrangement figure of terminal blocks

The terminal blocks arrangement in a control unit is shown in the following figure.

42
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

(1) Input power supply terminal block (CBJ-165)

DC power AC power

43
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

(2) Control board terminal blocks (CDJ-2486)

Reset equipment / motion sensor / external navigation

Reset unit Visual / audible-alarm unit


DIP switch (S1)

External navigation equipment/CAS/VDR Display


DIP switch (S2)

44
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.2 Setting of DIP switch

1) DIP switch location (S1, S2)

Refer to the arrangement figure of terminal block (CDJ-2486).

2) DIP switch (S1, S2) function

The switch for debugging


At ordinary operation, set S1 and S2 as follows.
No other settings should be used.

S1 S2

OFF ON

45
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.3 Power supply terminal block (CBJ-165 TB1)

• Outline of terminal block

DC24V+ DC24V- FG AC(L) AC(N)

• Wiring table
Signal name
DC24V+ DC power input +
DC24V- DC power input -
FG FG
AC(L) AC power input
AC(N) AC power input

46
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Wiring method
The cable outer diameter corresponds to AWG 28 ~ 12.
1) Cable preparation work
Strip off insulation by 8 to 9 mm.

8-9mm

2) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as far
as it goes, and then insert the cable. After that, pull out the screwdriver.

3) Fixing of cable

Cable

Fix cables on the clamp by


a cable tie.

47
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.4 Visual indication (LED warning lamp unit) / audible alarm (buzzer unit) connection
terminal block (CDJ-2486 TB1)

• Outline of terminal block

1 17
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8

• Wiring table
Terminal No. Terminal name I/O Function Connected unit
1 CH1(VI) + O Visual alarm unit power output +
2 CH1(VI) - - Visual alarm unit power output - LED warning lamp unit
3 CH1(VI) VI O Visual alarm unit control output
Audible alarm unit CH2
4 CH2(BZ) + O
power output +
Buzzer unit
Audible alarm unit CH2
5 CH2(BZ) BZ O
control output
Audible alarm unit CH3
6 CH3 + O
power output +
Buzzer unit
Audible alarm unit CH3
7 CH3 BZ O
control output
Audible alarm unit CH4
8 CH4 + O
power output +
Buzzer unit
Audible alarm unit CH4
9 CH4 BZ O
control output
Audible alarm unit CH5
10 CH5 + O
power output +
Buzzer unit
Audible alarm unit CH5
11 CH5 BZ O
control output
Audible alarm unit CH6
12 CH6 + O
power output +
Buzzer unit
Audible alarm unit CH6
13 CH6 BZ O
control output

48
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual
Terminal No. Terminal name I/O Function Connected unit
Audible alarm unit CH7
14 CH7 + O
power output +
Buzzer unit
Audible alarm unit CH7
15 CH7 BZ O
control output
Audible alarm unit CH8
16 CH8 + O
power output +
Buzzer unit
Audible alarm unit CH8
17 CH8 BZ O
control output

49
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Wiring method
The cable outer diameter corresponds to AWG 28-12.
1) Cable preparation work
Strip off insulation by 5 to 6 mm.

5-6mm

2) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as far
as it goes, and then insert the cable. After that, pull out the screwdriver.

3) Fixing of cable

Cable

Fix cables on the clamp by


a cable tie.

50
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.5 Reset button unit connection terminal block (CDJ-2486 TB2)

• Outline of terminal block

25 1

RESET5 RESET4 RESET3 RESET2 RESET1

• Wiring table
Terminal No. Terminal name I/O Function Connected unit
1 RESET1 + O RESET1 power output +
2 RESET1 - - RESET1 power output -
3 RESET1 RS I RESET1 reset input Reset button unit (*1)
4 RESET1 VI O RESET1 visual alarm output
5 RESET1 BZ O RESET1 audible alarm output
6 RESET2 + O RESET2 power output +
7 RESET2 - - RESET2 power output - Reset button unit
8 RESET2 RS I RESET2 reset input External navigation
9 RESET2 VI O RESET2 visual alarm output equipment (*2)
10 RESET2 BZ O RESET2 audible alarm output
11 RESET3 + O RESET3 power output +
12 RESET3 - - RESET3 power output - Reset button unit
13 RESET3 RS I RESET3 reset input External navigation
14 RESET3 VI O RESET3 visual alarm output equipment (*2)
15 RESET3 BZ O RESET3 audible alarm output
16 RESET4 + O RESET4 power output +
17 RESET4 - - RESET4 power output - Reset button unit
18 RESET4 RS I RESET4 reset input External navigation
19 RESET4 VI O RESET4 visual alarm output equipment (*2)
20 RESET4 BZ O RESET4 audible alarm output

51
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual
Terminal No. Terminal name I/O Function Connected unit
21 RESET5 + O RESET5 power output +
22 RESET5 - - RESET5 power output - Reset button unit
23 RESET5 RS I RESET5 reset input External navigation
24 RESET5 VI O RESET5 visual alarm output equipment (*2)
25 RESET5 BZ O RESET5 audible alarm output
*1. The Reset button unit connected to RESET1 has a function of an emergency call.
*2. Connect with the "-" terminal and a "RS" terminal.

• Wiring method
Same as wiring method of Clause 3.3.4 CDJ-2486 TB1.

52
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.6 Reset button unit / motion Sensor / external navigation equipment connection
terminal block (CDJ-2486 TB3)

• Outline of terminal block

15 1

RESET10 RESET9 RESET8 RESET7 RESET6


• Wiring table
Terminal No. Terminal name I/O Function Connected unit
1 RESET6 + O RESET6 power output +
2 RESET6 - - RESET6 power output - Reset button unit
3 RESET6 RS I RESET6 reset input External navigation
4 RESET6 VI O RESET6 visual alarm output equipment (*1)
5 RESET6 BZ O RESET6 audible alarm output
6 RESET7 + O Motion sensor 1 power supply +
7 RESET7 - - Motion sensor 1 power supply - Motion sensor
8 RESET7 RS I Motion sensor 1 reset input

9 RESET8 + O Motion sensor 2 power supply +


10 RESET8 - - Motion sensor 2 power supply - Motion sensor
11 RESET8 RS I Motion sensor 2 reset input

External navigation equipment 1


12 RESET9 RS I
reset input External navigation
External navigation equipment 1 equipment
13 RESET9 G -
GND
External navigation equipment 2
14 RESET10 RS I
reset input External navigation
External navigation equipment 2 equipment
15 RESET10 G -
GND
*1. Connect with the "-" terminal and a "RS" terminal.

• Wiring method
Same as wiring method of Clause 3.3.4 CDJ-2486 TB1.

53
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.7 External navigation equipment/ CAS (Central Alarm System)/ VDR connection
terminal block (CDJ-2486 TB4)

• Outline of terminal block

7 1
TX- TX+ NC NO COM - +

VDR SYS.FAIL AUTO IN


OUT OUT

• Wiring table
Terminal No. Terminal name I/O Function Connected unit
Automatic navigation detection contact
1 AUTO IN + I
input + External navigation
Automatic navigation detection contact equipment
2 AUTO IN - I
input -
SYS.FAIL OUT System FAIL contact output
3 O
COM Common
CAS
SYS.FAIL OUT System FAIL contact output
4 O (CENTRAL
NO Normal Open
ALARM SYSTEM)
SYS.FAIL OUT System FAIL contact output
5 O
NC Normal Close
Between control unit and VDR,
6 VDR OUT TX+ O
RS-422 communication transmission +
VDR
Between control unit and VDR,
7 VDR OUT TX- O
RS-422 communication transmission -

• Wiring method
Same as wiring method of Clause 3.3.4 CDJ-2486 TB1.

54
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.3.8 LCD Display unit connection terminal block (CDJ-2486 TB5)

• Outline of terminal block

1 4
+ - SD+ SD-

• Wiring table
Terminal No. Terminal name I/O Function Connected unit
1 + O 12V power output +
2 - - 12V power output -
Between control unit and display unit, RS-485
3 SD+ I/O LCD Display unit
communication transmission/ reception +
Between control unit and display unit, RS-485
4 SD- I/O
communication transmission/ reception -

• Wiring method
Same as wiring method of Clause 3.3.4 CDJ-2486 TB1.

55
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.4 LCD Display unit (NWZ-4650)


• Outline of connector

6 contacts connector 4 contacts connector


[DATA 1]
[DATA 2] Connect with control unit.
Connect with external device. (Communication signal)
[TERM.]
Turn ON and OFF
terminal resistance when
connecting DATA1.

14 contacts connector
[DC12V DATA]
Connect with control unit. (Power supply input)

[E]
Chassis Earth Terminal
Connect to ship earth

56
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Wiring table
(1) 14 contacts connector
Contact Contact
I/O Function Connected unit
No. name
1 DC+ I 12V DC power input +
Control unit
2 DC- I 12V DC power input -
3 ALM_COM - unused
4 ALM_NO - unused
5 ALM_NC - unused
6 ACK_IN+ - unused
7 ACK_IN- - unused
8 SD0-A - unused
9 SD0-B - unused
10 SD3-A - unused
11 SD3-B - unused
12 SD6-A - unused
13 SD6-B - unused
14 GND - unused

57
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

(2) 4 contacts connector


Contact Contact
I/O Function Connected unit
No. name
Between control unit and display unit,
1 SD1-A I/O
RS-485 communication transmission/ reception -
Control unit
Between control unit and display unit,
2 SD1-B I/O
RS-485 communication transmission/ reception +
3 SD1-C - unused
Control unit
4 GND - Frame GND
(Chassis)

(3) 6 pins connector of


Contact Contact
I/O Function Connected unit
No. name
1 DCOUT+ - unused
2 DCOUT- - unused
External navigation equipment
3 RXD2-B I
RS-422 communication reception -
External navigation equipment
4 RXD2-A I
RS-422 communication reception + External navigation
External navigation equipment equipment
5 TXD2-B O
RS-422 communication transmission -
External navigation equipment
6 TXD2-A O
RS-422 communication transmission +

58
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual
• Wiring method

1) 14 contacts connector

Display unit rear:


Connector contact number

14 13
12 11 10
9 8 7 6
5 4 3
2 1

LCD Display unit Rear

Fuse Holder
(Built-in 1A Fuses)
From NCK-175
(Power input)

1A
Red
+
1A Black
-
CFQ5766
From NCK-175
(Unused)
Power supply cable
CFQ-5766B: 3 m (Accessory)
CFQ-5766F: 20 m (Option)

59
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) 4 contacts connector

TERM. Switch
Display unit rear: Connector contact number

1 4

2 3

LCD Display unit Rear

SD1-A Brown From NCK-175


Red (communication
SD1-B signal)
CFQ5951 SD1-C Green Unused
Data Cable
GND Shield Flame
GND
CFQ-5951B : 3 m (Accessory)
CFQ-5951F : 20 m (Option)

[TERM. Switch]
Move the TERM. switch (terminator) to ON.

(上)
(Up)
ON
ON
When the rubber cap
is removed, the switch
appears.

OFF
(下)
(Down)

60
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3) 6 contacts connector

LCD Display unit Rear

61
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.5 Reset button unit (NCJ-895 TB1)


• Outline of terminal block

5 1
BZ VI RS E +12V

• Wiring table
Terminal Terminal
I/O Function Connected unit
No. name
1 +12V I Power supply input +
2 E - Power supply input -
3 RS O Reset output Control unit
4 VI I Visual alarm input
5 BZ I Audible alarm input

62
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• How to open a lid


Please open, centering on left-hand side not to twist an inner membrane sheet.
When a membrane sheet separated, attach so that a white side becomes inside.

Membrane sheet:
White side is inside.

Open, centering on left-hand side.

• Wiring method
The cable outer diameter corresponds to AWG 28-12.

1) Wiring
5 1

DC Power Input and signal I/O


from NCK-175

63
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) Cable preparation work


Strip off insulation by 5 to 6 mm.

5-6mm

3) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as far
as it goes, and then insert the cable. After that, pull out the screwdriver.

4) Fixing of couching clip


After the cables are connected to the terminal block, coil tightly the couching clip in the
housing to the cables.

Coaching clip

64
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Setting of DIP switch

1) DIP switch location

DIP switch
(S1)

2) DIP switch (S1) function


Audible alarm

HI
LO

HI High volume
LO Low volume (default)

65
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.6 Reset button unit (Waterproof) (NCJ-896 TB1)


• Outline of terminal block

5 1
BZ VI RS E +12V

• Wiring table
Terminal Terminal
I/O Function Connected unit
No. name
1 +12V I Power supply input +
2 E - Power supply input -
3 RS O Reset output Control unit
4 VI I Visual indication input
5 BZ I Audible alarm input

66
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• How to open a lid


Please open, centering on left-hand side not to twist an inner membrane sheet.
When a membrane sheet separated, attach so that a white side becomes inside.

Membrane sheet:
White side is inside.

Open, centering on left-hand side.

• Wiring method
The cable outer diameter corresponds to AWG 28-12.

1) Wiring
5 1

DC Power Input and signal I/O


from NCK-175

67
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) Cable preparation work


Strip off insulation by 5 to 6 mm.

5-6mm

3) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as
far as it goes, and then insert the cable. After that, pull out the screwdriver.

4) Fixing of couching clip


After the cables are connected to the terminal block, coil tightly the couching clip in the
housing to the cables.

Coaching clip
68
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

5) Fixing of cable ground


Tighten firmly the cable ground.

Tighten firmly the cable ground.

6) Seal the place at cable entrance with filling silicon.

69
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Setting of DIP switch

1) DIP switch location

DIP switch
(S1)

2) DIP switch (S1) function


Audible alarm

HI
LO

HI High volume
LO Low volume (default)

70
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.7 Buzzer unit (NVS-785 TB1)


• Outline of terminal block

4 1
BZ(E) +12V BZ(E) +12V

OUT IN
• Wiring table
Terminal Terminal
I/O Function Connected unit
No. name
1 +12V I Power supply input +
Control unit
2 BZ(E) I Control input
3 +12V_OUT O Power output+
Next to NVS-785
4 BZ(E)_OUT O Control output

71
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• How to open a lid


Please open, centering on left-hand side not to twist an inner membrane sheet.
When a membrane sheet separated, attach so that a white side becomes inside.

Membrane sheet:
White side is inside.

Open, centering on left-hand side.

• Wiring method
The cable outer diameter corresponds to AWG 28-12.

1) Wiring
4 1

DC Power Input and signal I/O


from NCK-175

72
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) Cable preparation work


Strip off insulation by 5 to 6 mm.

5-6mm

3) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as
far as it goes, and then insert the cable. After that, pull out the screwdriver.

4) Fixing of couching clip


After the cables are connected to the terminal block, coil tightly the couching clip in the
housing to the cables.

Coaching clip

73
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Connection method in case two or more sets connect with one line

4 1 4 1

next NVS-785

DC power output and signal

DC power input and signal input.

74
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• Setting of DIP switch

1) DIP switch location

DIP switch
(S1)

2) DIP switch (S1) function


Audible alarm

HI
LO

HI High volume
LO Low volume (default)

75
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.8 Motion sensor (NYG-5 TB1)


• Outline of terminal block

3 1
RS E +12V

• Wiring table
Terminal Terminal
I/O Function Connected unit
No. name
1 +12V I Power supply input +
2 E - Power supply input - Control unit
3 RS O Reset output

76
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• How to open a lid


Please open, centering on left-hand side not to twist an inner cable.

Open, centering on left-hand side.

• Wiring method
The cable outer diameter corresponds to AWG 28-12.

1) Wiring
3 1

DC power input and signal I/O


from NCK-175

77
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) Cable preparation work


Strip off insulation by 5 to 6 mm.

5-6mm

3) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as far
as it goes, and then insert the cable. After that, pull out the screwdriver.

4) Fixing of couching clip


After the cables are connected to the terminal block, coil tightly the couching clip in the
housing to the cables.

Coaching clip
78
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

3.9 LED warning lamp unit (NCD-2257 TB1)


• Outline of Terminal block

3 1
VI E +12V

• Wiring table
Terminal Terminal
I/O Function Connected unit
No. name
1 +12V I Power supply input +
2 E - Power supply input - Control unit
3 VI I Control input

79
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

• How to open a lid


Please open, centering on left-hand side not to twist an inner membrane sheet.
When a membrane sheet separated, attach so that a white side becomes inside.

Membrane sheet:
White side is inside.

Open, centering on left-hand side.

• Wiring method
The cable outer diameter corresponds to AWG 28-12.

1) Wiring
3 1

DC power input and signal I/O


from NCK-175

80
7ZPNA4321
3. Wiring
JCX-161 BNWAS Installation Manual

2) Cable preparation work


Strip off insulation by 5 to 6 mm.

5-6mm

3) Wiring to terminal block


Prepare a flat head screwdriver in which the spring of a terminal block carries out full
opening at 3.5 mm or less in width.

3.5mm

Insert the screwdriver into a square opening on upper portion of the terminal block as far
as it goes, and then insert the cable. After that, pull out the screwdriver.

4) Fixing of couching clip


After the cables are connected to the terminal block, coil tightly the couching clip in the
housing to the cables.

Coaching clip
81
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual
4 Installation setting
After the completing the installation and the wiring for the JCX-161, set the details in maintenance
mode.
Implement the following operations according to the system specification of each vessel.
> Setting BUZZER CH (Clause 4.2)
> Setting NMEA COMM (Clause 4.3)
> Setting RMS OUTPUT (Clause 4.4)
> MAINTENANCE function (Clause 4.5)
- EXTERNAL INPUT function (Clause 4.5.1)
- INPUT DATA function (Clause 4.5.2)
- Self-diagnosis (DIAGNOSIS) function (Clause 4.5.3)
- Firmware version and serial number display function (Clause 4.5.4)
- Password reset function (Clause 4.5.5)
> MASTER RESET function (Clause 4.6)
> SOFT UPDATE function (Clause 4.7)

82
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.1 Changing to maintenance mode


Before starting this installation setting, the mode must be changed to a maintenance mode to
prevent an operation error.
Change the mode to a maintenance mode by the initial operation.

Operating procedure

1) Display a main menu by pressing (normal mode).

2) Press long and for 3 seconds.

3) The menu is changed to a maintenance menu (maintenance mode).


When the mode is changed to a maintenance mode, the [M] icon is displayed at the bottom of
the screen.

BNWAS MENU Press and for 3 seconds


SET VALUE
OFFICER CALL
ALARM
HISTORY BNWAS EQUIPMENT
DISPLAY BUZZER CH
BUZZER TEST NMEA COMM
■ RMS OUTPUT
MAINTENANCE The [M] icon is
Normal mode MASTER RESET displayed.
SOFT UPDATE
■ [M]

Maintenance mode
• Returning to a normal mode

When is pressed or no operation is performed for 10 minutes, the mode is reset to a normal
mode.
When the power is turned on, the system starts in normal mode.

83
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.2 Setting BUZZER CH


This is to set to use (ON) / non-usage (OFF) information for the connection ports CH3 ~ CH8 of
buzzer units. The channel which does not connect a buzzer is set as OFF.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select “BUZZER CH” with , and then press . After that, the following screen is
displayed.

BNWAS BUZZER CH
CH3: ON ▼
CH4: ON ▼
CH5: ON ▼
CH6: ON ▼
CH7: ON ▼
CH8: ON ▼
■ [M]

3) Select a setting channel with , and then press in order to become ON/OFF setting
condition.

4) Select ON/OFF with , and then press . After that, its channel is set.

5) Press in order to return to maintenance mode.

84
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.3 Setting NMEA COMM (COMMUNICATION)


This function is to set a processing alarm list for receiving external navigation equipment alarms via
RS-422 serial signal from the 6 contacts connector. The list can be set to maximum 16 contents with
alarm number and alarm name. Alarms set at the list are output coverage as BNALR messages to
navigation equipment alarm sound and VDR.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select “NMEA COMM” with , and then press in order to display the following screen.

BNWAS NMEA COMM


01 RA301 RADER ALM1
02 RA302 RADER ALM2
03 EI501 ECDIS ALM1
NMEA COMM NO 04 ALARM NAME
05
▼06
■ [M] ALARM NO

3) Select a setting NMEA COMM number with , and then press . After that, the following
screen is displayed.

BNWAS NMEA COMM


ALARM NO
ALARM NAME
DELETE

■ [M]

4) Select a setting item with , and then press .


When “ALRAM NO” or “ALRAM NAME” is selected, a character input screen is displayed, and
then input an alarm number and an alarm name, respectively.
An alarm number can be inputted to 5 characters.
Moreover, an alarm name can be inputted to 12 characters.
Refer to the [Alarm number setting method] of the following page for the details of the alarm
number setting method.
The alarm name should be set arbitrary character strings to be able to identify which external
navigation equipment alarm is received.
Refer to the [Character input method] of the following page for the details of the character input
method.
When “DELETE” is selected, setting content in the NMEA COMM number is deleted.

5) Press in order to return to maintenance mode.

85
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

[Alarm number setting method]


Set the alarm number to correspond to the ALR (Set alarm state) sentence of IEC61162-1.

Alarm number (example): RA 300

$__ALR,hhmmss.ss,xxx,A,A,c--c*hh<CR><LF>

Alarm's description text


Alarm's acknowledge state ,A=acknowledged
V=unacknowledged
Alarm condition , A=threshold exceeded
V=not exceeded
Unique alarm number(identifier) at alarm source
Time of alarm condition change, UTC
Talker ID

[Character input method]

BNWAS ALARM NO

ABCDEFGHIJKLMNOPQRSTU
VWXYZ. 0123456789[\]_
"#$%&'()?@+-*/^,:;<=>
! [C][AC][OK][EXIT]
■ [M]

① Select one desirable character with , and then press .


[C] deletes one character, [AC] deletes all characters, [OK] ends this edit, and [EXIT] cancels
this edit.
Also deletes one character.

② When finished the edit, select [OK], and then press .


Then edited character string is reflected. When edit is canceled, select [EXIT], and then
press .

86
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.4 Setting RMS OUTPUT


This function is to set output ON/OFF of RMS messages to VDR.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select “RMS OUTPUT” with , and then press . After that, the following screen is
displayed.

BNWAS RMS OUTPUT


RMS OUTPUT: OFF ▼

■ [M]

3) Select a setting channel with , and then press in order to become the ON/OFF setting
condition.

4) Select ON/OFF with , and then press . After that, its channel is set.

5) Press in order to return to maintenance mode.

87
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.5 MAINTENANCE function

4.5.1 EXTERNAL INPUT function

This function is to display input conditions for the reset signals which are connected to the control
unit.
While pressing the reset button, "ON" is displayed on an applicable unit number (SW number).

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select sequentially “MAINTENANCE” and “EXTERNAL INPUT” with , and then the input
conditions for the reset signals are displayed.

BNWAS EXTERNAL INPUT


RESET
SW1 OFF , SW2 OFF
SW3 OFF , SW4 OFF
SW5 OFF , SW6 OFF
SW7 OFF , SW8 OFF
SW9 OFF , SW10 OFF
■ [M]

88
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.5.2 INPUT DATA function

This function is to display RS-422 input signal with character codes from external navigation
equipment, which is connected to the 6 contacts connector.
Receiving data from the serial ports can be displayed in the screen.
The serial ports and display formats (ASCII/BINARY) can be displayed.
The serial port which is an output setting cannot be displayed.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select sequentially “MAINTENANCE” and “INPUT DATA” with , and then press . After
that, the following screen is displayed.
3) Select a SIO[2] port with , and then press . After that, its receiving data is displayed in
the screen.
When is pushed again, the display stops.

When change the display format, press , and then the format of ASCII and BINARY
changes respectively.

Selected serial port Selected


Select a SIO[2] port. display format
SIO[2] ASCII *

'ENT':START/STOP Operation
'▲▼' :PORT
'<>' :ASCII/BINARY description
screen

When no data is displayed, check the connection and the setting of the serial port.

89
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.5.3 Self-diagnosis (DIAGNOSIS) function

This function is to perform self-diagnosis of the display unit and to display its result.
The following items can be diagnosed.
1) DISPLAY DIAG: ROM, RAM, and serial port of the display unit
2) MONITOR TEST: Screen LCD
The entire screen is highlighted repeatedly such as black to white, white to black.
Check if some dots are omitted.
3) CLICK SOUND TEST: Buzzer sound
Checks if the buzzer sounds of key operation.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select sequentially “MAINTENANCE” and “DIAGNOSIS” with .

3) Select a diagnosis item with , and then press . The diagnosis is performed and the
result is displayed.

90
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.5.4 Firmware version and serial number display function

This function is to display the firmware version, serial number and bar code number of the display
unit.
Moreover, about its serial number and bar code number, they can be rewritten from the display unit.
Also the firmware version, serial number and the bar code number held in the control unit itself can
be display. Moreover, about its serial number and bar code number, they can be rewritten.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

■ When firmware version, serial number and bar code number of the display unit are displayed:

2) Select sequentially “MAINTENANCE”, “SOFT VERSION”, and “DISPLAY VER” with .

BNWAS DISPLAY VER


FIRMWARE VER:
R01.00 Software version
SERIAL NO:
KF19372 Serial number
BARCODE NO:
01234567890 Bar code number
■ [M]

■ When firmware version, serial number and bar code number of the control unit are displayed:

2) Select sequentially “MAINTENANCE”, “SOFT VERSION”, and “CONTROL UNIT VER” with .

BNWAS CONTROL VER


FIRMWARE VER:
R01.00 Software version
SERIAL NO:
ME14346 Serial number
BARCODE NO:
00000000001 Bar code number
■ [M]

91
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

■ When serial number and bar code number of the display unit and the control unit are rewritten:

3) Select a rewriting item ("serial number" or " bar code number") with , and then press .
A character input screen is displayed, and then input a serial number and a bar code number,
respectively.
A serial number can be inputted to 7 characters.
Moreover, a bar code number can be inputted to 11 characters.
Refer to the [Character input method] of "4.3 Setting NMEA COMM" for the details of the
character input method.

92
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.5.5 Password reset function

This function is to reset a user password to the initial value “0000”.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select sequentially “MAINTENANCE” and “PASSWORD RESET” with .

3) Since the following pop-up is displayed, in performing, select "YES", and in canceling, select
"NO."
Then, is pressed.

RESET A PASSWORD?

YES NO

4.6 MASTER RESET function


When master reset is performed, the setting values are reset to the default values shown in the
following page.
Before performing master reset, it is recommended to keep a record of the current setting values.

Operating procedure

1) Display the maintenance menu by referring “4.1 Changing to maintenance mode”.

2) Select “MASTER REST” with , and then press .

3) Since the following pop-up is displayed, in performing, select "YES", and in canceling, select
"NO."
Then, is pressed.

INITIALIZE

YES NO

93
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

The setting range and initial value of a configuration parameter of operation

No. Subject name Classification Parameter Memory Initial value Remarks


AUTOMATIC
MANUAL
1 OPERATION MODE For users MANUAL ON Volatilization
ON
MANUAL OFF
INTERVAL 3min - 12min
2 For users Un-volatilizing 3
ALARM TIME 1min step
3rd STAGE 0 sec, 90 to 180sec
3 For users Un-volatilizing 90
ALARM TIME 10sec step
BRIDGE ALARM 0 to 30sec
4 For users Un-volatilizing 0
TRANSFER 10sec step
Audible alarm setting at the time
CAPTAIN of 2nd Stage Remote audible
C/O alarm
5 BACKUP OFFICER For users Un-volatilizing All ON
2nd OFFICER At least one audible alarm setting
3rd OFFICER should be ON. (don't perform all
OFF setting).
6 PASSWORD For users 0000-9999 Un-volatilizing 0000
7 CONTRAST For users 1 to 13 Un-volatilizing 5
8 DIMMER MAX For users 4 to 13 Un-volatilizing 9
9 DIMMER TYP For users 3 to 13 Un-volatilizing 6
10 DIMMER MIN For users 2 to 13 Un-volatilizing 4
11 CLICK SOUND For users ON/OFF Un-volatilizing ON Key click sound
12 BACK LIGHT For users ORANGE/WHITE Un-volatilizing WHITE
CONTINUOUS Sound pattern setting of audible
13 BUZZER SOUND For users Un-volatilizing ON
ON/OFF alarm
AC FAIL
DC FAIL
14 Alarm history For users Un-volatilizing NULL It holds up to 256 pieces.
COMM ERROR
SYSTEM FAIL
BackupOfficerName Character string up to
15 For users Un-volatilizing CAPTAIN
(Captain) nine characters
BackupOfficerName Character string up to
16 For users Un-volatilizing C/O
(Chief Officer) nine characters
BackupOfficerName Character string up to
17 For users Un-volatilizing 2ND
(2nd Officer) nine characters
BackupOfficerName Character string up to
18 For users Un-volatilizing 3RD
(3rd Officer) nine characters
For installation Connection / Non-connection
19 BuzzerSetting CH3 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
For installation Connection / Non-connection
20 BuzzerSetting CH4 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
For installation Connection / Non-connection
21 BuzzerSetting CH5 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
For installation Connection / Non-connection
22 BuzzerSetting CH6 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
For installation Connection / Non-connection
23 BuzzerSetting CH7 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
For installation Connection / Non-connection
24 BuzzerSetting CH8 ON/OFF Un-volatilizing ON
persons setting of audible alarm unit
16 kinds
ALARM NO: up to 5
For installation
25 NMEA COMM characters Un-volatilizing blank
persons
ALARM NAME: up to
12 characters
For installation
26 RMS output ON/OFF Un-volatilizing OFF RMS output On/Off setting
persons
For installation 7 degits, alphanumeric
27 Display serial number Un-volatilizing - It holds by a display unit.
persons character
11 degits,
Display bar code For installation
28 alphanumeric Un-volatilizing - It holds by a display unit.
number persons
character
Control unit serial For installation 7 degits, alphanumeric
29 Un-volatilizing - It holds by a control unit.
number persons character
11 degits,
Control unit bar code For installation
30 alphanumeric Un-volatilizing - It holds by a control unit.
number persons
character

94
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.7 SOFT UPDATE function


Software update of the display unit is performed with connecting to RS-232C terminal of an external
Personal Computer (PC) and operating the firmware update tool on the PC.

4.7.1 Updating

Software can be updated with connecting an external Personal Computer (PC).


When updating the software, a PC, a power supply/data cable, one set of PC software for the
update, and an update file are required.

■Required time of updating software

Unit Required Time (Standard) Remarks


LCD Display unit NWZ-4650 Approx. 2 minutes On baud rate setting: 115200 bps

■ Confirmation procedure of software version

1) Press in order to indicate the main menu (normal mode).

2) Press long and for more than 3 seconds.

3) So the screen is changed to the maintenance menu (maintenance mode).


When it changes to maintenance mode, the [M] icon is indicated under the screen.

BNWAS EQUIPMENT
BUZZER CH
NMEA COMM
RMS OUTPUT
MAINTENANCE The [M] icon is
MASTER RESET displayed.
SOFT UPDATE
■ [M]

4. Select sequentially "MAINTENANCE", "SOFT VERSION", "DISPLAY VER" with .

BNWAS DISPLAY VER


FIRMWARE VER:
R01.00
SERIAL NO:
KF19372
BARCODE NO:
01234567890
■ [M]

95
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

4.7.2 Software update procedure

1) Preparation
1.1) Prepare the followings:
- Personal Computer (PC)
OS: Windows XP, Windows Vista, or Windows 7
(The each OS is required corresponding to the Japanese version and the English version.)
Middleware library: .NET framework 3.5 is required.
COM port is required. When there is no COM port, prepare a USB serial conversion adapter.
- Power supply/data cable (CFQ-5953)
- One set of PC software (JrcUpdateTool.exe etc.) for the update
A distribution file "JrcUpdateTool_v030.zip" is extract.
Since the following file is included, it arranges to the same directory on a PC.

File name Contents

JrcUpdateTool.exe Executable file

JrcUpdateTool.exe.config Application setting file

jrcnet.csv JRC network definition file

lewnet.csv LWE network definition file

equipment.csv Equipment definition file

filter.csv Filter definition file

serial.csv Serial equipment definition file

Readme.txt Quick instruction document (English)

Readme_J.txt Japanese instruction document (for in- company use)

- Update file (xxxxxxx.img)

1.2) Copy one set of the PC software (JrcUpdateTool.exe etc.) for the update and the update file to
arbitrary folders of the PC.
1.3) Turn on the power supply of NWZ-4650. (Turn on the power supply of NCK-175.)
1.4) Confirm the current software version of NWZ-4650.
-> Refer to the "4.7.1 Updating" for the confirmation procedure of software version.
1.5) Turn off the power supply of NWZ-4650. (Turn off the power supply of NCK-175.)

96
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

1.6) Connect NWZ-4650 and the COM port (RS-232C) of the PC with the power supply/data cable
(CFQ-5953).
An internal wiring diagram is shown below.

NWZ-4650 Display

14Pins PC
Color Pin COM Port
Purple ⑦
Pin Function
Pink ⑩ ② Send

Bright ⑫ ③ Receive
Green
Brown ⑬ ⑤ GND

1.7) Turn on the power supply of NWZ-4650. (Turn on the power supply of NCK-175.)

97
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2) Performance of Update
2.1) Set NWZ-4650 into the standby state of software transfer.

① Press in order to indicate the main menu (normal mode).

② Press long and for more than 3 seconds.

③ So the screen is changed to the maintenance menu (maintenance mode).


When it changes to maintenance mode, the [M] icon is indicated under the screen.

BNWAS EQUIPMENT
BUZZER CH
NMEA COMM
RMS OUTPUT
MAINTENANCE The [M] icon is
MASTER RESET displayed.
SOFT UPDATE
■ [M]

④ Select " SOFT UPDATE " with .

⑤ Since the following pop-up is indicated, select "YES."

SOFTWARE
UPDATE

YES NO

⑥ So the following pop-up is indicated, and it is set the standby state of software transfer.

UPDATING NOW

98
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.2) When the PC is using other applications, close their applications, and then perform the PC
software (JrcUpdateTool.exe) for the update.

The screen at starting the PC software for the update

99
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.3) Setting a serial port

① Select [COM] in the [Interface] column, and change to the serial setting screen.

① Select

② Select the COM port for the update communication from the [Serial Port] list.
③ Click the [Open] button.

② Select

③ Click

100
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

④ Since the message "COM setting is OK." is indicated, click the [O.K.] button.

2.4) Select the connected destination equipment.

① Select the connected destination equipment " NPF-Low (Serial)" from the [Equipment] list.

② Select the baud rate [115200] from the [Baud rate] list.

① Select

② Select [115200]

101
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.5) Select the software for the update.

① Click the [Get version] button.


② Since the message "OK." is indicated, click the [OK] button.

If "Baudrate detection failed" is indicated, confirm the connection again.

③ Select [JCX-161-APL (Ver.R00.00.000)] from the [Software] list.

① Click

③ Select

102
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.6) Select the file for the update.

① Click the [Browse] button in order to open the file selection dialog.

① Click

② Select the update file (xxxxxxx.img) from the file selection dialog.

③ So the selected file information is displayed in the [Version] column and the [Information]
column.

103
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.7) Perform the update.

① Click the [Update] button, and then the update processing starts.

"Version: R00.00.000" and


"Information:J000,N000,C000"
are displayed always.

During updating, the following is indicated on the screen in the display unit. ① Click
R0030
Update now.
......

② When the update is completed normally, the following is indicated on the screen in the display
unit, and it automatically restarts.

R0000
Update completed.
Please reset.

③ When the update is completed, the progress bar may be indicated again, and the following
error pop-up may be indicated, but this update has been completed. Disregard this error, and
click the [OK] button.

104
7ZPNA4321
4. Installation setting
JCX-161 BNWAS Installation Manual

2.8) End the PC software (JrcUpdateTool.exe) for the update.

① When closing the application, click the [x] button of the window upper part.

① Click

3) Confirmation of software version


3.1) Confirm the current software version according to the same procedure in “4.7.1 Updating”. Then
check whether it has been updated or not.

3.2) Turn off the power supply of NWZ-4650. (Turn off the power supply of NCK-175.)

3.3) Remove the power supply/data cable connected between NWZ-4650 and the PC.

105
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

5 Operation check
5.1 Operation check of the control unit (NCK-175)

5.1.1 Operation check by voltage

Check the following operation at the terminal block on the PCB with a tester.

Item Tester Voltage


+ -
1 Check the 1st Stage Bridge audible
alarm output.
CH2: 1ST BUZZER TB1-4 TB1-5 ON: Approx. 0V
OFF: Unfixed
RESET1 TB2-5 TB2-2 ON: Approx. 12V
RESET2 TB2-10 TB2-7 OFF: Approx. 0V
RESET3 TB2-15 TB2-12
RESET4 TB2-20 TB2-17
RESET5 TB2-25 TB2-22
RESET6 TB3-5 TB3-2
2 Check the 2nd Stage Remote audible
alarm output.
CH3: CAPTAIN TB1-6 TB1-7 ON: Approx. 0V
CH4: C/O TB1-8 TB1-9 OFF: Unfixed
CH5: 2ND TB1-10 TB1-11
CH6: 3RD TB1-12 TB1-13
3 Check the 3rd Stage Remote audible
alarm output.
CH7: 3RD BUZZER TB1-14 TB1-15 ON: Approx. 0V
CH8: 3RD BUZZER TB1-16 TB1-17 OFF: Unfixed
4 Check the output for system fail.
(Generate AC FAIL, DC FAIL, or COMM ERROR.)
Normal Open TB4-3 TB4-4 Normal: Open
Abnormal: Short
Normal Close TB4-3 TB4-5 Normal: Short
Abnormal: Open

106
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual
Item Tester Voltage
+ -
5 Check the power output.
Main (AC/DC output) TP2 TP1 Normal: Approx. 12V
Backup (DC/DC output) TP3 TP1

107
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

5.2 Operation check of other units

Item Operation Content of check


NWZ-4650 Wait to pass dormant period. The visual indication starts. (The LCD
blinks.)
The 1st Stage Bridge audible alarm starts
in 15 seconds. (The reset button unit’s
LEDs blink short, and the buzzer sound.)
After that, press (ACK button) to stop
the alarm.
Press (dimmer) button. The brightness of LCD / operation key
changes.
Press (Emergency call) button All the buzzers of the reset button unit
for 2 seconds. /buzzer units sound.
After that, press (ACK button) to stop
their sound.
Select [OFFICER CALL] in the menu, The buzzers of the reset button unit and
and then perform it. backup officer’s buzzer unit sound.
After that, press (ACK button) to stop
their sound.
NCJ-895 Wait to pass dormant period. The visual indication starts. (The LEDs
NCJ-896 around the reset button blink.)
The 1st Stage Bridge audible alarm starts
in 15 seconds. (The reset button unit’s
LEDs blink short, and the buzzer sounds.)
After that, press the reset button to stop
the alarm.
Press [DIM] button. The brightness of the LEDs around the
reset button changes.
NYG-5 Cross in front of the sensor. The dormant period is reset.

108
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

Item Operation and operation Check content


NCD-2257 Wait to pass dormant period. The visual indication starts. (The LED lamp
blinks.)
The 1st Stage Bridge audible alarm start in 15
seconds. (The LED lamp blinks short.)
Press [DIM] button. The brightness of the LED lamp changes.
Select [BUZZER TEST] in the menu, The LED lamp lights on.
and then set the CH1(VISUAL) to
ON.
NVS-785 After the dormant period passed, wait The LED lamp lights on and the buzzer sounds.
to start the 2nd/3rd Stage Remote
audible alarms.
Select [BUZZER TEST] in the menu, The LED lamp lights on and the buzzer sounds.
and then set the CH2(1ST BUZZER)
– CH8(3RD BUZZER)to ON.

5.3 Operation check with external equipment

5.3.1 VDR output

Check the BNWAS serial output with the VDR maintenance software.
Item Operation Content of check
Output at state Press the reset button. A corresponding ALR sentence is
change outputted.
Periodic output The operation is unnecessary. The ALR sentence for showing no
warning is outputted with every 55
seconds.
An internal information (PJRCL/M)
sentence is outputted with every 1
minute.
Setup the VDR to acquire ALR sentences and "Remote Maintenance" (PJRCL/M) sentences.

Setup the VDR maintenance software


Setup Equipment Sentence Time out
VDR ALR 120 [s]
RMS PJRC 120 [s]

109
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

• ALR signal output specification

This system outputs messages as per IEC 61162-1 ALR sentence in accordance with "6.2
Output" of IEC 62616 Ed.1.

The format of ALR sentence is as follows.


(1) (2)(3)(4)(5)
$BNALR,hhmmss.ss,xxx,A,A,c--c*hh<CR><LF>

Alarm's description text

Alarm's acknowledge state ,A=acknowledged


V=unacknowledged
Alarm condition , A=threshold exceeded
V=not exceeded

Unique alarm number(identifier) at alarm source

Time of alarm condition change, UTC * Blank when there is no time information.

Talker ID:BN

(1) hhmmss.ss: this part may be left blank if the BNWAS does not include UTC time Information
(2) xxx: Designation of source of alarm or source of reset command. The automatic mode is
designated as "000".
(3) A: A = threshold exceeded
V = not exceeded
(4) A: A = Alarm acknowledged
V = Alarm unacknowledged
(5) c - - c: BNWAS mode : c1; c2; c3
c1= AUT or MAN or OFF
c2= Dormant period in min (03 - 12)
c3= Alarm stage: 1, 2 or 3.

In accordance with the above, the system outputs a BNALR sentence when any of the events in
the table below occurs.

110
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

Event Sentence (*1)


1st stage bridge audible alarm $BNALR,hhmmss.ss,000,A,V,C1=AUT;C2=03;C3=1*hh<CR><LF>
occurs
2nd stage remote audible alarm $BNALR,hhmmss.ss,000,A,V,C1=AUT;C2=03;C3=2*hh<CR><LF>
occurs
3rd stage remote audible alarm $BNALR,hhmmss.ss,000,A,V,C1=AUT;C2=03;C3=3*hh<CR><LF>
occurs
Reset signal input $BNALR,hhmmss.ss,001,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW1
Reset signal input $BNALR,hhmmss.ss,002,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW2
Reset signal input $BNALR,hhmmss.ss,003,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW3
Reset signal input $BNALR,hhmmss.ss,004,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW4
Reset signal input $BNALR,hhmmss.ss,005,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW5
Reset signal input $BNALR,hhmmss.ss,006,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW6
Reset signal input $BNALR,hhmmss.ss,007,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW7
Reset signal input $BNALR,hhmmss.ss,008,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW8
Reset signal input $BNALR,hhmmss.ss,009,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW9
Reset signal input $BNALR,hhmmss.ss,010,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
SW10
Reset signal input $BNALR,hhmmss.ss,021,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
LCD Display unit
Reset signal input $BNALR,hhmmss.ss,030,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
Serial port reset signal
Auto Pilot Input No. $BNALR,hhmmss.ss,100,V,A,C1=AUT;C2=03;C3=0*hh<CR><LF>
Set to Manual ON $BNALR,hhmmss.ss,021,V,V,C1=MAN;C2=03;C3=0*hh<CR><LF>
Set to Manual OFF $BNALR,hhmmss.ss,021,V,V,C1=OFF;C2=03;C3=0*hh<CR><LF>
Set to Automatic $BNALR,hhmmss.ss,021,V,V,C1=AUT;C2=03;C3=0*hh<CR><LF>
Dormant period changed $BNALR,hhmmss.ss,021,V,V,C1=AUT;C2=12;C3=0*hh<CR><LF>
Alarm received from $BNALR,hhmmss.ss,(SEQNO),A,V,BRIDGE ALARM*hh<CR><LF>
other navigational equipment
ACK received from $BNALR,hhmmss.ss,(SEQNO),A,A,BRIDGE ALARM*hh<CR><LF>
other navigational equipment
Alarm from other $BNALR,hhmmss.ss,(SEQNO),V,V,BRIDGE ALARM*hh<CR><LF>
navigational equipment restored

111
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual
Event Sentence (*1)
No Alarm per 55 seconds $BNALR,hhmmss.ss,000,V,V,C1=xx;C2=xx;C3=0*hh<CR><LF>
System fail $BNALR,hhmmss.ss,250,A,V,SYSTEM FAIL*hh<CR><LF>
AC Power fail $BNALR,hhmmss.ss,251,A,V,MAIN POWER FAIL*hh<CR><LF>
DC Power fail $BNALR,hhmmss.ss,251,A,V,BACK-UP POWER
FAIL*hh<CR><LF>
Control-Unit $BNALR,hhmmss.ss,253,A,V,COMMUNICATION
Communication fail FAIL*hh<CR><LF>
Emergency call $BNALR,hhmmss.ss,252,A,V,EMERGENCY CALL*hh<CR><LF>
*1. When various events occur, the portion of a bold letter changes.

112
7ZPNA4321
5. Operation check
JCX-161 BNWAS Installation Manual

5.3.2 Navigation equipment alarm

Navigation equipment alarm (Acknowledge on navigation equipment).


1. Output a warning on navigation equipment.
2. Check the navigation equipment alarm on BNWAS.
3. Acknowledge on the navigation equipment.
4. Check that the navigation equipment alarm of BNWAS stops.
5. Check the alarm history on BNWAS.

Navigation equipment alarm (Acknowledge on the BNWAS).


1. Output a warning on navigation equipment.
2. Check the navigation equipment alarm on BNWAS.
3. Acknowledge on the BNWAS. (Press button.)
4. Check that the navigation equipment alarm on BNWAS stops.
5. Check that the navigation equipment alarm of navigation equipment stops.
6. Check the alarm history on BNWAS.

• Navigation equipment alarm (example)

This system can receive the navigation equipment alarm correspond to


the ALR (Set alarm state) sentence of IEC61162-1.
The following is the example which received the alarm of the identification number 300
from the radar equipment.

$RAALR,hhmmss.ss,300,A,A,c--c*hh<CR><LF>

Alarm's description text


Alarm's acknowledge state ,A=acknowledged
V=unacknowledged
Alarm condition , A=threshold exceeded
V=not exceeded
Unique alarm number(identifier) at alarm source
Time of alarm condition change, UTC * Blank when there is no time information.
Talker ID: RA(Radar and/or radar plotting)

113
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual
6 Outline drawing
6.1 Control unit (NCK-175)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 4.5kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

Control unit (NCK-175) outline drawing

114
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.2 LCD Display unit (NWZ-4650)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.6kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

LCD Display unit (NWZ-4650) outline drawing (with the desk rack)

115
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.3 Reset button unit (NCJ-895)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.2 kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

Reset button unit (NCJ-895) outline drawing

116
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.4 Reset button unit (Waterproof) (NCJ-896) (Option)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.5 kg
IP SPEC : IP56
UNIT : mm
CATEGORY : Exposed

Reset button unit (Waterproof) (NCJ-896) outline drawing

117
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.5 Buzzer unit (NVS-785)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.2 kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

Buzzer unit (NVS-785) outline drawing

118
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.6 Motion sensor (NYG-5) (Option)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.4 kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

Motion sensor (NYG-5) outline drawing

119
7ZPNA4321
6. Outline drawing
JCX-161 BNWAS Installation Manual

6.7 LED warning lamp unit (NCD-2257) (Option)

COLOR : N4 SEMI-GLOSS
MASS : APPROX. 0.2 kg
IP SPEC : IP22
UNIT : mm
CATEGORY : Protected

LED warning lamp unit (NCD-2257) outline drawing

120
7ZPNA4321
JCX-161
Bridge Navigational Watch Alarm System

INSTALLATION
MANUAL

For further information,contact:

Not use the asbestos

URL http://www.jrc.co.jp
Marine Service Department
Telephone : +81-3-3492-1305
Facsimile : +81-3-3779-1420
e-mail : [email protected]
AMSTERDAM Branch
Telephone : +31-20-658-0750
Facsimile : +31-20-658-0755
e-mail : [email protected]
SEATTLE Branch
Telephone : +1-206-654-5644
Facsimile : +1-206-654-7030
e-mail : [email protected]
CODE No.7ZPNA4321 01ETM ISO 9001, ISO 14001 Certified
OCT. 2013 Edition 1 JRC Printed in Japan