18.03.03 Load Schedual

The document provides detailed specifications of the Main Distribution Board, including connected loads for various distribution boards and their respective standby loads. It lists the total connected load across different phases (R, Y, B) and includes descriptions of individual circuits and their load capacities. The total connected load is summarized as 1,159,890 kW with a standby load of 7,500 kW.

Uploaded by

Qanas Zahabi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
16 views22 pages

18.03.03 Load Schedual

The document provides detailed specifications of the Main Distribution Board, including connected loads for various distribution boards and their respective standby loads. It lists the total connected load across different phases (R, Y, B) and includes descriptions of individual circuits and their load capacities. The total connected load is summarized as 1,159,890 kW with a standby load of 7,500 kW.

Uploaded by

Qanas Zahabi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 22

Main Distribution Board

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

MSB.S 211,007 209,947 217,737 638,690 7,500

MSB 1 83,000 95,400 81,800 260,200

MSB 2 83,000 96,000 82,000 261,000 0

Total Connected Load (TCL) 377,007 401,347 381,537 1,159,890 7,500

MLTP
Page - 1 of 22 03-03-18
Main Distribution Board
MSB.S

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

EMSB 140,420 141,750 140,170 422,340 7,500

MDB.S1 5,000 5,000 5,000 15,000

MDB.S2 5,000 5,000 5,000 15,000

DB.B.L 3,380 5,650 4,760 13,790

DB.B.P 1,600 1,200 1,200 4,000

DB.G.L 5,090 4,200 5,520 14,810

DB.G.P 3,000 2,500 2,800 8,300

DB.1F.LP 3,900 3,640 6,250 13,790

DB.2F.LP 3,560 3,660 5,370 12,590

DB.3F.LP 3,560 3,660 5,370 12,590

DB.4F.LP 3,560 3,660 5,370 12,590

DB.5F.LP 7,610 5,220 6,700 19,530

DB.S.LP 6,400 6,200 5,400 18,000

DB.R.LP 3,670 3,350 3,570 10,590

DB SEC.G1 8,730 8,730 8,730 26,190

DB SEC.G2 2,197 2,197 2,197 6,590

DB SEC.G3 3,330 3,330 3,330 9,990

DB SEC.G4 1,000 1,000 1,000 3,000

SPARE 0 0 0

SPARE 0 0 0

Total Connected Load (TCL) 211,007 209,947 217,737 638,690 7,500

MSB S
Page - 2 of 22 03-03-18
Main Distribution Board
MSB.1

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

DB.T6.1.LP 8,300 9,600 8,200 26,100

DB.T7.1.LP 8,300 9,600 8,200 26,100

DB.T8.1.LP 8,300 9,600 8,200 26,100

DB.T9.1.LP 8,300 9,600 8,200 26,100

DB.T10.1.LP 8,300 9,600 8,200 26,100

DB.T11.1.LP 8,300 9,600 8,200 26,100

DB.T12.1.LP 8,300 9,600 8,200 26,100

DB.T13.1.LP 8,300 9,600 8,200 26,100

DB.T14.1.LP 8,300 9,600 8,200 26,100

DB.T15.1.LP 8,300 9,000 8,000 25,300

Total Connected Load (TCL) 83,000 95,400 81,800 260,200 0

MSB 1
Page - 3 of 22 03-03-18
Main Distribution Board
MSB.2

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

DB.T6.2.LP 8,300 9,600 8,200 26,100

DB.T7.2.LP 8,300 9,600 8,200 26,100

DB.T8.2.LP 8,300 9,600 8,200 26,100

DB.T9.2.LP 8,300 9,600 8,200 26,100

DB.T10.2.LP 8,300 9,600 8,200 26,100

DB.T11.2.LP 8,300 9,600 8,200 26,100

DB.T12.2.LP 8,300 9,600 8,200 26,100

DB.T13.2.LP 8,300 9,600 8,200 26,100

DB.T14.2.LP 8,300 9,600 8,200 26,100

DB.T15.2.LP 8,300 9,600 8,200 26,100

Total Connected Load (TCL) 83,000 96,000 82,000 261,000 0

MSB 2
Page - 4 of 22 03-03-18
Main Distribution Board
EMSB

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

ESMSB 81,000 81,000 81,000 243,000 3,000

EDB.L 8,120 9,350 7,470 24,940

EDB.P 3,300 3,400 3,700 10,400

Isolator for SAFF.01 2,500 2,500 2,500 7,500

Isolator for SAFF.02 2,500 2,500 2,500 7,500

Isolator for SAEF.01 3,000 3,000 3,000 9,000

Isolator for SAEF.02 3,000 3,000 3,000 9,000

Isolator for Garbage Compressor 4,000 4,000 4,000 12,000

Isolator for FP.01 15,000 15,000 15,000 45,000

Isolator for FP.02 15,000 15,000 15,000 45,000

Isolator for TP.01 1,500 1,500 1,500 4,500 4,500

Isolator for SP.01 1,500 1,500 1,500 4,500

SPARE 0 0 0

SPARE 0 0 0

SPARE 0 0 0

SPARE 0 0 0

Total Connected Load (TCL) 140,420 141,750 140,170 422,340 7,500

EMSB
Page - 5 of 22 03-03-18
Main Distribution Board
ESMSB

Connected Load (kW) Standby


Description Load
R Y B Total (kW)

Isolator for (Lobby) LAPF.01 3,000 3,000 3,000 9,000

Isolator for (Lobby) LAPF.02 3,000 3,000 3,000 9,000

Isolator for (Staire) SAPF.01 2,500 2,500 2,500 7,500

Isolator for (Staire) SAPF.02 2,500 2,500 2,500 7,500

Isolator for (Lift) LAPF.01 2,500 2,500 2,500 7,500

Isolator for (Lift) LAPF.02 2,500 2,500 2,500 7,500

Isolator for (Lift) LAPF.03 2,500 2,500 2,500 7,500

Isolator for (Lift) LAPF.04 2,500 2,500 2,500 7,500

Isolator for Window Cleaning System 3,000 3,000 3,000 9,000

Isolator for Lift.01 12,000 12,000 12,000 36,000

Isolator for Lift.02 12,000 12,000 12,000 36,000

Isolator for Lift.03 12,000 12,000 12,000 36,000

Isolator for Lift.04 12,000 12,000 12,000 36,000

Isolator for JP.01 4,000 4,000 4,000 12,000

Isolator for BP.01 2,000 2,000 2,000 6,000 3,000

Isolator for Garbage Shoot 3,000 3,000 3,000 9,000

SPARE 0 0 0

SPARE 0 0 0

Total Connected Load (TCL) 81,000 81,000 81,000 243,000 3,000

ESMSB
Page - 6 of 22 03-03-18
Distribution Board Location:
EDB.L Level:
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 10 1.5 LIGHTS EM. (STAIR-2) 18*10 MCB 180
1 Y 15 2.5 LIGHTS (STAIR-2) 18*100 SW. 1800
B 10 1.5 LIGHTS EM.(STAIR-2) 18*10 MCB 180
R 15 2.5 LIGHTS (STAIR-2) 18*100 SW. 1800
2 Y 15 2.5 LIGHTS (STAIR-1) 18*100 SW. 1800
B 10 1.5 LIGHTS EM.(STAIR-1) 18*10 MCB 180
R 15 2.5 LIGHTS (STAIR-1) 18*100 SW. 1800
3 Y 10 1.5 LIGHTS EM.(STAIR-1) 18*10 MCB 180
B 15 2.5 LIGHTS+EM.LIGHTS(STAIR-3) 5*100+5*10 SW. 550
R 10 1.5 LIGHTS+EM.LIGHTS+EXIT 3*100+18*10+6*10 SW. 540
4 Y 15 2.5 LIGHTS (Bas.) 9*(2*40)+2*100 SW. 920
B 10 1.5 EXIT+EM.LIGHT (Gr.) 6*10+13*10 SW. 190
R 15 2.5 LIGHTS (Gr.) 10*100 SW. 1000
5 Y 15 2.5 LIGHTS (Gr.) 8*100 SW. 800
B 15 2.5 LIGHTS (1F) 4*100+10*(2*40) SW. 1200
R 10 1.5 EXIT+EM.LIGHT (1F) 7*10+11*10 MCB 180
6 Y 15 2.5 LIGHTS (3F) 4*100+11*(2*40) SW. 1280
B 15 2.5 LIGHTS (2F) 4*100+11*(2*40) SW. 1280
R 10 1.5 EXIT+EM.LIGHT (2F) 7*10+14*10 MCB 210
7 Y 15 2.5 LIGHTS (4F) 4*100+11*(2*40) SW. 1280
B 15 2.5 LIGHTS (5F) 4*100+14*(2*40) SW. 1520
R 10 1.5 EXIT+EM.LIGHT (5F) 8*10+17*10 MCB 250
8 Y 10 1.5 EXIT+EM.LIGHT (3F) 7*10+14*10 MCB 210
B 10 1.5 EXIT+EM.LIGHT (4F) 7*10+14*10 MCB 210
R 15 2.5 LIGHTS (6F+7F) 10*100+8*10 SW. 1080
9 Y 15 2.5 LIGHTS (8F+9F) 10*100+8*10 SW. 1080
B 15 2.5 LIGHTS (10F+11F) 10*100+8*10 SW. 1080
R 15 2.5 LIGHTS (12F+13F) 10*100+8*10 SW. 1080
10 Y 15 - SPARE
B 15 2.5 LIGHTS (14F+15F) 10*100+8*10 SW. 1080
R 15 - SPARE
11 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
12 Y 15 - SPARE
B 15 - SPARE

TOTAL CONNECTED LOAD (kW)-SUMMER 24.940 8120 9350 7470

EDB.L
Page - 7 of 22 03-03-18
Distribution Board Location:
EDB.P Level:
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 40A HRC FUSES
WIRE LOAD
CKT CONTROLLED
PH RCCBO SIZE LOAD DESCRIPTION (WATTS)
No. BY
(mm²) R Y B
SECTION-1
PROTECTED BY
20 A
R 4 POWER (Bas. To 2nd Fl) 4*(2*100) SW. COMB. 800
30 mA
20 A
1 Y 4 POWER (3rd To 5th Fl) 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER (6th To 10th Fl) 5*(2*100) SW. COMB. 1000
30 mA
20 A
R 4 POWER (11th To 15th Fl) 5*(2*100) SW. COMB. 1000
30 mA
20 A
2 Y 4 POWER (Gr. To 5th Fl) for MD 6*100 SW. COMB. 600
30 mA
20 A
B 4 POWER (6th To 10th Fl) for MD 5*100 SW. COMB. 500
30 mA
20 A
R 4 POWER (11th To 15th Fl) for MD 5*100 SW. COMB. 500
30 mA
20 A
3 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 POWER 2*(2*100) SW. COMB. 400
30 mA
20 A
4 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
5 Y 4 Iso. For Gate Barrier 1*1000 Isolator 1000
30 mA
20 A
B 4 Iso. For Gate Barrier 1*1000 Isolator 1000
30 mA
20 A
R - SPARE
30 mA
20 A
6 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
7 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 0
20 A
8 Y - SPARE 0 0
30 mA
B 0
TOTAL CONNECTED LOAD (kW)-SUMMER 10.400 3300 3400 3700

EDB.P
Page - 8 of 22 03-03-18
Distribution Board Location:
MDB.S1 Level:
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT CONTROLLED
PH RCCBO SIZE LOAD DESCRIPTION (WATTS)
No. BY
(mm²) R Y B
SECTION-1
PROTECTED BY
R 1000
20 A
1 Y 4 SEC.Type.1 for 6th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
2 Y 4 SEC.Type.1 for 7th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
3 Y 4 SEC.Type.1 for 8th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
4 Y 4 SEC.Type.1 for 9th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
5 Y 4 SEC.Type.1 for 10th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 0
20 A
6 Y - SPARE 0 0
300 mA
B 0

TOTAL CONNECTED LOAD (kW)-SUMMER 15.000 5000 5000 5000

MDB.S1
Page - 9 of 22 03-03-18
Distribution Board Location:
MDB.S2 Level:
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT CONTROLLED
PH RCCBO SIZE LOAD DESCRIPTION (WATTS)
No. BY
(mm²) R Y B
SECTION-1
PROTECTED BY
R 1000
20 A
1 Y 4 SEC.Type.1 for 11th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
2 Y 4 SEC.Type.1 for 12th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
3 Y 4 SEC.Type.1 for 13th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
4 Y 4 SEC.Type.1 for 14th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 1000
20 A
5 Y 4 SEC.Type.1 for 15th Foor 3000 DB SEC.T.01 1000
300 mA
B 1000
R 0
20 A
6 Y - SPARE 0 0
300 mA
B 0

TOTAL CONNECTED LOAD (kW)-SUMMER 15.000 5000 5000 5000

MDB.S2
Page - 10 of 22 03-03-18
Distribution Board Location:
DB.B.L Level: Basement Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 40A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS (LIFT) 17*100 SW. 1700
1 Y 15 2.5 LIGHTS (LIFT) 17*100 SW. 1700
B 15 2.5 LIGHTS (LIFT) 17*100 SW. 1700
R 15 - SPARE
2 Y 15 2.5 LIGHTS Garbage Rms 18*100+1*10 SW. 1810
B 15 2.5 LIGHTS (LIFT) 17*100 SW. 1700
R 15 - SPARE
3 Y 15 - SPARE
B 15 - SPARE
R 10 - SPARE
4 Y 10 - SPARE
B 10 - SPARE
R 10 1.5 LIGHTS 11*(2*40) 880
5 Y 10 1.5 LIGHTS 12*(2*40) 960
B 10 1.5 LIGHTS 9*(2*40) 720
R 10 1.5 LIGHTS 10*(2*40) 800
6 Y 10 1.5 LIGHTS+COVE LIGHT 8m 11*100+8*10 1180
B 10 1.5 LIGHTS 8*(2*40) 40A 4P Contactor 640
Controlled by PB,
R 10 - SPARE and Timer
7 Y 10 - SPARE
B 10 - SPARE
R 15 - SPARE
8 Y 15 - SPARE
B 15 - SPARE

TOTAL CONNECTED LOAD (kW)-SUMMER 13.790 3380 5650 4760

DB.B.L
Page - 11 of 22 03-03-18
Distribution Board Location:
DB.B.P Level: Basement Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 20A HRC FUSES
WIRE LOAD
CKT CONTROLLED
PH RCCBO SIZE LOAD DESCRIPTION (WATTS)
No. BY
(mm²) R Y B
SECTION-1
PROTECTED BY
20 A
R 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
1 Y 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
B 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
R 4 POWER (LIFT) 4*100 SW. COMB. 400
30 mA
20 A
2 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
3 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 1000
20 A
4 Y 4 SEC.Type.01 3000 DB SEC.T.01 1000
300 mA
B 1000

TOTAL CONNECTED LOAD (kW)-SUMMER 4.000 1600 1200 1200

DB.B.P
Page - 12 of 22 03-03-18
Distribution Board Location:
DB.G.L Level: Ground Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 40A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 10 1.5 LIGHTS + EM.LIGHT 12*(2*40)+3*10 SW. 990
1 Y 15 2.5 LIGHTS + EM.LIGHT 12*100+2*10 SW. 1220
B 10 1.5 LIGHTS 10*(2*40) SW. 800
R 10 - SPARE
2 Y 10 - SPARE
B 10 1.5 LIGHTS 9*(2*40) SW. 720
R 10 - SPARE
3 Y 10 - SPARE
B 10 - SPARE
R 15 - SPARE
4 Y 15 - SPARE
B 15 - SPARE
R 15 2.5 LIGHTS 11*100 1100
5 Y 15 2.5 LIGHTS+COVE LIGHT 8m. 12*100+8*10 1280
B 15 2.5 LIGHTS 9*100 900
R 15 2.5 LIGHTS 9*100 900
6 Y 15 2.5 LIGHTS 10*100 1000
B 15 2.5 LIGHTS 16*100 1600
R 15 2.5 LIGHTS 11*100 1100
7 Y 15 2.5 LIGHTS 7*100 700
B 15 2.5 LIGHTS 15*100 40A 4P Contactor 1500
Controlled by PB,
R 15 2.5 LIGHTW 10*100 and Timer 1000
8 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
9 Y 15 - SPARE
B 15 - SPARE
R 10 - SPARE
10 Y 10 - SPARE
B 10 - SPARE

TOTAL CONNECTED LOAD (kW)-SUMMER 5090 4200 5520

DB.G.L
Page - 13 of 22 03-03-18
Distribution Board Location:
DB.G.P Level: Ground Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 30A HRC FUSES
WIRE LOAD
CKT CONTROLLED
PH RCCBO SIZE LOAD DESCRIPTION (WATTS)
No. BY
(mm²) R Y B
SECTION-1
PROTECTED BY
20 A
R 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
1 Y 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
B 4 POWER 3*100 SW. COMB. 300
30 mA
20 A
R 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
2 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*100 SW. COMB. 300
30 mA
20 A
R 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
3 Y 4 POWER 2*100 SW. COMB. 200
30 mA
20 A
B 4 JB For E.W.H. 1*2200 DP SW. 2200
30 mA
20 A
R 4 JB For E.W.H. 1*2200 DP SW. 2200
30 mA
20 A
4 Y 4 JB with AVA For FACP 1*1500 SW. COMB. 1500
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
5 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
6 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
TOTAL CONNECTED LOAD (kW)-SUMMER 8.300 3000 2500 2800

DB.G.P
Page - 14 of 22 03-03-18
Distribution Board Location:
DB.1F.LP Level: First Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 9*(2*40) 720
1 Y 15 2.5 LIGHTS 14*(2*40) 1120
B 15 2.5 LIGHTS 11*(2*40) 880
R 15 2.5 LIGHTS 10*(2*40) 800
2 Y 15 2.5 LIGHTS 9*(2*40) 720
B 15 2.5 LIGHTS 10*100 1000
R 15 2.5 LIGHTS 11*(2*40) 880
3 Y 15 2.5 LIGHTS 13*100+10*10 1400
B 15 2.5 LIGHTS 13*100 40A 4P Contactor 1300
Controlled by PB,
R 15 2.5 LIGHTS 11*100 and Timer 1100
4 Y 15 - SPARE
B 15 2.5 LIGHTS 10*100 1000
R 20 - SPARE
5 Y 20 - SPARE
B 20 - SPARE
R 20 - SPARE
6 Y 20 - SPARE
B 20 - SPARE
SECTION-2
60A,4POLE,30mA, RCCB
PROTECTED BY
20 A
R 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
7 Y 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
B 4 JB.1 for A/C 1*2070 DP SW. 2070
30 mA
20 A
R - SPARE
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
9 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
TOTAL CONNECTED LOAD (kW)-SUMMER 13.790 3900 3640 6250

DB.1F.LP
Page - 15 of 22 03-03-18
Distribution Board Location:
DB.2F.LP Level: 2nd. Floor
Typical DB.2F, 3F& 4F.LP (3 No.) Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 9*(2*40) 720
1 Y 15 2.5 LIGHTS 14*(2*40) 1120
B 15 2.5 LIGHTS 11*(2*40) 880
R 15 2.5 LIGHTS 13*(2*40) 1040
2 Y 15 2.5 LIGHTS 13*(2*40) 1040
B 15 2.5 LIGHTS 14*(2*40) 1120
R 15 2.5 LIGHTS 13*100+10*10 1400
3 Y 15 2.5 LIGHTS 11*100 1100
B 15 2.5 LIGHTS 13*100 40A 4P Contactor 1300
Controlled by PB,
R 15 - SPARE and Timer
4 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
5 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
6 Y 15 - SPARE
B 15 - SPARE
SECTION-2
PROTECTED BY
20 A
R 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
7 Y 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
B 4 JB.1 for A/C 1*2070 DP SW. 2070
30 mA
20 A
R - SPARE
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
9 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
TOTAL CONNECTED LOAD (kW)-SUMMER 12.590 3560 3660 5370
* Change color for balance

DB.2F.LP-3No
Page - 16 of 22 03-03-18
Distribution Board Location:
DB.5F.LP Level: 5Th. Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 11*(2*40) 880
1 Y 15 - SPARE
B 15 - SPARE
R 15 2.5 LIGHTS 6*(2*40) 480
2 Y 15 2.5 LIGHTS 9*(2*40) 720
B 15 2.5 LIGHTS 13*100+10*10 1400
R 15 2.5 LIGHTS 11*(2*40) 880
3 Y 15 2.5 LIGHTS 12*100 1200
B 15 2.5 LIGHTS 19*100 40A 4P Contactor 1900
Controlled by PB,
R 15 - SPARE and Timer
4 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
5 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
6 Y 15 - SPARE
B 15 - SPARE
SECTION-2
PROTECTED BY
20 A
R 4 POWER 3*100 SW. COMB. 300
30 mA
20 A
7 Y 4 POWER 3*100 SW. COMB. 300
30 mA
20 A
B 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
R 4 JB.1 for A/C/ 1*2070 DP SW. 2070
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
9 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 1*3000 40A 4P Contactor 3000
30 A Controlled by PB,
10 Y 6 Isolator for Signage Board 1*3000 3000
300 mA Timer and
B 1*3000 Photocell 3000

TOTAL CONNECTED LOAD (kW)-SUMMER 19.530 7610 5220 6700

DB.5F.LP
Page - 17 of 22 03-03-18
Distribution Board Location:
DB.S.LP Level:
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 60A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS for F06 7*100+10*10 800
1 Y 15 2.5 LIGHTS for F07 7*100+10*10 800
B 15 2.5 LIGHTS for F08 7*100+10*10 800
R 15 2.5 LIGHTS for F09 7*100+10*10 800
2 Y 15 2.5 LIGHTS for F10 7*100+10*10 800
B 15 2.5 LIGHTS for F11 7*100+10*10 800
R 15 2.5 LIGHTS for F12 7*100+10*10 800
3 Y 15 2.5 LIGHTS for F13 7*100+10*10 800
B 15 2.5 LIGHTS for F14 7*100+10*10 800
R 15 2.5 LIGHTS for F15 7*100+10*10 800
4 Y 15 2.5 LIGHTS for F06 7*100+10*10 800
B 15 2.5 LIGHTS for F07 7*100+10*10 80A 4P Contactor 800
Controlled by PB,
R 15 2.5 LIGHTS for F08 7*100+10*10 and Timer 800
5 Y 15 2.5 LIGHTS for F09 7*100+10*10 800
B 15 2.5 LIGHTS for F10 7*100+10*10 800
R 15 2.5 LIGHTS for F11 7*100+10*10 800
6 Y 15 2.5 LIGHTS for F12 7*100+10*10 800
B 15 2.5 LIGHTS for F13 7*100+10*10 800
R 20 2.5 LIGHTS for F14 7*100+10*10 800
7 Y 20 2.5 LIGHTS for F15 7*100+10*10 800
B 20 - SPARE
R 20 - SPARE
8 Y 20 - SPARE
B 20 - SPARE
SECTION-2
PROTECTED BY
20 A
R 4 POWER (6th To 9th Fl) for MD 8*100 SW. COMB. 800
30 mA
20 A
9 Y 4 POWER (10th To 12th Fl) for MD 6*100 SW. COMB. 600
30 mA
20 A
B 4 POWER (13th To 15th Fl) for MD 6*100 SW. COMB. 600
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
11 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
12 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
TOTAL CONNECTED LOAD (kW)-SUMMER 18.000 6400 6200 5400

DB.S.LP
Page - 18 of 22 03-03-18
Distribution Board Location:
DB.R.LP Level: Roof Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 40A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS+EM.LIGHTS 6*(2*40)+2*10 SW. 500
1 Y 15 2.5 LIGHTS+EXIT 2*(2*40)+6*100+2*10 SW. 780
B 15 2.5 LIGHTS 12*100 SW. 1200
R 15 2.5 LIGHTS 7*100 SW. 700
2 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
3 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
4 Y 15 -
B 15 -
SECTION-2
PROTECTED BY
20 A
R 4 POWER 4*100 SW. COMB. 400
30 mA
20 A
5 Y 4 POWER 5*100 SW. COMB. 500
30 mA
20 A
B 4 POWER 3*100 SW. COMB. 300
30 mA
20 A
R 4 JB for A/C .01 1*2070 DP SW. 2070
30 mA
20 A
6 Y 4 JB for A/C .02 1*2070 DP SW. 2070
30 mA
20 A
B 4 JB for A/C .03 1*2070 DP SW. 2070
30 mA
20 A
R - SPARE
30 mA
20 A
7 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
TOTAL CONNECTED LOAD (kW)-SUMMER 10.590 3670 3350 3570

DB.R.LP
Page - 19 of 22 03-03-18
Distribution Board Location:
DB.T6.1.LP Level: 6Th. Floor
Typical DB.T6.1.LP (18No) Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 100A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 8*100 SW. 800
1 Y 15 2.5 LIGHTS 10*100 SW. 1000
B 15 2.5 LIGHTS 8*100 SW. 800
R 15 2.5 LIGHTS + EF. 4*100+2*200 SW. 800
2 Y 15 - SPARE
B 15 2.5 LIGHTS 10*100 SW. 1000
R 15 2.5 EM.LIGHTS +EXIT 9*10+1*10 SW. 100
3 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
4 Y 15 - SPARE
B 15 - SPARE
SECTION-2
60A,4POLE,30mA, RCCB
PROTECTED BY
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
5 Y 4 POWER 4*(2*100) SW. COMB. 800
30 mA
20 A
B 4 POWER 4*(2*100) SW. COMB. 800
30 mA
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
6 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 POWER 2*100+1*(2*100) SW. COMB. 400
30 mA
20 A
7 Y 4 JB. for EWH 1*2200 DP SW. 2200
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
9 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 5000
20 A
11 Y 4 SEC.Type.02 15000 DB SEC.T.02 5000
300 mA
B 5000
R 0
20 A
12 Y - SPARE 0 0
300 mA
B 0

TOTAL CONNECTED LOAD (kW)-SUMMER 26.100 8300 9600 8200


* Change color for balance

DB.T6.1.LP-18No
Page - 20 of 22 03-03-18
Distribution Board Location:
DB.T15.1.LP Level: 15Th. Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 100A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 8*100 SW. 800
1 Y 15 2.5 LIGHTS 6*100 SW. 600
B 15 2.5 LIGHTS 8*100 SW. 800
R 15 2.5 LIGHTS + EF. 4*100+2*200 SW. 800
2 Y 15 - SPARE
B 15 2.5 LIGHTS 10*100 SW. 1000
R 15 2.5 EM.LIGHTS +EXIT 9*10+1*10 SW. 100
3 Y 15 - SPARE
B 15 - SPARE
R 15 - SPARE
4 Y 15 -
B 15 -
SECTION-2
60A,4POLE,30mA, RCCB
PROTECTED BY
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
5 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
6 Y 4 POWER (Microwave) 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER (Oven) 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 SPARE 2*100+1*(2*100) SW. COMB. 400
30 mA
20 A
7 Y 4 JB. for EWH 1*2200 DP SW. 2200
30 mA
20 A
B 4 POWER SW. COMB.
30 mA
20 A
R - SPARE
30 mA
20 A
8 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
9 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 5000
20 A
11 Y 4 SEC.Type.02 15000 DB SEC.T.02 5000
300 mA
B 5000
R 0
20 A
12 Y - SPARE 0 0
300 mA
B 0

TOTAL CONNECTED LOAD (kW)-SUMMER 25.300 8300 9000 8000

DB.T15.1.LP
Page - 21 of 22 03-03-18
Distribution Board Location:
DB.T15.2.LP Level: 15Th. Floor
Revision: 0

CONTROLLED BY: 100A TPN ON LOAD ISOLATOR WITH 3 Nos. 100A HRC FUSES
WIRE LOAD
CKT MCB CONTROLLED
PH SIZE LOAD DESCRIPTION (WATTS)
No. (A) BY
(mm²) R Y B
SECTION-1
60A,4POLE,300mA, RCCB
PROTECTED BY
R 15 2.5 LIGHTS 8*100 SW. 800
1 Y 15 2.5 LIGHTS 10*100 SW. 1000
B 15 2.5 LIGHTS 8*100 SW. 800
R 15 2.5 LIGHTS + EF. 4*100+2*200 SW. 800
2 Y 15 - SPARE
B 15 2.5 LIGHTS 10*100 SW. 1000
R 15 2.5 EM.LIGHTS +EXIT 9*10+1*10 SW. 100
3 Y 15 - SPARE SW.
B 15 - SPARE SW.
R 15 - SPARE SW.
4 Y 15 - SW.
B 15 -
SECTION-2
60A,4POLE,30mA, RCCB
PROTECTED BY
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
5 Y 4 POWER 4*(2*100) SW. COMB. 800
30 mA
20 A
B 4 POWER 4*(2*100) SW. COMB. 800
30 mA
20 A
R 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
6 Y 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
B 4 POWER 3*(2*100) SW. COMB. 600
30 mA
20 A
R 4 POWER 1*(2*100)+2*100 SW. COMB. 400
30 mA
20 A
7 Y 4 JB.1 for EWH 1*2200 DP SW. 2200
30 mA
20 A
B - SPARE
30 mA
20 A
R - SPARE
30 mA
20 A
10 Y - SPARE
30 mA
20 A
B - SPARE
30 mA
R 5000
20 A
11 Y 4 SEC.Type.02 15000 DB SEC.T.02 5000
300 mA
B 5000
R 0
20 A
12 Y - SPARE 0 0
300 mA
B 0

TOTAL CONNECTED LOAD (kW)-SUMMER 26.100 8300 9600 8200

DB.T15.2.LP
Page - 22 of 22 03-03-18