Cpu317f 2PNDP

The CPU 317F-2 PN/DP features password protection, a diagnostics buffer for error events, and maintenance-free data backup. It supports parameterization for various properties, integrated communication functions, and safety-oriented operations with self-tests and error diagnostics. The device is programmed using STEP 7 and has specific technical specifications including memory capacities, processing times, and communication interfaces.

Uploaded by

kadirhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views28 pages

Cpu317f 2PNDP

The CPU 317F-2 PN/DP features password protection, a diagnostics buffer for error events, and maintenance-free data backup. It supports parameterization for various properties, integrated communication functions, and safety-oriented operations with self-tests and error diagnostics. The device is programmed using STEP 7 and has specific technical specifications including memory capacities, processing times, and communication interfaces.

Uploaded by

kadirhan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 28

CPU 317F-2 PN/DP

Function

 Password protection;
a password concept protects the user program from unauthorized access.
 Diagnostics buffer;
the last 500 error and interrupt events are stored in a buffer for diagnostic purposes.
 Maintenance-free data backup;
all data is automatically backed up by the CPU if the voltage is interrupted and is available unchanged after the
voltage has been reconnected.

Parameterizable properties
The S7 configuration as well as the properties and response of the CPUs can beparameterized using STEP 7:

 Multi-Point Interface (MPI);


determination of node addresses.
 Start-up/cycle time behavior;
definition of maximum cycle time and loading.
 Clock memory;
setting of addresses.
 Protection level;
definition of access rights for program and data.
 System diagnostics;
definition of handling and scope of diagnostic messages.
 Watchdog interrupts;
setting of periodicity. Mar 2008
Page 1654 Siemens ITS
 Time-of-day interrupts;
setting of start date, start time, and periodicity.
 PROFIBUS DP master/slave interface;
user-oriented address allocation for distributed I/O.

Display and information functions


 Status and error indications;
LEDs indicate hardware, programming, time, I/O or bus errors and operating statuses such as RUN, STOP,
start-up.
 Test functions;
the PG is used to indicate signal status during program execution, to modify process variables independently
of the user program and to output the contents of stack memories.
 Information functions;
the PG can be used to obtain information about the memory capacity and operating mode of the CPU, the
current loading of the work and load memory, current cycle times and diagnostics buffer content in plain
text.

Integrated communication functions


 PG/OP communication
 Global data communication
 S7 basic communication
 S7 communication
 Open communication by means of TCP/IP
 PROFINET CBA
 Web server
 Data
Page 1655record routing Mar 2008 Siemens ITS
Communication
Safety-oriented and standard communication between the central controller and distributed stations takes place over
PROFIBUS DP and/or PROFINET. The specially developed PROFIsafe profile supports the transfer of user data
for the safety functions within the standard data message frame. Additional hardware components, e.g. special
safety buses are not required. The necessary software is either integrated in the hardware components as an
expansion of the operating system or loaded into the CPU later as a certified software block.

Mode of operation
The safety functions of the F-CPU are included in the F program of the CPU and in the fail-safe signal modules.
The signal modules monitor the output and input signals by means of discrepancy analysis and the injection of test
signals. The CPU checks the proper operation of the controller by means of periodic self-tests, command tests and
logic-based and time-based program execution checks. Furthermore, the I/O is checked using requests for signs of
life.If an error is diagnosed in the system, the system will be placed in a safe state. An F runtime license is not
required to operate the CPU 317F-2 PN/DP.

Programming
The CPU 317F-2 PN/DP is programmed in the same manner as the other SIMATIC S7 systems. The user program
for non-fail-safe plant units is created using tried and tested programming tools, e.g. STEP 7. SIMATIC S7
Distributed Safety option package The STEP 7 option package "SIMATIC S7 Distributed Safety" is required for
programming the safety-related program components. The package contains all the functions and blocks required to
create an F program. The F program with the safety functions is connected in F FBD or F LAD or using special
function blocks from the F library. Use of F FBD or F LAD simplifies configuration and programming of the
system and also acceptance testing thanks to the cross-system uniform presentation form. The programmer can
concentrate on configuration of the safety-related application without the need to use additional tools.

Technical specifications
Page 1656 Mar 2008 Siemens ITS
Technical specifications

6ES7 317-2FK14-0AB0
Product version
Hardware product version 01
Firmware version V3.2
General information
associated programming package STEP 7 V 5.5 or higher, Distributed Safety
V 5.4 SP4
Supply voltage
24 V DC Yes
Input current
Current consumption (rated value) 750 mA
Current consumption (in no-load operation), 150 mA
typ.Page 1657 Mar 2008 Siemens ITS
Inrush current, typ. 4A
I²t 1 A²·s
Power losses
Power loss, typ. 4.65 W
Memory
Work memory
•integrated 1 536 Kibyte
•expandable No
•Size of retentive memory for retentive data 256 Kibyte
blocks
Load memory
•pluggable (MMC) Yes
•pluggable (MMC), max. 8 Mbyte
•Data management on MMC (after last 10 a
programming), min.
Backup
•present Yes; Guaranteed by MMC (maintenance-
free)
•without battery Yes; Program and data
CPU-blocks
Number of blocks (total) 2 048; (DBs, FCs, FBs); the maximum
number of loadable blocks can be reduced
by the MMC used.
DB Page 1658 Mar 2008 Siemens ITS
•Number, max. 2 048; Number range: 1 to 16000
•Size, max. 64 Kibyte
FB
•Number, max. 2 048; Number range: 0 to 7999
•Size, max. 64 Kibyte
FC
•Number, max. 2 048; Number range: 0 to 7999
•Size, max. 64 Kibyte
OB
•Size, max. 64 Kibyte
Nesting depth
•per priority class 16
•additional within an error OB 4
CPU processing times
for bit operations, min. 0.025 µs
for word operations, min. 0.03 µs
for fixed point arithmetic, min. 0.04 µs
for floating point arithmetic, min. 0.16 µs
Counters, timers and their retentivity
S7 counter
•Number 512
•Retentivity
Yes
• adjustable
Page 1659 Mar 2008 Siemens ITS
0
• lower limit
511
• upper limit
Z 0 to Z 7
• preset
•Counting range
Yes
• adjustable
0
• lower limit
999
• upper limit
IEC counter
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
S7 times
•Number 512
•Retentivity
Yes
• adjustable
0
• lower
Page 1660 limit Mar 2008 Siemens ITS
511
• upper limit
No retentivity
• preset
•Time range
10 ms
• lower limit
9 990 s
• upper limit
IEC timer
•present Yes
•Type SFB
•Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total All, max. 256 KB
Flag
•Number, max. 4 096 byte
•Retentivity available Yes; MB 0 to MB 4095
•Retentivity preset MB 0 to MB 15
•Number of clock memories 8; 1 memory byte
Data blocks
•Retentivity adjustable Yes; via non-retain property on DB
•Retentivity preset Yes
Local data
Page 1661 Mar 2008 Siemens ITS
•per priority class, max. 32 768 byte; Max. 2048 bytes per block
Address area
I/O address area
•Inputs 8 192 byte
•Outputs 8 192 byte
•of which, distributed
8 192 byte
• Inputs
8 192 byte
• Outputs
Process image
•Inputs, adjustable 8 192 byte
•Outputs, adjustable 8 192 byte
•Inputs, default 256 byte
•Outputs, default 256 byte
Subprocess images
•Number of subprocess images, max. 1; With PROFINET IO, the length of the
user data is limited to 1600 bytes
Digital channels
•Inputs 65 536
•Outputs 65 536
•Inputs, of which central 1 024
•Outputs, of which central 1 024
Analog
Pagechannels
1662 Mar 2008 Siemens ITS
•Inputs 4 096
•Outputs 4 096
•Inputs, of which central 256
•Outputs, of which central 256
Hardware configuration
Racks, max. 4
Modules per rack, max. 8
Expansion devices, max. 3
Number of DP masters
•integrated 1
•via CP 4
Number of operable FMs and CPs
(recommended)
•FM 8
•CP, point-to-point 8
•CP, LAN 10
Time of day
Clock
•Hardware clock (real-time clock) Yes
•battery-backed and synchronizable Yes
•Deviation per day, max. 10 s; Typ.: 2 s
•Backup time 6 wk; At 40 °C ambient temperature
•Behavior of the clock following POWER- Clock continues running after POWER
ON Page 1663 OFF
Mar 2008 Siemens ITS
•Behavior of the clock following expiry of Clock continues to run with the time at
backup period which the power failure occurred
Operating hours counter
•Number 4
•Number/Number range 0 to 3
•Range of values 0 to 2^31 hours (when using SFC 101)
•Granularity 1 hour
•retentive Yes; Must be restarted at each restart
Clock synchronization
•supported Yes
•to MPI, master Yes
•to MPI, slave Yes
•to DP, master Yes; With DP slave only slave clock
•to DP, slave Yes
•in AS, master Yes
•in AS, slave Yes
•on Ethernet via NTP Yes; as client
1st interface
Type of interface Integrated RS 485 interface
Physics RS 485
Isolated Yes
Power supply to interface (15 to 30 V DC), 200 mA
max.
Functionality
Page 1664 Mar 2008 Siemens ITS
•MPI Yes
•DP master Yes
•DP slave Yes
•Point-to-point connection No
MPI
•Services
Yes
• PG/OP communication
Yes
• Routing
Yes
• Global data communication
Yes
• S7 basic communication
Yes
• S7 communication
No; but via CP and loadable FB
• S7 communication, as client
Yes
• S7 communication, as server
•Transmission rate, max. 12 Mbit/s
DP master
•Services
Page 1665 Yes
Mar 2008 Siemens ITS
• PG/OP communication
No
• Global data communication
Yes; I blocks only
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes
• S7 communication, as server
Yes
• Equidistance mode support
Yes; OB 61; isochronous mode can only
• Isochronous mode be used alternatively on PROFIBUS DP or
PROFINET IO
Yes
• SYNC/FREEZE
Yes
• Activation/deactivation of DP slaves
8
• Number of DP slaves that can be
simultaneously activated/deactivated,
Pagemax.
1666 Mar 2008 Siemens ITS
Yes; As subscriber
• Direct data exchange (slave-to-slave
communication)
Yes
• DPV1
•Transmission rate, max. 12 Mbit/s
•Number of DP slaves, max. 124
•Address area
8 Kibyte
• Inputs, max.
8 Kibyte
• Outputs, max.
•User data per DP slave
244 byte
• Inputs, max.
244 byte
• Outputs, max.
DP slave
•Services
Yes
• PG/OP communication
No
• Global data communication
Page 1667 No
Mar 2008 Siemens ITS
• S7 basic communication
Yes
• S7 communication
No
• S7 communication, as client
Yes; Connection configured on one side
• S7 communication, as server only
Yes
• Direct data exchange (slave-to-slave
communication)
No
• DPV1
•Transmission rate, max. 12 Mbit/s
•Automatic baud rate search Yes; only with passive interface
•Transfer memory
244 byte
• Inputs
244 byte
• Outputs
•Address area, max. 32
•User data per address area, max. 32 byte
2nd interface
Type of interface PROFINET
Physics
Page 1668 Ethernet RJ45
Mar 2008 Siemens ITS
Isolated Yes
Integrated switch Yes
Number of ports 2
Automatic detection of transmission speed Yes; 10/100 Mbit/s
Autonegotiation Yes
Autocrossing Yes
Media redundancy
•supported Yes
•Switchover time on line break, typically 200 ms; PROFINET MRP
•Number of stations in the ring, max. 50
Change of IP address at runtime, supported Yes
Functionality
•MPI No
•DP master No
•DP slave No
•PROFINET IO Controller Yes; Also simultaneously with IO-Device
functionality
•PROFINET IO Device Yes; Also simultaneously with IO
Controller functionality
•PROFINET CBA Yes
PROFINET IO Controller
•Services
Yes
• PG/OP
Page 1669 communication Mar 2008 Siemens ITS
Yes; with loadable FBs, max. configurable
• S7 communication connections: 16, max. number of instances:
32
Yes; OB 61; isochronous mode can only
• Isochronous mode be used alternatively on PROFIBUS DP or
PROFINET IO
Yes; Via TCP/IP, ISO on TCP, and UDP
• Open IE communication
•Transmission rate, max. 100 Mbit/s
•Number of connectable IO devices, max. 128
•Max. number of connectable IO devices for 128
RT
128
• of which in line, max.
•Number of IO devices with IRT and the 128
option "high flexibility"
61
• of which in line, max.
•Number of IO Devices with IRT and the 64
option "high performance", max.
64
• of which in line, max.
•IRT, supported Yes
•Shared
Page device,
1670 supported Yes
Mar 2008 Siemens ITS
•Prioritized startup supported Yes
32
• Number of IO Devices, max.
•Activation/deactivation of IO Devices Yes
8
• Number of IO Devices that can be
simultaneously activated/deactivated,
max.
•IO Devices changing during operation Yes
(partner ports), supported
8
• Max. number of IO devices per tool
•Device replacement without swap medium Yes
•Send cycles 250 μs, 500 μs,1 ms; 2 ms, 4 ms (not in
the case of IRT with "high flexibility"
option)
•Updating time 250 µs to 512 ms (depending on the
operating mode, see Manual "S7-300 CPU
31xC and CPU 31x, Technical Data" for
more details)
•Address area
8 Kibyte
• Inputs, max.
Page 1671 8 Kibyte
Mar 2008 Siemens ITS
• Outputs, max.
•User data per address area, max.
1 024 byte
• User data consistency, max.
PROFINET IO Device
•Services
Yes
• PG/OP communication
Yes; with loadable FBs, max. configurable
• S7 communication connections: 16, max. number of instances:
32
No
• Isochronous mode
Yes; Via TCP/IP, ISO on TCP, and UDP
• Open IE communication
Yes
• IRT, supported
Yes; With SFB 73 / 74 prepared for
• PROFIenergy, supported loadable PROFIenergy standard FB for I-
Device
Yes
• Shared device, supported
2
• Number
Page 1672 of IO controllers with Mar 2008 Siemens ITS
shared device, max.
•Transfer memory
1 440 byte; Per IO Controller with shared
• Inputs, max. device
1 440 byte; Per IO Controller with shared
• Outputs, max. device
•Submodules
64
• Number, max.
1 024 byte
• User data per submodule, max.
Open IE communication
•Open IE communication, supported Yes
•Number of connections, max. 16
•Local port numbers used at the system end 0, 20, 21, 25, 80, 102, 135, 161, 8080,
34962, 34963, 34964, 65532, 65533,
65534, 65535
•Keep-alive function, supported Yes
Communication functions
PG/OP communication Yes
Data record routing Yes
Global data communication
•supported Yes
•Number of GD loops, max.
Page 1673 8
Mar 2008 Siemens ITS
•Number of GD packets, max. 8
•Number of GD packets, transmitter, max. 8
•Number of GD packets, receiver, max. 8
•Size of GD packets, max. 22 byte
•Size of GD packet (of which consistent), 22 byte
max.
S7 basic communication
•supported Yes
•User data per job, max. 76 byte
•User data per job (of which consistent), 76 byte; 76 bytes (with X_SEND or
max. X_RCV); 64 bytes (with X_PUT or
X_GET as server)
S7 communication
•supported Yes
•as server Yes
•as client Yes; via integrated PROFINET interface and
loadable FB or via CP and loadable FB
•User data per job, max. See online help of STEP 7 (shared
parameters of the SFBs/FBs and of the
SFCs/FCs of S7 Communication)
S5-compatible communication
•supported Yes; via CP and loadable FC
Open IE communication
•TCP/IP
Page 1674 Yes;
Mar 2008 via integrated PROFINETSiemens
interface
ITS and
loadable FBs
16
• Number of connections, max.
1 460 byte
• Data length for connection type
01H, max.
32 768 byte
• Data length for connection type
11H, max.
Yes
• Several passive connections per port,
supported
•ISO-on-TCP (RFC1006) Yes; via integrated PROFINET interface and
loadable FBs
16
• Number of connections, max.
32 768 byte
• Data length, max.
•UDP Yes; via integrated PROFINET interface and
loadable FBs
16
• Number of connections, max.
1 472 byte
• Data
Page 1675 length, max. Mar 2008 Siemens ITS
Web server
•supported Yes
•Number of HTTP clients 5
•User-defined websites Yes
PROFINET CBA (at set setpoint
communication load)
•Setpoint for the CPU communication load 50 %
•Number of remote interconnection partners 32
•Number of functions, master/slave 30
•Total of all Master/Slave connections 1 000
•Data length of all incoming connections 4 000 byte
master/slave, max.
•Data length of all outgoing connections 4 000 byte
master/slave, max.
•Number of device-internal and PROFIBUS 500
interconnections
•Data length of device-internal und 4 000 byte
PROFIBUS interconnections, max.
•Data length per connection, max. 1 400 byte
•Remote interconnections with acyclic
transmission
500 ms
• Sampling frequency: Sampling time,
Pagemin.
1676 Mar 2008 Siemens ITS
100
• Number of incoming
interconnections
100
• Number of outgoing interconnections
2 000 byte
• Data length of all incoming
interconnections, max.
2 000 byte
• Data length of all outgoing
interconnections, max.
1 400 byte
• Data length per connection, max.
•Remote interconnections with cyclic
transmission
10 ms
• Transmission frequency:
Transmission interval, min.
200
• Number of incoming
interconnections
200
• Number of outgoing interconnections
Page 1677 2 000
Mar 2008 byte Siemens ITS
• Data length of all incoming
interconnections, max.
2 000 byte
• Data length of all outgoing
interconnections, max.
450 byte
• Data length per connection, max.
•HMI variables via PROFINET (acyclic)
3; 2x PN OPC/1x iMap
• Number of stations that can log on
for HMI variables (PN OPC/iMap)
500 ms
• HMI variable updating
200
• Number of HMI variables
2 000 byte
• Data length of all HMI variables,
max.
•PROFIBUS proxy functionality
Yes
• supported
16
• Number of linked PROFIBUS
Pagedevices
1678 Mar 2008 Siemens ITS
240 byte; Slave-dependent
• Data length per connection, max.
Number of connections
•Max. total number of instances 32
•usable for routing X1 as MPI: max. 10; X1 as DP master:
max. 24; X1 as DP slave (active): max.
14; X2 as PROFINET: 24 max.
S7 message functions
Number of login stations for message 32; Depending on the configured
functions, max. connections for PG/OP and S7 basic
communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 300
Test commissioning functions
Status/control
•Status/control variable Yes
•Variables Inputs, outputs, memory bits, DB, times,
counters
•Number of variables, max. 30
•of which status variables, max. 30
•of which control variables, max. 14
Forcing
•Forcing Yes
•Force,
Pagevariables
1679 Inputs, outputs
Mar 2008 Siemens ITS
•Number of variables, max. 10
Status block Yes; Up to 2 simultaneously
Single step Yes
Number of breakpoints 4
Diagnostic buffer
•present Yes
•Number of entries, max. 500
No
• adjustable
100; Only the last 100 entries are retained
• Of which powerfail-proof
•Number of entries readable in RUN, max. 499
Yes; From 10 to 499
• adjustable
10
• preset
Isochronous mode
Isochronous mode Yes; Via PROFIBUS DP or PROFINET
interface
Ambient conditions
Operating temperature
•Min. 0 °C
•max. 60 °C
Configuration
Page 1680 Mar 2008 Siemens ITS
programming
•Programming language
Yes
• LAD
Yes
• FBD
Yes
• STL
Yes
• SCL
Yes
• CFC
Yes
• GRAPH
Yes
• HiGraph®
•Command set see instruction list
•Nesting levels 8
Know-how protection
•User program protection/password Yes
protection
•Block encryption Yes; With S7 block Privacy
Dimensions
Width
Page 1681 40 mm
Mar 2008 Siemens ITS