Protection Presentation
Protection Presentation
ELECTRICAL PROTECTION
ELECTRICAL
SYSTEMS PROTECTION SYSTEM
Made By: Mourad Mohammed
INTRODUCTION
Acting Measuring
Analyzing
FUNDAMENTAL COMPONENTS OF PROTECTION
SYSTEM
• Current Transformer (CT).
• Voltage Transformer (VT).
• Protection relay.
• Circuit Breaker.
CURRENT TRANSFORMER
Transforming High current (200, 800, 1000, 1000A) to low current (1, 5A)
𝑰 𝑷 𝑵𝑺
=
𝑰𝑺 𝑵𝑷 Secondary Primary
Winding Conductor
𝑵𝑷 𝟏
𝑰𝑺 = 𝑰𝑷 ∗ = 𝟖𝟎𝟎 ∗
𝑵𝑺 𝟖𝟎𝟎
Iron Core
𝑰𝑺 = 1 A
CURRENT TRANSFORMER
IEC61869 Standard
CURRENT TRANSFORMER CLASSES
• PX Class:
• Special Order CT with high accuracy 0.25% acceptance error, the customer should provide
the supplier with the below information:
• Turns ratio
• Minimum kneepoint voltage
• Maximum secondary resistance
• Maximum excitation current at the rated minimum kneepoint voltage
CURRENT TRANSFORMER PROTECTION ZONES
Transformer
Generator Transmission
CTCTTransformer CT Line CT Transmission
Bus Bar CT Bus BarLine
CT CT
CURRENT TRANSFORMER PROTECTION ZONES
Transforming High Voltage (11, 132, 220, 400 KV) to Low Voltage (110, 100 V)
𝑉𝑆 𝑵𝑺
=
𝑉𝑃 𝑵𝑷
𝑵𝑆
𝑉𝑺 = 𝑉𝑷 ∗ = 110 V
𝑵𝑃
VOLTAGE TRANSFORMER
IEC61869 Standard
CIRCUIT BREAKER
• Closing Coil
• Tripping Coil (For MV, HV CBs have
2 Trip Coil)
• Spring for Close and Open
• Spring Charging Motor.
• Main Contacts.
• Auxiliary Contacts.
PROTECTION RELAY
• Protection purpose
• Detect electrical faults and disturbances
• Protect people and property
• Protection requirements
• Sensitive
• Fast
• Selective
• Reliable
• Stability
PROTECTION RELAY
• Blackout
• September 4, 2014 - Egypt - A major blackout struck Cairo and other cities.
• July 30 and 31, 2012 – India - Two severe power outages affected most
of northern and eastern India.
• List of major power outages - Wikipedia
PROTECTION RELAY
PROTECTION RELAY
• Digital Protection Relays have many protection functions included in one protection
relays like (OC, EF, OV, UV, BF, ….etc.).
• The More Importance,The More Protection.
PROTECTION RELAY
PROTECTION PANEL COMPONENTS
• Protection Relay
• Test Block
• Lockout Relay
• Trip Circuit Supervision
TYPES OF FAULT
TYPES OF FAULT
• Protection against excess current was naturally the earliest protection system to evolve
OVERCURRENT PROTECTION FUNCTION
• Measured
• Calculated
DIRECTIONAL EARTH FAULT PROTECTION
FUNCTION
UNDER & OVER VOLTAGE PROTECTION FUNCTION
• Distance Protection
DIFFERENTIAL PROTECTION
• Basically any differential protection he just compare the entry current with the exit
current.
• Idaly the differential should be zero during normal operation even during external fault
but actually that is not true due do many reasons: 2187
= 0.87
3849
= 0.96
2500 4000
1. CT Error at both end
2. Current Losses inside the equipment:
1. Magnetizing current inside the Transformers
2. Charging current inside the cables.
3. CT Mismatching for Transformer both End
DIFFERENTIAL PROTECTION
• Differential Characteristic
• Low Impedance
• High Impedance
Central Unit
PU PU PU PU PU
BB PROTECTION
BB PROTECTION
• Breaker Fail
TRANSFORMER DIFFERENTIAL
• Backup Protection
1. Over Current or Directional Over Current
2. Earth Fault or Directional Earth Fault
3. Under Voltage
4. Over Voltage