16272
16272
SECTION 16272
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
designation identifies the office that will review the submittal for the
Government. The following shall be submitted in accordance with Section
01335 SUBMITTAL PROCEDURES:
Wiring Diagrams;
Nameplate;
Instruction Manuals;
1.3 DEFINITIONS
All test equipment shall be calibrated and traceable to the National Bureau
of Standards.
a. Ratio Test.
b. Polarity and Phase Relation Test.
c. No-Load Loss and Excitation Current Test.
d. Low Frequency Dielectric Tests which include:
The following design tests shall be performed only if test reports are not
available on duplicate or essentially duplicate transformers.
a. Full ANSI Lightning Impulse Test(including one full wave, two chopped
waves, and one reduced wave).
b. Temperature Test.
c. Audible Sound Level Test.
PART 2 PRODUCTS
2.1 MANUFACTURERS
Electrical Characteristics
a. 1000 kVA.
b. Three Phase.
c. Mineral Oil.
d. Temperature Rise 45/55 degree C Rise
e. Cooling: OA/FA.
f. Frequency: 50 hertz.
g. The winding conductor shall be the manufacturers standard electrical
grade conductor material: Copper.
h. The cooling air(ambient temperature) shall not exceed 50 degrees C and
the average cooling air shall not exceed 40 degrees C in any 24 hour
period.
i. 15000 High-voltage and BIL: 95.
j. High voltage windings shall be Delta connected.
k. Taps for De-energized Operation shall be 2-2.5% FCAN & 2-2.5% FCBN.
l. Impedance shall be 5.75% plus or minus ANSI standard tolerance of 7.5%.
m 380Y/220 Low-voltage and BIL: 30.
n. Low-voltage windings shall be Wye.
o. Designed for step-up operation.
Low voltage spade bushings shall be sidewall mounted and enclosed in a full
length air chamber as required for application.
PART 3 EXECUTION
3.1 INSTALLATION
3.2 ACCEPTANCE
-- End of Section --