Electrical Machine Lab-2
Electrical Machine Lab-2
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Lab Manual
Electrical Machines Lab
(BEEL506)
CODE OF CONDUCT FOR LABORATORY
All students must observe the Dress Code while in the laboratory.
Sandals or open-toed shoes are NOT allowed. Foods, drinks and smoking
are NOT allowed.
All bags must be left at the indicated place.
The lab timetable must be strictly followed.
Be PUNCTUAL for your laboratory session.
Experiment must be completed within the given time.
Noise must be kept to a minimum.
Workspace must be kept clean and tidy at all time.
Handle all apparatus with care.
All students are liable for any damage to equipment due to
their own negligence.
All equipment, apparatus, tools and components must be RETURNED to
their original place after use.
Students are strictly PROHIBITED from taking out any items from the
laboratory.
Students are NOT allowed to work alone in the laboratory without
the Lab Supervisor
Report immediately to the Lab Supervisor if any injury occurred.
Report immediately to the Lab Supervisor any damages to
equipment
You should be punctual for your laboratory session and should not
leave the lab without the permission of the teacher.
Each student is expected to have his/her own lab book where they will
take notes on the experiments as they are completed.
The lab books will be checked at the end of each lab session. Lab
notes are a primary source from which you will write your lab reports.
You and your batch mates will work closely on the experiments
together. One partner doing all the work will not be tolerated. All the
Batch mates should be able to explain the purpose of the experiment
and the underlying concepts.
Please report immediately to the member of staff or lab assistant
present in the laboratory; if any equipment is faulty.
ASSESMENT
LAB REPORTS
Note that, although students are encouraged to collaborate during lab, each
must individually prepare a report and submit.
They must be organized, neat and legible.
Your report should be complete, thorough, understandable and
literate.
You should include a well-drawn and labeled engineering schematic for each
circuit Investigated.
Your reports should follow the prescribed format, to give your report
structure and to make sure that you address all of the important points.
Graphics requiring-drawn straight lines should be done with a straight edge.
Well drawn freehand sketches are permissible for schematics.
Space must be provided in the flow of your discussion for any tables or
figures. Do not collect figures and drawings in a single appendix at the end of
the report.
Reports should be submitted within one week after completing a
scheduled lab session
REPORTS FORMAT
Aim: A concise statement describing the experiment and the results. This
is usually not more than 3 sentences. Since the abstract is a summary of
what you have done, it’s a good idea to write this last.
Apparatus: Describe what equipment and components you used to
conduct the experiment.
Theory: Several paragraphs that explain the motivation of the
experiment. Usually in this statement you state what you intent to
accomplish as well as the expected results of the experiment.
Procedure: Describe how you conducted the experiment
Results and Analysis: This is the main body of the report. Graphs, tables,
schematics, diagrams should all be included and explained. Results of any
calculations should be explained and shown. State the results of the
experiment. Include any problems encountered.
Conclusion: Explain how the experiment went, and whether you were
able to achieve the expected results stated in the introduction
SAFETY PRECAUTIONS
(Artificial Respiration)
Place him/her on back. Clear his mouth and throat. Turn his/her head to
side and remove any foreign bodies with fingers.
Tilt his/her head back by holding lower jaw –this gives a clear air passage
way to his/her lungs and keep tongue out of throat.
You take deep breath of fresh air. Place mouth over his/her nose. Hold
mouth closed. Blow into nose. Adults-blow fully, children-puff gently.
Watch chest rise. Remove mouth–let chest fall. Continue until patient
resumes breathing.
Note: If chest does not rise when you blow check for obstruction in
his/her throat.
Listen to the air being exhaled. When flow of air stops blow it again
OBJECTIVE
VISION
To Educate and Prepare World Class Engineers for Global and Social
Technological Demands
MISSION
To strive for excellence in teaching and research and to promote academic
growth by offering state-of-the-art undergraduate, postgraduate and doctoral
programmes
To generate new knowledge by engaging in cutting-edge research for overall
development of students and society
To identify areas of specialization based on an informed perception of regional,
national and global needs
To undertake collaborative projects which offer opportunities for long-term
interaction with academia and industry
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
1 To Conduct No Load & Blocked Rotor Test on 3-Ph Sq. Cage Induction
Motor and plot performance curve
2 To Conduct Load Test on 3-Ph Sq. Cage Induction Motor and plot
performance curve
4 To Conduct Load Test on 3-Ph Slip Ring Induction Motor and plot
performance curve
6 To Find out OCC and SCC of an Alternator and its regulation using
synchronous impedance method.
7
To find regulation of Alternator using ZPF Method.
9 Synchronization of Alternators
11
12
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Experimental Panel:
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
To Conduct No Load & Blocked Rotor Test on 3 Ph Sq. Cage Induction Motor and plot
performance curve
2. INSTRUMENTS
3. THEORY
No load Test:
To obtain no load current and its power factor angle No load test is performed at rated voltage and
frequency. Let say Vo Io are the Voltage and current and φo is the PF angle at no load condition
The power consumed at no load is equal to the iron losses or the open circuit losses of the motor
So
4. CIRCUIT DIAGRAM
5. PROCEDURE
No Load Test
1) Connect the circuit as per circuit diagram
2) Ensure that motor is unloaded and variac is at zero position.
3) Switch on 3 Phase Supply through MCB , Push the start switch on panel (Green Push button)
4) Now start the motor with gradually increasing the voltage until it reaches Rated Voltage.
5) This is motor running at no load condition. Take down the readings of all the meters
multifunction meter power and PF and speed
6) Record the readings of meters
7) Switch off from the push switch RED and MCB
Blocked Rotor Test
1) Connect the circuit as per circuit diagram
2) Ensure that variac is at zero position.
3) Tighten the belt around motor pulley such that it is jammed
4) Switch on 3 Phase Supply through MCB , Push the start switch on panel (Green Push button)
5) Now gradually increasing the voltage and keeping an eye on current and stop until it reaches
Rated Current.
6) Take down the readings of all the meters multifunction meter power and PF and speed
7) Take down the voltage down to zero relase the tension in belt pulley
8) Switch off from the push switch RED and MCB
6. OBSERVATION
7. PERFORMANCE CURVES
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
To Conduct Load Test on 3 Ph Sq. Cage Induction Motor and plot performance curve
2. INSTRUMENTS
3. THEORY
The load test on induction motor is performed to compute its completer performance ie. Torque
slip efficiency power factor etc. During this test, the motor is operated at rated voltage and
frequency and normally loaded mechanically by brake and pulley arrangement from the observed
data the performance can be calculated following the steps given below
SLIP: The speed of motor drops slightly at application of load and can be calculated as
Where Ns is the synchronous speed and Nr is the running speed normally the slip is 2 to 5 %
TORQUE: The net force applied on the motor shaft by tightening the belt of brake drum, this net
force can be obtained by reading S1 and S2 of spring balances ie.
Net Force Exerted W= S1-S2 kg
Torque = W X r X 9.8 N-M
Where r is radius of pulley = 150mm = 0.15m
OUTPUT POWER: The output power in watts developed by the motor is given by
Output Power Watts
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. OBSERVATION
7. PERFORMANCE CURVES
Plot the following performance curves
1) Efficiency Vs Output Power
2) Torque Vs Output Power
3) Line Current Vs Output Power
4) PF Vs Output Power
5) Slip Vs Output Power
6) Torque vs speed
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
To Conduct No Load & Blocked Rotor Test on 3 Ph Slip Ring Induction Motor and plot
performance curve
2. INSTRUMENTS
3. THEORY
No load Test:
To obtain no load current and its power factor angle No load test is performed at rated voltage and
frequency. Let say Vo Io are the Voltage and current and φo is the PF angle at no load condition
The power consumed at no load is equal to the iron losses or the open circuit losses of the motor
Block Rotor Test:
To obtain short circuit current and its power factor blocked rotor test is performed where the shaft
of rotor is blocked to move by tightening of drum brake belt and motor is excited at a very reduced
voltage until rated current is reached the power consumed is directly equal to short circuit loss
(copper loss) of the motor
The readings of meters show Isc, Vsc and φsc here the short circuit current Isc is the current
corresponding reduced voltage Vsc but for rated voltage the short circuit current would be I’sc
So
4. CIRCUIT DIAGRAM
5. PROCEDURE
No Load Test
1) Connect the circuit as per circuit diagram
2) Short the rotor of slip ring motor
3) Ensure that motor is unloaded and variac is at zero position.
4) Switch on 3 Phase Supply through MCB, Push the start switch on panel (Green Push button)
5) Now start the motor with gradually increasing the voltage until it reaches Rated Voltage.
6) This is motor running at no load condition. Take down the readings of all the meters
multifunction meter power and PF and speed
7) Record the readings of meters
8) Switch off from the push switch RED and MCB
6. OBSERVATION
7. PERFORMANCE CURVES
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
To Conduct Load Test on 3 Ph Slip Ring Induction Motor and plot performance curve
2. INSTRUMENTS
3. THEORY
The load test on induction motor is performed to compute its completer performance ie. Torque
slip efficiency power factor etc. During this test, the motor is operated at rated voltage and
frequency and normally loaded mechanically by brake and pulley arrangement from the observed
data the performance can be calculated following the steps given below
SLIP: The speed of motor drops slightly at application of load and can be calculated as
Where Ns is the synchronous speed and Nr is the running speed normally the slip is 2 to 5 %
TORQUE: The net force applied on the motor shaft by tightening the belt of brake drum , this net
force can be obtained by reading S1 and S2 of spring balances ie.
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. OBSERVATION
7. PERFORMANCE CURVES
Plot the following performance curves
1) Efficiency Vs Output Power
2) Torque Vs Output Power
3) Line Current Vs Output Power
4) PF Vs Output Power
5) Slip Vs Output Power
6) Torque Vs speed
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Experimental Panel:
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
To Study the cascaded connection of Two 3 Phase Slip Ring induction motor
2. INSTRUMENTS
3. THEORY
A 3 Phase motor is a constant speed motor however the speed of induction motor can be controlled
by cascading of two induction motors at least one of which is induction motor other may be slip
ring or induction motor, the two induction motors are mechanically coupled and electrically
connected in cascade. In cascading the stator of the main motor is connected to supply mains and
its rotor output (slip power) at a slip frequency f2 (f2=sf1) is fed to the stator of second motor.
Hence the slip power of main motor is effectively utilized and fed to the auxiliary motor which
converts it to mechanical power and then adds to main motor output
Let the number of poles in Main motor P1 and no. of poles in aux. motor P2 then the synchronous
Or =
If the auxiliary motor develops torque in direction opposite to developed by main motor this
scheme is termed as differentially cascaded
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. OBSERVATION
7. RESULTS
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Experimental Panel:
1.
2.
3.
4.
5.
1. Objective
To Find out OCC and SCC of an Alternator and its regulation using synchronous impedance
method.
2. Apparatus Required
3. Theory
Below figure shows the Phasor diagram of the alternator, supplying full load current of I. ampere,
lagging the terminal voltage V by-an angle φ. The open circuit voltage E of the alternator is given
by,
The diagram has been drawn with the current as the reference Phasor and is self-explanatory. The
open circuit voltage as finally obtained from the Phasor diagram, corresponding to this loading
condition is E volts. Then the regulation of the alternator under the above loading condition- is
given by
Regulation = (E-V)/V x 100 percent
An approximate expression for the open circuit voltage can be established referring to the Phasor
diagram.
The above expression is for lagging power factor load. In case alternator is operating at leading
power factor open circuit voltage E can be found out in a similar way and is given by
The value of regulation obtained by this method is higher than obtained from as actual load test as
such it is called the pessimistic method.
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. Observation
7. Calculation
Regulation = (E-V)/V x 100 percent
8. Result
The graphs obtained between Open circuit Voltage and Field Current are OCC of the alternator
and between Short circuit Current and Field Current are SCC of the alternator
Co-workers:
1.
2.
3.
4.
5.
1. Objective:
2. Apparatus Required
3. Theory
This Zero power factor (ZPF) method is used to determine the voltage regulation of
synchronous generator or alternator. This method is also called Potier method. In the operation
of any alternator, the armature resistance drop IRa and armature leakage reactance drop IXL are
actually emf quantities while the armature reaction is basically MMF quantity. In the synchronous
Impedance, all the quantities are treated as EMF quantities as against this in MMF method all are
treated as MMF quantities.
Key Point: This zpf method is based on the separation of armature leakage reactance and
armature reaction effects. The armature leakage reactance XL is called Potier reactance in this
method; hence ZPF method is also called Potier reactance method.
To determine armature leakage reactance and armature reaction MMF separately two tests are
performed on the alternator. The two tests are
The machine speed is maintained constant at its synchronous value. The load current delivered by
an alternator to purely inductive load is maintained constant at its rated full load value by varying
excitation and by adjusting variable inductance of the inductive bad. Note that, due to purely
inductive load, an alternator will always operate at zero power factor lagging.
Key Point: In this test, there is no need to obtain number of points to obtain the curve. Only two
points are enough to construct a curve called zero power factor saturation curves.
The below is the graph of terminal voltage against excitation when delivering full load zero power
factor current. One point for this curve is zero terminal voltage (short circuit condition) and the
field current required delivering full load short circuit armature current. While other point field
current required to obtain rated terminal voltage while delivering rated full load armature current.
With the help of these two points, the zero power factor saturation curve can be obtained as
1. Plot open circuit characteristics on a graph paper as shown in the below figure.
2. Plot the excitation corresponding to zero terminal voltage i.e. short circuit full zero power
factor armature current. This point is shown as A in the below figure which the x-axis. Another
point is the rated voltage when the alternator is delivering full current at zero p.f. lagging. This
point is P as shown in the below figure.
3. Draw the tangent to O.C.C. through origin which is line OB as shown dotted in below figure.
This is called airline.
5. From point Q draw the line parallel to the airline which intersects O.C.C. at point R. Join RQ
and join PR. The triangle PQR is called Potier triangle.
7. The zero power factor full load saturation curve is now be constructed by moving triangle PQR
so that R remains always on OCC and line PQ always remains horizontal. The dotted triangle is
shown in the above figure. It must be noted that the Potier triangle once obtained is constant for a
given armature current and hence can be transferred as it is.
8. Though point A, draw a line parallel to PR meeting OCC at point B. From B, draw a
perpendicular on OA to meet it at point C. Triangles OAB and PQR are similar triangles.
9. The perpendicular RS gives the voltage drop due to the armature leakage reactance i.e. IXL
10. The length PS gives field current necessary to overcome the demagnetizing effect of armature
reaction at full load.
11. The length SQ represents field current required to induce an EMF for balancing leakage
reactance drop RS. These values can be obtained from any Potier triangle such as OAB, PQR and
so on.
1. Draw the rated terminal voltage Vph as a reference phasor. Depending upon at which power
factor (cos Φ) the regulation is to be predicted, draw the Current phasor Iph lagging or leading
Vph by angle Φ.
2. Draw Iph Raph voltage drop to Vph which is in phase with Iph. While the voltage drop
Iph XLph is to be drawn perpendicular to Iph Raph, vector but leading Iph Raph at the extremity
of Vph.
3. The Rph is to be measured separately by passing a d.c current and measuring the voltage across
armature winding. While XLph is Potier reactance obtained by Potier method.
Phasor sum of Vph rated, Iph Raph and Iph XLph gives the e.m.f. which is saying E1ph.
E1ph = Vph +Iph Raph +Iph XLph
4. Obtain the excitation corresponding to E1ph from OCC which is drawn. Let this excitation be
Ff1.This is excitation required for inducing EMF which does not consider the effect of armature
reaction.
5. The field current required to balance armature reaction can be obtained from Potier triangle
method, which is say FAR.
FAR = I (PS) = I (AC) .....
6. The total excitation required is the vector sum of the Ff1 and FAR. This can be obtained exactly
similar to the procedure used in MMF method.
7. Draw vector Ff1 to some scale, leading E1ph by 90°. Add FAR to Ff1 by drawing vector
FAR in phase opposition to Iph. The total excitation to be supplied by field is given by FR.
Once the total excitation is known which is FR, the corresponding induced emf Eph can be
obtained from OCC. This Eph lags FR by 90°.The length CD drops due to the armature reaction.
Drawing perpendicular from A and B on current Phasor meeting at points G and H respectively,
we get triangle OHC as right angle triangle. Hence Eph can be determined, analytically also. Once
Eph is known, the regulation of an alternator can be predicted as,
ZPF method takes into consideration the armature resistance and leakage reactance voltage drops
as EMF quantities and the effect of armature reaction as MMF quantity. This is the reality hence
the results obtained by this method are nearer to the reality those obtained by synchronous
impedance method and method. The only drawback of ZPF method is that the separate curve for
every load condition is necessary to plot if Potier triangles for various load conditions are
required.
1. ln the entire calculation procedure of Potier method, the armature resistance is neglected. But
practically armature resistance is very small and hence this assumption does not cause significant
error in the accuracy.
2. In Potier method, a zero power factor test is required to be done. But practically when
inductors are used, a perfect zero power factor cannot be achieved.
3. Consider the graphical interpretation of Potier method shown in the below figure.
In this graph, the distances RS, R' S' and BC are assumed equal. This represents the voltage drop
across the leakage reactance which is (Iaph) FL * XLph. This indicates that the point P in the zero
power factor method and point A in the short circuit test represent same leakage reactance of the
machine. But this is not true as the excitation under short circuit condition is OA while that for
point P is OA as shown.
Now the excitation OA' is much higher than OC and hence point P corresponding to saturated
conditions represents larger leakage flux which in the method assumed unchanged. Hence
practically the leakage reactance corresponding to saturated conditions is higher than that assumed
in the method. This introduces the error in the calculations.
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. Observation
7. Calculation
8. Result
The graphs obtained between Open circuit Voltage and Field Current are OCC of the alternator
and between Short circuit Current and Field Current are SCC of the alternator
2. INSTRUMENTS:
3. THEORY:
With constant mechanical load on the synchronous motor the variation of field current changes the
armature current drawn by the motor changes and so the power factor. As such behavior of
synchronous motor is described in three different operating modes of field excitation
Normal Excitation
The armature current is Minimum at particular value of field current which is called the normal
field excitation. The operating power factor is unity at this excitation and thus the motor is
equivalent to resistive type of load
Under Excitation
When the field current is decreased gradually below the normal excitation the armature current
increases and the operating power factor is decreased. The power factor under this condition is
lagging. Thus the current drawn by the motor is lagging current and behave as inductive load
Over Excitation
When the field current is increased gradually above the normal excitation the armature current
again increases and the operating power factor decreases. However, the power factor now is
leading in nature and synchronous motor draws a leading current, and behaves as capacitive load
If the above variation in armature and field currents are plotted a curve of shape of V is obtained
such a characteristics of Synchronous motor is called V curves of synchronous motor
For an increased constant load on the motor the V curves shifts upwards
4. CIRCUIT DIAGRAM
5. PROCEDURE
6. OBSERVATION
S.NO. If Ia PF W
7. RESULTS
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
Experimental Panel
Synchronization of Alternators
2) THEORY:
A large generating station normally consists of several AC generators to supply the total load on
the station. During the light hours only few generators can supply the demand . When the load on
stations increases generators are connected in parallel to the existing running generator in order to
cope up with supply and demand.
Before an incoming Alternator to be synchronized with other alternators on the same bus
bar the following conditions should be fulfilled
1. the voltage generated by the incoming alternator is equal to the bus bar voltage. It is
advisable to check the condition using same voltmeter for measuring both voltages
2. the phase sequence of the generated voltage of incoming alternator is the same as that
of bus bar
3. the frequency of the generated voltage of the incoming alternator is the same as that
of bus bar frequency
Condition one can be satisfied by equalizing the two voltages which are indicated by the voltmeter.
Other conditions of synchronization are indicated by a synchroscope and by lamp method. Before
using any one of the above methods to ascertain conditions (ii) and (iii) the speed of the incoming
alternator is adjusted to its rated value by varying the field current of the DC motor, which is the
prime mover for this alternator.
Synchroscope is the device by means of which we can correctly detect the frequency or the speed
of the incoming alternator with respect to the bus bar. The device is fed by the generated phase
voltage of one alternator on one side and other input by incoming alternator. It is clearly indicated
by the pointer that whether the incoming alternator is running fast or slow. As per the indication
obtained by this device the speed of incoming generator can be increased or decreased as the case
to equalize the frequency of the outputs from both the alternators.
To indicate the correct equalization of the phase sequence and frequency of both alternators, dark
lamp or bright lamp synchronization is used
In Bright lamp method, one set of lamps are connected directly across the similar phases of the
incoming alternator and the bus bar where as other two sets of lamps are cross connected between
the phases of incoming alternators and the bus bar, so that at the instant of synchronizing one set of
lamps which directly connected would be dark, while the other two sets lamps should be equally
bright. In thus method of the synchronizing if the frequencies of the alternators and bus bar are not
equalized the lamps will flicker, the alterations in lamps being rapid when there is large difference
in frequency and for slow when the difference in frequencies is smaller nearly equal.
The speed of both the alternators is so adjusted that set of lamps go in out very slowly. This
method clearly indicates the phase sequence also that of voltages of both the alternators
3) CIRCUIT DIAGRAM:
4) PROCEDURE:
Experimental Panel
When the alternator is short-circuited, the currents in all the three-phases rise rapidly to a high
value of about 10 to 18 times of full load current, during the first quarter cycle. The flux crossing
the air gap is large during a first couple of cycles. The reactance during these first two or three
cycle is least and the short circuit current is high. This reactance is called subtransient reactance
and is denoted by X”. The first few cycles come under sub-transient state.
After a first few cycles, the decrement in the r.m.s. value of short circuit current is less rapid than
the decrements during the first few cycles. This state is called the Transient State and the reactance
in this state is called transient reactance X’. The circuit breaker contacts separate in the transient
state.
Finally, the transient dies out and the current reaches a steady sinusoidal state called the Steady
State. The reactance in this state is called steady state reactance Xd. Since the short circuit current
of the alternator lags behind the voltage by 90 degrees, the reactance involved are direct axis
reactance.
As clear from the figure above, the d.c. components in the three phases are different; hence the
waveforms of the three phases are not identical. If voltage of phase, say, Y, is maximum at the
instant of short circuit, the DC component of short circuit current is zero. Hence the waveform is
symmetrical as shown in figure below.
If a circuit-breaker closes on existing fault, the current would increase to a high value during the
first, half cycle. The highest peak value of the current is reached
Madhav Institute of Technology & Science Gwalior-474005
(A Govt. Aided UGC and NAAC Accredited Institute Affiliated to R.G.P.V Bhopal, M.P)
2) INSTRUMENTS
3) THEORY
The armature reactance varies from Xq to Xd periodically.
Xd - is the synchronous reactance of armature coil offered to the flow of direct axis current.
Xq - is the synchronous reactance of armature coil offered to the flow of quadrature axis current
When voltage induced in the field winding is zero, armature current is minimum and the terminal
voltage is maximum. At this instant direct axis coincides with armature mmf and corresponding
reactance is Xd is given by
Similarly, when the voltage induced in the field winding is maximum (positive or negative)
armature current is maximum and terminal voltage is minimum. At this instant quadrature axis
coincides with armature mmf and corresponding reactance is Xq is given by
If the readings of maximum and minimum armature current and voltage are taken Xd and Xq can
be determined. The readings cannot be taken at higher armature current to avoid synchronization.
The ratio of Xq / Xd for the cylindrical rotor machine is around 0.95 this generally taken as one
and for salient pole m/c this ratio is 0.66 to 0.7.
4) CIRCUIT DIAGRAM
5) PROCEDURE
(1) Connect the circuit as shown. Set the variac output zero.
(2) Put on the DC supply and run the DC motor of a speed close to the synchronous speed of
alternator but less than synchronous speed.
(3) Put on the ac supply and increase the variac output to suitable value, observe the variations in
the voltmeter and ammeter readings.
(4) Adjust the speed of complete dc motor further to get maximum swings in ammeter and
voltmeter pointers.
(5) Note maximum and minimum readings of voltage and current.
6) OBSERVATION
SPEED: ……………….
2) INSTRUMENTS
3) THEORY
Positive Sequence Impedance: It is the ratio of the fundamental component of armature voltage,
due to the fundamental positive sequence component of armature current, to this component of
armature current at rated frequency. This is the usually sub transient reactance Xd” and Xq”) of
alternator.
Direct Axis sub transient reactance can be determined by applied voltage method in which a single
phase voltage is applied across 2 terminals of star connected wiring and one is kept open.
The test is repeated for all the three combinations first voltage is applied to A and B C is kept
open. Then B& C are applied voltage and A is kept open . then C & A are used and B is kept open.
Here we get three sets of readings A’, B’, C’.
And
5) PROCEDURE
(1) Connect the circuit as shown. Set the variac output zero.
(2) This experiment is to be taken at stand still position so do not start the DC Motor
(3) Now take any two pair of alternator coils as shown in theory and let the third coil hung
freely and field coil of alternator shorted give AC Voltage slowly through variac until rated
current flows through the coils
(4) Measure the voltage and current for this set
(5) Repeat above procedure with next set of coils and then next set
(6) So we will be having current and voltage for three sets R-Y, Y-B and B-R
6) OBSERVATION
And