Chiller - Modbus Address Table
Chiller - Modbus Address Table
2)
5. Communication Protocol
★(2) All data that the BMS communicates to the touch screen of the unit should be verified if they are among the effective range.
★(3) “Modbus Address” of the control panel ranges from 1 to 255 and is the communication address for the unit. No matter for
data monitoring or unit control, it should be set. The default setting is 1. Note: it can not be set repeatedly under the same
network.
31
Modbus Long-distance Monitoring Protocol (V2.2)
★(4) If there is no data change from the master unit, it will make read-only operation to the display screen of unit, only if there is a
data change, the write operation can be executed, the write operation cannot be operated repeatedly by timer if it already ran successfully.
The data for the Modbus communication protocol can be divided into two types: register and switching value. The former one indicates the
values of temperature, valves and other continuous, multi-mode values, while the later one indicates the value which only has two status, like
the temperature sensor failure (with only two options: “Yes” or “No”).
Notices:
1)“R”indicates only read is allowed; “R/W” indicates both read and write are allowed.
32
Modbus Long-distance Monitoring Protocol (V2.2)
0x200D (fixed),
High-efficiency air-
cooled
screw chiller
0x2015 (fixed),
Low- temperature
leaving water
high-efficiency
Word air-cooled
R 0 65535 0x200D Transfer Value= 1 / Uint16 √ √ √ √
0 Unit ID
screw chiller Actual Value
0x2018(fixed),
Low- temperature
for heat
high-efficiency
33
Modbus Long-distance Monitoring Protocol (V2.2)
air-cooled
screw chiller
Communication
Transfer Value=
Word protocol version
R 1.0 65535 / Actual Value×10 0.1 / Uint16 √ √ √ √
1
Word W/
/ / 0x0055 Transfer Value= 1 / Uint16 √ √ √ √
2 R On/Off 0x00AA:On
Actual Value
0x0055:Off
Word R/
/ / 0x0001 Transfer Value= 1 / Uint16 √ √ √ √
3 W Running Mode 0x0001:Cool
Actual Value
0x0003:Heat
Entering water
Transfer Value=
Word R/ temperature setpoint
/ 12 Actual Value×10 0.1 ℃ Uint16 √ √ √ √
5 W for cooling Low-
Low- temper
temperat ature
ure leaving
leaving water
water high-effi
34
Modbus Long-distance Monitoring Protocol (V2.2)
high-effici ciency:
ency: 20
minimum When
leaving the
water functio
temperat n of low
ure + 5 water
When the temper
function ature
of low for
water cooling
temperat is
ure for activat
cooling is ed:25
activated When
:8 the
When the functio
function n of low
of low water
water temper
temperat ature
ure for for
cooling is cooling
deactivat is
ed:10 deactiv
ated:20
Entering water
Transfer Value=
Word R/ temperature setpoint
35 45 / 40 Actual Value×10 0.1 ℃ Uint16 √ √ √ √
6 W for heating
Low- Low-
Leaving water temperat temper Transfer Value=
Word R/ temperature setpoint
/ 7 Actual Value×10 0.1 ℃ Uint16 √ √ √ √
7 W for cooling ature
35
Modbus Long-distance Monitoring Protocol (V2.2)
ure leaving
leaving water
water high-effi
high-effici ciency:
ency: 15
minimum When
leaving the
water functio
temperat n of low
ure water
When the temper
function ature
of low for
water cooling
temperat is
ure for activat
cooling is e:20
activated When
:3 the
When the functio
function n of low
of low water
water temper
temperat ature
ure for for
cooling is cooling
deactivat is
ed:5 deactiv
ated:15
Entering water
Transfer Value=
Word R/ temperature setpoint
40 50 / 45 Actual Value×10 0.1 ℃ Uint16 √ √ √ √
8 W for heating
R/ 0x0084.
Unlock password input
W When passwords
for frequent protection
Word are
(high-order) / / / Transfer Value= 1 / Uint16 √ √ √ √
9 111111(111111=0x0
Actual Value
36
Modbus Long-distance Monitoring Protocol (V2.2)
001
B207), it is
0x0001(0x0FF0)
R/ When passwords
W are
Unlock password input 111111
for frequent protection (111111=0x0001B20
Word
(low-order) / / 7), / Transfer Value= 1 / Uint16 √ √ √ √
10 it is 0xB207 (0x0FF0) Actual Value
Word R
/ / / / / / / /
11~15 Reserved
Word R
/ / / / / / / /
16 Reserved
Word
R / / / / / / / /
17 Reserved
Word R
/ / / / / / / /
18 Reserved
Word R
/ / / / / / / /
19 Reserved
Word R
/ / / / / / / /
20 Reserved
Word R
/ / / / / / / /
21~36 Reserved
Word R
/ / / / / / / /
37 Reserved
Word R
/ / / / / / / /
38 Reserved
R Serial numbers for Transfer Value=
Word dynamic passwords Actual Value×10
/ / / 0 0.1 % Uint16 √ √ √ √
39 (high-order)
37
Modbus Long-distance Monitoring Protocol (V2.2)
R
For the version 1.0,
the
Display panel program Transfer Value=
Word transmitted value =
version / / 10 Actual Value×10 0.1 Pa Uint16 √ √ √ √
42 10
0x000A
Word R
/ / / / / / / /
43~45 Reserved
Word R 0x0000:Off, 0x0001:
46 Cool,
Word 0x0003:Heat,
106 0x0004:Antifreeze,
Word 0x0008:Defrost
/ / 0 Transfer Value= 1 / Uint16 √ √ √ √
166 System status
Actual Value
Word
226
Word R
47
Word
Air conditioning leaving Transfer Value=
107 water temperature Actual Value×10
-30 70 / / 0.1 ℃ Uint16 √ √ √ √
Word
167
Word
227
Word R
48
Word Transfer Value=
Air conditioning
108 -30 70 / / Actual Value×10 0.1 ℃ Uint16 √ √ √ √
entering
Word
water temperature
168
Word
38
Modbus Long-distance Monitoring Protocol (V2.2)
228
Word R
49 Air conditioning water
Word antifreeze Transfer Value=
109 (anti-overheating Actual Value×10
-30 70 / 0 0.1 ℃ / √ √ √ √
Word temperature)
169
Word
229
Word R
50
Word Transfer Value=
110 Defrosting temperature
-30 70 / 0 Actual Value×10 0.1 ℃ / √ √ √ √
Word
170
Word
230
Word R
51
Word
Discharge ambient Transfer Value=
111 temperature Actual Value×10
-30 70 / 0 0.1 ℃ / √ √ √ √
Word
171
Word
231
Word R
52
Word
Transfer Value=
112 Discharge temperature
0 150 / 0 Actual Value×10 0.1 ℃ / √ √ √ √
Word
172
Word
232
Word R
53
Word / / / / / / / /
Reserved
113
Word
39
Modbus Long-distance Monitoring Protocol (V2.2)
173
Word
233
Word R
54
Word
114
/ / / / / / / /
Word Reserved
174
Word
234
Word R
55
Word
115
/ / / / / / / /
Word Reserved
175
Word
235
Word R
56
Word
Entering heat recovery Transfer Value=
116 water temperature Actual Value×10
-30 70 / 0 0.1 ℃ Uint16 √ √ √ √
Word
176
Word
236
Word R
57
Word
Heat recovery water
117 tank temperature 0 150 / 0 Transfer Value= 1 ℃ Uint16 √ √ √ √
Word
Actual Value
177
Word
237
Word R
Transfer Value=
58 Suction temperature
-30 70 / 0 Actual Value×10 0.1 ℃ Uint16 √ √ √ √
Word
118
40
Modbus Long-distance Monitoring Protocol (V2.2)
Word
178
Word
238
Word R
59
Word
119
/ / / / / / / /
Word Reserved
179
Word
239
Word R
60
Word
120
/ / / / / / / /
Word Reserved
180
Word
240
Word R
61 For the version 10,
Word
the
121 Program version
/ / transmitted value = / Transfer Value= 1 / Uint16 √ √ √ √
Word 10 Actual Value
181
Word
241
Word R
62
Word
122
/ / / / / / / /
Word Reserved
182
Word
242
Word R
63 / / / / / / / /
Reserved
Word
41
Modbus Long-distance Monitoring Protocol (V2.2)
123
Word
183
Word
243
Word R
64
Word
124
0 3550 0 Transfer Value= 1 kPa Uint16 √ √ √ √
Word High pressure
Actual Value
184
Word
244
Word R
65
Word
125
0 1040 0 Transfer Value= 1 kPa Int16 √ √ √ √
Word Low pressure
Actual Value
185
Word
245
Word R
66
Word
126
0 3550 0 Transfer Value= 1 kPa Uint16 √ √ √ √
Word Oil pressure
Actual Value
186
Word
246
Word R
67
Word
127 Economizer pressure
0 2100 0 Transfer Value= 1 kPa Int16 √ √ √ √
Word
Actual Value
187
Word
247
Word R Shell-and-tube pressure
0 2100 0 1 kPa Uint16 √ √ √ √
68 Transfer Value=
42
Modbus Long-distance Monitoring Protocol (V2.2)
43
Modbus Long-distance Monitoring Protocol (V2.2)
73 Reserved
Word
133
Word
193
Word
253
Word R
74
Word
134
/ / / / / / / /
Word Reserved
194
Word
254
R
0x0001:1 system;
Word
0x0002:2 systems;
75
0x0003:3 systems;
Word
0x0004:4 systems,
135 Compressors quantity
Default: 1 0 Transfer Value= 1 Uint16 √ √ √ √
Word
Actual Value
195
Word
255
Word R
76
Word
136
/ / / / / / / /
Word Reserved
196
Word
256
Word R
77
Word / / / / / / / /
Reserved
137
Word
44
Modbus Long-distance Monitoring Protocol (V2.2)
197
Word
257
Word R
78
Word
138 Refrigerant type 0x0000:R134A
0 Transfer Value= 1 Uint16 √ √ √ √
Word 0x0001:R22
Actual Value
198
Word
258
Word R
79
Word
139 Cooling/heat pump
0x0001:cooling 0 Transfer Value= 1 Uint16 √ √ √ √
Word
only; Actual Value
199
0x0000:heat
Word
259
Word R
80
Word
140
/ / / / / / / /
Word Reserved
200
Word
260
Word R
81
Word
141
/ / / / / / / /
Word Reserved
201
Word
261
Word R
Current of compressor
82 phase A 0 600 / 0 Transfer Value= 1 A Uint16 √ √ √ √
Word
Actual Value
142
45
Modbus Long-distance Monitoring Protocol (V2.2)
Word
202
Word
262
Word R
83
Word
Current of compressor
143 phase B 0 600 / 0 Transfer Value= 1 A Uint16 √ √ √ √
Word
Actual Value
203
Word
263
Word R
84 Transfer Value=
Word Current of compressor Actual Value
144 phase C 0 600 / 0 1 A Int16 √ √ √ √
Word
204
Word
264
Word R
85
Word
145
/ / / / / / / /
Word Reserved
205
Word
265
Word R Transfer Value=
86 Actual Value×10
Word
146
Compressor oil 0 150 / 0 0.1 ℃ Uint16 √ √ √ √
Word
temperature
206
Word
266
Word R
87 / / / / / / / /
Reserved
Word
46
Modbus Long-distance Monitoring Protocol (V2.2)
147
Word
207
Word
267
Word R
88
Word
148
/ / / / / / / /
Word Reserved
208
Word
268
Word R
89
Word
149
/ / / / / / / /
Word Reserved
209
Word
269
Word R
90
Word
System pressure
150 differential 0 3550 / 0 Transfer Value= 1 kPa Uint16 √ √ √ √
Word
Actual Value
210
Word
270
Word R
91
Word
151
/ / / / / / / /
Word Reserved
211
Word
271
Word R
/ / / / / / / /
92 Reserved
47
Modbus Long-distance Monitoring Protocol (V2.2)
Word
152
Word
212
Word
272
Word R
93
Word
Times of frequent
153 protection 0 8 / 0 Transfer Value= 1 / Uint16 √ √ √ √
Word
Actual Value
213
Word
273
Word R
94
Word
154
/ / / / / / / /
Word Reserved
214
Word
274
Word R
95
Word
155
/ / / / / / / /
Word Reserved
215
Word
275
Word R
96
Word For version 1.0
Transfer Value=
156 transmitted
1.0 65535 2.0 Actual Value×10 0.1 / Uint16 √ √ √ √
Word Unit protocol version value=10
216
Word
276
Word R / / / / / /
48
Modbus Long-distance Monitoring Protocol (V2.2)
Add. Bit Access Meaning “1”Meanli “0”Mean Defau Data Type Notices
Type ng ling lt Data (★)
Sub-ty Low-
Low-
tempe
pe tem
High- rature
pera
efficie leavin
ture Water
ncy g
for Cube
air-co water
heat purch
oled high-ef
high- ase
screw ficienc
effici order
chiller y
ency
air-co
air-c
oled
oole
screw
d
chiller
Byte 0 Irrecoverable error
R 0 Bool √ √ √ √
Bit 0 With Without Status Data
49
Modbus Long-distance Monitoring Protocol (V2.2)
Recoverable error
R 0 Bool √ √ √ √
Bit 1 With Without Status Data
R / / / /
Bit 2 Reserved
R / / / /
Bit 3 Reserved
R / / / /
Bit 4 Reserved
R / / / /
Bit 5 Reserved
R / / / /
Bit 6 Reserved
R / / / /
Bit 7 Reserved
Byte 1 Does module 1 exist?
Bit8 R 0 Bool √ √ √ √
Yes No Status Data
Does module 2 exist?
Bit9 R 0 Bool √ √ √ √
Yes No Status Data
Does module 3 exist?
Bit10 R 0 Bool √ √ √ √
Yes No Status Data
Does module 4 exist?
Bit11 R 0 Bool √ √ √ √
Yes No Status Data
Bit12 R / / / /
Reserved
Bit13 R / / / /
Reserved
Bit14 R / / / /
Reserved
Bit15 R / / / /
Reserved
Byte 2
Bit16 R / / / /
Reserved
Bit17 R / / / /
Reserved
50
Modbus Long-distance Monitoring Protocol (V2.2)
Bit18 R / / / /
Reserved
Bit19 R / / / /
Reserved
Bit20 R / / / /
Reserved
Bit21 R / / / /
Reserved
Bit26 R / / / /
Reserved
Bit30 R / / / /
Reserved
Bit31 R / / / /
Reserved
Byte 4 Water pump mode
Bit32 W/R 0 Bool √
Auto Manual Status Data
51
Modbus Long-distance Monitoring Protocol (V2.2)
Bit37 W/R / / / /
Reserved
Bit38 W/R / / / /
Reserved
Bit39 W/R / / / /
Reserved
Bit42 R / / / /
Reserved
Bit43 R / / / /
Reserved
BYTE5
Bit44 R / / / /
Reserved
Bit45 R / / / /
Reserved
Bit46 R / / / /
Reserved
Bit47 R / / / /
Reserved
Bit49 R / / / /
Reserved
52
Modbus Long-distance Monitoring Protocol (V2.2)
Bit50 R / / / /
Reserved
Bit51 R / / / /
Reserved
Bit52 R / / / /
Reserved
Bit53 R / / / /
Reserved
Bit54 R / / / /
Reserved
Bit55 R / / / /
Reserved
Bit56 R / / / /
Reserved
Bit57 R / / / /
Reserved
Bit58 R / / / /
Reserved
Bit59 R / / / /
Reserved
BYTE7
Bit60 R / / / /
Reserved
Bit61 R / / / /
Reserved
Bit62 R / / / /
Reserved
Bit63 R / / / /
Reserved
Reserved
Bit64 R 0 Bool √ √ √ √
Quick test Yes No Status Data for touch
BYTE8 screen
Forced defrosting
Bit65 R 0 Bool Reserved √ √ √ √
Yes No Status Data
for touch
53
Modbus Long-distance Monitoring Protocol (V2.2)
screen
Bit66 R / / / /
54
Modbus Long-distance Monitoring Protocol (V2.2)
Byte4 Bit81 R
0 Bit201
Bool √ √ √ √
Byte5 Bit321 Recoverable error With Without Status Data
5 Bit441
Bit82 R
Bit202 Reserved
Bool √ √ √ √
Bit322 Quick test Quick test Normal test Status Data for touch
Bit442 screen
Bit83 R
Bit203
/ / / /
Bit323 Reserved
Bit443
Bit84 R
Bit204
/ / / /
Bit324 Reserved
Bit444
Bit85 R
Bit205
/ / / /
Bit325 Reserved
Bit445
Bit86 R
Bit206 Frequency protection
alarm Bool √ √ √ √
Bit326 With Without Status Data
Bit446
Bit87 R Frequency protection
Bit207 lock Bool √ √ √ √
Bit327 With Without Status Data
Bit447
Bit88 R
Bit208
Byte1 / / / /
Bit328 Reserved
1
Bit448
Byte2
Bit89 R
6
Bit209
Byte4 Bool √ √
Bit329 Soft start error switch Cut in Cut off Status Data
1
Bit449
Byte5
Bit90 R
6
Bit210 / / / /
Reserved
Bit330
55
Modbus Long-distance Monitoring Protocol (V2.2)
Bit450
Bit91 R
Bit211
/ / / /
Bit331 Reserved
Bit451
Bit92 R
Bit212
/ / / /
Bit332 Reserved
Bit452
Bit93 R
Bit213
Bool √ √ √ √
Bit333 Oil pump On Off Status Data
Bit453
Bit94 R
Bit214
Bool √ √ √ √
Bit334 Fan 5 On Off Status Data
Bit454
Bit95 R
Bit215
Bool √ √ √ √
Bit335 Fan 6 On Off Status Data
Bit455
Bit96 R
Bit216
Bool √ √ √ √
Bit336 On Off Status Data
Bit456 Fan 1
Byte1 Bit97 R
2 Bit217
Bool √ √ √ √
Byte2 Bit337 On Off Status Data
7 Bit457 Fan 2
Byte4 Bit98 R
2 Bit218
Bool √ √ √ √
Byte5 Bit338 On Off Status Data
7 Bit458 Fan 3
Bit99 R
Bit219
Bool √ √ √ √
Bit339 On Off Status Data
Bit459 Fan 4
56
Modbus Long-distance Monitoring Protocol (V2.2)
Bit100 R
Bit220 Heat recovery water
pump Bool √ √ √ √
Bit340 On Off Status Data
Bit460
Bit101 R
Bit221 Auxiliary electric
heater 2 Bool √ √ √ √
Bit341 On Off Status Data
Bit461
Bit102 R
Bit222 Auxiliary electric
heater 1 Bool √ √ √ √
Bit342 On Off Status Data
Bit462
Bit103 R
Bit223 Air conditioning water
pump Bool √ √ √ √
Bit343 On Off Status Data
Bit463
Bit104 R
Bit224 Compression main AC contactor
Bool √ √ √ √
Bit344 On Off Status Data
Bit464
Bit105 R
Bit225
/ / / /
Bit345 Reserved
Bit465
Byte1
Bit106 R
3
Bit226
Byte2 / / / /
Bit346 Reserved
8
Bit466
Byte4
Bit107 R
3
Bit227
Byte5 / / / /
Bit347 Reserved
8
Bit467
Bit108 R
Bit228
/ / / /
Bit348 Reserved
Bit468
Bit109 R
Bit229 / / / /
Reserved
Bit349
57
Modbus Long-distance Monitoring Protocol (V2.2)
Bit469
Bit110 R
Bit230
/ / / /
Bit350 Reserved
Bit470
Bit111 R
Bit231
Bool √ √ √ √
Bit351 On Off Status Data
Bit471 4-way valve
Bit112 R
Bit232
/ / / /
Bit352 Reserved
Bit472
Bit113 R
Bit233
/ / / /
Bit353 Reserved
Bit473
Bit114 R
Bit234
/ / / /
Byte1 Bit354 Reserved
4 Bit474
Byte2 Bit115 R
9 Bit235
/ / / /
Byte4 Bit355 Reserved
4 Bit475
Byte5 Bit116 R
9 Bit236
/ / / /
Bit356 Reserved
Bit476
Bit117 R
Bit237
/ / / /
Bit357 Reserved
Bit477
Bit118 R
Bit238
/ / / /
Bit358 Reserved
Bit478
58
Modbus Long-distance Monitoring Protocol (V2.2)
Bit119 R
Bit239
/ / / /
Bit359 Reserved
Bit479
Bit120 R
~
Bit127
Bit240
~
Bit247
/ / / /
Bit360 Reserved
~
Bit367
Bit480
Byte1
~
5
Bit487
Byte3
Bit128 R
0
Bit248
Byte4 / / / /
Bit368 Reserved
5
Bit488
Byte6
Bit129 R
0
Bit249
Byte1 / / / /
Bit369 Reserved
6
Bit489
Byte3
Bit130 R
1
Bit250
Byte4 / / / /
Bit370 Reserved
6
Bit490
Byte6
Bit131 R
1
Bit251
/ / / /
Bit371 Reserved
Bit491
Bit132 R
Bit252
/ / / /
Bit372 Reserved
Bit492
Bit133 R
Bit253 / / / /
Reserved
Bit373
59
Modbus Long-distance Monitoring Protocol (V2.2)
Bit493
Bit134 R
Bit254
/ / / /
Bit374 Reserved
Bit494
Bit128
Bit248
R Bool √ √ √ √
Bit368 Low flow alarm With Without Error Data
Bit488
Bit129 Liquid line
Bit249 temperature sensor
R Bool √ √ √ √
Bit369 error With Without Error Data
Bit489
Bit130 Discharge
Bit250 temperature sensor
R Bool √ √ √ √
Bit370 error With Without Error Data
Bit490
Byte1 Bit131 Shell-and-tube
6 Bit251 pressure sensor error
R Bool √ √ √ √
Byte3 Bit371 With Without Error Data
1 Bit491
Byte4 Bit132
6 Bit252
R / / / /
Byte6 Bit372 Reserved
1 Bit492
Bit133
Bit253
R / / / /
Bit373 Reserved
Bit493
Bit134 Suction temperature
Bit254 sensor error
R Bool √ √ √ √
Bit374 With Without Error Data
Bit494
Bit135
Bit255
R / / / /
Bit375 Reserved
Bit495
60
Modbus Long-distance Monitoring Protocol (V2.2)
Bit136
Bit256 AC contactor interlock
R Bool √ √ √ √
Bit376 protection With Without Error Data
Bit496
Bit137 Fan over-current
Bit257 protection
R Bool √ √ √ √
Bit377 With Without Error Data
Bit497
Bit138
Compressor internal
Bit258 protection
R Bool √ √ √ √
Bit378 With Without Error Data
Bit498
Bit139
Byte1
Bit259
7 R Low oil level Bool √ √ √ √
Bit379 With Without Error Data
Byte3 protection
Bit499
2
Bit140 Water pump interlock
Byte4
Bit260 protection
7 R Bool √ √ √ √
Bit380 With Without Error Data
Byte6
Bit500
2 Air conditioning water
Bit141
Bit261 flow switch protection
R Bool √ √ √ √
Bit381 With Without Error Data
Bit501
Bit142
Bit262 Compressor
R Bool √ √ √ √
Bit382 over-current With Without Error Data
Bit502 protection
Bit143
Bit263 Waterless flow Pro.
R Bool √
Bit383 With Without Error Data
Bit503
Bit144
Byte1 Bit264
R High discharge Bool √ √ √ √
8 Bit384 With Without Error Data
protection
Byte3 Bit504
3 Bit145 Oil pressure
Byte4 Bit265 R difference protection Bool √ √ √ √
With Without Error Data
8 Bit385
61
Modbus Long-distance Monitoring Protocol (V2.2)
Byte6 Bit505
3
Bit146 System pressure
Bit266 difference protection
R Bool √ √ √ √
Bit386 With Without Error Data
Bit506
Bit147
Bit267
R Overheating Bool √ √ √ √
Bit387 With Without Error Data
protection
Bit507
Bit148
Bit268 Freeze protection
R Bool √ √ √ √
Bit388 With Without Error Data
Bit508
Bit149
Bit269
R Bool √ √
Bit389 Soft start error With Without Error Data
Bit509
Bit150 Compressor low
Bit270 pressure protection
R Bool √ √ √ √
Bit390 With Without Error Data
Bit510
Bit151 Compressor high
Bit271 pressure protection
R Bool √ √ √ √
Bit391 With Without Error Data
Bit511
Bit152 Low discharge
Bit272 superheating degree
R Bool √ √ √ √
Bit392 protection With Without Error Data
Byte1
Bit512
9
Bit153 System EXV
Byte3
Bit273 communication error
4 R Bool √ √ √ √
Bit393 With Without Error Data
Byte4
Bit513
9
Bit154 4-way valve abnormal
Byte6
Bit274 reversing
4 R Bool √ √ √ √
Bit394 protection With Without Error Data
Bit514
62
Modbus Long-distance Monitoring Protocol (V2.2)
63
Modbus Long-distance Monitoring Protocol (V2.2)
Bit524 error
64
Modbus Long-distance Monitoring Protocol (V2.2)
Bit532 error
65
Modbus Long-distance Monitoring Protocol (V2.2)
66
Modbus Long-distance Monitoring Protocol (V2.2)
Bit551
Bit192
Bit312
R / / / /
Bit432 Reserved
Bit552
Bit193
Bit313
R / / / /
Bit433 Reserved
Bit553
Bit194
Bit314
R / / / /
Bit434 Reserved
Bit554
Byte2 Bit195
4 Bit315
R / / / /
Byte3 Bit435 Reserved
9 Bit555
Byte5 Bit196
4 Bit316
R / / / /
Byte6 Bit436 Reserved
9 Bit556
Bit197
Bit317
R / / / /
Bit437 Reserved
Bit557
Bit198
Bit318
R / / / /
Bit438 Reserved
Bit558
Bit199
Bit319
R / / / /
Bit439 Reserved
Bit559
67