PPX Series

This document is an instruction manual for the PPX series pressure switch, detailing its features, wiring, and operational modes. It includes safety precautions, part descriptions, output modes, and mounting instructions. Users are advised to follow the guidelines for installation and operation to ensure proper functionality and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views4 pages

PPX Series

This document is an instruction manual for the PPX series pressure switch, detailing its features, wiring, and operational modes. It includes safety precautions, part descriptions, output modes, and mounting instructions. Users are advised to follow the guidelines for installation and operation to ensure proper functionality and safety.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

5 I/O CIRCUIT DIAGRAMS

MJE-PPX No.0040-81V
NPN output type

Standard type
INSTRUCTION MANUAL (Brown) +V
(Black) Load

Main circuit
Comparative output 1
PARECT PRESSURE SWITCH Load
+ 12 to 24V DC
100mA max.
PPX series (White) Comparative output 2 - ±10%
100mA max.
(Blue) 0V
Read this instruction manual carefully before using this product, particularly the section
describing safety.
Retain this instruction manual with the product for further consultation whenever necessary. High-function type
(Brown) +V
5V
Precaution (White)

Main circuit
● This product is designed for air / non-corrosive gas. Analogue voltage / current output Load
1kΩ or external input (Notes 1, 2, 3) + 12 to 24V DC
● (Black)
- ±10%
● Do not touch electric wiring connections (bare live parts): this will cause an electric shock. Comparative output 1
During wiring, keep the power off. Also, do not touch these live parts with wet hands. 100mA max.
● A product intended for use in Japan conforms to the Japanese Measurement Act. (Blue) 0V
Do not use a product intended for use overseas in Japan.

1 PART DESCRIPTION PNP output type


Output 1 operation Unit display 㸯 Standard type
PPX
indicator (Note 1, 2)
Connection (Brown) +V
Lights up when com- Main display connector
parative output 1 is ON
100mA max.

Main circuit
Sub display
Output 2 / analogue (Black) Comparative output 1 + 12 to 24V DC
voltage / current out- Setting value 100mA max.
- ±10%
put operation indicator DOWN key Load
Standard type: (White)
Comparative output 2 Load
Lights up when com- Setting value UP key Pressure port
parative output 2 is ON 6M type: R1/8 + M5 female screw (Blue) 0V
Mode selection key
High-function type: 6G type: G1/8 + M5 female screw
Lights up when analogue 6N type: NPT1/8 + M5 female screw High-function type
voltage / current output is set
(Brown) +V
Notes: 1) In the case of a model that is intended for use outside Japan, attach the unit switch plate corresponds to the set
pressure unit. 100mA max.
2) The product for use inside Japan can be set only to “MPa” or “kPa.”
Main circuit

(Black) +
Comparative output 1 12 to 24V DC
1kΩ (White) - ±10%
2 PIPING Analogue voltage / current output Load
or external input (Notes 1, 2, 3)
● When connecting a commercial coupler to the pres- 12mm spanner
(Blue) 0V
sure port, attach a 12mm spanner (14mm for 6G
type) to the pressure port’s hexagon section to fix Notes: 1) When the analogue current is output, the output load resistance should be 250Ω max.
the port, and then tighten with a tightening torque of 2) Take care that when the analogue current is output, 5V or more voltage generates.
9.8N·m or less (M5 female: 1N·m or less). The com- 3) When using the analogue voltage output, be careful to the input impedance of the connected device.
Furthermore, note that if the cable is extended, the cable resistance will cause the voltage to drop.
mercial coupler or pressure port section will be dam-
aged if the tightening torque is excessive.
Wrap sealing tape around the coupler when connect- 6 OUTPUT MODE AND OUTPUT OPERATION
ing to prevent leaks.
● The EASY mode, hysteresis mode or window comparator mode can be selected as
the output mode for comparative output 1 and comparative output 2.
3 MOUNTING Refer to <Comparative output 1 / 2 output mode setting> in “ 8 MENU SET-
TING MODE” for details.
● The sensor mounting bracket PPX-KL is available as an option. When mounting the sensor
onto the sensor mounting bracket, etc., the tightening torque should be 0.5N·m or less. EASY mode

● ON / OFF of the comparative output is controlled in this mode.


M3 (length 6mm) screws
with washers
H (Hysteresis)
Pressure

(Accessory with PPX-KL)


P

Sensor mounting bracket 0


PPX-KL (Optional) Comparative ON
output OFF
Notes: 1)
Refer to in “ 9 PRO MODE” for setting.
2) “ ” is displayed for comparative output 1 and “ ” for comparative output 2 on the sub-display.
● The panel mounting bracket PPX-KHS (optional), as well as the front cover PPX-KCB
(optional) are also available. Hysteresis mode
● For mounting of the panel mounting bracket, refer to the Instruction Manual en-
closed with PPX-KHS. ● The comparative output ON / OFF state can be controlled with randomly set hyster-
esis in this mode.

4 WIRING
Pressure

Cable with connector Hi H: 1digit or more


Connection method 2 digits or more when
PPX-C□ H (Hysteresis)
Lo using psi unit
● Insert the cable with connector PPX-C□ into
0
this product’s connection connector section
Comparative ON
output OFF
Release lever
Note: “ ” or “ ” is displayed for comparative output 1 and “ ” or “ ” for comparative output 2 on the
Disconnection method sub-display.
<Recommended product>
● Pressing the release lever of the cable with Contact: SPHD-001T-P0.5
Housing: PAP-04V-S
connector, pull out the connector. [JST Mfg. Co., Ltd.]
Note: Do not pull by holding the cable without pressing the release lever, as this can cause cable break or connector break.

<Connection connector pin arrangement>


Connector pin No. Terminal name
1 +V
2 Comparative output 1
Standard type: Comparative output 2
3
High-function type: Analogue voltage / current output or external input
1 2 3 4 4 0V
Window comparator mode 8 MENU SETTING MODE
● In this mode, the ON or OFF state of the comparative output is controlled with a ● The mode will change to RUN mode when the mode selection key is held down
pressure in the set range. during this setting process. In doing so, changed items before holding down the
mode selection key have been set.
H (Hysteresis)
Pressure

RUN mode
Hi
H (Hysteresis) Press for 2 sec.
Lo
<Comparative output 1 output mode setting> Window
0 Hysteresis comparator
Comparative ON EASY mode mode mode
output OFF
Notes: 1)
Refer to in “ 9 PRO MODE” for setting.
2) “ ” or “ ” is displayed for comparative output 1 and “ ” or “ ” for comparative output 2 on the
sub-display.
3)
● Standard type
<Comparative output 2 output mode setting> (Note 1) Window
7 RUN MODE OFF mode EASY mode
Hysteresis
mode
comparator
mode

Setting the threshold value

● Refer to <Comparative output 1 / 2 output mode setting>, <Analogue voltage


/ current output / external input selection> in “ 8 MENU SETTING MODE” for
setting conditions. ● High-function type
● The Sub display conducts the threshold value. Main display does not changed. <Analogue voltage / current output / external input selection>
Remote
Display is changed by pressing down. Analogue Auto-refer- zero-adjust- Analogue
voltage output ence input ment input current output
EASY mode
(Comparative output 2 is OFF)
Comparative output 1
EASY mode
Comparative output 2
Automatic
Comparative output 1
Hysteresis mode / Window
comparator mode · Lo side
Comparative output 2

Comparative output 1 Press: Increase threshold value to high pressure side. ● Standard type
Hysteresis mode / Window
comparator mode · Hi side Press: Decrease threshold value to low pressure side. <N.O. / N.C. selection> (Note 1)
Comparative output 2 Output 1: N.O. Output 1: N.C. Output 1: N.O. Output 1: N.C.
Output 2: N.O. Output 2: N.C. Output 2: N.C. Output 2: N.O.

Blinks alternately
(Note 2) (Note 3)

Notes: 1) If the set pressure range is exceeded, “ ” (exceeds the upper limit) or “ ” (exceeds the lower limit) will
● High-function type
appear on the sub display. “ ” will also appear if the Hi side threshold value exceeds the Lo side threshold
<N.O. / N.C. selection>
value when setting the “hysteresis mode / window comparator mode” threshold value.
N.O. N.C.
2) Auto-reference value and remote zero-adjustment value are displayed.
For details, refer to “ 11 AUTO-REFERENCE FUNCTION” and “ 12 REMOTE ZERO-ADJUSTMENT FUNCTION.”
3) In the dash line box is not displayed when not setting “ ” or “ ” in external input switch. For the setting
method, refer to <Analogue voltage / current output / external input selection> in “ 8 MENU SETTING
MODE.”

Zero-adjustment function <Response time setting>


2.5ms 5ms 5,000ms
● The zero-adjustment function forcibly sets the pressure value to “zero” when the
pressure port is opened.
Hold down Automatic

<Display color of the main display selection>


Key lock function Red when ON Green when ON
Green when OFF Red when OFF Always red Always green
● The key lock function prevents key operations so that the conditions set in each set-
ting mode are not inadvertently changed.
<Key lock set>
Hold down Automatic
<Unit selection> (Note 2)
2
MPa kPa kgf/cm bar psi

<Key lock released>


Hold down Automatic

inchHg (Note 3) mmHg (Note 3)


Peak / bottom hold function RUN mode

● The peak / bottom hold functions display the peak value and bottom value of the Notes: 1) If the comparative output 2 output mode setting is set to “ ”, the display of N.O. / N.C. selection is the same
as the high-function type.
2) In case Japanese, only “MPa” or “kPa” can be set. In the case of a low pressure type, the unit switch setting
● The peak value is displayed on the main display and the bottom value is displayed item is not displayed.
on the sub-display. 3) This is not displayed on the high pressure type.
● The higher vacuum side indicates the peak value, while the lower vacuum side indi-
Setting item Factory setting Description
cates the bottom value.
Comparative output 1
Sets the output operation of comparative output 1.
<Peak / bottom hold set> output mode setting
Comparative output 2
Hold down Blinks alternately output mode setting Sets the output operation of comparative output 2.
(Standard type only)
Analogue voltage /
current output / ex- Selects analogue voltage / current output, auto-reference input, or remote
<Peak / bottom hold released> ternal input selection zero-adjustment input.
(High-function type only)
Hold down
Low pressure type

N.O. / N.C. selection Normal open (N.O.) or normal close (N.C.) can be selected.
High pressure type

Sets the response time.


Response time setting The response time can be selected from 2.5ms, 5ms, 10ms, 25ms, 50ms,
100ms, 250ms, 500ms, 1,000ms or 5,000ms.
Displayed color of the
Displayed color of the main indicator can be changed.
main display selection
Low pressure type

Unit selection Pressure unit can be changed.


High pressure type
9 PRO MODE Code table

● The mode will change to RUN mode when the mode selection key is held down ● Main display (1st digit form left)
during this setting process. However, changed items before holding down the mode 1st digit
2nd digit
3rd digit
4th digit
selection key have been set. Standard type High-function type Standard type

Code
Analogue
RUN mode Comparative Comparative Displayed
N.O. / N.C. N.O. / N.C. voltage / cur- Threshold Displayed
output 1 output 2 color of the
When “No. display” or “Custom display” is set in “Sub display selection.” selection selection rent output / display color relation
Press for output mode output mode main display
external input
4 seconds <Sub-display selection>
When “ ” is set Change the displayed details with Analogue Comparative
<PRO mode> N.O. OFF OFF P-1, Lo-1
voltage output output 1
EASY Red when ON
RUN mode Comparative
N.C. N.O. Auto reference Hi-1
output 2
EASY
Remote zero- Comparative
N.O. N.C. P-2, Lo-2
When “ ” is set adjustment output 1
Set pressure Hysteresis Green when ON
range is displayed Analogue Comparative
N.C. N.O. Hi-2
on sub display. current output output 2
Hysteresis
Comparative
N.O. N.C. - ADJ.
Window output 1
comparator Always red
<Sub-display selection> Custom Comparative
Standard Display OFF Unit display No. display display N.C. N.O. - -
Window output 2
comparator Comparative
- - N.C. - -
output 1
Always green
Comparative
- - - - - -
output 2

<Display speed selection> ● Sub-display (5th digit from left)


250ms 500ms 1,000ms 5th digit 6th digit 7th digit 8th digit

Code
Response time Unit selection Display speed Eco mode
2.5ms MPa 250ms OFF
5ms kPa 500ms Std
2
10ms kgf/cm 1,000ms Full
25ms bar - -

Max. Min. 50ms psi - -


100ms mmHg - -
250ms inchHg - -
500ms - - -
1,000ms - - -
5,000ms - - -

● Standard type only

<Displayed color relation selection>


Relating with Relating with
10 SETTING COPY FUNCTION
comparative comparative
output 1 output 2 ● This can copy the settings of the master side sensor to the slave side sensor.

● Be sure to use the setting copy function between the identical models.
This function cannot be used between different models.
● Only one sensor can be connected on slave side with a master side sensor for the
setting copy function.
<Eco mode setting>
OFF Standard Max. Setting procedure

1. Set the setting copy function of the master side sensor to “Copy sending ON” or
“Copy sending ON-L”, and then press the mode selection key so that the sensor is
in copy ready state. For details, refer to <Setting copy mode> in “ 9 PRO MODE”.
2. Turn OFF the master side sensor.
<Setting check code> 3. Connect the master side sensor with the slave side sensor as shown below.
Automatic
Color code of cable
with connector
Power supply
Master side sensor Slave side sensor
(Brown) +V +V (Brown)
<Setting copy mode>
Copy sending Copy sending Copy sending (Blue) 0V 0V (Blue)
OFF ON ON-L
(Black) Comparative output 1 Comparative output 1 (Black)
Copy ready (White) Comparative output 2 (Note 1) Comparative output 2 (Note 1) (White)
state
Notes: 1) For the high-function type, external input.

<Reset setting> 4. Turn ON the master side sensor and the slave side sensor at the same time.
(Note 2) (Note 3)
5. Set contents (16-bit coded) are shown in orange on the main display of the master
side sensor and the copying starts.
6. The same code explained above is shown in green on the the main display of the
slave side sensor, and “ ” is shown on the sub-display (When copying is com-
RUN mode
plete.)
Setting item Factory setting Description 7. Turn OFF the power of the master side sensor and the slave side sensor and dis-
Changes the indication of the sub-display. connect the wire.
“ ” : Displays nothing.
“ ” : Presently selected pressure unit is displayed.
* If copying the setting to another sensor repeatedly, follow steps 3 to 7.
Sub-display selection
“ ” : Desired No. can be shown.
Notes: 2) Take care that if the power is not turned on at the same time, the setting contents may not be copied.
“ ” : Desired numbers, alphabets (some of them cannot be displayed)
3) Note that when the power is on, pulse output is output to comparative output 1.
and signs can be shown.
Display speed
Changes the speed of the displayed pressure value on the main display. To cancel the setting copy mode of master side sensor
selection
Sets hysteresis of the EASY mode and the window comparator mode.
value selection (8 steps)
1. Whilst the slave side sensor is disconnected, turn on the power of the master side
Displayed color rela-
sensor.
The setting contents set at the displayed color setting in Menu setting mode 2. Press the mode selection key for approx. 2 seconds.
tion selection
can be related with either comparative output 1 or comparative output 2.
(Standard type only)
Current consumption can be lowered.
“ ” : Normal operation (ECO mode is off.)
“ ” : If any key operation is not carried out for approx. 5 sec. in RUN
Eco mode setting mode, the display becomes dark.
“ ” : If any key operation is not carried out for approx. 5 sec. in RUN
mode, the display is turned off.
Press any key to temporarily show the normal indication.

Setting check code Current setting contents can be checked. For codes. refer to “Code table”.

The setting of the master side sensor can be copied to the slave side sensors.
For details, refer to “ 10 SETTING COPY FUNCTION.”
Setting copy mode “ ” : The setting contents are copied.
“ ” : The setting contents are copied, and the slave side sensor goes
into key-lock state.
Returns to default settings (factory settings).
Reset setting By pressing dowun mode key when “ ” mode, becomes default settings
(factory settings).
11 AUTO-REFERENCE FUNCTION (ONLY HIGH-FUNCTION TYPE) 14 SPECIFICATIONS
● The auto-reference function ON ● Model
corrects the set value using the Before PPX-R 1 2 3 - 4 - 5 - 6
OFF
auto-reference
detected pressure value during ON 1 : 01: Low-pressure type, 10: High-pressure type
auto-reference input as the refer- After
OFF 2 : N: NPN output type, P: PNP output type
ence pressure. auto-reference
3 : None: Standard type, H: High-function type
● Using the detected pressure val- Atmospheric pressure P(a) Set value 1 Set value 1’ 4 : 6M: R1/8 + M5 female screw (Note 1), 6G: G1/8 + M5 female screw (Note 2)
ue at auto-reference input P(a) Pressure 6N: NPT1/8 + M5 female screw (Note 3)
as a reference, the set value 1’ Detected pressure value Set value 1’ after auto-reference is: 5 : None: Cable with connector enclosed, J: No cable with connector (Note 4)
is automatically corrected to “set at auto-reference input 1’ = 1 + P(a)
6 : KA: For outside of Japan, None: For inside of Japan
value 1 + P(a)”.
Notes: 1) PNP output type is not available in the 6M type.
2) NPN output type and for inside of Japan are not available in the 6G type.
Settable range and set pressure range after correction 3) For inside of Japan is not available in the 6N type.
4) High-function type is not available in the J type.
● The set pressure range is wider than the rating pressure range so that the auto-
reference function can be handled. Type Standard type High-function type
Item Low-pressure type High-pressure type Low-pressure type High-pressure type
Pressure type Gauge pressure
If the corrected set value exceeds the set pressure range when auto-reference input Rated pressure range -100 to +100kPa -0.1 to +1.0MPa -100 to +100kPa -0.1 to +1.0MPa
is carried out, the set value will be automatically corrected to within the set pressure Set pressure range -101.0 to +101.0kPa -0.101 to +1.010MPa -101.0 to +101.0kPa -0.101 to +1.010MPa
range. Thus, take care not to exceed the set pressure range. Withstand pressure 500kPa 1.5MPa 500kPa 1.5MPa
Non-corrosive gas
Supply voltage 12 to 24V DC ±10%
Operation chart Normal operation: 720mW or less (current consumption 30mA or less at 24V supply voltage)
Power consumption (Note 1) ECO mode (STD): 480mW or less (current consumption 20mA or less at 24V supply voltage)
During normal operation During auto-reference input ECO mode (FULL): 360mW or less (current consumption 15mA or less at 24V supply voltage)
(each comparative output set to N.O.) (each comparative output set to N.O.) <NPN output type> <PNP output type>
NPN open-collector transistor PNP open-collector transistor
• Detected pressure at auto-reference input: 10kPa • Maximum sink current: 100mA • Maximum source current: 100mA
• Output mode: Hysteresis mode Comparative output • Applied voltage: 30V DC or less • Applied voltage: 30V DC or less
(between comparative output and 0V) (between comparative output and +V)
ON ON • Residual voltage: 2V or less • Residual voltage: 2V or less
Output Output (at 100mA sink current ) (at 100mA source current )
OFF OFF Output operation Selectable either N.O. or N.C., with key operation
Hysteresis Min. 1 digit (variable) (however, 2 digits when using psi units)
Applied pressure (kPa) 0 10 20 30 40 50 60 Applied pressure (kPa) 0 10 20 30 40 50 60 ±0.1% F.S. ±0.2% F.S. ±0.1% F.S. ±0.2% F.S.
Repeatability
Displayed value (kPa) 0 10 20 30 40 50 60 Displayed value (kPa) 0 10 20 30 40 50 60 ± within 2 digits ± within 2 digits ± within 2 digits ± within 2 digits
1 2 P(a) 1’ 2’ 2.5ms, 5ms, 10ms, 25ms, 50ms, 100ms, 250ms, 500ms, 1.000ms or 5,000ms
Response time
Set value (kPa) 10 20 Set value (kPa) 10 20 30 selectable with key operations
<High-function, low-pressure type> <High-function, high-pressure type>
Note: The set values shift in the same manner during the EASY mode or the window comparator mode. • Output voltage: 1 to 5V • Output voltage: 0.6 to 5V
• Zero point: Within 3V ± 5% F.S. • Zero point: Within 1V ± 5% F.S.
Analogue voltage output
• Span: Within 4V ± 5% F.S. • Span: Within 4.4V ± 5% F.S.
● The detected pressure value at auto-reference input becomes “zero” when the set- • Linearity: Within ± 1% F.S. • Linearity: Within ± 1% F.S.
ting of the external input selection function is changed or the power is turned ON • Output impedance: Approx. 1kΩ • Output impedance: Approx. 1kΩ
<High-function, low-pressure type> <High-function, high-pressure type>
again. • Output current: 4 to 20mA • Output current: 2.4 to 20mA
● The auto-reference input value can be checked when setting the threshold value in Analogue current output
• Zero point: Within 12mA ± 5% F.S. • Zero point: Within 4mA ± 5% F.S.
RUN mode. Refer to the threshold value setting in “ 7 RUN MODE” for details. • Span: Within 16mA ± 5% F.S. • Span: Within 17.6mA ± 5% F.S.
• Linearity: Within ± 1% F.S. • Linearity: Within ± 1% F.S.
• Load resistance: 250Ω (max.) • Load resistance: 250Ω (max.)
<High-function NPN output type> <High-function PNP output type>
12 REMOTE ZERO-ADJUSTMENT FUNCTION (HIGH-FUNCTION TYPE) External input
• ON voltage: 0.4V DC or less
• OFF voltage: 5 to 30V DC or open
• ON voltage: 5V to +V DC
• OFF voltage: 0.6V DC or less or open
• Input impedance: Approx. 10kΩ • Input impedance: Approx. 10kΩ
● The remote zero-adjustment function forcibly sets the pressure value to “zero” when • Input time: 1ms or more • Input time: 1ms or more
the external signal is inputted. Ambient temperature -10 to +50°C (No dew condensation or icing allowed), Storage: -10 to +60°C
Ambient humidity 35 to 85% RH, Storage: 35 to 85% RH
The set value is not corrected when remote zero-adjustment is input. Make sure that the Temperature characteristics
Within ±0.5% F.S. Within ±1% F.S. Within ±0.5% F.S. Within ±1% F.S.
(at +20°C reference) (at +20°C reference) (at +20°C reference) (at +20°C reference)
pressure and set value during remote zero-adjustment do not exceed the set pressure
range. Material Pressure port: Stainless steel (SUS 303Cu)
Mounting screw section: Brass (nickel-plated), O-ring: H-NBR, Key part: Silicon rubber
Weight Approx. 40g (6G type: approx. 45g) (Main body only)
Operation chart
PPX-C2 (Cable with a connector, 2m long) (optional for J type): 1 pc.
Accessories
Unit switching label: 1 pc. (for outside of Japan only)
During normal operation During remote zero-adjustment input
Note: Current consumption does not include the analog current output.
(each comparative output set to N.O.) (each comparative output set to N.O.)
• Detected pressure at remote zero-adjustment input: 10kPa
• Output mode: Hysteresis mode
15 CAUTIONS
ON ON
Output Output
OFF OFF ● This product has been developed / produced for industrial use only.
● Use within the rated pressure range.
Applied pressure (kPa) 0 10 20 30 40 50 60 Applied pressure (kPa) 0 10 20 30 40 50 60
● Do not apply pressure exceeding the pressure withstandability value. The dia-
Displayed value (kPa) 0 10 20 30 40 50 60 Displayed value (kPa) -10 0 10 20 30 40 50 phragm will get damaged and correct operation shall not be maintained.
1 2 1 2 ● Make sure that the power supply is off while wiring.
Set value (kPa) 10 20 Set value (kPa) 10 20
● Take care that wrong wiring will damage the sensor.
Note: The setting values shift in the same manner during the EASY mode or the window comparator mode. ● Verify that the supply voltage variation is within the rating.
● If power is supplied from a commercial switching regulator, ensure that the frame
● The remote zero-adjustment value is cleared when the setting of the external input ground (F.G.) terminal of the power supply is connected to an actual ground.
selection is changed or the power is turned ON again, and normal operation based ● In case noise generating equipment (switching regulator, inverter motor, etc.) is
on the atmospheric pressure is resumed. used in the vicinity of this sensor, connect the frame ground (F.G.) terminal of the
● The remote zero-adjustment value can be confirmed when setting the threshold equipment to an actual ground.
value in RUN mode. Refer to the threshold value setting in “ 7 RUN MODE”. ● Do not use during the initial transient time (0.5 sec.) after the power supply is
switched on.
● Extension up to total 100m or less, is possible with more than 0.3mm 2 of electric
13 ERROR INDICATION conductor cross-sectional area cable.
● In case of using this product as a CE Marking conformity product, the wire con-
Error message Cause Corrective action nected to this product must be within 30m.
The load is short-circuited causing
Turn the power OFF and check the load.
● Do not run the wires together with high-voltage lines or power lines or put them in
the same raceway. This can cause malfunction due to induction.
Applied pressure at the pressure port should be brought to ●
Pressure is applied during zero-
atmospheric pressure and zero-point adjustment should be
point adjustment.
done again.
● Avoid dust, dirt, and steam.
External input is carried out outside Applied pressure range should be brought within the rated
● Take care that the sensor does not come in direct contact with water, oil, grease, or
the rated pressure range. pressure range. organic solvents, such as, thinner, etc.
Communication error
● Do not insert wires, etc, into the pressure port. The diaphragm will get damaged
Check the wiring when using the copy function. and correct operation shall not be maintained.
(Disconnection, faulty connection, etc.)
Communication error ● Do not operate the keys with pointed or sharp objects.
(Incorrect model.) when using the copy function. ● Make sure that stress by forcible bend or pulling is not applied directly to the sensor
The applied pressure exceeds the cable joint.
upper limit of the display pressure
range. Applied pressure range should be brought within the rated
The applied pressure exceeds the pressure range.
lower limit of the display pressure
range.

When other error massage is displayed, contact us.