EET408PSA12
EET408PSA12
59.7 kV 40.0 kV
17.6 MW
16.0 MW
28.8 MVR
16.0 MVR
Arrows are
Generators are Transmission lines
used to
shown as circles are shown as a
single line show loads
Notation - Power
Power: Instantaneous consumption of energy
Power Units:
Watts = voltage x current for dc (W)
kW – 1 x 103 Watt
MW – 1 x 106 Watt
GW – 1 x 109 Watt
Installed U.S. generation capacity is about
775 GW ( about 2.9 kW per person)
Maximum load of Champaign/Urbana about
300 MW
Notation - Energy
Energy: Integration of power over time;
energy is what people really want from a
power system
Energy Units
Joule = 1 Watt-second (J)
kWh – Kilowatthour (3.6 x 106 J)
Btu – 1055 J;
1 MBtu=0.292 MWh
U.S. electric energy consumption is about
3600 billion kWh (about 13,333 kWh per
person, which means on average we each
use 1.5 kW of power continuously)
Power System Examples
Electric utility: can range from quite small, such
as an island, to one covering half the continent
there are four major interconnected ac power
systems in North American, each operating at 60 Hz
ac; 50 Hz is used in some other countries.
Airplanes and Spaceships: reduction in weight
is primary consideration; frequency is 400 Hz.
Ships and submarines
Automobiles: dc with 12 volts standard
Battery operated portable systems
Utility Restructuring
Driven by significant regional variations in
electric rates
Goal of competition is to reduce rates through
the introduction of competition
Eventual goal is to allow consumers to choose
their electricity supplier
1.2. THE MODERN POWER
SYSTEMS
The power system of to day is a complex interconnected
network.
The advantages of interconnection system are
1. We need a few machines to draw peak load, only
2. A few machines be operated at no load be up
against the sudden load.
3. The power can supplied from the other company
which is lower cost.
4. Possibly, buy the power energy is costless than self
generated.
But, the problems are:
1. Generation
2. Transmission and Sub transmission
3. Distribution
4. Loads.
1.3. THE PROBLEMS IN
POWER SYSTEM
Load flow
Optimal Power Flow and
Economic Operation of power
systems
Short-Circuit
Stability
1.4.1. SINGLE LINE DIAGRAM
OF POWER SYSTEM
.
T1
T 3
2
Load B
2
Load A
actual quality
quantity in per − unit =
base value of quantity
S
S per − unit =
SB
V
Vper−unit =
VB
Cont’d
. I
I per − unit =
I B
Z
Z per − unit =
ZB
where:
1. the numerators ( actual values) are phasor quantities
or complex values and
2. the denominators (base values) are always real
numbers.
Per Unit Calculations
A key problem in analyzing power systems is
the large number of transformers.
It would be very difficult to continually have to refer
impedances to the different sides of the
transformers
This problem is avoided by a normalization of
all variables.
This normalization is known as per unit
analysis.
Per Unit Conversion Procedure, 1ø
Pick a 1 ø VA base for the entire system,
SB
Pick a voltage base for each different
voltage level, VB. Voltage bases are
related by transformer turns ratios.
Voltages are line to neutral.
Calculate the impedance base,
ZB= (Vb)2/SB
Calculate the current base, IB = VB/ZB
Convert actual values to per unit
A minimum of four base quantities are required
to completely define a per-unit system
1. volt-ampere
2. voltage
3. Current
4. impedance
In three-phase system:
.
S B
I B =
V
3V B
B
3
Z B =
I B
2 2
(VB ) (kVB )
ZB = =
SB MVAB
Example 1.5.1
Given a 100-V sinusoidal source in series with a
3-Ω resistor, a 8-Ω inductor and a 4-Ω
capacitor.
Solve the problem in per-unit on base of Vbase =
100V and Sbase = 500VA.
Calculate the complex power delivered to each
of the four elements in the circuit in per-unit
Solution
Solution
S base 500
. I base = = = 5A
V base 100
V base 100
Z base = = = 20 Ω
I base 5
2
V base ( 100 ) 2
Z base = = 20 Ω
S base 500
We convert the circuit values to per-unit
.
0
V 100 ∠ 0 0
V pu = = = 1∠ 0 = 1 + j0
V base 100
R 3
R pu = = = 0 . 15
Z base 20
X L 8
X Lpu = = = 0 . 40
Z base 20
X C 4
X Cpu = = = 0 . 20
Z base 20
The circuit is shown in Fig. 1.5.3 where
all values in per-unit
.
0.15 J0.40
-j0.20
1+j0 Ipu
V pu 1∠ 0 0 0
I pu = = = 4 . 0 ∠ − 53 . 1
Z pu 0 . 25 ∠ + 53 . 1 0
Cont’d
.S Rpu = I 2 R = ( 4 ) 2 ( 0 . 15 ) = 2 . 4 + j 0 )
2
S Lpu = jI X L = j ( 4 ) 2 ( 0 .4 ) = 0 + j 6 .4
2 2
S Cpu = − jI X C = − j ( 4 ) (. 0 . 2 ) = 0 − j 3 . 2
2
0.25(18 / 500)
X "= 2
= 0.0405 per − unit
20 / 100
Note:
Resistance and reactance of a device in
percent or per-unit are usually available
from the manufacturer
The advantages of the per-unit system for
analysis are described as follow:
The per-unit system gives us a clear idea of relative
magnitudes of various quantities, such as voltage, current,
power and impedance.
The per-unit impedance of equipment of the same general
type based on their own ratings fall in a narrow range
regardless of the rating of the equipment. Whereas their
impedance in ohms vary greatly with the rating.
The per-unit values of impedance, voltage and current of a
transformer are the same regardless of whether they are
referred to the primary or the secondary side. This is the
great advantage since the different voltage levels disappear
and the entire system reduces to a system of simple
impedance.
The per-unit systems are ideal for the computerized analysis
and simulation of complex power system problems.
The circuit laws are valid in per-unit systems, and the power
and voltage equations as given by (1.5) and (1.6) are
simplified since the factors of 3 and are eliminated in the
per-unit system.
1.5.2. PER-UNIT IMPEDANCES IN SINGLE-
PHASE TRANSFORMER CIRCUIT.
For transformer:
If leakage reactance had been measured on the high-voltage side, the value would be
2
440
X = 0.06 = 0.96Ω
110
High-voltage base impedance:
0.440 2 x1000
X = = 77.5Ω
2.5
In per-unit
0.96
X = = 0.0124 per − unit
77.5
So, a great advantage in making per-unit computations
is realized by the proper selection of different bases for
circuits connected to each other through a transformer.
300Ω
A B C
A-B B-C
300 x 22 = 1200 Ω
300 x 22 x 0.12 = 12 Ω
12
= 0.63 per − unit
19
0.63+j0
Remember:
The kilovoltampere base should be the same in all parts of the system,
and the selection of the base kilovolts in one part of the system
determines the base kilovolts to be assigned,
according to the turns ratios of the transformers,
to the other parts of the system.
1.6. THE PER-UNIT SYSTEM IN
THREE-PHASE TRANSFORMERS
The possible connection of the three-
phase transformer is:
∆-Y
Y - ∆
Y – Y
∆ - ∆
The theory is the same for a three-phase transformer
as
for a three-phase bank of a single-phase transformer
Advantage of a three-phase transformer
then three single-phase transformers:
The three-phase unit has the advantage of
requiringless iron to form the core, and is
therefore more economical then three single-
phase units and occupies less space.
Advantage of three single-phase
transformers then a three-phase
transformer:
The three single-phase units have the
advantage of replacement of only one unit of
the three-phase bank in case of a failure
rather than losing the whole three-phase
bank.
The connection diagram of three-phase transformer:
.
A B C
H1 H2 H3
h1 h2 h3
a b c
.
jX IA=1.0
+ +
J0.10
VAN
Ia jX Ia IA=1.0
+ +
J0.10
VAN=1.0
VAN EAN
Further, since Vbase XL-N = 13.8/√3 = 7.967 kv for the low-voltage ∆ windings,
The criterion for the selection of base voltage involves the square
of the ratio of line-to-line voltages and not the square of the turns
ratio of the individual windings of the Y - ∆ transformer.
Conclusion:
1. To transfer the ohmic value of impedance
from the voltage level on one side of a three-
phase transformer to the voltage level on the
other, the multiplying factor is the square of
the ratio of line-to-line voltages regardless of
whether the transformer connection is Y – Y
or Y - ∆.
2. In per-unit calculations involving
transformers in three-phase circuits we
require the base voltages on the two sides of
the transformer to have the same ratio as
the rated line-to-line voltages on the two
sides of transformer. The kilovoltampere
base is the same on each side.
Example 1.6.2
Three transformers, each rated 25 MVA,
38.1/3.81 kV, are connected Y - ∆ with a
balanced load of three 0.6Ω, Y – connected
resistor. Choose a base of75 MVA, 66 kV for
the high-voltage side of the transformer and
specify the base for the low-voltage side.
Then, determine the load resistance RL in
ohms referred to the high-voltage side and
the per-unit value of this resistance on the
chosen base.
Solution:
Since √3x38.1 kV is equals 66 kV, the rating
of the transformer as the three-phase bank is
75 MVA, 66Y/3.81∆ kV. So, base for the low-
voltage side is 75 MVA, 3.81 kV.
By equation
By equation
(base voltage, kVL− L ) 2
. Base impedance =
baseMVA3φ
2
So, base impedance on the low-voltage side is:
( 3.81 )
= 0.1935Ω
75
0. 6
and on the low-voltage side RL = = 3.10 per − unit
0.1935
2
Base impedance on the high-voltage side is
( 66 )
= 58.1Ω
75
The resistance referred to the high-voltage side is
2
66
0.6 = 180Ω
3.81
180
RL = = 3.10 per − unit
58.1
1.7. PER-UNIT IMPEDANCES OF THE
THREE-WINDING TRANSFORMERS
Selection base:
E2
- I3
+
E1
+
E3
-
N1 -
N3
I1pu +
E2pu
E1pu I3pu
+
E3pu
- -
-
Fig 1.7.1 (c). Per-unit equivalent
circuit – ideal transformer
.
I2pu
I1pu
+
E2pu
E1pu I3pu
+
E3pu
- -
-
Note:
Two-winding transformer have the same
kilovoltampere rating for both the primary
and secondary windings, BUT all three
windings of a three-winding transformer may
have different kilovoltampere ratings.
The impedance of each winding of a three-
winding transformer may be given in percent
or per-unit based on the rating of its own
winding, or tests may be made to determine
the impedances.
In any case, all the per-unit impedances
must be expressed on the same
kilovoltampere base
Three single-phase transformer ≠ Three-
phase transformer
Three-phase transformer ≠ Three-winding
transformer
Three impedances may be measured by the
standard short-circuit test, as follows:
Zps leakage impedance measured in
primary with secondary short-circuited
and tertiary open
Zpt leakage impedance measured in
primary with tertiary short-circuited and
open secondary
Zst leakage impedance measured in
secondary with tertiary short-circuited
and primary open
The impedances of each separate winding
Zps = Zp + Zs
Zpt = Zp + Zt
Zst = zs + Zt
Where:
Zp = impedance of the primary winding
Zs = impedance of the secondary winding
Zt = impedance of the tertiary winding
The Zp, Zs and Zt:
.
1
Z p = (Z ps + Z pt − Z st )
2
1
Z s = (Z ps + Z st − Z st )
2
1
Z t = (Z pt + Z st − Z ps )
2
Example 1.7.1
A constant voltage source (infinite bus) supplies a
purely resistive 5MW, 2.3kV three-phase load and a
7.5MVA, 13.2 kV synchronous motor having a
subtransient reactance of X” = 20%. The source is
connected to the primary of the three-winding
transformer described in Fig 1.9. The motor and the
resistive load are connected to the secondary and
tertiary of the transformer. Draw the impedance
diagram of the system and mark the per-unit
impedances for a base of 66kV, 15 MVA in the
primary. Neglect exciting current and all resistance
except that the resistive load.
Solution
The constant-voltage source can be represented by a
generator having no internal impedance.
The resistance of the load is 1.0 pu on a base of 5
MVA, 2.3kV in the tertiary. Expressed on a 15 MVA,
2.3 kV base, the load resistance is:
The load resistance is:
. R = 1. 0 x
15
= 3.0 pu
5
J0.05
J0.02 J0.40
15
+ X " = 0.20 = 0.40 pu
Eأل J0.07
+ 7.5
Em
3.0
-
- Fig.1.7.2. Impedance diagram for example 1.7.1
T1 T2
G1
L
2
M3
Data system
Component MVA KV R X
.
Generator 30 13.8 0.1 per-unit Xs = 1.0 per-unit