E - RPC .MD UNI
E - RPC .MD UNI
MD-UNI
time relays
RPC-1MD-UNI RPC-3MD-UNI
• Immediate activation of the selected function
- without having to temporarily turn off the power supply
General data
Electrical life • resistive AC1 > 0,5 x 105 16 A, 8 A, 250 V AC
Mechanical life (cycles) > 3 x 107
Dimensions (L x W x H) 90 ¸ x 17,5 x 64,6 mm
Weight contact 1 CO: 65 g contacts 3 CO: 88 g
Ambient temperature • storage -40...+70 oC
(non-condensation and/or icing) • operating -20...+50 oC
Cover protection category IP 20 EN 60529
Relative humidity up to 85%
Shock / vibration resistance 15 g / 0,35 mm DA 10...55 Hz
Time module data
Functions E, Wu, Bp, Bi, R, Ws, Wa, Esa, B, T
Time ranges OFF - permanent switching off; ON - permanent switching on
1 s ¹; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment smooth - (0,1...1) x time range (does not refer to range ON / OFF)
Setting accuracy / Repeatability ± 5% º ¹ / ± 0,5% ¹
Values affecting the timing adjustment temperature: ± 0,05% / °C supply voltage: ± 0,01% / V
Recovery time AC: ≤ 400 ms DC: ≤ 150 ms
28.12.2023
www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays
Time functions
E - ON delay. Ws - Single shot for the set interval triggered by closing of the control
contact S.
On applying the supply voltage U the set interval T begins - off-delay The input of the time relay is supplied with voltage U continuously.
of the output relay R. After the interval T has lapsed, the output relay R Closing of the control contact S immediately switches the output relay R
switches on and remains on until supply voltage U is interrupted. on for the set interval T. After the interval T has lapsed, the output relay R
is switched off. In the course of the interval T, any opening of the control
Wu - ON for the set interval. contact S does not affect the function to be performed. The output relay
R may be switched on again for the set interval, after the interval T has
lapsed, by closing the control contact S again.
Bp - Symmetrical cyclical operation pause first. The input of the time relay is supplied with voltage U continuously.
Closing of the control contact S does not start the interval T, and it does
not change the position of the output relay R. Opening of the control
contact S immediately switches on the output relay R for the set time.
After the interval T has lapsed, the output relay R switches off. Opening
and closing of the control contact S in the course of the interval T does
not affect the function to be performed. The output relay R may be swit-
ched on again for the set interval with another closing and opening of the
Applying the supply voltage U starts the cyclical operation from the control contact S.
interval T - switching the output relay R off followed by switching on the
output relay R for the interval T. The cyclical operation lasts until the Esa - ON and OFF delay with the control contact S.
supply voltage U is interrupted.
www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays
Time functions
B - Cyclical operation controlled with closing of the control contact S. T - Generation of the 0,5 s pulse after the interval T.
The input of the time relay is supplied with U voltage continuously. Applying the supply voltage U starts the interval T. After the interval T has
Closing of the control contact S immediately switches on the output relay R. lapsed, the output relay switches on for 0,5 s (the time of the NO contact
Each next closing of the control contact S results in a change of the status of the output relay).
of the output relay R to an opposite one (the feature of a bistable relay).
ON / OFF - Permanent switching on / off.
The functions ON and OFF are selected with T time range adjusting knob.
In the ON function, the normally open contacts are closed all the time
whereas in the OFF function they are open. The position of the function
-adjusting knob is of no significance in these functions as is the preset
U - supply voltage; R - output state of the relay; S - control contact state; measurement time. The ON or OFF functions are used for the time relay
T - measured time; t - time axis operation control in electric systems.
Additional functions
Supply diode: it is lit permanently when the time is not being measured. Triggering: depending on the function to be performed, the relay is trig-
In course of the T time measurement, it flashes at 500 ms period where gered with the supply voltage or by connection of the S contact to the A1
it is lit for 50% of the time, and off for 50% of the time. line. For DC supply, the positive pole must be connected to the A1 line.
The level of the S contact activation is adjusted automatically depending
Adjustment of the set values: on the supply voltage.
- the values of time and range are read in the course of the relay’s
operation. The set values may be modified at any moment, Supply: the relay may be supplied with DC voltage or AC voltage
- it is possible to change the function during operation of the relay, which 48...63 Hz of 10,8...264 V.
results in triggering operation with a new setting. It is not necessary
to switch the supply off and on again for the relay to start operating with
a new setting.
Dimensions
1 CO 3 CO
64,6
17,5
3,5 44
10
24
55,4
78,1
98,8
35,4
90
45
28.12.2023
PRECAUTIONS:
1. Ensure that the parameters of the product described in its specification provide a safety margin for the appropriate operation of the device or system and never use
the product in circumstances which exceed the parameters of the product. 2. Never touch any live parts of the device. 3. Ensure that the product has been connected
correctly. An incorrect connection may cause malfunction, excessive heating or risk of fire. 4. In case of any risk of any serious material loss or death or injuries
of humans or animals, the devices or systems shall be designed so to equip them with double safety system to guarantee their reliable operation.
www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays
S ¶ S ¶
18 18
Yellow LED 15 15
Function-adjusting 16 16
knob
28
25
26
Time range
and function ON / OFF 38
adjusting knob 35
36
Time-adjusting
knob 1 CO 3 CO
Mounting
Relays RPC-.MD-UNI are designed for direct mounting on 35 mm rail mount acc. to EN 60715. Operational
position - any. Connections: max. cross section of the cables: 1 x 2,5 mm2 (1 x 14 AWG), stripping length: 6,5 mm,
max. tightening moment for the terminal: 0,5 Nm.
Ordering codes
R P C M D U N I
Number and type of contacts Rated input voltage
MD - multifunction
width 17,5 mm, one changeover contact, contact material AgSnO2, rated input voltage
12...240 V AC/DC AC: 50/60 Hz
RPC-3MD-UNI time relay RPC-.MD-UNI, multifunction (relay perform 10 functions), cover - modular,
width 17,5 mm, three changeover contacts, contact material AgSnO2, rated input voltage
12...240 V AC/DC AC: 50/60 Hz