E - RPC .MD UNI

The RPC-.MD-UNI time relays are multifunctional devices that offer 10 time functions and 8 time ranges, designed for low-voltage systems with AC/DC input voltages. They feature cadmium-free contacts, modular covers, and are compliant with EN 61812-1 and RoHS standards. The relays can be directly mounted on a 35 mm rail and have various operational capabilities, including ON delay, OFF delay, and cyclical operations.

Uploaded by

m.azarutheen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views4 pages

E - RPC .MD UNI

The RPC-.MD-UNI time relays are multifunctional devices that offer 10 time functions and 8 time ranges, designed for low-voltage systems with AC/DC input voltages. They feature cadmium-free contacts, modular covers, and are compliant with EN 61812-1 and RoHS standards. The relays can be directly mounted on a 35 mm rail and have various operational capabilities, including ON delay, OFF delay, and cyclical operations.

Uploaded by

m.azarutheen
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

RPC-.

MD-UNI
time relays
RPC-1MD-UNI RPC-3MD-UNI
• Immediate activation of the selected function
- without having to temporarily turn off the power supply

• Multifunction time relays (10 time functions; 8 time ranges)


• Cadmium - free contacts 1 CO and 3 CO • AC/DC input voltages
• Cover - modular, width 17,5 mm • Direct mounting on 35 mm rail mount
acc. to EN 60715 • Applications: in low-voltage systems
• Compliance with standard EN 61812-1
• Recognitions, certifications, directives: RoHS,
Output circuit - contact data
Number and type of contacts 1 CO 3 CO
Contact material AgSnO2
Max. switching voltage 300 V AC
Rated load AC1 16 A / 250 V AC 8 A / 250 V AC
DC1 16 A / 24 V DC 8 A / 24 V DC
DC1 0,3 A / 250 V DC 0,2 A / 250 V DC
Rated current 16 A / 250 V AC 8 A / 250 V AC
Max. breaking capacity AC1 4 000 VA 2 000 VA
Min. breaking capacity 1 W 10 mA
Contact resistance ≤ 100 mΩ
Max. operating frequency 600 cycles/hour at rated load AC1
Input circuit
Rated voltage AC: 50/60 Hz AC/DC 12...240 V terminals (+)A1, (-)A2
Must release voltage ≥ 0,1 Un
Operating range of supply voltage 0,9...1,1 Un
Rated power consumption DC ≤ 1,5 W
Range of supply frequency AC 48...63 Hz
Control contact S ¶ • min. voltage · 0,7 Un
• min. time of pulse duration · AC: ≥ 50 ms DC: ≥ 30 ms
• max. length of control line 10 m
Insulation according to EN 60664-1
Insulation rated voltage 250 V AC
Rated surge voltage 4 000 V 1,2 / 50 µs
Overvoltage category III
Insulation pollution degree 2
Flammability class V-0 for modular cover, UL 94
Dielectric strength • input - output 4 000 V AC type of insulation: basic
• contact clearance 1 000 V AC type of clearance: micro-disconnection
• pole - pole 2 000 V AC contacts 3 CO, type of insulation: basic

General data
Electrical life • resistive AC1 > 0,5 x 105 16 A, 8 A, 250 V AC
Mechanical life (cycles) > 3 x 107
Dimensions (L x W x H) 90 ¸ x 17,5 x 64,6 mm
Weight contact 1 CO: 65 g contacts 3 CO: 88 g
Ambient temperature • storage -40...+70 oC
(non-condensation and/or icing) • operating -20...+50 oC
Cover protection category IP 20 EN 60529
Relative humidity up to 85%
Shock / vibration resistance 15 g / 0,35 mm DA 10...55 Hz
Time module data
Functions E, Wu, Bp, Bi, R, Ws, Wa, Esa, B, T
Time ranges OFF - permanent switching off; ON - permanent switching on
1 s ¹; 10 s; 1 min.; 10 min.; 1 h; 10 h; 1 d; 10 d
Timing adjustment smooth - (0,1...1) x time range (does not refer to range ON / OFF)
Setting accuracy / Repeatability ± 5% º ¹ / ± 0,5% ¹
Values affecting the timing adjustment temperature: ± 0,05% / °C supply voltage: ± 0,01% / V
Recovery time AC: ≤ 400 ms DC: ≤ 150 ms
28.12.2023

LED indicator green LED U ON - indication of supply voltage U


green LED U flashing - measurement of T time
yellow LED R ON/OFF - output relay status
¶ The control terminal S is activated by connection to A1 terminal via the external control contact S. · Where the control signal is recognizable.
¸ Length with 35 mm rail catches: 98,8 mm. ¹ For first range setpoint (1 s) setting accuracy and repeatability are smaller than the given ones in
technical parameters (significant influence of the operational relay operating time, processor start-time, and the moment of supply switching as referred
to the AC supply course). º Calculated from the final range values, for the setting direction from minimum to maximum.
1

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays

Time functions

E - ON delay. Ws - Single shot for the set interval triggered by closing of the control
contact S.

On applying the supply voltage U the set interval T begins - off-delay The input of the time relay is supplied with voltage U continuously.
of the output relay R. After the interval T has lapsed, the output relay R Closing of the control contact S immediately switches the output relay R
switches on and remains on until supply voltage U is interrupted. on for the set interval T. After the interval T has lapsed, the output relay R
is switched off. In the course of the interval T, any opening of the control
Wu - ON for the set interval. contact S does not affect the function to be performed. The output relay
R may be switched on again for the set interval, after the interval T has
lapsed, by closing the control contact S again.

Wa - ON for the set interval triggered with the control contact S.

Applying the supply voltage U immediately switches the output relay R


on for the set interval T. After the interval T has lapsed, the output relay
R switches off.

Bp - Symmetrical cyclical operation pause first. The input of the time relay is supplied with voltage U continuously.
Closing of the control contact S does not start the interval T, and it does
not change the position of the output relay R. Opening of the control
contact S immediately switches on the output relay R for the set time.
After the interval T has lapsed, the output relay R switches off. Opening
and closing of the control contact S in the course of the interval T does
not affect the function to be performed. The output relay R may be swit-
ched on again for the set interval with another closing and opening of the
Applying the supply voltage U starts the cyclical operation from the control contact S.
interval T - switching the output relay R off followed by switching on the
output relay R for the interval T. The cyclical operation lasts until the Esa - ON and OFF delay with the control contact S.
supply voltage U is interrupted.

Bi - Symmetrical cyclical operation pulse first.

The input of the time relay is supplied with voltage U continuously.


Closing of the control contact S starts the interval T - on-delay of the
output relay R. After the interval T has lapsed, the output relay R swit-
Applying the supply voltage U starts the cyclical operation from switching ches on. Opening of the control contact S begins further measurement of
on the output relay R for the set interval T. After the interval T has lapsed, the interval T - off-delay of the output relay R, and after the interval has
the output relay R switches off for the interval T. The cyclical operation lapsed, the output relay switches off. In case the time for which the con-
lasts until the supply voltage U is interrupted. trol contact S is closed in the course of measurement of the on-delay of
the output relay R is shorter than the set interval T, the output relay R
R - OFF delay with the control contact S. will switch on after the set interval T, and the output relay R will remain in
on position for the interval T. When the output relay R is in on position,
closing of the control contact S does not affect the function to be
performed.

The input of the time relay is supplied with voltage U continuously.


Closing of the control contact S immediately switches on the output relay
R. Opening of the control contact S starts the set time of the delayed
switching off of the output relay R. After the interval T has lapsed, the output
relay R switches off. If the control contact S is closed during the interval
T, the already measured time is reset, and the output relay R is switched
on again. The OFF delay of the output relay R will start when the control U - supply voltage; R - output state of the relay; S - control contact state;
contact S is opened again. T - measured time; t - time axis
28.12.2023

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays

Time functions

B - Cyclical operation controlled with closing of the control contact S. T - Generation of the 0,5 s pulse after the interval T.

The input of the time relay is supplied with U voltage continuously. Applying the supply voltage U starts the interval T. After the interval T has
Closing of the control contact S immediately switches on the output relay R. lapsed, the output relay switches on for 0,5 s (the time of the NO contact
Each next closing of the control contact S results in a change of the status of the output relay).
of the output relay R to an opposite one (the feature of a bistable relay).
ON / OFF - Permanent switching on / off.
The functions ON and OFF are selected with T time range adjusting knob.
In the ON function, the normally open contacts are closed all the time
whereas in the OFF function they are open. The position of the function
-adjusting knob is of no significance in these functions as is the preset
U - supply voltage; R - output state of the relay; S - control contact state; measurement time. The ON or OFF functions are used for the time relay
T - measured time; t - time axis operation control in electric systems.

Additional functions

Supply diode: it is lit permanently when the time is not being measured. Triggering: depending on the function to be performed, the relay is trig-
In course of the T time measu­rement, it flashes at 500 ms period where gered with the supply voltage or by connection of the S contact to the A1
it is lit for 50% of the time, and off for 50% of the time. line. For DC supply, the positive pole must be connected to the A1 line.
The level of the S contact activation is adjusted automatically depending
Adjustment of the set values: on the supply voltage.
- the values of time and range are read in the course of the relay’s
operation. The set values may be modified at any moment, Supply: the relay may be supplied with DC voltage or AC voltage
- it is possible to change the function during operation of the relay, which 48...63 Hz of 10,8...264 V.
results in triggering operation with a new setting. It is not necessary
to switch the supply off and on again for the relay to start operating with
a new setting.

Dimensions

1 CO 3 CO
64,6
17,5
3,5 44
10
24
55,4
78,1

98,8

35,4
90

45

28.12.2023

PRECAUTIONS:
1. Ensure that the parameters of the product described in its specification provide a safety margin for the appropriate operation of the device or system and never use
the product in circumstances which exceed the parameters of the product. 2. Never touch any live parts of the device. 3. Ensure that the product has been connected
correctly. An incorrect connection may cause malfunction, excessive heating or risk of fire. 4. In case of any risk of any serious material loss or death or injuries
of humans or animals, the devices or systems shall be designed so to equip them with double safety system to guarantee their reliable operation.

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]
RPC-.MD-UNI
time relays

Front panel description Connection diagrams

S ¶ S ¶

Green LED (+)A1 A2(-) (+)A1 A2(-)

18 18
Yellow LED 15 15
Function-adjusting 16 16
knob
28
25
26
Time range
and function ON / OFF 38
adjusting knob 35
36
Time-adjusting
knob 1 CO 3 CO

¶ The control terminal S is activated by connection to A1 terminal via the


external control contact S.

Mounting

Relays RPC-.MD-UNI are designed for direct mounting on 35 mm rail mount acc. to EN 60715. Operational
position - any. Connections: max. cross section of the cables: 1 x 2,5 mm2 (1 x 14 AWG), stripping length: 6,5 mm,
max. tightening moment for the terminal: 0,5 Nm.

Two catches: Mounting wires


easy mounting in clamps:
on 35 mm rail, universal screw
firm hold (cross-recessed
(top and bottom). or slotted head).

Ordering codes

Type Number and type Time functions Rated input voltage


of contacts performed

R P C M D U N I
Number and type of contacts Rated input voltage

1 - 1 CO UNI - 12...240 V AC/DC AC: 50/60 Hz


3 - 3 CO

Time functions performed

MD - multifunction

Examples of ordering codes:


RPC-1MD-UNI time relay RPC-.MD-UNI, multifunction (relay perform 10 functions), cover - modular,
28.12.2023

width 17,5 mm, one changeover contact, contact material AgSnO2, rated input voltage
12...240 V AC/DC AC: 50/60 Hz
RPC-3MD-UNI time relay RPC-.MD-UNI, multifunction (relay perform 10 functions), cover - modular,
width 17,5 mm, three changeover contacts, contact material AgSnO2, rated input voltage
12...240 V AC/DC AC: 50/60 Hz
4

www.relpol.com.pl Export Sales Department phone +48 68 47 90 832, 951 • e-mail: [email protected]