The KIDDE® Control Relay Modules (GSA-CR, GSA-MCR, GSA-CRR, GSA-MCRR) are intelligent analog addressable devices designed for use with VS & VM control systems to control external appliances and activate sounder bases. They feature a Form 'C' dry relay contact, automatic device mapping, and electronic addressing for easy installation and maintenance. The modules are compatible with Kidde's Signature Series and meet various agency listings, ensuring reliability in fire alarm systems.

Uploaded by

scramirez1983
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2 views

Modulo Control-Relay

The KIDDE® Control Relay Modules (GSA-CR, GSA-MCR, GSA-CRR, GSA-MCRR) are intelligent analog addressable devices designed for use with VS & VM control systems to control external appliances and activate sounder bases. They feature a Form 'C' dry relay contact, automatic device mapping, and electronic addressing for easy installation and maintenance. The modules are compatible with Kidde's Signature Series and meet various agency listings, ensuring reliability in fire alarm systems.

Uploaded by

scramirez1983
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

KIDDE® Catalog u Intelligent Input/Output

Compatible with VS & VM control systems

Technology that saves lives

Control Relay
Modules
GSA-CR, GSA-MCR, GSA-CRR,
GSA-MCRR
7300-1483:
GSA-CR 0115

GSA-MCR

S3424

Overview Standard Features


The Control Relay Module and the Polarity Reversal Relay Module • Provides one no/nc contact (GSA-CR/MCR)
are part of the Signature Series system. They are intelligent analog Form “C” dry relay contact can be used to control external
addressable devices available in either plug-in (UIO) versions, or appliances such as door closers, fans, dampers etc.
standard 1-gang mount versions. • Allows group operation of sounder bases
The GSA-CR/MCR Control Relay Module provides a Form The GSA-CRR/MCRR reverses the polarity of its 24 Vdc
“C” dry relay contact to control external appliances such as output, thus activating all Sounder Bases on the data loop.
door closers, fans, dampers etc. This device does not provide • Plug-in (UIO) or standard 1-gang mount
supervision of the state of the relay contact. Instead, the on-board UIO versions allow quick installation where multiple modules
microprocessor ensures that the relay is in the proper ON/OFF are required. The 1-gang mount version is ideal for remote
state. Upon command from the loop controller, the GSA-CR/MCR locations that require a single module.
relay activates the normally open or normally-closed contact. • Automatic device mapping
The GSA-CRR/MCRR Polarity Reversal Relay Module provides Signature modules transmit information to the loop controller
a Form “C” dry relay contact to power and activate a series of regarding their circuit locations with respect to other Signature
GSA-AB4G Audible Sounder Bases. Upon command from the devices on the wire loop.
Signature loop controller, the GSA-CRR reverses the polarity of its • Electronic addressing
24 Vdc output, thus activating all Sounder Bases on the data loop. Programmable addresses are downloaded from the loop
Standard-mount versions (GSA-CR and GSA-CRR) are controller, a PC, or the SIGA-PRO Signature Program/Service
installed to standard North American 1-gang electrical boxes, Tool; there are no switches or dials to set.
making them ideal for locations where only one module is • Intelligent device with microprocessor
required. Separate I/O and data loop connections are made to All decisions are made at the module to allow lower
each module. communication speed with substantially improved control panel
response time and less sensitivity to line noise and loop wiring
Plug-in UIO versions (GSA-MCR and GSA-MCRR) are part of
properties; twisted or shielded wire is not required.
the UIO family of plug-in Signature Series modules. They function
identically to the standard mount versions, but take advantage • Ground fault detection by address
of the modular flexibility and easy installation that characterizes Detects ground faults right down to the device level.
all UIO modules. Two- and six-module UIO motherboards are
available. All wiring connections are made to terminal blocks on
the motherboard. UIO assemblies may be mounted in Kidde
enclosures.

Page 1 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1
Installation Application
GSA-CR and GSA-CRR: modules mount to North American 2½ The operation of Signature Series control relays is determined by
inch (64 mm) deep 1-gang boxes and 1½ inch (38 mm) deep 4 their sub-type code or “Personality Code.”
inch square boxes with 1-gang covers and GSA-MP mounting
Personality Code 8: CONTROL RELAY (GSA-CR/MCR) -
plates. The terminals are suited for #12 to #18 AWG (2.5 mm2 to
Dry Contact Output. This setting configures the module to
0.75 mm2) wire size.
provide one Form “C” DRY RELAY CONTACT to control Door
Closers, Fans, Dampers, etc. Contact rating is 2.0 amp @
Compatible electrical box 24 Vdc; 0.5 amp @ 120 Vac (or 0.25A @ 220 Vac for non-UL
applications). Personality Code 8 is assigned at the factory. No
user configuration is required.
Personality Code 8: POLARITY REVERSAL RELAY MODULE
(GSA-CRR/MCRR). This setting configures the module to reverse
Wall plate, white the polarity of its 24 Vdc output. Contact rating is 2.0 amp @ 24
(1-gang)
Vdc (pilot duty). Personality Code 8 is assigned at the factory. No
user configuration is required.

M
Compatibility
ALAR
FIRE DULE
MO
These modules are part of Kidde’s Signature Series intelligent
Status LEDs
processing and control platform. They are compatible with VM,
and VS Series control panels.
LED viewing ports

Warnings & Cautions


This module will not operate without electrical power. As fires
GSA-MCR and GSA-MCRR: mount the UIO motherboard inside frequently cause power interruption, we suggest you discuss
a suitable Kidde enclosure with screws and washers provided. further safeguards with your local fire protection specialist.
Plug the module into any available position on the motherboard
and secure the module to the motherboard with the captive
screws. Wiring connections are made to the terminals on the
motherboard (see wiring diagram). UIO motherboard terminals Testing & Maintenance
are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. The module’s automatic self-diagnosis identifies when it is
defective and causes a trouble message. The user-friendly
maintenance program shows the current state of each module
UIO Motherboard and other pertinent messages. Single modules may be turned
off (deactivated) temporarily, from the control panel. Availability of
maintenance features is dependent on the fire alarm system used.
Scheduled maintenance (Regular or Selected) for proper system
Plug-in (UIO) operation should be planned to meet the requirements of the
Module Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ULC 536 standards.

Electronic Addressing - The loop controller electronically


addresses each module, saving valuable time during system
commissioning. Setting complicated switches or dials is not
required. Each module has its own unique serial number stored
in its on-board memory. The loop controller identifies each device
on the loop and assigns a “soft” address to each serial number.
If desired, the modules can be addressed using the SIGA-PRO
Signature Program/Service Tool.
Kidde recommends that this module be installed according to
latest recognized edition of national and local fire alarm codes.

Page 2 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1
Typical Wiring
Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.5mm2) wire sizes.
Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog
sheet for detailed wiring requirement specifications.

Notes
1 Refer to Signature Loop Controller Installation
Sheet for wiring specifications.
2 NFPA 72 requires that the GSA-CR/GSA-MCR
be installed in the same room as the device it is
controlling. This requirement may not apply in all
markets. Check with your local AHJ for details.
3 The GSA-UIO6R and the GSA-UIO2R do not come
with TB14.
GSA-CR Control Relay
4 The GSA-UIO6 does not come with TB8 through
TB13.
5 Supervised and power-limited.
Normally Open Common Normally Closed
6 If the source is nonpower-limited, maintain a
space of 1/4 inch from power-limited wiring or use
FPL, FPLP, FPLR, or an equivalent in accordance
with the National Electrical Code.
2 7) Maximum #12 AWG (2.5mm2) wire.
1 23 4 Min. #18 (0.75mm2).
1
Data In
3
4 4
3 3
2 2
1 1
TB7 TB14
No connections required for
Data Out MCR. Other modules may
require connections.
473387358
CAT NO.
MCR

4
3
2
Green LED (Normal) 1
Red LED (Active) TB15

1 23 4
4
No connections required for
MCR. Other modules may
require connections.

GSA-MCR Control Relay

Page 3 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1
Typical Wiring
Modules will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG (1.50mm2) and #12 AWG (2.50mm2) wire sizes.
Note: Sizes #16 AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease of installation. See Signature Loop Controller catalog
sheet for detailed wiring requirement specifications.

AB4G AB4G AB4G


Audible Base Audible Base Audible Base
6254A-003
EOL Relay

Listed 24 VDC + 1
Nominal Power 2
Supply
- 1
2 2 2
2

1 2

3 3

CT1
CR CRR 3
GSA-CRR

Signature +
DATA

Controller
- 3
3 Optional CR
for disabling/disconnecting
sounder base
GSA-MCRR
GSA-CRR Schematic GSA-MCRR Schematic

DATA (+) IN/OUT


Power In Power Out
Polarity reverses 6254A-003

DATA (-) OUT


when activated. EOL Relay

11
1
DATA (-) IN
Audible required for

10
2
Bases supevision

SIG +
SIG -

9
4

8
7
6
5
7 8 7
Signature
Notes Data Data Out
Circuit
1 Refer to the Signature controller installation sheet For normal operation CT1
for wiring. 8
For General Fire
Alarm Operation
2 One Pair of Wires (24 Vdc power). UL/ULC Listed 4 3 2 1
24 Vdc power
3 One Pair of Wires (Signature Data). supply or

4 Single Wire (24 Vdc power). 1 23 4 1 23 4


5 The GSA-UIO6R and the GSA-UIO2R do not come MCRR
with TB14. 7 1 UIO(R) series motherboard
Data Out 4
6 The GSA-UIO6 does not come with TB8 through TB13. 3
2
7 Supervised and power-limited. 4 1 No connections required for
Signature 5
3 TB14 MCRR. Other modules may
Data
8 If the source is nonpower-limited, maintain a space Circuit
2 require connections.
1
of 1/4 inch from power-limited wiring or use FPL, TB7
473387360

473387359

FPLP, FPLR, or an equivalent in accordance with


CAT NO.

CAT NO.

Data In
MCRR

MCRR

the National Electrical Code. 4 Green LED (Normal)


3 Red LED (Active)
9 Maximum #12 AWG (2.5 mm² ) wire; Minimum 2
#18 AWG (0.75 mm² ). 1 No connections required for
TB15
10 End-of-Line Relay must monitor and report power Green LED (Normal) MCRR. Other modules may
Red LED (Active) 1 23 4 1 23 4 require connections.
supply trouble to control panel.
11 Class B Data wiring may be “T-tapped.” 6 6
Optional MCRR
or MCR for
No connections required for MCRR. Other
disabling/disconnecting
an audible base. modules may require connections.

Page 4 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1
Specifications
Catalog Number GSA-CR GSA-MCR GSA-CRR GSA-MCRR
Description Control Relay Polarity Reversal Relay
Type Code Personality Code 8 (Factory Set) Personality Code 8 (Factory Set)
Address Requirements Uses 1 Module Address
Operating Current Standby = 75 µA Activated = 75 µA
Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Relay Type and Rating Form C, 2 Amps @ 24 Vdc (pilot duty), 0.5 Amps @ 120 Vac and 0.25 Amps @ 220 Vac (220 Vac is non-UL).
Not rated for capacitive loads.
Mounting North American 2½ inch Plugs into UIO2R, UIO6R or North American 2½ inch Plugs into UIO2R, UIO6R or
(64 mm) deep 1-gang boxes UIO6 Motherboards (64 mm) deep 1-gang boxes UIO6 Motherboards
and 1½ inch (38 mm) deep and 1½ inch (38 mm) deep
4 inch square boxes with 4 inch square boxes with
1-gang covers and GSA-MP 1-gang covers and GSA-MP
mounting plates mounting plates
Construction & Finish High Impact Engineering Polymer
Storage and Operating Operating Temperature: 32°F to 120°F (0°C to 49°C)
Environment Storage Temperature: -4°F to 140°F (-20°C to 60°C) Humidity: 0 to 93% RH
LED Operation On-board Green LED - Flashes when polled On-board Red LED - Flashes when in alarm/active
Compatibility Use With: Signature Loop Controller
Agency Listings UL, ULC, CSFM, MEA

Ordering Information
Ship Weight - lbs
Catalog Number Description
(kg)
GSA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
GSA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
GSA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
GSA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)

Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1 (0.6)
GSA-UIO2R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
GSA-UIO6R Universal Input-Output Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
GSA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
GSA-AB4G Audible (Sounder) Detector Base 0.3 (0.15)

Accessories
MFC-A Multifunction Fire Cabinet - Red, supports Signature Module Mounting Plates 7.0 (3.1)
GSA-MB4 Transponder Mounting Bracket (allows for mounting two 1-gang modules in a 2-gang box) 0.4 (0.15)
GSA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
GSA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
GSA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)

Page 5 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1
Signature Series Overview
The Signature Series intelligent analog-addressable system from Kidde is an entire
family of multi-sensor detectors and mounting bases, multiple-function input and output
modules, network and non-network control panels, and user-friendly maintenance and
service tools. Analog information from equipment connected to Signature devices is
gathered and converted into digital signals. An onboard microprocessor in each Signature
Technology that saves lives device measures and analyzes the signal and decides whether or not to input an alarm.
The microprocessor in each Signature device provides four additional benefits – Self-
Contact us diagnostics and History Log, Automatic Device Mapping, Stand-alone Operation and
Phone: 888.244.9979 (Option 4) Fast, Stable Communication.
Email: [email protected]
Website: kidde-esfire.com Self-diagnostics and History Log – Each Signature Series device constantly runs self-
checks to provide important maintenance information. The results of the self-check are
Kidde is a Carrier brand.
8985 Town Center Pkwy, automatically updated and permanently stored in its non-volatile memory. This information
Bradenton, FL 34202 is accessible for review any time at the control panel, PC, or using the SIGA-PRO
Signature Program/Service Tool. The information stored in device memory includes:
© 2020 Carrier
All rights reserved.
• Device serial number, address, and type
• Time and date of last alarm
• Most recent trouble code logged by the detector — 32 possible trouble codes may be
used to diagnose faults.
Automatic Device Mapping –The Signature Data Controller (SDC) learns where each
device’s serial number address is installed relative to other devices on the circuit. The
SDC keeps a map of all Signature Series devices connected to it. The Signature Series
Data Entry Program also uses the mapping feature. With interactive menus and graphic
support, the wired circuits between each device can be examined. Layout or “as-built”
drawing information showing branch wiring (T-taps), device types and their address are
stored on disk for printing hard copy. This takes the mystery out of the installation. The
preparation of as-built drawings is fast and efficient.
Device mapping allows the Signature Data Controller to discover:
• Unexpected additional device addresses
• Missing device addresses
• Changes to the wiring in the circuit.
Most Signature modules use a personality code selected by the installer to determine
their actual function. Personality codes are downloaded from the SDC during system
configuration and are indicated during device mapping.
Standalone Operation – A decentralized alarm decision by the device is guaranteed.
Onboard intelligence permits the device to operate in standalone (degrade) mode.
If Signature loop controller CPU communications fail for more than four seconds, all
devices on that circuit go into standalone mode. The circuit acts like a conventional alarm
receiving circuit. Each Signature device on the circuit continues to collect and analyze
information from its slave devices. When connected to a panel utilizing standalone op-
eration, modules with their “personality” set as alarm devices (IDC) will alarm should their
slave alarm-initiating device activate.
03-27-20

Page 6 of 6 D ATA S H E E T K85001-0239


Not to be used for installation purposes. Issue 1.1