4.1 Cascade Control
4.1 Cascade Control
design.
◼ The feedback controller acts only after the process feels the upset. It
therefore can never yield perfect control where the controlled variable
does not deviate from the set point during load or set point changes.
◼ PID controller does not always provide the best possible control for all
processes especially for processes with large dead times and/or cascade
compensate
5 April 2021 for the effects 15U602
of known or measurable
Process Control disturbances. 3
Possible configurations
◼ The dynamics of the secondary loop are much faster than those of
the primary loop. This allows the use of higher gains in the
secondary controller to suppress more effectively the effect of the
disturbance occurring in the secondary loop without affecting the
stability of the system.
Let
In conventional feedback
This means that the inner loop has a time constant of 0.1
minute
The characteristic equation of the overall system is