The document details the programmable logic and opto input mappings for the MiCOM P543 device, including various trip outputs and alarm indications. It outlines the configuration of input and output contacts, as well as the associated data block (DDB) numbers for each function. Additionally, it includes information on external trips and fault recording mechanisms within the system.

Uploaded by

Edna Mekp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
11 views14 pages

000 Ele THX Example

The document details the programmable logic and opto input mappings for the MiCOM P543 device, including various trip outputs and alarm indications. It outlines the configuration of input and output contacts, as well as the associated data block (DDB) numbers for each function. Additionally, it includes information on external trips and fault recording mechanisms within the system.

Uploaded by

Edna Mekp
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 14

MiCOM P543 Programmable Logic

Opto Input Mappings Auto Close


DDB #854
L1 L5 L5 Q0 CLOSE COM
DDB #036

L2
L2 L2 VTC FAIL MCB/VTS
DDB #033 DDB #438
L11 L11 SF6 Block
DDB #042
L3
L3 L3 EXT TRIP CBF
DDB #034
External Trip3ph
DDB #534 L3 L3 EXT TRIP CBF
DDB #034
Trip 3ph
1 S

DDB #526
L4
L7 L7 Q0 close pos CB Aux 3ph(52-A)
DDB #038 DDB #420 L1 L1 RESET
DDB #032

L8 L8 Q0 open pos CB Aux 3ph(52-B) 1000


1
DDB #039 DDB #424 Q0springcharged
L9
DDB #040
Pick
L13 L13 Diff block Inhibit C Diff
DDB #044 DDB #455
External Trips:
Initiate Any Trip
DDB #522
Block Zone 1 Gnd Autoreclose
DDB #384
Block Zone 1 Phs
DDB #385
(if enabled).
Trip 3ph
DDB #526 1
Block Zone 2 Gnd
CBF initiation L3 L3 EXT TRIP CBF
DDB #034
L14 dist block
DDB #386 is segregated
L14
DDB #045
1 Block Zone 2 Phs
DDB #387
VTS Fast Block Block Zone 3 Gnd
DDB #832 DDB #388 Trip 3ph
DDB #526
Block Zone 3 Phs
DDB #389 CBfail1 Trip 3ph
DDB #834
Block Zone P Gnd
DDB #390
Block Zone P Phs
DDB #391
Block Zone 4 Gnd
DDB #392
Block Zone 4 Phs L15 TC1
DDB #393 L15
DDB #046

L8 Q0 open pos
&
L8
DDB #039

L16 L16 TC2


DDB #047
&
L6 L6 Q0 OPEN COM Init Trip CB L12 drive unit fail
DDB #037 DDB #439 DDB #043

L10 L10 SF6 alarm


DDB #041

Q0springcharged
L9
DDB #040
1
L11 L11 SF6 Block
DDB #042
Any Trip
DDB #522
1
Opto L5 & L16 can be found on other pages L1 L1 RESET
DDB #032

AR 3pole in prog
DDB #844

A/R Lockout
DDB #306

Page 1

IDiff>Start A
DDB #738 MiCOM P543 Programmable Logic
IDiff>>Start A Zone 1 N Start
DDB #1438 DDB #744
Zone 1 A Start Zone 2 N Start
DDB #741 Start Phase DDB #748
Zone 2 A Start
DDB #745 Mappings. Used in Zone 3 N Start
DDB #752
Zone 3 A Start Fault Record & on Zone P N Start
DDB #749 DDB #756
Zone P A Start
LCD Display Zone 4 N Start
DDB #753 DDB #760
Zone 4 A Start Zone Q N Start
DDB #757 DDB #1849

Zone Q A Start
1 Started Phase A
DDB #956
DDB #1846
IN>1 Start
I>1 Start A DDB #777
DDB #762
IN>2 Start
DDB #778
I>2 Start A
DDB #766 Caution: Do
Not remove IN>3 Start
I>3 Start A DDB #779
MiCOM P543 Programmable Logic MiCOM P543 Programmable Logic

Output Contacts
1 0
SG-opto Invalid
DDB #288
R1 Q0 close
R1 com Prot'n Disabled
Straight DDB #000 R1
DDB #289
0 Static Test Mode
& 50
R3Q0closecom pr
DDB #290
Test Loopback
SD Dwell DDB #002
R2
R3 DDB #291
Q 0 Test IM64
R DDB #292

1 150
R2 Q0 open 1
VT Fail Alarm
DDB #293
Dwell DDB #001
R3
R2
CT Fail Alarm
00 0 DDB #294
k-Up Remote CT Alarm
150 DDB #296
0 R5 Q0 open 2
Dwell DDB #004 R5 Power Swing
DDB #297
0 R5
CB Fail Alarm
DDB #298
200
R2 Q0 open2 pr CB Monitor Alarm
Dwell DDB #005 R6
DDB #299
0 R6 CB Lockout Alarm
DDB #300
200 CB Status Alarm
R4 Q0 open 1 pr DDB #301
Dwell DDB #003 R4

0 CB Trip Fail
DDB #302
R7
CB Close Fail
150 DDB #303

1 Dwell
0
R7 Trip to BBP
DDB #006 R7 Man CB Unhealthy
DDB #304
R8 No C/S Man Close
DDB #305
A/R Lockout
DDB #306
A/R CB Unhealthy
DDB #307
R9

1
A/R No Checksync
DDB #308
10000 Reserved
1 Pick-Up
0 R10
DDB #309
GPS Alarm
DDB #310
Signalling Fail
DDB #311

1 R11
Comm Delay Alarm
DDB #312
C Diff Failure
DDB #313
20000 IM64 SchemeFail
DDB #314
Pick-Up
R12 IEEE C37.94 Fail
0 DDB #315
Aid 1 Chan Fail
DDB #317
S
Q Aid 2 Chan Fail
DDB #318
R R13
F out of Range
DDB #319
Incompatible Rly
DDB #332
R14 InValid Mesg Fmt
DDB #333
Main Prot. Fail
DDB #334
Config Error
DDB #335
Re-Config Error
DDB #336
Comms Changed
DDB #337
Battery Fail
DDB #352
Trip Outputs
Field Volts Fail
are generated DDB #353

by the internal Max Prop. Alarm


DDB #338
single/three
phase trip
conversion Page 2
logic.

MiCOM P543 Programmable Logic MiCOM P543 Programmable Logic

Any Ground Start >> page7 >> page6 Any Ground Start

>> page6 Any Phase Start


Any Trip
DDB #522
I2>1 Start
DDB #567
I2>2 Start
DDB #568
I2>3 Start
DDB #569
I2>4 Start
DDB #570
V<1 Start
DDB #788
V<2 Start

1 Started Phase N
DDB #959
DDB #792
V>1 Start
MiCOM P543 Programmable Logic

Output Contacts
LEDs
Diff Trip
DDB #582
Diff InterTrip
DDB #586
1 Latching
LED1 Red
DDB #1024
LED1 Grn
DDB #1025
Zone 1 Trip
DDB #608
LED2 Red
DDB #1026
Zone 2 Trip Latching
DDB #613 LED2 Grn
DDB #1027

Zone 4 Trip LED3 Red


DDB #628 DDB #1028
Latching
Zone P Trip LED3 Grn
DDB #623 DDB #1029
I>2 Trip LED4 Red
DDB #659 DDB #1030
Latching
I>3 Trip LED4 Grn
DDB #663 DDB #1031
I>4 Trip LED5 Red
DDB #667 DDB #1032
Latching
LED5 Grn
DDB #1033

IN>1 Trip LED6 Red


DDB #671 DDB #1034
Latching
IN>2 Trip LED6 Grn
DDB #672 DDB #1035

IN>3 Trip LED7 Red


DDB #673 DDB #1036
Latching
LED7 Grn
DDB #1037

IN>4 Trip LED8 Red


DDB #674 DDB #1038
Latching
LED8 Grn
DDB #1039
R4
0
R14 Failpr trip FnKey LED2 Red
Dwell DDB #013 R14
DDB #1042
0 CBfail1 Trip 3ph Latching
DDB #834
1 FnKey LED2 Grn
DDB #1043
General Alarm CBfail2 Trip 3ph
DDB #835

FnKey LED3 Red


Non - DDB #1044
CB Fail Alarm
DDB #298 Latching FnKey LED3 Grn
DDB #1045

1
L11 L11 SF6 Block
DDB #042
drive unit fail FnKey LED4 Red
L12
DDB #043 Non - DDB #1046
L10 SF6 alarm Latching FnKey LED4 Grn
L10
DDB #041 DDB #1047

FnKey LED5 Red


L13 L13 Diff block Non - DDB #1048
DDB #044
Latching FnKey LED5 Grn
DDB #1049
L14 L14 dist block
DDB #045 FnKey LED6 Red
DDB #1050
Latching
FnKey LED6 Grn
DDB #1051

L3 EXT TRIP CBF FnKey LED7 Red


L3
DDB #034 Non - DDB #1052
Latching FnKey LED7 Grn
DDB #1053
L15 TC1
&
L15
DDB #046 FnKey LED8 Red
L7 Q0 close pos
Non - DDB #1054
L7
DDB #038 Latching FnKey LED8 Grn
DDB #1055

L16 L16 TC2


DDB #047 & FnKey LED9 Red
L7 L7 Q0 close pos
DDB #038
Non - DDB #1056
Page 3 Latching FnKey LED9 Grn
L11 SF6 Block DDB #1057
L11
DDB #042
L10 L10 SF6 alarm FnKey LED10 Red
DDB #041 Non - DDB #1058
Latching FnKey LED10 Grn
L2 L2 VTC FAIL DDB #1059
DDB #033

MiCOM P543 Programmable Logic


Diff Trip A
DDB #583
Diff InterTrip A
DDB #587
Zone 1 A Trip
DDB #609
Zone 2 A Trip
DDB #614
Zone 3 A Trip
DDB #619
Any Start Zone P A Trip
DDB #736 DDB #624
Zone 4 A Trip
DDB #629
Zone Q A Trip
DDB #1838
0
Trip 3ph Output R13
DDB #526
Dwell DDB #012 R13

Any Trip Fault REC TRIG


DDB #522 DDB #702

df/dt>1 Trip
DDB #601
df/dt>2 Trip
DDB #602
df/dt>3 Trip
DDB #603
df/dt>4 Trip
DDB #604
V<1 Trip
DDB #683
V<2 Trip
DDB #687
V>1 Trip
DDB #691
V>2 Trip
DDB #695
VN>1 Trip
DDB #700 1 CBFNonITrip
DDB #1893

VN>2 Trip
DDB #701
V1>1 Cmp Trip
DDB #925
V1>2 Cmp Trip
DDB #926
F<1 Trip
DDB #1161
F<2 Trip
DDB #1162
F<3 Trip
DDB #1163
F<4 Trip
DDB #1164
F>1 Trip
DDB #1165
F>2 Trip
DDB #1166

MiCOM P543 Programmable Logic


Page 4
Diff Trip C
DDB #585
Diff InterTrip C
DDB #589
Zone 1 C Trip
DDB #611
Zone 2 C Trip
DDB #616
Zone 3 C Trip
DDB #621
Zone P C Trip
DDB #626
Zone 4 C Trip
DDB #631
Zone Q C Trip
DDB #1840
Aided 1 Trip C
DDB #635
Aid 1 WI Trip C
DDB #639
1 Faulted Phase C
DDB #954

Aided 2 Trip C
DDB #770 "Started Phase"
DDB signals IN>4 Start
DDB #780
I>4 Start A
DDB #774
ISEF>1 Start
IDiff>Start B DDB #781
DDB #739
IDiff>>Start B ISEF>2 Start
DDB #1439 DDB #782
Zone 1 B Start Any Phase Start >> page6
1
DDB #742 ISEF>3 Start
Zone 2 B Start DDB #783
DDB #746
Zone 3 B Start ISEF>4 Start
DDB #750 DDB #784
Zone P B Start
DDB #754
Zone 4 B Start Phase Select N
DDB #758 DDB #1013

Zone Q B Start
1 Started Phase B
DDB #957
Any Trip
DDB #1847 DDB #522

I>1 Start B
DDB #763 >> page5 Any Phase Start
I>2 Start B
DDB #767

I>3 Start B
DDB #771 Phase Select N
DDB #1013
I>4 Start B 10
DDB #775 Any Trip
DDB #522 Pu
IDiff>Start C
DDB #740
IDiff>>Start C This logic ensures correct
DDB #1440
Zone 1 C Start N indications for faults
DDB #743
involving ground. The pulse
Zone 2 C Start
DDB #747 prevents pole scatter
Zone 3 C Start
DDB #751 affecting the N indication.
Zone P C Start
DDB #755
Zone 4 C Start
DDB #759
Zone Q C Start
DDB #1848 1 Started Phase C
DDB #958

I>1 Start C
DDB #764
L1 L1 RESET
L5 DDB #032
I>2 Start C
DDB #768

I>3 Start C This logic c


DDB #772
indications at t
I>4 Start C
Page 5
DDB #776

MiCOM P543 Programmable Logic Inputs to Trip


Diff Trip A Conversion
DDB #583
Logic:These Raw trip
Diff InterTrip A signals are then
DDB #587
processed in relay fixed
Zone 1 A Trip
DDB #609
logic, to obtain the AR Trip Test
DDB #576
correct single, or three Perm InterTrip
Aided 1 Trip A
DDB #633
pole trip response. DDB #590
Broken Wire Trip

Aid 1 WI Trip A
1 Trip Inputs A
DDB #530
DDB #679
Thermal Trip
DDB #637 CBF Int Init A DDB #680

Aided 2 Trip A
1 DDB #1950 I2>1 Trip
DDB #571
DDB #643 I2>2 Trip
DDB #572
Aid 2 WI Trip A I2>3 Trip
DDB #647 Caution: Do DDB #573
Not remove I2>4 Trip
DDB #574
AR Trip Test A
DDB #577 "Trip Inputs" ISEF>1 Trip
DDB #675
DDB signals ISEF>2 Trip
Diff Trip B DDB #676
DDB #584 ISEF>3 Trip
DDB #677
Diff InterTrip B ISEF>4 Trip
DDB #588 DDB #678
V<1 Trip
Zone 1 B Trip DDB #683
DDB #610 V<2 Trip
DDB #687
Aided 1 Trip B V>1 Trip
DDB #634 DDB #691

Aid 1 WI Trip B
1 Trip Inputs B
DDB #531 V>2 Trip
DDB #695
DDB #638 CBF Int Init B VN>1 Trip

Aided 2 Trip B
1 DDB #1951 DDB #700
VN>2 Trip
DDB #644 DDB #701
F<1 Trip
Aid 2 WI Trip B DDB #1161
DDB #648 F<2 Trip
DDB #1162
AR Trip Test B F<3 Trip
DDB #578 DDB #1163
DDB #796
V>2 Start
DDB #800
VN>1 Start
DDB #804
VN>2 Start
1
DDB #805
F<1 Start
DDB #1155
F<2 Start
DDB #1156
F<3 Start
DDB #1157
F<4 Start
DDB #1158
F>1 Start
DDB #1159
& F>2 Start
DDB #1160
V1>1 Cmp Start
DDB #923
V1>2 Cmp Start
DDB #924

Any Phase Start >> page7 df/dt>1 Start


DDB #597
df/dt>2 Start
DDB #598
df/dt>3 Start
DDB #599
df/dt>4 Start
DDB #600
&
ulse
0

N Phase Start >> page 7 then page 8 then page 9

& 1 Reset Relays/LED


This reset
DDB #444

controls:
Reset latched
relays, Reset
latched LEDs,
Reset A/R
Lockout. >> page 6 N Phase Start
clears all latched
the start of Any Trip
Page 6

MiCOM P543 Programmable Logic MiCOM P543 Programmable Logic


page 11 >> Trip Inputs 3Ph
Pred. OST
DDB #551
OST
DDB #553
Stub Bus Trip
DDB #591
Zone 2 Trip
DDB #613
Zone 3 Trip
DDB #618
Zone P Trip
DDB #623
Zone 4 Trip
DDB #628
Zone Q Trip
DDB #1837
I>1 Trip
DDB #655
I>2 Trip
DDB #659
I>3 Trip
DDB #663
I>4 Trip
DDB #667
IN>1 Trip
DDB #671
IN>2 Trip
Trip Inputs 3Ph >> page 12 DDB #672
IN>3 Trip
1 DDB #673
IN>4 Trip
DDB #674
Caution: Do Aid1 DEF Trip3Ph
Not remove DDB #641

"Trip Inputs"
Aid1 WI Trip 3Ph
DDB #642 1
DDB signals Aid1 Delta Tr3Ph
DDB #640
Aid2 DEF Trip3Ph
DDB #651
Aid2 WI Trip 3Ph
DDB #652
Aid2 Delta Tr3Ph
DDB #650
Loss ofLoad Trip
DDB #654
Aided 1 Trip A
DDB #633
Aid 1 WI Trip A
DDB #637
1 Faulted Phase A
DDB #952

Used in Fault Aided 2 Trip A


DDB #643
Record Aid 2 WI Trip A
initiation DDB #647

Caution: Do Not I>1 Trip A


DDB #656
remove "Any I>2 Trip A
DDB #660
Start" DDB I>3 Trip A
DDB #664
signal
I>4 Trip A
DDB #668
AR Trip Test A
DDB #577
AR Trip Test
DDB #576
Diff Trip B Faulted Phase Flag,
DDB #584
Used in Fault
Diff InterTrip B
DDB #588 record and on LCD
Zone 1 B Trip
DDB #610 display.
Zone 2 B Trip Caution: Do Not
DDB #615
Zone 3 B Trip
remove "Faulted
DDB #620 Phase" DDB
Zone P B Trip
DDB #625 signals
Zone 4 B Trip
DDB #630
Zone Q B Trip
DDB #1839
Aided 1 Trip B

1
DDB #634 Faulted Phase B
Aid 1 WI Trip B DDB #953
DDB #638
Aided 2 Trip B
DDB #644
Aid 2 WI Trip B
DDB #648
I>1 Trip B
DDB #657
I>2 Trip B
DDB #661
I>3 Trip B
DDB #665
I>4 Trip B
DDB #669
AR Trip Test B
DDB #578
AR Trip Test
DDB #576

N Phase Start >>page 8 then page >>


9 page 6 then page 7 N Phase Start N Phase Start >> page 9

Page 7 Page 8

This logic
c MiCOM P543 Programmable Logic enables Check
Synchro to
function only
for Live Line
/ Live Bus
conditions.
CS1 Enabled
DDB #881

Live Bus
DDB #886
& CS2 Enabled
DDB #882

Dead Line
DDB #889
&
Dead Bus
DDB #887
&
Live Line
DDB #888
1 Ctl Check Sync
Safety
DDB #898
Interlock.
Check Sync 1 OK
DDB #883 Logic must be
satisfied before
Check Sync 2 OK
DDB #884 any manual CB
closures can
proceed.
1 Trip Inputs 3Ph SysChks Inactive
DDB #529 DDB #880

AR Force 3 pole
DDB #858
Caution: Do
Not remove
Aid 1 Chan Fail
1 Force 3Pole Trip
DDB #533

"Trip Inputs" DDB #317

DDB signals Aid 2 Chan Fail


DDB #318
DDB #645
Aid 2 WI Trip C
DDB #649
I>1 Trip C
DDB #658
I>2 Trip C
DDB #662
I>3 Trip C
DDB #666
I>4 Trip C
DDB #670
AR Trip Test C
DDB #579 Faulted Phase
AR Trip Test Flag, Used in Fault
DDB #576
record and on LCD
display.
Caution: Do Not
Zone 1 N Trip
DDB #612 remove "Faulted
Zone 2 N Trip
DDB #617 Phase" DDB
Zone 3 N Trip signals
DDB #622
Zone P N Trip
DDB #627
Zone 4 N Trip
DDB #632
Zone Q N Trip
DDB #1841
Aided 1 Trip N
DDB #636
Aided 2 Trip N
DDB #646
IN>1 Trip
DDB #671
IN>2 Trip
DDB #672
IN>3 Trip
1 Faulted Phase N
DDB #955
DDB #673
IN>4 Trip
DDB #674
VN>1 Trip
DDB #700
VN>2 Trip
DDB #701
ISEF>1 Trip
DDB #675
ISEF>2 Trip
DDB #676
ISEF>3 Trip
DDB #677
ISEF>4 Trip
DDB #678

>> page 6 then page 7 the page 8 N Phase Start

Page 9
F<4 Trip
DDB #1164
F>1 Trip
DDB #1165
Diff Trip C F>2 Trip
DDB #585 DDB #1166
V1>1 Cmp Trip
Diff InterTrip C DDB #925
DDB #589 V1>2 Cmp Trip
DDB #926
Zone 1 C Trip df/dt>1 Trip
DDB #611 DDB #601
df/dt>2 Trip
Aided 1 Trip C DDB #602
DDB #635
1 Trip Inputs C df/dt>3 Trip
DDB #532 DDB #603
Aid 1 WI Trip C df/dt>4 Trip
DDB #639 CBF Int Init C DDB #604

Aided 2 Trip C
1 DDB #1952 IREF> Trip
DDB #682
DDB #645

Aid 2 WI Trip C
DDB #649
Caution: Do
AR Trip Test C
DDB #579 Not remove
"CBF Int Init"
Trip 3ph
DDB signals
DDB #526

Page 10
Pole Discrepancy
DDB #699
TOR Trip Zone 1
DDB #704
TOR Trip Zone 2
DDB #705
TOR Trip Zone 3
DDB #706
TOR Trip Zone P
DDB #708
TOR Trip Zone 4
DDB #707
TOR Trip Zone Q
DDB #1842
TOR Trip CNV
DDB #557
SOTF Trip CNV
DDB #558
SOTF Trip Zone 1
DDB #709
SOTF Trip Zone 2
DDB #710
SOTF Trip Zone 3
DDB #711
SOTF Trip Zone P
DDB #713
SOTF Trip Zone 4
DDB #712
SOTF Trip Zone Q
DDB #1843
Zone 1 Trip
DDB #608

Page 11
Signalling Fail
DDB #311

L4 L4 BLOCK AR
1 Block CB AR
DDB #448
DDB #035

FK1 AR BLOCK
DDB #1096
1 Non -
FnKey LED1 Red
DDB #1040
Latching FnKey LED1 Grn
Default PSL DDB #1041
CB Succ 3P AR
blocks autoreclose DDB #852
if any aided Power Swing
DDB #297
Inhibit WI
DDB #458
scheme channel
fails.

Page 12 Page 13