IO-GRID M Modbus RTU Connection Operating Manual (FATEK-PLC) en
IO-GRID M Modbus RTU Connection Operating Manual (FATEK-PLC) en
V2.0.0
2
1. Remote I/O Module System Configuration List
Part No. Specification Description
3
2. FATEK PLC Connection Setup
This chapter explains how to use the WinProladder program to connect FATEK PLC with
For detailed information, please refer to the Winproladder Manual
※All FATEK's RS485 communication modules have the following pins on the terminal blocks
(from top to bottom):
First pin: “+”
Second pin: “-”
Third pin: “Ground”
4
II. Connect Port2 (RS485 A/B) on the top of the machine to the interface module (1/2) to
convert it into a RJ45 connector, which will be connected to the main controller
5
2.2 FATEK PLC Connection Setup
I. Launch WinProladder and set up the communication ports
※This demonstration utilizes communication module CB55 RS485 with Port2 in its address
※The communication parameter setting must be consistent with to enable communication
6
II. Editing the program- Click on “Set up program block diagram”, then from the drop-
down menu, select “Communication Commands” and then select “M-BUS”
7
IV. Internal Related Relays
※The form’s starting address must be the same with that of the register from the SR command
8
VI. Setting the Communication Commands
Ⓐ station number
Ⓑ From the drop-down menu, select “Read” or “Write” to PLC
Ⓒ With double word data, select “2” for data length
Ⓓ Read ’s value to PLC R1’s address
※ ’s register address
Note:
※ ’s first GFDI-RM01N has the register address at 1000(HEX) converted to
4096(DEC)+1, and the starting address at 404097
※ ’s first GFDO-RM01N has the register address at 2000(HEX) converted to
8192(DEC)+1, and the starting address at 408193